Home

N-Series TeraFrame Gen 3 User Manual

image

Contents

1. 2 Partially open the door but not as far as 90 degrees 3 Disconnect the ground wire 4 Open the door to exactly 90 degrees and pull the door away from the cabinet frame 15 Installing the Rear Doors 1 Hold the door in a 90 degree open position 2 Align the hinges on the door with the hinges on the frame and slide the hinges together i er P Les LA YS SY er AS if R 3 ie SO a Ds TA A er i f Os LL ls ales a J 3 SS VA Si A g cl XY x y A a Dy 3 Rotate the door to the closed position 4 Insert the hinge pins from the top of the hinge into both the upper and lower door hinges 5 Open the door and reconnect the ground wire Removing and Installing the Top Panel Removing the One Piece Top Panel 1 Remove two 2 shipping brackets on top of cabinet using 13mm socket wrench 2 Open the rear door s of the cabinet Remove grounding wire from the top panel item 1 in image next page 3 Depress and hold the two 2 spring retainers item 2 in image next page that hold the top panel to the frame 4 Push up on the top panel and remove 16 Installing the Top Panel 1 Align the front edge of the top panel with the frame 2 Lower the top panel sliding it forward to make contact with the front of the frame 3 Lower the back of the top panel Insure that the two 2 spring retainers have snapped in place and secur
2. 25 Thermal Management cont d Air Dam 1 Side 42U x 800 39386 X00 For 31 5 800 mm and 40 1016 mm 45U x 800 39386 X03 wide cabinets 48U x 800 39386 X06 52U x 800 39386 X10 42U x 1016 39384 X00 45U x 1016 39384 X03 48U x 1016 39384 X06 52U x 1016 39384 X10 39386 XXX 39384 XXX Air Dam 2 Side 42U x 800 39387 X00 For 31 5 800 mm and 40 1016 mm 45U x 800 39387 X03 wide cabinets 48U x 800 39387 X06 52U x 800 39387 X10 42U x 1016 39385 X00 45U x 1016 39385 X03 48U x 1016 39385 X06 52U x 1016 39385 X10 R R R R R 39387 XXX 39385 XXX X Color C Black E Glacier White 26 Shelves Trays and other accessories Cage Nuts amp Screws 25 M6 cage nuts and screws for square punched rails Screws 50 12 24 screws for tapped rails Rack Mount Cable Shelf 1U x 19 W brush sealed openings on front for cable pass through Concrete Floor Installation Kit Four 4 floor anchors Runway Elevation Kit 2 3 50 75 mm H 4 6 100 150 mm H 27 12637 001 13517 701 40604 001 40604 004 10506 712 10506 716
3. B pral 13mm Open Ended Wrench Access Anchoring the cabinet to the floor Insure that the cabinet has been properly leveled All leveling feet should be in firm contact with the floor and the cabinet should not rock in any direction A level placed on the cabinet frame should confirm that the cabinet is level If the cabinet is not level adjust the leveling feet with a 5mm ball driver or 13 mm open end wrench until the cabinet is level and the cabinet will not rock in any direction Then remove the transport casters and install cable seals if included N Series TeraFrame Cabinets whether bayed together or standing alone should be anchored to the floor The floor attachment brackets shown on the next page are used to anchor the cabinet to the floor The brackets attach to the outside of the frame Installation requires four anchors either 3 8 or M10 hardware ordered separately 11 ae Floor Attachment Bracket The mounting locations for the brackets are shown in the figure below Attach the cabinet to the floor with 3 8 or M10 hardware appropriate for your type of flooring Bonding the cabinet to the telecommunications ground N Series TeraFrame Cabinets should be bonded to the telecommunications ground The top panel side panels doors and mounting rails on the TeraFrame cabinet are electrically bonded to the frame A ground strap bonds the panels and doors to the frame In order to bond the cabinet to the te
4. 39434 012 39434 016 39436 012 39436 016 25190 001 39327 X00 Power Management One set of Standard PDU brackets is included with the N Series TeraFrame Gen 3 Cabinet Additional PDU brackets are available as well as a wide range of power strips and PDU s including monitored and switched versions Standard PDU Brackets 39110 701 Two 2 brackets Attaches to the cabinet vertical frame member Full Height PDU Bracket Dual for 2 2 W 56 mm PDUs Attaches to the cabinet frame 42U 39086 X00 45U 39086 X03 48U 39086 X06 52U 39086 X10 Wide for 2 7 W 69 mm PDUs 42U 39221 X00 45U 39221 X03 48U 39221 X06 52U 39221 X10 X Color C Black E Glacier White 24 Thermal Management Vertical Exhaust Duct Kit Includes top panel bottom panel and exhaust duct 14 20 356 508 mm Vertical Exhaust Duct Kit Includes top panel bottom panel and exhaust duct 20 34 508 863 mm Vertical Exhaust Duct Kit Includes top panel bottom panel and exhaust duct 34 60 863 1523 mm Bottom Panel with Grommets Seals bottom of cabinet Snap n Filler Panel 1U X19 Black 6 EA 2U X19 Black 6 EA 1U X19 Black 50 EA 2U X19 Black 50 EA 39440 X10 39440 X12 39440 X16 39441 X10 39441 X12 39441 X16 39442 X10 39442 X12 39442 X16 39410 X01 34537 001 34538 001 34537 002 34538 002 More El Drs OT De J J X Color C Black E Glacier White
5. 45U x 1016 48U x 1016 52U x 1016 39375 000 39375 003 39375 006 39375 010 39380 X00 39380 X03 39380 X06 39380 X10 39381 X00 39381 X03 39381 X06 39381 X10 39128 X00 39128 X03 39128 X06 39128 X10 39129 X00 39129 X03 39129 X06 39129 X10 800W 39377 X01 1016W 39377 X02 X Color C Black E Glacier White 22 AIT ANLE N 39380 XXX 39381 XXX A A 39128 XXX 39129 XXX Cable Management cont d Cable Port Seal Kit Top Two 2 full length sections Cable Port Seal Kit Bottom Two 2 full length sections Cable Entry Brush Kit Top Two 2 full length sections Cable EntryBrush Kit Bottom Two 2 full length sections Cable Port Brush Kit 800W x 1000D 800W x 1050D 800W x 1100D 800W x 1200D 1016W x 1100D 1016W x 1200D 800W x 1000D 800W x 1050D 800W x 1100D 800W x 1200D 1016W x 1100D 1016W x 1200D 800W x 1000D 800W x 1050D 800W x 1100D 800W x 1200D 1016W x 1100D 1016W x 1200D 800W x 1000D 800W x 1050D 800W x 1100D 800W x 1200D 1016W x 1100D 1016W x 1200D Brushes for two 2 large cable knock outs in cabinet top panel Cable Radius Drop Manager One 1 bracket Attaches to top frame slides X Color C Black E Glacier White 23 39413 008 39413 010 39413 012 39413 016 39415 012 39415 016 39414 008 39414 010 39414 012 39414 016 39416 012 39416 016 39433 008 39433 010 39433 012 39433 016 39435 012 39435 016 39434 008 39434 010
6. MATERIALS CPI uses only recyclable materials in all of its cabinet Y A packaging Please save packaging for later use or dispose of properly All wood wo components of CPI pallets have been properly treated to comply with the pest free certifications required by foreign countries 6 If the cabinet is to be reshipped save all packaging materials for reuse DISCLAIMER CPI is not responsible for any damage to the cabinet or its contents after the cabinet is repackaged and reshipped 7 After the cabinet is unpacked check the cabinet and the hardware kit to insure that all of the components and hardware items have been received with the cabinet If any components are missing or damaged email Technical Support at techsupport chatsworth com or call toll free at 800 834 4969 US amp Canada Monday to Friday 5 a m to 5 p m Pacific Time 10 Installation Moving the cabinet A The TeraFrame Cabinet has been provided with four 4 casters to allow the cabinet to be rolled into position CAUTION The N Series TeraFrame cabinet ships on casters Move the cabinet by pushing on the front or the rear of the cabinet Do not push the cabinet from the sides Once the cabinet has been moved to the final location level and anchor the cabinet per the instructions below L es AL S Hex Driver Access Z 0 mM I NIL Outer leveler in 1016W cabinet only WAN
7. terminal block 5 2 Phillips Screwdriver a For installing M6 screws into cage nuts to secure equipment in mounting rails b For removing and installing door hinges c For installation and removal of PDU brackets 6 5mm Ball Hex Driver a For adjusting leveling feet Unpacking CAUTION The TeraFrame cabinet is heavy Use a minimum of two 2 people to unpack and remove the cabinet from the pallet CAUTION The TeraFrame casters are for moving the cabinet short distances over smooth floor surfaces only Move shipping pallet as close as possible to the final installation location before unpacking CAUTION The TeraFrame casters are not intended to support cabinet loads for extended periods of time Always level and anchor the cabinet after positioning Inspect the cabinet for damage If any damage to the cabinet is observed contact your distributor or CPI Customer Service 1 Carefully remove the plastic wrap surrounding the cabinet using a utility knife Be careful not to allow the knife to contact the cabinet as this may damage the unit 2 Remove the four 4 cardboard corner protectors 3 Inspect inside the cabinet to insure all items are securely fastened to the cabinet Remove any items that were shipped inside the cabinet but are not fastened to the cabinet 4 Remove the shipping bracket that anchors the cabinet to the pallet using a 13 mm 1 2 socket wrench 5 Remove the cabinet from the pallet RECYCLABLE
8. N Series TeraFrame N Series TeraFrame Gen 3 Cabinet System User s Manual CHATSWORTH PRODUCTS techsupport chatsworth com 2014 Chatsworth Products Inc All rights reserved Chatsworth Products CPI CPI Passive Cooling www chatsworth com eConnect MegaFrame Saf T Grip Seismic Frame SlimFrame TeraFrame GlobalFrame Cube iT Plus Evolution OnTrac QuadraRack and Velocity are federally registered trademarks of Chatsworth Products Simply Efficient is a trademark of Chatsworth Products All other trademarks belong to their respective companies Rev 2 08 14 MKT 60020 606 Contents N Series TeraFrame Gen 3 Cabinet Overview sscssscssccssccssccsccssscesscessosscesccessasscesccessoescscsessonssonses 3 Introduction to the N Series TeraFrame Gen 3 Cabinet ccccssecccccssssecccseeseccsseeecesseeecessauaeseesaaasess 3 SF Le Aad LUO Lars eae Nieto cient E tre CO T OnE CO 3 intended U Geron metes ee sre a nce teal cial ducat to E OE 5 Components of the N Series TeraFrame Gen 2 Cabinet ccccccccssccccsecccsscceesceseeeceeeceeeneeseaeeseeeeeneaes 6 MAGI ele TAR Wal Ci cate EE EET E E 7 TO GIS ROUTE anaa ae Dante wrt Nee EE a Mn Seer re SCE eer Ee ee eee 9 Oya es er 4 ay lt eresees ee eee reer rt RC enn ne eee en Poe ee eee aoe ee 9 Installatoneeies do ac A STR GOS 11 MOVING ARE CABIN CU ieonnttmedmemtedeitdod mesa dens E Oa 11 ANGCHOFING THe Ca DINE ECO NE TOOK etc els cadets 11 Bonding the cabinet t
9. cabinet 6 Repeat steps 1 4 for the other end of the cabinet 13 Configuring the cabinet The N Series TeraFrame Gen 3 Cabinet can easily be configured for a variety of applications Not only can the standard cabinet components be adjusted or removed but a broad range of accessories can be installed to create a cabinet solution that meets all the needs of your installation requirements Removing and Installing the Front Door CAUTION To avoid personal injury and reduce the risk of damaging the door or the cabinet one person should support the door while another person retracts the hinge pins and removes the door from the frame Removing the Front Door 1 Open the front door approximately 60 degrees 2 Disconnect the ground wire 3 Retract the hinge pin from the lower hinge 4 While supporting the door retract the hinge pin from the upper hinge 5 Pull the door away from the frame 14 Installing Front Door 1 Hold door in partially open position and align hinges on door with hinges on frame and slide hinges together 2 Insert hinge pin in upper hinge 3 Insert hinge pin in lower hinge 4 Reconnect ground wire 5 Close front door Removing and Installing the Rear Doors Removing the Rear Doors 1 With the doors closed lift and remove the hinge pins from both the upper and lower hinges on the door that you want to remove
10. e the top panel from lifting 4 Reconnect top panel ground wire 17 Removing and Installing the Side Panels Removing the Side Panels 1 Unlock the top side panel latch with the key if necessary 2 Retract the top side panel latch by pulling down and allowing it to tilt away from the cabinet 3 Disconnect the ground wire from the top side panel 4 Lift up on the side panel and remove it from the cabinet 5 Lift up on the bottom side panel and tilt it away from the cabinet 6 Disconnect the ground wire from the bottom side panel 7 Remove the bottom side panel Installing the Side Panels 1 Align the bottom side panel with the cabinet frame and slip the side panel into the side of the frame 2 Connect the ground wire 3 Rotate the side panel up to meet the frame and slightly lift to engage the lower half of the two side panel catches on both ends of the frame 18 Align the top side panel on the bottom side panel and slip the side panel into the side of the frame Connect the ground wire Rotate the top side panel up to meet the frame and slightly lift to engage the upper half of the two side panel catches on both ends of the frame The latch engages the front to rear frame member above the side panel Lock the side panel with the key if necessary 19 Adjusting the Equipment Rails 1 Use a 13 mm socket wrench to loosen but do not remove the nuts securing the equipmen
11. lecommunications ground use the Ground Terminal Block included to connect a bonding conductor ordered separately to the telecommunications ground or signal reference grid Remove the mask sticker at desired grounding location and apply generous coating of gray antioxidant For top location remove hole plug and route the bonding conductor through frame top first Secure grounding wire to the terminal block Attach the block to the cabinet frame with an 8 mm wrench using two M5 bolts and nuts L A Vole 12 Baying cabinets together N Series TeraFrame Cabinets can be bayed fastened together with solid side panels in place with a shared solid or with no side panels depending on installation requirements Cabinets must be the same height and depth 1 Install side panels as required Side panels must be used on cabinets with Air Dam or Intake Duct Air Managers Not shown below for clarity 2 Remove the hole plugs on top of cabinet frame 3 Use the supplied hardware and a 13mm Socket wrench to attach the baying bracket included in the hardware kit to the first cabinet Make sure to use the correct set of holes to bay the cabinets side by side 24 4 Move the second cabinet so that the cabinets are aligned This may also require adjusting the leveling feet if the second cabinet vvas not set at the same level as the first cabinet 5 Use the supplied hardware to attach the baying bracket to the second
12. o the telecOMMUNICATIONS GFOUNT cccescccesecccsseceesceceeeceaeceeesceeeueeseeeeaeeeees 12 CONTISUPING the caometseiioscidimemisimdsmitimitietuesmenmmmnm smssstuemteistsntametitaltemeris 14 Removing and Installing the Front DOOr ccccccccssccceseceeseeccscecececesecececeeenceeeneceeeceeeceseusessueeegeeeees 14 Removing ana installing the REAR DOO S item E N 15 Removing and installing the Top Paneleimeistadentmeant see te we aes anes 16 Removing and Installing the Side Panels eccscceesstisvecdsaicsnsdecatuseentnaneened sassweacdieveraeath tetes arena AA 18 Adj sting the Equipment Rallsiemilommyh mmtmsmbemtatmetanm nmsmdelmuesssmen 20 Stalling hestandardPDUBracRetS siaueeesttece o ed este dcl avet lec 20 i staling EquUiDMent sament lames aid a a a a o 21 Cable Manag SiS i sss teens ace eTa a N O A E E O mene arenes 21 PCCOSSONOS aea EE e OOE EO 22 Cable Mace CN a T E a easiness se detent 22 POWER IVIG MAS CINVCIN ascens eo tades sento N E 24 INC Gh aa Ae MENE msnm tetes E emetent NAE 25 N Series TeraFrame Gen 3 Cabinet Overview Introduction to the N Series TeraFrame Gen 3 Cabinet The N Series TeraFrame Gen 3 Cabinet System from Chatsworth Products CPI has been developed to meet a wide range of application needs The N Series is available in multiple widths heights and depths allowing for precise alignment with the size and capacity requirements for most installations The N Series TeraFrame Gen 3 Cabinet acces
13. oncombustible surface only Safety Information Ad WARNINGS Unload equipment from the cabinet before moving it Two or more cabinets can be bayed together coupled to enhance their stability Each cabinet should be anchored to the floor Before loading equipment in the cabinet be sure to adjust and lock the leveling feet to level the cabinet Do not use casters to stabilize the cabinet always anchor the leveling feet or the cabinet frame to the floor Always load heavy equipment such as a UPS at the bottom of the cabinet first and add lighter equipment on higher levels A safety risk exists when equipment is mounted on a shelf installed more than 30 inches 760 mm above the floor in a cabinet without doors and or side panels The equipment may accidentally slide or be accidentally pushed off the shelf and fall on personnel When equipment is mounted on a shelf in this condition securely fasten the equipment to the shelf or cabinet frame in a manner that will prevent the equipment from accidentally sliding off the shelf The following accessories may be used to secure certain equipment on shelves monitor tie down kit P N 11725 701 seismic equipment tie down bracket P N 14061 719 or equipment tie down bracket P N 16356 719 The cabinet can support many system configurations The amount of force required to tip or make the cabinet unstable differs with each Read and follow your equipment manufacturer s specific a
14. ries TeraFrame Gen 3 Cabinet is provided with hardware to secure equipment to the mounting rails This hardware includes 50 sets of M6 cage nuts and screws or 100 12 24 screws depending on rail style Additional hardware is available separately see Other Accessories on page 27 Cable Management CPI cable management products provide the proper cable bend radii for better data transmission fewer tangled cords and cable damage and ease in moving adding and changing connections The products assist in complying with ANSI TIA EIA installation of Category 5 5e 6 6a and fiber cables Separate the cables by type gather into bundles and fasten loosely with hook and loop fasteners CPI offers Saf T Grip Straps to fasten cable bundles P N 0200X series See Accessories Cable Management on page 22 for more information 21 Accessories Cable Management Finger Manager Kit For equipment rails Two 2 full height sections Cable Lashing Manager Slim One 1 full height panel Attaches to the cabinet frame 5 W 130 mm Cable Lashing Manager Wide One 1 full height panel Attaches to the cabinet frame 9 8 W 250 mm Ring Cable Manager For 31 5 800 mm wide cabinets One 1 full height section Ring Cable Manager For 40 1016 mm wide cabinets One 1 full height section Telescoping Cable Manager One 1 telescoping section with 5 cable spools 42U x 800 45U x 800 48U x 800 52U x 800 42U x 1016
15. sories including cable management power management thermal management and more offer additional flexibility enabling the cabinet to be further configured to support many different applications Safety Information Keep a printed copy of this User s Manual especially the following safety information in or near the cabinet A WARNINGS Improper use of this product or failure to follow these instructions may result in equipment damage personal injury or death Read and understand all instructions for proper installation and use of this product Only trained service personnel or licensed electricians shall install the equipment Be sure to use sufficient personnel to safely remove the cabinet from the pallet Do not attempt to move large cabinets by yourself Obtain adequate assistance to stabilize the cabinet during movement or hire professional equipment riggers Move cabinets on installed casters with extreme care Sudden stops excessive force and uneven surfaces may cause the cabinet to overturn Move the cabinet with the back as the leading edge Never push on the sides The cabinet shall be level stable bolted and appropriately secured to the building structure Castors are only provided to transport the cabinet from the receiving location to its install location The cabinet shall be installed in a Restricted Access Location and only used by trained service personnel Suitable for mounting on concrete or other n
16. ssembly installation and safety instructions When servicing slide mounted equipment such as servers Secure all equipment other than the unit being serviced in position to prevent it from sliding out and destabilizing the cabinet Slowly extend only one unit at a time Extending multiple units may cause the cabinet to tip over Rapid deployment of the unit could cause the cabinet to tip For protection of the equipment and personnel ground each cabinet individually to the Telecommunications Equipment Bonding Conductor TEBC or Signal Reference Structure SRS Provide the minimum spacing between the accessories components and the housing that shall be maintained for safe operation of the equipment when installed in accordance with the National Electric Code ANSI NFPA 70 As appropriate all wiring and equipment should be installed in accordance with NFPA 70 National Electrical Code and the applicable sections of ANSI C2 National Electrical Safety Code Intended Use Keep a printed copy of the Preface of this User s Manual in or near the cabinet e Install the cabinet only in a Restricted Access Location such as a data center e Use indoors only in environmentally controlled areas do not use outdoors in harsh environments or in air handling spaces e Use the cabinet for information technology and telecommunications equipment including servers and peripherals e Allow only qualified service personnel
17. t rail to the frame in two 2 locations 2 Move the equipment rail forward or backward to the desired location 3 Tighten the nuts in two 2 locations on cabinet Markings are provided on the frame to help align the equipment rails so that they are vertical as well as in the same location as the rails on the opposite side of the frame Installing the Standard PDU Brackets 1 Choose the desired corner of the cabinet to install the PDU Brackets and install cage nuts in square holes 2 Position PDU bracket against vertical frame member and install 2 screws through holes into cage nuts Torque screws to 168 in lb 19 Nm using a Phillips screw driver 3 Repeat for second PDU Bracket 20 Installing Equipment The N Series TeraFrame Gen 3 Cabinet supports all manufacturers equipment that conforms to the EIA ECA 310E standard Most equipment attaches directly to the equipment mounting rails however some manufacturers may provide brackets or slide assemblies that require additional installation Rack mount unit U markings are clearly printed on the side of the equipment rails to simplify installation of components Align equipment with the U markings on each side of the cabinet before securing the equipment NOTE Equipment rails should be adjusted to the desired location front to rear prior to installing equipment See Adjusting the Equipment Rails on page 20 The N Se
18. to use the cabinet e The cabinets must be anchored to the floor to ensure stability and a safe working environment e The load bearing capacity of the N Series TeraFrame Gen 3 Cabinet is 4 Slide Static 2 500 Ib 1134 kg Components of the N Series TeraFrame Gen 2 Cabinet nar NY Ty 1 Frame 8 Double rear perforated door 2 Front door 800W shown 9 Solid rear door 3 Equipment mounting rails 10 Solid rear door with perforated insert 4 Cable Manager Fingers 11 Bottom Panel included with VED 5 Standard top panel 12 Standard PDU bracket 6 Vertical Exhaust Duct top panel 13 Air Dam not shown 7 Side Panel 14 Side airflow intake duct not shown Included Hardware 1 2 Keys x2 E gt x 50 x 50 3 2 Standard PDU Brackets 4 M6x16 Screw and Front Mount Nut UI ANG x 2 x 4 4 2 Baying Brackets 4 M8x16 Hex Head Screws 4 M8 Hex Nuts x2 x4 x4 5 4 Anchor Brackets 4 M8x20 Hex Head Screws fi h 7 yi fi AE dF e 7 A E SH lt Y Y x 4 x2 Getting Started Tools Required 1 Utility Knife a For removing stretch wrap from around cabinet 2 13mm Socket Wrench a For removing shipping brackets securing cabinet to pallet b For adjusting equipment mounting rail c For installing baying brackets 3 13 mm Open End Wrench a For adjusting leveling feet 4 8mm Socket or Open End Wrench a For installing ground

Download Pdf Manuals

image

Related Search

Related Contents

Finisar XFP 850nm 300m    Gigabyte S1082 128GB Black, Silver  B_3095133 - Banner Engineering  Ficha Téc.  - Userpage  tel 1-800-945-7730 ~ fax 1-800-933-5107  Bandridge BPC7110GE surge protector  MANTENIMIENTO DE MOTOR DE LA MAQUINARIA AGRÍCOLA  MODEL 2900 Upflow Brining  

Copyright © All rights reserved.
Failed to retrieve file