1. Last Updated 10 March 2009 TB 960704B Technical Bulletin Communicating with Honeywell ST3000 STT3000 Smart Transmitters OMNI FLOW COMPUTERS INC 2 SW e 12620 West Airport Boulevard Suite 100 US Omni Sugar Land Texas 77478 United States of America Phone 281 240 6161 Fax 281 240 6162 www omniflow com 52 0003 0001 Rev B TB 960704B Communicating with HoneywellTM ST3000 STT3000 Smart Transmitters NOTE User Manual Reference This Technical Bulletin complements the information contained in the User Manual and is applicable to all firmware revisions This Technical Bulletin was previously published as an appendix to user manuals of firmware revisions Version 70 and earlier Communication with Honeywell ST3000 STT3000 Smart Transmitters This feature allows you to communicate with Honeywell Smart Temperature and Pressure Transmitters via OMNI s type Process I O Combo Module and using Honeywell s DE Protocol Table of Contents SO OPIS e E 3 ADStraACh 3 Digitally Enhanced DE Protocol Overview oreet ertt t eb e eb pere 3 Transmitter Database siento pi kash des ei aAa EENAA AEA tod ada en A dofus 3 Using the Honeywell Handheld nmn 3 Combo Module LED Status Indicators ret o ione epe eui eder eid eR e ERE 4 Switching Between Analog a
2. he handheld communicator The digital signal can be calibrated using the normal OMNI analog input method described in Chapter 8 of Volume 1 52 0003 0001 Rev Omni Page 3 of 7 TB 960704B Communicating with HoneywellTM ST3000 STT3000 Smart Transmitters Combo Module LED Status Indicators Each I O channel of the H Combo module has a set of two 2 LED indicators one 1 green and one 1 red The green LED shows all communication activity taking place on the channel flow computer transmitter and handheld communicator if connected The Red LED lights only when the flow computer is transmitting data to the transmitter Normal digital operation is indicated by a regular pulsation of the green LED about 3 per second The red LED will be seen to blink whenever a configuration change is made in the flow computer which affects that particular transmitter Switching Between Analog and Digital Mode Auto Mode Connecting an analog mode Honeywell smart transmitter to the computer will cause the flow computer to automatically switch the transmitter to the digital DE mode sending out a communication request to the Honeywell transmitter A switch over to the digital mode by the transmitter will cause the green LED on the H combo module to pulse steadily indicating that communications have been established Manual Operation For manual operation do the following e Disable communications between the Honeywell transmitter and t
3. he flow computer by deleting all I O point assignments within the flow computer to that I O point e Using the Honeywell SFC SCT or any Honeywell handheld communicator press Shift A D and wait till the handheld displays Change to Analog e Answer Yes by pressing Enter SFC Working will be displayed The H Combo module s green LED on that channel will stop pulsing e Re enter the I O point to cause the OMNI to send the communication request command to the Honeywell and after three 3 commands send the green LED on the Honeywell module will pulse at a steady 3Hz rate Viewing the Status of the Honeywell Transmitter from the OMNI Front Panel To verify the data being received from the smart transmitter press Input Status and Enter from the front panel The following displays H1 2 Transmitter 25 00 IDLE 0 150 0 00 Conformity bit SW Revision 2 1 Serial Transmitter Type GP 3000 PT202 00 H1 2 Transmitter Indicates the Honeywell Combo Module H1 the channel number on that module Channel 2 in this case PV Process variable value in percentage of the transmitter s span A 25 00 displayed on the OMNI could mean that the transmitter is not communicating refer to Status 52 0003 0001 Rev B NS Omni Page 4 of 7 TB 960704B Communicating with HoneywellTM ST3000 STT3000 Smart Transmitters Status LRV Span Damp Seconds Conform
4. in engineering units The transmitter will not accept configuration entries which exceed this value ASCII string used to identify the transmitter 52 0003 0001 Rev B Y Omni Page 5 of 7 TB 960704B Communicating with HoneywellTM ST3000 STT3000 Smart Transmitters SV Secondary Process Variable Value expressed in C This represents sensor temperature for pressure transmitters and junction temperature for temperature transmitters The flow computer may or may not have a value in this field depending upon whether the SV is included in the part of the transmitter s database which is sent to the OMNI 52 0003 0001 Rev Omni Page 6 of 7 TB 960704B Communicating with HoneywellTM ST3000 STT3000 Smart Transmitters DOCUMENT REVISION HISTORY DOCUMENT INITIAL RELEASE DATE incaiatdencatnnd ax ERA 03 May 2003 REVISION DATE PURPOSE CHANGE REQUEST A 03 May 2003 Maintained on the Web Initial release B 10 March 2009 DCR 090079 52 0003 0001 Rev B Y Omni Page 7 of 7
5. ity Bit Software Revision Serial Transmitter Type URL ID TAG There are five status states 1 OK Communications between the flow computer and smart Honeywell transmitter are OK The database within the transmitter matches the flow computer 2 Idle This flow computer I O point has been assigned to a Honeywell transmitter but is not receiving data from the transmitter Possible cause is a wiring problem such as reversal of wiring If you observe the status LEDs you will note that the flow computer attempts to establish communications by sending a wake up command every ten 10 seconds or so 3 Bad PV Communications between the flow computer and smart Honeywell transmitter are OK but the transmitter has determined that a critical error has occurred within the transmitter meaning the value of the process variable cannot be trusted The flow computer will set the transducer failure alarm and follow the fail code strategy selected by the user for this transducer 4 DB Error Communications between the flow computer and smart Honeywell transmitter are OK but the flow Computer has determined that the database within the flow computer does not agree with the database within the transmitter If you observe the status LEDs you will note that the flow computer attempts to correct the transmitters database by writing the correct data to the transmitter once every 30 45 Seconds or so 5 4 Byte The transmitter is operating in
6. n the 6 byte Broadcast Mode In this mode the transmitter transmits the following data to the flow computer every 366 msec Byte 1 Status Flags Byte 2 4 Process Variables Span Value 3 byte floating point Byte 5 Database ID indicates where in the transmitter s database Byte 6 below belongs Byte 6 Database Data Value Transmitter Database By using the data contained in Bytes 5 and 6 the flow computer builds and maintains an exact copy of the smart transmitters configuration database A transmitter database varies in size from about 90 bytes for a pressure transmitter to 120 bytes for a temperature transmitter It takes between 30 and 45 seconds to completely build a copy of the transmitter database within the flow computer The transmitter database is continuously compared against the flow computer configuration settings for that transmitter The flow computer automatically corrects any differences between the databases by writing the correct configuration data to the transmitter Using the Honeywell Handheld Communicator The flow computer is responsible for configuring entries within the transmitter 1 Lower Range Value LRV or Zero 2 Transmitter Span or Upper Range Limit URL 3 Damping Factor 4 Tag Name Any changes made to one 1 two 2 and three 3 using the handheld communicator will be overwritten by the flow computer In the digital mode it is not necessary to calibrate the transmitter output using t
7. nd Digital nennen 4 A to MOG E 4 Manual OD Graton T L 4 Viewing the Status of the Honeywell Transmitter from the OMNI Front Panel 4 52 0003 0001 Rev Omni Page 2 of 7 TB 960704B Communicating with HoneywellTM ST3000 STT3000 Smart Transmitters Scope All firmware revisions of OMNI 6000 OMNI 3000 Flow Computers have the feature of communicating with Honeywell ST3000 Smart Transmitters This feature uses Honeywell s Digitally Enhanced DE Protocol and requires that an H Combo I O Module be installed in your flow computer Abstract Using H Combo I O Modules the OMNI Flow Computer can communicate with Honeywell Smart Temperature and Pressure Transmitters using Honeywell s DE Protocol Up to four 4 transmitters can be connected to each H Type Combo Module with loop power being provided by the combo module Digitally Enhanced DE Protocol Overview Digital data is transmitted serially between the flow computer and Honeywell Smart Transmitters by modulating the current in the two wire loop connecting the devices Power for the transmitter is also taken from this current loop Data is transmitted at 218 47 bits per second with a digital 0 20 mA and a digital 1 4 mA In normal operation the Honeywell transmitter operates i
8. the 4 Byte Broadcast Mode Because the flow computer will not tolerate this mode of operation this status display should only be displayed momentarily as the flow computer will automatically switch the transmitter into the 6 Byte Broadcast Mode Lower Range Value of the transmitter in engineering units Engineering units are degrees Celsius for temperature transmitters inches of water for differential pressure transmitters and pounds per square inch for pressure transmitters The Span of the transmitter in engineering units the Span is the difference between the lower and upper ranges of the transmitter Engineering units are degrees Celsius for temperature transmitters inches of water for differential pressure transmitters and pounds per square inch for pressure transmitters The flow computer will display DB Error if the user tries to enter a span of 096 or a span which would exceed the transmitter s upper range limit URL Damping Time of the transmitter output in seconds Meaningful only with differential pressure transmitters Conformity Bit 0 linear output Conformity Bit 1 square root output This bit should always be 0 for smart temperature transmitters Current Software installed within the smart device Serial Number of the smart transmitter Valid transmitter types are TT Temperature Transmitter DP Differential Pressure Transmitter GP Gauge Pressure Transmitter Upper Range Limit of the transmitter