1. SSL State The SSL of the LINQ8PD CB can be turned on and off by clicking Turning SSL On Turning SSL Off button Change Username and Password Field Name Description Username Enter the new Username up to 32 characters required to access the LINQ8PD CB Password Enter the new Password up to 32 alpha numeric characters required to access the LINQ8PD CB Confirm Password __ Re enter the new Password Click Save Username and Password button a dialog box with appear New settings have been applied click OK After saving the new username and password will be active 4 Event Log and Heartbeat Timer Fig 10 pg 12 Fig 10 Click Event Log tab The LINQ8PD CB event log will open 5 This screen will display the event log along DP Altronix Device M anagement Interface LING with the heartbeat timer setup Status Setup Network Settings Security Settings Events Log Help v1 99 22 oo Ls Event Lo Event Log The event log will display the Site ID LINQ8 S Monday Sept 21 2015 2 30 pm 50 most recent events Display Refresh Log Heartbeat Timer Settings Last updated To update the Event Log click Display Refresh Log masias button the most recent events will be displayed T 7 Days 0 Hours 0 Y Minutes 0 w Seconds Submit Heartbeat Timer The heartbeat timer will send a tr
2. EZ U Aioneg asna w mE Ww EES UN eno asna Ww EES Ww ETES w eLo asna w PESA w EES 11901 iva 1 E I DODDDODOIDDDODODD OUT1 OUT2 OUT3 OUT4 OUTS OUT6 OUT7 OUTB OOOO AC Fail u lt Battery Fail o LINQ8PD LINQ8PDCB Terminal Connector Identification Terminal Legend Description A GND RESET FACP reset GND FACP EOL Connects to EOL or next LINQ8PD CB RET FACP EOL or next LINQ8PD CB D FACP IN Wet input from FACP FACP RLY 1 2 FACP reporting relay E Downlink Connection to power supply or second LINQ8PD CB module Uplink Connects to next LINQ8PD CB upstream from this module If this is the first LINQ8PD CB in the daisy chain this connector is not used BAT Local LED Indicates battery ies thresholds D FACP AC BAT LEDs Indicates status of FACP AC and Battery D Heartbeat LED Indicates the LINQ8PD CB is operational WI RJ45 Ethernet LAN or laptop connection enables LINQ8PD CB programming and status monitoring USB Laptop connection enables LINQ8PD CB initial setup and programming N Battery Fail Indicates low battery condition e g connect to alarm panel Relay normal
3. 192 168 168 200 Submit Trap Receiver IP Settings eC From event report linginfo E Subject Username event report Password SMTP server IP smtp gmail com SMTP server Port 587 Outgoing Email Address 1 Outgoing Email Address 2 Outgoing Email Address 3 Outgoing Email Address 4 Outgoing Email Address 5 Submit Test Email Submit Email Settings Restore Factory Settings Reboot Server ar SNMP Port Settings SNMP Port Trap Message Port 161 162 Submit Port Settings Field Name Description Subnet Mask When operating in DHCP the router will assign the subnet mask values Gateway TCP IP gateway of the network access point router being used will be displayed Enter the HTTP port number assigned to the LINQ8PD CB module by the network administrator to allow remote access and monitoring The default inbound HTTP Port port setting is 80 HTTP is not encrypted and unsecure Even though HTTP can be used for remote access it is recommended primarily for use with LAN con nections HTTPS Port Enter the HTTPS port number assigned to the LINQ8PD CB module by the network administrator to allow remote access and monitoring The default inbound port setting is 443 Bei
4. FACP Status Indicates FACP status of the output LINQ8PD LINQ8PDCB 14 Notes LINQ8PD LINQ8PDCB LINQ8PD LINQ8PDCB Notes Notes Altronix is not responsible for any typographical errors Product specifications are subject to change without notice ps 140 58th Street Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Made in U S A u SINN der IILINQ8PD K020 MEMBER 16 LINQ8PD LINQ8PDCB
5. Network Setup Altronix Dashboard USB Connection The USB connection on the LINQ8PD CB is used for Network and Trap Receiver configuration only When connected to a PC via the USB cable the LINQ8PD CB will receive power from the USB port allowing programming of the LINQ8PD CB prior to being connected to the power supply 1 Install the software supplied with the LINQ8PD CB on the PC being used for programming This software should be installed on all computers that will have access to the LINQ8PD CB 2 Connect the supplied USB cable to the USB port on the LINQ8PD CB and the computer 3 Click Dashboard Icon on the desktop of the computer and open the Dashboard 4 Click USB Network Setup button located in the upper right hand side of the Dashboard This will open the USB Network Setup screen In this screen the MAC Address of the LINQ8PD CB module will be found along with the Network Settings Trap Receiver Settings and SNMP Port Settings 1 Network Settings Fig 2a pg 5 In the IP Address Method field select the method that the IP Address for Pies the LINQ8PD will be obtained Static or DHCP then follow the appropriate steps Dashboard USB Network Setup ecg STATIC Ling8 USB Network Settings Field Name Description MAC Address BC 34 00 30 01 77 nn Ps IP Address Enter the IP address assigned to the LINQ8PD CB by the Network Settings A Trap Receiver Settings B network administrat
6. 8 pg 10 Field Name Description Device ID Enter a descriptive name for the device connected to the output Current High Low Enter both the high current limit and low current limit in the appropriate fields for the connected Device 5 If either of these limits are exceeded an SNMP trap message and or email notification will be generated Voltage High Low Enter both the high voltage limit and low voltage limit in the appropriate fields for the connected Device If either of these limits are exceeded an SNMP trap message and or email notification will be generated 10 LINQ8PD LINQ8PDCB FACP Trigger Fig 8 pg 10 From the pull down menu select how the output will operate when the FACP input is triggered FACP Trigger Setting Function Description Inactive The selected output will not switch when the FACP input is triggered Non Latching The selected output will switch when the FACP input is triggered and reset when the FACP trigger input is returns to a non triggered state The selected output will switch to a latched position when the FACP input is triggered The selected output will remain latched until Latching nd the Output Reset is triggered Battery Backup Fig 8 pg 10 From the pull down menu select Yes if the output will remain ON in the event of a power failure Select No if the output will turn OFF in the event of a power failure Output Status Fig 8 pg 10 Output St
7. Batteries should be inspected at least once a year Even though the expected battery life is 5 years it is recommended changing batteries in 4 years Max Charge Current Output Relay configuration Fig 7 pg 10 Three 3 output relays of the LINQ8PD CB can be configured for various uses From the pull down menu select the desired setting for each relay Output Relay 1 Setting Description AC The relay will energize when AC trouble is detected Com Trouble The relay will energize when on all trouble conditions Fig 7 Output Relay 2 Bat Capacity 7 AH Battery Service Date o2 02 2015 Battery The relay will energize when Battery trouble is detected SI 20 Oupa Com Trouble y Tamper The relay will energize when the tamper input is triggered en 2 75 A Output Relay 2 Tamper Y Output Relay 3 Max Charge Current 0 9 A Output Relay 3 FACP VY FACP The relay will energize when the FACP input is triggered Tamper The relay will energize when the tamper input is triggered Fig 8 Output Device ID Current High A Current Low A Voltage High V Voltage Low V FACP Trigger Battery Backup Output Status 1 Enter ID 3 0 27 7 3 Latching v Yes Y On Off Output Configuration Fig
8. voltage of each of the eight outputs This helps avoid potential damage Disconnect the AC mains of the connected power supply ies Note Do connect AC and DC simultaneously to INP1 and INP2 Output Connections Connect devices to be powered to the terminals marked OUT1 to OUT8 on LINQ8PD CB carefully observing polarity When two power supplies are connected to the LINQ8PD CB verify that the output voltage matches the operating voltage of the connected devices Battery Connections Skip this step when connecting AC power supplies or DC power supply ies without batteries Connect the power supplies battery charging circuit to the terminals marked BAT IN connect the battery leads to the terminals marked BAT OUT Note Do not connect battery ies until all connections have been made For 24VDC operation connect two 12VDC batteries in series using the supplied yellow battery jumper For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of output voltage When the use of stand by batteries is desired they must be lead acid or gel type Battery and AC Supervision Connections Skip this step when connecting AC power supplies These connections are required to monitor AC and Battery Trouble conditions These conditions cannot be monitored when connected to a non supervised power supply Connect the common C and normally open N O contact of the power suppli
9. CB module email address Password Enter the username password SMTP server IP Enter the SMTP IP address of the in house email server SMTP server Port Enter the SMTP port assigned to the in house email server Outgoing Email Address 1 5 Enter up to five outgoing email addresses a Click Submit Email Settings button and the email settings will be saved Email service provider Field Name Description From Enter the email address for the LINQ8PD CB module Subject Identify the location of the LINQ8PD CB i e the Site ID Username Enter the username associated with the LINQ8PD CB module email address Password Enter the username password SMTP server IP Enter the SMTP IP address of the email service provider SMTP server Port Enter the email SMTP port number The default SMTP email ports are 25 or 465 unless otherwise specified Outgoing Email Address 1 5 Enter up to five outgoing email addresses a Click Submit Email Settings button and the email settings will be saved Altronix default email service Opos All required sender and network fields have already been populated Outgoing Email Address 1 5 Enter up to five outgoing email addresses Click Submit Email Settings button to save the email settings Test the email setup by clicking Test Email button An email will be sent to all Outgoing email addresses If the test email is not recei
10. Note When remote access is required or using multiple devices on the same network it is recommended to assign an independent port to each connected device HTTPS Port System Port Trap Receiver Settings Fig 2b pg 5 a Enter up to five SNMP trap receiver IP addresses When accessing the LINQ8PD CB remotely check with the network administrator for proper configuration b Click Submit Trap Receiver IP Settings button a dialog box will display New Trap Receiver IP settings will take effect after the server is rebooted click OK SNMP Port Settings Fig 2c pg 5 SNMP uses the default port 161 for general SNMP messages and port 162 for SNMP trap messages In the event these ports need to be changed enter the new port numbers assigned by the network administrator a Click Submit Port Settings button a dialog box will display New Port settings will take effect after the server is rebooted click OK b After all information has been entered Click Reboot Server button Fig 2d pg 5 a dialog box will display Please allow up to 30 sec for the server to reboot click OK After the LINQ8PD CB has been rebooted all programmed information will be saved d Disconnect the USB cable from the LINQ8PD CB module If the LINQ8PD CB has not been connected to the power supply ies being monitored refer to Installing LINOSPD Board on pg 2 e Connect one end of the
11. batteries are not connected If batteries are not connected skip this section PS1 PS2 Amps Voltage Limits Fig 5 pg 9 Fig 5 g Field Name Description PS1 Volts High Limit 27 7 V Enter both the Voltage Limit High and Voltage Limit Low for the connected power supplies If either of these PS1 Volts Low Limit 4 V PS1 PS2 Voltage Limit q i limits are exceeded an SNMP trap message and or email notification will be generated Seine ed A PS1 PS2 Amp Limit Enter both the Amp Limit High and Amp Limit Low for the connected power supplies If either of these limits DU P are exceeded an SNMP trap message and or email notification will be generated PS1 Amps Low Limit 0 A FACP Trigger Fig 6 pg 9 From the pull down menu select either Wet or Dry Select Description Wet Trigger Input voltage from the fire alarm signal circuit will disconnect all outputs programmed for FACP disconnect Dry Trigger A short or open on the supervised FACP input will disconnect all outputs programmed for FACP disconnect Fig 6 Input Function Fig 6 pg 9 From the pull down menu select either Reset or Tamper FACP Trigger Dry v Select Description Input Function Reset v Reset When using the FACP Interface with outputs set in latching mode the reset trigger input is designated as the FACP manual rele
12. D CB module will be found along with the programming fields for the Network Settings Trap Receiver Settings SNMP Port Settings and Email Settings Network Settings Fig 3a pg 7 In the IP Address Method field select the method that the IP Address for the LINQ8PD CB will be obtained Static or DHCP then follow the appropriate steps STATIC Fig 3a pg 7 Fig 3 N Device Management Interface TECHNOLOGY Status Setup Network Settings Security Settings Events Log Help Field Name Description IP Address Enter the IP address assigned to the LINQ8PD CB by the network administrator Subnet Mask Enter the Subnet of the network Gateway Enter the TCP IP gateway of the network access point router being used Note Gateway configuration is required to properly receive emails from the device Network Settings Site ID LINQ8 Monday Sept 21 2015 2 30 pm Network Settings Email Settings IP Address Subnet Mask Gateway HTTP Port HTTPS Port System Port MAC Address IP Address Method STATIC A 192 168 168 107 255 255 255 0 192 168 0 11 80 443 667 BC 34 00 30 01 72 Submit Network Settings HTTP Port Enter the HTTP port number assigned to the LINQ8PD CB module by the network administrator to allow remote access and monitoring The default inbound port set
13. Input Function FACP reset tamper Output Reset Trigger N O N C Battery Monitor Configuration Capacity Charge Level Max Charge and Discharge Current Service Date Configurable Output Relay s Individual Output Configuration Device ID Voltage and Current Limits High Low FACP Trigger Setting latching non latching inactive Battery Backup Terminal Connector Identification Network Security e Secure Socket Layer SSL Reporting SNMP trap messages e E mail notifications Event Log tracks history Fire Alarm Interface Supervised FACP disconnect Latching or Non Latching FACP reset N C or N O Mechanical Board Dimensions 5 5 L x 3 625 W x 0 96 H 139 7mm x 92 07mm x 24 38mm Product weight approx 0 4 Ibs 0 18kg Shipping weight approx 0 7 lbs 0 32kg GND GND RET FACPIN FACP RLY 2 RESET FACP EOL RET FACP IN FACP RLY 1 PEER i ENRZE DODDDOOD Er ee ov D ON 9 ON va synduj AUG OOOO o To 2 e LINQ8PD o lo e JE Altronix Corp 15 a Brooklyn NY 11220 S a z Ei pe E aha z 8 ir
14. LING Network Power Distribution Module Installation and Programming Manual LINQ8PD Network Power Distribution Module Eight 8 Fused Outputs LINQ8PDCB Network Power Distribution Module Eight 8 PTC Outputs Altronix DOC LINQ8PD Rev 110515 More than just power Overview Altronix LINQ8PD CB network power distribution module facilitates monitoring reporting and control of one 1 or two 2 low voltage AC or supervised DC power supply chargers over the network Reports diagnostics via Email SNMP notifications greatly reducing system downtime and eliminating unnecessary service calls LINQ8PD CB retrofits with most currently installed multi output power supply chargers Input Power Inputl Input2 12VAC 28VAC 12 5 amp each or 12VDC 28VDC 12 5 amp each Note Do connect AC and DC simultaneously to INP1 and INP2 Outputs Eight 8 fused or PTC protected outputs LINQ8PD Blade fuses are rated 3 amps LINQ8PDCB PTCs are rated 2 5 amps e Power output s can be locally or remotely controlled e Surge Suppression Status Monitoring e Power Supply ies output voltage and load Voltage and load of each output FACP trigger and reset status e Unit temperature Celsius e Power Supply AC and Battery status Battery health LINOSPD Fig 1 Specifications Programming Features e Power Supply ies voltage and load limits High Low FACP trigger type wet or dry N O N C
15. Name DE A Unit Name Name of the device Email Address aia Cea Nana Domain name or IP address of the server This is Submit SSL Settings ee eae typically assigned by the network administrator Email Address An email address used to contact the organization E e e O After all fields have been completed click Submit SSL Settings button a dialog box will appear Please allow up to 30 sec for server to reboot click OK A self signed SSL certificate will be generated with the information provided in the SSL certificate settings fields The certificate will be valid for 500 days and time stamped with the time settings present on the LINQ8PD CB module The date and time must be synced with the host computer before generating an SSL certificate Using a private SSL certificate and Key Private SSL Certificates and Keys must be uploaded using the Altronix Dashboard For additional information refer to the Altronix Dashboard setup user manual section Updating firmware SSL certificate and Key LINQ8PD LINQ8PDCB 11 SSL Status Certificate Status Fig 9b pg 11 Key Status Fig 9b pg 11 Message Descriptions Message Descriptions Certificate OK Valid SSL Certificate Key OK Valid SSL Key Bad Certificate Invalid SSL Certificate Bad Key Invalid SSL Key No Certificate A Valid SSL Certificate has not been loaded No Key A valid SSL Key has not been loaded
16. ap message indicating that the LINQ8PD CB is still connected and communicating 5 Setting the Heart Beat Timer a Click the button labeled Heartbeat Timer Setting b Select the desired time between heartbeat messaging in the Days Hours Minutes and Seconds in corresponding fields c Click the button labeled Submit to save setting 6 Updating Firmware Firmware updates must be done using the Altronix Dashboard For additional information refer to the Updating firmware SSL certificate and Key section in the Altronix Dashboard setup user manual 12 LINQ8PD LINQ8PDCB Fig 11 M Altronix Device Management Interface LIN LA ronIx g TECHNOLOGY Status Setup Network Settings Security Settings Events Log Help Status Monday Sept 21 2015 2 30 pm Site ID LINQ8 Minimize Minimize Others LINQ8PD ID LINQ8 DEV PS1 Output Voltage 27 5 VDC FACP Status Normal AC Status Normal Battery Charge Leve 100 PS1 Load FAO 255A Reset B Not Triggered Battery Status Normal Battery Current D 0 A Charging PS2 Output Voltage NUM 13 7 VDC Tamper Status Battery Capacity AL 7AH Battery Condition MZ Normal PS2 Load 2 55A Temperature 31 C Battery Voltage 27 3V Battery Service Date 11 05 2018 Output Device ID Output Current A Output Voltage VDC FACP Status 1 E Lobby 23 27 Normal 2 Main Office 0 5 13 6 Latchi
17. ase N When the outputs are set in non latching mode or the FACP interface is not being used Max Temp 50 C Tamper the reset trigger input Output Reset Trigger Fig 6 pg 9 From the pull down menu select either N O or N C Select Description N O Normally Open reset Trigger Input N C Normally Closed Trigger input Max Temp The LINQ8PD CB will measure the ambient temperature of the enclosure it is mounted in Entering a high temperature limit in Celsius if this limit is exceeded an SNMP trap message and or email notification will be generated LINQ8PD LINQ8PDCB 9 Battery Monitor Configuration Fig 7 pg 10 The LINQ8PD CB displays the real time battery health Select Description Battery Capacity Enter the battery rating in amp hours Battery Charge Level Enter the estimated percentage charge level of the Battery at the time of installation Max Battery Enter the high current limit to be drawn from the battery in the event of a power failure If this limit is exceeded an Discharge Current SNMP trap message and or email notification will be generated Enter the maximum charge current of the connected power supply If this limit is exceeded an SNMP trap message and or email notification will be generated Enter the date on which the installed batteries need to be serviced An SNMP trap message and or email notification will be generated on the entered date Battery Service Date Note
18. atus indicates if the output is On powered or Off not powered The output can be turned on or off the clicking On Off button After all fields have been programmed click on Submit Setting button a dialog box will display New Setting Submitted click OK All programmed information in now saved 3 Security Settings Fig 9 pg 11 Click on Security Settings tab The LINQ8PD CB security setting page will open This section is used to enable disable Secure Socket Layer SSL and to change Username and Password SSL will encrypt all the communication with a secure key An SSL certificate could be self signed Figs or obtained ae a third party certification company i N Device Managemen t Interface LINQ SSL Certificate Setting Fig 9a pg 1 1 Status Setup Network Settings Security Settings Events Log Help Generating a self signed SSL Certificate and Key er low acid as Field Name Description Two code representing the state A A a F B State oe E State Certificate Status No Cert where the organization is located aid Location The city where the organization is located e The legal name of the organization ape a LA Organization This should not be abbreviated and should Unit Name Change Username and Password include suffixes such as Inc Corp or LLC Common
19. door use only and should be installed by qualified personnel 1 Disconnect the AC mains and batteries if used from the power supply ies before connecting the LINQ8PD CB 2 Mount LINQ8PD CB into position and secure with mounting screws Interconnecting two 2 LINQ8PD CB modules Two 2 LINQ8PD CB s can be interconnected to enable both units to be accessed from a single IP address Connect interface cable supplied to the interface port marked DOWNLINK of first LINQ8PD CB which will be the master to interface port marked UPLINK of second LINQ8PD CB Power Supply Input Connection The LINQ8PD CB can be connected to two independent AC or DC power supplies that can be routed thru each of the individual outputs Each output is equipped with an input selection switch which is used to route the desired input to the output This switch also has a center off position that can be used to turn power off to an output a Single Power Supply Input Connect the output of the power supply to the terminals marked INP1 and set the Input selection switch for each output to the INP1 position b Dual Power Supply Inputs When the use of two independent power supplies is desired connect one power supply to the terminals marked INP1 and the second power supply to the terminals marked INP2 Set the Input selection switch for each output to the appropriate position Reconnect the AC mains of the connected power supply ies and verify the
20. es AC and Battery supervision relay to the corresponding DRY Inputs of the LINQ8PD CB If required to connect supervisory trouble reporting devices to outputs marked AC FAIL BAT FAIL supervisory relay outputs marked NC and C to appropriate notification devices Use 22 AWG to 18 AWG for supervision reporting Fire Alarm Interface options not evaluated by UL The Fire Alarm Interface and Reset options are programmable via the web interface FAI input trigger options supervised normally closed NC normally open NO polarity reversal input from signaling circuit or wet input will trigger selected outputs a Normally Open NO input Connect the supplied 2 2k resistor supplied in parallel with the normally open trigger circuit to the terminals marked GND FACP EOL b Normally Closed NC input Connect the supplied 2 2k resistor supplied in series with the normally closed trigger circuit to the terminals marked GND FACP EOL c Signaling Circuit Wet input trigger Connect the positive and negative of the signaling circuit wet input trigger to the terminals marked FACP IN and FACP IN d Fire Alarm Reset If a output is programmed to latch with manual reset connect either a normally open N O or normally closed N C dry input to the terminals marked RESET amp GND Reconnect AC power mains to the connected power supply ies and connect back up batteries LINQ8PD LINQ8PDCB Establishing Network Connection
21. ly energized when DC power is present NC C NO Contact rating 1 amp Y 30VDC AC Fail Indicates loss of AC power e g connect to audible device or alarm panel Relay normally energized NC C NO when AC power is present Contact rating 1 amp Y 30VDC power limited OR a 24VAC 28VAC or 12VDC 24VDC continuous output P AC NO C Connection to AC Fail terminals on power supply Q BAT NO C Connection to BAT Fail terminals on power supply BAT OUT Connection to stand by batteries S BAT IN Connection to BAT terminals on power supply D INP2 Second AC or DC power supply input Note Do connect AC and DC simultaneously to INP1 and INP2 INP1 First AC or DC power supply input Note Do connect AC and DC simultaneously to INP1 and INP2 LED Diagnostics LED Flash Codes Description ON Charge Discharge current working properly o ene Blinking Charge Discharge current on the battery exceed limits ON FACP triggered PACE OFF FACP released AC ON Input signal active OFF Input signal inactive ON Input signal active BAI OFF Input signal inactive ON Output is ON and working properly OUT1 OUT8 OFF Output is OFF Blinking _ Output is ON and voltage and or current exceeds limits LINQ8PD LINQ8PDCB Installation Instructions Wiring methods shall be in accordance with the National Electrical Code NFPA 70 NFPA 72 ANSI and with all local codes and authorities having jurisdiction Product is intended for in
22. network cable to the network jack on the LINQ8PD CB and the other to the network connection or the PC to be used for programming Note Email notification must be setup via the Browser Ref to Email Settings in the Browser Setup section of this manual B Browser Setup When not using the Altronix Dashboard USB connection for the initial Network setup the LINQ8PD CB needs to be connected to the power supply ies being monitored refer to Installing LINOSPD Board on page prior to programming Factory Default settings e IP Address 192 168 168 168 e User Name admin e Password admin Set the static IP address for the laptop to be used for programming to the same network IP address as the LINQ8PD CB i e 192 168 168 200 default address of the LINQ8PD CB is 192 168 168 168 Connect one end of the network cable to the network jack on the LINQ8PD CB and the other to the network connection of the laptop Open a browser on the computer and enter 192 168 168 168 into the address bar A dialog box Authentication Required will appear requesting both user name and password enter the default values here Click Log In button The status page of the LINQ8PD CB will appear This page displays the real time status and health of each power supply connected to the LINQ8PD CB LINQ8PD LINQ8PDCB 1 Network setup Click Network Settings tab This will open the Network Setting screen In this screen the MAC Address of the LINQ8P
23. ng 3 Graphics Department 1 2 27 3 Inactive 4 SMD Machinery 0 7 272 Normal 5 Production 0 5 27 3 Latching 6 Shipping 0 27 3 Inactive F Receiving 0 27 2 Normal 8 Loading Docks 0 27 3 Latching Connection Status OK Status Identification Fields Description PS1 PS2 Output Voltage amp Load Indicates Power Supply 1 and 2 output voltage and load FACP Status Indicates if FACP is triggered or not triggered Reset Indicates if FACP Reset is triggered or not triggered Tamper Status Indicates if Tamper is triggered or not triggered Temperature Indicates unit temperature Celsius AC Status Indicates AC trouble contact status Battery Status Indicates Battery trouble contact status Battery Capacity Indicates Amp Hour rating of the connected battery ies Battery Voltage Indicates battery voltage of the connected battery ies Battery Charge Level Indicates the charge level of the connected battery ies Battery Current Indicates the battery charge discharge rate in amps Battery Condition Indicates the condition of the connected battery ies Battery Service Date Indicates the next service date of the connected battery ies Output 1 8 Indicates output Device ID Descriptive name for the device connected to the output Output Current A Indicates output load in amps Output Voltage V Indicates output voltage in volts
24. ng encrypted and more secure HTTPS is highly recommended for remote access Click the Submit Network Settings button a dialog box will display New network settings will take effect after the server is rebooted click OK LINQ8PD LINQ8PDCB Trap Receiver Settings Fig 3b pg 7 a Enter up to five SNMP trap receiver IP addresses When accessing the LINQ8PD CB remotely check with the network administrator for proper configuration b Click Submit Trap Receiver IP Settings button a dialog box will display New Trap Receiver IP settings will take effect after the server is rebooted click OK SNMP Port Settings Fig 3c pg 7 SNMP uses the default port 161 for general SNMP messages and port 162 for SNMP trap messages In the event these port need to be changed enter the new port numbers assigned by the network administrator Click Submit Port Settings button a dialog box will display New SMNP port settings will take effect after the server is rebooted click OK Email Settings Fig 3d pg 7 The LINQ8PD CB can send emails via an in house email server email service provider i e Gmail Yahoo or Altronix default email service In house email server Field Name Description From Enter the email address assigned to the LINQ8PD CB module by the system administrator Subject Identify the location of the v i e the Site ID Username Enter the username associated with the LINQ8PD
25. or IP Address Method STATIC v Trap Receiver 1 Subnet Mask Enter the Subnet of the network oO Enter the TCP IP gateway of the network access point router SS E ne Gateway being used a l l Subnet Mask 255 255 255 0 Trap Receiver 3 Note Gateway configuration is required to properly receive emails Gateway 192 168 0 11 Trap Receiver 4 from the device Enables standard remote access and monitoring Enter the port Be en HTTP Port number assigned to the LINQ8PD CB module by the network HIPS Fod 1448 E administrator Default Port setting 80 System Port 667 Enables secure remote access and monitoring Enter the port num SIIUIP IPSS amp gt HTTPS Port ber assigned to the LINQ8PD CB module by the network adminis ESEIDIINEMOIR SANS Skipper hen trator Default Port setting 443 Used to update device firmware Enter the port number m oe T System Port assigned to the LINQ8PD CB module by the Restore Factory Settings Eee network administrator Default Port setting 667 D a Click Submit Network Settings button a dialog box will display Reboot Server New network settings will take effect after the server is rebooted click OK Note When remote access is required or using multiple devices on the same network it is recommended to assign an independent port to each connected device DHCP Fig 2a pg 5 Connect LINQ8PD CB to the DHCP router to obtain IP address a After selecting DHCP in the IP Add
26. ress Method field click Submit Network Settings button a dialog box will display New network settings will take effect after the server is rebooted click OK Next click Reboot Server button Fig 2d pg 5 After the LINQ8PD CB reboots the IP address assigned will appear in the IP Address field It is recommended to have the assigned IP Address reserved on the router to ensure continued access to the LINQ8PD CB see the network administrator LINQ8PD LINQ8PDCB Field Name Description Subnet Mask When operating in DHCP the router will assign the subnet mask values Gateway Enter the TCP IP gateway of the network access point router being used Enables standard remote access and monitoring Enter the port number assigned to the LINQ8PD CB module by the network administrator HTTP Port Default Port setting 80 Enables secure remote access and monitoring Enter the port number assigned to the LINQ8PD CB module by the network administrator Default Port setting 443 Used to update device firmware Enter the port number assigned to the LINQ8PD CB module by the network administrator Default Port setting 667 b Click Submit Network Settings button a dialog box will display New network settings will take effect after the server is rebooted click OK
27. ting is 80 HTTP is not encrypted and unsecure Even though HTTP can be used for remote access it is recommended primarily for use with LAN connections HTTPS Port Enter the HTTPS port number assigned to the LINQ8PD module by the network administrator to allow remote access and monitoring The default inbound port setting is 443 Being encrypted and more secure HTTPS is highly recommended for remote access System Port Used to update device firmware Enter the port number assigned to the LINQ8PD CB module by the network administrator Default Port setting 667 a Click Submit Network Settings button a dialog box will display New network settings will take effect after the server is rebooted click OK DHCP Fig 3a pg 7 After selecting DHCP in the IP Address Method field click Submit Network Settings button a dialog box will display New network settings will take effect after the server is rebooted click OK Next click Reboot Server button After rebooting the LINQ8PD CB will be set in the DHCP mode The IP address will be assigned by the router when the LINQ8PD CB is connected to the network It is recommended to have the assigned IP Address reserved to ensure continued access see the network administrator Trap Receiver Settings B Trap Receiver IP Address 1 Trap Receiver IP Address 2 Trap Receiver IP Address 3 Trap Receiver IP Address 4 Trap Receiver IP Address 5
28. ved contact the network administrator and repeat the email setup steps After all fields have been programed click Reboot Server button a dialog box will display Please allow up to 30 sec for server to reboot click OK All programmed information will be saved after the server has rebooted LINQ8PD LINQ8PDCB 2 Setup Fig 4 pg 9 Note If the Altronix Dashboard is being used for LINQ8PD CB setup refer to the Folder and Device configuration section in the Altronix Dashboard setup user Site ID Enter Loc A nassen Monday Sept 21 2015 2 30 pm Sync with muB manual Click on Setup tab The LINQ8PD CB setup page will open E i x o aaa This page is used to configure all operating functions of the LINQ8PD CB eA EN PS2 Presence wD ne mE Fig 4 Setup Field Name Description Enter a descriptive name that will identify the location building company or campus where the LINQ8PD CB installed PS2 Presence From the pull down menu select No to disable PS2 if only one power supply is connected Battery Presence A Site ID The Site ID will appear in both the trap message and email notifications Date Time Clicking on Sync Date Time with Computer will set the LINQ8PD CB to the time of the host computer LINQ8PD CB ID Enter a descriptive name and or location of the LINQ8PD CB From the pull down menu select No if