image

Contents

1. charge the battery for four hours during initial use A Connect the Loads Connect the loads to the output hardwire connector o Apply the Electrical Shock Warning Label Apply the electrical shock warning label to the panel in a way that is clearly visible to the user Risk of electrical shock hazardous live parts inside this panel may be energized from the battery supply even when the input ac power is disconnected 6 0 Operating Instructions 1 Output Connector The output connector will provide protection from surges and power failures to the critical loads 2 Switch ON Green Mode Enabled After connecting the UPS to the utility power press the ON button until you hear the first beep then release the button immediately The Green Mode is enabled i e if a load less than forty watts or no load is connected and the UPS operates in the Backup Mode The UPS will enter into the Green Mode status after three minutes of backup time the green light will flash every three to five seconds and after a short period of time and the unit will enter a power save status by shutting down to prevent deep discharge of the battery To reactivate the unit power the unit OFF then ON again or reapply utility power 3 Switch ON Green Mode Disabled After connecting the UPS to the utility power press the ON button and keep pressing it until you hear two short beeps Bi Bip then release the button immediately The Gree
2. 2 Low Battery rapid beeping In ON Battery Mode when the battery energy runs low the UPS beeps rapidly until the UPS shuts down from battery exhaustion or returns to Ac Input Normal operation 3 Overload continuous alarm When the UPS is overloaded the connected loads exceed the maximum rated capacity the UPS sounds a continuous alarm and LED to warn of an overload condition Reduce the load to eliminate the overload Clearwater Tech Phone 800 894 0412 Fax 208 368 0415 Web www clrwtr com Email info clrwtr com 8 0 PIN Out Configuration for DB9 Connector Female Connector PIN No RS 232 Signal Open Collector Signal rem A GND GND E me mm CE f o DTR Data terminal ready RTS Request to send RD Transmitted data GND Signal Ground TX Received data When a remote shutdown signal is applied for one second the UPS will shut down in three minutes 9 0 Battery Backup Times i so svn SDU5005__ SDUG50 SDU 8505 se ss lb mw cv ss Pm RE Clearwater Tech Phone 800 894 0412 Fax 208 368 0415 Web www clrwtr com Email info clrwtr com 10 0 Troubleshooting Probable Cause Reguired Action UPS is OFF or the ON OFF Test button Press the ON OFF Test button for was not pushed for 14 seconds more than 2 seconds Recharge the UPS for at least 4 hours Battery voltage is less than 10 V If the unit still does not start check the UPS is not
3. 3 FCC Part 15 Subpart B Class A For Conditions of Acceptability in accordance with UL 508A see 13 0 Conditions for Safe Use of SDU 500 amp 850 Clearwater Tech Phone 800 894 0412 Fax 208 368 0415 Web www clrwtr com Email info clrwtr com 13 0 Conditions for Safe Use of SDU 500 amp 850 NOTE Applicable for U S only Considerations shall be given to the following 1 10 The eguipment shall be installed in compliance with the enclosure mounting spacing casualty and segregation reguirements of the ultimate application The eguipment has been judged on the basis of the reguired spacings for use in Overvoltage Category lll and Pollution Degree 3 and in the Second Edition of the Standard for Uniterruptible Power Supply Eguipment UL 1778 par 23 and table 23 1 which would cover the component itself if submitted for unrestricted listing The suitability of grounding connection shall be determined in the end use product The eguipment is provided with means for permanent mounting the suit ability of assembly shall be determined in the end use product Equipment is considered acceptable for use in a maximum ambient of 50 C The eguipment inside live parts are energized from the battery supply even when the input ac power is disconnected For CNR investigation total harmonic distortion of 44 8 and maximum single harmonic of 33 1 The equipment was investigated under 20 amperes branch
4. ON LED will not light input fuse Other failure Call SolaHD Technical Support Load is less than 20 W in Backup a Normal condition Mode Loose ac input power connection Tighten the ac power connection Circuit breaker trips Reset the breaker UPS is always in Backup Mode Line voltage too high too low or blackout Other failure Call SolaHD Technical Support Battery is not fully charged Recharge the UPS for at least 4 hours Backup time is too short Other failure Call SolaHD Technical Support Continuous beep RED cyerinad Overload condition Remove the overload indication x Recharge the UPS for at least 8 hours Red LED is flashing Battery failure Perform UPS self test C AUTION Do not attempt to open the UPS or replace the battery Call SolaHD Technical Support for further instructions 11 0 Storage 11 1 Storage Conditions Store the UPS covered and upright in a cool dry location with its battery fully charged Before storing charge the UPS for at least four hours Remove any accessories in the accessory slot and disconnect any cables connected to the computer interface port to avoid unnecessary draining of the battery 11 2 Extended Storage During extended storage in environments where the ambient temperature is 15 to 30 C 5 to 86 F charge the UPS battery every six months During extended storage in environments where the ambient temperature is 30 to 45 C 86 to 113 F charge th
5. 0 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 i 9 V Output Output terminal providing 12 V power source to the optional relay card 10 Remote RS232 communication port DB 9 connector 11 Tel Surge Protection Data line surge protection for phones UL497A 4 3 What s Included The SDU UPS is shipped with the following items User manual UPSMON software CD NOTE Monitoring diagnostic software is included on the UPSMON CD The software is compatible with Windows NT and Windows 2000 including XP operating systems UPSMON DB 9 serial cable RJ 11 cord Electrical shock warning label 4 4 Accessories e UPSMON USB RS232 to USB adapter cable e RELAYCARD SDU Dry contact relay box SDU PMBRK Mounting brackets to secure the UPS to the wall back of the panel or enclosure Clearwater Tech Phone 800 894 0412 Fax 208 368 0415 Web www clrwtr com Email info clrwtr com 5 0 Installation Instructions 1 Placement Install the UPS in a protected area with adeguate airflow and free of excessive dust Do not operate the UPS outdoors 2 Connect to Utility To power up the UPS connect the ac input connector to the utility power 3 Charge the Battery The UPS charges its battery whenever it is connected to utility power For best results
6. SOLAND Uninterruptible Power Systems SDU Series 500 850 500 5 850 5 Instruction Manual Clearwater Tech Phone 800 894 0412 Fax 208 368 0415 Web www clrwtr com Email info clrwtr com While every precaution has been taken to ensure accuracy and completeness in this manual SolaHD assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions 2008 SolaHD All rights reserved throughout the world Specifications are subject to change without notice SolaHD name and logo are registered trademarks of EGS Electrical Group LLC All names referred to are trademarks or registered trademarks of their respective owners Aungue se han tomado todas las precauciones para asegurar la exactitud y acuciosidad de este manual SolaHD no asume responsabilidad alguna y rechaza toda responsabilidad por da os que pudieran resultar debido al uso de esta informaci n o por cualquier error u omisi n 2008 SolaHD Todos los derechos reservados en el mundo entero Las especificaciones pueden cambiar sin previo aviso El nombre y el logotipo de SolaHD son marcas registradas de EGS Electrical Group LLC Todos los nombre mencionados son marcas comerciales o registradas de sus respectivos titulares Bien que toutes les pr cautions aient t prises afin d assurer que les renseignements du pr sent manuel sont complets et exacts Sola Hevi Duty n assume aucune r
7. Screw Terminals see table below 6 IP20 rated Output Screw Terminals see table below C CET EEE Insulation Withstands Volts Ac 2000 V min PCB Hole Diameter 1 8 mm wire strip length 8 mm 10 24 AWG Tn 7 Input Circuit Breaker Protection from ac overload and short circuit 8 Remote ON OFF The remote switch provides the same functions as the front panel switch including ON OFF Test functions with Green Mode enabled or disabled Clearwater Tech Phone 800 894 0412 Fax 208 368 0415 Web www clrwtr com Email info clrwtr com 4 0 System Description continued 4 2 Bottom Panel Md CE e oo0900000000000 o0000000000000 oo000000000000 o0000000000000 o0000000000000 00000000000000 00000000000000 00000000000000 00000000000000 00000000000000 00000000000000 00000000000000 00000000000000 DS pesssssssssecs o 2200000000099 O P229099c000005 IO po999999999999 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 o000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 0000000000000000 000000000000000
8. allation If this eguipment does cause harmful interference to radio or television reception which can be determined by turning the eguipment OFF and ON the user is encour aged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the UPS and the receiver Connect the UPS into a circuit different from that which the receiver is connected Consult the dealer or an experienced radio TV technician for help Clearwater Tech Phone 800 894 0412 Fax 208 368 0415 Web www clrwtr com Email info clrwtr com 4 0 System Description 4 1 Front Panel Industrial UPS O Oo 00 e BRO 1 Power ON OFF Test Button Press the button for more than one second to turn the UPS ON Press the button for less than one second to activate the self testing Press for more than five seconds to turn OFF 2 Battery Warning Overload Indicator Red LED The LED flashes when the battery needs to be recharged and tested The LED will illuminate when the unit is subjected to an overload condition If the unit shuts down due to over load the LED and alarm will continue for two minutes 3 ON Battery Indicator Yellow LED The LED illuminates when the UPS is supplying battery power to the loads 4 Ac Input Normal Indicator Green LED The LED illuminates when the line input voltage is normal 5 IP20 rated Input
9. arranty Information 14 1 Product Registration To register your product for updates and information on service and support e Visit the Technical Support section of our Web site Click on the Product Registration link and fill in the form This will register your product with SolaHD 14 2 Warranty Information Please see Terms and Conditions of Sale Clearwater Tech Phone 800 894 0412 Fax 208 368 0415 Web www clrwtr com Email info clrwtr com
10. circuit in accor dance with the National Electrical Code ANSI NFPA 70 to reduce the risk of fire connect only to a circuit provided with 20 amperes maximum branch circuit over current protection Use No 18 AWG 90 C copper wire and 9 Ib in Torque force when connecting to terminal block Polarity Identification in UPS unit for filed wiring terminals Provided with label adjacent to the unit supply connections See below for details Clearwater Tech Phone 800 894 0412 Fax 208 368 0415 Web www clrwtr com Email info clrwtr com 11 The following tests were additionally conducted at specified conditions as noted below in accordance with the Standard for Industrial Control Eguip ment UL 508A 17th Edition Temperature Test Models SDU 850 and SDU 500 were mounted in an enclo sure 150 of the dimensions of the device overall 420 by 180 by 160 mm in accordance with par 42 6 of UL 508A The suitability usage of industrial control eguipment shall be considered in end application Breakdown of Components Test Model SDU 850 had been conducted through a 30 ampere non time delay fuse in accordance with par 57 5 of UL 508A 12 The products Models SDU 850 and SDU 500 were evaluated based on Pollution Degree 3 and Overvoltage Category lll criteria and a minimum end use ambient of 40 C so that these devices do not have to be derated when installed within an industrial control panel 14 0 Product Registration amp W
11. clrwtr com 3 0 Introduction Congratulations on your choice of the SDU Uninterruptible Power System UPS The SDU is a compact Off Line DIN rail mountable UPS which provides condi tioned power to sensitive electronic equipment It supplies connected equipment with stepped approximation to sinewave power to simulate the power generated by the utility The SDU is a powerful microprocessor controlled UPS Input voltage range is 80 to 110 ideal protection for the critical connected loads Battery charging occurs automatically when ac power is applied no need to switch ON the UPS When power fails the UPS can be automatically turned OFF as long as the connected loads are not operating to save the baitery energy The SDU also includes an automatic self test feature to test the UPS function and battery If the battery is no longer useful the unit will sound an alarm and an LED indicator will illuminate NOTE This eguipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in an industrial installation This eguipment uses generates and can radiate radio freguency energy and if not installed and used in accordance with the instruc tions may cause harmful interference with radio communications However there is no guarantee that interference will not occur in a particular inst
12. e Operate the UPS only from a properly grounded earthed ac supply To reduce the risk of electric shock do not remove the cover as it has no user serviceable parts inside Some components are live even when ac power is disconnected For service contact a gualified technician Although your UPS has been designed and manufactured to assure personal safety improper use can result in electrical shock or fire To ensure safety please observe the following rules Turn OFF UPS and disconnect the ac supply before cleaning Do not use liguid or aerosol cleaners A dry cloth is recommended to remove dust from the surface of your UPS Do not install or operate the UPS in or near water Do not place the UPS on an unstable cart stand or table Do not place the UPS under direct sunlight or close to heat emitting sources To allow proper ventilation of the UPS do not block or cover the top and bottom sides of the unit Never block or insert any objects into the ventilation holes or other openings of the UPS Keep all vents free of dust accumulation that could restrict airflow Clearwater Tech Phone 800 894 0412 Fax 208 368 0415 Web www clrwtr com Email info clrwtr com Follow all warnings and instructions marked on the UPS Do not attempt to service the UPS as it has no user serviceable parts inside Refer all repairs to gualified service personnel Do not dispose of batteries in a fire they may explod
13. e Do not open or damage the battery Released electrolyte is harmful to the skin and eyes and may be toxic If your UPS demonstrates any of the following conditions turn OFF the UPS disconnect the ac supply and contact your local distributor SolaHD representa tive or SolaHD Technical Support at 1 800 377 4384 Liguid has been spilled on the UPS The circuit breaker opens freguently The UPS does not operate in accordance with the user manual 1 2 Conditions of Use Your UPS provides conditioned power to connected eguipment The maximum load must not exceed that shown on UPS rating label If uncertain contact your distributor or SolaHD Technical Support at 1 800 377 4384 U S Only For Conditions of Acceptability in accordance with UL 508A see 13 0 Conditions for Safe Use of SDU 500 amp 850 2 0 Warnings Defined A DANGER Danger Indicates an imminently hazardous situation that if not avoided will result in death or serious injury This signal word is limited to the most extreme situations AWARNING Warning Indicates a potentially hazardous situation that if not avoided could result in death or serious injury A CAUTION Caution Indicates a potentially hazardous situation that if not avoided may result in minor or moderate injury It may also be used to alert against unsafe practices Clearwater Tech Phone 800 894 0412 Fax 208 368 0415 Web www clrwtr com Email info
14. e UPS battery every three months Clearwater Tech Phone 800 894 0412 Fax 208 368 0415 Web www clrwtr com Email info clrwtr com 12 0 Specifications Catalog Number Description sous sDuas souss spuesos INPUT 50 or 60 Hz 10 auto sensing OUTPUT Voltage on battery Simulated sine wave Frequency on battery 50 or 60 Hz 0 5 auto sensing Transfer Time lt 4 milliseconds PROTECTION Circuit breaker for overload and short circuit protection Overload Protection UPS automatic shutdown if overload exceeds 105 of nominal at 20 s 120 at 10 s 130 at 3 s UPS output cut off immediately BATTERY Type Sealed maintenance free lead acid batteries Typical Recharge Time to 90 of full capacity Backup Time at full load Osm om m ALARM 8 hours ON Battery Slow beeping every 4 seconds Battery Low Rapid beeping every second Overload Continuous beeping sound ENVIRONMENT Ambient Operation 0 95 humidity non condensing 50 C up to 10 000 ft 3000 m Audible Noise lt 40 dBA 1 m from surface WEIGHT amp DIMENSIONS Net Weight Ib kg 11 4 5 0 11 5 5 2 11 9 5 4 HxWxD in mm 4 88 x 11 1 x 4 55 124 x 281 x 116 SAFETY APPROVALS UL 1778 C UL Recognized for industrial CE Marked LVD EN62040 1 1 EMC applications in accordance with UL 508A EN50091 2 EN61000 3 2 EN61000 3 3 without derating Overvoltage Category 3 IEC801 2 IEC801 3 IEC801 4 IEC1000 2 2 Pollution Degree
15. esponsabilit et d cline toute responsabilit pour des dommages d coulant de l utilisation de cette information ou de toute erreur ou omission 2008 SolaHD Tous droits r serv s mondialement Les caract ristiques techniques sont sujettes modification sans pr avis Le nom et le logo SolaHD sont des marques d pos es de EGS Electrical Group LLC Tous les noms voqu s sont des marques de commerce ou des marques d pos es de leurs propri taires respectifs Clearwater Tech Phone 800 894 0412 Fax 208 368 0415 Web www clrwtr com Email info clrwtr com 1 0 Important Safety Instructions This manual contains important safety instructions that should be followed during the installation of the Uninterruptible Power System UPS Please read all safety installation and operating instructions before attempting to install or operate the UPS Please adhere to all warnings on the unit and in this manual during installa tion and operation The UPS is designed for Industrial or Commercial use and can be installed and operated by individuals without previous training 1 1 Safety Precautions Warnings To prevent the risk of fire or electric shock install the UPS in a temperature and humidity controlled ventilated enclosure free of conductive contaminants moisture flammable liguids gases and corrosive substances AWARNING PbH2SO4 Enclosure has to be properly ventilated if productis installed insid
16. n Mode is now disabled Any kind of load whether smaller than forty watts or larger will not affect the normal operation of the UPS under Ac or Battery Mode 4 Switch OFF To switch OFF the UPS press and hold the Power ON OFF Test button until the Ac Power Normal LED or ON Battery LED turns OFF Clearwater Tech Phone 800 894 0412 Fax 208 368 0415 Web www clrwtr com Email info clrwtr com 6 0 Operating Instructions continued 5 Self test Use the self test to verify both the operation of the UPS and the condition of the battery In normal utility power push the Power ON OFF Test button for less than one second the UPS will perform a self test During the self test the UPS runs in Backup Mode If the UPS passes the self test it returns to Ac Input Normal operation 6 Remote ON OFF To ensure the remote ON OFF function connect a remote push button switch in series with 5 30 V dc voltage source to the ON OFF terminal as shown below L a Remote Push Button Switch 5 30 Vdc The remote switch provides the same functions as the front panel switch including ON OFF Test functions with Green Mode enabled or disabled If the Green Mode is not needed a remote toggle switch can be used 7 0 Battery Overload Alarms 1 ON Battery slow beeping When in ON Battery Mode the yellow LED illumi nates and the UPS sounds an audible alarm The alarm stops when the UPS returns to Ac Input Normal operation

Download Pdf Manuals

image

Related Search

Related Contents

  Infotainment Radio Bolero Manual de instrucciones  N°231 - Cinémas Gaumont Pathé    4 installation  MC Crypt Plattenspieler DJ-2600 Direct MC Crypt Record Player DJ  NEC EA294WMi-BK Mechanical Drawings : Free Download, Borrow, and Streaming : Internet Archive  Sun Fire E6900/E4900 Systems Site Planning Guide  取扱説明書  Avaya 3616 For SRP User's Manual  