Home

Daikin REYQ120PATJ Specifications

image

Contents

1. EE _ in For detailed instructions please refer to proper Installation Manual 24 Standard supplied accessories Confirm the following accessories are included The storage location of the accessories is shown in figure 1 Refer to figure 1 1 Clamps Manuals etc 2 Accessory pipes Installation Space Examples The installation space requirement shown in figure 2 is a reference for cooling During installation install the units using the most appropriate of the patterns shown in figure 2 for the location in question taking into consideration human traffic and wind If the number of units installed is more than that shown in the pattern in figure 2 install the units that there is no air short cuircuting As regards to space in front of the unit consider the space needed for the refrigerant piping when installing the units as determined by local codes If the space requirements in figure 2 do not apply contact your contractor or Daikin directly Refer to figure 2 1 Front side 2 No limit to wall height 3 Service space of front side 4 Service space of suction side For Patterns 1 and 2 in figure 2 Wall height for front side no higher than 59 in Wall height on the suction side no higher than 19 5 8 in Wall height for sides no limit If the height is exceeded the abo
2. ee x 4 i M 1 gt iat A hs in li i g Wak di am Fj i i ia aryl 4 Lb x li Hr s i Fia I Lan i ae 3 y f i i If ON NEW C IRUCTIO ie a I a 1 Wi I i Daikin s VRVIII system is the 7th generation of the original Daikin VRV launched in 1982 Completely re engineered to realize opportunities for VRV in taller larger buildings it utilizes the latest advances in refrigeration and air conditioning technology The totally new Daikin Inverter compressor system delivers improved efficiency and performance while ensuring satisfaction of demands throughout the connected zones With a choice of 460V 3ph 60Hz or 208 230V 3ph 60Hz the heat pump or heat recovery configurations power up to 20 Ton capacity from a single piping network The system also allows up to 41 indoor fan coil units a 200 connection index and integrated controls with BMS options and piping limitations never before seen with a DX system With these attributes VRVIII naturally positions itself wherever traditional chilled water systems are desired m 3 iml d 5 p ig im g a a pa ie i a A i A i LS l i on ia fi f f ad ie a f 343 N7 MT FT 3z azo ALL Commercial sites can range in size from a few hundred to several thousand square feet That s why Daikin offers the new VRVIII air cooled system with advanced fea
3. Improvement of the cooling heating changeover Continuous operation during oil recovery Sound level reduction of branch selector unit No system interruption in mode changeover With most VRF systems when changing an indoor unit from cooling to heating the heating operation for the full system is shut down The system pressure must equalize in the hot gas line which causes disruption to all units in heating The heating is then started for the full system and each indoor unit has to go through a hot start the indoor unit coil has to be at approximately 93 F before the fan starts to avoid cold drafts This sequence of operation can take approximately 10 minutes With the new branch selector unit BSVQ_P only the indoor units changing trom cooling to heating will shut down and only those will go through a hot start causing no system disruption and only six minutes of downtime for the indoor unit changing operation mode The changeover time can be shortened depending on the pipe length from the branch selector unit to indoor unit by simply reprogramming the indoor unit range 3 10 minutes Traditional VRF Model EV EV CD CD mr ll M Wy C gt H II C gt H j Om O lt lam jo lt 4 l l I M MA M Oe De EV EV cD C I I I Fanor i AA 4 FAN gi eis Heating interruption 10min No system memunton Iml EV EV EV EV CD CD ir CD 6D I I I I I S IA S
4. 17 33 50 67 83 100 x 4 46 7ft Total 33x2 17 33 50 x8 J0 Jt 33ft III SS I e m Ha O III As shown above using a 2 pipe heat recovery system results in an increase of about 209o additional piping and insulation in best case scenario augmenting both cost of supplies and labor Moreover the Daikin VRV system ensures an easier compliance with local and national refrigerant safety standards such as ASHRAE Standard 15 Cooling Widely acknowledged as the most advanced system of its type in the market VRV represents a powerful combination of advanced inverter heat pump and control technologies When cooling a space the system can operate at full load EER levels as high as 12 2 6 Ton heat pump and 12 6 6 Ton heat recovery However the system can operate at much higher EER levels during part load operation Buildings are made up of many individual zones which can have varying heating and cooling requirements It is more efficient to cool or heat an individual space as needed than to condition all of the space throughout the building all of the time VRV systems have the ability to control the amount of refrigerant flowing to each of the indoor units enabling the use of up to 41 indoor units with differing capacities and styles providing individualized comfort control simultaneous heating and cooling in different zones and heat recovery from one zone to another Based on a simulation developed by Daikin s proprieta
5. Concealed floor standing unit 100 Outside Air Processing Unit FXNQ_MVJU FXMQ_MFVJU a gt a gt a gt A gill a gt a gt A Available 11 types 51 models il Available with a capacity reduction plug two additional models Condensate pump standard on model Outside air connection possible on model DAIKIN AC ABSOLUTE COMFORT 15 Single Module Systems Model Performance Refrigerant Piping Connection Ratio Unit Fan Electrical Compressor Name RXYQ72PAYD RXYQ96PAYD RXYQ108PAYD Nominal Cooling Capacity Btu h 72 000 96 000 108 000 Rated Cooling Capacity Btu h 70 000 92 000 104 000 Rated Cooling Input Power system kW 5 74 8 29 9 45 Rated Full Load EER system 12 2 11 1 11 0 Nominal Heating Capacity Btu h 81 000 108 000 122 000 Rated Heating Capacity Btu h 77 000 103 000 116 000 Rated Heating Input Power system kW Btu h 6 6 9 1 10 3 Rated Full Load COP system 3 4 30 32 Power V ph Hz 460 3 60 460 3 60 460 3 60 Sound Pressure Level at 3ft dB A 58 58 60 Refrigerant Type and Quantity Ibs R 410A 18 1 R 410A 19 8 R 410A 20 1 Liquid Pipe Main Line in 3 8 Braze 3 8 Braze 1 2 Braze Suction Gas Pipe Main Line in 3 4 Braze 7 8 Braze 1 1 8 Braze Vertical Pipe Length if unit is below FCU ft 295 295 295 Vertical Pipe Length if unit is above FCU ft 1
6. malfunction code has been activated This allows the end user if desired to reset the system and run on 50 of heating cooling until a service technician arrives 14 Automatic Charge Function Conventional Way 1 Calculation of additional refrigerant charging volume 2 Charging the unit with additional refrigerant 3 Measuring the weight of the cylinder we 4 Judgment based on pressure test operation Indoor VRVIII temperature With VRVIII however these four steps are omitted since the 90 F VRVIII unit can be charged with the necessary amount of refrigerant automatically via a push button on the PCB Automatic charging will cease once the appropriate amount of refrigerant has been transferred If temperature drops below 32 F outdoors manual charging is necessary After having switched to heating and once the 50 F indoor temperature rises above 32 F push the auto charge button to activate auto charge function Outdoor Automatic Test Simplified Commissioning 32 F 109 F temperature When refrigerant charging has ceased pushing the test operation button on the PCB will initiate a check on the wiring shut off valves sensors and refrigerant volume This test ceases automatically when completed Easy Maintenance Self Diagnostic Function This function operated via push button on the PCB speeds up troubleshooting and should be used for start up and Test operation button maintenance Disconnect
7. 1 1 8 Braze 1 3 8 Braze High and Low Pressure Equalization Pipe in 3 4 Braze 3 4 Braze 3 4 Braze 3 4 Braze 3 4 Braze Vertical Pipe Length if unit is below FCU ft 285 295 295 295 295 Vertical Pipe Length if unit is above FCU ft 164 295 with Option 164 295 with Option 164 295 with Option 164 295 with Option 164 295 with Option Actual Pipe Length Equivalent Length ft 540 620 540 620 540 620 540 620 540 620 Total Pipe Length ft 3 280 3 280 3 280 3 280 3 280 Connectable Indoor Unit Ratio 50 130 as Standard Up to 200 is permitted depending on application amp fan coil unit selection Maximum Number of Indoor Units Qty 25 29 33 37 41 Weight Ibs 573 573 573 573 573 573 573 573 573 573 Dimensions H x W x D in 66 1 8 x 36 5 8 x 30 1 8 x 2 Air Flow cfm 6 530 6 530 6 530 6 530 6 530 6 530 7 060 6 530 7 060 7 060 External Static Pressure in W G 0 32 0 32 0 32 0 32 0 32 Fan Motor Output and Quantity kW Qty 0 75x2 0 75x2 0 75x2 0 75x2 0 75x2 Maximum Overcurrent Protection MOP A 254 25 254 25 254 25 25 30 30 30 Minimum Circuit Amps MCA A 20 2 20 2 20 3 20 2 20 3 20 3 20 5 20 3 20 5 20 5 Minimum Starting Current MSC A 69 69 69 77 78 Compressor Rated Load Amps RLA A 7 1 4 7 1 3 9 8 4 7 1 3 9 4 8 4 3 9 8 4 3 9 8 4 6 1 8 4 6 1 8 4 x2 Compressor Type Daikin Scroll x 4 Daikin Scroll x 4 Daikin Scroll x 4 Daikin Scroll x 4 Daikin Scroll
8. 5 5 amp dias N S e External Static Pressure ESP i ete z The additional ESP up to 0 32 W G provides tar more flexibility when designing condensing units in plant room applications No additional components are required to extend the fan performance It is now even easier to put a condensing unit on each floor or in a mechanical room and duct out the discharge air Wife ESP up to 0 32 W G Exhaust duct Superior Heating Comfort Thanks to the newly adopted continuous heating Each heat exchanger is defrosted by using heat during defrost function cold draft discharge from the transferred from one heat exchanger to the other in indoor unit during defrost is eliminated Therefore the outdoor unit heating comfort is improved and better maintained Outdoor unit Outdoor unit Defrosting Ex1 not available in single module heat pump Heating Operation While on Defrost Operation The first graph below shows the defrost cycle on the previous model where It uses a reverse cycle defrost of 10 to 14 minutes and then has to perform a hot start With VRVIII the outdoor unit continues in heating and the fans will switch to LL Low Low Defrost lasts for 8 to 12 minutes and because heating operation has continued no hot start is required Heating operation while on defrost operation The new VRVIII allows continuous heating Heating cycle is continued also while in defrost operation No hot start Manfold
9. 60 Sound Pressure Level at 3ft dB A 58 58 60 Refrigerant Type and Quantity Ibs R 410A 18 1 R 410A 19 8 R 410A 20 1 Liquid Pipe Main Line in 3 8 Braze 3 8 Braze 1 2 Braze Suction Gas Pipe Main Line in 3 4 Braze 7 8 Braze 1 1 8 Braze Refrigerant Piping Vertical Pipe Length if unit is below FCU ft 295 295 295 Vertical Pipe Length if unit is above FCU ft 164 295 with Option 164 295 with Option 164 295 with Option Actual Pipe Length Equivalent Length ft 540 620 540 620 540 620 Total Pipe Length ft 3 280 3 280 3 280 ain ma nae Connectable Indoor Unit Ratio 50 130 as Standard Up to 200 is permitted depending on application amp fan coil unit selection Maximum Number of Indoor Units Qty 12 16 18 Unit Weight Ibs 560 560 560 Dimensions H x W x D in 66 1 8 x 36 5 8 x 30 1 8 66 1 8 x 36 5 8 x 30 1 8 66 1 8 x 36 5 8 x 30 1 8 Air Flow cfm 6 530 7 060 Fan External Static Pressure in W G 032 0 32 Fan Motor Output and Quantity kW Qty 0 5x1 0 75x1 Maximum Overcurrent Protection MOP A 40 50 60 A Minimum Circuit Amps MCA A 36 1 36 1 41 3 Minimum Starting Current MSC A 131 131 132 Compressor Rated Load Amps RLA A 14 2 7 8 16 8 12 2 16 8 Compressor Type Daikin Scroll x 2 Daikin Scroll x 2 Daikin Scroll x 2 Compressor Compressor Set Up 1 INV 1 FIX 1 INV 1 FIX 1 INV 1 FIX Compressor Capacity Control 20 100 14 100 14 100 1 Indoor temp 80 FDB or 67 FWB outdoor temp 9
10. the outdoor unit modules is PI g ge MH i operating due to low load refrigerant is bypassed I ao to the other outdoor unit through the pressure I ne equalizing pipe By utilizing both heat exchangers part T EN a S I Equalizing pressure pipe I I load energy efficiency is improved ene eee fener Partial ele I meee aa Is operation 53 F595 FT TIT Previous Model FFA Lil And Competitors Flare or Shutoff Outdoor Brazed Shutoff Outdoor flange valve unit joint valve unit To minimize the chance of leaks the piping connections inside the outdoor unit are all brazed Also the flared connections were changed to brazed connections on liquid and gas shutoff valves High low pressure gas pipe Suction gas pipe Equalizing pressure pipe Liquid pipe gt Flare connections Brazed joints In order to make operation time equal for each compressor in a manifolded system the outdoor units are used in rotation The operation priority starts once the following conditions have been met On completion of oil recovery cycle On completion of defrost Upon restart once a system has stopped The cyclical start up sequence of multiple outdoor unit systems equalize compressor duty and extends operating lite Back up redundancy Should a fault occur on a compressor the system can be set into emergency mode This will allow the system to operate at partial capacity for a period of 24 hours until t
11. 000 184 000 206 000 240 000 Rated Cooling Input Power system kW 11 31 14 04 1720 19 43 24 49 Rated Full Load EER system 12 2 11 4 10 7 10 60 9 80 mm Nominal Heating Capacity Btu h 162 000 188 000 216 000 243 000 270 000 Rated Heating Capacity Btu h 154 000 180 000 206 000 232 000 258 000 Rated Heating Input Power system kW Btu h 13 3 16 0 18 9 21 25 23 63 Rated Full Load COP system 3 4 3 3 3 2 3 2 3 2 Power V ph Hz 208 230 3 60 208 230 3 60 208 230 3 60 208 230 3 60 208 230 3 60 Sound Pressure Level at 3ft dB A 61 61 62 62 63 Refrigerant Type and Quantity R 410A 18 14 18 1 R 410A 19 8 18 1 R 410A 19 8 19 8 R 410A 20 1 19 8 R 410A 20 1420 1 Liquid Pipe Main Line 1 2 Braze 5 8 Braze 5 8 Braze 5 8 Braze 5 8 Braze Suction Gas Pipe Main Line 1 1 8 Braze 1 1 8 braze 1 1 8 Braze 1 1 8 Braze 1 3 8 Braze High and Low Pressure Gas Pipe Main Line 7 8 Braze 7 8 Braze 1 1 8 Braze 1 1 8 Braze 1 1 8 Braze es High and Low Pressure Equalization Pipe 3 4 Braze 3 4 Braze 3 4 Braze 3 4 Braze 3 4 Braze PMI Vertical Pipe Length if unit is below FCU 295 295 295 295 295 Vertical Pipe Length if unit is above FCU 164 295 with Option 164 295 with Option 164 295 with Option 164 295 with Option 164 295 with Option Actual Pipe Length Equivalent Length 540 620 540 620 540 620 540 620 540 620 Total Pipe Length 3 280 3 280 3 280 3 280 3 280 Connection Connectable Indoor Unit Rati
12. 3 4 Braze 33 Note REYQ72PAYD In case of connecting with a 07 18 type indoor unit match to the size of field pipe using the attached pipe REYQ96PAYD Connection between the attached pipe and the field pipe must be brazed REYQ120PAYD 2 In case of connecting with indoor unit capacity index 54 or more and 60 or less match the size of the field pipe using the attached pipe T Connection between the attached pipe and the field pipe must be brazed Double Module Systems VRVIII 460V Heat Recovery Model Performance Refrigerant Piping Connection Ratio Unit Fan Electrical Compressor 12 Ton 14 Ton 16 Ton 18 Ton 20 Ton Name REYQ144PAYD REYQ168PAYD REYQ192PAYD REYQ216PYDNR REYQ240PYDNR Combination REMQ72PAYD x 2 ego REMQ96PAYD x 2 je eee y REMQ120PYDNR x 2 Nominal Cooling Capacity Btu h 144 000 Rated Cooling Capacity Btu h 138 000 160 000 184 000 206 000 240 000 Rated Cooling Input Power system kW 11 31 14 04 17 20 19 43 24 49 Rated Full Load EER system 12 2 11 4 10 7 10 60 9 80 Nominal Heating Capacity Btu h 162 000 188 000 216 000 243 000 270 000 Rated Heating Capacity Btu h 154 000 180 000 206 000 232 000 258 000 Rated Heating Input Power system kW Btu h 13 3 16 0 18 9 21 25 23 63 Rated Full Load COP system 3 4 3 3 3 2 3 2 3 2 Power V ph Hz 460 3 60 460 3 60 460 3 60 460 3 60 460 3 60 Sound Pressure Level at
13. 3ft dB A 60 Refrigerant Type and Quantity Ibs R 410A 18 1 18 1 R 410A 19 8 18 1 R 410A 19 8 19 8 R 410A 20 1 19 8 R 410A 20 1420 1 Liquid Pipe Main Line in 1 2 Braze 5 8 Braze 5 8 Braze 5 8 Braze 5 8 Braze Suction Gas Pipe Main Line in 1 1 8 Braze 1 1 8 braze 1 1 8 Braze 1 1 8 Braze 1 3 8 Braze High and Low Pressure Gas Pipe Main line in 7 8 Braze 7 8 Braze 1 1 8 Braze 1 1 8 Braze 1 1 8 Braze High and Low Pressure Equalization Pipe in 3 4 Braze 3 4 Braze 3 4 Braze 3 4 Braze 3 4 Braze Vertical Pipe Length if unit is below FCU ft misin aga 295 205 295 Vertical Pipe Length if unit is above FCU ft 164 295 with Option 164 295 with Option 164 295 with Option 164 295 with Option 164 295 with Option Actual Pipe Length Equivalent Length ft 540 620 540 620 540 620 540 620 540 620 Total Pipe Length ft 3 280 3 280 3 280 3 280 3 280 Connectable Indoor Unit Ratio 50 130 as Standard Up to 200 is permitted depending on application amp fan coil unit selection Maximum Number of Indoor Units Qty 25 29 33 37 41 Weight Ibs 463 463 573 463 573 573 573 573 573 573 Dimensions H x W x D in 66 1 8 x 36 5 8 x 30 1 8 x 2 Air Flow cfm 6 350 6 350 6 530 6 350 6 530 6 530 7 060 6 530 7 060 7 060 External Static Pressure in W G 0 32 0 32 0 32 0 32 0 32 Fan Motor Output and Quantity kW Qty 07x2 En 05X2 0 79X2 ONS 2 Maximum Overcurrent Protection MO
14. 5 FDB Equivalent piping length 25 ft 7 5 m level difference 0 ft 2 Indoor temp 70 FDB outdoor temp 47 FDB or 43 FWB Equivalent piping length 25 ft 7 5 m level difference 0 ft 3 The tested system EER and COP values reflect full load efficiency only and are the results from testing to the Alternate Test Method ATM guidelines provided by the U S Department of Energy DOE in the Federal Register Vol 74 No 68 Friday April 8 2009 Notices Pages 15955 15958 RXYQ72PATJ RXYQ96PATJ RXYQ108PATJ 18 Double Module Systems Name RXYQ144PATJ RXYQ168PATJ RXYQ192PATJ RXYQ216PTJUR RXYQ240PTJUR Mode Combination RXYQ72PATJ x 2 bin i RXYQ96PATJ x 2 e i RXYO120PTJUR x 2 Nominal Cooling Capacity Btu h 144 000 240 000 Rated Cooling Capacity Btu h 138 000 160 000 184 000 206 000 240 000 Rated Cooling Input Power system kW 11 31 14 04 17 20 19 43 24 49 Rated Full Load EER system 12 2 11 4 10 7 10 60 9 80 E SR Nominal Heating Capacity Btu h 162 000 188 000 216 000 243 000 270 000 Rated Heating Capacity Btu h 154 000 180 000 206 000 232 000 258 000 Rated Heating Input Power system kW Btu h 13 3 16 0 18 9 21 25 23 63 Rated Full Load COP system 3 4 3 3 3 2 3 2 3 2 Power V ph Hz 208 230 3 60 208 230 3 60 208 230 3 60 208 230 3 60 208 230 3 60 Sound Pressure Level at 3ft dB A 61 63 Refrigerant Type and Ouantity Ibs B
15. 64 295 with Option 164 295 with Option 164 295 with Option Actual Pipe Length Equivalent Length ft 540 620 540 620 540 620 Total Pipe Length ft 3 280 3 280 3 280 Connectable Indoor Unit Ratio 50 130 as Standard Up to 200 is permitted depending on application amp fan coil unit selection Maximum Number of Indoor Units Qty 12 16 18 Weight lbs 53 573 S Dimensions H x W x D in 66 1 8 x 36 5 8 x 30 1 8 66 1 8 x 36 5 8 x 30 1 8 66 1 8 x 36 5 8 x 30 1 8 Air Flow cfm 6 530 7 060 External Static Pressure in W G 0 32 0 32 Fan Motor Output and Quantity kW Qty 0 75x1 0 75x1 Maximum Overcurrent Protection MOP A 25 25 30 Minimum Circuit Amps MCA A 20 2 208 ACIS Minimum Starting Current MSC A 65 65 65 Compressor Rated Load Amps RLA A 7 1 3 9 8 4 6 1 8 4 Compressor Type Daikin Scroll x 2 Daikin Scroll x 2 Daikin Scroll x 2 Compressor Set Up 1 INV 1 FIX 1 INV 1 FIX 1 INV 1 FIX Compressor Capacity Control 20 100 14 100 14 100 1 Indoor temp 80 FDB or 67 FWB outdoor temp 95 FDB Equivalent piping length 25 ft 7 5 m level difference 0 ft 2 Indoor temp 70 FDB outdoor temp 47 FDB or 43 FWB Equivalent piping length 25 ft 7 5 m level difference 0 ft 3 The tested system EER and COP values reflect full load efficiency only and are the results from testing to the Alternate Test Method ATM guidelines provided by the U S
16. A cm AS IR wh a ae I i i i at ii HOT START 7 HOT START ELECTRONIC EXPANSION VALVES amp KD 502 amp AS I VR III ELECTRONIC EXPANSION VALVE Previous Model The Daikin Difference In most VRF systems the heating mode for the Tull system has to allow the high pressure in the hot gas line to equalize before heating is started There then has to be at least 44 psi difference between gas and suction to have enough force to switch the 3 way valve which could cause refrigerant noise The new branch selector unit has dual expansion valves on both suction and high low pressure gas pipes in place of the 3 way valve in the previous model This allows the pressure from the branch selector unit to indoor unit to slowly equalize by opening the sub expansion valve on high low pressure pipe closing all other valves in the branch selector unit before full heating operation begins for that indoor unit This eliminates the need to stop the heating mode in the full system and reduces sound level Also the solenoid valve and capillary tube supply to the liquid sub cool heat exchanger is replaced by an expansion valve to eliminate the switching sound of the solenoid valve and also to enable some control of the amount of refrigerant to flow through the sub cool heat exchanger Branch Selector unit Liquid pipe SSS SSS SS SS SS SS SS SSS SS SS SS SS eS Faics aaih Indoor unit SSS SS eS Se a ELECTRONI
17. C EXPANSION VALVES ELECTRONIC EXPANSION VALVE High low pressure gas pipe LE I il a Suction gas pipe E gt Ewe EEE m Am Eo b em ee ee paia do do Eo ee Eo dos dol Eo Eo ee Eo do m En Eo dh ee a s ee In heating operation Benefits of Daikin VRVIII using 3 pipe configuration in its heat recovery version Daikin s VRV heat recovery uses a dedicated hot gas pipe during heating operation allowing for higher off coil temperatures even at lower ambient conditions thus increasing the heating capacity of the system Compared to a 2 pipe heat recovery system using a liquid gas mixture line the Daikin system eliminates the friction occurring between pure gas and pure liquid when used in the same pipe Also the 2 pipe heat recovery systems have a lower hot gas temperature which can result in a lack of heating capacity and off coil temperatures Daikin s layout example The Daikin 3 pipe system allows for installation of smaller easily hidden branch selector units facilitating installation in remote spaces Say TIT WAaAaAD MUMU oe Total 33ftx3 3ftx3 6x3x7ft 83ftx3 12x10ftx2 PDO MA Branch selector unit Other VRF layout examples 2 pipe systems usually require a Competitors branch J ngoor unl bulky branch controller box needing a drain connection controller box Branch controller box located at the end of the hallway Branch controller box centrally located Total 33x2
18. Department of Energy DOE in the Federal Register Vol 74 No 68 Friday April 8 2009 Notices Pages 15955 15958 RXYQ72PAYD RXYQ96PAYD RXYQ108PAYD 16 Double Module Systems Model Performance Refrigerant Piping Connection Ratio Unit Fan Electrical Compressor Name RXYQ144PAYD RXYQ168PAYD RXYQ192PAYD RXYQ216PYDNR RXYQ240PYDNR Combination RXYQ72PAYD x 2 a ao RXYQQ6PAYD x 2 eae RXYQ120PYDNR x 2 Nominal Cooling Capacity Btu h 144 000 168 000 192 000 216 000 240 000 Rated Cooling Capacity Btu h 138 000 160 000 184 000 206 000 240 000 Rated Cooling Input Power system kW 11 31 14 04 17 20 19 43 24 49 Rated Full Load EER system 12 2 11 4 10 7 10 6 9 80 Nominal Heating Capacity Btu h 162 000 188 000 216 000 243 000 270 000 Rated Heating Capacity Btu h 154 000 180 000 206 000 232 000 258 000 Rated Heating Input Power system kW Btu h 13 3 16 0 18 9 21 25 23 63 Rated Full Load COP system 3 4 3 3 3 2 3 2 3 2 Power V ph Hz 460 3 60 460 3 60 460 3 60 460 3 60 460 3 60 Sound Pressure Level at 3ft dB A 62 61 62 62 63 Refrigerant Type and Quantity Ibs R 410A 18 14 18 1 R 410A 19 8 18 1 R 410A 19 8 19 8 R 410A 20 1 19 8 R 410A 20 1 20 1 Liquid Pipe Main Line in 1 2 Braze 5 8 Braze 5 8 Braze 5 8 Braze 5 8 Braze Suction Gas Pipe Main Line in 1 1 8 Braze 1 1 8 Braze 1 1 8 Braze
19. MSC A 65 65 65 Compressor Rated Load Amps RLA A 2 4 4 7 0 4 2 7 0 6 0 6 8 Compressor Type Daikin Scroll x 2 Daikin Scroll x 2 Daikin Scroll x 2 Compressor Compressor Set Up 1 INV 1 FIX 1 INV 1 FIX 1 INV 1 FIX Compressor Capacity Control 20 100 14 100 14 100 1 Indoor temp 80 FDB or 67 FWB outdoor temp 95 FDB Equivalent piping length 25 ft 7 5 m level difference 0 ft 2 Indoor temp 70 FDB outdoor temp 47 FDB or 43 FWB Equivalent piping length 25 ft 7 5 m level difference 0 ft 3 The tested system EER and COP values reflect full load efficiency only and are the results from testing to the Alternate Test Method ATM guidelines provided by the U S Department of Energy DOE in the Federal Register Vol 74 No 68 Friday April 8 2009 Notices Pages 15955 15958 The Branch Selector units are used for VRVIII Heat Recovery applications Please refer to engineering data for details Model Name BSVQ36PVJU BSVQ60PVJU BSVQ96PVJU a Power Supply gii Total Capacity Index of Connectable Indoor Units Lessthan36 Lessthan60 Less than 96 a Maximum Number of Connectable Indoor Units 5S 8o 5 Casing nu Galvanized Steel Plate a Dimensions H x W x D 8 3 16 x 15 5 16 x 12 13 16 G sessment cae a Indoor 3 8 Braze 0 7 8 Braze a fi Firing 3 8 Braze Connections Outdoor Sucti m 7 8 Brae Discharge Gas Pipes 1 2 Braze
20. P A 254 25 254 25 254 25 25 30 30 30 Minimum Circuit Amps MCA A 16 7 16 7 20 3 16 7 20 3 20 3 20 5 20 3 20 5 20 5 Minimum Starting Current MSC A 69 69 77 78 Compressor Rated Load Amps RLA A 7 1 x 2 3 9 8 4 7 1 3 9 8 4 3 9 8 4 3 9 8 4 6 1 8 4 6 1 8 4 x 2 Compressor Type Daikin Scroll x 2 Compressor Set Up 1 INV x 2 1 INV 1 FIX 4 1INV 1 INV 1 FIX x2 1 INV 1 FIX x 2 1 INV 1 FIX x 2 Compressor Capacity Control 13 100 9 100 7 100 7 100 6 100 1 Indoor temp 80 FDB or 67 FWB outdoor temp 95 FDB Equivalent piping length 25 ft 7 5 m level difference 0 ft 2 Indoor temp 70 FDB outdoor temp 47 FDB or 43 FWB Equivalent piping length 25 ft 7 5 m level difference 0 ft 3 The tested system EER and COP values reflect full load efficiency only and are the results from testing to the Alternate Test Method ATM guidelines provided by the U S Department of Energy DOE in the Federal Register Vol 74 No 68 Friday April 8 2009 Notices Pages 15955 15958 REYQ144PAYD REYQ168PAYD REYQ192PAYD REYQ216PYDNR REYQ240PYDNR For Branch Selector unit specifications refer to page 20 Single Module Systems Connection Ratio Connectable Indoor Unit Ratio Model Name REYQ72PATJ REY Q96PATJ REYQ120PATJ Nominal Cooling Capacity Btu h 72 000 96 000 120 000 Ra
21. PTJU RXYQ192PAYD RXYQ72PAYD RXYQ144PAYD RXYQ192PATJ Unit Model Number RXYO72PATJ RXYO108PAYD RXYQ144PATJ RXYQ216PYDNR RXYQ96PAYD RXYQ108PATJ RXYQ168PAYD RXYQ216PTJUR RXYQ96PATJ RXYQ168PATJ RXYQ240PYDNR RXYQ240PTJUR KHRP26M22H KHRP26M22H max 4 branches KHRP26M22H max 4 branches KHRP26M33H max 4 branches KHRP26M33H max 8 branches REGNE Heaget KHRP26M33H max 8 branches KHRP26M72H max 8 branches KHRP26M72H max 8 branches max 8 branches KHRP26M73HU max 8 branches KHRP26A22T KHRP26A33T KHRP26M72TU KHRP26M72TU KHRP26M73TU Outdoor Unit multi piping connection kit BHFP22P100U Increase height difference between indoor PCB RXYQ_PYDN and outdoor unit to 295ft PCB RXYQ_PTJU Name of Options BSVQ36PVJU BSVQ60PVJU BSVQ96PVJU ao Cool Heat Selector KRC19 26A ttf Fixing Box KJB111A 25 Choosing the right controls Unless it is controlled managed and operated in an appropriate manner a high performing system will not be able to provide the energy etficiency or comfort it claims Promoting the systemization of control management not only improves efficiency but also represents a number of possibilities in terms of convenience Daikin s line up of intelligent controls gives 26 the user the ability to address all needs in one package and one supplier Daikin Daikin controls are optimized tor VRV technology and offers highly scalable solutions for all applications and budgets It also allows for lower co
22. ed system during defrost Approximately 30 or more capacity can be e amp ane produced with no hot start required All other VRF systems require the system to switch to cooling then a hot start to preheat the indoor unit before resuming operation Previous Model Indoor fan stops Mioedey lt __ gt _ gt Time Defrost 10 14 min Hot start This causes a disruption to the heating and space No hot start required with VRVIII temperature Airflow down LL Mioede gt Time Continuous heating during oil return When the previous model is in heating mode to perform an oil recovery cycle two hours after initial start up and every eight hours thereafter the system must change to cooling With the improvements to VRVIII outdoor unit and branch selector unit the Change to cooling operation lt o Cc un lt fo 2 us system continues in the heating mode during the full Wray Heating mm on operation oil recovery cycle Daikin is the only VRF manufacturer S EGE continues that is capable of continuous heating during oil return Offers simultaneous cooling and heating operation on the same piping network Heating operation for room not significantly heated by the sun Branch Selector Unit By adding high pressure low pressure gas piping and a branch selector unit sold separately simultaneous heating and cooling operation can be provided b
23. ed thermistors faulty solenoid valves or motor operated valves compressor malfunctions communication errors etc can be diagnosed quickly Automatic Information Storage During unit operation storage of data from the last five minutes occurs automatically In cases of malfunction analysis of data from the last five minutes will be carried out to identity the location of the problem and cause of malfunction Measures to eliminate the cause of malfunction can then be a implemented Ducted Duct free Ventilation VRV Indoor Units Capacity Range Indoor Type MBH 7 5 09 12 18 24 30 36 42 48 54 72 96 Tons 0 6 0 75 1 1 5 2 2 5 3 3 5 4 4 5 6 8 FXTO PAVJU Vertical air handling unit A A horizontal right configuration is possible g g FXMQ_PVJU DC ducted concealed ceiling medium static u F gt a F gt UP y oP ee BP Wee u a gt UP oP Concealed ceiling unit medium static FXMQ_MVJU a gt a gt Slim duct built in concealed ceiling unit 3 x 3 4 way ceiling mounted cassette FXDQ_MVJU FXFQ_MVJU X i k S N ua a a ma gt w a gt 2 x 2 4 way ceiling FXZQ_M 7VJU gt D gt URE amp gt UP Ua UAS gt SP UP gt SP ee ee mounted cassette x FXAQ_MVJU Wall mounted unit A FXHQ_MVJU I Ceiling suspended unit A A A A FXLO MVJU Floor standing unit A A A
24. eration efficiency is improved sharply Did you know Daikin is the only company in the world dedicated to manutacturing heating and High performance low noise new scroll compressor operates at a faster cooling units compressors and Improving the high efficiency compressor to achieve a high EER and COP Reluctance DC scroll compressor Daikin s unique scroll compressor minimizes heat loss and is driven by a high efficiency motor to achieve significant energy savings te Th di has b L High torque and efficiency is attained with the use of Baan A eee oe refrigerant All Daikin systems neodymium magnets Achieves 70 reduction in volume analysis for increased strength and in North America employ The secret to raising energy efficiency utilization of the advantages oil film Powerful magnets ms F control of the high thrust variable speed compressors mechanism and non ozone depletion potential R 410A refrigerant which optimize energy High thrust mechanism conservation By introducing high pressure oil the reactive force from the fixed scroll is added to the internal force thereby reducing thrust losses This results in improved efficiency and lower sound levels M DC motor Ferrite magnet Neodymium magnet Neodymium magnets are much more powerful than the widely used ferrite magnets DAIKIN AC ABSOLUTE COMFORT VRVIII Cooli
25. he problem can be rectified Manual Back Up Single Module If the system is set to emergency inverter compressor operation the standard compressor will operate at the index of the indoor units in thermostat on at a minimum 50 of the connected ratio 10 Ton System il Capacity approx INVERTER Alarm Trouble Stop STANDARD Alarm Operate Trouble 16 Ton System Trouble Stop Stop Trouble No 2 Unit Capacity approx Operate Operate Outdoor Unit A Outdoor Unit B Previous time Priority 1 Priority 2 This time Priority 2 Priority 1 Next time Priority 1 Priority 2 If the system is set to emergency standard compressor operation the inverter compressor can operate even if only one indoor unit with less than 50 index is in thermostat on Back Up Operation Trouble Alarm y Operated by remote controller or field setting again ig Auto or Manual Back Up of Manifolded Systems In case of compressor trouble in a manifolded system it is required to disable the entire module with the malfunction It is not possible to disable only one compressor and leave the other compressor running in that module This is due to oil balancing within the system The emergency mode in a manitolded system can be set to manual or automatic via a field code The automatic mode is achieved by pressing the on off button for four seconds once the compressor
26. i si R 410A 19 8 18 1 R 410A 19 8 19 8 R 410A 20 1 19 8 R 410A 20 14 20 1 Liquid Pipe Main Line in 1 2 Braze 5 8 Braze 5 8 Braze 5 8 Braze 5 8 Braze Suction Gas Pipe Main Line in 1 1 8 Braze 1 1 8 Braze 1 1 8 Braze 1 1 8 Braze 1 3 8 Braze Refrigerant Piping High and Low Pressure Equalization Pipe in 3 4 Braze 3 4 Braze 3 4 Braze 3 4 Braze 3 4 Braze Vertical Pipe Length if unit is below FCU ft 295 295 295 295 295 Vertical Pipe Length if unit is above FCU ft 164 295 with Option 164 295 with Option 164 295 with Option 164 295 with Option 164 295 with Option Actual Pipe Length Equivalent Length ft 540 620 540 620 540 620 540 620 540 620 Total Pipe Length ft 3 280 3 280 a ee Connectable Indoor Unit Ratio 50 130 as Standard Up to 200 is permitted depending on application amp fan coil unit selection Maximum Number of Indoor Units Qty 25 29 33 37 41 Unit Weight Ibs 560 560 560 560 560 560 560 560 560 560 Dimensions H x W x D in 66 1 8 x 36 5 8 x 30 1 8 x 2 Air Flow cfm 6 530 6 530 6 530 6 530 6 530 6 530 7 060 6 530 7 060 7 060 Fan External Static Pressure in W G 0 32 0 32 0 32 0 32 0 32 Fan Motor Output and Quantity kW Qty 0 75x2 O Oax 2 075X 2 OSX 2 Maximum Overcurrent Protection MOP A 40 40 50 40 50 50 50 60 60 60 Minimum Circuit Amps MCA A 36 1 36 1 36 1 36 1 36 1 36 1 41 3 36 1 41 3 41 3 Electrical Minimum Starting C
27. ifreann Nominal Heating Capacity Btu h 81 000 108 000 135 000 Rated Heating Capacity Btu h 77 000 103 000 130 000 Rated Heating Input Power system kW Btu h 6 4 8 9 11 5 Rated Full Load COP system 3 5 3 4 3 3 Power V ph Hz 460 3 60 460 3 60 460 3 60 Sound Pressure Level at 3ft dB A 58 58 60 Refrigerant Type and Quantity Ibs R 410A 22 7 R 410A 23 4 R 410A 23 8 Liquid Pipe Main Line in 3 8 Braze 3 8 Braze 1 2 Braze Suction Gas Pipe Main Line in 3 4 Braze 7 8 Braze 1 1 8 Braze Refrigerant Piping High and Low Pressure Gas Pipe Main line in 5 8 Braze 3 4 Braze 3 4 Braze Vertical Pipe Length if unit is below FCU ft 295 295 295 Vertical Pipe Length if unit is above FCU ft 164 295 with Option 164 295 with Option 164 295 with Option Actual Pipe Length Equivalent Length ft 540 620 540 620 540 620 Total Pipe Length ft 3 280 3 280 3 280 Cae inn Connectable Indoor Unit Ratio 50 130 as Standard Up to 200 is permitted depending on application amp fan coil unit selection Maximum Number of Indoor Units Qty 12 16 20 Unit Weight Ibs Hey ey 732 Dimensions H x W x D in 66 1 8 x 51 3 16 x 30 1 8 66 1 8 x 51 3 16 x 30 1 8 66 1 8 x 51 3 16 x 30 1 8 Air Flow cfm 6 700 7 410 Fan External Static Pressure in W G 0 32 0 32 Fan Motor Output and Ouantity kW Qty 0 35x2 0 35x2 Maximum Overcurrent Protection MOP A 20 25 25 Flectrical Minimum Circuit Amps MCA A 16 20 4 20 5 Minimum Starting Current
28. ital Input Output units IN Native application or feature for this device E Dependent upon capabilities of the third party energy management system Freedom to control the air conditioning system via the Internet from home or any other location with a PC Should a malfunction occur a notification is sent by e mail to a cell phone or PC any e mail address specified by the user This gives administrators the freedom to leave the room building where the controller is located Intelligent intellige Controller Managerfff DCS601C71 IMP 128 256 512 768 1 024 64 groups 128 indoor units connectable 1 024 indoor units 128 groups with DCS601A72 organized in up to 200 control groups Management of Daikin units and ancillary equipment Management of Daikin units and ancillary equipment Touch screen display Operation on one master PC and one sub PC Built in Ethernet port Web enabled optional sub PC option Alarm e mail function Remote monitoring via the Web Alarm e mail function Connect VRV to your BMS via BACnet or LonWorks using Daikin s integrated control system solutions Compatible with BACnet and LonWorks the two leading open network communication protocols the interfaces offered by Daikin provides a seamless connection between VRV and your BMS RL af LonWorks OE LonWorks Network Compatible Interface BACnet Network Compatible Interface Interface for LonWorks networks Interface for Building Management Systems Co
29. mmunication via LON protocol twisted pair wire Communication via BACnet protocol BACnet IP 64 units connectable per interface 256 units connectable per BACnet gateway Unlimited site size with DAM411B51 Quick easy installation Unlimited site size Quick easy installation WARNINGS e Always use a licensed installer or contractor to install this product Do not try to install the product yourself Improper installation can result in water or refrigerant leakage electrical shock fire or explosion e Use only those parts and accessories supplied or specified by Daikin Ask a licensed contractor to install those parts and accessories Use of unauthorized parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage electrical shock fire or explosion e Read the User s Manual carefully before using this product The User s Manual provides important safety instructions and warnings Be sure to follow these instructions and warnings For any inquiries contact your local Daikin sales office In all of us a green heart Intertek 2010 Daikin Industries Limited Daikin Daikin AC Absolute Comfort and its design VRV and REFNET are trademarks pending or registered trademarks of Daikin Industries Limited All rights reserved LonWorks and LON are registered trademarks of Echelon Corporation BACnet is a Data Communication Protocol for Building Automatio
30. n and Control Networks developed under the auspices of the American Society of Heating Refrigerating and Air Conditioning Engineers ASHRAE Organization DAIKIN INDUSTRIES oRGANIZATIo Organization gt DAIKIN INDUSTRIES LTD AIR CONDITIONING MANUFACTURING DIVISION THAILAND LTD Q Scope of Registration inn an S ISO Py s THE DESIGN DEVELOPMENT AND MANUFACTURE Scope a HIS Moin Del tnte re seal elites THE DESIGN DEVELOPMENT ui facilities and subsidiaries in Japan OF COMMERCIAL AIR CONDITIONING HEATING AE E AND MANUFACTURE OF AIR o 58 are certified under the ISO 14001 COOLING REFRIGERATING EQUIPMENT A sey COMMERCIAL HEATING EOUIPMENT RESIDENTIAL CONDITIONERS AND THE we International standard for COMPONENTS INCLUDING an a environmental management COMPRESSORS USED FOR THEM us EC99J2044 AIR CONDITIONING EQUIPMENT HEAT RECLAIM VENTILATION AIR CLEANING EQUIPMENT MARINE TYPE CONTAINER REFRIGERATION UNITS COMPRESSORS AND VALVES J MI 0107 Daikin AC Americas Inc 1645 Wallace Drive Suite 110 Carrollton TX 75006 USA www daikinac com info daikinac com 866 4DAIKIN 972 245 1510 lJ SE 1 0 08 B Dealer Information Daikin s products are subject to continuous improvements Daikin reserves the right to modify product design specifications and information in this brochure without notice and without incurring any obligations
31. ng DB Heating WB z R 122 Extended Operation Range 122 F Advanced Proportional Integral Derivative PID control of the outdoor 110 F a unit enables the VRVIII series to operate at outdoor ambient conditions 104 F uil down to 23 F in cooling mode and down to 4 F in heating mode 92 F A new Low Ambient Cooling feature allows the VRVIII heat recovery 80 F systems to operate as low as 4 F in cooling mode as well 68 F hy M Daikin is the only VRF manufacturer to provide capacity tables up to 56 F 1 122 F for high ambient design applications The cooling is guaranteed 44 F at those temperatures However both efficiency and cooling output will 32 F ae Start dropping over 110 F 20 F i pa Standard operation Ea Extended operation j Standard operation 38 F range cooling range cooling range heating 4 F p 4 4 Long Refrigerant Piping Lengths i Linear piping between condensing unit and furthest located fan coil 540 620 E Ls 7 x unit equivalent o i Total one way piping in the complete piping network Vertical height separation between the condensing unit and the 2 oe fan coil units if outdoor unit is below 164 295 e cool pi v Vertical height separation between fan coil units D i f Linear piping between 1st REFNET and furthest located fan coil unit 2 2 295ft if outdoor unit is above and accessory PCB is installed a ag E t w OL YN og
32. ntity kW Qty 052 0o52 Maximum Overcurrent Protection MOP A 40 45 50 E Minimum Circuit Amps MCA A 36 1 43 8 44 2 Minimum Starting Current MSC A lel 151 131 Compressor Rated Load Amps RLA A 4 8 14 0 8 4 14 0 12704 13 6 Compressor Type Daikin Scroll x 2 Daikin Scroll x 2 Daikin Scroll x 2 Compressor Compressor Set Up 1 INV 1 FIX 1 INV 1 FIX 1 INV 1 FIX Compressor Capacity Control 20 100 14 100 14 100 1 Indoor temp 80 FDB or 67 FWB outdoor temp 95 FDB Equivalent piping length 25 ft 7 5 m level difference 0 ft 2 Indoor temp 70 FDB outdoor temp 47 FDB or 43 FWB Equivalent piping length 25 ft 7 5 m level difference 0 ft 3 The tested system EER and COP values reflect full load efficiency only and are the results from testing to the Alternate Test Method ATM guidelines provided by the U S Department of Energy DOE in the Federal Register Vol 74 No 68 Friday April 8 2009 Notices Pages 15955 15958 For Branch Selector unit specifications refer to page 20 REYQ7 2PATJ REYQ96PATJ REYQ120PATJ 22 Double Module Systems Name REYQ144PATJ REYQ168PATJ REYQ192PATJ REYQ216PTJUR REYQ240PTJUR Mous Combination REM072PATJ x 2 bai REMQ96PATJ x 2 Ba x REMQ120PTJUR x 2 Nominal Cooling Capacity 144 000 168 000 192 000 216 000 240 000 Rated Cooling Capacity 138 000 160
33. o 50 130 as Standard Up to 200 is permitted depending on application amp fan coil unit selection Ratio Maximum Number of Indoor Units Qty 25 29 33 37 41 Unit Weight Ibs 450 450 560 450 560 560 560 560 560 560 Dimensions H x W x D in 66 1 8 x 36 5 8 x 30 1 8 x 2 Air Flow 6 350 6 350 6 530 6 350 6 530 6 530 7 060 6 530 7 060 7 060 Fan External Static Pressure 0 32 0 32 0 32 0 32 0 32 Fan Motor Output and Ouantity 0 75x2 0 75x2 0 75x2 0 75x2 0 75x2 Maximum Overcurrent Protection MOP 40 40 50 40 50 50 60 50 60 60 Minimum Circuit Amps MCA 36 1 36 1 36 1 36 1 36 1 36 1 41 3 36 1 41 3 41 3 Electrical Minimum Starting Current MSC 137 138 154 155 Compressor Rated Load Amps RLA 14 2 14 2 7 8 16 8 14 2 7 8 16 8 x 2 a i 12 2 16 8 x 2 Compressor Type Daikin Scroll x 1 Daikin Scroll x 3 Daikin Scroll x 4 Daikin Scroll x 4 Daikin Scroll x 4 Compressor Compressor Set Up 1 INV x 2 1 INV 1 FIX 11INV 1 INV 1 FIX x2 1 INV 1 FIX x 2 1 INV 1 FIX x 2 Compressor Capacity Control 13 100 9 100 7 100 7 100 6 100 1 Indoor temp 80 FDB or 67 FWB outdoor temp 95 FDB Equivalent piping length 25 ft 7 5 m level difference 0 ft 2 Indoor temp 70 FDB outdoor temp 47 FDB or 43 FWB Equivalent piping length 25 ft 7 5 m level difference 0 ft 3 The tested system EER and COP values reflect full load efficiency only and are the results fr
34. om testing to the Alternate Test Method ATM guidelines provided by the U S Department of Energy DOE in the Federal Register Vol 74 No 68 Friday April 8 2009 Notices Pages 15955 15958 a For Branch Selector unit specifications refer to page 20 REYO144PATJ REYO168PATJ cc a ee ia REYQ192PATJ REYO216PTJUR s REYQ240PTJUR Ea q ao i RA Figure 1 Figure 2 If installed as a single unit When insta Pattern 1 Iled in serial See eee one eee ee ee OO 134 1 l gt 3 8 2 Al E 5 8 gt e gt 3 gt 3 8 Pattenmi2 o a i IE gt 1 318 S718 gt 2 E ae a 2 P oftea eae icra Pattern 1 jet 3 4 gQ 41 i 23 8 s gt 19 5 8 k scal Y 3 AE y Pattern 2 isa 7 8 Ci s PETE 2 Le gt 19 5 8 Pes cl Y 3 2 E E Pattern 3 jet 3 4 2778 1 a h2 Front side Pattern 3 1134 O Ol Q gt 7 7 8 f a534 1 534 Suction side Service eee Se E el 19 5 8 2 Figure 3 n2 space 2 or more or more lt gt lt gt avy Mrs E ot a 5 260 o o Mai
35. ral attributes of a VRV system position it as an alternative to a chiller system The Features of VRV EER Energy efficient all systems incorporate inverter variable speed compressors Many zones individual control up to 41 zones on one piping network Centralized system long piping up to 3 280 ft total Tight temperature control Proportional Integral Derivative Large capacity modular systems combination Quiet operation down to 25dB A indoor High level control BACnet LonWorks Intelligent Manager Intelligent Touch Controller Superior heating performance Absolute Comfort Part Load Performance VRV 10 20 30 40 50 60 70 80 Load 90 100 Example VRV system part load curve i Building s energy demand in hours Annual Why Refrigerant The commonly used methods of heat transfer in air conditioning solutions each exercise different operational characteristics regarding adding or removing heat energy to a conditioned space This diagram represents the energy transfer possible per pound of media due to the performance characteristic of the fluid used The use of refrigerant reduces installation space compared to other heat transfer methods 0 14 watts Ib WATER 2 6 watts Ib 25 watts Ib VAV VWV VRV Why is VRV an efficient alternative The heating and cooling system in a commercial building is used at 70 or less of its maximum capacity tor 75 of the operational
36. respectively Comp A Comp B Capacity Btu h Ambient Temperature F Reduced factory charge The factory refrigerant charge has been reduced for si all outdoor units by up to 34 compared to previous oe VRV models This allows for easier application to E MR satisfy local and national safety standards such as Suu ASHRAE standard 15 w 37 90 37 41 15 00 72 MBH 96 MBH 144 MBH 168 MBH 192 MBH 216 MBH 240 MBH The reduction in the factory charge puts Daikin at up to 10 less factory refrigerant charge than our VRF competitors an excellent advantage to engineers when it comes to satisfying local and national safety standards J Daikin vrvi i Industry Average Heat pump 208 230V used as example Fusible plugs Receiver mm Environmental consciousness plug The fusible plugs used in older systems as the pressure relief device in the liguid receiver have been replaced with pressure relief valves Now instead of releasing the refrigerant to the atmosphere it is relieved to the low pressure side of the system a far more EV environmentally conscious solution The safety valve is activated If ya VT Fluid line sa Lb the pressure exceeds 570psi Pressure relief valves in low pressure side of Fluid line system BPR Intake line High low pressure gas pipe ey BR Environmental consciousness Outdoor unit 1 CC I Outdoorunit2 II Suction gas pipe o rSn A I When only one of
37. ry tool EnergyCalc the graphic below charts an EER curve and the cooling demand of a building over the time period of one year Analysis of the building s annual cooling demand shows the required cooling capacity is below 70 of the maximum design capacity 75 of the time With Daikin building owners save energy by not paying to heat or cool an empty or unused space VRV performance and energy use are highly application dependent and should be obtained from detailed analysis Building s energy demand in hours Annual For example 1 the graphic shows that over the course of one Tull operational year the building s VRV system analyzed operates tor 223 hours at 70 of Its maximum capacity thus being at part load operation Under this specific operational condition the Daikin VRV has an EER of 16 i in this example 9 8 i i i 72 MBH 96 MBH 108 120 MBH 144 MBH 168 MBH 192 MBH 216 MBH 240 MBH un a aaa oaa a aaa aa 30 40 50 60 70 80 EER Full load EER Full load EER Fi Heat Pump pg Heat Recovery DOE Minimum Level Example VRV System Part Load Curve Heating Comparing a VRVIII and its competition at full load in heating the VRVIII 6 Ton heat recovery is 4 more efficient VRVIII has also more capacity in heating during low Daikin ambient operation compared to standard VRF systems At temperatures of 4 FWB VRVIII has more heating capacity than equivalent VRF systems by 16 and 23
38. st alternatives to traditional energy management systems when centralized control is required ERE s it a si i uni BRC1E71 BRC2A71 DCS302C71 DCS301C71 DCS601C71 Intelligent BACnet LonWorks Navigation Simplified Centralized Unified Intelligent Touch Manager Interface Interface Simple individual zone control E A Individual zone control with 7 day programmable scheduling i Multi zone control without scheduling functions E Basic central point on off control of all air handling units H Advanced multi zone control of small to medium size projects C Advanced multi zone control of large commercial projects E m B Advanced multi zone control with scheduling logic and calender C Automatic cooling heating changeover for heat pump systems C C Single input batch shutdown of all connected air handlers L1 cj a W Web browser control and monitoring via Intranet and Internet C m m Bi E mail notification of system alarms and eguipment malfunctions C E nu Multiple tenant power billing for shared condenser applications E E Temperature set point range restrictions im E a mu Graphical user interface based upon a PC platform F l Start stop control of ancillary building systems if ia E ia Daikin VRV integration with BACnet based automation systems Daikin VRV integration with LonWorks based automation systems w 1 Requires one or more DEC102A51 US2 Dig
39. ted Cooling Capacity Btu h 70 000 92 000 114 000 Rated Cooling Input Power system kW 5 56 7 93 10 36 Rated Full Load EER system 12 6 11 6 11 0 E TERE Nominal Heating Capacity Btu h 81 000 108 000 135 000 Rated Heating Capacity Btu h 77 000 103 000 130 000 Rated Heating Input Power system kW Btu h 6 4 8 9 115 Rated Full Load COP system 3 5 3 4 3 3 Power V ph Hz 208 230 3 60 208 230 3 60 208 230 3 60 Sound Pressure Level at 3ft dB A 58 58 60 Refrigerant Type and Quantity Ibs R 410A 22 7 R 410A 23 4 R 410A 23 8 Liquid Pipe Main Line in 3 8 Braze 3 8 Braze 1 2 Braze Suction Gas Pipe Main Line in 3 4 Braze 7 8 Braze 1 1 8 Braze Refrigerant Piping High and Low Pressure Gas Pipe Main Line in 5 8 Braze 3 4 Braze 3 4 Braze Vertical Pipe Length if unit is below FCU ft 295 295 295 Vertical Pipe Length if unit is above FCU ft 164 295 with Option 164 295 with Option 164 295 with Option Actual Pipe Length Equivalent Length ft 540 620 540 620 540 620 Total Pipe Length ft 3 280 3 280 3 280 50 130 as Standard Up to 200 is permitted depending on application amp fan coil unit selection Maximum Number of Indoor Units Qty 12 16 20 in Weight Ibs 730 730 Dimensions H x W x D in 66 1 8 x 51 3 16 x 30 1 8 66 1 8 x 51 3 16 x 30 1 8 66 1 8 x 51 3 16 x 30 1 8 Air Flow cfm 6 700 7 410 Fan External Static Pressure in W G 0732 0 32 Fan Motor Output and Qua
40. time VRV offers ease of design and installation Chilled water Complicated System central plant layout with boiler Cooling Tower Top Floor Building Floors And also EXP Tank Machine Valves Room Header Chiller 53 FSV 3ST TII Simple System z JJ M Layout Top Floor Condensing Unit Refrigerant Piping Building Eas mm Floors TA T OOo Fan Coil Units Machine Not needed Room VRVIII opens up opportunities in larger more complex buildings Daikin is using the latest and most revolutionary technologies in the development of the VRVIII system for large sized buildings The system offers greater energy savings easier installation longer actual and total piping length and more Heat exchanger The new heat exchanger contributes to a high EER and COP because of an increase from 7 to 10 of the effective length as well as an optimized e Pass heat exchanger DC fan motor e Across entire range of models from 6 to 20 Ton e Efficiency improvement by approximately 40 especially at low speed DC fan motor DC motor efficiency structure comparison with a conventional AC motor 100 JRF III DC motor Efficiency 200 300 400 500 600 700 800 900 1000 Motor speed rpm j al a En alll Smooth sine wave DC Inverter By adoption of the Sine Wave Inverter which smoothes the rotation of the motor op
41. tures to meet practically any challenge Completely re engineered to realize opportunities for VRV in taller larger buildings it utilizes the latest advances in refrigeration and air conditioning technology Available up to 20 Ton in one system 208 230V 60H7 3ph or It is widely used worldwide in applications such as 460V 60HZ 3ph Health care Heat pump heating and cooling and heat recovery Hotels and conference facilities simultaneous heating and cooling across multiple zones Offices systems available Residential multi family Individual zone control Restaurants Can operate up to 41 indoor fan coil units Retail stores Auto charging function Schools Continuous heating during defrost operation a te Longest pipe lengths in product class Advanced zoning capabilities Excellent energy efficiency especially at part load conditions Daikin s optimized scroll compressor designed tor R 410A provides a quiet reliable energy efficient operation Anticorrosion treatment standard on exterior metal parts and heat exchanger i Fully compatible with the complete Daikin control suite me ae anes a ars re gaan ey including Intelligent Touch Controller Intelligent Manager Ill available simultaneously across multiple zones and LonWorks and BACnet gateways a Ee VRV is a commercially applied heating and cooling system that distributes refrigerant rather than water to multiple fan coil units serving the conditioned spaces The natu
42. urrent MSC A 137 137 138 154 155 Compressor Rated Load Amps RLA A 14 2 x2 7 8 16 8 14 2 N ae 12 2 16 8 x 2 Compressor Type Daikin Scroll x 4 Daikin Scroll x 4 Daikin Scroll x 4 Daikin Scroll x 4 Daikin Scroll x 4 Compressor Compressor Set Up 1 INV 1FIX x2 1 INV 1 FIX x2 1 INV 1 FIX x 2 1 INV 1 FIX x 2 1 INV 1 FIX x 2 Compressor Capacity Control 13 100 9 100 7 100 7 100 6 100 1 Indoor temp 80 FDB or 67 FWB outdoor temp 95 FDB Equivalent piping length 25 ft 7 5 m level difference 0 ft 2 Indoor temp 70 FDB outdoor temp 47 FDB or 43 FWB Equivalent piping length 25 ft 7 5 m level difference 0 ft 3 The tested system EER and COP values reflect full load efficiency only and are the results from testing to the Alternate Test Method ATM guidelines provided by the U S Department of Energy DOE in the Federal Register Vol 74 No 68 Friday April 8 2009 Notices Pages 15955 15958 ig er RXYQ144PAT RXYO168PATJ C i RXYO192PATJ RXYO216PTJUR RXYO240PTJUR Single Module Systems Model Name REYQ72PAYD REYQ96PAYD REYQ120PAYD Nominal Cooling Capacity Btu h 72 000 96 000 120 000 Rated Cooling Capacity Btu h 70 000 92 000 114 000 Rated Cooling Input Power system kW 5 56 7 93 10 36 Rated Full Load EER system 12 6 11 6 11 0 a
43. ve calculate h1 and h2 shown in the figure below and add h2 2 to the service space of front side and h1 2 to the service space of suction side An inverter unit may cause electronic noise generated trom AM broadcasting Examine where to install the main unit and electric wires keeping proper distances away from stereo equipment personal computers etc Particularly for locations with weak reception ensure there is a distance of at least 10 ft for indoor remote controllers place power wiring and transmission wiring in conduits and ground the conduits Refer to figure 3 1 Indoor unit 2 Branch switch overcurrent breaker 3 Remote controller 4 COOV HEAT selector 5 Personal computer or radio REYO144PAYD REYO96PAYD REYO144PATJ REYO216PYNDR REYQ72PAYD REYQ96PATJ REYQ168PAYD REYQ216PTJUR Entetepe ltt REYQ72PAT REYQ120PAYD REYQ168PAT REYQ240PYNDR REYQ120PATJ REYQ192PAYD REYQ240PTJUR REYQ192PATJ KHRP25M33H KHRP25M33H max 8 branches KHRP25M33H max 8 branches KHRP25M72H REFNET Header max 8 branches KHRP25M72H max 8 branches max 8 branches KHRP25M73HU max 8 branches KHRP25A22T KHRP25A33T KHRP25M72TU KHRP25M72TU KHRP25M73TU Outdoor Unit multi piping connection kit BHFP26P90U BSVQ36PVJU Branch Selector box for Heat Recovery BSVQ60PVJU BSVQ96PVJU Increase height difference between indoor PCB REYQ PYDN and outdoor unit to 295ft PCB REYQ
44. x 4 Compressor Set Up 1 INV 1FIX x2 1 INV 1 FIX x 2 1 INV 1 FIX x 2 1 INV 1 FIX x 2 1 INV 1 FIX x 2 Compressor Capacity Control 13 100 9 100 7 100 7 100 6 100 1 Indoor temp 80 FDB or 67 FWB outdoor temp 95 FDB Equivalent piping length 25 ft 7 5 m level difference 0 ft 2 Indoor temp 70 FDB outdoor temp 47 FDB or 43 FWB Equivalent piping length 25 ft 7 5 m level difference 0 ft 3 The tested system EER and COP values reflect full load efficiency only and are the results from testing to the Alternate Test Method ATM guidelines provided by the U S Department of Energy DOE in the Federal Register Vol 74 No 68 Friday April 8 2009 Notices Pages 15955 15958 RXYQ144PAYD RXYQ168PAYD RXYQ192PAYD RXYQ216PYDNR RXYQ240PYDNR r SS EE eee Single Module Systems Model Name RXYQ72PATJ RXYQ96PATJ RXYQ108PATJ Nominal Cooling Capacity Btu h 72 000 96 000 108 000 Rated Cooling Capacity Btu h 70 000 92 000 104 000 Rated Cooling Input Power system kW 5 74 8 29 9 45 Rated Full Load EER system 12 2 11 1 11 0 TE ER Nominal Heating Capacity Btu h 81 000 108 000 122 000 Rated Heating Capacity Btu h 77 000 103 000 116 000 Rated Heating Input Power system kW Btu h 6 6 9 1 10 3 Rated Full Load COP system 3 4 E E Power V ph Hz 208 230 3 60 208 230 3 60 208 230 3
45. y a single system pa Cooling operation for rooms SS aly heated by the sun i The example below shows two 6 Ton heat pump systems one operating in full cooling 6 Tons and one operating in full heating 6 Tons the power inputs were 5 74kW and 6 83kW respectively giving a total of 12 57kW When looking at the same example with a heat recovery system with 50 of the capacity operating in full cooling 6 Tons and 50 operating in full heating 6 Tons the power input for the system can be as low as 5 31kW this would mean about half reduction in power input Indoor Temperature 67 F WB cooling Heat Pump 70 F DB heating Outdoor Temperature 95 F WB cooling asa es 47 F DB heating Power Input Heating 6 83kW Cooling 5 74kW 22 519 Btu T Simultaneous Approximately cooling and heating 50 5 31kW Reduction Cooling Cooling Heating Heating Heat Recovery SS gai lea Se es el pe ee os ile ele oi l TIT TT i Power Input Cooling Cooling Heating Heating The new branch selector unit BSVQ_P has improved the cooling heating changeover oil recovery cycle and sound level by utilizing expansion valves in place of the 3 way valve and solenoid subcooling valve found in the previous model In the new branch selector unit there is a main and sub expansion valve for the high low pressure gas pipe the _of SOLENOID VALVE suction gas pipe and one for the subcooling circuit

Download Pdf Manuals

image

Related Search

Related Contents

TRAMPA PARA CUCARACHAS FUMIGAX ECOLÓGICA  取扱説明書ダウンロード  Voxtel R100/R110    User Manual - Canadian Appliance Source  DeLOCK SATA 100cm left/up metal yellow  User Manual User Manual  Philips 40PFL4706 46" Full HD Wi-Fi  Manuel d`utilisation  FIN 361 - College of Business  

Copyright © All rights reserved.
Failed to retrieve file