Home
        Technical manual
         Contents
1.                    70  70  8  8  8  8  8  8                                          Fig 4 Minimum distance of the  heater from walls and ceiling  scheme    Rev4  del 17 09 2013 Pagina 16    INSTALLATION    The warm air heater must be installed by skilled personnel  qualified pursuant to law  The warm air heater must  be installed according to national and local regulations     TEMPERATURES   The operating temperatures of burner and electric components are    minimum 0  C  maximum 60  C    In the case of  EX  versions installed outdoor  at operating temperatures below 09C  CMT recommends an anti   frost kit  mounted in the burner booth on demand  This kit maintains the temperature inside the burner booth at  0  C when the outdoor temperature drops below this limit     BURNER   The warm air heater is supplied together with a modulating pre mixed gas burner  series RX   complete with gas  ramp  modulating kit and modulating air sensor  all these elements can form a complete heating unit  The burner  is assembled  wired to the warm air heater and the tri thermostat  adjusted and tested    Anyway  during the first start up and periodical inspections  check that combustion parameters are the ones  shown in the technical data table on Chapter DATA SHEET    If the appliance has to be re adjusted  for example if the burner is replaced   this operation must be performed  by a qualified engineer  according to the instructions provided in the RX burner manual  delivered together with  t
2.             tal  1             ON y  ZHOS          36  ATddNS YAMADA 1V33N39       Pagina 28    Rev4  del 17 09 2013    GENERAL POWER SUPPLY       400V  N  50Hz TR        RSTN    HH           BEENDEN  E        HEF         T2    RTI 4    9272    NEN  UE  A       L I l l ee ee 1 SSA   4  5 6       7     8 9          12 13 14 15 16 17 18 19 20 21    i 3 1  2  8  7 5     1          0 10 V                         Negri                 PIS    pl x  E     Ne N  lt    I   amp        x    8 Y yg 5 sz    x 2h 35       Be       jg   Le x         gt  x       lt     J     O O za  e    IG  Moster switch   CE  Switchin VENTILATIDN position   CI  Switchin HEATING position   FAN  Automatic control thermostat of the fan  LIMIT   Burner safety thermostat with manual reset   LIMIT  Max thermostat of the burner with automatic reset   MV1  Fan motor 1   FAN   MV2  Fan motor 2   FAN   S1 Voltage signal lamp   Se Signal lamp operation of remote control swiches thermal relays   3   Signal lamp operation of SAFETY LIMIT2    V1   Line fuse  3 15 A   F2   Fuse du    transformateur In case of short circuit or overload  the         Fusible of 24V line master swich CIG  disconnected  automatically   To reset it turn the swich anticlockwise   TF   Fire stop damper and then clockwise   TA   Timer line or TA Before thise operation  try to ldentify  TR   Transformer 230 24 V the reason for the problem   SB  Burner locking signal output The operation of safety LIMIT  yhat turns  hi  burner operation counter out
3.     3U  430 ga8604s 4nd4no 4as3uno  5 uo 3 o 4ad 4auang         Ci 401  10934 134V9        suun  30UA eod        4nd4no aa4uno2                  aauuno  Ty     UOISJ9A                             03 Au                      asjuy auojag 4nd4no you6js 6420  aeuung  gS       WHvM 005 08      WVYIVIA                  gt         puo     2 0  2 49u4ojsuod     dl             Typ                                     asjw  20 3 y3u9 YIAS 243          3  1  sS  4 O             u   Jdawjj   YL     yo 0u03 no 4aduop dogs   4 34   41   paj42auuo2s p  DI  u2  S       50                               JO 3 n24 2 34OuS 40 2592 uJ 4auung jo         5  4     4               4na4ouJ4034Suo44 np ujopuoras asnj         cna  ach  y         28513 247   TA         13375 JO                    duo  1046    gS  5           ou4auy SIYIMS 1043402              30                    duo 1046    2     duo  10465                  IS    40304 uoj  TAW   asau DI  0WOFNO uijj i aeuanog 3YY jo  403souJsu4 xowW  LIWII  335234 jonuou u3jM 4043SOUuJ4a8Uu4 439305 4euung  21197         243 40 41045044943   04FUOI                     NY Y   40141509 5SNIIV3H Ul423iI S  12    46141509 NOILVTILN3A UlUYIFIMS  32  u24  S       50        DI    48408U                  y 30 D400Q  9214322 3    VWITI 132393  3014710933 DI    o   MS        om   lt   om      4 8  of   223    E   gt   m 2              Psion          9 8                               68    9  5     2   U    6X     vdX    ONS       AOL 0    24 Ly   o9    N        di
4.    A CUT    VI   2222222              Y        23        hnnnunnnri              EUM                         2  FFF       Rev4 del 17 09 2013 Pagina 19    TABLE OF PRESSURE DROPS IN CMT PIPES AND ELEMENTS   FOR FLUE AND COMBUSTION AIR INTAKE     MODEL    Available pressure  Pa  for flue and combustion air intake        CO        TN     gt A   UI             Flue    PIPE DESCRIPTION    Combustion air intake    Combustion air intake                                 r    Flue 4 9  Rigid pipe   150 mm  Length 1 m    Combustion air intake 3 3       ELEMENT DESCRIPTION    Flue  90   moulded bend R D 1 5      100 mm  Combustion air intake             Flue 10 8 12 4 18 2  90   moulded bend R D 1 5     130 mm    Combustion air intake 15 0 13 4    Flue 9 8  90   moulded bend R D 1 5     150 mm    Combustion air intake 6 6     gt  mper  45  moulded bend R D 1 5   100 mm  Combustion air intake EE        TN    Flue  45  moulded bend R D 1 5     130 mm  Combustion air intake    o         Flue 4 9    45   moulded bend R D 1 5     150 mm       Combustion air intake 3 3     Chinese hat    terminal   100 13 7     Chinese hat  terminal   130 3 8    00  N    12 7       Chinese hat    terminal   150    TR terminal     100 mm    6 9    10 9    15 9  8 6    27 3  14 7  Flue   Combustion air intake    Combustion air intake    T LI                    TR terminal     130 mm    o         D        TR terminal     150 mm    Combustion air intake    w  UY       Rev4  del 17 09 2013 Pagina 20              L
5.   16  Frame made of aluminium  sections   17  External insulated panels                                      Models from  80  to  200   three phase  with fan s drive motor                            1  Air outlet   2  Fume box door   AN   3  Burner MS  1  lt    4  Burner anchor plate               5  Centrifugal fan     y   NI   GB     6  Air inlet        UA               7                xn       C   ja zi   8  Stack connection   M E PAS     9  Rear fume box Lo  4    9 1  Front fume box   10  Heat exchanger       11  Combustion chamber   12  Fan motor   13  Fan Limit Limit2   14  Electrical board   15  Air baffles   16  Frame made of aluminium sections  17  External insulated panels   18  Motor s belt tightening slide   19  Pulleys and drive belts                                  Note  for 80 100 the burner has a protection  see item 15 mod  50 65     Rev4  del 17 09 2013 Pagina 7    Models from  250  to    300    three phase  with fan s drive motor    1  Air outlet   2  Fume box door   3  Burner   4  Burner anchor plate   5  Centrifugal fan   6  Air inlet grille   7  Condensate drain   8  Stack connection   9  Rear fume box   9 1  Front fume box   10  Heat exchanger   11  Combustion chamber   12  Fan motor   13  Fan Limit Limit2   14  Electrical board   15  Air baffles   16  Frame made of aluminium sections  17  External insulated panels  18  Motor s belt tightening slide  19  Pulleys and drive belts       Fig 1 Warm air heater 1Ph with air recovery duct and head heater and
6.   must be cleaned at appropriate intervals  Remove it from its housing and  blow compressed air or wash it  see the  Maintenance  paragraph    The air inlet grille  6   when dirty  must be cleaned by a brush or an air exhauster  without removing  it   Should the appliance be moved to another place  be sure this manual follows it  so that the new user  and or installer can consult it     MEANING OF THE SYMBOLS USED ON THE ELECTRICAL BOARD CONTROLS    Ventilation Operation of the remote Operation of the manual Burner aff  only switch 5 thermal relays safety Limit    Ace CE    Voltage Heating       x Je Me       Rev4  del 17 09 2013 Pagina 2    GENERAL INFORMATION    The warm air heater is fit for the following applications    a  Direct heating of the air conveyed by a ventilating unit The heat exchange occurs by contact  between the external walls of the combustion chamber and the air    b  Ventilation only    To use it as according to  a   the heater shall be connected to the power line  the gas piping and a  suitable combustion product condensate drainage system    To use it according to  b   simply connect it to the power line    This warm air heater is to be used to heat the ambient air    This appliance must not be used for other purposes and  in particular  at an average outlet  air temperature over 80  C  during normal operation    CAUTION  The manufacturer is liable for the operating characteristics of the heater  providing that it is used according to the instructions 
7.   to issue the certificate of the gas supply system  as well as the final test certificate   2  The burner is supplied with the type of gas for which it has been designed   3  The calibration of the FAN  LIMIT and LIMIT2 thermostats is correct  see Chapter TRE   THERMOSTAT   4  The flue system is compliant  see the provisions regulations applicable to flues   as well as the  combustion air piping  if any   5  The environment ensures enough ventilation and combustion air  according to the standards in  force    6  The condensate disposal piping it has been installed according to the norms  see Chapter  CONNECTING THE CONDENSATE DRAIN   Note  Carefully read the manual of the burner supplied by the manufacturer    OPERATION DESCRIPTION   Heating phase  The master switch on the electrical board must be in the  1  position  and the  change over switch in the  HEATING  position  Whenever the room thermostat requires heating  the  burner begins its self test and pre wash cycle  which is followed by combustion  Within approximately  5 minutes from the beginning of the combustion  the FAN thermostat starts the ventilating unit  automatically  When the burner is turned off by the room thermostat  the ventilating unit remains on in  order to cool the heat exchanger  and is turned off automatically by the FAN  to prevent cold air  supply    The burner can be stopped also by the LIMIT  the burner s max  temp  thermostat   calibrated at  80      if the temperature of the air leaving the he
8.  HEATERS OF THE  AS COND          EX  SERIES             14  DATASHEET  series    AS COND       AS COND  EX                 lios 15  INSTALLING THE WARM AIR HEATER        ITS ACCESSORIES                                     nennen enne nnne 16  HEATER LOCATION AND GEEARAN CE  usara uta DEO d        um tia 16  HEATER  LOCATION                                                                   16  HEATER DISTANCE FROM WALLS          un      Sana ukasa ran il 16  IEEE Mr Mem      17  TEMPERATUR                                    it a ceda  17  BURNER                                 17  BAS PIRE s za                   LU                     aaa nawan 17  GAS WHORE AND ALARM DEVICE aria               17  ELECTRICALCONNECTHONS uuu      17  CONNECTION  OFTHE FLUE FO THE STACK uuu u un      a un      18                                            uu Qum            18  TABLE OF PRESSURE DROPS IN CMT PIPES AND ELEMENTS                eene enne nnne 20  FLUE AND COMBUSTION AIR INTAKE ELEMENTS  eii             ena             ca    bea Ub                   22  CONNECTING THE CONDENSATE DRAIN soll u u P                       de Pi fep Er iol Gu dut           23  ASSEMBLY      DIRECT AIR DEBIVERY  PLENUM      unu A      24  INSPECHONS ON FIRST START UP uuu teatro    eth      abbastanza 24  B nis iSo TAS    to 25  zh e MPO Cm 27  WP NH        ei 30  CEEBNING THE HEAT EXCHANGER T                                                                     30  IROUDEESHO TING uuu uuu y         __  _6__6_
9.  LARGE field  Displays ambient temperature checked by the    CLIMA     Select Sleep operating mode  Lockmode  The parameter has already been set  Time bands active or display Clock  Selecttemperature  inside outside        aximurn  minimum  Fig  3    11   SMALL field  Displavs temperature of SetPoint     Rev4  del 17 09 2013 Pagina 37     A   Version with direct connection forthe digital input                           Ambient Temperature             R2  Output 2   ANDA       Power oi BEER  Fig  4 supply 22 35     Code With roof top  do not connect  ADCA000110 terminals 1 2     Analog output    Connessione chiave  programmazione  paramet  IROPZKEYOO                Connessione per sonda  dise di uriia esterna    Fig 5 Fig 6    MOST IMPORTANT PARAMETERS TO BE SET BY THE INSTALLER    We remember that     parameters dFA e dSA are factory set and must not be changed by the installer customer  iif not agree with the manufacturer of the  warm air heater    parameter rtC real time must be set by the installer    parameters SLP  dAy  nlt and relevant ambient temperature Set Point T  winter  summer  day  night   can be modified b  the installer  from the default value factory set  see table of parameters   In order to set  verifie the parameters procede as follows     SETPOINT for ambient temperature T  depending on different function modes dAy  nlt  several temperature Set Point T are factory  set  you can see on display SMALL   11  fig  3    To reset change press SET for more than 5 
10.  Limit signal lamp    a tri thermostat consisting of 3 thermostats  which perform the following control and safety functions   located on the top  above the heat exchanger       FAN  TR   thermostat normally opened  to automatically start and stop the ventilating unit during the   HEATING  phase     LIMIT  TW   normally closed  automatic reset max  temp  thermostat for the burner  which stops the  burner automatically  to make sure that the temperature of the air leaving the heater does not exceed  the safety limit      LIMIT2  STB   normally closed  automatic reset safety thermostat for the burner  which stops the  burner automatically  to make sure that the temperature of the air leaving the heater does not exceed  the safety limit set by the reference standard  It is calibrated at 100 C  by the manufacturer  these  limit must never be modified  to prevent dangerous overheating  to reset the burner  see the  instructions on Chapter TRE THERMOSTAT      Rev4  del 17 09 2013 Pagina 3    OTHER ESSENTIAL SAFETY REQUIREMENTS    Electrical equipment  All warm air heaters are checked for conformity as follows   Visual inspection on the electric circuit  and connection tightening   Check the grounding continuity   Insulation resistance test   Voltage test    v v v v    Temperatures  The temperatures of accessible zones  for the manual use of the warm air heater  are  in compliance with the reference European standard     Noise  Appropriate measures have been adopted to minimize nois
11.  be ordered separately    CAUTION  When the filter has been washed for the third time  replace it with a new filter  with the  same code     v v v v    VENTILATING UNIT  Check  at least once at the beginning of each season    gt  The proper alignment of pulleys and drive belts  if any  and check them for wear  if necessary   replace them with belts of the same size    gt  The direction of rotation of the ventilating unit  indicated by the arrow on the fan  see fig 7    gt  The belt tensioning  Grasp them  they must not be become loose by more than 2 3 cm  see fig  8   To adjust tensioning  screw or unscrew the belt tightening bolt on the motor slide  18     gt  The motor absorption  in Ampere  must not exceed the value specified on Chapter DATA  SHEET    gt  Check the tri thermostat performance  see Chapter TRI THERMOSTAT      BURNER   For burner maintenance  comply with the instructions provided in the RX burner manual  delivered together with  the heater    Check    1  The gas pipe tightness   2  The tightness and condition of the stack and connecting ducts or of the flue system combustion air intake     COMBUSTION ANALYSIS   At least once  at the beginning of each heating season  unless the current standards require shorter intervals   have a combustion analysis carried out and recorded in the POWER PLANT or PLANT HANDBOOK    NOTE  Take note of all replaced components     TABLE OF MINIMUM MAINTENANCE INTERVALS    MINIMUM INTERVAL TYPE OF PERIODICAL MAINTENANCE  Every day C
12.  instrument  Basic insulation  between the relays   UL 873  NO 1A resistive 24Vac  30Vdc  100 000 cycles  PILOT DUTY  24Vac     make 15    break 1A  30 000 cycles       Precision of humidity measurement  in the models where featured       3 rh at 25C      5  rH from 0 to 60   C  range 10 90   Rh    CONNECTIONS   The installer must connect the  CLIMA  regulator   see fig  4   to the electric control board of roof top  with n  6 cables   and  keeping separate the tension cables from the analogue output 0 10V ones for the RX burner proportional regulation   The  CLIMA   regulator must be installed not more than 30 m  from the warm air heater X or roof top  as cable length     e digital input       non insulated version  direct connection of the voltage free contact  contact closing current  3 5 mA        insulated version with external power supply and 24 Vac contact  class II safety external power supply separated from the 24 Vac  of the  instrument  Fig  4b   Outside probe connection with standard Carel probes   10K 25        3435        maximum length  30 m with min cable cross section 0 5 mm          Digital input connection  maximum length 10 m  min  cable cross section 0 5             e Analogue output connection  maximum length 10 m  min  cable cross section 0 5 mm    e Relay output connections  cable length max 30 m  And cross section from 1 5 to 2 5 mm   Reinforced insultion class II      Relay output   to use the instrument in compliance with UL 873  a load with a maxi
13.  outputs by supervisor has been set  but there is no connection  parameter Lin   on     TECHNICAL SPECIFICATIONS      Power supply  24 Vac  10   15  50 60Hz 1 VA  22 35        0 5W  e Operating conditions  0T60  C  10 90 RH non condensing  e Storage conditions   20T70  C  10 90 RH non condensing  e Dimensions  mm   135x86x36mm   e Environmental pollution  normal      Degree of pollution  degree II   e Software class and structure  A   e Actions type  1C      Index of protection  IP20      Ball pressure test temperature on the plastic of the frontal case  100           Ball pressure test temperature on the plastic of the back case  125   C   e Classification according to protection against electric shock  IT  to be integrated into class I or II appliances   e Period of electrical stress across the insulating parts  long   e Control device designed to be supplied to  manufacturers  installers and maintenance personnel   e Immunity against voltage surges  category 1   e Cross section of the wires  mm    from 0 5 to 1 5 mm      e Precision of the inside temperature measurement      19C  e Precision of the outside temperature measurement  NTC  standard 10k  range    40   60   C precision     0 5   C   sensor precision       1  C from 0 to 40   C      1 5   C above  e 0 10V analogue output  non insulated  for proportional control  precision    5  max load 2 KOhm  max current 5 mA      Approval of the relay outputs  EN60730 1  NO 1 1 A 250Vac  class II reinforced insulation from the
14.  selection using the  button  ff changing the temperature display mode using parameter Unt  this becomes the default display  made when switching the Instrument an   Parameter for control with average value sensor values  Defines the average control temperature            based on the weighted average of the Inside temperature   m and outside temperature  TEL    the measurements rust be valid and Tm is achieved with the following formula        z        ned    TE         100     1510 15                         OFF       Select serial communication     0              protocol 96 kbys   1  CAREL protocol 192 kb s   2  Modbus 9 6 kb s  even parity  8 bits  1 sion  3  Modbus 15 2 khys  even parity  8 bits  1 stop   amp  ri qien Sits  2 stop    Password for ci the parameters    Set to tino password  s required   Set other than zero  the ame value must be entered to access the par      __  bei                       Note  the     symbol means that the parameter 5 shown an 2    fields     Rev4  del 17 09 2013    Pagina 41       ACCORRONI A2B Accorroni E G  s r l                       Via d Ancona  37   60027 Osimo  An    Tel  071 723991 r a    Fax 071 7133153  Climate Technology web site  www accorroni it   e mail  a2b accorroni it    
15.  soe  aso  ime                       ow                me    e   ze   xe   65   es            ime                              no  70  aro  wo   ze   x   e   95      1  complete with burner and gas ramp                 O    1  complete with burner and gas ramp       Rev4  del 17 09 2013 Pagina 12    PLENUM   STANDARD HEAD FOR DIRECT AIR DELIVER  WARM AIR HEATERS OF THE  AS COND  SERIES    Air blown by the nozzles on three sides  and dimensions in mm    7    1  Short side  Q    long side  P    short side  Q      2  The final speed of the blown air is 0 15 m sec  and the nozzle fins    deflection is 09  If deflection   30     multiply the blown air value by 0 65        Note  T x S   R x S   DIMENSIONS OF A SINGLE NOZZLE    Rev4  del 17 09 2013 Pagina 13    FILTER BOXES ON AIR INLET DELIVERY     WARM AIR HEATERS OF THE   AS COND  and  AS COND EX  SERIES    Filters    pressure drops and dimensions in mm    V Y    Pressure drop    s0   870   620         530 560            7  Sor             2006004   Xe      6   670   620                  560  needs   9 _  E Lii me I   so   580  680  _60        630 101006058 _    1x625x500x48  ow  B  1x625x400x48    350   1460   840   200   1400  800     625400098   19    2x625x500x98  w           1440    200     1400     800     4x625x40098      2x625x500x98      1440     1400     4x625x400x98    aa   2  625  500  98   1x625x400x98   2x625x400x98   2x625x400x98    Efficiency ASHRAE52 76 DUST WEIGHT  87     2  Pressure drop of a new filter  CAUTIO
16.  the  main menu       Accesses the menu for displaying the current outside temperature  and the maximum and minimum since the instrument  was last switched on  To display the various temperatures press Av   For the meanings see the box with the house symbol  Press the PRG button to return to the main menu    A From the main menu increases the value of set point displayed in the large field  From the other menus displays the    variables or the parameters or alternatively changes the value if first pressing SET           Rev4  del 17 09 2013 Pagina 35       v From the main menu decreases the value of set point displayed in the large field  From the other menus displays the  variables or the parameters or alternatively changes the value if first pressing SET           Important  the operating mode can be changed with the instrument on or off  When the mode is changed  the user is asked whether to  use the default parameters for that mode  If yes  press SET  tasto UP and SET again  Otherwise press PRG to exit     TABLE OF ERRORS  Code displayed Description    ALE External alarm generated by the digital input  If set from parameter   EE Parameter memory alarm  Stops control of the instrument until the default parameters are loaded   E1 Inside temperature probe alarm   E2 Outside temperature probe alarm   Eth Digital temperature or humidity sensor alarm  only in the models where featured    Ert Real time clock alarm  only in the models where featured    ELN No link  control of the
17.  the condensate produce during methane combustion is approx  3 5  This pH can be  neutralised by a condensate neutralisation kit     TO THE HEATER                               _ 2 TOTHEHEATER               A 4  F F elbow     Mi    FF elbow        1  M 3 8  F reduced nipple   1  M 3 8  F reduced nipple    cry  fy         A       EEN                                   Trap B01 003 000024    La   Trap B01 003 000024    EE   As y  o      MATERIAL  CONDENSATE    POLYPROPYLENE DRAIN PIPE MATERIAL  _ _ CONDENSATE    POLYPROPYLENE DRAIN PIPE    Fig 5 Trap with closed piping and trap with open piping    Rev4  del 17 09 2013 Pagina 23    ASSEMBLY OF DIRECT AIR DELIVERY PLENUM    The plenum  if any  must be assembled as described on chapter PLENUM of this manual  it is  recommended to apply silicone sealant on contact surfaces    In the standard version  the plenum is provided with grilles on three sides and adjustable  horizontal vertical fins     CAUTION  Make sure the air delivery fins are not too inclined  for their capacity and  delivery would be reduced     INSPECTIONS ON FIRST START UP          Check the performance of burner RX and make sure that the emissions of CO2  CO and Nox do  not exceed the pre determined tolerances  as shown in the table on Chapter DATA SHEET   Consul the manual of the RX burner  delivered together with this warm air heater    Visually check that the burner flame is regular and does not hit the bottom of the combustion  chamber    Check that the directio
18.  warm air heater 3Ph with  heatd heater     Rev4  del 17 09 2013 Pagina 8    WEIGHTS and DIMENSIONS  ASCOND   SERIES    Weight in  kg  and dimensions in  mm          Head Heater  connection                    Connection of  the      delivery             Connection of  the      delivery  duct                The air inlet grille is on the left till Mod  200   On the right till Mod 250 onward  The grille position can be reversed           HEATER Weight  1  Net  Head Flue Air Outlet Inlet Air Inlet Frame Flue                    n             E   F   G  H   I   L        Kg   Kg   Kg      50   870   636   1750    65   870   636   1750       B0   1020   750   1950    405   935    670   940   600   940    40    190    270   282    27         100 1020   750   1950   405   935   670   940   690   940   40   130   275   287   27        150   1440   1020   2340   405   1070   940   1360   760   1360   40   150   435   450   42      175   1440   1020   2340   405   1070   940   1360   760   1360   40   150   440   455   42      200   1440   1020   2340   405   1070   940   1360   760   1360   40   150   445   460   42       250   1790   1020   2340   405   1130   940   1710   760   1710   40   200   570   590   50       300   1790   1020   2340   405   1130   940   1710   760   1710   40   200   580   600   50      1  complete with burner and gas ramp       Rev4  del 17 09 2013 Pagina 9    COMPOSITION OF THE  AS COND EX  SERIES HEATER    Models from  50  to  65   three phase  with fan s d
19. 3 phase voltage heaters bearings  unit     8  During operation  the burner stops before the   1  LIMIT Operation             iu pere on  2  Safety LIMIT2 operation  2  2  Reset the burner See Chapter  TRI THERMOSTAT            A A A           NR CNN iii  NOTE  IN CASE OF BURNER FAILURE  CONSULT THE MANUAL OF THE    RX    BURNER  DELIVERED TOGETHER WITH THE WARM AIR HEATER     4  Contact the authorised after sales service of the burner        1  Reset the thermal relays  according to 8 2         ANNEXES  MANUAL  Clima    CAREL for the modulation of burner    Clock digital proportional temperature regulator  Timer and real time clock for day and night  operation   Delivered with the warm air heater series AS COND   AS COND EX  with modulating burner RX    General features   CLIMA  Carel mod  ADCA000110  is an electronic instrument  installed in the heated room  as the remote user terminal  with  following operating functions    1  Regulates the modulation of the RX burner  The modulation starts when  CLIMA  detects a room temperature of Set Point T  minus 29C  configured by the manufacturer with parameter dFA    CLIMA  operates a proportional regulation  modulation   of the RX burner  with 0 10V analogue output  Example     CLIMA  room temperature Set Point 20       CLIMA  starts modulate the burner when detect 18     and modulates between  18 20        The modulation can be operated even         NTC sensor on air outlet temperature  example SET POINT 44     of air outlet  temp
20. 6_6___  _  _    _      33  ANNEXES                                ts 34  MANUAL  Clima  CAREL for the modulation of burner                                             nn             34  MOST IMPORTANT PARAMETERS TO BE SET BY THE INSTALLER                                                      38    Rev4  del 17 09 2013 Pagina 1    VERY IMPORTANT NOTICE    This manual is an essential and integral part of the warm air heater and must always follow it  The  user or the installer must read it carefully  before operating or handling the appliance   The manufacturer may not be held liable for any damage to people  animals and property caused by       improper use of the appliance        unintended use of the appliance       any use of the appliance non compliant with the instructions of this manual       any use non compliant with European  national and regional laws  regulations and standards        The manufacturer will accept no liability in the event that the heater is not installed  periodically  checked or serviced by authorised service centres or qualified staff  i e   engineers with a specific  technical knowledge about heating installations in inhabited buildings    This appliance may not be used by people  including children  with reduced physical  sensing and  mental capabilities or with insufficient experience and knowledge  unless they are monitored or  instructed by a person responsible for their safety   This manual is an integral part of the warm air heater  and there
21. AX GAS CONSUMPTION      15     1013 mba                   620 at 20 mbar 6 47 28 57          GAS G25 at 25 mbar 752   94   121   150   220   250   293   3324   3853  PROPANE G31 at 37 mbar 4 75 20 98   2432  CAT              67   09   a   ss   ss    amp p       e      NOx   x50 Mg kWh   Classe 5    ELECTRICAL DATA O  Fan motor supply voltage V Ph Hz 230 V   1   50 400 V   3 N   50  50Hz      Sound pressure  at 5 m  CS  sasa    ELECTRICAL DATA  WITH USEFUL PRESSURE   300 Pa    ELECTRICAL DATA  WITH USEFUL PRESSURE 2300                      _  IVETE           Fan motor supply voltage V Ph Hz 400 V   3 N   50          Flue connection combustion air intake        100 100 130 130 150 150 200 200    GAS CATEGORY II 2H3B P    Type of appliance  based on exhaust tipo B23    C13    C33     C53  devices combustion air intake    Warm air heaters can be used together RIELLO RX80   RX80   RX100S    RX120 RX250 RX250 RX250 RX350 RX350  with RIELLO burner S PV S PV PV S PV S PV S PV S PV S P S P    Air flow rate at 18 9C 4700    Useful static pressure    24000  200  3    5   s   aw   sso   56         9 9 3  0 1 162  3  5 5 88  1             2 4  D2  1 0 0 00     0     3  1 5  3    2  19   0    95 12    Rev4  del 17 09 2013 Pagina 15    INSTALLING THE WARM AIR HEATER AND ITS ACCESSORIES    IMPORTANT  This part of the manual is intended for the installer or qualified personnel     HEATER LOCATION AND CLEARANCE  The warm air heater must be installed according to the provisions of the Ministeri
22. DI PROTEZIONE CONFIG  TIPO    PROTECTION LEVEL IP X5D CONFIG  TYPE B23  C13          C53  PROTECTION DEGREE CONFIG  TYPE       Rev4  del 17 09 2013 Pagina 4    PACKAGING    The warm air heater is delivered on a pallet  and is protected by a pluribol film  The air inlet plenum  if  installed  is packaged together with heater or separately  according to the models     TRANSPORT  LOADING AND UNLOADING   Transport  loading and unloading must be carried out carefully  to prevent damage to the appliance  as  well as to people  animals and property    To load and unload the appliance  use a lift truck of suitable capacity  according to the safety factor   see the gross weight of the appliance in the table on Chapter WEIGHT AND DIMENSIONS   During  these operations  the centre of gravity of the appliance must remain in the middle  without dangerous  inclinations    After removing the packaging  check the condition of the appliance  If in doubt  contact the  manufacturer or its agent  The heater is a compact appliance  with its electrical board and the burner     PACKAGING MATERIALS   Packaging materials  wood  cardboard  polystyrene  nails etc   shall be collected and disposed of  according to the laws in force    CAUTION  Dont leave these materials within the reach of children  because they may be a source of  danger        Generator series  AS COND EX  packaged    POSITIONING    After removing its packaging  the heater must be positioned as described on page 17   CAUTION  Don t tur
23. During installation  make sure the heater is isolated from the mains supply  by means of a dedicated  omnipolar switch  min  space for contact opening  3 mm   installed upstream of the heater  of suitable  size  based on the heater s total electric load and in compliance with current standards  The main power  cables must be of suitable size and T marked  The ground cable must be longer than the others  by  approx  2 cm   The heater s supply voltage must be 1F 230Vac  50 and 65  and 3F 400V N 50Hz  80 to  200   The heater must be grounded according to the standards in force       Connect the fire damper  if installed  to the heater s electrical board  When installing the room  thermostat       nstall it in a room heated by the warm air heater  Do not leave it under direct sunlight  Do not install it  on a cold wall  but rather on an internal wall  Do not install it in a place directly blown by the air jet     Rev4  del 17 09 2013 Pagina 17    CAUTION  Do not connect the timer  if installed  in series with the mains supply  connect it  to the room thermostat s line  Otherwise  the timer would turn off the heater  and all the  unused heat would remain in the appliance  which could be damaged     CONNECTION OF THE FLUE TO THE STACK   If requested by local regulations  or when other options are selected  the warm air heater must be connected to  a stack of proper sized  made of suitable materials and installed according to national and local environmental  regulations and standar
24. EGEN  Available pressure  Pa  for flue and combustion air intake EXE  PIPE DESCRIPTION Pressure drop in CMT pipe for  length unit Pa m   O       Rigid pipe   200 mm  Length 1 m      Rigid pipe    250 mm  Length 1 m   pe Papa         Rigid pipe    300 mm  Length 1 m  ELEMENT DESCRIPTION Pressure drop Pa element    me afe   90   moulded bend R D 1 5      200 mm               90   moulded bend R D 1 5     250 mm              ____  90   moulded bend R D 1 5     300 mm   fe Rsa   45   moulded bend R D 1 5     200 mm          45   moulded bend R D 1 5      250 mm    45   moulded bend R D 1 5     300 mm        Chinese hat  terminal   200     Chinese hat  terminal 250              ameer    TT   _         I   pasene O  Few                        w    TR terminal     200 mm    TR terminal     250 mm    TR terminal     300 mm       Rev4  del 17 09 2013 Pagina 21    FLUE AND COMBUSTION AIR INTAKE ELEMENTS     T6  CHINESE                T20   WEATHERPROOF  TERMINAL    90  MOULDED  BEND          90  T UNION    45  MOULDED  BEND    5 30   ADJUSTABLE  FLASHING   T7      WINDPROOF  WALL TERMINAL                     ELEMENT   ELEMENT DIMENSIONS      A a  dus    gt   185   210  205   225   le  92   90  213   235  DE    120   160  150   150    A  B  A  B  A  B    200      150  2            240   185  240   135  5  0    9  245    140  310           i    170   220  150   150       Rev4  del 17 09 2013    Pagina 22    CONNECTING THE CONDENSATE DRAIN    The warm air heater is provided with a condens
25. IEeT shows alarm EHI and DET D ect      Oto 50    Humidification set point 1010 70 W rH     E    Dehumidification set point 100 70    Humidity differential for the activation of      analogue output and the rely     Dehumidification differential for the activation of the relay  Parameter to define the humidiication dehumidtication status In day and night mode    Activates      deactwates humidification or dehumidification control  based on DIP 4  with the time bands   The parameter can have the following three values   0  Time bands disabled   The hurnidificationzdehurnkdhcatlon contro  ls always active  IF featured  and E configured In relation to    1  Time bands enabled    When switching to the daytime band  hurnidiicatiengdehumidficatlan cantral  depends on dip  E  When switching to the night band  humidificationdehumidiicatian control  depends an           Is  deactivated     2  Time bands enabled   When switching to the daytime band  humidificationidehumidification contro  depends on dip  E  deactivated    When switching to the night band  humidificatiendehurnidification control  depends on           ls  activated    Humidity set point automatically compensated by the outside temperature       humidity control ls featured  the ambient humidity Is controlled with an automatic set point  defined  from 1H to 7H using the buttons  as specified In the corresponding table  see page 15     If set to OFF the mode    disabled   Setting one of the levels In the table  the control
26. N  For plant calculations  this pressure  drop for rather dirty  but not clogged  filters must be increased by at least 50    and must be subtracted from the useful head of the heater        Rev4  del 17 09 2013 Pagina 14    DATA SHEET series   AS COND     AS COND EX       THERMAL PERFORMANCE   50   80       250   300    Rated heat input Qn E m 2 gw 313  Rated heat rating Pn 73 0 1166   1786   2018   2342   269   310   Pn 7 7 1 f  Heat input at 50  of the rated heat input 30 55 49 25   10 5   119   162   187 8    191 3    I    Thermal efficiency at 50  of the rated    heat input Hue    101 8    102 6 104 9 101 8 104 8 104 5 103 9 103 3    7  3  9  2  7  7  9    2 02    109    Minimum heat input Qmin    NEN   D    me                 wo Dm Des  MN     ma          a  sa   s  s    6  6 1  8      0  2  06           4     15  50     4    Heat rating at        23 3    7 9  31 8  2  Thermal efficiency at minimum heat input 106  Qmin  3  5  0    Backpressure in the combustion chamber  pus 4  with G20 at Qn 4                                the combustion chamber         4  with        at        Condensate produced when the room       temperature is 20        2   AERAULIC PERFORMANCE  15    106 9    Heat rating at 50  of the rated heat  input    107 8 107 8 106 9 106 9 106 9 107 4    8  9   3  6 2  5 9     5  0    SD              N    SD                  A IM     pat el           pw  wee   de 3 dove ns    6100 15800 20800   C   am   no  am  ue  ue   2  DELTA T AIR at PN   C 37 4 37 1  M
27. T  TW   Arancio Orange       Ricarica  100  C LIMIT2  STB        TRITERMOSTATO TRITHERMOSTAT JUMO  3Ph     Serie GP XP Presso       FAN  TR  Bianco  White UR   Rosso Red  Rosso  Red  Grigio  Grey LIMIT  TW   Arancio Orange    LIMIT2  STB        Rev4  del 17 09 2013 Pagina 26    ELECTRICAL DIAGRAMS    40197109354 713499 UHM    Sa3lv3H                  69 06 40 WVeDVIG       E ECC          fi Vertes weeded    oM    ge804s 4nd4no aa4uno   uono48d               gu   4nd4no Jajuno gt                                    TY   andano youbis             usuung  gs    G9 puo 0G                     puoGg          vg   esng aUll  Ij   v       eun          VI   jpubd jou3uoo jeuung 4O430u         AN  23534 DIZOWOAND YIM USsUUNG ay  4O 303so0uJ4a8u3 xoyw           323524  onuou ua3iM 4043SOuua8ua  93340S               21191          SYR JO  3934SOuJ4a8Uu  JOUZUOD 2I40uO4hnuy  NY 4  UO IZISOd SNILV3H UlYIFIMS  I2   UO IZISOd               U IU  23l S  39   U241IMS         5      DI       19110454  ayy      suoli gt auuo     34019710933           132395 OL    ZH 05  A        dl    AlddNS              1989N39           s   S   2   8   s   r  EE   z   N   2  D                  LLL T       J9 D  U                      eu  jo            105132213    Pagina 27    Rev4  del 17 09 2013                   T0e 20 v0    10119  9 LL 34 04n2                u23J4S 1043402                 IM  HERE A null                                     JOJ UDzIKS 10 502 230028   Tl  es ES duo       pajouBis S           
28. WARM AIR HEATERS    fitted with low NOx modulating  pre mixed gas burners    AS COND  AS COND EX          USE INSTALLATION AND  MAINTENANCE MANUAL        gt  lt   TT  Q         O  Y   lt   Q         O  Y   lt         ACCORRONI    A       INDEX    WND E eT amam                                             1  COMPOSETIONAOE THE  AS COND SERIES  HEATER all ecc 7  Models from    50    to  65   with single phase motor  directly coupled to the fan                                                         y  Models from  80  to  200   three phase  with fan s drive Motor                   i 7  Models from  250  to  300  three phase  with fan s drive motor                                                    nnn 8  WEIGHTS and DIMENSIONS   AS COND  SERIES    irri tii deret Pelo      Gro Gavan opo          Reg        9  COMPOSITION      THE    AS COND EX    SER ESFIEATER neri E                     Z aypa sd so oltre 10  Models from  50  to  65   three phase  with fan s drive motor                                                  nne 10  Models from  80  to  200   three phase  with fan s drive motor                                                  enne 10  Models from  250  to  300   three phase  with fan s drive motor                                            eene 11  WEIG  TS and  DIMENSIONSTAS COND EX  SERIES inicia estetico p L        b pat ba EE ERES paa tS b   Si      12  PLENUM   STANDARD HEAD FOR DIRECT AIR DELIVER                  i 13  FILTER BOXES ON AIR INLET DELIVERY   WARM AIR
29. after sales service  to check the burner           3  With the master switch on  I   the voltage 1  Poor connection of the room thermostat timer   lamp on  the change over switch in the HEATING  position and the room thermostat on  the burner    does not start     2  Defective burner   3  The max  LIMIT thermostat is on        3  Wait until the air temperature drops below 65         4  Like 8 3   with the SAFETY LIMIT OPERATION   1  The max  LIMIT2 thermostat is on  because the air leaving   1  Reset the burner  as described on Chapter TRI   switch on  the appliance is overheated  THERMOSTAT    5  Come al punto 3   ma il bruciatore dopo la fase di ii  pela va birnir orto motetid  prelavaggio va in blocco e non si forma la fiamma         Se  1  Excess FAN calibration    1  Calibrate it  see Chapter TRE THERMOSTAT   6  The burner is on  but the ventilating unit is not   2  Defective FAN  2  Contact the after sales service to have it replaced     yet running and  then  starts stops continuously    3  The temperature of the incoming air is below 0  C  3  Try to increase this temperature   4  Insufficient gas flow rate  4  Contact the authorised after sales service of the burner     7  The burner is on  but the fan does not start 1  The remote control switch s thermal relays are on  due to  and the the motor    REMOTE CONTROL SWITCH THERM  lamp is        2  Faulty electric motor s   defective contact or seized 2  Contact the after sales service  to check the ventilating  only for 
30. al Decree dated 12  April 1996 and of other regulations and standards  as applicable  of which the installer must be aware     Ventilate the room where the warm air heater is installed according to the provisions of the laws   regulations and standards referenced above    Try to cover all the heated area with the blown air   In the presence of considerable air infiltration  e g  from doors   adjust the air flow   Do not direct the air flows against obstacles  such as pillars and stored material   If the room is provided with air extractors  install the warn air heater on the opposite wall  as  well as an outside air intake  in order to supply new air     v v v v    HEATER LOCATION  Leave an appropriate clearance around the heater  free of combustible material  and calculate the distance in  compliance with the M D  dated 12 April 1996     HEATER DISTANCE FROM WALLS   To calculate the minimum distance of the heater from walls and ceiling  refer to the M D  dated 12 April 1996 and  other regulations in force  The minimum distances recommended by the manufacturer for maintenance of heater   burner and accessories  if any  are indicated below           B  1     mm          1000_   6s  100    so   100            1000   aso   130  1300   200   1300   25e   1300                       1300 _    1300   80        1300   820   60      Check this height based on the possibility of  disassembling and servicing the flue system        0   0  20  20  20  20  20  20  20                  89   
31. and subject to the limits described  throughout this manual    Warranty   If the heater is not installed according to this manual  the warranty will become null and void     STRUCTURAL INSPECTION AND SAFETY REQUIREMENTS    The warm air heater is made of an aluminium frame and an external panelling in pre painted sheet   the panels  interior is insulated by a glass wool mattress The heating section includes a combustion  chamber and a heat exchanger  In this area the insulating mattress is protected from overheating by  galvanized steel sheet  The ventilating section  with a centrifugal fan  driven by a single phase or  three phase belt drive electric motor  is coupled with the heating section    The ventilating unit is provided with a finger protection grille  that can be removed only by means of a  tool  The combustion chamber  made of stainless steel for high temperatures  is bolted to the frame   so that its thermal expansion does not affect its life over the time  The heat exchanger  made of  stainless steel pipes  is welded to the combustion chamber  Inspection and maintenance operations  may be carried out through large openings on both sides    On the front of the heater you can find  a pre mixed gas burner  with gas ramp   the modulation kit  connected to an air temperature sensor and an electrical control board with      Master switch   HEATING     BURNER STOP     VENTILATION switch     Voltage signal lamp     Signal lamp for remote switch s thermal relays     Safety
32. ar panel  flue connection  8  and the 2 covers of rear fume box  9     Clean the pipe interior  after removing the vortex tubes    Collect the soot at the back  Before reinstalling the 2 covers of the fume box  check that its seals are  intact  otherwise  replace them with similar seals  with the same code   Remove the pipe on flue  connection  8  and clean rear fume box  9      COMBUSTION CHAMBER  11    Remove the burner from its plate  4     Clean external walls for soot and deposits    Check that the combustion chamber is not damaged    Check that the seal of the burner supporting plate and the relevant seal on the nozle are in good  condition  if not  replace them with seals having the same code    Note  All seals are asbestos free and compliant with EC standards     CLEANING THE FILTER ON AIR INLET   the filter is an accessory     dirty filter reduces the air flow  increases discharge temperature  reduces heat  exchange and heater efficiency  It is very important to clean the filter at regular intervals  so that it remains  always clean  The cleaning interval depends on the amount of dust in filtered air     To clean it  proceed as follows     Rev4  del 17 09 2013 Pagina 30    Remove the filter from its seat   Shake it and leave the dust fall   Blow the filter with counter current compressed air   From time to time  for a more thorough cleaning  wash the filter in warm water with some  detergent  dry and place it in its seat again   CAUTION  The filter is an accessory to
33. ate drain pipe  flue side  which drains the condensate  produced in the heat exchanger  The sloping tubes of the heat exchanger let the condensate flow  towards the rear fume box and the condensate drain  A trap is also supplied  and the installer shall  connect it to the heater s condensate drain pipe and to the condensate disposal system  see the  drawing below   Unions must be watertight  The disposal system piping must be calculated based on  the condensate litres hour  see the table on Chapter DATA SHEET   and its internal diameter must not  be less than 20 mm    The condensate disposal pipes must be made of synthetic material  such as PVC or corrosion proof  stainless steel   Do not use galvanized steel pipes    The trap provided is complete with a float valve  to prevent fume leaks  and must be filled with water  before the first start up    The condensate disposal piping can be      provided with trap and closed disposal pipe  Use this system for warm air heaters installed in the  heated ambient or inside a room    Due to frost hazard  install an open piping  see the drawing below  for outdoor disposal systems   Caution  the condensate disposal piping must be installed at a level lower than the trap      free  this system is recommended for outdoor warm air heaters  if permitted by local regulations  The  condensate is drained directly outside    Caution  To let the condensate out  make sure the warm air heater has been installed on a flat surface   Caution  The pH of
34. ater exceeds this temperature limit  The LIMIT resets  the burner automatically  once the air has cooled  The burner can be stopped also by the LIMIT2  the  burner s safety thermostat   calibrated at 100  C  if the temperature of the air leaving the heater  exceeds the safety limit set by the applicable standard    To reset the burner  let the air cool down and then proceed as specified on chapter TRI THERMOSTAT  of this manual     CAUTION  The LIMIT2 activation detects an operational fault  please contact an authorised after   sale service or qualified technical personnel     STOP   If the switch is moved to the  BURNER STOP  position  the burner stops  while the ventilating units  continues to turn  up until it is turned off by the FAN thermostat  on completion of the cooling phase    to de energize the heater  move the master switch  IG  to position  O     CAUTION  Before disconnecting power supply  with the master switch   make sure that  the heater has cooled down  otherwise the appliance life could be shorter     Ventilation phase  Turn the switch to the  VENTILATION  position  the heater will work as fan only   and the burner will be cut off    CAUTION  Never turn off the heater using the master switch  use its own switch  the room  thermostat or the clock  if installed  otherwise  the heat exchanger is likely to be still  heated and could be strained     MODULATION REGULATOR CAREL TYPE CLIMA   read his instructions supplied with  the heater    The burner  of modulatin
35. changer   11  Combustion chamber   12  Fan motor   13  Fan Limit Limit2   14  Electrical board   15  Air baffles   16  Frame made of aluminium sections  17  External insulated panels  18  Motor s belt tightening slide  19  Pulleys and drive belts    20  Booth protecting burner and electric components                                                                                        Rev4  del 17 09 2013       Pagina 11          WEIGHTS and DIMENSIONS  AS COND EX  SERIES    Weight on  kg  and dimensions on               Head Heater      connection    O  Zo  CY        SA                     Connection     of the air  EE recovery   2 duct    Z  Se       i     EL   4       e             SRR       G SHAN  y    Pe    EIZO  005     SA  RAR  CAAA     4  RE   lt  NL  H    OO  A            S  Y                          M    The air inlet grille is on the left till Mod  200   On the right till Mod 250 onward    The grille position can be reversed     n       Air delivery AVES     Bumercabn            Heater weight    PEERS AE ane connection connection exhaust   met   packed    nce Marina              rai HE       wo   s     us   sso   596   sso eo  e30  4o          wo       22  so 200   750   1950          670   sso   650  sso         1220   no        307    aoo   xm   750   isso   ss       o         ss0    n   me   mo xe                je         2340   im sw   162   roo  1360  sso   isso   iso   vs   e     ame          1020   2340   1070   ow   182   200    eso   isso   iso   seo  
36. ctrical connections of the thermostat are performed in order to keep the fan  always on  see scheme below       gt  LIMIT2  STB   Security limit thermostat for the burner  normally closed with manual reset  to  automatic stop the burner in case the average air outlet temperature overheat above the pre   set value  The set point at 100  C  is fixed by the manufacturer  This set point must not be  changed  The LIMIT2  when intervening   stops the burner  while the fan keeps turning to cool  the heat exchanger   To reset the burner  first wait the air outlet temperature drops down  than push the reset    green button      Resetting the STB D  verrouillage de STB  1  Hutmutter   1   2  Wiedereinschaltknopf   2   9  Hutmutter   1     E abschrauben  En dr  cken  bis der Mikro  um  aufschrauban   PRA F               S  WTHc 2240   1 Unscrew     L Press reset knob  2      1  Screw cap nut  cap nut  1     until the microswitch is i  1  back on         2 resat  Pp  i  Devisser Appuyer sur le bouton de r  ar  e  Visser l   crou  l   crou borgne   i 1 mement  2  jusqu    ce que la borgne  1     1          micronupteur soit d  verrouill           gt  LIMIT  TW   Temperature limit thermostat for the burner  normally closed   to automatic stop  the burner when the average air outlet temperature exceeds the pre set value  The set point   fixed by the manufacturer inside the casing  is at 70  C  and can be increased maximum at  80  C  The LIMIT reset is automatic  when air outlet temperature 
37. drops of about 14 C  below       his set point    1  Setpoint spindle Bl Remove housing cover  1  Potentiom  tre    Retirer le couvercle du    2  Setpoint marker and adjust setpoint spin   2  Rep  re de boitier et r  gler le poten     3  Internal scale dle using a screwdriver  consigne tiom  tre    l aide du tour      Put housing cover back iE his ini evis   on and tighten up the   3  Echelle interne    Replacer et visser le cou   screws  vercle du boitier     CAUTION  Make sure that the manual reset LIMIT2 is not activated due to       Low air flow rate  caused by obstructions and obstacles in the air exhaust distribution    system  e Clogged air filters  if installed   e Heater stopped using the master switch or owing to a power failure during operation    Rev4  del 17 09 2013 Pagina 25    e Operation of the fire damper    e Tri thermostat bulbs too inclined downwards or too close to the heat exchanger  that    speed up its operation     Once all these problems have been solved  if the fault persists contact the after sales service or    qualified personnel  CAUTION  Check  before the first start up  that the tri thermostat bulbs are  inclined upwards and do not touch the heat exchanger     TRITERMOSTATO TRITHERMOSTAT JUMO  1       Serie C    Bianco  White FAN  TR   Marrone  Brown  Rosso  Red    LIMIT  TW   Arancio Orange    LIMIT2  STB     TRITERMOSTATO TRITHERMOSTAT JUMO  3Ph     Serie G     GP XP Tenso    Grigio  Grey FAN  TR   Bianco  White   Rosso  Red  Rosso  Red LIMI
38. ds  The diameter of the pipe connecting the heater to the stack must be equal to or  larger than the flue  all joints must be sealed  When dimensioning the ducts stack system  please remember that  the maximum pressure drop must not exceed 50 Pa     FLUE COMBUSTION AIR INTAKE   The warm air heaters of the X series are fit for the following flue combustion air intake systems  B23 and of tight  type  C13  C33  C53  C63    Please consult national and local regulations and standards  to make sure that the desired system can be  installed    Comply with the installation diagrams provided throughout this manual  The sum of maximum pressure drops  between the flue and the combustion air intake   if installed   including terminals  must not exceed 50 Pa    For more information about duct joints  please contact A2B Accorroni directly or your supplier    The table on the next page shows the pressure drops in the pipes  flue combustion air intake for a variety of  models and diameters  supplied by A2B Accorroni  These pipes and elements are made of smooth stainless steel   A2B Accorroni warrants the heater performance if its own pipes and elements are mounted  as specified in the  table FLUE AND COMBUSTION AIR INTAKE ELEMENTS   The installer can use pipes and elements  manufactured by other companies  providing that pressure drops do not exceed the ones shown in the table  PRESSURE DROPS IN PIPES AND ELEMENTS        Rev4  del 17 09 2013 Pagina 18      4   Ns         IN A 4   1007040000 
39. e emissions  The relevant values  in  db A   are listed in the table on table DATA SHEET     Signals  The signals on controls and alarm devices consist of symbols based on ISO7000  These  symbols are explained on Chapter MEANING OF THE SYMBOLS     WARM AIR HEATER DATA PLATE    A data plate  made with an ultra destructible film  which  once removed  cannot be used again  is  affixed on the front of each warm air heater  and shows its technical characteristics   A facsimile of this plate is shown here below     GENERATORE D ARIA CALDA A CONVEZIONE FORZATA CON BRUCIATORE A  GAS PREMISCELATO BASSO NOX CL 5    FORCED CONVECTION WARM AIR HEATER WITH GAS PREMIX BURNER LOW  NOX CL 5    GENERATEUR D AIR CHAUD A CONVECTION FORCEE AVEC BRULEUR GAZ  PREMIX LOW NOX CL 5    MOD  N   101001 MESE ANNO  TYP   9121235 2   MONTH YEAR E  AS COND 65 MOIS ANNEE 02 2010    PORTATA TERMICA NOMINALE   NOMINAL HEAT INPUT   DEBIT CALORIFIQUE NOMINAL 76 kW  POTENZA TERMICA NOMINALE   PUISSANCE CALORIFIQUE UTILE   THERMAL RATED POWER 73 kW  RESA TERMICA ALLA Pn 96 1                                     AIR DELIVERY   DEBIT AIR 6 100 mc h  PRESSIONE STATICA UTILE   AVAILABLE AIR PRESSURE p   PRESSION AIR DISPONIBLE a    POTENZA ELETTRICA ASSORBITA    RATED POWER INPUT n   1   0 736 kW  PUISSANCE ELECTRIQUE ABSOR     TENSIONE   TENSION 230 1F 50HZ    PAESE DESTINAZIONE IT CATEGORIA TI  COUNTRY OF DESTINATION CATEGORY 2H3B P  PAYS DE DESTINATION CATEGORIE    MADEINITALY        0694BU1913 C     0694    GRADO 
40. erature  The modulation starts at 42  C of air outlet temperature   or by NTC sensor on air recirculation temperature   example SET POINT 20  C of air recirculation temperature  modulation starts at 18       In this case there is a need of a room  thermostat to switch ON OFF the burner  This solution is applied also with roof top operated by PCB controller    2  Operates as room thermostate  switch off the burner when detects room temperature of Set Point T  11  set on the     CLIMA     The burner start on again when room temperature is    0 5 C  configured by the manufacturer with parameter dlF   of Set Point T  11   The burner start on at a modulate thermal power  set by the manufacturer with parameter dSA   Example   CLIMA  room temperature Set Point 20       CLIMA  switch off the burner when detects 20      when detects  19 5     in the room  CLIMA  starts on again the burner  This function is not operating with roof top  because  operated by PCB controller    3  Setting the clock  the time bands  and the default value of the timer for the burner RX and so for the warm air heater  in   heating   For this setting press PRG and  by pressing in sequence SET        SET set the following parameters  rtC   real  time  dAy  starting time of day mode  nlt  starting time of night mode  SLP eventually  time interval between dAy day  running mode  and nlt night running mode  With the clock incorporate is possible set the time bands modes  2 bands per  day  the same for all the 7 day
41. ess the PRG button    After time bands are set  simbol CLOCK will appear on display     The  CLIMA  regulator is ready  To start operate press ON     For more information on the regulator  CLIMA   consult the general Clima CAREL manual on web site  www carel com and go on the  type ADCA000110    Rev4  del 17 09 2013 Pagina 38    6 1 Description of the parameters for the  standard version    The parameters avallable depend on the clima model used and the level    set        1 or 2     code       BI  6    Parameter range   default            mote  day temperature set point In cooling          night temperature set point in cooling   day temperature set point in heating   night temperature set point in heating  single day temperature set point for automatik modes  single night temperature set point for automatic modes    Temperature differential for relay 1  This Is an            in or subtracted from the set point depending on the contral  or heatin    Tempera UE difesential   relay 2   This Is an absolute value and ts added in or subtracted from the set paint depending on the control        differential   This value ls added to or subtracted from the set point according to the control mode selected  cooling or  heating   Analogue output offset Forn to the set point   This value 15 added to or subtracted from to the set point according to the operating mode  cooling       heating   Maximum water temperature        ONAOEF radiant floor ap   imode 8  all dipswitches off   The  SC
42. fore shall be maintained carefully and  must always follow the appliance in the event of a change in ownership   CAUTION  This warm air heater must not be used in explosive atmosphere   The plant project  installation  start up  periodical inspections and repairs of this warm air heater must  be carried out only by skilled personnel   In particular  all obligations provided for by European  national  regional and local laws  regulations   standards and recommendations applicable to design and installation  authorisations  periodical  inspections  maintenance  combustion controls and emissions into the atmosphere shall be understood  and complied with by the user and the said skilled personnel   In case of troubles and faulty operation of the appliance  the user must disconnect power supply and  avoid any attempt of repair  so as not to damage the appliance and or third parties  See the  description in the  Troubleshooting  paragraph of this manual   CAUTION  Before maintenance or servicing  cut off power supply to the appliance  by  selecting turning the master switch to   O    At the end of the heating season  the user must contact skilled personnel to have the combustion  chamber and the heat exchanger cleaned  and  based on the intervals provided for by law  to check  the performance of the other components and safety devices  by conducting a combustion test  The  results of these operations shall be registered on the  heating plant handbook    The air inlet filter  if any
43. g type  is controlled  during flame modulation phases  by the ambient  terminal device type  Clima   supplied with the heater  with an air sensor NTC in it  The  Clima  is to  be installed in the room to be heated  To set the ambient temperature for the modulation read    here down   OUTSIDE TEMPERATURE S PROBE           Press to  increaseW       Option on request                        Rev4  del 17 09 2013 Pagina 6    The  Clima    device operates on the burner as modulation control  room thermostat  clock  thermostat    For example  when we set 20      the modulating starts on at 18     and the burner will be turned off  just when it will reach 20      The burner will start anew at 19 5  C  The regulator CLIMA is powered  with 24V  so the electric board contains the transformer of 230V 24V  The regulator send a signal of 0   10V for flame modulation  The communication cable 0 10V between Clima and burner could have the  max distance of 10 m with section 0 5 mm   or just max 30 mt with concealed cable with section 1 5  mm     COMPOSITION OF THE  AS COND    SERIES HEATER  Models from    50     to  65   with single phase motor  directly coupled to the fan    1  Air outlet   2  Fume box door   3  Burner   4  Burner anchor plate   5  Centrifugal fan   6  Air inlet grille   7  Condensate drain   8  Stack connection   9  Rear fume box   9 1  Front fume box   10  Heat exchanger   11  Combustion chamber   12  Fan motor   13  Fan Limit Limit2   14  Electrical board   15  Air baffles 
44. he heater    NOTE  the CO value should range between 0 and 20 ppm    GAS PIPE   The gas pipe must be manufactured to reference UNI CIG or Country standards  Pipe diameters must be  calculated according to the heater capacity and distance from the meter  and sized so that the total pressure  drop between the meter and any heater does not exceed 1 mbar  methane  and 2 mbar  LPG   The reference  UNI CIG standards illustrate the diameter tables  based on capacity and length    Install a valve and a gas filter near the heater  For methane  make sure that the meter can deliver the gas  volume required  For propane  install a two stage pressure reducing system  install a first stage reducer close to  the tank  calibrated at 1 5 bar  and a second stage reducer before the internal piping     GAS SHUT OFF AND ALARM DEVICE    The warm air heater must be provided with a gas shut off and alarm device to detect any gas leak  in compliance  with national local laws and regulations in force     ELECTRICAL CONNECTIONS    see wiring diagrams on chapter ELECTRIC DIAGRAM    Electrical connections must comply with national and local regulations and standards  IEE standards included    This heater is delivered complete with all electrical connections  except for connection to power supply and  remote control or room thermostat  to be carried out by the installer  based on the wiring diagram on Chapter  ELECTRIC DIAGRAM of this manual    Do not de energize the heater using the master switch        
45. ion sheet     GENERAL WARNINGS  Avoid installing the boards in environments with the following characteristics   e Strong vibrations or knocks   e Exposure to jets of water       Strong magnetic and or radio frequency interference  for example  near transmitting antennae        Exposure to direct sunlight and to the elements in general   e To clean the display use a soft cloth  Do not use water or solvents   e Operation at particularly low temperatures may cause an evident decrease in the response speed of the display  This should be  considered  normal and does not indicate a malfunction   e A power supply voltage other than that specified may seriously damage the instrument   e Separate as much as possible the control cables from the cables to the inductive loads and power cables to avoid possible  electromagnetic  disturbance  Never insert power cables  including the electrical cables  and probe and serial communication cables 0 10V in the  same conduits   Do not install the communication cables in the immediate vicinity of power devices  contactors  circuit breakers or similar    The cables that come out of the controller must not be in view  but rather run inside the conduit   e If the appliance is used in a manner not specified by the manufacturer  the rated protection of the appliance may be compromised    FUNDAMENTAL OPERATIONS OF THE INSTRUMENT  Below is the meaning of the buttons in normal operating conditions     BUTTON MEANING       Power Switch the  CLIMA  instru
46. l cables from the relay cables    Place a clamp around the two groups of cables  signal and power supply  relay outputs  near the terminals   e Check inside the  CLIMA  the dipswitches must be in the following position  see the table below       Name Switch Switch Switch Switch Model Product code    Basic temperature control with one ADCA000110  relay only     Analogue output associated with  temperature        e Reconnect  if previously disconnected  the flat connection cable between the rear and the front panel  ensuring the polarity is correct     Rev4  del 17 09 2013 Pagina 34    e Close the instrument with the opposite movement  making sure the flat connection cable does not hinder the operation   e To ensure electrical safety  EN60730 1   insert the plastic tab and tighten the screw to stop the instrument from opening  see Fig  2      SERIAL CONNECTION OPTION   To connect the instrument to the supervisor serial line  the accessory code IROPZ48500 is required  For correct operation  turn the  instrument off and connect the option to J1  as shown in Fig  6  For details on the RS485 serial line  see the instruction sheet enclosed  with the accessory     PARAMETER PROGRAMMING OPTION   The optional programming key code PSOPZKEYOO or PSOPZKEYAO can be used to program the parameters on the instrument        connect the key  turn the instrument off and connect the key to J1  as shown in Fig  6  For further information on the operation of the  key  see the corresponding instruct
47. lean air filters  if installed  if they are clogged   Once every 80 hours    At least once at the beginning of each   Clean and inspect the heat exchanger   heating season    Clean and inspect the combustion chamber    Clean and inspect the ventilating unit     Check the performance of electrical and safety  components    Combustion analysis    At least once at the beginning of each  heating season       Rev4  del 17 09 2013 Pagina 31       Rev4  del 17 09 2013 Pagina 32    TROUBLESHOTING    Use the table below to identify any possible problems  If a problem cannot be solved as suggested in the table  contact the authorised after sales       service or qualified personnel     FAILURE CAUSE  REMEDY    1  The master switch is on     and the change  1  The electrical board is not energised  1  Check that the master switch upstream of the electrical  over switch in the VENTILATION position  the board is on    signal lamp is off and the ventilating unit     2  Replace the fuse with another piece  with the same  stopped                                characteristics     2  Like n   1   but the REMOTE CONTROL 1  E intervenuta la termica del teleruttore e ha tolto tensione al         deck turn off the master d ree open ae  SWITCH THERM  lamp is on motore  electrical board cover and press the push button of the  only for 3 phase voltage heaters remote control switch s thermal relays     1  Contact the after sales service  to have the component  repaired or replaced     2  Contact the 
48. ler Independently sets a humidity set point In relation to  the outside temperature        Rev4  del 17 09 2013    Pagina 39                  ele                 Parameter for set point compensation   Parameter CSt enables and sets the gain for set point compensation according to the outside  temperature    IFCst                               disabled    Also see parameters Cit and Cis    Max differential for the compensated set point   The maximum value for the compensated set point ls limited by this parameter  In heating mode  If the  difference calculated for set point compensation Is higher than CdF  the instrument uses        as the  maximum difference from the set point    Similarly  in cooling mode If the difference calculated for set point compensation 5 less than CdF  the  Instrument uses Cde as the maximum difference fom the set point    Threshold for set point compensation in heating mode    Temperature set point compensation In heating based on the autsde temperature measurement           Ep  Tent     Cit    Cst    r1        a    Thresh old for set point compen zem n xum mode     Temperature set point compensation In cooling based on the outside temperature measurement   compensated set polnt   setpoint    Text   set point   CtS    CSt   Compensation E activated only If  Text  gt  set p   Configuration TZA e TZA H   Additional modes for the automatic operation    For temperature control only  TZALE   Configuration 1  temperature contro  with set point and dead ba
49. ment On Off  The button may be disabled  if the On Off function is associated with the digital  input   When the instrument is switched off  all controls are disabled  except for the antifreeze function        C F Selects the temperature display mode  between degrees Celsius and Fahrenheit  When pressed switches between the two  temperature units        SET Used to display and when necessary set  using the buttons cv   the set point displayed in the SMALL field  If pressed for more  than 5 seconds  accesses the parameters menu    To scroll the various parameters  use4 v   When on a parameter  to modifie press SET  than modifie with 4 v and confirm  by pressing the SET button again  and to exit the parameters menu  press the PRG button        J Activates the opposite operating mode to the current mode  sleep when in day mode or day when in sleep mode   for the  time displayed    To change or reset the timer  use to increase or decrease the time  Press again to exit and return to the main menu  If the  mode is already active pressing the button will show the time remaining until the timer expires              prg Accesses the menu for setting the clock  the time bands  and the default value of the timer   When first pressing the button       the current time is displayed  rtc   to display the other parameters  use the 4 v  To set a new parameter s value press SET  when the required parameter is displayed and change the value using with 4 v  Press again PRG to exit and return to
50. mum voltage of 24 Vac  class II  can be  connected   e UL instructions for the connections     Use 75  copper  CU  conductor and wire size No  22 14 AWG  stranded or solid    Rev4  del 17 09 2013 Pagina 36      Use Terminal tightening torque of 4 Lb In when green  PTR  terminal block is used or 7 Lb In when black  SAURO  terminal series  is used   WARNING  All connections  except for the relays  must be connected to low voltage circuits with reinforced insulation     IMPORTANT WARNINGS  The CAREL product is a state of the art product  whose operation is specified in the technical documentation supplied with the product  or can be downloaded  even prior to purchase  from the website www carel com   The client  builder  developer or installer of the final equipment  assumes every responsibility and risk relating to the phase of  configuration the product in order to reach the expected results in relation to the specific final installation and or equipment   The lack of such phase of study  which is requested indicated in the user manual  can cause the final product to malfunction of which  CAREL can not be held responsible     The final client must use the product only in the manner described in the documentation related to the product itself  The liability of  CAREL in relation to its own product is regulated by CAREL s general contract conditions edited on the website www carel com and or  by specific agreements with clients     READ AND SAVE  THESE INSTRUCTIONS       Fig  1 
51. n of rotation of the fan s  is the one indicated by the arrow on the  impeller  see fig  7    Check motor absorption by means of ammeter and make sure it does not exceed the values  specified on Chapter DATA SHEET    Check the performance of heater thermostats  FAN  LIMIT and LIMIT2  see Chapter TRI   THERMOSTAT    Perform a combustion analysis   Prepare a power station or plant handbook and record the information required to be disclosed  pursuant to the laws  rules  regulations and standards in force                                   Fig 6 Electrical board for 1Ph and 3Ph     Fig 7 Direction of rotation of the fan s     Rev4  del 17 09 2013 Pagina 24    TRI THERMOSTAT    Three thermostats composed of a FAN  LIMIT2 and LIMIT    FAN  TR   fan thermostat  normally open  to automatic start and stop the fan when the average air  outlet temperature reaches a pre set value  The set point is fixed by moving the setpoint marker  2  in  an internal scale  3   placed inside the TR casing  This adjustment must be set to 30  C    Setting this value over  a delay on fan starting may be caused  so increasing fuel consumption and impairing the  long life of the heater  On the cooling phase  the thermostat stops the fan at about 14  C  lower his starting point     o For all installations  EXCEPT for installations such as PRESSOSTATIC structure   the fan is operated as described in paragraph FAN  TR      o For application in PRESSOSTATIC STRUCTURE the FAN must operate  continuously   The ele
52. n the heater upside down    INSPECTIONS BEFORE START UP    The heater is equipped with an electrical board  which comprises    A master switch   A HEATING     BURNER STOP     VENTILATION switch   A terminal board   Thee signal lamps on the board s door indicate    1  VOLTAGE  the board is powered   2  THERMAL RELAYS ON  the remote switch s thermal relays have de energized the fan  From  mod   X80  to mod   X300  only    3  LIMIT2 ENABLED   the safety Limit has de energized the burner    Check that       the electrical board is properly connected to the single phase power line  for models  50  and     65     three phase from mod   80  to mod     300     and that the main power cable has a suitable  section for Ampere absorption    gt  the rotation direction of the fan s  is the one shown on the impeller  figure 13       the calibration of the remote switch s thermal relays is correct  from mod   80  to mod      300      the relevant values  In Amperes  are shown on Chapter DATA SHEET       there are no obstacles on the delivery and on the recovery nozzle  which could obstruct air  circulation    gt  the fins of the air delivery nozzles  if any         not too inclined  so as not to reduce their capacity    gt  the air inlet filters are clean  not to reduce the air capacity     v v v v    Rev4  del 17 09 2013 Pagina 5    OTHER INSPECTIONS IN THE HEATING PHASE   Check that    1  The fuel supply pipe to the burner is compliant with the Standards in force  Ask the piping installer
53. nd oniy  22051     Configuration   temperature control only with automatic changeover of the set point   Configuration 3  temperature contro  only with cooling and heating set point  automatic changeover  and manual ON OFF control for outlet fan           rn an   humidity control  T2A Hk   f 1  temperature control with set point and dead band oniy  2511  Two set points for  hurmidity   m z  temperature and humidity contral with cooling and heating set point and automatic    Active display configuration  Used to set the values shown In the lange and small fields on the depla     The large held displays the hours and the small held the minutes  15 minute steps     Digital Input configuration   OFF  disabled   1 select remote cooling heating  i remote                3 select cay night set alternativo   4 remote alarm   Digital contact polarity    Used to choose whether to consider the digital Input active when closed or open or alternatively whether  or nat there           In the opticalhytsolated version   vo        active du the Input ls closed  PO  active when the Input Is open  sol ated         active when     ls pee al              Control a operating     Enables the possibility to define the operating mode  coding heating  by parameter rather than by DIP 2   dis  Parameter El 5 disabled  Eu p mode E selected           4      the rear     Select cooling heating   wiran      mode enabled by the previous parameter     Selects the mode  coding or heating   E  The Instrument wo
54. put off the burner is signalled by lamp S3           burner peration counter output stage     To reset it push the resetting button of  the limite       RB   Control burner relay      1   Remote control switch for fan motor MV1          Remote control switch thermal cutout   1                 INSTALLER CONNECTION  Te   Remote control switch for fan motor MV2  RT    Remote control switch thermal cutout Te    R1   Timer Fan start    Timer Fon Off       KIND DF MODIFICATION    Rev4  del 17 09 2013 Pagina 29    MAINTENANCE    The warm air heater and the burner must be serviced by an authorised service centre or by  qualified personnel  in compliance with the requirements set forth by law  For proper and  safe warm air heater operation  and for its long life  the operations listed below should be carried out  at regular intervals                     Before doing maintenance      servicing the appliance  disconnect it from mains supply  and close fuel supply     CLEANING THE HEAT EXCHANGER   the heat exchanger must be cleaned from soot and deposits  to preserve heat exchange capacity   Clean it at the end of each heating season or more often  Start up defects could be due to the  presence of soot inside the heat exchanger  obstructing the exhaust gas line  The accumulation of  excess soot could depend on a variety of reasons  such as faulty draught  poor quality fuel  lack of air  in the burner  To clean the heat exchanger  proceed as follows              FLUES  10    Remove the re
55. rive motor    1  Air outlet   2  Fume box door   3  Burner   4  Burner anchor plate   5  Centrifugal fan   6  Air inlet grille   7  Condensate drain   8  Stack connection   9  Rear fume box   9 1  Front fume box   10  Heat exchanger   11  Combustion chamber   12  Fan motor   13  Fan Limit Limit2   14  Electrical board   15  Air baffles   16  Frame made of aluminium sections  17  External insulated panels     20  Booth protecting burner and electric    components                                                             Models from  80  to  200   three phase  with fan s drive motor    1  Air outlet   2  Fume box door   3  Burner   4  Burner anchor plate   5  Centrifugal fan   6  Air inlet grille   7  Condensate drain   8  Stack connection   9  Rear fume box   9 1  Front fume box   10  Heat exchanger   11  Combustion chamber   12  Fan motor   13  Fan Limit Limit2   14  Electrical board   15  Air baffles   16  Frame made of aluminium sections  17  External insulated panels   18  Motor s belt tightening slide  19  Pulleys and drive belts    20  Booth protecting burner and electric    components                                                                               Rev4  del 17 09 2013 Pagina 10    Models from  250  to  300   three phase  with fan s drive motor    1  Air outlet   2  Fume box door   3  Burner   4  Burner anchor plate   5  Centrifugal fan   6  Air inlet grille   7  Condensate drain   8  Stack connection   9  Rear fume box   9 1  Front fume box   10  Heat ex
56. rks In cooling mode  I  The Instrument works In heating mode       Rev4  del 17 09 2013 Pagina 40       Enabling this parameter allows the outputs to be controlled directly via the serial connection  Warning  if  enabled      contral  amp  performed independently by the Instrument    If active and the supervisor does not query the Instrument for more than two minutes  the outputs are  automatically disabled and the no link error        Is signalled on the display    no  the function Is disabled  yES  the function ls enabled    inside temperature callbration  digital sensor      NTC    Within    medmum of   10T  10to 10    Cutside temperature calibration  NTC sensor    Within a medmum of   10       10 10    Digital humidity sensor calibration   Within a maximum of 4 15  rH    Parameter access level    Level of access the control parameters for the active mode    Level 1  basic access  only the essential parameters for correct operation    Level 2  advanced access  used to set all the parameters for the selected control mode   Lock    The lock parameter used to disable some functions af the Instrument  as per the following settings            OFF  LOC   1  The UP DOCWNM and time bands buttons are disabled  LOC   2  Only the time bands button Is disabled  In these cases  the LOOK symbol    shown on the display whenever attempting to perform an  unauthorised operation   Temperature display mode  Sets the temperature display mode  in degrees Fahrenheit ar Centigrade  Unlike direct
57. s of the week  In case of electric feeding s lack  rtC real time remains in memory for 2 days  maximum    The supervisor remote control option  purchasing the accessory code IROPZ48500  allows the data from the instrument to be  monitored and saved   The function  of Set Point compensation based on the outdoor temperature probe reading NTC is available  For this  CLIMA  must be  connect to the NTC outdoor temperature probe reading  option on demand      Installation   CLIMA  regulator is delivered  together with the warm air heater and burner with parameters dFA   dSA  dlF already configured by  the manufacturer  see par  1 and 2   The installer must set the rtC real time parameter  and dAy  starting time of day mode  nlt   starting time of night mode  SLP eventually  time interval between dAy day running mode  and nlt night running mode   Disconnect the power supply to the controller and the loads before working on the instrument   For correct installation  proceed as follows   e separate the front panel from the rear part by levering the tab  as shown in Figure 2   e Fasten the instrument to the wall horizontally  so as to allow the circulation of air  For accurate measurements  position the  instrument away from sources of heat or humidity  away from windows or outside walls   e Pass the connection cables though the centre hole in the bottom shell and connect them to the terminal block provided  observing the  markings shown on the label  Separate the connection and contro
58. seconds  for enter the parameter s menu   To scroll the various parameters  use v   When on a parameter  to modifie press SET  than modifie with 4 v and confirm by pressing  the SET button again  For the current parameter on display is possibile change it directly with 4 v   To exit the parameters menu  press  the PRG button   Ambient temperature factory Set Point are     Set winter day   default 20 0  C  and night   default 18      minimum setting temperature 10        prg  CLOCK  TIME BANDS    Press button PRG  parameter rtC is show  to scroll the various parameters  use   v  When on a  parameter  to modifie press SET  than modifie with 4 v and confirm by pressing the SET button again  To exit the parameters menu   press the PRG button   Parameters to verifie reset are     tC  dochh min __      To disable the time bands function  set parameter rtC OFF  as follows  press the PRG button  select parameter rtC  and change his  value into 00 00  than press once more with   v to select OFF and press SET to confirm   By parameter rtC OFF the function mode is allways day  and only day Set Points are operating  the night Set Points will be operating        af    only by pressing button 2     Change of status manual        SLP manual changeover duration between dAy day band and nlt night band  To change this duration  press PRG and scroll   v to  display SLP  Press SET and with   y modifie SLP value  or eliminate it  down to OFF  Press SET to confirm  To exit the parameters  menu  pr
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Eaton ePDU Managed 0U 16x C13  Manuel utilisateur  Garmin Software Version 0534.21 Cockpit Reference Guide  Use and maintenance instructions EN Instrucciones de uso y  Philips SatinPerfect Epilator HP6579/00  Guide environnemental Ecofac  Baumatic BR200.3A refrigerator  FMI SVYD18NRA User's Manual  電動パンチ VS-55型 (PDF:465KB)  Baumatic BF18SS hob    Copyright © All rights reserved. 
   Failed to retrieve file