Home
        TC5-2N6FA
         Contents
1.    Replace the fuse     Make sure the cable is firmly  plugged in with the tabs in place     Correct the wiring  In particular   make sure two different lines  are connected to each motor   line L1 modulated by the  controller should be combined  with another line  N for 115V or L2  for 230V  to activate the motor or  heating unit  Also  make sure the  Stage COMMON is supplied by  line L1     Verify if the motor or heating unit  is defective by connecting it to  an alternate power supply   Replace the motor or heating  unit If it still is not operating     Listen to see if there is a clicking  sound when the Stage s pilot  light turns on  If there is no  clicking sound  contact your  distributor to repair the control   ler            5 2  6        TECHNICAL SPECIFICATIONS    TC5 2N6FA Supply     115 230          1896    896   50 60Hz  L1 same phases as Stage 1  and 2  overload and  overvoltage protection fuse  F12 1A fast blow     Stage 1  Variable output  115 VAC  1 2         230 VAC  1 5 HP   Mot 10A   50 60 Hz  fuse F1 15A slow blow     Stage 2  Variable output  115 VAC  1 2         230 VAC  1 5 HP   Mot 10A   50 60 Hz  fuse F2 15A slow blow     Stage 3  ON OFF output  115   230 VAC  30VDC  50   60 Hz  Mot 6A  10A  Res   heating or cooling  fuse F7 15A slow blow     Stage 4  ON OFF output  115   230 VAC  30VDC  50   60 Hz  Mot 6A  10A  Res   heating or cooling  fuse F8 15A slow blow     Curtain 1 output  OPEN CLOSE output  115 230 VAC  60 Hz  30VDC  5A  winch output  fuse 
2.    TC5 2N6FA       The figure below explains the operation of zoned heaters     HEATING HEATER   OUTPUT TURNS ON  HEATER  TURNS OFF    ON    OFF       HEATER HEATER T   DIFFERENTIAL OFFSET  SET POINT    If the room temperature rises   at Set Point   Heater Offset 1  Probes 1 2   Heater 1 turns off     at Set Point   Heater Offset 2  Probes 3 4   Heater 2 turns off   If the room temperature falls   at Set Point   Heater Offset 1   Differential 1  Probes 1 2   Heater 1    turns on     at Set Point   Heater Offset 2   Differential 2  Probe 3 4   Heater 2  turns on     50 TC5 2N6FA rev 01        5 2  6         Adjusting Heater Offsets    The heater offset can provide substantial energy savings if correctly  adjusted according to the outside temperature  This offset repre   sents the number of degrees below the set point at which the heat   ing units turn off  see diagram above   The offset of heaters 1 and 2  can be adjusted from  10  F to 20 0  F   5 6  C to 11 1 C   If the off   set is negative  the heating units will turn off at temperatures above  the set point  If cascading heating is used  only Heater 1 offset is  used       Set selection knob to HEATER 1 OFFSET DIFFERENTIAL or  HEATER 2 OFFSET DIFFERENTIAL The current heating off   set is displayed  alternating with the letters   OFSEt      e  Usethe adjustment knob to adjust the offset to the desired  value     E Adjusting Heater Differentials    The heating differential is the temperature difference between the  moment t
3.   De icing Cycle Time 1 minute 1 to 720 minutes  De icing Time 15 seconds 15 to 900 seconds  Motor curve 4 Curve 1 10      0 5 to 20 F  Stages 3  4 Differential 2 F  1 1  C   0 3 to 11 190   Dead Band 2    1 1 C  0 5 to 20  F  0 3 to 11 1  C   Time On 15 seconds 10 to 900 seconds  Curtains Time Off 90 seconds 0 to 900 seconds  n    40 to 99 9  F  Outside Set Point 70 F  21 C   40 to 37 7 C   0 5 to 20  F  Offset 8 0   4 4  C   0 3 to 11 190      0 to 900 seconds                GD seconds in increments of 15 sec   Time Off 10 minutes 0 to 60 minutes  1 0 5 to 20  F  Mist Offset 14  F  7 8 C   0 3 to 11 1  C            0 5 to 20  F  Differential 2      1 1       0 3 to 11 190      i 0 to 99   Mist Shut off humidity level 95   100    not used           0 5 to 20  F  Heater Differential 2 F  1 1  C   0 3 to 11 190    10 to 20  F  Heater Heater Offset 2 0 F  1 1    87 to 11 17   Max  Temperature Diff  0 5 to 20  F  Between Zones      eG   0 3 to 11 1 C      2 0 5 to 40  F  High Offset 12 0  F 6 7  C   0 3 to 22 25            0 5 to 40  F  Low Offset 10 0  F 5 6   C   0 3 to 22 2  C   NOTES  i  Initial parameter settings are not saved once they are modified   ii  If the power supply is cut off  the last parameter settings recorded until the power is restored     60     5 2  6     rev 01        5 2  6        MEMORY CARD    The memory card is used to create a backup copy of your  controller s configuration  The card is also useful to transfer the  configuration of one controller to a
4.   The cur   rent minimum speed flashes on the display     e Press the push button to display the points of the ramp cur   rently defined until the word ON appears  twenty one clicks      e Turnthe adjustment knob counterclockwise by one notch   The word OFF flashes on the display  The Minimum Speed  Ramp Pilot Light turns off  indicating that the minimum speed  ramp is now deactivated         5 2  6            01 33        5 2  6        Differential Settings    Refer to the diagram at the beginning of the ventilation chapter for  further information on the follow ing parameters     m Adjusting the Bandwidth of Stage 1    The Stage 1 bandwidth is the temperature interval over which the  speed of variable stage 1 fans increases or decreases proportionally  to the temperature  The bandwidth can be adjusted betw een 0 5  F  and 20 0  F  0 3  C and 11 1           e Set the function to STAGE 1     BANDWIDTH TIMER  The  current bandw idth of stage 1 flashes on the display  alter   nating with the letters  BAnd      e Use the adjustment knob to adjust the bandw idth to the de   sired value     ES Adjusting the Offset of Stage 2    The offset of stage 2 is the temperature difference from the end of  stage 1  set point   bandwidth of stage 1  at which stage 2 fans  start running at their minimum speed  The offset can be adjusted  between 0 5  F and 20 0  F  0 5  C and 11 1 C      e Set the function to STAGE 2 OFFSET BANDWIDTH  The  current offset of Stage 2 flashes on the display  alte
5.   the stage turns on  except      the case of the heater and mist  offsets where the value displayed is the temperature at which  the stage turns off   If the user turns the adjustment knob  the  relative value reappears  For example  when the user turns the  selection knob to a differential position  i e  DIFFERENTIALS 3 4   the sequence is as follows      i  The current differential for stage 3 flashes on the display   alternating with  3           3          ii  If  after about 10 seconds  no action is taken by the user  the  absolute temperature value is displayed  alternating with  St 3 On    In this case  the absolute value is  Set Point   Bandwidth 1    Offset 2   Bandwidth 2   Differential 3     12 TC5 2N6FA rev 01        5 2  6               When the user turns the adjustment knob to make an adjustment  to the stage 3 differential  the relative value reappears on the dis     play        Locking the Parameter Settings    The parameter settings can be locked to prevent accidentally modi   fying them  When the settings are locked  only the temperature set  points  minimum ventilation speeds and manual mode can be modified   as long as the temperature ramp and the minimum ventilation speed  ramp are deactivated respectively      To lock the parameter settings       g      Setinternal switch  1 to ON  The Locked OFF  Parameter Pilot Light turns on     To unlock the parameter settings               Setinternal switch  1      OFF  The Locked       Parameter Pilot Light turn
6.  01    7        5 2  6      INSTALLATION    Mounting Instructions    Open the latch and lift the cover  Remove the black caps located on  each of the four mounting holes  Mount the enclosure on the wall  using four screws  Be sure the electrical knockouts are at the bottom  of the enclosure in order to prevent water from entering the control   ler  Insert the screws in the mounting holes and tighten  Fasten the  four black caps provided w ith the controller onto the four mounting  holes  The enclosure must be mounted in a location that will allow the  cover to be completely opened right up against the w all     Connections    To connect the controller  refer to the wiring diagram enclosed with  this user s manual        Set the voltage switch to the appropriate voltage     B Use the electrical knockouts provided at the bottom of the  enclosure  Do not make additional holes in the enclosure   particularly on the side of the enclosure when using a com   puter communications module     B It may be necessary to install a transformer in order to sup   ply the appropriate voltage to the heating unit     ALARM CONNECTION  There are two types of alarms on the mar   ket  One type activates when current is cut off at its input  whereas  the other activates when current is supplied at its input  For an alarm  of the first type  use the NO terminal as shown on the wiring dia   gram  For an alarm of the second type  use the NC terminal        ALL WIRING MUST BE DONE BY AN AUTHORIZED ELECT
7.  100 DAYS    A ramp is defined using ten points  Each point specifies a day number  and a set point for that day  Once the points of the ramp are defined   the ramp must be activated  The controller will change the tempera   ture set point every hour in a linear fashion betw een consecutive points  of the ramp  When the last point of the ramp is reached  the tempera   ture set point for that day is maintained until the ramp is reactivated     NOTES    i  All ten points of the ramp must be specified  If ten points are not  needed  repeat the last temperature value for each unnecessary point     ii  Certain restrictions apply to reduce the risk of errors     The highest possible day number is 255     Decreasing day numbers are not allow ed       Increasing temperatures are not allow ed     The temperature variation cannot exceed 3  F  1 6  C  per day     18 TC5 2N6FA rev 01        5 2  6        m Specifying the Ramp    The points of the ramp can only be modified while the ramp is dis   abled  Refer to the 4  section of this chapter to disable the ramp     e Set the function to SET POINT TEMP RAMP  The current  temperature set point flashes on the display   the value does  not flash if the ramp is activated  Refer to the 4th section of  this chapter to disable the ramp     Repeat the follow ing steps for each of the ten points  point 0  to point 9    e Press the push button  The day number of the first point of    the ramp  point 0  is displayed  dO x   where  x  is the day  num
8.  If a defective probe is detected  the Defective Probe Pilot Light  turns on  The room temperature shown on the display corresponds  to the average temperature measured by the probes in w orking  condition     To identify the defective probe     Set the function to PROBE TEMP   MIN   MAX  If the  probe connected to input  1 is not defective  the let   ters  PRI  are displayed  alternating with the on off  state of the probe and the temperature measured by  the probe  If the probe is defective  the letters  PRI   are displayed  alternating with the state of the probe  and the letter  P         Press the push button to step to the follow ing probe     Proceed as explained above to make sure all probes are  in working order     TC5 2N6FA rev 01    11        5 2  6        CHANGING THE PARAMETER SETTINGS  Using the Display    ET       Flashing Values   The display will flash in certain cases  and not in others  The flashing indi      00 7 S O  cates that the value shown can be     adjusted  A value that is not flashing P          cannot be adjusted     Relative and Absolute Values    Some parameter adjustments are displayed both as a relative value  and an absolute temperature  This applies all heating and cooling  differentials  the mist differential and the heater offset  The pa   rameter is first displayed as a relative value  The corresponding  absolute temperature is displayed after six seconds if no action is  taken by the user  The absolute value is the temperature at which
9.  ON  Since the two heater outputs operate independently  differ   ent probes are assigned to each output  Probes 1 and 2 are assigned  to Heater 1 and Probes 3 and 4 are assigned to Heater 2  Individual  probes can be turned on or off using the internal switch settings  If  both probes are activated for a given heater  the average tempera   ture from both probes is used  if they are not activated  the heater  uses the room temperature  If only one heater is active  heater 1  uses the room temperature     ZONE 2 ZONE 1    PROBES 3  amp  4    PROBES 1  amp  2    NOT USED  MINIMUM HEAT    YOUNG ANIMALS       Both heating zones can have negative and positive heater offsets   Using a negative offset allows activating the heating output above  the temperature set point  this can be useful to control heat mats for  instance     To avoid ventilation problems w hen using zoned heating  a special  protection is built into the device  Suppose the animals are young and  confined to one part of the building  zone 1  while the rest of the  building is heated at a minimum level  zone 2   If the temperature  difference betw een zones is too high and zone 1 fans operate ac   cording to the average temperature for both zones  cooling in zone 1  may be insufficient  A built in protection will operate the fans ac   cording to the probes of the zone with the highest temperature w hen   ever the temperature difference betw een zones is greater than a  user defined value     TC5 2N6FA        01 49 
10.  ROOM TEMP MIN          or OUTSIDE           5     POINT  The corresponding temperature is displayed              the adjustment knob clockwise by one notch  The maxi   mum room temperature is displayed  alternating w ith the let   ters  Hi        Turm the adjustment knob counterclockwise one notch  The  room temperature is displayed once again              the adjustment knob counterclockw ise one notch fur   ther  The minimum room temperature flashes on the display   alternating with the letters  Lo   If any minimum or maxi   mum temperature reading is out of range  the controller dis   plays the letter  P  instead of displaying a temperature     NOTE  If you let the display flash for more than 10 seconds  the    controller resets the min and max temperatures currently in memory   the display stops flashing to indicate the reset has been done      TC5 2N6FA        01 15        5 2  6       5  Viewing Min Max Probe Temperatures    Follow this procedure to see the lowest and highest temperature read   ings that have been recorded by each probe since the last reset         Set the function to PROBE TEMP   MIN   MAX  The tem   perature reading of probe 1 is displayed  alternating w ith the  letters  Pr 1  and the on off state of the probe       Turn the adjustment knob clockwise by one notch  The maxi   mum temperature of probe 1 is displayed  alternating w ith  the letters  Pr1 Hi        Turm the adjustment knob counterclockwise one notch  The  current temperature of probe 1 i
11.  an alarm in the case of a power failure  a fault  in the supply circuit or a high or low temperature  Temperature alarms  are defined according to the set point as shown in the diagram be   low  The temperature alarm can either be set off if the average tem   perature exceeds the limits or if the reading of a single probe ex   ceeds the limit     Room  Temperature        High Temperature Alarm      High Alarm Offset    Low Alarm Offset    Time    Alarm Settings    The high and low alarm offsets range from 0 5  F to 40  F  0 3  to 22 2 C      Set the selection knob to ALARMS  The current low  alarm offset flashes on the display  alternating with the  letters  LoAL   Use the adjustment knob to set it to  the desired value     Press the push button  The high alarm offset flashes on  the display  alternating with the letters  HiAL   Use  the adjustment knob to set it to the desired value     Press the push button  The alarm type  TyPE  is dis   played  alternating w ith the w ord  ALL  or  Ind      Use the adjustment knob to select  ALL  for an alarm  to sound when the average temperature exceeds the  defined high or low limits  select  Ind  for alarm to sound  w hen the reading of an individual probe exceeds the  high or low temperature limits        TC5 2N6FA rev 01    53        5 2  6        TEST MODE    A test mode allows you to simulate temperature changes and verify  the performance of your controller  In test mode  the temperature  probe inputs are turned off  allow ing t
12.  greater than bandwidth 1  and must be set separately for each curtain     e Set the selection knob to CURTAINS     OFFSET DEAD BAND  The  offset of curtain 1 flashes on the display  alternating with the letters   10FS      e Use the adjustment knob to set curtain 1 offset to the desired value     e Press the push button tw ice  The offset of curtain 2 flashes on  the display  alternating with the letters  2 OFS      e Use the adjustment knob to set curtain 2 offset to the desired value     TC5 2N6FA        01 45        5 2  6        EI Adjusting the Curtains Dead Band    The dead band is the temperature difference betw een the opening and  closing temperatures of the curtains  It ranges from 0 5  F to 20 0  F  0 3  C  to 11 1  C  and must be adjusted separately for each curtain     Set the selection knob to CURTAINS     OFFSET DEAD BAND   The offset of curtain 1 flashes on the display  alternating with the  letters  1 OFS      Press the push button  The dead band for curtain 1 flashes on the  display  alternating with the letters  1 BND      Use the adjustment knob to set the dead band of curtain 1 to the  desired value     Press the push button tw ice  The dead band for curtain 2 flashes  on the display  alternating with the letters  2 BND      Use the adjustment knob to set the dead band of curtain 2 to the  desired value     Dn Adjusting the Curtain Timer    The curtain timer is made of a Time ON and of a Time OFF  The Time ON  ranges from 10 to 900 seconds and the Time O
13.  humidity level is displayed once again     e Turn the adjustment knob counterclockwise one notch fur   ther  The minimum humidity reading flashes on the display   alternating with the letters  rH Lo      NOTE  If you let the display flash for more than 10 seconds when the  maximum or minimum humidity is displayed  the controller resets the  minimum and maximum humidity values currently in memory  the  display stops flashing to indicate that the reset has been done      B Adjusting the Relative Humidity Set Point    When the relative humidity exceeds the humidity set point  the mini   mum speed of stage 1 fans is increased by a proportional amount to  compensate for the increase in humidity  Note that the humidity com   pensation feature must be activated forthis to work     e Set the function to STAGE 1 RH COMPENSATION  The rela   tive humidity set point is displayed alternating with the let   ters  Set      e  Usethe adjustment knob to adjust the set point to the de   sired value     28 TC5 2N6FA rev 01        5 2  6        E Adjusting the Minimum Speed Compensation    This is the increase in the minimum speed for a relative humidity  equal to the humidity set point   1096  It ranges from 0 to 10096     Set the function to STAGE 1 RH COMPENSATION  The rela   tive humidity set point is displayed alternating with the let   ters  Set      Press the push button  The current minimum speed compen   sation is displayed  alternating w ith the letters   SPEEd      Use the adjustment
14.  knob to adjust the minimum speed com   pensation to the desired value     n Activating Deactivating Humidity Compensation    Set the function to STAGE 1 RH COMPENSATION  The rela   tive humidity set point is displayed alternating with the let   ters  Set      Press the push button twice  The current on off state of hu   midity compensation flashes on the display     Use the adjustment knob to adjust the on off state to the  desired value         5 2  6            01 29        5 2  6        Minimum Ventilation Speed Ramp    The user can define a minimum ventilation speed ramp to adjust the  minimum speed of stage 1 automatically over a given time period  A  ramp is defined by ten points and each point specifies a day number  and a fan speed for that day  Once the points are defined  the mini   mum speed ramp must be activated  When the minimum speed ramp  is activated  the controller adjusts the minimum speed of state 1  fans every hour in a linear fashion betw een two consecutive points     When the last point of the ramp is reached  the ramp is deactivated   The controller maintains the minimum speed specified for this point  until the ramp is reactivated or until a new single minimum speed is  specified using the first method     STAGE 1 MIN   SPEED          SPEED 10   nis  SPEED 9          SPEED 8    e   SPEED7 4s                             SPEED 6           SPEED 5         SPEED 4         SPEED 3    E    SPEED 2    9       SPEED 1   e    DAY1 DAYS DAY10 DAY 17 DAY 25 DA
15.  probes are dry   shows ance is induced on a and move them away from   sudden probe  drafts and sources of radiant   variations in heating    room tem        perature  There is electrical Do not run probe cables next to  noise near an ex  other power cables  When  tended probe cable  crossing other power cables     cross at 90                  TC5 2N6FA        01 55        5 2  6           PROBLEM CAUSE SOLUTION    Stage 1 or 2  fans are not  running     The wiring is incor   rect     The Stage s fuse is  open     The display board  interconnect cable is  not plugged into the    power supply board  properly     The minimum speed  is too low     The fan motor is  defective     The On time of stage 1  fans in minimum  ventilation is set to  zero     56 TC5 2N6FA rev 01    Correct the wiring  In particular   make sure two different lines are  connected to each motor  line L1  modulated by the controller  should be combined with another  line  N for 115V or L2 for 230V  to  activate the motor  Also  be sure  the Stage 1 and 2 COMMON is  supplied by line L1     Replace the fuse     Make sure the cable is firmly  plugged in with the tabs in  place     Adjust the minimum speed to a  higher value     Check if motor is defective by  connecting it to an alternate  power supply  Replace the  motor if it still doesn t operate     Set the On Time to a  value other than zero            5 2  6                              SOLUTION       Stage 1 or 2 The wiring is incor   fans run rect   con
16.  the running time is decreased gradually until the  minimum ventilation settings are reached     64 TC5 2N6FA rev 01        5 2  6        SET POINT  The set point is the target room temperature  When the  temperature is above the set point  the controller cools the room by  turning on the cooling fans  When the temperature is below the set  point  the controller heats the room by turning on the heaters     TEMPERATURE RAMP  The controller can be set to automatically  change the temperature set point over a given period of time in  accordance with the user s requirements  The set point decreases  over time as the animals grow     ZONED HEATERS  When zoned heaters are used  heaters in each  zone operate according to their own probes rather than the average  temperature for the entire room  In this way  heaters across zones  are independent of one another     TC5 2N6FA rev 01 65       890 00563         01     895 00630 REV  01                         
17. E OFF    42     5     6     rev 01        5 2  6        When the temperature falls to 79  F  the curtains begin to close and  continue to do so until fully closed if the temperature remains below this  point  If the temperature rises to 79 3  F  the curtains stop closing     The curtains close intermittently according to the time on and time  off settings     TIME ON      gt   gt     CLOSE    STOP CLOSING    gt     TIME OFF        5 2  6            01 43        5 2  6        CURTAIN OPERATING TIME COMPENSATION    1  Normal Mode  Without Compensation    The curtains open and close intermittently according to the specified  opening time  closing time and time off  as described on the preced   ing pages  There is no outside temperature compensation     2  Progressive Mode  With Compensation    The controller can use the current outside temperature to adjust the  opening and closing times of the curtains  This feature must be acti   vated from the front panel  see below   An outdoor temperature  probe must be connected to input   5 forthis feature to work     Room Temperature Rises  When the curtains open  the controller  increases TIM E ON by 596 for every 1  F  0 6  C  difference betw een  the outside temperature and the outside Set Point  The TIME OFF is  decreased by the same amount  This is true if the outside tempera   ture is greater than the outside set point    The higher the outside temperature  the time on increases  causing  the curtains to open faster              Ro
18. F3 5A slow blow     Curtain 2 output  OPEN CLOSE output  115 230 VAC  60 Hz  30VDC  5A  winch output  fuse F5 5A slow blow     Heater 1  115 230 VAC  30VDC  50   60 Hz  Mot 6A  10A Res   fuse F10   15A slow blow     Mist   Heater 2  115   230 VAC  30VDC  50   60 Hz  Mot 6A  10A Res    fuse F9 15A slow blow     Alarm  ON OFF output  3A  115 230 VAC  30VDC  fuse F11 3A slow blow   Probes  Low voltage   lt  5V   isolated from the supply  Operating range    40 0  F to 120 0  F   40 0  C to 48 9  C   Accuracy  1 8  F  1  C  between  41  F and 95  F  5  C and 35  C      Enclosure  ABS  moisture and dust tight        The room temperature where the controller is located  MUST ALWAYS REMAIN BETWEEN 32   AND 104   F  0    AND 40  C               TC5 2N6FA        01 59    C5 2N6FA    FACTORY SETTINGS                                                                                                       PARAMETER FACTORY SETTINGS RANGE OF VALUES     0 0  F and 99 0  F  Temperature Set Point 75  F 23 9  C   17 0 and 37 2    Minimum Speed 40  10   to 100    Time On 15 seconds 0 to 900 seconds  in increments of 15 sec   Stage 1 Time Off 0 seconds  i 0 5 to 20  F  Bandwidth 2    1 1 C   0 3 to 11 1  C       Motor curve 4 Curve 1 10  Humidity Set Point 6596 40 to 100   Humidity Control 0 to 100  of st 1  Compensation Percentage 60  9 202209  minimum speed  0 5 to 20  F  Offset 0 5 F  0 3  C   0 3 to 11 1       0 5 to 20  F  Bandwidth 2  1 1    0 3 to 11 1    Min  Speed 40  10   to 100   Stage 2
19. FF from 0 to 900 seconds  and can be adjusted in increments of 5 seconds  The timers must be set  separately for each curtain     Set the selection knob to CURTAINS     TIMER  The Time ON of  curtain 1 timer flashes on the display  alternating with  1 On      Use the adjustment knob to set the Time ON of curtain 1 timer to  the desired value     Press the push button  The Time OFF of curtain 1 timer is displayed   alternating with  1 OFF      Usethe adjustment knob to set the Time OFF of curatin 1 timer to  the desired value     46     5     6     rev 01        5 2  6        e Press the push button once again  The Time ON of curtain 2 timer  flashes on the display  alternating with  2 On      e Use the adjustment knob to set the Time ON of curtain 2 timer to  the desired value     e            the push button  The Time OFF of curtain 2 timer is displayed   alternating with  2 OFF      e Use the adjustment knob to set the Time OFF of curtain 2 timer to  the desired value     B Adjusting the Outside Set Point    The outside set point is used for compensating curtain operating times as  a function of outside temperature  see above   It can be adjusted betw een   40 0  F and 99 9  F   40 0  C and 37 7  C        Set the selection knob to OUTSIDE TEMP   SET POINT  The cur   rent outside temperature is displayed     e Press the push button  The outside set point is displayed   alternating with the letters  SEt        Use the adjustment knob to adjust the outside set point to the  de
20. RI   CIAN AND MUST COMPLY WITH APPLICABLE CODES  LAWS  AND REGULATIONS  BE SURE POWER IS OFF BEFORE DOING    ANY WIRING TO AVOID ELECTRICAL SHOCKS AND EQUIP   MENT DAMAGE     8  TC5 2N6FA rev 01        5 2  6        Motor Types    The relationship betw een the voltage supplied to a motor and its  operating speed is described by a motor curve  This curve varies  w ith the make and capacity of the motor  The various motors avail   able in the industry have been divided into ten categories and the  controller has been programmed with a different motor curve for  each of these categories  To ensure that the controller supplies the  correct voltages  an appropriate curve must be selected for stage 1  and stage 2 according to the type of fan motors used     Eg Selecting a Motor Type for Stage 1 and Stage 2    Refer to the list of motors enclosed with this user s to choose the  proper motor type     e Set the function to STAGE 1 MOTOR TYPE or to STAGE 2  MOTOR TYPE  The motor type of the selected stage is dis   played  alternating with the letters  tYPE      e Press the push button once  The motor type flashes       Use the adjustment knob to adjust the motor type to the  desired value     e Press the push button once again to validate the new value         5 2  6            01 9    TC5 2N6FA    Temperature Probes    m Connecting the Probes    The controller is supplied w ith one temperature probe connected to  input   1  Up to three additional probes can be connected to the  contro
21. Temperature Controller    TC5 2N6FA       USER S MANUAL                    5 2  6                   TABLE      CONTENTS                                                                                  nn 2                        5                                 nnne    nnn nnn nn nnn nnn nnn 3  FEATURES    iiec iini ino n n C E ERG E OC OE RR ER      ER RR 4  LOCATION OF THE CONTROLS                eene nnns 6  Controller Status       5                      mme 7  Internal Switches                        HH Hmm 7                                                    nennen nnn nnn nnn nn nnn nn nnn 8  Mounting Instructions                                   200 0 menn 8  Connectioris                                            netu ete sidus 8  Motor  IV POS uiae our        e been eh leah A        9  Temperature Probes                        0 1  10  CHANGING THE PARAMETER SETTINGS                                           12  Using the                                                       0000  12  Locking the Parameter Settings                                          13  TEMPERATURE SETTINGS                eene nnns 14  Temperature  UTflts   2 1 treo doo etr eld              14  Viewing Temperatures                                   0202000022 1    14  Temperature Set                                          2        102444 17  Temperature                                 mene 18  VENTILATION SETTINGS              enne 22  Cooling Operation             sssssssseeen mn 22  Minim
22. Y 35 DAY 40 DAY 60 DAY 80 DAY100 DAYS    NOTES   i         minimum speed ramp must be deactivated before speci   fying the points on the ramp  see below       ii  All ten points of the ramp must be specified  If you do not  need ten different points  repeat your last minimum speed  for each unnecessary point of the ramp     iii  Certain restrictions apply to reduce the risk of errors       decreasing minimum speeds are not allow ed     the min  speed variation cannot exceed 1096 per day     30     5 2  6     rev 01        5 2  6      m Specifying the Minimum Speed Ramp    The points of the ramp can only be modified while the ramp is  disabled  Refer to the 4   section of this chapter to disable the  ramp     e Set the function to STAGE 1 MIN SPEED RAMP  The  current minimum speed of stage 1 flashes on the display    the value does not flash if the ramp is activated  Refer  to the 4th section of this chapter to disable the ramp     Repeat the following steps for each of the ten points   point 0 to point 9            e Press the push button  A day number is displayed  alter   nating with the word  dO x   where      is the day num   ber        Using the adjustment knob  set the day number of the  first point of the ramp to the desired value     e Press the push button once again  The minimum speed of  the first point  point 0  is displayed  PO x  where x repre   sents the speed     e Use the adjustment knob to adjust the minimum speed of  the first point of the ramp to the desir
23. ber           Using the adjustment knob  set the day number of the first  point of the ramp to the desired value     e Press the push button once again  The temperature set point  associated with the first point of the ramp  point 0  is dis   played   0      e Using the adjustment knob  adjust the set point of the first  point of the ramp to the desired value     Once all points of the ramp are defined  activate the ramp as ex   plained below      TC5 2N6FA        01 19        5 2  6        E Activating the Temperature Ramp    If you have just finished specifying the points on the ramp        e Press the push button once again  The word OFF flashes       the display     e Turn the adjustment knob clockwise one notch  The word  ON flashes on the display and the Temperature Ramp Pilot  Light turns on  indicating that the temperature ramp is now  activated     If you have previously defined the points on the ramp     e Set the function to SET POINT TEMP RAMP  The current  temperature set point flashes on the display     e Press the push button to display all points of the ramp until  the word OFF appears  tw enty one clicks      e Turn the adjustment knob clockwise one notch  The word  ON flashes on the display and the Temperature Ramp Pilot  Light is lit  indicating that the temperature ramp is now acti   vated     20 TC5 2N6FA rev 01        5 2  6        ES Adjusting the Day Number    The current day number can be adjusted in order to move forward or  backw ard on both ramps  
24. can be  operated either continuously or intermittently to reduce the level of hu   midity and supply oxygen to the room     RAMPING FUNCTIONS  Ramping functions provide an automatic adjustment of the set point and  minimum ventilation fan speed over a given period of time     CHOICE OF TEN MOTOR TYPES   The variation in motor speed resulting from a change in voltage will de   pend on the make and capacity of the motor  In order to achieve a high  degree of compatibility betw een controller and motor  the user can choose  from among ten different motor types  thus ensuring that the correct volt   age is supplied     HIGH LOW TEMPERATURE ALARM OUTPUT    HUMIDITY COMPENSATION   The stage 1 minimum speed can be adjusted automatically as a function  of relative humidity  As humidity increases  the minimum speed of stage  1 fans increases proportionally to compensate for the change     TC5 2N6FA rev 01        5 2  6        ZONED OR CASCADING HEATERS    FULL SPEED FAN START UP  In order to overcome the inertia of the ventilation system components and  de ice the fan blades in cold weather conditions  the controller supplies  maximum voltage to the variable speed fans during the 2 seconds imme   diately follow ing each start up     DE ICING CYCLE  A de icing cycle is provided for de icing stage 2 variable speed fans in  cold weather conditions     FOUR INDEPENDENT TEMPERATURE PROBE INPUTS   Up to four temperature probes can be connected to the controller in order  to obtain a more ac
25. crease in speed proportion   ally to the temperature     CASCADING HEATERS  Heaters operate in a sequence  As the av   erage room temperature falls  additional heaters are turned on as  needed     DEFAULT VALUE  A typical parameter setting defined at the fac   tory     DIFFERENTIAL  The differential is the temperature difference be   tw een the moment the constant speed fans or heating units of a  given stage start running and the moment they return to a stop     MINIMUM VENTILATION CYCLE  When the room temperature is  below the set point  the Stage 1 fans operate intermittently to pro   vide minimum ventilation to the room     MINIMUM VENTILATION SPEED RAMP  When Stage 1 operates  variable speed fans  they will run at minimum speed during the mini   mum ventilation cycle  The user can define a minimum ventilation  speed ramp to adjust the Stage 1 minimum speed automatically over  a given time period  The minimum speed increases over time as the  animals grow     OFFSET  An offset is a temperature difference from the set point  that normally defines a cut off point for a stage operation  For ex   ample  a heater offset of 2  F means the heaters will turn off at 2   F  below the set point     STAGE 1 RAMP  When the temperature rises to the point where  Stage 1 constant speed fans are needed for cooling  the running time  of the fans is increased gradually from the minimum ventilation set   tings up to full operation  Likewise  when the temperature falls be   low the set point 
26. curate reading of the average room temperature and a  faster reaction time     OUTSIDE TEMPERATURE COMPENSATION ON CURTAIN SPEED  Curtain opening and closing times can be decreased as a function of out   side temperature     OVERLOAD AND OVERVOLTAGE PROTECTION  Fuses are installed at the input and outputs of the controller to protect its  circuitry in the case of an overload or overvoltage     MEMORY CARD   A memory card is used to create a copy of your controller s parameters     COMPUTER CONTROL  The controller can be connected to a computer  thus making it possible to  centralize the management of information and diversify control strategies     CONTROL OF AIR INLET MOVEMENT   If the     5 2  6     is used in combination with a PF 6 controller  the  movement of the air inlets can be coordinated with the operation of the  fans using a potentiometer located on the panel drive  This allows the air  inlets to be adjusted correctly  without the influence of uncontrollable  factors such as wind or air from adjoining rooms     TEST MODE    A test mode allows you to simulate temperature changes and verify con   troller performance     TC5 2N6FA rev 01 5        5 2  6        LOCATION OF THE CONTROLS    OTHER FUNCTIONS            E   5               amp                1 4    CURT     MIST    FUNCTIONS ADJUSTMENTS       6  TC5 2N6FA rev 01        5 2  6        Controller Status LEDS                                                 LED MEANING   VARIABLE STAGE 1 Turns on when variable 
27. ed value     TC5 2N6FA        01 31        5 2  6        B Activating Minimum Speed Ramp    If you have just finished specifying the points on the ramp        Press the push button once again  The word OFF flashes on  the display     Turn the adjustment knob clockwise by one notch  The word  ON flashes on the display and the Minimum Speed Ramp  Pilot Light turns on  indicating that the minimum speed ramp  is now activated     If you have previously specified the points on the ramp        Set the function to STAGE 1 MIN SPEED RAMP  The cur   rent minimum speed flashes on the display     Press the push button to display the points of the ramp cur   rently defined until the w ord OFF appears  tw enty one clicks      Tum the adjustment knob clockwise by one notch  The word  ON flashes on the display and the Minimum Speed Ramp  Pilot Light turns on  indicating that the minimum speed ramp  is now activated     32 TC5 2N6FA rev 01        5 2  6      E Adjusting the Day Number    The current day number can be adjusted in order to move forward or  backward on both ramps  temperature and minimum ventilation speed  ramps  at the same time  Note that the current day is set to  OFF  if  no ramp function is enabled     e Set the function to CURRENT RAMPING DAY  The current  day number is displayed  alternating with the letters  day        Use the adjustment knob to set the day number to the  desired value     n Deactivating Minimum Speed Ramp    e Set the function to STAGE 1 MIN SPEED RAMP
28. er is incorrect  the letters  COPY  and   Error  will flash on screen  In this case  turn the adjustment knob  once to exit the error menu then refer to the table below to see  possible error causes     8  Once the transfer is over  open the controller s cover  and re   move the memory card from the connector  Close the controller s  enclosure afterw ards     9  Lock the card switch        if required     62 TC5 2N6FA rev 01        5 2  6        TEAR      Error  SOLUTION    If you want to copy the controller s configuration on  the memory card  make sure the switch at the  bottom of the card is at the unlocked position     The memory card is  write protected    If you want to transfer the card s configuration in  the controller  make sure internal switch  1 of the  controller is at the  OFF  position     The controller is write  protected    The memory card   is blank or its content Make sure a valid configuration is written on the  is incompatible with card before starting a transfer    the controller    Make sure the memory card is properly inserted in  the connector then retry the transfer  Do not move  or hold the card while the transfer is ongoing     The transfer  is incomplete    The memory card is defective  try with another  card  contact your dealer      The connector is defective  contact you dealer            TC5 2N6FA rev 01 63        5 2  6        GLOSSARY    BANDWIDTH  The temperature interval over which the variable   speed fans of a given stage increase or de
29. fset is displayed  alternating with the letters  OFSEt      e Press the push button  The mist differential is displayed  al   ternating with the letters  dIF      e Using the adjustment knob  set the differential to the desired    value        Adjusting the Mist Offset    The mist offset is the temperature difference from the set point at  which the mist units turn off  It can be adjusted between 0 5  F and  20 0  F  0 3  C and 11 1 C      e Set the function to MIST OFFSET DIFFERENTIAL  The mist  offset is displayed  alternating with the letters  OFSEt      e Using the adjustment knob  set the offset to the desired value     40 TC5 2N6FA rev 01        5 2  6        E Adjusting the Mist Timer Settings    The timer s On Time can be adjusted from 0 to 900 seconds  in incre   ments of 15 seconds  the Off Time can be adjusted from 0 to 60 min   utes  To deactivate mist cooling  set the Time On to zero  This param   eter is only displayed if mist units are enabled  internal switch  6      e Set the function to MIST TIMER  The current Time On for  the mist cycle is displayed  alternating with the letters  t On      e Usethe adjustment knob to set the Time On to the desired  value  in minutes      e Press the push button The current Time Off for the mist  cycle is displayed  alternating with the letters  t Off      e Use the adjustment knob to set the Time Off to the desired  value  in minutes           Adjusting the Mist Shutoff Set Point    The mist shutoff set point is the humidit
30. he De icing On Time    The de icing duration ranges from 0 to 900 seconds  Note that the  de icing On Time must be shorter or equal to the Cycle Time     e Set the function to STAGE 2 DE ICING the current de icing  cycle time is displayed  alternating with the letters   CYCLE      e Press the push button  The current de icing time is displayed   alternating with the letters  t On      e Use the adjustment knob to adjust the de icing time to the  desired value     38     5 2  6     rev 01        5 2  6           Mist Cooling    The last cooling stage can be used as a mist stage  Set internal switch   6 to ON to activate this stage  This mist stage can only be used if  only one heating stage is enabled  internal switch  6 to ON      Mist Mist units turn on  Mist units turn off in timer mode    ON EE    DIFFERENTIAL       OFF      Mist Offset Room  Set Point Temperature    Mist units start running according to a timer cycle  Time On  and Time Off  when their start temperature is reached  Set  Point   Mist Offset   Differential      If the humidity compensation is activated  the mist units are  shut off when the humidity level is too high     TC5 2N6FA        01 39    TC5 2N6FA       Adjusting the Mist Differential    The mist differential is the variation in room temperature betw een  the moment the mist units turn on and the moment they turn off  It  can be adjusted between 0 5  F and 20 0  F  0 3  C and 11 1          e Set the function to MIST OFFSET DIFFERENTIAL  The mist  of
31. he change  At  humidity levels at or below the humidity set point  the minimum speed  is equal to the normal uncompensated speed  The user specifies the  percentage increase in minimum speed for a relative humidity equal  to the humidity set point   1096  For example  if the minimum speed  is 4096 and the compensation adjustment is 3096  the minimum speed  will be adjusted to 7096 of full speed when the humidity rises 1096  above the humidity set point  In addition to adjusting the minimum  speed  the humidity compensation feature also changes the opera   tion of the minimum ventilation cycle  if the controller is operating in  minimum ventilation mode when the relative humidity exceeds the  humidity set point  the minimum ventilation fans are operated con   tinuously rather than cycled     Stage 1  Min  Speed        10096  Compensation begins       Compensation 96        Normal  Min  Speed    0     Relative Relative  Humidity Humidity  Set Point    When a compensation is applied to the minimum speed  the compen   sation pilot light turns on     TC5 2N6FA rev 01 27    TC5 2N6FA    m Viewing the Relative Humidity  The relative humidity is expressed as a percentage     e Set the function to RELATIVE HUMIDITY MIN MAX  The  current relative humidity is displayed              the adjustment knob clockwise by one notch  The maxi   mum humidity reading flashes on the display  alternating with  the letters  rH Hi      e Turn the adjustment knob counterclockwise one notch the  current
32. he heating units turn on and the moment they turn off  see  diagram above   It can be adjusted betw een 0 5  F and 20 0  F  0 3  C  and 11 1  C      e Set selection knob to HEATER 1 OFFSET DIFFERENTIAL or  HEATER 2 OFFSET DIFFERENTIAL The current heating off   set is displayed  alternating with the letters   OFSEt      e Press the push button  The differential is displayed  alternat   ing with the letters  diF      e Use the adjustment knob to adjust the differential to the de   sired value     TC5 2N6FA        01 51        5 2  6        Adjusting the Security Differential for Zoned  Heaters    The security differential is the maximum temperature difference  allow ed betw een the heating zones 1 and 2  If the temperature  difference betw een these zones exceeds the security level  the  controller will make the fans run according to the temperature  perceived in the warmest zone  The security differential can be  adjusted betw een 0 5  F and 20  F  0 3  C and 11 1  C     e Set selection knob to HEATER 2 OFFSET DIFFERENTIAL  The current heating offset is displayed  alternating with  the letters  OFSEt      e Press the push button twice  The security differential is  displayed  alternating with the letters  2n diF    This  parameter is only available if zoned heaters are used  i e    internal switch  8 is ON        Use the adjustment knob to adjust the security differential  to the desired value     52 TC5 2N6FA rev 01        5 2  6      ALARM SETTINGS    The controller sets off
33. ime On to zero and Time Off to  any value     3  Torun the fans intermittently  set the Time On to the de   sired running time and Time Off to the desired off time     TC5 2N6FA rev 01 25    TC5 2N6FA  EI Adjusting the Minimum Speed of Stage 1    The minimum speed can be adjusted betw een 10 and 10096   e Set the function to STAGE 1 MIN SPEED RAMP  The mini   mum speed of stage 1 flashes on the display  alternating  with the letters  SPEEd      e Use the adjustment knob to adjust the minimum speed to the  desired value     NOTE  This speed can only be adjusted if the minimum speed ramp is  disabled  see M inimum Ventilation Ramp chapter      E Adjusting the Minimum Ventilation Timer    Time on and Time Off can be adjusted betw een 0 and 900 seconds   in increments of 15 seconds     e Set the function to STAGE 1 BANDWIDTH TIMER  The cur   rent bandw idth of stage 1 flashes on the display  BAnd      e Press the push button  The current Time On of stage 1 flashes  on the display  t  On      e Use the adjustment knob to adjust the Time On to the de   sired value     e Press the push button  The current Time Off of stage 1  flashes on the display  t  Off      e Use       adjustment knob to adjust the Time Off to the de   sired value     26 TC5 2N6FA rev 01        5 2  6        Humidity Compensation    The minimum speed of stage 1 can automatically be adjusted as a  function of relative humidity  As humidity increases  the minimum  speed increases proportionally to compensate for t
34. ller in order to obtain a more accurate reading of the average  room temperature and a faster reaction time     e Use inputs  2  3 and 4 to connect additional probes  as  shown on the wiring diagram enclosed     CAUTION  Probes operate at low voltage and are isolated from the  supply  Be sure that probe cables remain isolated from all high volt   age sources  In particular  do not route the probe cables through the  same electrical knockout as other cables  Do not connect the shield  from the probe cable to a terminal or a ground     Switches are used to activate or deactivate the additional probes  connected to the controller   e Activate each additional probe by setting    the appropriate switch to ON  ON H  3      Switch  3 activates the probe connected  to input  2       Switch  4 activates the probe connected  to input  3       Switch  5 activates the probe connected  to input  4     10 TC5 2N6FA rev 01        5 2  6        ES Extending the Probes    Each probe can be extended up to 500 feet  150 meters   To  extend a probe     Use a shielded cable of outside diameter betw een 0 245  and 0 260 in  6 22 and 6 60 mm   the cable dimensions  should not be under 18 AWG  to ensure the cable entry  is liquid tight  Do not ground the shielding     It is preferable to solder the cable joint to ensure a proper  contact between the two cables     CAUTION  Do not run probe cables next to other power cables     When crossing over other cables  cross at 90       EH Defective Probes   
35. ltage   w e recommend installing an additional protection device on  the controller s supply circuit     The room temperature w here the controller is located MUST  ALWAYS REMAIN BETWEEN 32  F AND 104  F  0  C TO  40  C      To avoid exposing the controller to harmful gases or exces   sive humidity  it is preferable to install it in a corridor     DO NOT SPRAY WATER ON THE CONTROLLER             FOR CUSTOMER USE   Enter the serial number located on the  side of the controller below for future  reference     Model number  TC5 2N6FA  Serial number        TC5 2N6FA        01 3    4        5 2  6        FEATURES    The TC5 2N6FA is an electronic device used for environmental control in  livestock buildings  It allows the user to maintain a specified target tem   perature by controlling the operation of ventilation and heating equip   ment  Two stages of variable speed fans  two stages of constant speed  fans  as well as curtains  foggers and heaters can be connected to the  controller     The main features of the     5 2  6     are as follows     FIVE DIGIT DISPLAY   A five digit display provides a high level of accuracy  allowing the user to  specify a temperature to within one tenth of a degree  in Fahrenheit or  Celsius units      PILOT LIGHTS  Pilot lights indicating the state of outputs allow the user to monitor the  operation of the system without having to enter the building     MINIMUM VENTILATION CYCLE   When ventilation is not required for cooling  the first stage fans 
36. n be adjusted between 0 5  F and 20 0  F  0 3  C and  11 1           e Set the function to STAGES 3 4 DIFFERENTIAL  The cur   rent differential of Stage 3 flashes on the display  alternat   ing with the letters  3 diF     e Use the adjustment knob to adjust it to the desired value     e Press the push button  The current differential of Stage 4  flashes on the display  alternating with the letters  4 diF      e Use the adjustment knob to adjust it to the desired value     36     5 2  6     rev 01        5 2  6        De icing of Stage 2 Fans   Stage 2 fans can automatically be de iced in cold weather condi   tions  When a de icing cycle starts  Stage 1 fans are stopped then  stage 2 fans start running at full speed for 2 seconds  Stage 2 fans  then run at the minimum speed of stage 2 during the de icing time   Once the de icing time has elapsed  stage 2 fans stop and the opera   tion of stage 1 is resumed  Set internal switch  9 to ON to activate  this function     DE ICING TIME    DE ICING CYCLE TIME    EX Adjusting the De icing Cycle Time  The de icing cycle time is the time lapse betw een de icing cycles  It  ranges from 1 to 720 minutes  Note that the cycle time must be    greater or equal to the de icing On Time     e Set the function to STAGE 2 DE ICING the current de icing  cycle time is displayed  alternating with the letters   CYCLE      e Use the adjustment knob to adjust the cycle time to the de   sired value     TC5 2N6FA rev 01 37        5 2  6      B Adjusting t
37. nd 4 when the room tem   perature decreases of 2  F  1 1  C  below their respective differen   tial  Set the internal switch  7 to ON to activate this function        Ventilation  Level    stage 4 Je nnne    stage 3    stage 2       4  Hysteresis  4    Hysteresis  gt   2     2               lt     Bandwidth       4    Differential           Differential           Stage 2 Stage 3 Stage 4    24 TC5 2N6FA rev 01        5 2  6        Minimum Ventilation Cycle    When the room temperature is below the set point  the fans of stage 1  operate according to the minimum ventilation cycle  Running the fans  even though ventilation is not required for a cooling purpose is useful  to reduce humidity levels and supply oxygen to the room  It also  prevents the fans from freezing in winter     TIME ON  STAGE 1                           STAGE1     MIN  SPEED  OFF   lt  gt   TIME OFF  STAGE 1    During the Time On  stage 1 fans run at their minimum speed and  the pilot light of stage 1 is lit  during the Time Off  the fans return to  a stop and the pilot light turns off  Note that the minimum speed of  stage 1 can automatically be adjusted over time with a ramp  see  below      NOTE  The controller supplies maximum voltage to the variable speed  fans for 2 seconds immediately following each start up   Minimum Ventilation Cycle Settings    1             the fans continuously at minimum speed  set the Time  Off to zero and Time On to any value other than zero     2       stop the fans  set the T
38. nother controller of the same    type     The switch at the bottom of the card is used to lock or to unlock  the card      locked   g   unlocked                              Internal Switches                                Card Switch          Connector    Electronic  top board                   TO TRANSFER A CONFIGURATION   1  Openthe latch and lift the controller s cover     2  If you are about to copy the controller s configuration on the memory  card  make sure the card s switch is atthe unlocked position     3  Insert the card in the connector located on the electric board  inside the controller  Referto the illustration above to position the  TC5 2N6FA rev 01 61        5 2  6           memory card correctly     4  If internal switch  12 is at the OFF position  simply switch it to  the ON position  if internal switch  12 is at the ON posi    tion  return to the OFF position then switch it back to ON      9              ORE 12    5  Closethe controller s cover     6  The transfer menu should be displayed on screen  Use the  adjustment buttons to select whether you want to transfer the memory  card s content into the controller    COPY   to   CTRL   or if you  wish to transfer the controller s content into the memory card               to   CARD       7           you have chosen the proper type of transfer  press and  hold the Other Functions button for 5 seconds  The controller will  automatically return to the ROOM TEMP menu once the transfer is  completed  If the transf
39. o change the temperature used  by the controller to operate the stages  The controller operates as  before using the new temperature settings     Enable   disable the test mode          Setthe function to TEST MODE  The test mode status flashes  on the display     e Use the adjustment knob to select the desired test mode  status  On or Off    Setting the test mode temperature      Once the test mode is enabled  press the push button            test mode temperature is displayed  alternating w ith the let   ters  tSt      NOTE  If no user activity is recorded after 4 minutes in test mode   the controller automatically exits from the test mode     54 TC5 2N6FA rev 01        5 2  6        TROUBLESHOOTING GUIDE    PROBLEM SOLUTION       The display The circuit breaker on Reset the circuit breaker   doesn t work    the service panel is off  or tripped     The wiring is incorrect    Fix the wiring     The input fuse is Replace the fuse    open    The voltage selector Set the switch to the correct  switch is in the wrong position    position    The display board Plug the cable     interconnect cable is  unplugged from the  power supply board              The display Probe   1 is improp  Fix the probe s connection    shows the erly connected    letter  P    The Defective   One or more probes Follow the procedure described   Probe Pilot   are defective  in DEFECTIVE PROBES to   Lightis on  identify and replace the defec    tive probe    The display A variation in resist  Make sure the
40. o the minimum ventilation cycle     e AtSet Point  stage 1 fans stop operating according to the  minimum ventilation cycle and increase in speed as the room  temperature rises          AtSet Point   Bandwidth 1  stage 1 fans reach full speed         AtSet Point   Bandwidth 1   Stage 2 Offset  stage 2 fans  start running at their minimum speed     e AtSet Point   Bandwidth 1   Stage 2 Offset   Bandwidth  2  stage 2 fans reach full speed          AtSet Point   Bandwidth 1   Stage 2 Offset   Bandwidth  2   Diff  3  stage 3 fans start running     e  AtSet Point   Bandwidth 1   Stage 2 Offset   Bandwidth  2   Diff  3   Diff  4  stage 4 fans start running   IF THE ROOM TEMPERATURE FALLS       e  AtSet Point   Bandwidth 1   Stage 2 Offset   Bandwidth  2 4 Diff  3  stage 4 fans return to a stop     e  AtSet Point   Bandwidth 1   Stage 2 Offset   Bandwidth  2  stage 3 fans return to a stop  stage 2 fans start decreas   ing in speed as the temperature decreases     e AtSetPoint   Bandwidth 1   Stage 2 Offset   0 3  F  stage  2 fans return to a stop     e  AtSetPoint   Bandwidth 1  Stage 1 fans start decreasing  in speed as the temperature decreases         5 2  6            01 23    TC5 2N6FA    e  AtSet Point  Stage 1 fans reach minimum speed       Below the Set Point  stage 1 fans stop operating continu   ously and operate according to the minimum ventilation cycle  at minimum speed       USING A FIX HYSTERESIS ON VENTILATION STAGES 3 4   This function allow s deactivating stages 3 a
41. om Temperature Falls  When the curtains close  the controller  increases TIM E ON by 596 for every 1  F  0 6  C  difference betw een  the outside temperature and the outside Set Point  TIM E OFF is de   creased by the same amount  This is true if the outside temperature  is lowerthan the outside set point        The lower the outside temperature  time on increases  causing the  curtains to close faster           NOTE  If  after compensation  the time off value is less than or equal  to ten seconds  it is set to zero     44     5     6            01        5 2  6        Settings    m Manual Control of the Curtains      Set the selection knob to CURTAINS MANUAL MODE  The status  of the manual control mode is displayed for curtain 1     e Use the adjustment knob to select the proper manual mode status  for curtain 1      LAUt       select the automatic control mode     1 OPn  to manually open curtain 1  the letters  1 OPn  flash  on the display for 5 seconds then the curtain 1 starts  opening       1 CLo  to manually close curtain 1  the letters  1 CLO  flash  on the display for 5 seconds then curtain 1 starts  closing      1 OFF  to stop the actuator of curtain 1     e            the push button to select the manual mode status of curtain 2     E Adjusting the Curtain Offset    The offset is the number of degrees  above the set point  at which a curtain  starts closing in timer mode  refer to the previous graph   It can be adjusted  from 0 5 to 20 0  F  0 3 to 11 1  C   must be
42. rnating  with the letters  OFSET      e Use the adjustment knob to adjust the offset to the desired  value     34 TC5 2N6FA rev 01        5 2  6           Adjusting the Bandw idth of Stage 2    The bandwidth of Stage 2 is the temperature interval over which the  speed of variable stage 2 fans increases or decreases proportionally  to the temperature  The bandw idth can be adjusted betw een 0 5  F  and 20 0  F  0 3  C and 11 1 C          Set the function to STAGE 2 OFFSET BANDWIDTH  The cur   rent offset of Stage 2 flashes on the display  alternating w ith  the letters  OFSET      e Press the push button  The current bandwidth of Stage 2 is  displayed  alternating with the letters  BAnd      e Use the adjustment knob to adjust the bandwidth to the de     sired value     n Adjusting the Minimum Speed of Stage 2    The minimum speed of stage 2 fans can be adjusted betw een 1096  and 10096     e Set the function to STAGE 2 MIN SPEED  The minimum speed  of stage 2 flashes on the display  alternating w ith the letters   SPEEd      e Use the adjustment knob to adjust the minimum speed to the  desired value     TC5 2N6FA rev 01 35        5 2  6        l Adjusting the Differentials of Stages 3 4    The differential of stage 3 is the temperature difference from the  moment stage 2 fans reach full speed and the moment stage 3 fans  start  the differential of stage 4 is the temperature difference above  the start temperature of stage 3 at which stage 4 starts  Stage 3 4  differentials ca
43. s displayed once again       Tumthe adjustment knob counterclockw ise one notch fur   ther  The minimum temperature of probe 1 flashes on the  display  alternating with the letters      1 Lo      e        the adjustment knob clockwise by one notch  The cur   rent temperature of probe 1 is displayed once again     e Press the push button to select another probe then proceed  as explained above to see the minimum and maximum tem   perature readings of the desired probe     NOTE  If you let the display flash for more than 10 seconds  the  controller resets the minimum and maximum temperatures of the  selected probe  the display stops flashing to indicate that the reset  has been done      16     5     6     rev 01        5 2  6        Temperature Set Point  The temperature set point is the target room temperature  It can be    adjusted between 0 0  F and 99 0  F   17 8  C and 37 7  C    Adjusting the Temperature Set Point        Set the function to SET POINT TEMP RAMP  The current  set point flashes on the display     e Use       adjustment knob to adjust the set point to the de   sired value     NOTE  The temperature set point can only be adjusted while the  temperature ramp is deactivated  see follow ing section      TC5 2N6FA        01 17        5 2  6        Temperature Ramp    The user can define a temperature ramp to adjust the set point auto   matically over a given time period     SET POINT  TEMPERATURE       DAY4 DAY 15 DAY21 DAY 30 DAY 36 DAY 45 DAY 55 DAY70 DAY 80 DAY
44. s off        TC5 2N6FA        01 13    TC5 2N6FA    TEMPERATURE SETTINGS    Temperature Units  Temperatures can be displayed in either Celsius or Fahrenheit units        Set internal switch  2 to the desired position     ON  to display temperatures in Celsius units   OFF  to display temperatures in Fahrenheit units     Viewing Temperatures    m Viewing the Room Temperature    The room temperature is the average value of all temperatures  measured by activated probes in proper operating condition     e Set the function to ROOM TEMP MIN   MAX  The aver   age room temperature is displayed     B Viewing the Outside Temperature    e Set selection knob to OUTSIDE TEMPERATURE  The out   side temperature is displayed     14 TC5 2N6FA rev 01        5 2  6      Viewing Probe Temperatures    The controller can display probe temperatures individually  Probes  can also be turned on or off to control the temperature in different  parts of the building     e Set the function to PROBE TEMP   MIN   MAX  The tem   perature reading of probe 1 is displayed  alternating w ith the  letters  Pr 1  and the on off state of the probe     e  Foreach additional probe  press the push button  The tem   perature reading of probe x is displayed  alternating with the  letters  Prx  and the on off state of the probe  etc      4  Viewing Min Max Temperatures    Follow this procedure to see the lowest and highest room tempera   ture values that have been recorded since the last reset         Set the function to
45. sired value     D Activating Outside Temperature Compensation      Setthe selection knob to OUTSIDE TEMP   SET POINT  The cur   rent outside temperature is displayed       Press the push button twice  The current on off status of the  outside compensation feature is displayed     e Use the adjustment knob to enable or disable the compensation  function     TC5 2N6FA rev 01 47    TC5 2N6FA    HEATER SETTINGS    The controller can control up to two heating stages  Set internal  switch  6 to  ON  to use one heating stage  set it to  OFF  to use  both heating stages     CASCADING HEATERS  When cascading heating is used  the operation of heating stages is  based on the average room temperature  internal switch  8 is OFF      HEATER 2  TURNS ON           HEATING  OUTPUTS HEATER 2  TURNS OFF  HEATER 1  TURNS ON  HEATER 2  ON HEATER 1    TURNS OFF  HEATER 1           l  ON             HEATER 1  OFFSET        ER2  DIFFERENTIAL    HEATER 1    DIFFERENTIAL ROOM T     SET POINT    If the room temperature rises      at Set Point   Heater 1 Offset   Heater 1 Differential  Heater 2  turns off      at Set Point   Heater 1 Offset  Heater 1 turns off     If the room temperature falls      at Set Point   Heater 1 Offset   Heater 1 Differential  Heater 1  turns on      at Set Point   Heater 1 Offset   Heater 1 Differential   Heater 2  Differential  Heater 2 turns on     48 TC5 2N6FA rev 01        5 2  6        ZONED HEATERS   To configure your system for zoned heaters  set internal switch  8  to
46. stage 1 fans are on    VARIABLE STAGE 2 Turns on when variable stage 2 fans are on    STAGE 3 Turns on when stage 3 is on    STAGE 4 Turns on when stage 4 is on    MIST Turns on when the mist output is on    CURTAIN 1 OPEN Turns on when curtain 1 opens    CURTAIN 1 CLOSE Turns on when curtain 1 closes    CURTAIN 2 OPEN Turns on when curtain 2 opens    CURTAIN 2 CLOSE Turns on when curtain 2 closes    HEATER 1 Turns on when heating output 1 is on    HEATER 2 Turns on when heating output 2 is on    RH COMPENSATION Turns on when a RH compensation function is on    TEMP RAMP Turns on when the temperature ramp function is activated   MIN SPEED RAMP Turns on when the minimum speed ramp function is activated   PROBE DEFECT Turns on when    probe is defective    ALARM Turns on when an alarm condition is detected           Intemal Switches    Internal switches are located on the inside of the front cover  All  switches are set to OFF when the controller is shipped from the fac                                   tory       OFF ON  1 UNLOCKED PARAMETERS LOCKED PARAMETERS  2 FAHRENHEIT DEGREES CELSIUS DEGREES  3 PROBE 2 DISABLED PROBE 2 ENABLED  4 PROBE 3 DISABLED PROBE 3 ENABLED  5 PROBE 4 DISABLED PROBE 4 ENABLED  6 2 HEATERS  amp  0 MIST 1 HEATER  amp  1 MIST  7 ADJUSTABLE HYSTERESIS FIX HYSTERESIS OF 2 0  F  8 CASCADING HEATERS ZONED HEATERS  9 DE ICING DISABLED DE ICING ENABLED  10 RESERVED  11 RESERVED  12 SWITCH FROM OFF TO ON TO ACCES THE TRANSFER MENU                TC5 2N6FA rev
47. temperature and minimum ventilation speed  ramps  at the same time  Note that the current day is set to  OFF  if  no ramp function is enabled         Setthefunction to CURRENT RAMPING DAY  The current    day number is displayed  alternating with the letters  day      e  Usethe adjustment knob to set the day number to the de   sired value     mn Deactivating the Temperature Ramp    e Set the function to SET POINT TEMP RAMP  The current  temperature set point is displayed     e Press the push button to display the points of the ramp actu   ally defined until the word ON appears  twenty one clicks      e        the adjustment knob counterclockwise one notch  The  word OFF flashes on the display and the Temperature Ramp  Pilot Light turns off indicating that the temperature ramp is  now deactivated     TC5 2N6FA rev 01 21        5 2  6        VENTILATION SETTINGS    Cooling Operation    TheTC5 2N6FA controls two stages of variable speed fans  Stage  1 2 andtwo stages of constant speed fans  Stage 3 4      VENTILATION  LEVEL              STAGE 4                                             STAGE                                         STAGE2                                   STAGE 1                Min Ventilation Bandw  Diff  Diff        Room  Cycle Stagel Stage2 Stage   Stage3              Temp   Temperature  Set Point    22 TC5 2N6FA rev 01        5 2  6        IF THE ROOM TEMPERATURE RISES     e When room temperature  lt  Set Point  stage 1 fans run at  minimum speed according t
48. tinuously at    full speed  The ambient tempera     ture is above the set  point     Fix the wiring     Adjust the set point to the  desired value        Stage 1 or2 The selected motor  fans run ramp is inappropri   erratically  ate     The differential is too  small     The Time On or Time  Off is too short     Stage 1 fans do  Time off is set to zero   not stop  running when  the controller  is operating in  minimum  ventilation  cycle     The wiring is incorrect        Humidity compensation  is activated and relative  humidity exceeds set    point     Select an appropriate motor  ramp     Adjust the differential to a  higher value     Adjust the Time On or Time Off  to a higher value     Set the Time Off to a value other  than zero     Correct the wiring  In particular   make sure two different lines  are connected to each motor   line L1 modulated by the  controller should be combined  with another line     for 115V or L  for 230V  to activate the motor   Also  be sure the stage 1 COM   MON is supplied by line L1     Adjust set point or deactivate  compensation as required     TC5 2N6FA rev 01    2       57        5 2  6                              CAUSE    SOLUTION       Stage 3 4 is  not operating              The Stage s fuse is  open     The display board  interconnect cable is  not plugged into the  power supply board  properly     The wiring is incor   rect     The fan motor or  heating unit is  defective     The controller is  defective     58 TC5 2N6FA rev 01    
49. um Ventilation                                           02070002 20022 21  25  Minimum Ventilation Cycle Settings                                      25  Humidity                                                     2                       27  Minimum Ventilation Speed Ramp                                           30  Differential  Settings are terio eo teet Leto tentata 34  De icing of Stage 2 Fans                                                      37  Mist Cooling eem 39  NATURAL VENTILATION              enne nnns 42  Principle of Operation                                                42  ET                         44  HEATER 5            65                                                              nnn nnn nnn 48  ALARM SETTINGS                                   nn nn nnn 52  TEST MODE                                               nua 54  TROUBLESHOOTING GUIDE                   eem 55  TECHNICAL SPECIFICATIONS                     een 59  FACTORY SETTINGS               eeseennennenen nnn nnn nnn nnn nan 60  MEMORY                                          61  GLOSSARY        64    TC5 2N6FA rev 01        5 2  6      PRECAUTIONS       We strongly recommend installing supplementary natural ven   tilation as well as a back up thermostat on at least one cooling  stage  refer to the wiring diagram enclosed with this user s  manual to connect the thermostat      Although fuses at the input and outputs of the controller  protect its circuits in case of an overload or overvo
50. y level above w hich mist units  are disabled  This parameter is only displayed if mist units are enabled   internal switch  6   The mist shutoff value ranges from 0 to 100   of humidity  To disable this function  increase the parameter value  until you reach the word  no      e Set the function to MIST RH COMPENSATION  The humid   ity level above which mist units turn off is displayed  alter   nating with the letters  rH OFF      e  Usethe adjustment knob to set the humidity level over which  the mist stage stops operating     TC5 2N6FA        01 41        5 2  6        NATURAL VENTILATION  Principle of Operation    The TC5 2N6FA controls two curtains  These curtains have  independent parameter settings  Offset  Dead Band and timer  and  their operation is based on a predefined selection of temperature  probes  Curtain 1 operates according to the average temperature of  probes 1  amp  2  curtain 2 according to temperature probes 3  amp  4     Curtains open    Curtains close       in timer mode Vien         ON   Td  OFF     4         Offset Dead Band Temperature  79 F 89  F    Set Point   75  F    In the example above  when the temperature rises to 89  F  the cur   tains begin to open and continue to do so until fully open if the tem   perature remains above this point  If the temperature falls to 88 7  F   the curtains stop opening     The curtains open intermittently according to the time on and time    off settings   TIME ON       _  gt   OPEN    STOP OPENING    gt     TIM
    
Download Pdf Manuals
 
 
    
Related Search
 TC5 2N6FA 
    
Related Contents
Cyrillic 2.1  Curtis FR320  Emerson 92S Instruction Manual  dreamGEAR ISOUND-5378 soundbar speaker  Kit pédagogique : Du corps humain aux cellules  ダウンロードはこちらから  Contrat Territorial Gestion Quantitative de l`eau  InFocus U630 Network Card User Manual  取扱説明書 東芝インターホ  TiVo Premiere 4    Copyright © All rights reserved. 
   Failed to retrieve file