        APC VT Power Supply User Manual
         Contents
1.                                                          O  Press     Chrg 100      gt  Control Logging   Load 000  Status Display   xxxVin 000Vout x0Hz Setup Diags   Runtime  Ohr Om Help  e o  pin    Turn Load Off Press pa Confirm  Press       f Y Turn Load OFF   NO  Abort          gt  YES  Turn Load OFF                   If the UPS is running in parallel operation  this procedure must be carried out on each  UPS     Turn load ON     How to connect the UPS output to the load equipment                                                     Press Use ETUDES TR Press  Chrq 100  ontro ogging  Load 000     Status Display  xxxVin OOOVout x0Hz Setup Diags  Runtime  Ohr Om    Help  Use Press Use   Press  Confirm      gt  Turn Load On         f Y Turn Load OFF    NO  Abort           gt  YES  Turn Load ON                               If the UPS is running in parallel operation  this procedure must be carried out on each  UPS     12 Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 990 2282A 001    Operation     Operation Procedures    How to view the Status screens    o                               Press Use Seal E   Press  Chrg 100  ontro ogging  Load 000          Status Display  xxxVin 000Vout x0Hz Setup Diags  Runtime  Ohr Om    Help             Use the UP DOWN keys to go through the parameters        View    Parameters       Voltage on all    Utility mains voltage  V   bypass voltage  V   and output voltage  V  for each phase              phases   Current on all Utility mains
2.          Check that the UPS is in bypass  The green Q Remove the Front Panel from the UPS  see   LOAD ON  and the yellow  BYPASS  LEDs the Receiving and Unpacking sheet referred  are lit  to under the section Companion manuals      990 2282A 001 Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 7    Operation     Operation Procedures    Single System   turning into external bypass     A    Warning    e    Use        g                                             Turn the internal mechanical bypass    lever upwards to activate it  The load    will now be supported directly by    utility mains power        Reinstall the Front Panel     In bypass operation the batteries are still powered  If a total power off is required the batteries  must be pulled out to the red disconnect line  see the section How to perform a total power off           Chrg 100    Load 000    xxxVin 000Vout x0Hz  Runtime  Ohr Om                         UPS into Bypass  Do Self Test  Simulate Power Fail  Start Runtime Cal                Press    Press    Q From the external MBP  Turn the bypass    switch  Q003  to position    1     ON        If the UPS has to be completely isolated     removed  see the section How to perform a    total power off     Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation    e    Use    M  g    o    Use         g                                gt  Control Logging  Status Display  Setup Diags  Help  Confirm   UPS into Bypass  NO  ABORT     gt  YES  UPS into Bypass         
3.      From the XR Enclosure s   if available   Set    From the external MBP  Turn all input    the DC disconnect switch  if available  to the switches  Q001  to position    1     ON    ON position       From the external MBP  Turn all output    From the external MBP  Turn the output  switches  Q002  to position    1     ON   isolation breaker  Q004  to position    1     ON        From the UPS  Turn load ON each of the UPS Check that the load is ON   units from the display via Control     Turn  Load on  Yes  turn Load on     The UPS system is now ready to support the load     Note    Auto detection on frequency     if a problem occurs call APC Customer Support  see the  back cover of this manual      Note    990 2282A 001 Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 21    Configuration    Settings       How to change the Clock and the Alarms in the Setting menu    Alarms Runtime    Par   Redundancy    Chrg xxx   Load xxx   xxxxVin  Runtime    Status  Diags  Setup Help  Logging       Clock  The Clock menu changes the date and the clock settings and it time stamps events in the  event log  To avoid inaccuracies  change the clock setting at daylight saving time                 o e  Press Use  Chrg 100  Control Logging  Load 000    S Status Display  xxxVin 000Vout x0Hz    gt  Setup Diags  Runtime  Ohr Om g Help                                              pui Setti Pross Dat 24 S 2006 dien   ettings     Date   Sep         Shutdown Alarms Time  13 45 51  Default  gt  Cloc
4.     Install the Battery Module in the lowest   Position the Battery Unit to slide in between  available bay  four across in 523 mm  20 in  the grooves and push completely into the  UPS versions  two across in 352 mm  14 in  UPS to ensure connection     UPS versions      If a problem is reported  ensure that the modules in question are correctly installed  If the  problem persists  see the section Troubleshooting     Note    Allow for a 24 hour recharging period of the batteries after system start up     Note    32 Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 990 2282A 001    Troubleshooting    Status and Alarm Messages       This section lists the status and alarm messages that the UPS might display  The messages are listed in    alphabetical order  and a suggested corrective action is listed with each alarm message to help you    troubleshoot problems     Display messages       Display Message    Meaning    Corrective Action       Automatic Self Test  Started     The UPS has started pre programmed  battery test     No corrective action is necessary        ABus Communication  Fault     Communication fault detected on the  ABus     Check ABus wiring  If this does not  help contact APC        ABus Termination Fault     ABus termination is missing     Check if termination is present  If this  does not help contact APC        Batt Temperature  Exceeded Upper Limit     The temperature of one or more bat   tery units has exceeded the system  specifications     Contact AP
5.     Press    Press       From the external MBP  Turn the output    switch  Q002  to position    0     OFF      990 2282A 001    990 2282A 001    Parallel System   turning into external bypass     A    Warning    o       Press       Chrq 100    Load 000    xxxVin 000Vout x0Hz  Runtime  Ohr Om                e    Use       UPS into Bypass       Do Self Test    Simulate Power Fail     Start Runtime Cal          Press                Q From the UPS  Check that all UPS units are in  bypass on each of the displays       From the external MBP  Turn the bypass  switch  Q003  to position    1     ON      Q From the external MBP  Turn the output  isolation breaker  Q004  to position    0     OFF       D From the external MBP  Check that all output  lamps are lit  Q002       B From the external MBP  Turn all input  switches  Q001  to position    0     OFF       D From the UPS  Disconnect the batteries by    pulling them out to the red disconnect line       For a total UPS shut down see the section How    to perform a total power off     Operation     Operation Procedures    In bypass operation the batteries are still charged  If a total power off is required  the batteries  must be pulled out to the red disconnect line  see the section How to perform a total power off                             Use CEDERE     Press  ontro ogging   f Y Status Display  Setup Diags      Help   Use ETT Press  onfirm       UPS into Bypass  NO  ABORT       gt  YES  UPS into Bypass                Q From the ex
6.    How to use the Diags screen    The Diags  View troubleshooting information     o             Chrq 100    Load 000    xxxVin OOOVout x0Hz  Runtime  Ohr Om                    M  g           gt  Fault  amp  Diagnostics  System Information  Switch status  Raw Status Dump             Note    990 2282A 001    Diags Screen    For more details on the Fault and Diagnostics screens  see the section Troubleshooting     Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation    Press    Press    Use    g    Operation     Operation Procedures          Control  Status  Setup    Logging   Display     Diags   Help                Press    15    Operation     Operation Procedures    How to perform a total power off    Total power off     single system without MBP                                                                                                                 miim  CT   ESL ERN  CIT  isis    I          l     n  n          i        rf     T Tey T               Un     Im        XR Enclosure    Q Check that the load is OFF        From the XR Enclosure s   if available   Set  the DC disconnect switch to the OFF position        From the XR Enclosure s   if available    Disconnect the batteries by pulling them out to  the red disconnect line shown on each battery    unit     WARNING                  Q From the UPS  Turn OFF the UPS from the  display via Control  Turn Load Off  Yes   Turn Load Off    Q From the UPS  Disconnect the batteries by   pulling them out to the red disconnect
7.    Only trained personnel familiar with the construction and the equipment may    A restart the UPS     Warning      Set the utility mains breaker to the ON position        If your installation includes an XR Battery Enclosure  SUVTBXR2B6S SUVTBXR6B6S  with a  DC disconnect switch  set the DC disconnect switch to the ON position     Q  Wait approximately 30 seconds for the system to boot up and carry out a self test   Note    After system boot up  the display will automatically ask you to confirm select voltage and frequency as  shown in the following     Voltage confirmation  At restart  the display will prompt you through the following screens     o e    Use Press Use    Confirm Voltage Apply load         gt  Yes       Use 400V  VILE                Press     gt  Yes  use 400V  v No  select another                            990 2282A 001    When the Confirm Voltage prompt appears on  the screen  go to the desired voltage using the UP   DOWN keys and press ENTER           Chrg xxx              Load xxx              xxx Vin xxxVout xxHz  Run time  xxhr xxmin                The green  LOAD ON  LED is now lit  Press ESC  two times and the display will show the above  Overview Screen     Q  The UPS is now ready to support the load     Note    When the prompt Apply load appears  go to Yes  using the UP DOWN keys and press ENTER if you  want the UPS to provide a load output now   If  you do not want UPS load output at this point  go  to No      Smart UPS   VT 10 40 kVA 400V  208V 
8.  200V     Operation 19    Operation     Operation Procedures    Auto detection on frequency     if a problem occurs call APC Customer Support  see the  back cover of this manual      Note    Restart     single system with MBP        Only trained personnel familiar with the construction and the equipment may    restart the UPS   Warning    From the XR Enclosure s   if available   Q From the UPS  Connect the batteries by  Connect the batteries by pushing them in  pushing them in        From the XR Enclosure s   if available   Set    From the external MBP  Turn the input switch    the DC disconnect switch  if available  to the  Q001  to position    1     ON    ON position      From the external MBP  Turn the output    From the UPS  Turn load ON from the display  switch  Q002  to position  I   ON   via Control     Turn Load on   Yes  turn  Load on       Check that the load is ON     Q  The UPS is now ready to support the load     Note    Auto detection on frequency     if a problem occurs call APC Customer Support  see the  back cover of this manual    Note    20 Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 990 2282A 001    Operation     Operation Procedures    Restart     parallel system        Only trained personnel familiar with the construction and the equipment may  restart the UPS system     Warning    From the XR Enclosure s   if available   Q From the UPS  Connect the batteries by  Connect the batteries on the UPS units by pushing them in     pushing them in   
9.  current  A   bypass current  A   and output current  A  for each phase    phases   kVA and kW Apparent power  kVA  and real power  kW  generated by the UPS and the connected  load    Frequencies Utility mains frequency  bypass frequency  and output frequency in Hertz  Hz         Load and batteries    Load  Percentage of the load in relation to the total UPS capacity                 Bat Voltage Shows either the positive or negative half of the battery voltage  the lower value of the  two will appear     Bat Cap Percentage charge on the batteries in relation to the total battery capacity   Runtime  The predicted runtime at the present load    Batteries Bat AmpHr  Battery capacity  including both external and internal batteries   UPS Temp  The highest external battery temperature    Alarm thresholds Load  An alarm will be set when the load is above the threshold level     Runtime  An alarm will be set when the runtime is below the threshold level        Parallel Status    Local UPS is slave master     of UPSs OK  Indicates the number of parallel UPS units that is OK     of UPSs fail  Indicates the number of parallel UPS that has failed        Par load Status    KVA and KW  Total apparent power  KVA  and real power  KW  generated by the  parallel UPS units and the connected load    Par redundancy  n 1  an alarm will be set if the redundancy level is below the threshold  level        Parallel Operation  Mode          The parallel operation mode can be off  load on  requested bypa
10.  if available  on the  isolate to position    0     OFF   XR Enclosure to the OFF position     Q From the UPS  Disconnect the batteries in the   From the XR Enclosure s   if available    UPS which you want to isolate by pulling them Disconnect the batteries by pulling them out to  out to the red disconnect line  the red disconnect line     Parallel system     turning the isolated UPS into normal operation     Q From the external MBP  Turn the input switch   From the UPS  Connect the batteries by   Q1  connected to the UPS you want to turn pulling them in     into normal operation to position    1     ON         From the XR Enclosure s   if available      From the XR Enclosure s   if available   Set  Connect the batteries by pulling them in  the DC disconnect switch  if available  on the    XR Enclosure to position ON     Q From the external MBP  Turn the output    From the UPS  Turn load ON from the display  switch  Q002  connected to the UPS you want on the UPS you want to turn into normal  to turn into normal operation to position  T  operation via Control Turn Load on Yes    ON   turn Load on       From the UPS  Press Esc two times to get back G From the UPS  On the Overview Screen  check  to the Overview Screen  that the load percentage of the UPS units is    approximately the same     18 Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 990 2282A 001    Operation     Operation Procedures    How to perform a restart    Restart     single system wihout external MBP  
11.  line    shown on each battery unit     Set the utility mains breaker to the OFF or  LOCKED OUT position  If the UPS has dual  utility mains supply  set both supplies to the  OFF or LOCKED OUT position     The lockout procedures at utility mains breaker must be followed  If necessary  install a    Warning padlock     16 Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation    990 2282A 001    Operation     Operation Procedures    For details on how to remove Battery Locks  if available  see the section How to remove  and install battery locks  if available         Total power off     single system with MBP     Q Check that the load is OFF  Q From the UPS  Turn load OFF the UPS from  the display via Control Turn Load off   Yes   turn Load off       From the external MBP  Turn the output Q From the external MBP  Turn the input switch   switch  Q002  to position    0     OFF    Q001  to position    0     OFF         From the XR Enclosure s   if available   Set    From the UPS  Disconnect the batteries in the  the DC disconnect switch  if available  on the UPS by pulling them out to the red disconnect  XR Enclosure s  to the OFF position  line       From the XR Enclosure s   if available    Disconnect the batteries by pulling them out to    the red disconnect line     Total power off     parallel system     Q Check that the load is OFF  Q From the UPS  Turn load OFF each of the UPS  units from the display via Control  Turn  Load off Yes  turn Load off        From the external M
12.  pull out the card      one on each side of the card         Install the new card     Reattach the 2 Torx screws     How to replace and install a battery module    General safety prior to battery module replacement     When replacing Battery Modules  replace with the same numbers of the  SYBT4     Note    Servicing of batteries should be performed or supervised by personnel knowledgeable of  A  batteries and the required precautions  Keep unauthorized personnel away from batteries     Caution DPO not dispose of battery or batteries in a fire  The battery may explode     Do not open or multilate the battery or batteries  Released electrolyte is harmful to the  skin and eyes  It may be toxic     A battery can present a risk of electrical shock and high short circuit current  The  following precautions should be observed when working on batteries       Remove watches  rings  or other metal objects      Use tools with insulated handles      Wear rubber gloves and boots      Do not lay tools or metal parts on top of batteries       Disconnect charging source prior to connecting or disconnecting battery terminals     e Use two people to lift components weighing between 18     32 kg   40     70 Ib     28 Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 990 2282A 001    Maintenance     Parts Replacement    Battery module  One Battery Module consists of four Battery Units  shipping in the Enclosures         4 x 24 kg   4 x 53 Ibs    How to remove a battery compartment cover   o
13. BP  Turn the output Q From the external MBP  Turn all output  isolation breaker  Q004  to position    0     OFF   switches  Q002  to position    0     OFF    Q From the external MBP  Turn all input    From the XR Enclosure s   if available   Set  switches  Q001  to position    0     OFF   the DC disconnect switch  1f available  to the  OFF position       From the UPS  Disconnect the batteries in the   From the XR Enclosure s   if available    UPS units by pulling them out to the red Disconnect the batteries on the UPS units by    disconnect line  pulling them out to the red disconnect line     990 2282A 001 Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 17    Operation     Operation Procedures    Total power off     isolating one UPS in a parallel system       From the UPS  From the Main Menu screen Q From the UPS  Turn load OFF from the display  select Status and scroll down to Status of on the UPS to be isolated via Control  Turn  actual redundancy  n  in order to check that Load off   Yes  turn Load off   the remaining UPS s  will be able to carry the    load when one UPS is isolated        From the external MBP  Check that the output   From the external MBP  Turn the output  lamp  Q002  of the UPS to be isolated is lit  switch  Q002  connected to the UPS you want  to isolate to position    0     OFF         From the external MBP  Turn the input switch   From the XR Enclosure s   if available   Set   Q001  connected to the UPS you want to the DC disconnect switch 
14. C Customer Support   see back cover         Battery over voltage  warning     The battery voltage is too high and  the charger has been deactivated     Contact APC Customer Support   see back cover         Bypass Not Available    The frequency or voltage is out of    Correct the input voltage to provide       the battery charge is low   Note  Runtime is limited in duration     Input Freq Volt Out Of acceptable range for bypass  This an acceptable voltage or frequency   Range  message occurs when the UPS is   online  and indicates that the bypass   mode may not be available if   required   Discharged Battery  The UPS is in battery operation and No corrective action is necessary     Shut down the system and the load  equipment or restore incoming  voltage        Emergency PSU Fault     The redundant Emergency Power  Supply Unit  PSU  is not working   The UPS will continue to work nor   mally  but the PSU should be  replaced     Contact APC Customer Support   see back cover            EPO Activated  The Emergency Power Off switch has   Deactivate the Emergency Power Off  been activated  switch   Fan fault  A fan has failed  Contact APC Customer Support  see    back cover         Int  Mech  Bypass  Switch Closed           The internal mechanical switchgear is  closed        No corrective action necessary  The  UPS is in internal mechanical bypass  operation           990 2282A 001    Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation    33    Troubleshooting     Status and A
15. On ee s E A IET ee 22    How to change the Clock and the Alarms in the Setting menu   22    How to change the Beeper setup  the Contrast  and the  Language in the Display menu              ellen 23    990 2282A 001 Smart UPS   VT 10 40 kVA  400 V  208 V  200 V     Operation i    Matta    Parts Replacement 0  ede eee ee eae ee ews 25  How to determine if you need a replacement part           25  How to return parts to APC           0002 cee ee eee 25  How to store the battery modules                      26  How to replace a Network Management Card              28  How to replace and install a battery module               28    Troubleshoollfg oo eor te a teet ene    Status and Alarm Messages                    seeees esses  33    Display messages        2 0   nn 33    ii Smart UPS   VT 10 40 kVA  400 V  208 V  200 V     Operation 990 2282A 001    All safety instructions in the Safety Sheet  990 2822  shall be read  understood   and followed prior to handling using the system  Failure to do so could result in  Warning equipment damage  serious injury  or death     For safety reasons  the trained user is only allowed to operate the display and replace the following  components       Network Management Card with temperature sensor  training necessary       Battery Module  training necessary     990 2282A 001 Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 1    Overview    User Interface       Interface area    The four LEDs to the left of the display indicate the operati
16. ates the UPS and allows maintenance to be performed  An external MBP is mandatory if the UPS is  running in parallel     Optional parallel operation    The connected load is powered by multiple UPS units to increase system redundancy or to increase  power  The internal mechanical bypass lever is not available     6 Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 990 2282A 001    Operation Procedures       How to turn into bypass    Single System   turning into internal bypass      gt     Cauti    s  3  3  Q    The load is not protected by the UPS and the power is not conditioned when the internal  mechanical bypass lever is activated   on    In bypass operation the batteries are still charged  If a total power off is required  the batteries  must be pulled out to the red disconnect line  see the section How to perform a total power off     This procedure is not applicable to parallel systems as the internal mechanical bypass lever is  unavailable     Note          If the UPS is running and controllable through the display  carry out steps 1 through 5  If not   go directly to step 6                                                     Note  Press Use Press  Chrg 100   gt  Control Logging  Load 000  Co f Y Status Display Co  xxxVin 000Vout x0Hz Setup Diags  Runtime  Ohr Om    Help  Use Pr     UPS into Bypass Press ve Confirm  oe  f Y Do Self Test   S UPS into Bypass GO  Simulate Power Fail NO  ABORT  g Start Runtime Cal F  gt  YES  UPS into Bypass    e                   
17. bution  on the 3 phases via the display  If the  load is unevenly distributed  adjust  the load distribution        Weak Batt s  Detected   Reduced Runtime     One or more weak batteries detected     Replace the weak batteries           XR Battery Fuse Blown        XR Battery Fuse blown  Runtime is  lower than expected        Replace the blown fuse in XR Enclo   sure  only applicable if your installa   tion includes an XR   Enclosure         Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation       990 2282A 001    APC       www apc com    APC Worldwide Customer Support    Customer support for this or any other APC product is available at no charge in any of the following ways       Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer  support requests         www apc com  Corporate Headquarters   Connect to localized APC Web sites for specific countries  each of which provides customer support  information         www apc com support   Global support searching APC Knowledge Base and using e support       Contact an APC Customer Support center by telephone or e mail         Regional centers    Direct InfraStruXure  1  877 537 0607  Customer Support Line  toll free     APC headquarters U S    1  800 800 4272    Canada  toll free    Latin America eom  Europe  Middle East   353  91 702000  Africa  Ireland    Japan  0  35434 2021  Australia  New Zealand   61   2  9955 9366  South Pacific area  Australia         Local  country specific ce
18. gh the menu screens and make your changes with the UPIDOWN and the ENTER keys  as described for the Clock and the Alarms in the Settings menu     990 2282A 001 Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 23    Configuration     Settings    The Beeper setup  In the Beeper setup you can choose between the following options     Never  If you select this setting  the Beeper will be active at internal UPS errors only     PwrFail 30  If you select this setting  the Beeper will be active at internal UPS errors and at utility   mains or bypass errors  The Beeper will only sound if the fault has been present for more than 30  seconds     PwrFail  If you select this setting  the Beeper will be active at internal UPS errors and at utility   mains or bypass errors  The Beeper will sound immediately when the error is occurring     LOW BATT  If you select this setting  the Beeper will be active at internal UPS errors at utility   mains or bypass errors  at power failures  and at a low battery level  if the UPS runs in battery  operation      24 Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 990 2282A 001    Maintenance    Parts Replacement       A Read Safety Sheet 990 2822 prior to replacing parts  available in the    Documentation Storage Area    Warning    How to determine if you need a replacement part    To determine if you need a replacement part  contact APC Customer Support and follow the procedure  below so that the APC Customer Support representative can assi
19. gh the sub menu screens  Control  Status  Setup  Logging  Display  Diags  and Help  see  the section Menu tree      990 2282A 001    The selector arrow is controlled  by the UP DOWN keys  The arrow  marks the item you may open by  pressing ENTER       Y  g    Main Menu Screen             Control  Status  Setup    Logging  Display  Diags  Help             Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 3    Overview     User Interface    Menu tree    The menu tree provides a quick overview of the functions and views you can access     Overview  Screen    Chrg xxx   Load xxx   xxxVin  Runtime    Control Display  Status     Diags  Setup Help  Logging    Main Menu  Screen       Control   Turn load  off on    UPS into out  of bypass    Status  Vin Vbyp Vout         Frequencies    oad  amp  Bat     Temp    Batteries    Alarm  thresholds    Parallel status       Load    Par   redundancy    System      pem    View log  Logging  Logging  View statistics  Beeper setup  Display  Display setup    Contrast Faults and  Diagnostics  Information Byp SW    Q3 External   Byp SW  Raw Status Status from  Data MBP    Help   on any screen   amp  any line  press     for context  sensitive help       Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 990 2282A 001    A    Caution    990 2282A 001    Overview     User Interface    The display provides access to more functions than described in this manual  Those functions  should not be accessed without the assistance of APC Customer Sup
20. have the original shipping materials  ask the representative about obtaining a new set   Pack the module properly to avoid damage in transit  Never use styrofoam beads or other loose packaging  materials when shipping a module  The module may settle in transit and become damaged  Enclose a  letter in the package with your name  RMA number  address  a copy of the sales receipt  description of  the problem  a phone number  and a check as payment  if necessary      Q  Damages sustained in transit are not covered under warranty     Note    990 2282A 001 Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 25    Maintenance     Parts Replacement    How to store the battery modules    26    The battery modules must be stored indoors and with their protective packaging still in place     A e  Ambient temperature  Relative Humidity  Storage place free from vibration    15   to 40 C 5 F to 104  F 25 85  Non condensing dust  direct sunlight  and moisture                          Stored batteries should be recharged at regular intervals depending on the storage temperature                    Storage Temperature Recharge interval   15   to 20 C 5 F to 68  F 9 months   20   to 30  C 68  F to 86  F 6 months   30   to 40  C 86  F to 104  F 3 months             Caution  Do not store the batteries for more than 12 months     Replaceable parts  only trained personnel         Part APC Part No   Battery Module SYBT4  Network Management Card with temperature sensor AP9619       ensure optimal 
21. he  load was reduced  or the threshold  was decreased     No corrective action is necessary        No Batteries Are  Connected     No battery power is available     Check that the batteries are inserted  properly        No Master is Present in  the Parallel System     No parallel master is present  The  parallel system will not be able to  function properly     Contact APC        Number of Battery  Modules Decreased     One or more battery modules were  removed     No corrective action is necessary        Number of Battery  Modules Increased     One or more battery modules were  added     No corrective action is necessary        Overload on a Parallel  Unit     One or more systems has overload   Note that the entire parallel system    will not be able to return from bypass     No corrective action is necessary           PBus Communication  Fault on Cable 1        Communication fault detected on the  PBus 1 or PBus 2        Check PBus 1 or PBus 2 wiring   If this does not help contact APC        Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation       990 2282A 001    Troubleshooting     Status and Alarm Messages       Display Message    Meaning    Corrective Action       PBus Communication  Fault on Cable 2     Communication fault detected on the  PBus 1 or PBus 2     Check PBUS 1 or PBus 2 wiring   If this does not help contact APC        PBus Termination Fault  on Cable 1     PBus 1 or PBus 2  termination is missing     Check if termination is present  If this  does no
22. k      System Other                   Change date Change month       Press Press    e     p Ef se   2006 ua Date  24 2006     Date  ep     Date      f  Time  13 45 51 f Y Time  13 45 51                                     22 Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 990 2282A 001    Configuration     Settings      To goto Time Q The procedure to change the Time features is  Use Press the same as described for date and month    Date  24 Sep 2006         Time  13 45 51 Press  g    to return to previous screen s                       Alarm thresholds  The procedure for changing the Alarm thresholds is the same as described under the  Clock changes  Please be aware of the below notes     If the load level exceeds the pre programmed threshold  the UPS will display a warning     Note  Redundancy  The state of redundancy that will trigger an alarm  Choices are   e N 0   The power requirement exceeds the redundancy limit  Redundancy is not  Nora available       N 1   The power requirement does not utilize the last unit  Redundancy is available     e N 2   The power requirement does not utilize the last two units  Redundancy is  available             N 3   The power requirement does not utilize the last three units  Redundancy is  available     How to change the Beeper setup  the Contrast  and the Language in the Display menu    Chrg xxx   Load xxx   xxxxVin  Runtime    Control Display   Status Diags   Setup Help Beeper setup  Logging       Display    Work your way throu
23. larm Messages    34       Display Message    Meaning    Corrective Action       Int  Mech  Bypass  Switch Open     The internal mechanical switchgear is  open     No corrective action is necessary        Low Battery     The UPS is in battery operation and  the battery charge is low   Note  Runtime is limited in duration     Shut down the system and the load  equipment or restore incoming volt   age        Load Is No Longer    The load previously exceeded the    No corrective action is necessary              Above Alarm Threshold    alarm threshold and the situation has  been corrected either because the load  decreased or the threshold was  increased   Load Power Is Above The load has exceeded the user  Option 1  Use the display interface to  Alarm Threshold  specified load alarm threshold  raise the alarm threshold   Option 2  Reduce the load   Parallel Redundancy The load has exceeded the user Option 1  Use the display interface to  Below Alarm Threshold    specified load alarm threshold  raise the alarm threshold   Option 2  Reduce the load   Parallel redundancy is now restored   Mains Not Available  The frequency or voltage is out of Correct the input voltage to provide  Input Freq Volt Out of acceptable range for normal acceptable voltage or frequency   Range  operation        Min Runtime Restored     The system runtime dropped below  the configured minimum and has  been restored  Additional Battery  Modules were installed  the existing  Battery Modules were recharged  t
24. nly applicable to the 200 V version                 990 2282A 001                      e    Unscrew two M6 screws  one in each side of  the UPS      Pull top free of enclosure     Lift battery compartment cover free of the    two slots     Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 29    Maintenance     Parts Replacement    30    How to remove and install battery locks  if available   If your system is equipped with Battery  Locks  follow the below procedure to remove the battery locks       Remove the M6 screw attaching the battery  lock to the shelf     Q Push the battery lock to the left  push it  upwards and remove                          Use reverse procedures for installation of       battery locks                    Replacement     Batteries must be replaced by trained personnel only  see the section General safety  prior to Battery Module replacement      Caution    Directions for replacement  APC recommends that a whole battery module  four batteries  is replaced  at the same time to ensure optimal runtime  see Example 1   However  it is only necessary to replace two  batteries at the same time according to Example 2 and 3 in the below tables                                               seo Co  Col A Col B Col C Col D  Enclosure  Example 1 New New New New  Example 2 New New Old Old  Example 3 Old Old New New  352mm  14 in  Col A Col B  Enclosure  Example 1 New New  New New  New New  Example 2  Old Old  Old Old  Example 3  New New                   Smar
25. nters  go to www apc com support contact for contact information     Contact the APC representative or other distributor from whom you purchased your APC product for  information on how to obtain local customer support     Entire contents copyright 2007 American Power Conversion Corporation  All rights reserved   Reproduction in whole or in part without permission is prohibited  APC  the APC logo  PowerChute and  Smart UPS VT are trademarks of American Power Conversion Corporation  All other trademarks   product names  and corporate names are the property of their respective owners and are used for  informational purposes only          TIAE icd    
26. onal status of the UPS  The five  navigation keys to the right are used to select and open menu items  to access information  change  system parameters  and to get context sensitive help        Chrg 100   Load 000   230Vin 000Vout 50Hz       Run time  O0hr 30m                                                 Q LOAD ON When the green LED is lit  the UPS provides power to the load equipment      ON BATT When the yellow LED is lit  power flows from the batteries to the load   Q BYPASS When the yellow LED is lit  power to the load is supplied through bypass      FAULT When the red LED is lit  a fault condition exists   o LCD SCREEN Displays alarms  status data  instructional help  and configuration items   Q UP AND DOWN Used to scroll through and select menu items    NAVIGATION KEYS  9 HELP KEY Opens context sensitive help      ENTER KEY Opens menu items and confirms changes to system parameters   1  ESC KEY Returns to previous screen displayed        Display interface    Overview Screen  LCD screen   The Overview Screen is the main entrance to the user functions  of the display interface     Overview Screen          Chrg 100    Load 000    230Vin 000Vout 50Hz  Runtime  Ohr Om                The ENTER key takes you from the Overview Screen to the Main Menu Screen     2 Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 990 2282A 001    Overview     User Interface    Main Menu Screen  From the Main Menu Screen it is possible to command  configure  and monitor the  system throu
27. port in order to avoid  unwanted load impacts  For APC World Wide Customer Support  refer to the back cover of  this manual  If you by accident get beyond the functions described  press ESC to return to    previous screens     Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 5    Operation Modes       The UPS has different operation modes  If the installation includes a Maintenance Bypass Panel   MBP   an external maintenance bypass operation mode will also be available     Normal operation    The UPS converts utility mains power to conditioned power for the connected load     Battery operation    The UPS provides power to the connected load from its internal and  if available  external batteries  for a finite period  The UPS transfers to battery operation if the supply of utility mains power fails  or  is outside the pre defined limits     Internal bypass operation    Internal bypass keeps the load supplied with utility mains power during maintenance of the UPS   power sections  In internal bypass operation  utility mains power is sent directly to the connected  load bypassing all internal UPS functions and filters  Battery back up is not available in internal   bypass operation even though the batteries are in place     External maintenance bypass operation    The UPS can be connected to an optional external MBP  When activated  this panel bypasses the entire   UPS enclosure  feeding utility mains power directly to the load  An activated external MBP completely  isol
28. runtime  However  it is only necessary to replace two batteries at the same    Q  APC recommends that a whole battery module  four batteries  is replaced at the same time to  time  See section How to replace and install a battery module  Directions for replacement     Note    Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 990 2282A 001    Maintenance     Parts Replacement    User interface  front                                                                       Q Network Management Card with temperature sensor  used for remote system control    and monitoring  e mail notifications etc  For configuration and use  refer to the separate    user manual  Network Management Card with Environmental Monitor     shipped with the UPS      Computer interface port for the connection of computers with APC Powerchute   software       Internal Mechanical Bypass Lever  used to bypass the upstream utility mains power around the UPS  to support the load directly   internal bypass operation  Not applicable in parallel systems        Service port  for APC maintenance personnel only       Display port for the connection of display communication cable     Parallel operation port       Documentation storage         Power Module     990 2282A 001 Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 27    Maintenance     Parts Replacement    How to replace a Network Management Card                                                                  Loosen the two Torx screws    Carefully
29. s     Never attempt to switch back the UPS into normal operation till you have verified that there  are no internal UPS faults     Caution    From the external MBP  Turn the output Q From the UPS  Check that the yellow  switch  Q002  to position  1   ON    BYPASS  LED is lit and the green  LOAD  ON  LED is lit      From the external MBP  Turn the bypass Q From the UPS  Turn out of bypass from the  switch  Q003  to position    0     OFF   display via Control UPS out of bypass     Yes  UPS out of bypass     Q From the UPS  Check that the UPS is in  normal operation  The yellow  BYPASS   LED turns off and the green  LOAD ON  LED    remains lit     10 Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 990 2282A 001    Operation     Operation Procedures    Parallel System   turning into normal operation from external bypass        Never attempt to turn the UPS into normal operation till you have verified that there are no    internal UPS faults   Caution  Q From the external MBP  Turn all input  switches  Q001  to position    1     ON         From the external MBP  Turn all output  switches  Q002  to position    1     ON   The  lamp indicator of the output isolation breaker   Q004  is still lit     Q From the XR Enclosure s   if available   Set  the DC disconnect switch  if available  to the  ON position       From the UPS  Turn ON all UPS units from  each display via Control  Turn Load ON   Yes  Turn Load ON     Q From the UPS  Turn the UPS units into  bypass from one UPS di
30. splay via Control   UPS into bypass Yes  UPS into bypass   Check that the UPS units are in bypass  The  green  LOAD ON  and the yellow  BYPASS   LEDs are lit       From the external MBP  Turn the output  isolation breaker  Q004  to position    1     ON    Now the lamps  Q003   Q004  are lit      B From the UPS  Turn the UPS units out of  bypass from the display via Control UPS  out of bypass Yes  UPS out of bypass     Q From the external MBP  Check that all the  output lamps  Q002  are lit     Q From the UPS  Connect the batteries in the  UPS by pushing them in        From the XR Enclosure s   if available    Connect the batteries by pushing them in     Q From the external MBP  Check that all the  lamps  Q002  are unlit       From the external MBP  Check that the lamp  indicator of the output isolation breaker is lit   Q004       D From the external MBP  Turn the bypass  switch  Q003  to position    0     OFF   The  lamps  Q004  are unlit  but  Q003  is lit until  the UPS is running in normal operation     990 2282A 001 Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 11    Operation     Operation Procedures    How to turn load OFF ON via the display interface    Disconnecting the UPS output to the load does NOT de energize the UPS  Always follow  the total power off procedure if you need to de energize the UPS in emergency    Warning Situations  see section How to perform a total power off     Turn Load OFF   How to disconnect the UPS output to the load equipment     
31. ss  in bypass due to fault  or maintenance              Press the ESC key to return to the previous menus     990 2282A 001    Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 13    Operation     Operation Procedures    How to view Logging and Statistics    The View Log  View the 100 most recent UPS log events  and view the logged details of the events  such  as date  time of occurrence  and event number                                                  Use   Ss es Press  Chrg 100  ontro ogging  Load 000  f   Status Display  xxxVin 000Vout x0Hz Setup Diags  Runtime  Ohr Om g Help  Use Press  E 24 Sep 15 06 48  15 Press     gt  View log      Y Clear log    Mains out of Range    View statistics    On Line    v g pense    Logging Screen  example                             Q The top line states date  time  and event  number  Lines 2  3  and 4 are part of the event  list  To view the entire list  Use the UPDOWN  keys to go through the log events and press  ENTER to get a detailed description of a    particular event     The View Statistics  View the statistics on the operation mode changes  the inverter time  and the  duration of battery operation                                                        O e  Chrg 1002 daas pd Control     Loggi nes    ontro ogging  Load 000    S Status Display  xxxVin 000Vout x0Hz Setup Diags  Runtime  Ohr Om B Help  View log  Clear log     View statistics  Logging Screen  14 Smart UPS   VT 10 40 kVA 400V  208V  200V   Operation 990 2282A 001 
32. st you promptly     1  In the event of a module failure the display interface may show additional    fault list    screens  Press  any key to scroll through these fault lists  record the information  an provide it to the representative     2  Write down the serial number of the unit so that you will have it easily accessible when you contact  APC Customer Support     3  If possible call APC Customer Support from a telephone that is within reach of the UPS display  interface so that you can gather and report additional information to the representative     4  Be prepared to provide at detailed description of the problem  A representative will help you solve  the problem over the telephone  if possible  or will assign a return material authorization  RMA   number to you  If a module is returned to APC  this RMA number must be clearly printed on the  outside of the package     5  If the unit is within the warranty period  repairs or replacements will be performed free of charge  If  it is not within the warranty period  there will be a charge     6  If the unit is covered by an APC Service Contract  have the contract available to provide  information to the representative     How to return parts to APC  Call APC Customer support to obtain an RMA number     To return a failed module to APC  pack the module in the original shipping materials  and return it by  insured  prepaid carrier  The APC Customer Support representative will provide the destination address   If you no longer 
33. t UPS   VT 10 40 kVA 400V  208V  200V     Operation 990 2282A 001    Maintenance     Parts Replacement    Follow the below procedures if you need to change or add a battery module  e g  if you receive a display    message reporting a bad battery  or if you need to add batteries for increased runtime                                                                               When removing Battery Modules  start from    Holding the battery handle  gently push the  the highest level and work down  battery upwards and pull it halfway out of  the enclosure  A lock mechanism prevents it  from being pulled all the way out      To release the battery from the lock  mechanism  gently push the battery upwards  again and pull it out  while another person    supports the battery   Installation  If additional batteries are needed for extra runtime  or if you install battery replacement    modules  be aware of the following     Batteries must be replaced by trained personnel only  see the section General safety  prior to Battery Module replacement      Caution  Do not install Battery Modules in the UPS until you are ready to power up the system   Disregarding this caution can result in a deep discharge of the batteries and cause  permanent damage  The time between battery installation and powering up the UPS  Caution    should not exceed 72 hours or 3 days     990 2282A 001 Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 31    Maintenance     Parts Replacement    UPS   XR        
34. t help contact APC        PBus Termination Fault  on Cable 2     PBus 1 or PBus 2  termination is missing     Check if termination is present  If this  does not help contact APC        Parallel Configuration  Fault     The parallel system has not been con   figured correct     Contact APC           Parallel Redundancy The parallel redundancy has been No corrective action is necessary   Restored  restored   Replace Batt s   One or more Battery Modules need See the section How to replace and    replacement  only applicable with  internal batteries      install a battery module for proce   dures        Runtime Is Below Alarm  Threshold     The predicted runtime is lower than  the user specified minimum runtime  alarm threshold  Either the battery  capacity has decreased  or the load  has increased     Option 1  Allow the battery modules  to recharge    Option 2  If possible  increase the  number of battery modules    Option 3  Reduce the load    Option 4  Decrease the alarm  threshold    Contact APC Customer Support    see back cover         Site Wiring Fault     Wrong phase rotation on the input  side  The UPS will continue to supply  conditioned power from batt     An electrician should check that the  UPS has been wired properly        Shutdown Due To Low  Battery     The UPS was in Battery Operation  and shut down the load when no more  battery power was available     No corrective action is necessary   Note  If the problem reoccurs  con   sider increasing the battery capaci
35. tallation  MBP   CAN I O Board      990 2873    1 Smart UPS   VT 10 40 kVA  400 V  208 V  200 V   Operation 990 2282A 001    About this Manual    How to find updates to this manual    You can check for updates to this manual on the APC Web site  www apc com      2 Smart UPS   VT 10 40 kVA  400 V  208 V  200 V   Operation 990 2282A 001    Contents       rj                                    OVervIe Wo uctus sa kaka    User MAC  sin a      klar iene REPE RANT ED 2  Interface area              lle 2  Display interface                 ellen 2  MENU TR  aa e A E a a DUE maia ada e aa a 4    Operat Mpesa oaa    Operation Modes         c r cle eee eee aur xn dee ee ene 6  Normal operation    1    0 eee ee 6  Battery operation    1    ee 6  Internal bypass operation            00 002 ee eee eee 6  External maintenance bypass operation                   6  Optional parallel operation                    ell  6  Operation Procedures             00 cece eee ee ee eee 7  How to turn into bypass          0 2000 nannan 7  How to turn into normal operation                     10  How to turn load OFF ON via the display interface           12  How to view the Status screens                 llle 12  How to view Logging and Statistics                    14  How to use the Diags screen                 lle    15  How to perform a total power off                 less  16  How to perform a restart         0 220 eee ee ee 19    Configuration   oet eer nn oe    Settings eui xat Me ape det Vd qos RRR 
36. ternal MBP  Check that the bypass  lamp indication is lit  Q003      Q From the external MBP  Check that the lamp  indication of the output isolation breaker is lit   Q004      O From the UPS  Turn OFF each UPS from the  display via Control     Turn Load off     Yes   Turn Load off      D From the external MBP  Turn all output  switches  Q002  to position    0     OFF       D From the XR Enclosure s   if available   Set  the DC disconnect switch  1f available  to  position OFF      D From the XR Enclosure s   if available    Disconnect the batteries by pulling them out to    the red disconnect line     Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation 9    Operation     Operation Procedures    How to turn into normal operation    Single System   turning into normal operation from internal bypass     Never attempt to switch back the UPS into normal operation till you have verified that there  are no internal UPS faults   Caution      Check that the UPS is in bypass  The green Q Turn the mechanical bypass lever downwards   LOAD ON  and the yellow  BYPASS  LEDs are into a horizontal position to deactivate the    lit  internal bypass operation        Press ESC to return to the previous menus and   Check that the UPS is in normal operation     turn out of bypass from the display via The yellow  BYPASS  LED turns off and the  Control UPS out of bypass Yes  UPS out green  LOAD ON  LED remains lit   of bypass     Single System   turning into normal operation from external bypas
37. ty        Static Bypass Switch  Fault     The Static Bypass Switch has failed     Contact APC Customer Support  see  back cover         System Failure Detected  by Surveillance     The system has detected an internal  error     Check for other alarms and contact  APC customer support if the problem  persists           System Start Up  Configuration Failed        System configuration error  Unable to  determine system voltage and or  Enclosure size     Check for other alarms and contact  APC customer support if the problem  persists              990 2282A 001    Smart UPS   VT 10 40 kVA 400V  208V  200V     Operation    35    Troubleshooting     Status and Alarm Messages    36       Display Message    Meaning    Corrective Action       System Not Synchro   nized to Bypass     The system cannot synchronize to  bypass  The mode may not be avail   able     Option 1  Decrease the input fre   quency sensitivity    Contact APC Customer Support    see back cover     Option 2  Correct the bypass input  voltage to provide acceptable voltage  on frequency        UPS In Bypass Due To  Fault     The UPS has transferred to Bypass  Mode because a fault has occurred     Contact APC Customer Support   see back cover         UPS In Bypass Due To  Overload     The load exceeded the power  capacity  The UPS has switched to  Bypass Mode     Decrease the load        UPS Is Overloaded     The load exceeded the system power  capacity     Option 1  Decrease the load    Option 2  Check the load distri
38. ww w apc com       Operation    Smart UPS  VT    10 40 kVA     400 V  10 30 kVA     208 V  10 30 kVA     200 V                   pu em                        j    l    s       About this Manual       IMPORTANT SAFETY INSTRUCTIONS  SAVE THESE INSTRUCTIONS    This manual is intended for the user of the Smart UPS   VT     It refers to important safety warnings and instructions  gives an introduction to the display interface   and provides information on operation  load connection  parts replacement  troubleshooting  total  power off and restart     Only graphics of Smart UPS   VT with built in batteries are shown in this manual  but the  manual is intended for the users of one or more units within the Smart UPS   VT family range     Note    Companion manuals  For additional information about   Smart UPS   VT 400 V     Safety     990 2822  e Receiving and Unpacking     990 2284    Receiving and Unpacking  with batteries      990 1747    Installation     990 2283     nstallation  with batteries      990 1598    Installation  in parallel      990 3045    Installation  MBP CAN I O Board      990 2873  Smart UPS   VT 208 V     Safety     990 2822    Receiving and Unpacking  with batteries      990 1747    Installation     990 2869  e Installation  in parallel      990 3045    Installation  MBP CAN I O Board      990 2873A  Smart UPS   VT 200 V     Safety     990 2822    Receiving and Unpacking     990 2358    Installation     990 2360     nstallation  in parallel      990 3045    Ins
    