1. VAC 50 60 0 2 Hz Battery mode Note The output power of the UPS is de rated to 90 of its nominal value when the output voltage of the UPS is adjusted to 208V Batteries Model No 101KT 102KT 103KT Number and type 3x12VX7 2Ah 8x12VX7 2Ah 8x12VX7 2AnN 10 2 Operating Environment Operating Temperature 0 C to 40 C Operating Altitude lt 1000m Storage temperature 0 C 40 C 10 3 Typical Battery Backup Times at 25 C in minutes Model No 100 Load 50 Load 10 4 Dimensions and Weights Dimensions W x D x H mm EGE 102KTL 192X460X340 EGE 103KT 192X460X340 EGE 103KTL 192X460X340 10 5 Safety and EMC Standards GB4943 EN62040 1 1 safety Conducted Emission GB7260 2 EN62040 2 Class B Radiated Emission GB7260 2 EN62040 2 Class B Harmonic Current EN61000 3 2 Voltage Fluctuations and Flicker EN61000 3 3 EMS EN61000 4 2 ESD cccsseesseeeeeeeeeeeeeeeeeeeees Level 4 EN61000 4 3 RS ccccccccccccceeeeeseseeseeeeeeeeeeeeeeeeaeeeees Level 3 EN61000 4 4 EFT ccccccccccecceseeeseeseeeeeeeeeeeeeeeeeeees Level 4 EN61000 4 5 Surge cccceceeeeeeteesecetseseeeteeeeeesenees Level 4 EN61000 2 2 Immunity to low frequency signals 11 Communication Port 11 1 RS232 Interface The following is the pin assignment and the description of DB 9 connector at the rear of the UPS TXD Output 11 2 AS400 Interface Optional In a
2. 4 No Output Mode of Operation The LCD display of the UPS in the no output mode of operation is shown in the figure below In this mode of operation information about the input mains supply the battery the UPS output and the load are displayed The code that indicates this mode of operation is 00 MODE HI 208 VAC BYPASS DISABLE 220 VAC 240 VAC 60 HZ BYPASS ENABLE Fig 6 4 No output mode of operation 6 5 Abnormal Mode of Operation This mode of operation occurs if a fault occurs A code will be displayed to indicate the type of the fault occurring In addition to the code that describes the type of the fault some warning words as short that indicates an output short circuit will be displayed Refer to chapter 4 to determine the meaning of the warning words 7 Setting The UPS Parameters The front panel button switches are used to set the UPS output voltage and frequency and to disable or enable the bypass circuit The UPS output voltage can be set to 208VAC 220VAC 230VAC or 240VAC The UPS output frequency can be set to 50Hz or 60Hz The UPS bypass circuit can be set to enable or disable state Note that these parameters can be set only when the UPS is in the bypass or in the no output mode While the UPS is in the bypass or in the no output mode if the Select button is pressed for more than one second a flickering black round dot will be shown in front of the 208V on the LCD
3. Charge the battery for at Battery backup time is Battery not fully least 1 2 hours and then shorter than nominal charged or battery check battery backup time value faulty Contact the service representative Warning code 13 is shown on the LCD Charger or Battery Contact the service panel the alarm beeps faulty representative once per second Warning code 10 is shown on the LCD panel Fan is locked or not Check fan s and contact working the service representative Please have the following information ready when you call the after Sales service Department e Model number and serial number e Date of failure or problem e Symptoms of failure or problem 9 Maintenance 9 1 Operation Please note that this UPS has no user serviceable parts inside If the battery service life 3 to 5 years at 25 C ambient temperature has been exceeded the batteries have to be replaced For battery replacement contact your dealer 9 2 Storage lf the UPS is stored in a temperate climatic environment recharge the battery every three months by connecting the UPS to the mains power supply for a period of one to two hours You should shorten the charging intervals to two months at locations subject to high temperatures 10 Technical Specifications 10 1 Electrical specifications Electrical input Mode No EGE 101KTLIEGE 102KT EGE 102KTLIEGE 103KTL 6 54 5 60 Hz Curenta Electrical output 208 220 230 240 2
4. LCD while if the mains input supply voltage becomes lower than the minimum input voltage accepted by the UPS the L sign will be shown on the LCD If the input mains supply is lost both H and L signs will disappear and the input voltage and frequency will display zeros MODE BAT TERY 208 VAC 230 VAC 50HZ BYPASS DISABLE 220 Vac 240 VAC 60 HZ BYPASS ENABLE Fig 6 2 Battery mode of operation The display of battery test mode is the same as battery mode but H and L signs will not be shown unless the input mains voltage is higher or lower than the values accepted by the UPS The code that indicates the battery mode of operation is 03 while the code that indicates the battery test mode is 04 6 3 Bypass Mode of Operation The LCD display of the UPS in the bypass mode of operation is shown in the figure below In this mode of operation information about the input mains supply the battery the UPS output and the load are displayed The code that indicates this mode of operation is 01 The block BYPASS on the LCD display indicates that the bypass circuit is in operation The UPS alarm beeps once every two minutes BYPASS DISABLE 220 VAC 240 VAC 60 HZ BYPASS ENABLE Fig 6 3 Bypass mode of operation Note that in the bypass mode the load is supplied directly from the input mains supply and no backup exists in case of mains failure 6
5. cable of the UPS to the input mains supply to operate the UPS in the utility power mode 4 Connect the external battery cable between the external battery socket on the rear panel of the UPS and the external battery cabinet The UPS will start charging the external battery 5 This external battery cable has three wires the red is the wire the black is the wire and the green yellow is the grounding wire Caution The output sockets of the UPS system may carry live voltage even if the input power supply has been disconnected or the bypass switch is on OFF position 6 UPS Operating Modes On the LCD panel of the UPS a code is displayed to indicate the operating mode of the UPS The codes displayed can also indicate a fault or a warning The table below shows the meanings of the different codes that can be displayed on the UPS LCD Note that at any time instant only one operating mode or a fault mode can be represented If several warnings exist in a given operating mode the codes of these warnings and the code that indicates the operating mode are shown cyclically Once a fault comes forth the codes of all existing warnings will not be displayed and only the code of the existing fault will be displayed Operating mode code Operating mode eode Newouiputmode 00 Ovevload tau o7 Bypass mode o1 Overtemperature aut o8 tine mode o Sitealwarning meneren o6 Charger tai waring 13
6. 6 1 Line Mode of Operation The LCD display of the UPS in the line mode of operation is shown in the following figure In this mode of operation information about the input mains supply the battery the UPS output and the load are displayed The block INVERTER on the LCD display indicates that the inverter is in operation Note that the code that indicates this mode of operation is 02 208 VAC 230 VAC 50HZ BYPASS DISABLE 220 VAC 240 VAC 60 HZ BYPASS ENABLE Fig 6 1 Line mode of operation If the UPS becomes overloaded the percentage of the load will be shown and the audible alarm will beep twice per second In this case the UPS load has to be decreased to less than 90 of its rated power capacity 6 2 Battery Mode of Operation The LCD display of the UPS in the battery mode of operation is shown in the figure below In this mode of operation information about the input mains supply the battery the UPS output and the load are displayed The block INVERTER on the LCD display indicates that the inverter is in operation Note that 1 When the UPS is in the battery mode the alarm beeps once every 4 seconds To silence the alarm press the ON button for more than one second Pressing the ON button again for more than one second resumes the alarm again 2 If the mains input supply voltage becomes higher than the maximum input voltage accepted by the UPS the H sign will be shown on the
7. If the Select button is again pressed continuously the flickering dot will move to the front of the 220V 230V 240V 50Hz 60Hz Bypass Disable and Bypass Enable cyclically To select any of these possible choices press the Enter button for more than one second The output voltage and frequency of the UPS will be changed to the selected value after the UPS is turned on by pressing the ON button If the Bypass Enable was selected The UPS will turn to bypass mode in several seconds While if Bypass Disable was selected the UPS will turn to No Output mode The following figures show the steps required to change the UPS output voltage from 220V to 230V 230 VAC BYPASS DISABLE 220 VAC 240 VAC 60 HZ BYPASS ENABLE step 1 After pressing the Select button for more than one second one flicking round dot will appear in front of the 208Vac 208 VAC BYPASS DISABLE 220 VAC BYPASS ENABLE Step 2 Pressing the Select button twice again the flicking round dot will move to the front of the 230Vac BYPASS DISABLE BYPASS ENABLE Step 3 Pressing the Enter button the dot in front of the 230Vac will stop flicking and the dot in front of the 240Vac will begin flicking This indicates that the output voltage 230Vac has been selected 208 VAC 230 VAC BYPASS DISABLE 220 VAC 240 VAC 60 HZ BYPASS ENABLE Step 4 After the UPS turns to ON th
8. OOPUWER fl USER MANUAL EGE Series UPS 1 3KVA High Frequency Online UPS Uninterruptible Power Supply TABLE OF CONTENTS 1 Safety Instructions 1 1 Transport 1 2 Set Up 1 3 Installation 1 4 Operation 1 5 Maintenance Servicing and Faults Commonly Used Symbols Introduction Panel Description Connection and Operation 5 1 Inspection 5 2 Connection 5 3 Battery Charging 5 4 Turning On the UPS 5 5 Test Function 5 6 Turning Off the UPS 6 UPS Operating Modes 6 1 Line Mode of Operation 6 2 Battery Mode of Operation 6 3 Bypass Mode of Operation 6 4 No Output Mode of Operation 6 5 Abnormal Mode of Operation 7 Setting the UPS Parameters 8 Troubleshooting 9 Maintenance 9 1 Operation 9 2 Storage 10 Technical Specifications 10 1 Electrical Specifications 10 2 Operating Environment 10 3 Typical Battery Backup Times 10 4 Dimensions and Weights 10 5 Safety and EMC Standards 11 Communication Port 11 1 RS232 Interface 11 2 AS400 Interface optional 12 Software For All Models Appendix 1 UPS Rear Panel own 1 Safety Instructions Please read the following user manual and safety instructions before installing this unit and starting it up 1 1 Transport Please transport the UPS system in its original packing carton to protect it against damage due to shock and impact 1 2 Set up As condensation may occur if the UPS is moved directly from cold to warm environment and in order to dry the UPS before installat
9. PS output voltage It can be displayed from 0 to 999Vac Displays the value of the frequency of the UPS output It can be displayed from 0 to 99Hz Displays the load in Watt or VA as a percent of the UPS Output power rating Only the maximum of these two readings is displayed from 0 to 199 SHORT Indicates that the load or the UPS output is short circuited and the UPS will shutdown Indicates that the load is higher than the UPS output OVER LOAD power rating Battery Information Displays the value of the battery voltage It can be displayed from 0 to 999Vdc Ph me a Of Displays the battery stored capacitance in percent It can Ct ta O be displayed from 0 to 199 Indicates that the battery is over charged the UPS will be OVER CHARGE switched to battery mode Indicates that the battery voltage is low the UPS will Mode Fault Warning code Information FAULT Displays the operating mode the fault code and the MODE warning codes of the UPS For the meaning of these WARNING codes refer to page 13 Inverter operating Information 208 VAC 930 Vac Indicates the value of the desired UPS output voltage One of these four values can be selected when the UPS 220 VAC 240 VAC is in the No output or in the Bypass mode Indicates the value of the desired UPS output frequency One of these two values can be selected when the UPS is in the No output or in the Bypass mode BYPASS DISABLE Indicates if t
10. UPS output sockets will be supplied via the bypass circuit If the UPS is in the Bypass or in the No output mode this button is Select Button used to enter the configuration mode and to select the UPS output voltage and frequency and to disable or enable the bypass circuit If the UPS is in the Bypass or in the No output mode this button is Enter Button used to confirm the selected UPS output voltage and frequency and the disabling enabling state of the bypass circuit Bypass Operating Inverter Operating Information Information Input po H Bas Se8Vac Output Information oo H Si HZ Information INPUT e PEA ee FAULT Mode Fault Warning MODES 4 _ T oo ov Load Code Information WARNING LOAD Information 208 Vac 230 VAC BYPASS DISABLE 220 VAc 240 VAC 60HZ BYPASS ENABLE Output voltage and frequency and Bypass Battery enable disable Selection Information Information Fig 4 2 Front panel LCD of the UPS Display Information or Data Input Information Displays the value of the input supply voltage It can be displayed from 0 to 999Vac Displays the value of the frequency of the input supply It can be displayed from 0 to 99Hz Indicates that the input supply voltage is higher than the specified range the UPS will work in the battery mode Indicates that the input supply voltage is lower than the specified range the UPS will work in the battery mode Displays the value of the U
11. ddition to the communication protocol mentioned above this UPS series has AS400 card an optional accessory for AS400 communication protocol This interface provides true relay contact output to peripheral devices The following is the pin assignment and description of DB 9 connector in AS400 card Description VO Pin Description VO UPSFail Output 6 Bypass Output __ GND inut 8 UPSON Output Remote Shutdown Input 9 LineLoss Output _ ee eee Common Input Fig 10 1 Pin assignment of the DB 9 interface of AS400 Protocol Please contact your local distributor for details 12 Software For All Models The Free downloaded Software WinPower WinPower is a brand new UPS monitoring software which provides a user friendly interface to monitor and control your UPS This unique software provides safely auto shutdown for multi computer systems in case of power failure With this software you can monitor and control any of your UPS systems on the same LAN no matter how far are these UPS systems Pe Winpower Manager eri 0 agent Read e ai IOI x oyster Logs UPS Tools Womtor Preference Language Help sisemeR Root UPS Status UPS Normal Voltage Frequency Ilax Volt Nin Volt h Model Voltage Cor Port BATTERY Standard IN i Terp ILL Capacity 20041028 13 53 35 Agent Start Installation Procedure The following is the installat
12. e output voltage will be 230Vac 8 Troubleshooting lf the UPS alarm is activated use the following table to determine and resolve the problem Even the UPS is connected to the mains power supply there are no warning tones and no indications are shown on the LCD panel Check building wiring socket outlet and the UPS input cable No input supply voltage Warning code 09 is shown on the LCD panel Mode code 03 is shown on the LCD panel and the warning word H or L may be also Phase and neutral conductors of the UPS input are reversed Input power supply voltage and or frequency is out of tolerance Rotate mains power socket by 180 Check the input power Supply source and inform the service representative if necessary displayed Even the mains power supply is available mode code 00 or 01 is shown on the LCD panel Inverter is not Press the ON switch switched on Mode code 03 is shown on the LCD panel the alarm beeps 1 beep every 4 seconds The UPS is in the battery Mains power supply mode When audible alarm failure beeps once per second the battery is almost empty Fault code 07 is shown on the LCD panel the alarm beeps once per Remove some of the loads from the UPS output and restart Overload second Fault code 05 or 06 or 08 is shown on the LCD Contact the service UPS fault panel the alarm beeps representative continuously
13. he Bypass circuit is going to be disabled or enabled One of these two states can be selected when BYPASS ENABLE the UPS is in the No output or in the Bypass mode 5 Connection and Operation This UPS system has to be wired and installed by a qualified technician and in accordance with the applicable safety regulations When installing the electrical wiring of the UPS please take into consideration the rated current carrying capacity ampacity of the incoming feeder 5 1 Inspection Inspect the packing carton and its contents for any damage Inform the carrier agency immediately if you find any sign of damage Keep the packing cartons in a safe place for future use Note Please ensure that the incoming feeder is isolated and secured to prevent it from being switched on again 5 2 Connection 5 2 1 UPS Input Connection The current carrying capacity ampacity of the socket outlet to which the UPS is connected must be greater than the UPS input current over 10A for 1KT 1KT XLand 2KT models and over 16A for 2KT XL 3KT and 3KT XL models 5 2 2 UPS Output Connection The outputs of the UPS EGE 101KT L EGE 102KT L EGE 103KT L are socket type only Simply plug the load power cord to the UPS output socke to complete the connection UPS Model Number of Socket Outlets Output Terminal Block EGE 103KT L Caution Do not connect equipment such as printers which may overload the UPS system 5 3 Battery Chargi
14. ion please allow acclimatization time of at least two hours Do not install the UPS system near water sources or in dump environment Do not install the UPS where it could be exposed to direct sunlight or near heat Do not block off the ventilation openings of the UPS cabinet 1 3 Installation Do not connect appliances or items of equipment which may overload the UPS such as laser printers to the output of the UPS Place the cables in such a way that no one can step on or trip over them Do not connect home appliances such as hair dryers to the output of the UPS This UPS can be operated by any individual with no previous experience Connect the UPS only to an earthed shock proof socket outlet The socket outlet to which the UPS is connected must be easily accessible and close to the UPS Use only VDE tested CE marked cable as the power cable of your computer to connect the UPS to the building socket outlet Use only VDE tested CE marked power cables to connect the loads to the UPS This UPS is an operator installable When installing the equipment it should be ensured that the sum of the earth leakage current from the UPS and the load connected to it must not exceed 3 5mA 1 4 Operation Do not remove or unplug the input cord when the UPS is turned on This removes the safety ground from the UPS and the equipment connected to the UPS This UPS contains its own energy source bat
15. ion procedure for the WinPower software 1 Connect to the website http www ups software download com winpower htm 2 From the different choices mentioned in this web page select the operating system you are using and follow the instructions described on the website to download the software 3 When downloading is finished enter the serial number 511C1 01220 0100 478DF2A to install the software When your computer restarts the WinPower software will appear as a green icon located in the system task manager near the clock Appendix 1 UPS Rear Panel Communication Port Intelligent Slot Cooling Fan External Battery Socket Breaker Network Fax Modem Output Socket Surge Protection Input Socket The rear panel of the EGE 101KT and EGE 101KTL models Communication Port Intelligent Slot External Battery Socket Cooling Fan Output Socket Breaker Input Socket Network Fax Modem Surge Protection The rear panel of the EGE 102KT EGE 102KTL and EGE 103KT EGE103KTL models tarokUWER ESIS ENERJI VE ELEKTRONIK SAN TIC A S Dudullu Organize Sanayi Bolgesi Esenkent Mah Baturalp Sok No 14 Umraniye ISTANBUL Tel 90 216 540 90 00 Fax 90 216 540 90 10 E mail esis esis com tr
16. ng To fully charge the batteries of the UPS keep the UPS connected to the mains supply for 1 2 hours During this period the UPS can be used to supply the load but in this case the battery autonomy time will be less than the values specified 5 4 Turning On the UPS 5 4 1 With Mains Power Connected Press the ON button continuously for more than one second to turn on the UPS At the beginning of the turning on process the UPS performs a self test After finishing the self test the inverter starts and the UPS becomes in the line mode The LCD screen lights up to indicate the status of the UPS 5 4 2 Without Mains Power Connected Even the mains power supply is not connected pressing the ON button I continuously for more than one second will turn on the UPS At the beginning of the turning on process the UPS performs a self test After finishing the self test the inverter starts and the UPS becomes in the battery mode The LCD screen lights up and indicates the status of the UPS Note The default setting for the bypass circuit is the no output state This state can be configured using the front panel button switches or software 5 5 Test Function To test the UPS press the ON button I of the UPS or disconnect the input mains supply 5 6 Turning Off the UPS 5 6 1 In Line Mode Press the OFF button e l continuously for more than one second At the beginning the UPS performs a self test After finishing the self
17. rrent The following precautions and any others necessary measures should be observed Remove watches rings or other metal objects Use tools with insulated handles Replace the batteries with the same number and type as the originally installed ones Do not dispose of the batteries in a fire Batteries may explode Do not open or destroy the battery Released electrolyte is harmful to skin and eyes It may be toxic When replacing a fuse use only one of the same type and the same current and voltage ratings as the original fuse Do not dismantle the UPS system 2 Commonly Used Symbols The following are the symbols used in this manual or on the UPS system to alert you to important information Users should be familiar with these symbols and understand their meanings o Tumngon meus O Turning OFF the UPS pe curent o Of Alarmsitence Recycle Keep UPS in a Clean Area 3 Introduction This on line UPS incorporates the latest in double conversion topology which provides perfect protection for your critical and power supply sensitive equipment specially Novell Windows NT and Unix servers The double conversion principle eliminates all the mains power disturbances Here a rectifier converts the alternating current of the mains supply to direct current This direct current charges the batteries and powers the inverter The inverter in its turn generates a sinusoidal AC voltage which permanently s
18. teries The output of the UPS may carry live voltage even when the UPS is not connected to an AC supply For complete disconnection of the UPS system first press the OFF button for more than one second then disconnect the mains power supply cable Ensure that no fluids or other foreign objects can enter the UPS system This UPS operates with hazardous voltages repairs must be carried out only by qualified service technician 1 5 Maintenance servicing and faults This UPS operates with hazardous voltages repairs must be carried out only by qualified maintenance technician Caution risk of electric shock Even after the UPS has been disconnected from the mains supply building socket outlet dangerous high voltages are still existing inside the UPS Before carrying out any type of servicing and repair disconnect the mains supply and the batteries Verify that no hazardous voltage exists on the terminals of the capacitors Only persons adequately familiar with batteries and with the required precautionary measures my replace the UPS batteries unqualified persons must not deal with batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Before touching any terminal or wire please verify that no voltage is present Batteries can present a risk of electrical shock and have high short circuit cu
19. test the UPS becomes in the standby or the bypass mode A voltage may exist at the output of the UPS if the bypass is enabled Disconnect the mains power to remove the UPS output voltage 5 6 2 In Battery Mode To turn off the UPS press the OFF button e l continuously for more than one second At the beginning of the turning off process the UPS performs 5 6 2 In Battery Mode To turn off the UPS press the OFF button lr continuously for more than one second At the beginning of the turning off process the UPS performs a self test After the self test is finished the UPS turns off completely 5 7 Audible Alarm m ute If the alarm is activating in the battery mode press the ON button di continuously for more than one second to clear it The alarm will be activated again when the battery voltage becomes low to remind you to shutdown the load 5 8 Procedure of external battery connection for long backup time models S models Units with CE marks 1 Use the battery pack of 36VDC 3 cells of 12V each for the 101KTL models Use the battery pack of 96VDC 8 cells of 12V each for the 102KTL and 103KTL models Connection of battery packs with wrong battery voltages will cause damage 2 One end of the external battery cable will be plugged into the external battery socket of the UPS and the other end will be connected to the external battery cabinet 3 Do not connect any load to the UPS output Connect the input power
20. upplies the loads with uninterrupted clean and sine wave_ voltage Computers and peripherals are thus powered entirely by the inverter In the event of mains power failure the maintenance free batteries supply the inverter This series of UPS units are produced in three power ratings 1kVA 2kVA and 3kVA with standard battery backup time and with extended battery backup time as shown in the table below EGE 101KT EGE 101KTL E EGE 102KT Standard battery EGE 102KTL xtended battery backup time backup time EGE 103KT EGE 103KTL L denotes models with extended battery backup times 4 Panel Description 588vac EMEN S5 Hz 7 INVERTER faii OVER CHARGE FAULT SE8Vpc MODE S L T aii WARNING BATTERY 208 Vac 230 VAC 220 Vac 240 Vac Select Button Enter Button SOOVAC oo HZ LCD Screen BYPASS DISABLE BYPASS ENABLE ON Button Alarm Silence OFF Button Fig 4 1 Front panel of the UPS The following table describes the function of the button switches of the front panel This button has two functions Turning on the UPS system By pressing this button the UPS ON Button Alarm Silence system turns on Deactivating the audible alarm By pressing this button the audible alarm can be deactivated By pressing the OFF button b the inverter turns off and if the OFF Button mains power supply is normal the UPS system switches to Standby or Bypass mode The