1. 9 7 Installation precautions The following precautions are necessary when installing beam detectors In a room where an air inlet is positioned in the ceiling the beam detector should be placed near to the air inlet Select an appropriate installation place where the detector is unaffected by air being drawn into a ventilated opening gt The distance between the receiver and the wall immediately behind the receiver should be less than 7 5m 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 34 If more than one detector is installed they must be positioned in such a manner that they cannot affect each other s operation The detector should be positioned such that a shutter or hanging wall will not affect it The detector should be positioned such that it will be unaffected by moving objects The detector should not be installed in a rooftop or place where open air circulates The detector should be installed where the distance between top and bottom of the space is greater than 0 5m The monitoring distance between the emitter and receiver is 5m to 100m and the maximum distance of coverage between the line of the beam is 7 5m Therefore the maximum area of coverage is 1500m If there is a probability of people walking in the area of the beam then the beam detector should be installed at least 2 7m from the floor The beam detector should not be installed at a height greater than 25m unless
2. gt The control panel is incompatible with the interface PCB 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 29 gt The interface PCB is defective 8 8 Detector in fault panel not registering condition gt The control panel is incompatible with the interface PCB The interface PCB is defective gt The interface fault monitoring jumpers have been incorrectly set Verify the fault monitoring function of the control panel 9 Installation guide lines The Hochiki SPB ET beam detector must be installed according to the requirements laid out in national or local standards The following guidelines for installation are provided to give information in certain installation conditions where no advice or regulations are provided by the relevant standard 9 1 General installation conditions Figure 12 relates to the typical installation condition i e in a long straight area and details the siting positions of the beam detector Ceiling H ceiling height h mounting height I1 2side wall distance 12 back wall distance P distance between optical axes L distance between Emitter Receiver If H 15m then use beam detectors at locations 1 and 2 If H gt 15m then beam detectors should be mounted at locations 1 2 3 4 and 5 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 30 For Detectors at 1 and 2 For detectors at 3 4 and 5 h 0 8H h H 2 I1 lt 7m l1
3. anual 24 5 7 Receiver installation termination PCB When the SPB ET beam detector is used with the installation termination PCB supplied with the termination module certain other functions are provided This PCB has been designed to make the connection to a conventional or analogue addressable control panel through a suitable zone monitor unit much easier The following facilities are provided by the interface PCB gt Easy connection to emitter and receiver gt Compatibility with UK electrical installation boxes for termination of fire cables Removable connection plug for easy connection of fire cables Reset of beam detector power when fire detection zone is reset gt Three options of fault for compatibility with different fire panels Full monitoring of wiring to the beam detector gt Remote Fire LED connection 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 25 6 Specification Installation Environment Indoor use only Principle of Operation Light beam obscuration near infra red Rated voltage 24V Operating voltage range 15 0 33V dc Peak surge voltage 42V Current in alarm 50mA Non alarm current SPB ET only 250uA Non alarm current Interface module with SPB ET From detection zone Initial data hold time Typically 30 seconds Compensation method 0 5 per hour towards initial value Compensat
4. behind the Beam Detector body 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 13 Fire Alarm Z Z Z Z Pan EOL Pan EOL Control Panel El E2 Beam Detector Beam Detector Receiver Emitter Figure 5 Termination module wiring diagram Note Beam detectors should be installed to comply with local installation requirements governing the maximum area of coverage for a zone Now set up the beam as described in sections 2 7 and 2 6 Section 2 4 2 should be skipped as it is inappropriate to this installation version 2 4 2 Installation option 2 detector only For some applications the installation kit may not be required in this situation the beam detector can be installed on its own if this is the case the detector should be wired as in figure 6 However if this method is used no head removal facilities will be available It is necessary to wire the emitter from the receiver with 2 wires since the emitter does not work as a separate unit from the receiver 2 4 2 1 Emitter Installation procedure Screw the detector mounting plate firmly to the wall or other suitable mounting point Open the detector cover as described in section 2 3 and then take the wires into the back of the detector through the hole so that they come out below the terminal connector The wires can be installed either behind the detector or from below the detector depending on the suitability of the installation If the wi
5. long lasting test filters for testing all models of Hochiki beam detector and have been manufactured from wire mesh They also come with an attachment so that they can be mounted to the Hochiki detector removal pole thus enabling testing of the filter from ground level First determine the sensitivity that the beam detector should be set to and then select the correct filter values from Table 1 Using the lowest filter value prove that the detector is not too sensitive by placing the filter between the emitter and receiver for at least one minute It is not set to the correct sensitivity if the detector goes into fire alarm or fault during this process Next place the higher value filter between the emitter and receiver for at least one minute During this period a fire alarm should occur If no alarm occurs or a fault occurs then the detector is not operating as expected Sensitivity setting Type of test Filter Value Filter Number 25 Operation 40 Non operation 15 0 4 0 2 N N Non operation 30 No 3 Non operation 40 No 4 Table 1 TSK B100 test filter values 2 8 2 Using the TBF E These filters have been designed as disposable test filters for testing the Hochiki SPB ET beam detector and have been manufactured from plastic They are either supplied as a separate item or are included in the option with termination module They are intended to be used once and then thrown away as due to their construct
6. lt 5m 12 lt 1m P lt 14m P lt 5m L 25m to 100m L 25m to 100m Figure 12 General installation conditions 9 2 Installation in Saw tooth type ceilings In installations where there is a saw tooth shape to the ceiling the detectors should be mounted with the axis either in condition A or condition B according to Figure 13 If the height of the ceiling a is greater than 0 2 H do not install with the axis according to line B Figure 13 Installation in saw tooth shaped roofs 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 31 9 3 Installation in circular type ceilings The installation in a cylindrical or circular roofed building should be in accordance with In the case of the cylindrical roof position A or B for the detector s axis is acceptable B o Pam ut Fd dus B oA A gt H H v Cylindrical roof Spherical roof Figure 14 Installation in circular shaped ceilings 9 4 Installation in sloped ceilings The installation for a sloped type roof or ceiling will be as shown in Figure 15 Either position A or B is acceptable for installation of the SPB ET A A Figure 15 Installation under a sloped ceiling 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 32 9 5 Installation in a monitor roof The installation for a monitor roof should be pe
7. maintain proper performance the detector should be checked every six months 3 2 Visual check Check the condition of both the emitter and receiver for physical damage or any other condition that might impair proper operation Ensure that both the receiver and emitter are still firmly secured to the wall or other fixing point If necessary clean the lens cover with a damp soft cloth Washing liquid or detergent must not be used 3 3 Operation checks Perform the sensitivity check function as defined in section 2 8 3 4 Precautions for insulation resistance checking If the wiring to a beam detector is to be tested for insulation resistance using a high voltage tester such as a Megger the wiring to the beam detector must be disconnected from the detector otherwise permanent damage of the detector may result If the termination module is used then the disconnection of the orange terminal connector from the PCB will enable testing to be carried out 3 5 Re initialisation after cleaning or re adjustment Because the beam detector contains sophisticated processing algorithms to take account of fluctuations in the beam intensity and alignment if during routine maintenance the beam 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 20 detector lenses have been cleaned or re aligned then it will be necessary to make the detector read and store its initial value This can be done by one of t
8. the fire detection system is connected directly to the fire brigade or via a central station and rapid attendance by the fire brigade is possible In any case the maximum installation height is 40m 9 8 Smoke Patterns The following smoke patterns should be considered when considering beam detector installation 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 35 Height in metres A C A This pattern is produced by hotter burning fires and is very narrow at ground level Therefore it may be easier to detect at a higher level or at the ceiling B This type of smoke produced by a smouldering fire will not rise above 15m and therefore to cover this type of risk it is necessary to install the detector below 15m C This smoke pattern will be detected by detectors installed at any height Figure 20 Typical smoke patterns fe HOCHIKI World Class Leaders in Fire Detection since 1918 HOCHIKI EUROPE UK LTD GROSVENOR ROAD GILLINGHAM BUSINESS PARK GILLINGHAM KENT M E8 0SA ENGLAND TEL 44 0 1634 260133 FAX 44 0 1634 260132 EMAIL PSUPPORTGHOCHIKIEUROPE COM WEB WWW HOCHIKIEUROPE COM Hochiki Europe UK Ltd reserves the right to alter the specification of its products from time to time without notice Although every effort has been made to ensure the accuracy of the information contained within this document it is not warranted or represented by Hochiki Europe UK Ltd to b
9. 096 7096 or no operation The sensitivity setting only affects the determination of the fire signal Basically the higher the percentage setting the less sensitive the beam detector will be since the production of a fire signal requires that the signal seen by the receiver should be reduced by more than the amount of the sensitivity setting For example a sensitivity of 2596 requires a reduction of the signal by 1 4 of its initial value to produce a fire 5 5 Total obscuration of the beam If the beam detector is totally obscured then a fault signal will be produced first followed by a fire signal within a few seconds This has been implemented in this way as the total fault obscuration may not really be a fire condition The fault condition will disappear when the total obscuration condition is removed but the fire alarm will remain until the beam detector is reset 5 6 Automatic compensation for change of signal strength From the time that the beam detector is initialised the signal at the receiver is checked every hour for variation and will be altered by 0 5 back towards the original stored value The beam detector will store the initialisation value when either the cover is closed after the sensitivity has been set sensitivity not in the no operation position or if the beam detector is powered up with the sensitivity set and the receiver s cover closed 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M
10. 1 Hochiki SPB ET Beam Detector User M anual 10 The connection of this unit requires the use of a dual gang installation box either flush mount or surface mount Suggested types are MK897 ALM surface mount M K862 ZIC flush mount but any equivalent type is suitable providing that it has a minimum depth of 25mm This item should be firmly fixed to the wall or other suitable mounting point first With reference to the wiring diagram below ensure that the field wiring is terminated into the dual gang installation box Unplug the 2 way white connector from the Termination PCB Install the wires into the correct socket slot and secure by the terminal screw pe Dual gang electrical box surface or flush mounted pu a Faceplate Beam Detector Nye ene Bracket a 1 iL 7 Ea Ses Field wiring connector connects to termination ton Ribbon Cable 7 Termination PCB PBE e Mounted on rear of faceplate Figure 3 Termination module assembly Ensure the white connector is facing with the screw terminals pointing upwards and that the cables are insulated and neatly located into the base of the installation box Securing Face Plate Ensure that the Beam Detector mounting bracket is located the correct way up see Figure 3 Plug the 2 way white connector into the termination PCB Secure the faceplate with the screws supplied Ribbon Cable Installation to Termination M odul
11. PHOTO ELECTRIC BEAM DETECTOR MODEL SPB ET INSTALLATION PROCEDURE Hochiki SPB ET Beam Detector User M anual 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual Contents Contents 1 1 General Description 1 2 Detection principle 2 Installing the detector 2 1 Siting 2 2 Mounting and removing the detector 2 3 Opening the detector cover 2 4 Installation 2 5 Closing the detector cover 2 6 Adjustment procedure 2 7 Setting the Sensitivity amp Switches for Operation 2 8 Sensitivity check procedure 3 Maintenance 3 1 General 3 2 Visual check 3 3 Operation checks 3 4 Precautions for insulation resistance checking 3 5 Re initialisation after cleaning or re adjustment 4 Terminal layout and part designation 4 1 Emitter 4 2 Receiver 5 Summary of the SPB ET s functions 5 1 Alarm signal output and indicator lamp 5 2 Fault signal output and indicator lamp 5 3 Indication of normal operation 5 4 Sensitivity setting 5 5 Total obscuration of the beam 5 6 Automatic compensation for change of signal strength 5 7 Receiver installation termination PCB 6 Specification 7 Sensitivity selection 8 Troubleshooting 8 1 Monitor LED fails to flash 8 2 Fire signal continues after reset 26 27 27 27 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual Fault signal cannot be reset Detector in fire panel not registering condition Detecto
12. by an amount that exceeds the sensitivity setting of the detector then a fire signal is produced by closing the fire relay contact and lighting the fire LED on the receiver It should be noted that the SPB ET has a sophisticated processing and analysing circuit and therefore a fire will not occur immediately the obscuration exceeds the sensitivity value but will take typically 10 to 15 seconds to produce the fire signal The fire decision is based on an averaging technique and therefore the time to fire alarm will vary depending on the level of obscuration and the sensitivity setting 5 2 Fault signal output and indicator lamp 5 2 1 General The beam detector may produce a fault condition for one of many different reasons which will depend on whether the detector has just been set up or is in normal operation The fault signal will be produced by opening the fault relay contact and illuminating the yellow fault LED on the receiver 5 2 2 After adjustment re initialisation The beam detector will produce a fault after or during adjustment for one of the following reasons gt The cover of the receiver was closed but the sensitivity was left OFF gt The light level is too low reaching the beam gt The light level is too high reaching the beam gt The sensitivity has been set but the cover of the receiver was not closed within 5 minutes gt SW3 and SW4 are in the incorrect positions 5 2 3 During normal ope
13. cover between the thumb and fingers near the top of the cover and squeeze the cover firmly so that the top of the cover expands slightly The cover can then be pulled away from the detector housing This should be done by pulling the cover at an angle of 45 upwards and away from the detector Next hold the detector cover firmly at the bottom and pull away from the detector housing until a click is heard The cover should now be able to drop down and rest on the cover retaining clips thus allowing access inside the detector housing Refer to Figure 2 for more details DETECTOR HOUSING DETECTOR COVER DETECTOR COVER DETECTOR HOUSING Figure 2 opening the detector housing 2 4 Installation The detector is available in two installation options depending on the country and wiring requirements Please check that the beam detector contains the correct components for the option required Option 1 SPB ET including termination module SPB ET2WI refer to section 2 4 1 for installation details 1 Emitter 1 Receiver 1 Installation manual 4 Fixing screws 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 9 1 Emitter mounting plate termination module PCB on the back 1 Receiver mounting plate termination module PCB on the back 1 2 way cable for connection between mounting plate and emitter 1 10 way cable for connection between mounting plate and receive
14. e Connect the socket from the 2 way ribbon cable to the white connector on the Termination PCB ensuring correct friction lock fitting and correct polarity Fit the Beam Detector body onto the hooks of the mounting bracket and slide down to fix ensuring that the ribbon cable is pushed into the space behind the Beam Detector body 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 11 2 4 1 2 Receiver Installation procedure Ribbon cable installation to Beam Detector Open the detector cover as described in section 2 3 Thread the 10 way ribbon cable through the back of the beam detector so that the connector remains at the rear of the beam detector and the flying leads exit the bottom front of the beam detector Install the harness into the beam connector starting with the Black wire to E1 and following in cable order through to FC The wires should be pushed into the holes of the connector whilst the white push key is pressed with a small screwdriver This will enable the wire to push completely home Pull the wire to make sure that it is firmly held by the connector Beam Detector Receiver Connections EP I fe ff y x B L Termination Module Connector Wire Installation The connection of this unit requires the use of a dual gang installation box either flush mount or surface mount Suggested types are M K897 ALM surface mount M K862 ZIC flush mount but any equivalent type is usable providing t
15. e a complete and up to date description Please check our web site for the latest version of this document 2 3 0 294 1ss2 Feb2001
16. eceiver one of the 6 small LED s located between the terminals and the normal monitor LED s will be flashing these LED s are small square LED s located in the main PCB and are located below the main alignment and status LED s The LED flashing will indicate the amount of light reaching the receiver refer to figure 10 Move to the emitter and look through the alignment sight hole Turn either the horizontal or vertical alignment screws until the receiver can be seen in the centre of the sight hole When installing the units in a dimly lit area it may be difficult to see the receiver and emitter In this case alignment can be made by turning the alignment adjustment wheels until the alignment setting LED can be seen in the centre of the sight hole Close the cover of the emitter move to the receiver and repeat the alignment procedure refer to figure 11 Sight Hole Other Detector Figure 8 Detector alignment 2 6 2 Signal strength adjustment First set both adjustment wheels to their minimum setting by rotating so that the front of the wheel as turned all the way to the bottom and then turn the adjustment wheel coarse adjustment until the further most right hand red signal strength LED is flashing These LED s are small square LED s located in the main PCB and are located below the main alignment and status LED s refer to section 4 if in doubt as to the LED location This means that the signa
17. elect a suitable position for the installation of both emitter and receiver such that there are no visible obstructions between them Remember that the beam detector works on the principle of reduction of light between the receiver and emitter If there is any possibility of an object remaining within the beam for a few seconds then the siting of the detector is unsuitable For mounting either the emitter or receiver it is important to establish that the mounting place such as the wall is solid and that the beam detector alignment will be rigid The wall may appear to be solid but may be subject to twisting or other changes when the temperature outside the building varies greatly during one day for instance on cold frosty days The installer must ensure that the beam will not be subject to misalignment due to changes in the building itself The spacing and siting in specific types of locations is covered in section 9 The beam detector must not be installed in the following locations gt Where the ceiling height is greater than 40m gt A roof top or place where open air circulates gt Where the distance between top and bottom of the space is less than 0 5m gt In locations where a large amount of dust fine powder or water vapour is present gt In locations such as kitchens where smoke occurs normally gt In locations which are exposed to extremely high temperatures gt Where access to the detector is impossible for maintenance purpose
18. er upwards so that the cover engages with the top of the detector housing Then hook the top of the cover over the metal hook protruding outward from the top of the detector housing Pull down the top of the cover ensuring that it is flush with the detector housing top Now push the cover at the bottom firmly towards the detector housing until it locks back into place Refer to Figure 7 for more details DETECTOR HOUSING DETECTOR Figure 7 closing the detector cover 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 16 2 6 Adjustment procedure The adjustment procedure is carried out by first using the sight holes and alignment adjustment screws Following this the signal strength is adjusted by using the signal adjustment wheels coarse and fine and the signal strength LED s Refer to section 4 for details of the position of the relevant parts on the detector when making the following adjustments 2 6 1 Alignment adjustment Open the covers of the emitter and receiver as described previously At the receiver confirm that both sensitivity setting switches SW1 and SW2 are set to OFF sensitivity off refer to Figure 9 Power up the receiver this will automatically power up the emitter and then wait two minutes for the beam detector to stabilise At this time the red operating LED will flash in synchronisation with the red alignment setting LED once every second On the r
19. etector body located near to the retaining clip Hook the back of the detector body to the 4 prongs of the mounting plate and slide down firmly ensuring that the cables are not trapped or damaged by the detector The detector body should lock into place by the locking mechanism which is located on the bottom right hand corner of the detector and then secured using the locking screw Refer to the mechanical drawing Figure 1 The wires should be pushed into the holes of the connector whilst the white push key is pressed with a small screwdriver This will enable the wire to push completely home Pull the wire to make sure that it is firmly held by the connector ZONE PAN Ve L1 L IN Ve C1 L IN NOT USED L2 L OUT Ve L C2 L OUT Ve TC COM ZONE EOL RECEIVER NEXT DETECTOR EMITTER FO FIRE LED Ve E FC FIRE LED Ve E2 Figure 6 Wiring diagram for use without the installation kit The connections for the emitter and receiver are detailed below The terminal names are marked above the terminals on the beam detector Refer to section 4 for a drawing of the terminal positions Emitter E1 E2 to E1 E2 of the receiver Receiver E1 E2 to E1 E2 of the emitter L1 We in C1 Ve in C2 Ve out TC Ve out Now set up the beam as described in the following sections 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 15 2 5 Closing the detector cover Move the cov
20. f the detector setting will be stored within 10 seconds With the cover closed confirm that the flash interval of the operation LED is approximately once every 3 seconds If the flash rate is still once every second then the detector cover has not been closed correctly and will not initialise In this case the detector will not move to the supervisory status and will not operate correctly T Note For compliance with BS 5839 Pt 5 as approved by LPCB it is not allowed to use these sensitivity settings If the detector goes into fault after initialisation the following conditions may have occurred gt The cover of the receiver was closed but the sensitivity was left OFF gt The light level is too low reaching the beam gt The sensitivity has been set but the cover of the receiver was not closed SW3 and SW4 are in the incorrect positions 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 18 Run through the alignment and signal strength procedure again until the beam detector will initialise correctly 2 8 Sensitivity check procedure After installing the detector or during periodic maintenance it is important to ascertain that the detector has the correct fire sensitivity This can be achieved by the use of filters Hochiki produce two types of filters for this purpose the first being the TSK B100 the second being the TBF E 2 8 1 Using the TSK B100 These filters have been designed as rugged
21. hat it has a minimum depth of 25mm This item should be firmly fixed to the wall or other suitable mounting point first With reference to the wiring diagram above ensure that the field wiring is terminated into the dual gang installation box Unplug the 8 way white connector from the Termination PCB Install the wires into the correct socket slot and secure by the terminal screw Ensure the grey connector is facing upwards and that the cables are insulated and neatly located into the base of the installation box Fault M onitoring Selection The module can be configured to provide correct operation for three different types of zone fault indication which provide the same fault detection functions as Hochiki s conventional detector bases when the detector heads are removed The configuration is achieved using jumpers at the top of the termination PCB refer to figure 4 and the selection should be made according to the type of fire alarm control panel being used 1 No line continuity option zone is open circuit during fault Jumpers LK1 LK4 amp LK6 ARE MADE all other jumpers are removed 2 Line continuity using Zener circuit option produces detector removal fault at the control panel 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 12 Jumpers LK2 amp LK5 ARE MADE all other jumpers are removed 3 Line continuity using Schottky diode option produces detector removal fault at the control panel Jumper
22. ion limits 20 to 50 of the initial value Fire condition Red fire LED on receiver lit amp 470 ohm across zone Fault condition Yellow fire LED on receiver lit amp line continuity options Monitor condition Cover open Both left hand and central 5mm red LED s flash Cover closed Left hand 5mm red LED flashes Monitor condition flash repetition time Receiver cover open 1 per second Receiver cover closed 1 per 3 seconds Minimum level determined as total obscuration fire and fault together 90 Minimum time needed to reset from fire 100msec Minimum time needed before beam can reset after fire produced 3 seconds Operating temperature range 10 C to 50 C Maximum humidity 95 R H Beam length 5m to 100m Sensitivity 25 50 or 70 obscuration Size emitter or receiver 86mm x 100mm Weight without termination module Emitter 425g Receiver 490g Colour White Ivory Black lens Housing material ACS resin Mounting Wall mounting Connection method SPB ET Push in terminals Termination module screw terminals Wiring method SPB ET only 2 wire Termination module 2 wires for zone Number of wires between emitter and receiver 2 3 0 294 1ss2 Feb2001 2 wires non polarised Hochiki SPB ET Beam Detector User M anual 26 7 Sensitivity selection The sensitivity of the detector shou
23. ion the characteristics cannot be guaranteed over a long period First determine the sensitivity that the beam detector has been set to and then select the correct filter from the set according to the text on the filters Range 1 relates to 25 range 2 to 50 and range 3 to 70 sensitivity setting Using the No Alarm filter prove that the detector is not too sensitive by placing the filter between the emitter and receiver for at least One minute It is not set to the correct sensitivity if the detector goes into fire alarm or fault during this process 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 19 Next place the Alarm filter between the emitter and receiver for at least one minute During this period a fire alarm should occur If no alarm occurs then the detector is not operating as expected Note When testing the 70 sensitivity setting it is possible that the alarm filter may produce a fault signal as well as a fire alarm signal 3 Maintenance 3 1 General The detector contains an automatic compensation function which allows the detector to Operate correctly even when the amount of signal reaching the receiver has changed the compensation rate is 0 5 hour This means that minor changes due to contamination and beam alignment will not affect the sensitivity of the detector There is of course a limit that the detector can compensate for and this is 50 and 20 of the initial setting In order to
24. l strength is ata maximum Adjust either the fine adjustment wheel or the coarse adjustment wheel until one of the green signal LED s flashes If it is not possible to adjust 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 17 either wheel to cause one of the green LED s to flash then it will be necessary to re check the alignment If the signal stays always in the yellow LED region then the alignment is incorrect and the signal strength is too weak If the signal strength always stays in the red LED region then it means that the signal strength is too high In this case the probable cause is that the emitter and receiver are too close They must have a separation of at least 5 meters 16 feet 2 7 Setting the Sensitivity amp Switches for Operation Set the sensitivity to the required value using switches SW1 and SW2 according to the distance and ceiling height as recommended in section 7 SW3 and SW4 should always be left in the positions shown in the table below The sensitivity for the positions of SW1 and SW2 are shown in Figure 9 together with a side view of the on and off positions as viewed with the detector in its normal installation orientation SWI position SW3 position SW4 position Percentage dB s Obscuration Obscuration 25 1 25 50 T 3 017 70901 5 231 Figure 9 Sensitivity setting After setting the sensitivity close the cover of the receiver the initial values o
25. ld be set according to either the recommendations of a national standard or if there are none then according to the information provided within this document relating to ceiling height and distance between the emitter and receiver See Table 2 Distance between Ceiling height less than 15m Ceiling height more than 15m receiver and emitter Maximum Minimum Maximum Minimum sensitivity sensitivity sensitivity sensitivity Table 2 Sensitivity setting for beam length Note These figures are derived from the regulations governing beam detector installation in Japan and are not necessarily correct for any other country Therefore they are only guidelines for beam detector installations outside Japan If a lower sensitivity setting is used outside of the limits the detector may still be able to detect fire conditions however the detector s response will be delayed t Note LPC approval only covers the sensitivity set to 25 Therefore if the installation requires compliance with BS 5839 Pt 5 in accordance with LPC approval these sensitivity settings must not be used 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 27 8 Troubleshooting The following conditions relate to the SPB ET itself 8 1 Monitor LED fails to flash 8 1 1 Receiver The monitor LED should flash every 3 seconds every 1 second if the cover on the receiver is open If it does not the reason may be as follows gt Zo
26. ne voltage to the receiver less than 15V gt Receiver is damaged Ensure that the receiver has been powered for more than 30 seconds and that the power at the receiver is greater than 15V 8 1 2 Emitter The monitor LED should flash every 3 seconds every 1 second if the cover on the receiver is open If it does not the reason may be as follows No power on the emitter wiring short circuit or open circuit gt Zone voltage to the receiver less than 15V gt Receiver is damaged gt Emitter is damaged Ensure that the power at the emitter is present approximately 8V and also that the receiver is working 8 2 Fire signal continues after reset When a fire has occurred there may be certain circumstances that will prevent the beam detector from resetting These are gt There is an obstruction of the optical path between emitter and receiver Ensure there is no obstruction gt The optical axis has been altered suddenly The beam will need re alignment gt The emitter has stopped working Check the voltage is present at the emitter gt Insufficient time between fire and reset At least 3 seconds are required before resetting the beam after the fire signal has occurred 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 28 8 3 Fault signal cannot be reset 8 3 1 Fire also occurs If a fire and fault occur at once it is because the beam detector has been totally obscured The reas
27. on will be the same as for 8 2 above 8 3 2 Fault only If a fault has been generated without any obvious reason it has occurred due to one of the following reasons gt Contamination limit has been exceeded light received has changed by more than 50 gt The CPU in the detector has lost its stored initial values and the CPU is unable to initialise the detector correctly as the values read are out of range gt The detector cover has been closed without setting the sensitivity gt SW3 and SW4 are in the incorrect positions To clear these conditions the set up and adjustment procedure should be repeated 8 4 Detector in fire panel not registering condition gt The zone is incorrectly wired to the beam detector The wiring must be done in accordance with the relevant wiring diagram 8 5 Detector in fault panel not registering condition gt The zone is incorrectly wired to the beam detector The wiring must be done in accordance with the relevant wiring diagram The following conditions relate to the SPB ET if it is used with the termination module option 1 The conditions already mentioned still apply 8 6 Fault signal cannot be reset If the fault cannot be reset it will be due to the following gt Beam detector is defective or removed from interface PCB 8 7 Detector in fire panel not registering condition gt Panel does not use 470 ohms to detect a fire condition
28. r 3 Installation test filters Option 2 SPB ET detector only refer to section 2 4 2 for installation details 1 Emitter 1 Receiver 2 Metal mounting brackets 1 Installation manual 4 Fixing screws 3 Installation test filters The installation method varies depending upon the installation option used For correct installation refer to the relevant instructions for the installation option 2 4 1 Installation option 1 with termination module The termination module is designed to facilitate installation of the SPB ET beam detector to fire cables using a standard surface flush dual gang installation box The module also provides three types of fault monitoring configurations simple beam reset and remote fire indication 2 4 1 1 Emitter Installation Procedure Ribbon cable installation to Beam Detector Open the detector cover as described in section Thread the 2 way ribbon cable through the back of the beam detector so that the connector remains at the rear of the beam detector and the flying leads exit the bottom front of the beam detector Install the harness into the beam connector starting with the Red wire to E2 and the Brown wire to El The wires should be pushed into the holes of the connector whilst the white push key is pressed with a small screwdriver This will enable the wire to push completely home Pull the wire to make sure that it is firmly held by the connector Wire Installation 2 3 0 294 1ss2 Feb200
29. r in fault panel not registering condition Fault signal cannot be reset Detector in fire panel not registering condition Detector in fault panel not registering condition 9 Installation guide lines General installation conditions Installation in Saw tooth type ceilings Installation in circular type ceilings Installation in sloped ceilings Installation in a monitor roof Installation in corridors or aisles Installation precautions Smoke Patterns 2 3 0 294 1ss2 Feb2001 1 1 General Description The photoelectric beam detector consists of an emitter and a receiver which face each other at a distance of between 5 and 100 meters In the event of fire the smoke generated will decrease the amount of near infrared light incident on the receiver This decrease is electronically interpreted to identify the occurrence of fire An important feature of the detector is that it monitors the protected space linearly This enables the detector to identify a fire before it soreads even when the smoke is scattered over a large area The fire detection sensitivity is switch selectable in 3 settings of 25 50 and 70 beam obscuration 1 2 Detection prindple A near infrared pulsed beam generated by the emitter is sensed by the photo diode of the receiver where it is converted into an electrical signal This signal is then amplified and applied via an A D converter to a microprocessor The normal s
30. ration The beam detector will produce a fault during normal operation for one of the following reasons gt The cover on the receiver has been opened for more than 5 minutes 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 23 gt Thelimit of contamination has been reached The detector is only able to compensate for contamination or alignment change up to a certain point gt The obscuration is greater than 90 a fire alarm signal will also be produced The power has been removed for more than 30 seconds and when powered up the initial received data is too low 5 3 Indication of normal operation When the covers of the receiver or emitter are closed then the red LED visible through the outside of the case will flash every 3 seconds to indicate that the detector is operating correctly If the cover of the receiver is open then both red LED s the centre alignment LED is not visible unless the cover is open on the receiver will flash every second The opening of the receiver cover will make the LED s on the emitter and receiver flash at the faster 1 flash per second rate If the cover of the emitter is open then both red LED s on the receiver will flash The rate of flash will not be affected by opening the cover of the emitter 5 4 Sensitivity setting The receiver is provided with a DIL switch with 2 bits available for setting the sensitivity of the beam detector The settings can be 2596 5
31. res are to come in from below then it will be necessary to break the knock out slot from the bottom of the detector body located near to the retaining clip Hook the back of the detector body to the 4 prongs of the mounting plate and slide down firmly ensuring that the cables are not trapped or damaged by the detector The detector body should lock into place by the locking mechanism which is located on the bottom right hand corner of the detector and secure using the locking screw Refer to the mechanical drawing Figure 1 Connect the two wires which run from the receiver to the emitter The wires should be pushed into the holes of the connector whilst the white push key is pressed with a small screwdriver This will enable the wire to push completely home Pull the wire to make sure that it is firmly held by the connector 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 14 2 4 2 2 Receiver Installation procedure Screw the detector mounting plate firmly to the wall or other suitable mounting point Open the detector cover as described in section 2 3 and then take the wires into the back of the detector through the hole so that they come out below the terminal connector The wires can be installed either behind the detector or from below the detector depending on the suitability of the installation If the wires are to come in from below then it will be necessary to break the knock out slot from the bottom of the d
32. rformed as in Figure 16 The detector s installation height should be 0 8H or higher If there is ventilation in the top part of the roof then the detector must be placed below the opening The detector should be installed in accordance with the following height restriction H a gt h gt 0 8H 4 v d B lt b Figure 16 Installation in a monitor roof 9 6 Installation in corridors or aisles 9 6 1 Closed corridor When the detector is installed in a corridor with a closed corner it is possible to use just one detector as shown in Figure 17 providing that the distance L is less than 7 5m Figure 17 Installation in a closed corridor 9 6 2 Corridor with open adjoining aisle When the detector is installed in a corridor with an area adjoining which is open as shown in Figure 18 it is necessary to consider the adjoining area as a separate detection area 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 33 o Y Figure 18 Installation in an open corridor 9 6 3 Corridor with corners When the detector is installed in a corridor with a bend and an aisle as shown in Figure 19 it will be necessary to use at least 2 beam detectors to cover the corridors If the distance P is greater than 15m then another beam detector will need to be installed at point C cg d 200 05 P B v Figure 19 Installation in a corridor with corners
33. s In locations which may be exposed to sunlight exceeding 5000 lux it is recommended that in locations where the beam detector may be surrounded by glass then the receiver should where possible be fitted so that it faces a northerly direction only relevant to countries in the northern hemisphere gt Where the rigid fixing of either the emitter or receiver is impossible Where access to the beam detector to align and set is impossible 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 2 2 Mounting and removing the detector The detector can be fixed to the metal bracket by hooking the detector body to the four prongs of the mounting plate and then by sliding down firmly until the detector is locked into place and then locking using the locking screw see Fig 1 Removal of the detector can be achieved by slackening the locking screw and pressing the locking mechanism located on the bottom left hand side of the detector housing Whilst pushing the locking mechanism with either a narrow rod or screwdriver the detector is lifted upwards until it disengages from the mounting plate MOUNTING DETECTOR PLATE HOUSING gel SS a SLIDE DOWN MOUNTING PLATE l c 7 Figure 1 Locking mechanism 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 8 2 3 Opening the detector cover Hold the detector
34. s LK1 LK3 LK4 amp LK6 ARE MADE all other jumpers are removed Note The Termination M odule is factory configured for Schottky diode line continuity If in doubt check the correct line continuity suitability for the control panel Warning When the Zener option is used it must be connected to a control panel that is able to use this type of option If connected either to an unsuitable panel or a 24V power supply the interface could be damaged due to over current 8 way two part grey connector for field wiring termination D D S wu wu Remote L Remote LED Zone EOL 1 2 Zone Pan Zone EOL Zone Par rr 1 2222292o2 mi Fault monitoring jumpers LINKS NORMAL SCHOTTKY ZENER ei Link Fitted 10 way ribbon cable socket on reverse of PCB Figure 4 SPB ET Receiver termination PCB Securing Face Plate Ensure that the SPB ET mounting bracket is located the correct way up see Figure 3 Plug the 8 way grey connector into the Termination PCB Secure the faceplate with the screws supplied Ribbon Cable Installation to Termination M odule Connect the socket from the 10 way ribbon cable to the white connector on the Termination PCB ensuring correct friction lock fitting and correct polarity Fit the Beam Detector body onto the hooks of the mounting bracket and slide down to fix ensuring that the ribbon cable is pushed into the space
35. tate signal the initial beam data once stored in the microprocessor is used as a reference for comparison with subsequent beam signals When there is sufficient difference between actual beam strength and stored reference data to indicate the occurrence of a fire then a fire signal is produced A fault signal together with a fire signal is generated if the axis of the beam is completely obstructed as opposed to the partial obscuration due to smoke The microprocessor also provides compensation for a change in received signal value with time caused by contamination of the optics or slight alignment changes The processed signal is adjusted at a rate of 0 5 towards the reference data every hour When the limit of compensation is reached the microprocessor will automatically produce a fault signal In order to improve the performance of the detector and to enhance the rejection of noise the emitter and receiver are synchronised together and therefore the emitter must be powered directly from the receiver Principle of operation Synch nnisation w Fire Signal Emitti an AS m Signal converter Computer gt mi ting QU U Sh Amplifier A D converter Control circuit L p Fault Signal Smoke Emitter U J Receiver E f 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 6 2 Installing the detector 2 1 Siting S
36. wo methods Either by removing the power from the detector for more than the data hold time stated in the specification section 6 Or by switching the sensitivity off DIP switch bits 1 and 2 to OFF and then back to the required sensitivity 4 Terminal layout and part designation 4 1 Emitter Figure 10 Light Beam Adjustment Light Beam Adjustment yr Vertical Screw Horizontal X Operating Indicator LED red Emitter Wiring Terminals Alignment Setting Led red 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 21 4 2 Receiver Se Signal Adjustment Screw Fine Signal Adjustment em Screw Coarse Light Beam Adjustment Screw Light Beam Adjustment Screw Vertical Fault LED Yellow Horizontal Alignment Setting LED Red Sensitivity Operating Indicator and Adjustment LED Fire LED Red Green Sensitivity Adjustment Sensitivity LED Yellow mr oo zz Adjustment BARE LED Red bc po Fc rp L c1 L1 Sensitivity Switches Switches SW3 SW4 SWI SW2 I En ot Switches SW1 SW2 Switches SW3 SW4 must positions can be varied always be in these positions according to which sensitivity has been selected Figure 11 2 3 0 294 1ss2 Feb2001 Hochiki SPB ET Beam Detector User M anual 22 5 Summary of the SPB ET s functions 5 1 Alarm signal output and indicator lamp When the beam is obscured
Download Pdf Manuals
Related Search
Related Contents
BR-PT - PROTAB26 - Manual Android 4.1 CYFD User`s Access Guide Instructions – Parts List – Service Manual OM, Rider 16, 2000-11 STREX Cell Strain Instrument User Manual Paramétrage Anleitung - CONRAD Produktinfo. Untitled - Livingiseasy.co.uk HP Clemco 60 User's Manual Copyright © All rights reserved.