        G3ZA-8A403-FLK-UTU
         Contents
1.     Be sure to mount an End Plate on each side of the G3ZA so that it  does not slide on the DIN Track     To mount an End Plate  hook the bottom of the End Plate on the  bottom of the DIN Track  1   place the top of the End Plate on the DIN  Track  2   and then pull down on the End Plate  Tighten the screw on  the End Plate to secure it            PPOO    End Plate O End Plate    Note  Always mount one End Plate on each side of the G3ZA   Installation Example    When installing the SSRs next to the G3ZA  provide sufficient space  between the G3ZA and SSRs  as shown in the following diagram        Reference example   When applying 25 A to the G3PE 225B  a manipulated variable of  100    separate the SSRs from the G3ZA by at least 50 mm     Do not touch the G3ZA while power is being supplied           mm min        Mounting with Screws    Logs mm ewe       Mounting Dimensions  Unit  mm     Two  4 2 dia     or M4  _ amp     8440 3             y   7       350 3        gt        To convert millimeters into inches  multiply by 0 03937  To convert grams into ounces  multipl    In the interest of product improvement  specifications are subject to change without notice     oOmRon       Read and Understand This Catalog  Please read and understand this catalog before purchasing the products  Please consult your OMRON representative if you have any questions or  comments     Warranty and Limitations of Liability    WARRANTY    OMRON s exclusive warranty is that the products are free fro
2.    Set a communications unit number on SW1 so that the host system  can identify the Controller        swi fo  i 2 fs f4  s je  7  s Jo Ja  B  c  b  E  F    Unit No   00  ot  o2 Jos  o4  os  os  o7  os  os  10  14  r2 f13  14  15    A    Default    Note  A unique unit number must be set for each node  Controller  on  the same communications line  Do not set the same unit  number for more than one node    If 17 or more Units must be connected  refer to the G3ZA Multi   channel Power Controller User s Manual  Cat  No  Z200      Communications Baud Rate    Set the baud rate for communicating with the host system on SW2     swat to  Baud rate 196  19 2  38 4  57 6   Do not set     A  Default       E Connection Configuration  Single phase SSR    R phase  S phase  T phase              Load power  supply   Trigger  signal    CT  4 channel model only     Load Load    Example for Connecting Two SSRs  e g   heater   e g   heater     Note  Connect a power supply with the same phase as the SSRs to  the load power supply terminals on the G3ZA     E Host Device Connection Example    G3ZA    Three phase SSR    R phase  S phase  T phase       Control  power  supply    CT  4 channel model only     Note  Connect to one of the three phases on the load power supply  input terminals of the G3ZA     Example of Connection to EJ1 Modular Temperature Controller       EJ1N TC4    EJ1C EDU    or  EJ1N TC2                         G3ZA G3ZA G3ZA  Connection port          Port A  connector   USB connectio
3.   Ver 2 0 or higher    Wire terminal k and terminal     Do not use terminal kt and terminal It    x Do not remove the attached resister        DIN Track End Plate  Stopper   PFP 100N PFP M    18  PFP 50N         7 30 15         50 ae  a ar      25 15  5 M4 spring  1 000  500   washer    Dimension in parentheses    are for the PFP 50N                             OmRON       Safety Precautions    G3ZA       Refer to Safety Precautions for All Power Controllers         N WARNING    Do not touch the terminals and the wires while power is  being supplied  Doing so may possibly result in electric  shock  Make sure that the terminal cover is installed  before using the product      gt            CAUTION    Do not allow pieces of metal  wire clippings  or fine  metallic chips or filings from installation to enter the  product  Doing so may occasionally result in electric  shock  fire  or malfunction     Do not use the product in locations of flammable or  explosive gases  Doing so may occasionally result in  minor or moderate explosion  causing minor or moderate  injury  or property damage     Do not attempt to disassemble  repair  or modify the  product  Doing so may occasionally result in minor or  moderate injury due to electric shock     Perform correct setting of the product according to the  application  Failure to do so may occasionally cause  unexpected operation  resulting in minor or moderate  injury  or damage to the equipment     Ensure safety in the event of product fail
4.   aa Hole diameter     po Name   Mode     current DIN Track PFP 100N  Current Transformer Oto50A  E54 CT1 PEP 5ON      12 0dia    Oto50A __ E54 CT3     CT  12 0 dia  Oto50A  E54 CT3 ETE SI  30 0 dia  Oto150A  G3ZA CT 150L         Be sure to read the precautions for correct use and other precautions in the following users manual before using the  1 Power Controller   l l  l l    G3ZA Multi channel Power Controller User   s Manual  Cat  No  Z200        G3ZA  Specifications       E Ratings    Load power supply 100 to 240 VAC 400 to 480 VAC  Item voltage range    Power supply voltage 100 to 240 VAC  50 60 Hz   Operating voltage range 85 to 264 VAC    Load power supply voltage 100 to 240 VAC 400 to 480 VAC  Load power supply voltage range 75 to 264 VAC 340 to 528 VAC  Manipulated variable input 0 0  to 100 0   via RS 485 communications     Current transformer input  See note 1   Single phase AC  O to 50 A  primary current of CT   Single phase AC  O to 150 A  primary current of CT    Trigger output One voltage output for each channel  12 VDC  15   Max  load current  21 mA   with built in short circuit protection circuit     Alarm output NPN open collector  one output  Max  applicable voltage  30 VDC  Max  load current  50 mA    Residual voltage  1 5 V max   Leakage current  0 4 mA max     LED indicators    Optimum cycle control  Soft start optimum cycle control  See note 2    Three phase optimum cycle control    Ambient operating temperature    10 to 55  C  with no icing or condens
5.  re    Models with 4 Channels  Control Points    CT Inputs  and Heater Burnout Detection    Trigger output  12 VDC  21 mA    Trigger output    Trigger output  12 VDC  21 mA    Trigger output       D       24  18                   SW1   Alarm output connector  See note 2     only models with load power supply  voltage of 400 to 480 V         30 VDC  50 mA        Alarm output         OOOG0  GOO    O    SIO    Sw2  Models with Load Power  Supply Voltage of 400 to 480 V    Om m OO  RS 485 4 A    B            Power supply voltage    100 to 240 VAC  50 60 Hz          O00000              Load power supply voltage  400 to 480 VAC  50 60 Hz    Note  Connect the power supply  100 to 240 VAC  for the  G3ZA across terminals 1 and 2 and the load power  supply for the SSR loads across terminals 4 and 6        Operation Indicators    Operation indicator   Meaning       READY  Green  Lit while power is being supplied   SD RD  Orange  Lit while communicating with the host     OCC  Orange  Corresponds to the RUN and STOP operating    commands   Lit during operation      Lights or flashes when an error is detected   Setting Switches    e Always turn OFF the power supply before setting the switches  The  switch settings are read only when the power supply is turned ON    e Use a flat blade screwdriver to set the switches and be sure not to  leave a switch set between two settings        x   gt  X  2  Q v Q D   O  PA O S  a Oy A Oy   68 i 68 Lo  SW1 SW2    oOmRon       Communications Unit Number 
6.  terminals  M3   width  5 8 mm max   for wiring and attach insulative sleeves  To  connect bare wires  use AWG22  cross section  0 326 mm   to  AWG 14  cross section  2 081 mm   to wire the power supply  terminals and AWG22  cross section  0 326 mm   to AWG16   cross section  1 039 mm   for other terminals    7  Be sure to confirm the correct terminal and polarity when wiring   the terminal block and connectors      Do not connect any conductors to unused terminals      In order to prevent inductive noise  wire the lines connected to the  product separately from power lines carrying high voltages or  currents  Do not wire in parallel with or in the same cable as  power lines  Other measures for reducing noise include running  lines along separate ducts and using shield lines     1S     oa A    oO       OMRON    10 Attach a surge suppressor or noise filter to peripheral devices that  generate noise  in particular  motors  transformers  solenoids   magnetic coils  or other devices that have an inductance  component    Do not install the product near devices generating strong high   frequency fields or surges  When using a noise filter  check the  voltage and current and install it as close to the product as  possible      For a safety disconnection of the power line in the application  the  equipment must be provided with disconnecting devices suitable  for isolation     e g   circuit breakers defined in IEC60947 2  power switches  defined in IEC60947 3  power plugs  etc      V
7. Multi channel Power Controller    G3ZA    Optimum Cycle Control for High precision  Control with Low Noise     0791C 167V DIS A   e       e Smaller than a Normal Power Controller     e Enables low noise power control in combination with zero cross  SSRs   See note      e One Controller can control up to 8 SSRs     e RS 485 communications to set manipulated variables and  heater burnout detection  The Smart FB Library for the G3ZA  can also be used     e CE Marking       Main Upgraded Functions  e Soft start function added for lamp heaters     e Three phase optimum cycle control added for three phase  heaters     e Combining with special CT for150 A current detection     Note  The G3ZA must be used in combination with an SSR without the  zero cross function when the soft start function is used        AN Refer to Safety Precautions on page 9              Features       Comparison between the G3ZA and Normal Power Controllers  O nem   __NormalPowerControllers              o               oa         O                 Connections Power Controllers Controlled Using Current Output of 4   Control Using Communications from a Host Device    e Direct connection is possible using an EJ1 Modular  Temperature Controller     Multi channel Temperature Controller EJIN EJ1N TC4 or EJ1C   HFU   EJ1N TC2  EDU                         Modular Temperature  Controller  EJ1           Power Controller Power Controller Power Controller    DPAP j   i  ey  w    o Eight SSRs    4 to 20 mA commands Program
8. applicable third party certification documents identifying ratings and limitations of use that apply to the  products  This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product   machine  system  or other application or use     The following are some examples of applications for which particular attention must be given  This is not intended to be an exhaustive list of all possible  uses of the products  nor is it intended to imply that the uses listed may be suitable for the products     Outdoor use  uses involving potential chemical contamination or electrical interference  or conditions or uses not described in this catalog     Nuclear energy control systems  combustion systems  railroad systems  aviation systems  medical equipment  amusement machines  vehicles   safety equipment  and installations subject to separate industry or government regulations     Systems  machines  and equipment that could present a risk to life or property   Please know and observe all prohibitions of use applicable to the products     NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE  SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS  AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND  INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM     PROGRAMMABLE PRODUCTS  OMRON shall not be responsible for the user s programming of a 
9. ation       ion     Indications  Control method    Note  1  CT inputs are provided only on Models with heater burnout detection   2  Use an SSR without the zero cross function  G3PA LIBL VD  for soft start optimum cycle control   Refer to G3PA for details         E Performance    Current indication   Current Range  accuracy 0to50A  3A  O to 150A   9 A  0 to 100    6   See note     for models with heater burnout detection     100 MQ min   at 500 VDC  between primary  and secondary    Dielectric strength   2 000 VAC  50 60 Hz for 1 min between  primary and secondary    Insulation  resistance    Vibration  resistance    Vibration frequency  10 to 55 Hz   acceleration  50 m s  in X  Y  and Z directions    300 m s  three times each in six directions  along three axes    Approx  200 g  including terminal cover   Degree of    IP20   protection   Memory protection   EEPROM  non volatile memory   number of  writes  100 000     Installation Overvoltage category Ill   environment pollution degree 2  according to IEC 60664 1     UL508  Listing   CSA22 2 No  14  EN50178   EN61000 6 4  EN55011  1998  A1  1999  Class A  Group 1    EN61000 6 2  2001    Shock resistance    Approved    standards    Note  When measured with percentage selected for the current  monitor parameter and the maximum current measurable with  the CT at 100      OMRON       E Communications Specifications    Multipoint  RS 485   1  vi  S      Communications method    Max  transmission distance  31  via multidrop connect
10. ch phase for a  Control Capacity of 50  when a three phase heater SSR is connected     Load power    supply    R S phase AAAA AAAA AA    st phase JLA A      A Of NO  VUV VVVUVVVVV V    tol DAANAAALDADA  VVVVVVVUV       Connections    G3ZA       E Terminal Arrangement    Models with 8 Channels  Control Points    No CT Inputs  and No Heater Burnout Detection    Trigger output    Trigger output    12 VDC  21 mA 12 VDC  21 mA    Trigger output          CH6 COM CH7 CH8    Trigger output  12 VDC  21 mA N        Trigger output        Trigger output  12 VDC  21 mA    Trigger output       l 19  13                  Models with Load Power Supply Voltage ERROR  of 100 to 240 V       7  1    Alarm output  30 VDC  50 mA    o    Power supply voltage    100 to 240 VAC  50 60 Hz    Load power supply voltage  100 to 240 VAC  50 60 Hz       Note  Connect the power supply  100 to 240 VAC  for the  G3ZA across terminals 1 and 2 and the load power  supply for the SSR loads across terminals 4 and 6     Note  1  The following CTs can be used  sold separately    0 to 50 A  E54 CT1 and E54 CT3  O to 150 A  G8ZA CT150L    2  Use C Grid SL connectors from Molex Inc     C Grid SL Housing  Model  50 57 9406  70066 0180       Fart Number   Packaging  Wire size      Housing  5057 0406             Crinp  16 02 0069  Reel __ AWG  24 10 50  Terminal  76 02 0086  Reel ___ AWGH22 to 24       Hand      63811 8800  _  AWGi f24 to 30  Crimp Tool  63811 8700 _   AWG 22 to 24    PPPG  SOO    1 2  14 15  gt  16 17  ee
11. ersion 1 0 Usage Precautions    Version 1 0 is for single phase loads only  Connect a single phase  zero cross SSR  Do not connect a three phase SSR  or to an SSR  that is not magnet relay or zero cross     Version 2 0 Usage Precautions    e Check the G3ZA settings and select the correct SSR from the  following when wiring an SSR     e SSR with zero cross function for single phase heaters            e SSR without zero cross function for single phase heaters  e Three phase SSR  Do not connect a magnet relay     e Check the G3ZA settings and select the correct CT from the  following when wiring a CT     e E54 CT 1  e E54 CT3  e G3ZA CT150L       E Precautions for Correct Use  Wiring    Use M3 crimp terminals     A   Y   A  Fo  5 8 mm max    Y    Use wires that withstand a minimum of 70  C   DIN Track    Secure the DIN Track with screws in at least three locations     DIN Track  PFP 50N  50 cm  PFP 100N  100 cm                       Mounting the G3ZA    Mount the G3ZA as shown in the diagram  First  pull down the DIN  Track mounting hook  1  and hook the top of the G3ZA on the DIN  Track  2   Then press the G3ZA onto the DIN Track far enough so   that it can be locked in place  3  and push the DIN Track mounting  hook up to lock the G3ZA in place  4       1   4     Removing the G3ZA    Use a flat blade screwdriver to pull down the DIN Track mounting  hook  1  and then pull out on the bottom of the G3ZA  2      ALL DIMENSIONS SHOWN ARE IN MILLIMETERS     G3ZA  Mounting End Plates
12. ions  Synchronization method top start synchronization      ions   Communications baud rate 9 6  19 2  38 4 or 57 6 kbps   Default  9 6 kbps    ASCII  Communications data length  7 or 8 bits  Default  7  Communications stop bits 1 or 2 bits  Default  2    Communications parity Vertical parity  None  even  or odd  Default  Even    W Current Transformer Specifications   Order Separately     nem   Specification  Model number E54 CT1 E54 CT3 G3ZA CT150L    Max  continuous 50 A 120 A 150 A   heater current  See note     Detection current 50 A 150 A   with G3ZA   Dielectric strength  1 000 VAC for 1 min 2 000 VAC for  1 min    connected  Weight Approx  11 5 g   Approx  50 g  Approx  130 g    Accessories None Connection  None  terminals  2   Plugs  2     Note  The maximum continuous current is 50 A for the G3ZA in combination  with the E54 CTS           Applicable SSR and Control Methods    The G3ZA can be used for a variety of applications by selecting the  SSR drive  For example  inrush current can be reduced at startup by  selecting soft start optimum cycle control if a single phase halogen  heater is used     Control CT 4 channel   Example of  method models only    supported  heater    Single phase Optimumcycle  O to50Aor0O  Single phase  heater SSR with control heater  zero cross function       Soft start    Single phase  heater SSR without   optimum cycle  to 150 A  4  zero cross function   control Units heater    0to50Aor0  Single phase  halogen    Three phase Three phase  Ot
13. ld enables switching to soft start control when the current  value is below the set value  and switching to optimum cycle control  when the current value is above the set value  The default setting is  20 0      Variable Parameter Setting  type range    85 C5 Ch1 to Ch8 Control 0 0  to 20 0  Switching MV  Threshold    100 0   Example  For channel 1  soft start optimum cycle control is  performed under the following conditions  control switching MV   40 0   MV  100    soft startup time  20 s      1  Ch 1 Control Switching MV Threshold is set to 40 0  and Ch1  MV is set to 100 0  by writing to the variable area     2  Ch1 Soft Startup Time remains at the default  Setting is not  required     3  Once the Control Switching MV Threshold is written  the  changes are saved and become enabled the next time the  power is turned ON        MvV Control Capacity    100 0     40 0           A    Time    Soft startup time  20 s     AAANANAANAA  VVVVVVV VV V    Soft start Optimum cycle control       A  v  A  v    Three phase Optimum Cycle Control    e Three phase optimum cycle control is a control method that turns  the output ON and OFF every two cycles     e Turning the output ON and OFF every two cycles enables optimum  cycle control for three phase heaters     e Use a three phase heater SSR with a zero cross function for three   phase optimum cycle control     Note  Refer to page 6 for details on connecting to three phase  heaters     The following figure shows the current waveform of ea
14. m defects in materials and workmanship for a period of one year  or other period if specified   from date of sale by OMRON     OMRON MAKES NO WARRANTY OR REPRESENTATION  EXPRESS OR IMPLIED  REGARDING NON INFRINGEMENT  MERCHANTABILITY  OR  FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS  ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS  DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE  OMRON DISCLAIMS ALL OTHER  WARRANTIES  EXPRESS OR IMPLIED     LIMITATIONS OF LIABILITY    OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL  INDIRECT  OR CONSEQUENTIAL DAMAGES  LOSS OF PROFITS OR COMMERCIAL LOSS  IN ANY WAY CONNECTED WITH THE PRODUCTS  WHETHER SUCH CLAIM IS BASED ON CONTRACT  WARRANTY  NEGLIGENCE  OR STRICT  LIABILITY     In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted     IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY  REPAIR  OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS  OMRON S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED  STORED  INSTALLED  AND MAINTAINED AND NOT  SUBJECT TO CONTAMINATION  ABUSE  MISUSE  OR INAPPROPRIATE MODIFICATION OR REPAIR     Application Considerations    SUITABILITY FOR USE    OMRON shall not be responsible for conformity with any standards  codes  or regulations that apply to the combination of products in the customer s  application or use of the products     At the customer s request  OMRON will provide 
15. mable Controller    Serial Communications Unit  RS 485     Power controller Power controller Power controller Power controller                8 total 8 total  Control method   Phase Control Optimum Cycle Control  High precision Zero Cross Control   e Response is fast and high precision temperature control    Outputs are turned ON and OFF each half cycle   is possible  e Zero cross control is performed   e Harmonics and noise are problems  e Noise is suppressed while achieving high speed response with    high precision temperature control        OmRON       G3ZA  Model Number Structure    E Model Number Legend  G3ZA OOOOO O 0          12 3 45 6 7    No    Meaning   Code   Specifications    No   Meaning        s  Code   Specifications  Z No  of control points Load power supply voltage 100 to 240 VAC    e  echamos a  40010 480 VAC  2   Control method Optimum cycle control 5 Communications specifications RS 485  Heater burnout detection 6   Communications protocol CompoWay F  None    International standards Approved by T  V  UL  and  CSA     Ordering Information    E List of Models    Neme Number of control channels Load power supply voltage   Modei    Multi channel Power Supported 100 to 240 VAC G3ZA 4H203 FLK UTU  Controller 400 to 480 VAC G3ZA 4H403 FLK UTU    Not supported 100 to 240 VAC G3ZA 8A203 FLK UTU  400 to 480 VAC G3ZA 8A403 FLK UTU    Note  When using the heater burnout detection function  CTs must be ordered separately              E Accessories  Order Separately   
16. n possible  using a E58 CIFQ1  sold separately     Port B  RS 485  CompoWay F     Connection port                              De GOOG  MaOGDO 2    Load power supply   for zero cross detection     Power supply for  Multi channel  Power Controller    OMRON            Eight SSRs          G3ZA  Dimensions       Note  All units are in millimeters unless otherwise indicated   E Multi channel Power Controllers    G3ZA 4H203 FLK UTU  G3ZA 4H403 FLK UTU  G3ZA 8A203 FLK UTU  G3ZA 8A403 FLK UTU          Mounting Hole Dimensions   For Direct Mounting     Two  4 2 dia  or M4                    POOOOO  PPPLPPP                                     84 84 0 3  peo  PPPOPO  pas  i To e Loo i  i R 2 3 a we ma   J     35 0 3     gt     oOmRon       G3ZA  E Accessories  Order Separately     Current Transformer  CT   E54 CT1         21       2 8    5 8 dia  Fla    T  il    ie  ice    ps    rl                                        Two  3 5 dia   EE  n   a   so a   Current Transformer  CT   E54 CT3   20     2 36 dia  E54 CT3 Accessories      e Contactors Contactor    UE  H A TE    i 18         40 x 40                            Two  M3  depth  4  e Plugs    cen  15        o        Approx  6 dia       30            a  22  a             Current Transformer  CT   G3ZA CT150L    26 max     Mounting Hole Dimensions          Two M5 screw holes or  two 5 5 dia  holes    Go                          Zd    LL                                   Note  The G3ZA CT150L is for use only in combination with the G3ZA
17. o change without notice     OMRON Corporation    Industrial Automation Company    http   www ia omron com    c Copyright OMRON Corporation 2012 All Right Reserved     
18. o50Aor0  Three phase  heater SSR with optimum cycle  to 150 A  up to   heater  zero cross function   control 2 Units    Optimum Cycle Control    e Optimum cycle control is performed by driving SSRs according to  load power detection and trigger signals   Zero cross SSRs are  used     e Noise is suppressed while ensure high speed response by turning  outputs ON and OFF each half cycle to achieve high precision  temperature control     1 5th ON  20      Control  Capacity  20     Note  Refer to Connection Configuration on page 6 for connecting to  an SSR     Soft start Optimum Cycle Control    e Soft start and optimum cycle control enables control of outputs with  limited inrush current even for loads with characteristics like halo   gen heaters     e Use a single phase heater SSR  without the zero cross function   for soft start optimum cycle control  Refer to G3PA for details on  SSRs without the zero cross function    e Set the Soft start Up Down Time to control output    e Current is not detected during Soft start  The current value  heater  ON current value  heater OFF current value  and effective current  value  will be O A  and the current error alarm  heater burnout  detection  SSR short circuit detection  and heater overcurrent  detection  will always turn OFF     OMRON       G3ZA  Setting the Control Switching MV Threshold    The Control Switching MV Threshold function is enabled when soft   start optimum cycle control is used  Setting the Control Switching MV  Thresho
19. programmable product  or any consequence thereof     Disclaimers    CHANGE IN SPECIFICATIONS    Product specifications and accessories may be changed at any time based on improvements and other reasons     It is our practice to change model numbers when published ratings or features are changed  or when significant construction changes are made   However  some specifications of the products may be changed without any notice  When in doubt  special model numbers may be assigned to fix or  establish key specifications for your application on your request  Please consult with your OMRON representative at any time to confirm actual  specifications of purchased products     DIMENSIONS AND WEIGHTS    Dimensions and weights are nominal and are not to be used for manufacturing purposes  even when tolerances are shown     PERFORMANCE DATA    Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty  It may represent the  result of OMRON   s test conditions  and the users must correlate it to actual application requirements  Actual performance is subject to the OMRON  Warranty and Limitations of Liability     ERRORS AND OMISSIONS    The information in this document has been carefully checked and is believed to be accurate  however  no responsibility is assumed for clerical   typographical  or proofreading errors  or omissions        2012 4  In the interest of product improvement  specifications are subject t
20. ure by taking  safety measures  such as installing a separate monitoring  system to provide alarms for preventing excessive  temperature rise  Product failure may occasionally  prevent control operation  resulting in damage to the  connected facilities and equipment     Tighten the terminal screws securely using a tightening  torque within the following ranges  Loose screws may  occasionally cause fire  resulting in minor or moderate  injury  or damage to the equipment    Terminal screws  0 40 to 0 56 N m    E Precautions for Safe Use      Do not use the product in the following locations   e Locations subject to direct radiant heat from heating equipment          Q0        l    e Locations where the product may come into contact with water  or oil    e Locations subject to direct sunlight    e Locations where dust or corrosive gases  in particular  sulfuric  or ammonia gas  are present    e Locations subject to extreme temperature changes  e Locations where icing or condensation may occur  e Locations subject to excessive shocks or vibration    N      Use this product within the rated load and power supply      Ensure that the rated voltage is achieved no longer than 2 s after  turning the power ON      Use store within the rated temperature and humidity ranges      Minimum mounting distance of G3ZA is 10 mm    When mounting the G3ZA near the SSRs  mount the G3ZA so as  to not interfere with the heat dissipation of the SSR    6  Use the specified size of insulated type crimp
    