Home
Dingo Reference Manual
Contents
1. 12 Low Battery Disconnect LSET LON 0 12 4 0 IN 13 l M 13 ININ 13 lan 13 13 MIT p 13 OUST IESE A A 13 13 6 0 DATA Menu Retrieving Performance Data 14 6 1 amp 6 2 VMAX Se nes 14 Rev I 5 4 02 13 Dingo 2020 Reference Manual 6 3 FTIM Float time Display 5 la 14 6 4 SOC State of Charge Display 14 6 5 TEMP External Battery Temperature Sensor Display 15 Setting Lockout 15 6 6 SOLV Solar Voltage Display 15 6 7 HIST History display 15 7 0 SET menu REN ERIS 17 17 TA NMOLT 17 7 3 PROG Adjusting Regulation Settings 17 Program Function Table Generic 17 Program Description 17 Settings Used in Program
2. 30 days ago For further information visit www plasmatronics com au
3. a Lo Normalised to 2 25V cell 0 4 2 05 23 20 00 10 00 0 00 10 00 20 00 30 00 40 00 50 00 16 MIN Temperature 60 00 Fig 7 4 3B Temperature compensation curves e Dingo 2020 Reference Manual Rev 1 5 4 02 13 TIME gt PROG gt REG gt MODE gt EVNT XP dd CHRG 1 Y LOAD Y IN OUT DATA SET Fig 7 5 MODE Menu LSET gt Set function of LOAD terminal GSET Set function of general purpose terminal ESET Set control of external switches BSET gt Set function of B input BAT2 gt Set Regulation voltage for 2nd battery control PWM gt Set which terminals use Pulse width Modulation BCAP gt Set amp Hour capacity of the battery 20 20 000AH ALRM gt Set voltage at which to activate alarm EET gt Reset system losing today s data and time DFLT Reload factory default settings 7 5 MODE Menu Adjusting Configuration Settings PROG 4 only The MODE submenu contains most of the settings for the configuration of the Dingo other than the main regulation settings 7 5 LSET amp GSET There are two output terminals on the Dingo LOAD and and six logical control functions The LSET and GSET settings define which of the six functions controls each of these output terminals Note that the settings described below are different from the LSET and GSET screens described
4. The G relay terminals do not need a catch diode across the relay coil to protect from the flyback voltage This protection is built into the G terminal Intermediate Relay 4e It can be difficult to determine what current is required to operate the remote start The best way to do this is to measure it Short the remote start terminals with a multimeter on its current range Generator and measure the current R t The manufacturer s manual should contain this SIMOIS information but often does not Start Unit The generator control provided by the Dingo is G relay switches a larger relay simple a contact closure is provided when the generator should run and the contacts open when the generator should be stopped It does not handle the issues associated with starting such as fuel and what to do if the generator does not start This should be handled by the remote start unit Fig 2C Generator start wiring with an intermediate relay Dingo 2020 Reference Manual Rev 1 5 4 02 13 3 0 LOAD Menu LOAD The LOAD screen gives real time total load current in Amps This total is the sum of the current flowing through the load terminal LINT and any external load current This may be current from an external switchblock or an external current measured using a current shunt and a DSA LINT From the LOAD screen a long push displays LINT Load Internal This is the real time
5. 11 0 13 0V Dingo 2020 Reference Manual TIME gt VOLT gt PROG gt REG gt MODE gt 4 BMAX gt Set max boost voltage gt Set max equalisation voltage gt Set equalisation time EFRA gt Set days between eq cycles 9887 gt Set absorbtion voltage ATIM gt Set absorbtion time icd gt Set float voltage pst gt Set hysteresis Brin gt Set boost return voltage GLIM gt Set charge current limit BERG gt Set max days to between boost cycles TCMP tt ti fil gt Set temp compensation profile 7 4 1 HYST Hysteresis Value When not in PWM mode the Dingo controls the battery voltage by simply switching the charge current on and off It turns off the charge current at the relevant voltage set point for the state Float Boost Equalise Absorption and allows the charge current to turn back on at a slightly lower voltage The gap between the two voltages is called hysteresis Example With the Dingo in float mode and slow switching i e not using PWM the charge current will be turned on until the battery voltage rises to the FLTV value Once the FLTV value has been reached the charge current will be turned off until the battery voltage falls to FLTV HYST float voltage minus the hysteresis value at which time the charge current will be turned on again until the battery reaches FLTV and the cycle begins again The larger the hysteresis values the slower the
6. 35 2 Specifications 35 A 3 The Alarm Led uses cii vibe Rcntige Dd bp tips QUELS RO IU CPOE Uu n ian o ei DR mE 36 A 4 Current limits amp thermal derating 36 5 Block Diagram sceau UR eiu 36 A 6 Mechanical Information amp Legal statement on warranty 38 Programs 0 3 Menu System adsense melee pr Resina intr Hb RE ERE 39 Program 4 Menu System for custom settings esses 40 Settings and History record 4l Dingo 2020 Reference Manual Rev 1 5 4 02 13 Introduction Please read the User Guide before reading this manual In most cases the User Guide provides all the information needed for effective installation of the Dingo and there is no need for the user to read this Reference Manual Some users will require further information This manual provides a detailed technical description of the operation of the controller This manual assumes more technical knowledge than the User Guide If you are in any doubt it is recommended you do not adjust the advanced settings described in this manual Incorrect adjustment may reduce the effectiveness of your Dingo and could damage your battery All voltage values used in this manual assume 12 system Scale voltages for other system voltages e g 24V system voltages x 2 48V system voltages x 4 Display Additio
7. Alarm Wiring alarm light or other type of alarm connected to the LOAD or G terminal There is no audible alarm built into the Dingo It can send a signal or power to an external alarm of some kind The reverse function could be used to turn off a low priority load when the battery voltage is getting low RI Value IK 1 4W 596 24V 2K2 1 2W 596 48V 4K7 1W 596 Higher wattage resistors may be used RI values are calculated to give adequate LED brightness at low battery voltage but not burn out at high battery voltages eg in case output function changed by mistake Settings SET PROG 4 SET MODE GSET 8 on when battery voltage alarm setting SET MODE ALRM 11 4V for example Set as required 7 5 8 RSET amp DFLT Reset RSET A long push on RSET will reset the Dingo s microcontroller it s brain This has the same effect as disconnecting the power to the controller except that it can be done without removing a wire It is a warm reboot Reset has the effect of clearing the day s Performance Data and setting the clock to 10 00 am Note that you will need to re enter the current time on the internal clock but your other settings and history will be retained Set Defaults DFLT A long push on DFLT will cause the settings for Program 4 to be reset to the settings for Program This provides a way to return the program 4 settings to the factory settings 5 4 02 13
8. GSET if using the G relay to switch the changeover relay BSET I B input used for 2nd battery control The B sense input is wired to the positive terminal of the second battery and allows voltage monitoring of the second battery voltage This allows the regulator to perform basic single stage regulation of the second battery by switching the relay on or off to connect disconnect the charge source second regulator is NOT required The changeover relay will need to meet the following minimum specifications Correct coil voltage to match the system voltage ie able to handle the maximum battery voltage Output contacts rated for DC current Output contacts rated to handle the maximum current that the connected panels can output Note It is suggested that customers leave some panels permanently connected to the regulator 501 input Ist solar and switch all the other panels 2nd solar across with the relay This leaves a regulated maintenance charge available for the Rev 1 5 4 02 13 Dingo 2020 Reference Manual primary battery and can minimise the amount of cause some ringing on turn off Keep wiring as switching required by the relay which switches over short as possible and panel cable pairs together each time the primary battery bank voltage falls cable tie On long wiring runs at higher voltages below HYST The maximum relay switching some damping may be necessary an
9. gt Set days between generator exercises Set length of generator exercise gt View change number of days since last exercise or run time if generator running Rev I 5 4 02 13 Dingo 2020 Reference Manual GSET Turn on when battery voltage falls to G ON for GDEL minutes Turn off when the voltage rises to GOFF for GDEL minutes Quiet time applies i Turn on when the State of Charge SOC In the GSET screen a long push will manually change the state of the generator output The GEN indicator at the bottom of the screen is visible when the generator function wants the generator to be running Note the Generator will not turn on during the quiet time if selected see below falls to G ON of the battery capacity Turn off when the voltage rises to GOFF for GDEL minutes Quiet time applies GMOD 2 Turn on when SOC falls to The generator can operate in four different modes The generator mode is selected in the GMOD screen and can be 0 6 Turn off when SOC rises to GOFF96 Quiet time applies Quiet time In modes 0 1 amp 2 the generator is screen the generator will run for GRUN hours not allowed to operate from 9pm until 9am so as 4 No quiet time Turn on when battery voltage falls to G ON for GDEL minutes to enforce a quiet time Modes 4 6 are the same as modes 0 2 except Turn off when the voltage rises to GOFF that there is no quiet time for GDEL minutes N d he GSET d
10. if the battery voltage is which function controls the general purpose lower than the alarm voltage setting ALRM relay and whether it is on closed or off open This could be used to turn on an alarm light when the function is active o Dingo 2020 Reference Manual Rev 1 5 4 02 13 Shunt Control The Dingo supports either series control shunt control or both at the same time In a hybrid system the main solar component is controlled by the SOL input and the other charge component wind hydro etc is directly connected to the battery and controlled by a dump load which diverts excess charge The dump load is managed by the shunt control function This can operate via the LOAD or G terminal either directly or through a relay These functions are configured in the LSET and GSET screens see above Regulating Wind Hydro Shunt control is appropriate for wind generators or microhydro systems which require a constant load on the charging source so the generator doesn t overspeed and destroy itself In this case the charging source must remain connected to the battery at all times Shunt control also referred to as diversion control refers to the technique of controlling the battery voltage by drawing energy from the system with a dump load rather than disconnecting the charge source as series control does on the solar input To regulate a wind or microhydro installation with shunt control
11. rate of switching on and off will be NOTE When switching a mechanical relay for regulation purposes the HYST value may need to be increased so that the relay does not wear out quickly due to rapid switching o Dingo 2020 Reference Manual Rev 1 5 4 02 13 Timers The HYST value is also used to start and stop the timers associated with the different regulator charging states Boost Equalise and Absorption Example When the Dingo changes to the Absorption state an internal timer is started to monitor how long the regulator has been in Absorption If however the battery voltage falls lower than ABSV HYST this timer is stopped and starts again when the battery voltage rises above ABSV HYST This ensures that the regulator holds the system in the required state for the correct programmed time and doesn t continue to the next charging stage until this time has elapsed NOTE An exception to this is the Equalise State which will terminate after 4 days if unable to complete the full specified time period 7 4 2 CLIM Charge Current Limit The Dingo has a built in charge current limit If the charge current exceeds the CLIM setting the charge duty cycle will be reduced to limit the average charge current This allows the Dingo to protect itself from overheating due to excessive charge current The maximum charge current can also be limited for small batteries where the full array current might be too much for the
12. 5 2 SW I toC 0 charge switch on to charge SET EVNT Setting for program number Parameter 0 2 3 STRT 0 STOP TIME Hr EMOD Settings for Program 4 If program 4 is selected then all settings can be accessed and adjusted After TIME VOLT and PROG there are entry points for three further sub menus REG Allows the user to customise the regulation settings see below for details MODE Allows the user to adjust other configuration options EVNT Settings for the event controller Rev 15 4 02 13 CHRG LOAD Y IN Y OUT DATA Y SET Fig 7 4A Regulation Settings Program 4 only 7 4 REG menu Customising Regulation Settings PROG 4 only To adjust the regulation settings long push on SET short push to and long push see fig 7 44 The settings given below are for 12 systems For other system voltages the value can be scaled from this eg for a 24V system multiply all voltages by 2 SET REG Submenu Summary Name Description Range boost mode equalisation cycles ATIM 0 4 0 hours Float voltage 13 0 15 0V HYST Hysteresis used when 0 1 1 0 not in PWM mode BRTN Voltage below which return to Boost mode occurs CLIM Charge current limit 0 5 20A BFRQ Maximum number of days 1 20 between boost cycles TCMP Selection of temperature compensation profile see below 7 4 3
13. 7 6 EVNT Menu Event Control The event controller allows something to happen when a set of conditions is met There are many applications for this feature such as Turning on a light at night Using waste energy pumping water in the afternoon if the Dingo is in the float state Sensor operated timed lighting at night Turning on sprinklers for an hour if it s over a certain temperature Using the Event Controller Step Select PROG 4 In Programs 0 3 the event controller is set up to do a night light function This function is available on the load terminal in programs 2 amp 3 and on an external switch For users who wish to use the event controller in a different way Program 4 must be selected Step 2 Set LSET GSET or ESET It is necessary to tell the Dingo which output switch will be controlled by the Event Controller For the LOAD terminal this is done using the Fig 7 6A Event Control Menu PROG 4 only pio d CHRG Dingo 2020 Reference Manual LSET setting For the G relay use the GSET setting Also the event control can be assigned to one or more of the external switch blocks connected to the bus by using the ESET settings These settings are described in Section 7 5 Step 3 Set the STRT condition The Dingo must be told what signifies the start of the event Move to the EVNT menu as shown in Figure 7 6A A long push on EVNT will move to the STRT setting STRT uses the following ta
14. opposite sense to normal it is possible to select the inverse of each control e g for shunt regulation The switches are numbered to 9 then A B and When switch is being controlled by the charge controller it is turned on or off to try to maintain the controllers target voltage The controller tries to reduce the amount of switching to a minimum to reduce any electrical interference caused by switching 8 3 Connecting external devices Each device connected to the controller must be discovered by the controller and given a number There are two ways to do this Each device will have a means to set its own number Each device must have its own number and no two numbers can be the same When connected the device will display information or be controlled according to that number Dingo 2020 Reference Manual Rev 1 5 4 02 13 Gen Solar Solar Solar Load f Shunt External Switch Switch Switch Cunt Computer Interface 2 3 Sensor Battery It is also possible to have the controller discover each device and assign it a number based on the device s serial number The lowest serial number will be given the lowest device number The next lowest serial number will be given the 2nd lowest device number and so on until all devic
15. right to repair or replace The decision to replace is only to be made by us or one of our authorised agents 2 We are not responsible for costs incured by the user or installer in retrieving or reinstating a faulty unit 3 We will not pay the cost of freighting faulty units to us or being returned from us 4 We are not resposible for damage to other devices or property which may have occured due to the failure of a unit 5 While care has been taken to protect the device against lightning strikes we will not honor the guarantee in respect of lightning damage 137mm 54 S B L S B L QF 37mm CI CDI D DJ 1 5 116mm 4 6 Rev 1 5 4 02 13 Dingo 2020 Reference Manual Programs 0 3 Menu System Programs with fixed settings Section 1 BOST gt EQUL gt gt Vi Y X 2 CHRG CINT External GRUN Set length of generator exercise GDAY View change of days since last exercise or run time if generator running ye 4 IN External 5 OUT INT External 4 Clear 7 6 DATA VMAX VMIN FTIM SOC TEMP SOLV gt HIST gt DAY1 gt IN gt OUT gt VMAX gt VMIN FTIM SOC NEXT gt BACK gt EXIT 1111 DAY 2 IN OUTAVMAX VMIN gt
16. the battery will probably be damaged under or overcharge if this setting is in error for more than a few days 7 3 PROG Adjusting Regulation Settings The Dingo comes with a number of preconfigured programs which are set up for generic batteries For custom installations selecting program 4 allows the user to adjust each setting individually If you find you are unable to change your settings it may be because the lockout setting is activated This setting is designed to prevent unwanted tampering please see the Setting Lockout information in section 6 5 Dingo 2020 Reference Manual Fig 7A The SET Menu SET gt TIME VOLT PROG gt REG MODE EVNT 411 Set Set Set time battery program voltage Program Function Table Generic Programs Program 0 1 2 Functions No Night Light Night Light Low Battery Disconnect Low Battery Disconnect is enabled for Programs 0 3 Programs 2 amp 3 turn on the LOAD terminal at night for lighting applications Program Description PROG O0 Use with liquid electrolyte lead acid ie flooded batteries The LOAD terminal is set to turn off when the battery is low Also known as Low Battery Disconnect PROG 1 Use with sealed or gel lead acid batteries The LOAD terminal is set to turn off when the battery is low PROG 2 Use with liquid electrolyte lead acid batteries ie flooded The LOAD terminal is set to turn on all
17. the internet The network side is DC isolated from the Dingo side All of the data is remotely accessible and all settings can be adjusted It can also be accessed through a web browser or using SNMP Remote Control DRC The Dingo can be accessed remotely with the remote control All of the functions work in the same way as on the actual controller Includes built in audible alarm and display backlighting A 2 Specifications Nominal system voltages 12 24 32 36 48 Maximum voltage BAT to BAT 100 Max voltage to BAT for V minute Maximum voltage SOL to SOL Max voltage LOAD to LOAD Max voltage between the G relay terminals Max voltage B sense to BAT Max continuous charge current SOL Max continuous load current LOAD Max load current for 5 minutes V V V V A A A mA Max G relay current Battery Temp sensor range C 70 upply Current Dingo only 60V Supply Current max with acces Meter Accuracy lt 2 2 display digits 16mm 6 AWG Wire size Signal Green Terminal Block 0 2 1 3mm 26 16 AWG Max storage temperature upply Current Dingo only 12 359 08 mA mA mA Max power wire entry size Dingo 2020 Reference Manual Rev 1 5 4 02 13 A 3 The Alarm Led The alarm led is used to indicate a number of different conditions The states are on not flashing battery voltage alarm voltage slow flash most
18. your best guess of the batteries actual capacity when used in the way you intend to use it For example if you think the battery will mostly be charged and discharged at around the 20h rate C 20 you should set the capacity of you battery at the 20h rate 6 7 HIST History display from the manufacturer s literature If you Six pieces of data are recorded each day These expect the battery to be used at a variety of are charge and discharge currents try to estimate Total Ah IN for the 24hrs This is a measure of an average the energy collected that day e Peukerts equation can be used to estimate Total Ah OUT for the 24hrs This is a measure of the loss in capacity at higher discharge rates Correction based on Peukerts equation is not done automatically because it does not model discontinuous and variable rate discharge very VMIN the minimum battery voltage that day well and changes with battery age the energy used that day VMAX the maximum battery voltage that day FTIM time of day the controller changed to float mode if it didn t 6 5 TEMP Display External Battery SOC the state of charge at the end of the da Temperature and Setting Lockout 5 4 These figures are a very good guide to how well the solar system is performing The user can compare the energy collected with the energy used and get some feedback about the balance between collection and use This screen displays the external batter
19. 2 GSET toggle does not work during generator exercise 3 A small amount of overcharge will occur if battery is already fully charged Use a low GRUN value if this is of concern GDEL Generator changeover delay A programmable delay in minutes is used to prevent false turn on or off of the generator due to large transient loads Default setting is 10 min The generic programs PROG 0 3 use voltage driven generator control GMOD 0 See settings used in Programs 0 3 for on off voltages etc Generator Example For example if SOC triggered generator on voltage triggered generator off and no quiet time is desired set up the regulator as follows SOC 96 ON Voltage OFF no quiet time GEXD GRUN as required SET REG Check these settings are correct for your battery type Mode menu GSET if using terminal for GSET 2 generator control or LSET if using LOAD terminal LSET 2 for generator control Note when changing from prog 0 3 to program 4 the user can load the default settings for program into the Dingo using the DFLT screen in the MODE menu See section 7 5 8 This can save a lot of time Generator Control For many generators it is possible to control their operation remotely This is either a remote start or run function built into the generator or a separate remote start unit There is usually a pair of contacts that will cause the generator to run if they are closed This can be done wit
20. FTIM gt SOC NEXT BACK EXIT 11 set to adjust Toggle setting lockout showing means current BATW settings adjustable a 7 SET TIME VOLT PROG 4 Set Set Set Set time battery Program battery voltage capacity Toggle function status on off m m mm m m GSET 1009 DAY 3 gt IN gt OUT gt VMAX gt VMIN gt FTIM gt SOC NEXT gt BACK gt EXIT DAY99 gt IN gt OUT gt VMAX gt VMIN gt FTIM gt SOC gt NEXT gt BACK gt EXIT Thin arrow short push mm Thick arrow long push 1 Explained in User Guide p8 time gt Note will not toggle if clock is 1 1 1 between 9pm gt 9am Quiet 1 3 LOAD m NT External 2 w gt oa gt Toggle low battery disconnect status on off v v DAY2 DAY99 DATA v DAY DATA 11 DAY4 DAY2 DATA M DAY1 DAY98 DATA Dingo 2020 Reference Manual Rev 1 5 4 02 13 Program 4 Menu System For adjustable settings Thin arrow short push gt Thick arrow long push Explained in User Guide p8 Section x BATV BOST gt EQUL ABSB FLOT Y 2 CINT External J 1 x Note GSET will not togg
21. QUL and ABSB which occurs at high cell voltages The Dingo displays the time on the equalisation or will keep the battery voltage at the absorption absorption timer is displayed When this time voltage ABSV until it has been at this voltage for reaches the set time ETIM or ATIM the Dingo the absorption time ATIM When the absorption will advance to the next state Remember that time is finished the Dingo advances to the Float the timers will stop if the voltage falls too far state below the set point If there is a cloudy period and there is insufficient charge current to keep the voltage up to ABSV then the absorption timer will stop and resume Many battery manufacturers recommend that the when the voltage comes back up to ABSV battery bank be given an overcharge occasionally This is a deliberate overcharge designed to equalise the voltages and specific gravities of all the cells in the bank by bringing them all up to full charge and to stir up the electrolyte in liquid cells 1 2 Equalise optional To allow some margin the timer actually runs if the voltage is above ABSV HYST HYST is the hysteresis setting used for slow speed switching usually about 0 4V to reduce stratification 1 4 FLOT Float The Dingo supports an automatic programmed In this state the battery has been fully charged equalisation This state allows the battery voltage The charge current is now used to keep the to rise until it gets to the equalisatio
22. Rev 15 4 02 13 Dingo 2020 Reference Manual D2020 Advanced Solar Charge Controller Dingo Reference Manual oo Solar Charge Regulator 12 48 20 e Dingo 2020 Reference Manual Rev 1 5 4 02 13 Contents 1 4 Additional Installation Notes 4 gil 5 Overload 5 Thermal T o 5 1i m 3 1 0 c 6 The Regulation Cycle 6 1 1 BOST Boost IT 6 Returning to Boost state 6 1 2 Equalise optional 7 7 Dae EY TAP E E 7 2 0 MG a 8 sS cH 8 m 8 CEA e E 8 Generator Ecc 8 GSE A 9 GMOD n 9 GEXD Generator Exercise 9 GDEL Generator changeover delay 10 Generator Example 10 3 0 LOAD Menu 12 ES D E E E A 12 EINT err 12 LEAT
23. The following accessories plug into the serial port socket which is under the wiring cover External Shunt Adaptor DSA Up to four external shunts can be added to the Dingo to allow it to measure larger currents than it is capable of measuring directly The shunt adaptor measures the current in a shunt eg SH200 converts it to digital information and sends that information back to the Dingo The connection to the shunt is DC isolated from the Dingo so the shunt can be placed in any part of the circuit Currents up to 250A can be read in 0 1 steps See the DSA instruction sheet for more information Computer Serial Interface DUSB A serial interface is available which allows the Dingo to communicate with a computer It connects to the computer s USB port The computer side is DC isolated from the Dingo side This is a quick way to load settings into the Dingo or extract performance data All of the data is remotely accessible and all settings can be adjusted Software is available for IBM compatibles to make this easy Data can then be loaded into a spreadsheet or other applications Modem Serial Interface D232 The serial interface is also available in a version designed for remote access via a modem This uses an RS232 interface configured as a DTE device Dingo 2020 Reference Manual Ethernet Interface DNET ethernet interface is available which allows the Dingo to communicate with a computer a network or
24. XAVMIN FTIM SOC NEXT BACK EXIT SET TIME VOLT PROG gt gt gt y y 4 Y DAY4 DAY2 DATA Set Set Set DAY99 l UTAVMAXAVMIN FTIM SOC NEXT BACK EXIT time battery Program voltage LSET m Set function of LOAD terminal GSET gt Set function of general purpose terminal G BMAX Se max boost voltage ESET gt Select which internal function controls an external switch EMAX Se max equalisation voltage Set function of B input ETIM gt Se equalisation time BAT2 gt Set Regulation voltage for 2nd battery control Y EFRQ Se days between eq cycles PWM gt Set which terminals use Pulse width Modulation ABS Se absorbtion voltage BCAP gt Set amp Hour capacity of the battery S ATIM Set absorbtion time ALRM Set voltage at which to activate alarm Set float voltage RSET gt Reset system losing today s data and time Y MYST gt Set hysteresis DFLT gt Return settings to factory defaults BRTN Se boost return voltage CLIM Se charge current limit ESET Submenu not shown for clarity BFRQ gt Se max days to between boost cycles ji See section 7 5 2 TCMP Se temp compensation profile v DAY1 DAY98 DATA STRT gt Set what determines start of Event Setting Set value which goes with STRT STOP Set what stops Event Setting gt Set value which goe
25. XIT 2 DAY99 DATA v DAY 2 gt IN gt OUT gt VMAX gt VMIN gt FTIM gt SOC gt NEXT gt BACK EXIT DAY 3 DAY1 DATA v DAY 3 gt IN gt OUT gt VMAX gt gt FTIM gt SOC gt NEXT gt BACK gt EXIT Be DAY4 DAY2 DATA DAY 99 gt IN gt OUT gt VMAX gt VMIN gt gt SOC gt NEXT gt BACK gt EXIT 1 DAY98 DATA Rev 1 5 4 02 13 BATV 7 0 SET menu n CHRG The set menu contains most of LOAD the settings which control the IN operation of the controller OUT DATA 7 1 TIME This screen displays the time on the controller s clock A 24hr format is used for system time with a resolution of 6 minutes 0 1 hours So for example 14 3 is 2 18 NOTE Removing power to the regulator i e turning it off will reset the system time to 10 0hrs 10 00 AM The time must be set whenever the regulator is restarted Incorrect system time will result in misleading history data since this is stored at midnight of each day Generator quiet time and time driven event control will also be affected 7 2 VOLT Set VOLT to the nominal system voltage for the installation This setting determines the regulation and control voltage set points for the system For correct regulation this setting MUST be correct NOTE The controller will not be damaged if the voltage is set incorrectly but
26. a dedicated dump load must be available for the Dingo to switch across the battery The dump load current should be larger at the range of expected battery voltages than the maximum charge current available from your generator The function of the dump load is to soak up energy coming in which the battery cannot store in order to maintain the desired battery voltage 7 5 2 ESET External switch setup The Dingo has a serial bus which allows the user to add external devices to increase the control system s capability One such device is an electronic switch This can be used to increase the charge current being regulated or increase the load current being controlled by the load disconnect function The user needs to select which internal function will control each external switch block This is done in the ESET sub menu A long push on ESET brings up the first switch setting Short pushes move to the next switch until ESET returns after switch C The following table shows the control options SET MODE ESET Selection Summary EGER On when Dingo wants to charge 22 29 Off when Dingo wants to charge On when load should be off Off when load should be off 4 Alarm normal On when battery ALRM voltage 5 Alarm inverse Off when battery lt ALRM voltage Event normal On when the event is active 7 Event inverse Off when the event is active 7 5 3 BSET Configuring the B Sense Input The terminal lab
27. able test condition TMOD TMOD is active when Value to set Always active None Pr buses 6 lt setting 8 jTime seting Note VEXT depends on the setting of BSET If BSET 2 then VEXT is the voltage on the sense terminal This voltage is relative to the terminal in the negative direction max 27V If BSET is less than 2 then VEXT is an external voltage read by a bus accessory After setting the TMOD value a short push will move to the associated setting as for STRT and STOP Step 6 Finally a short push displays a screen which shows the current state of each of the conditions and whether the event is currently active If the event is inactive then to turn it on all three conditions STRT EMOD and TMOD must become active i e show as When the event is active if the STOP condition takes place or the TMOD or EMOD condition goes inactive ie 0 then the event will turn off If the display shows E ON then the event is currently active If it Shows EOFF then the Dingo 2020 Reference Manual Rev 1 5 4 02 13 Whether EMOD is on 1 or off 0 if EOFF Whether STRT is on 1 or off 0 ON Whether STOP is on 1 or off 0 Whether TMOD is on 1 or off 0 1 EOFF Fig 7 7A Event State event is currently not active but will become active when all of the preset condition
28. amage due to over discharge the Dingo has a function which turns off the load if the battery voltage falls too low If correctly configured equipment connected to the Load terminal the load will be turned off when the battery voltage falls below the LOFF voltage for LDEL minutes Once turned off the load will not be reconnected until the voltage rises above the L ON voltage for LDEL minutes The L ON voltage should be set high enough so that some recharge will have taken place before reconnection otherwise the disconnection process can oscillate This feature is optional and can be disabled either by connecting the user load directly to the battery or by setting LOFF low enough so that the low battery disconnect function never activates The LOAD indicator at the bottom of the screen is visible when the low battery disconnect function wants to disconnect the load Note that other settings can override the function so the LOAD indicator does not necessarily mean that power has actually been disconnected from the load When the disconnect timer has begun to timeout the alarm led will flash at a 2 second rate with the led mostly on If the load disconnect function operates then the alarm led continues flashing but with the led mostly off The Low Battery Disconnect function can also be toggled manually by a long push when in LSET menu see Figure 3A 15 4 02 13 Selecting a load switch The low battery
29. are sub menus These are entered by doing a long push in the main menu They allow access to more information and control of more advanced features The following pages describe each submenu in detail Dingo 2020 Reference Manual Rev 1 5 4 02 13 1 0 Menu The screen shown at power up displays the real time battery voltage A long push on the BATV screen will display the state of the charge regulation cycle The Battery Charge Cycle The Dingo s sophisticated regulation system is designed to keep the battery fully charged without overcharging it To achieve this it uses a charge control process with three main states These states are Boost Absorption and Float It also uses a fourth state from time to time called the Equalisation state See fig 1 1 BOST Boost In the boost state all the charge current available is used to charge the battery As the battery charges its voltage rises When the voltage reaches the boost maximum voltage BMAX and remains there for 3 minutes the controller will automatically advance to the absorption state and then later to the float state Returning to Boost state To get this charge cycle to repeat the Dingo must return to the boost state There are three ways that it can do this CHRG LOAD Y IN Pn SET BOST EQUL gt ABSB FLOT AL Fig The Menu Structure a Low Battery Voltag
30. ation is achieved The Dingo can automatically sense the presence of a temperature sensor if one of the auto sense profiles is selected However if operation at temperatures below 12 C is common it is better to use the non auto sense profile 4 7 The auto sense will not detect sensors colder than 16 Fig 7 4 3B shows the temperature compensation curves for each TCMP setting Consult the battery manufacturer for correct compensation for the battery used 1 5 4 02 13 Connecting a Temperature Sensor The temperature sensor should be connected to the T and T terminals on the green terminal block see p37 The sensor wire with the stripe goes to the T terminal and the sensor wire without the stripe goes to T terminal The wires may be extended if necessary without affecting the accuracy Note The DTB bolt on metal lug has no electrical connection to metal lug housing so it can be connected to either the negative or positive battery terminal Dingo 2020 Reference Manual Neoprene sponge temperature sensor mounting DTB Battery Fig 7 4 3A Attaching a Temperature Sensor to a battery 2 6l 25 245 4 Ni NOU NE OMNCM MONS 24 Diagram Key 2 35 x Linear Gentle Curve 23 Steeper Curve Limited Linear 2 25 2 2 13 7 gt Non Autosense should be ise 1 5 215
31. bank The Dingo has a separate single stage controller for a 2nd battery built into it This allows the second battery to charge if the main battery has reached the float state and the voltage on the 2nd battery is below the setting in the BAT2 screen The second battery control function uses a relay to switch the solar array positive from the primary battery to the secondary battery NOTE Second battery control is not suitable for use in positive ground systems since it uses the B sense input and requires the battery positive terminals to be separated i e not both connected to the chassis Use a positive ground controller in this case With the negatives of the two batteries joined together the Dingo can read the voltage on the second battery from the B sense input An external switching device such as a changeover relay will be required to switch the positive of the solar panel s from the SOL terminal of the Dingo to the positive terminal on the second battery see fig 7 5 44 Use either the Load terminal or G relay for switching the changeover relay the relay max current is only 300mA but this should be enough Use LOAD or G output to switch relay Wiring for G output shown Fig 7 5 4A Second Battery Control to drive most relays The following settings will also need to be configured PROG 4 allows changing LSET GSET BSET etc LSET 6 or LSET if using load terminal for relay
32. battery This is useful for systems which are marginal in winter but have too much charge current for the battery in summer It can also be useful where there is an initial ageing effect in the first few months of the life of the module For example with amorphous modules the initial current may be more than the charge current rating of the Dingo Making use of this feature panels can be installed with the full rating calculated after the initial drop off NB Current limiting is only done for the Dingo It is not done for the external charge switches 7 4 3 TCMP Temperature compensation Default 0 Adjustable in Program 4 only A temperature sensor is available which allows the SET REG TCMP Selection Summary Function Example Battery bmV C linear auto sense default gentle curve BP Solar Block auto sense General Purpose use this if in doubt auto sense Absolyte battery non auto sense use this if in doubt non auto sense steeper Sonnenshein Dry Fit non auto sense Absolyte battery No temperature Failsafe if short sensor across T inputs Note Without a temperature sensor fitted the Dingo TEMP display will be blank if autosense is enabled and shows 2 if non autosense Dingo to adjust its regulation voltage settings to compensate for variations in battery temperature The setting TCMP is used to select a temperature profile which determines how this compens
33. ble to determine what will start the event After setting the STRT value a short push will move you to the setting which goes with that STRT value For example if you set STRT to 3 you will see SOLV Whenever the solar panel voltage drops below the value you set in SOLV the event will start if the other conditions permit If the start condition is to be ignored then select STRT 0 so that the start condition is always active Note A start occurs when the start condition changes from inactive to active and the EMOD amp TMOD conditions are active Further starts are blocked while the start condition remains active When the start condition goes inactive it clears the block This prevents an event being immediately retriggered when it finishes TIME gt PROG gt REG gt MODE gt EVNT Y LOAD Y IN Y di SET STRT gt Set what determines start of Event Setting gt Set value which goes with STRT STOP Set what stops Event Setting gt Set value which goes with STOP EMOD gt Set second condition for Event TMOD Set third condition for Event Setting Set value which goes with TMOD EOFF EON View current state of Event Controller e Dingo 2020 Reference Manual Rev 1 5 4 02 13 SET EVNT STRT Selection Summary STRT Event starts when Value en set O Always starts Time gt setting 0 0 23 9 Hw 2 Solar panel voltage SOLV open circuit gt set
34. creen The indicator will disappear A useful SOC to be adjusted to the users best estimate of memory aid is to consider that stands for the present SOC Adjustable on this screen The SOC figure should be treated with caution To enable adjustment of settings again long as there are many reasons that it may be push on the TEMP screen again If you have Inaccurate successfully enabled settings adjustment the The Dingo does not automatically have will reappear while TEMP is showing knowledge of the whole system It only The controller remembers the state of the knows what you tell it For SOC to work settings lockout when the power is disconnected well it must be measuring all charge Ah in and discharge Ah out If the battery can charge or discharge without the Dingo 6 6 SOLV Solar Volt Display knowing SOC will not be very accurate oar This screen displays the open circuit solar panel The effecti ity of the batt d e capacity the battery reduces voltage with age BCAP should be reduced in older batteries to adjust for this The charge current through the SOL terminal is turned off while the Dingo is displaying this screen If the view is left on the SOLV screen the charge current will be automatically reconnected after 18 24 minutes This is to prevent battery failure due to lack of charge failsafe When you set up BCAP on installation you should choose
35. d possibly rate is one cycle per 30 seconds A pair of DC some external clamping of transients With highly output solid state relays is a good choice here inductive wiring the transients may be large enough to damage the FET switch Consult the This setup may not be the best use of available d ee factory if further information is required charge current Consider if it would be better to increase the size of the primary battery bank LOAD terminal PWM switching 7 5 5 PWM and Slow Switching For PWM control to be available on the LOAD When the Dingo is trying to keep the battery terminal LSET must be set for Function 10 voltage constant it does this by turning the Shunt Control charge current on or off as required It can do DO NOT set LSET to Function 1 Inverted this quickly or slowly Shunt Control if using PWM on load terminal see the LSET table PWM should only be enabled on the LOAD terminal PWM 2 or 3 if the LOAD terminal SET MODE PWM PROG 4 Only is being used to directly switch a dump load no o An exception to this is when the LOAD terminal PWMonSOLtermindony is driving a solid state electronic relay non mechanical as these can usually switch at the NOTE PWM is not available on the G relay PWM fast switching In the fast switching mode the Dingo uses Slow Switching non PWM pulse width modulation PWM at 58Hz It is recommended t
36. disconnect is an internal logical function To do something other than act as a warning it has to be used to control a load switch This can be done in three different ways It can control the Dingo s LOAD terminal or the G General Purpose Output relay or an external switchblock attached to the bus The sense of its operation can also be reversed i e it can turn on the terminal when the function decides the load should be disconnected This can then be used as a low battery alarm or to drive a relay to turn off other loads The connection to real switches is set up in the MODE menu See section 7 5 for details DO NOT CONNECT AN INVERTER OR ANOTHER BATTERY TO THE LOAD TERMINAL This terminal is rated at 20A Most inverters draw larger currents than this and have their own low battery cut off circuitry anyway In general Inverters should be connected directly to the battery 4 0 IN Menu IN The IN screen gives a running total of Amp hours Ah or energy that has been put into the battery during the day since midnight This total is the sum of Solar Ah collected directly through the Dingo and any measured external Ah input IN INT From the IN screen a long push displays INT Internal Ah IN This is the running total of Ah collected through the SOL terminal over the day since midnight A long push will clear the INT running total IN External From the INT screen a short push displays any external Ah contribu
37. e If the battery voltage falls below the boost return voltage BRTN for more than 10 minutes then the Dingo will switch back into the boost state The delay is necessary to prevent large short term loads causing unnecessary returns to Boost b Programmed boost cycles optional The Dingo will automatically do a boost cycle after set number of days regardless of battery voltage c Manual boost The user can manually set the Dingo into the boost state or any of the regulation states To manually advance to the next state do a long push on This will show the current regulator state BOST Boost EQUL lt Equalise ABSB Absorption or FLOT Float A long push on that state will manually advance into the next state Or to return to the BATV screen without changing the state do a short push 4 EMAX x Oo s 1 9 LBMAX I ABSV Fig The Battery Charge Cycle m ETIM ATIM FLTV BRTN BOOST EQUALISATION ABSORPTION FLOAT BOOST Time Rev I 5 4 02 13 Dingo 2020 Reference Manual Note if ETIM is 0 then the Equalise state will 1 3 ABSB Absorption bypassed If ATIM is 0 then the Absorption state will bs bypassed In this state the Dingo tries to keep the battery voltage constant while the last part of the battery On the BOST and FLOT displays the battery charging occurs This prevents excessive gassing voltage is shown On the E
38. elled B right most terminal of the green terminal block is intended as a sense input for the battery positive voltage This can be connected directly to the positive terminal of the battery so that the true battery voltage can be read This is important if there is significant voltage drop along the wiring including any fuse between the BAT terminal on the Dingo and the real battery positive If there is significant voltage drop on the negative side then take the BAT terminal directly to the battery negative via a fuse The fuse need only be rated for the Dingo supply current say 00mA Take the negative side of the charge current from the array to the battery separately via it s own fuse The intention is that the array current does not pass through the same wire as the Dingo negative supply current See figure 7 5 3A Rev 1 5 4 02 13 Dingo 2020 Reference Manual Fuse Breakers 7 Connect 1 close to anel s battery L terminals 7T Battery O Fuse Breakers T d S TL Sense wire Connect to Battery Positive Terminal NOTE Low Current B Sense wires can be significantly smaller than other wires If the B input is not being used for this then it I be used for sensing the voltage on a second battery being charged or for providing a voltage input for the event controller VEXT 7S 9B connection S
39. es have a number This plug and play system is selected by choosing the auto option on the external device if it is available The connection of external devices to the serial bus is done with phone cable with modular plugs These are 6P4C plugs sometimes called RJ 2 These loop through each device either using the two sockets on the device or using a double YU Fig 8 1 Example of a larger system adaptor for single socket devices 8 4 Troubleshooting If a current measuring device does not appear in the external list of devices then check the following things a If the device address selection is set to manual check that two devices are not assigned to the same address number b Check the cabling to the device If the cable has a plug on it that is the wrong way round then it will not communicate c The discovery process can take a few minutes if a new device is added while the system is running Rev 15 4 02 13 A 0 Appendices Accessories There are accessories which can enhance the usefulness of the controller External Battery Temperature Sensor DT or DTB The DT is a plastic cased unit for direct attachment to the battery case The DTB has a bolt on lug for attaching to the battery terminal either terminal The unit connects to the T and T inputs on the green plug in terminal block under the wiring cover See Section 7 4 3 for further details about this unit
40. escribed in Fi 5 No quiet time Turn on when the State dn of Charge SOC falls to ON 96 of the 2A with the screen of the same name described in battery capacity Turn off when the voltage Section 7 5 2 which sets the G terminal function rises to GOFF for GDEL minutes GEXD Generator Exercise No quiet time Turn on when SOC falls to ON96 Turn off when SOC rises to To prevent the generator from seizing up it GOFF is good practice to exercise the generator periodically The Dingo supports this with an Quiet Time M NoQuetTime GMOD 0 2 3 4 5 6 Name Description Range Slr ee Ep p spe qe Lue p oq fe fe fo Set delay before on off change SOC Current SOC 0 100 Long push to adjust e GRUN Set length of generator exercise 0 4 0 hrs View change of days since 2 60 days last exercise Active Parameter for relevant generator mode GMOD M Manual GMOD GMOD Settings GEXD Set days between generator 2 60 days exercise Dingo 2020 Reference Manual Rev 1 5 4 02 13 automatic generator exercise function which will turn on every GEXD days The number of days since the last exercise is shown on the GDAY screen The generator will run for GRUN hours When exercising the elapsed time is shown as GTIM Both GDAY and GTIM can be adjusted Note 1 There is no generator exercise when 3 manual start
41. f you set STOP to I you will see TIME Once started the event will then continue until the time reaches the time you specify in the TIME setting To allow events which go past midnight there are special rules SET EVNT STOP Selection Summary STOP Event stops when Value to set O Stopneveracive Time gt setting 0 0 23 9 TIME 2 Solar panel open circuit voltage SOLV gt setting 3 Solar panel open circuit voltage SOLV lt setting 4 External voltage VEXT VEXT gt setting External voltage VEXT VEXT setting on and time gt setting TIME PB off and time gt setting TIME Repeat stop at min intervals if TIME time gt setting Repeat stop at 3 min intervals if TIME time gt setting Repeat stop at 6 min intervals if TIME time gt setting Repeat stop at 12 min intervals TIME if time gt setting Battery voltage gt setting VBAT Battery voltage lt setting VBAT Stop after a set run time RUN 0 240min Stop after a set run time RUN 0 0 24 0h Note After up to min delay Note VEXT has the same meanings as in the STRT table Note PB has the same meanings as in the STRT table Rev 15 4 02 13 For the combinations start and stop 1 or START 1 6 11 and TMOD 8 then events can be active in a time period crossing midnight If the stop time or TMOD 8 setting is less than the start time then the controller assu
42. h a switch or a relay The Dingo provides a G relay which can be used for this purpose This relay is voltage free and solid state It can carry a current of up to 300mA and can block 85V For some generators it is possible to connect the G relay directly to the remote start input on the generator The wiring for this is shown in fig 2B Fig 2B Generator start relay wiring S B L S B L F MEE Generator Remote Start Unit Generator controlled directly by the G relay Rev 1 5 4 02 13 Dingo 2020 Reference Manual This direct connection will work if the current flowing through the remote start terminals is less than 300mA If the current is greater than this then it will be necessary to use an intermediate relay with a higher contact current rating The G relay switches the intermediate relay which in turn switches the remote start terminal The wiring for this is shown in fig 2C Chose a relay with a contact current rating suitable for remote start unit and coil voltage which is the same as the system voltage The relay coil should not draw more than 300mA when it f is energised Be careful with automotive relays because they can often be poor relays requiring mr rr ea SS large coil currents Use relays from the electronics industry which generally have lower drive power
43. hat PWM control be used unless n slow switching PWM mode the Dingo there is good reason not to as it provides a controls the battery voltage by slowly switching smoother control and faster charging the charge current on and off It turns the charge current OFF at the voltage set point for the relevant charge state and turns the charge current back ON at a slightly lower voltage PWM may generate some audio or radio frequency interference If you experience noise on electronic equipment for example AM radio you could try selecting SET MODE PWM 0 slow The gap between these two voltages is called switching only option available when PROG 4 If hysteresis and is adjustable HYST The larger this does not fix the problem it s unlikely that the hysteresis value the slower the rate of noise is generated by the Dingo switching on and off HINT Increase the Hysteresis value if using shunt control with a mechanical relay so the relay switches less often The radio frequency interference from the Dingo has been tested in PWM mode and found to be very low It is at least 5dB below the domestic limit for European CE American FCC and Australian In the slow switching mode the regulator limits EMI compliance standards the maximum switching speed to 0 25 seconds between changes This virtually eliminates any audio or radio frequency interference 7 NOTE More must taken at higher system voltage
44. in Section 2 and 3 The six internal control functions are a Low battery disconnect This also controls the LOAD indicator at the bottom of the screen b Run the backup generator This also controls the GEN indicator at the bottom of the screen c Charge a second battery Indicates when the solar input can be diverted to a 2nd battery d Battery voltage alarm output Provides an output based on the battery voltage e Shunt regulation Gives an output useful for regulation by dumping the input energy f Event controller An output which is active when a specified set of conditions occurs SET MODE Selection Summary Name Description Range d ND the LOAD switch Select the control of EN the relay external switchblocks e B sense input 0 3 I e 2nd battery control 13 0 16 0V PWM Select which terminals use PWM SOL LOAD 0 3 BCAP Amp hour capacity of the battery bank 20 20 000Ah ALRM Alarm voltage 10 0 18 0 Clears day data and time Used to reset factory default settings Rev 1 5 4 02 13 Dingo 2020 Reference Manual SET MODE LSET SET MODE GSET Low battery on when function Mr al disconnect wants to disconnect disconnect to disconnect battery ESTE Low battery off when function disconnect to disconnect battery disconnect wants to disconnect default battery control default to run generator control wants to run generator control to run generator control want
45. ing external switch blocks attached to the serial bus The DUSB D232 amp DNET interfaces allow remote monitoring and adjustment Custom Dingo 2020 Reference Manual settings can be stored on a computer and uploaded into the controller Data from the controller can be downloaded into the computer and displayed easily Overload Protection The Dingo has overcurrent protection on both the load and charge switches If the user accidently short circuits the load or the charge connections then the switch will turn off very quickly before any damage is done to the switch If the user overloads the load switch then the load switch will disconnect after a period of time to protect itself from overheating It will reconnect automatically once the switch cools If the charge input is overloaded then the controller will turn the charge switch off as required to reduce the average charge current into the Dingo For details see section A 4 Thermal Protection The Dingo has a temperature sensor on the circuit board The function of this sensor is to tell the Dingo how hot its own circuit board is so that it can reduce the charge current the major heating source in order to protect against overheating See section A 4 for details of thermal derating Menus The Dingo has a simple main menu This is described in the user guide and provides most the information required for normal use Behind each of the main menu screens
46. ingo to operate without reducing the charge current depends on five factors the ambient temperature the load current the time that it has been hot the battery voltage and the number of external devices attached to the serial bus For example it takes about hour for the Dingo internal temperature to reach equilibrium under fully loaded conditions It is difficult to construct a simple derating table because of these factors The following information is a guide to what sort of performance can be expected in a number of situations 1 20A Charge current OA Load current 12V battery No external devices The controller may operate at full current up to an ambient of 60 C 140 2 20A Charge current 20A Load current 48V battery 10 external devices The controller can operate at full current up to an ambient of 50 C 122 F If the ambient temperature is a few degrees above this it can take an hour or more from cold before the Dingo will begin to limit the charge current 3 Calculate the limit It is possible to estimate the onset of limiting from the following approximate formula Maximum ambient temperature Tmax 71 0 028 charge current 0 016 load current 2 0 004 Vbat Ne 5 Where currents are in amps temperature in oC and Ne is the number of external devices Valid for Tamb 45 609C Limiting may occur for at temperatures gt Tmax A 5 Block Diagram This Dingo Controller is de
47. into the bus are called external or EXT for short They appear in the charge load IN and OUT displays after the internal i e actually going through the Dingo readings Because the current from an external device might be in either the charge into the battery or load out of the battery direction the external devices appear in Dingo 2020 Reference Manual both the charge and load displays In the case of an external generator the charge display would show the generator current and the load display would always be zero In the case of an inverter charger the current could either be in either direction and either the load or charge will be non zero depending on direction 8 2 Controlling external switches An external switch device must be controlled by something The Dingo allows each switch to be controlled by one of these four internal functions The battery charge controller 2 Low voltage load disconnect 3 Alarm 4 Event Control If the external switch is a maximum power point tracker then it is only controlled by the charge controller The charge controller sends the MPPT the target voltage and the current battery voltage The MPPT then tries to achieve the desired target voltage Selection of control for on off switches is done in the SET MODE ESET menu see section 7 5 3 It is necessary to set the control for each external switch attached Because it is sometimes necessary for the switch to work in the
48. le if clock is GSET gt Toggle function status on off lt lt between 9pm gt 9am Quiet GMOD Set generator control mode i time unless GMOD is set to i D or 4 2 4 5 or 6 no Quiet time 1 1 or 5 1 3 1 gt Set V ISOC to start generator een G OFF gt Set SOC to stop generator GOFF GOFF m Set V to stop generator GbEL GOEL gt Set delay before on off change SOC SOC gt State of Charge SOC Long push to adjust GEXD GEXD GEXD gt Set days between generator exercises GRUN GRUN GRUN GRUN gt Set length of generator exercise GDAY GDAY GDAY View change of days since last exercise or run time GTIM if generator exercising Y 3 LOAD External 4 LSET gt Toggle low battery disconnect status on off N LOFF gt Set voltage at which load disconnects L ON gt Set voltage at which load reconnects 4 IN mm External LDEL Set delay before switching Clear Clear va 5 OUT INT External V V Clear Clear M a 6 DATA VMAX VMIN FTIM SOC TEMP SOLV HIST ws DAY 1 IN OUT VMAXVMIN gt FTIM gt SOC NEXT BACK EXIT V DAY2 DAY99 DATA 4 Toggle setting lockout set to adjust 099 0 setting DAY 2 IN OUTAVMAX VMIN gt FTIM gt SOC NEXT BACK EXIT A showing means purren settings adjustable DAY3 DAY1 DATA T T DAY 39IN OUTSVMA
49. load current used by equipment connected to the regulator s LOAD terminal External Load From the LINT screen a short push displays the load current reading from any external device attached which can measure current If the device is a maximum power point tracker MPPT then this device is Shown as MPTx where x is the device number Similarly for switchblocks the display is SWHx and for shunt adaptors SHNx The device number can be from to 4 for shunt adaptors and from to 12 for MPPT or Switchblocks To fit the display numbers greater than 0 are given letters So 10 is isb and 12 is This list also allows the user to check that the Dingo has found or discovered all the external devices attached to the bus This discovery process is automatic If a device is not on the list and should be then refer to section 8 4 for troubleshooting advice Name Description Range LOFF voltage at which load 10 0 12 5 V disconnects LON Set voltage at which load 11 0 16 0 V reconnects LDEL Set delay before 0 15 min switching on off BATV External CHRG N LOAD LSET gt Toggle low battery disconnect status on off UN d LOFF Set voltage at which OUT load disconnects M LON gt Set voltage at which DATA load reconnects Y SET LDEL gt Set delay before o switching Fig 3A LOAD Menu Low Battery Disconnect LSET LOFF LON LDEL To prevent battery d
50. ly on low battery disconnect in progress slow flash mostly off load disconnected reversed solar connection indication on the test terminal fast flash 4 Current limits amp thermal derating Current limits short circuit protection The charge input has a current limit which acts to protect the Dingo from excessive charge current and can be used to protect small batteries from excessive charge rates This is fixed at 20A for programs 0 3 and is adjustable in program 4 at the SET REG CLIM screen There is also short circuit protection If the current out from the terminal exceeds 37A then the charge switch is turned off When this disconnection occurs the boost annunciator will start flashing It can be reset by a long push in the SOLV screen The load output has a current limit This acts to protect the Dingo from overheating due to excessive load current If the load current exceeds 30A for the load disconnect delay time LDEL then the load will disconnect As well as this current limit there is load short circuit protection If the load current exceeds about 10A the load switch is turned off immediately If this occurs the LOAD annunciator will start flashing It can be reset by a long push in the LOAD LINT LSET screen Thermal derating The Dingo has an internal temperature sensor which acts to protect it from overheating The charge current is reduced to limit the internal temperature The ability of the D
51. mes that the stop time is on the next day If the stop condition is to be ignored select STOP 0 stop condition is never active NOTE an event will not start if the stop condition is active when the start condition becomes active In other words stop has priority over start Step 5 Next short pushes bring the EMOD setting and then the TMOD setting These settings can be used to set more conditions which must be true for the event to be active For example the EMOD setting could be used to ensure the light only turns on if the Dingo is in the Float state EMOD If additional conditions are not needed they can be set to zero and they will be disregarded always active SET EVNT EMOD Selection Summary EMOD EMOD is active when Always active EMOD condition is irrelevant IEEE pee is in Float mode in I Y 6 Dingo is in Float and it s Y 8 Alwaysactive N 9 DingoisinFlot mode N 10 isng IN 1 fitsday Note External D will come from a bus accessory Dingo 2020 Reference Manual For settings O to 7 the low battery disconnect LBD function will override the EMOD condition and make EMOD inactive if the load should be disconnected This makes it possible to disable an event if the battery voltage is too low Settings 8 15 are the same as 0 7 but without the LBD overide SET EVNT TMOD Selection Summary The TMOD setting provides an extra adjust
52. n voltage battery voltage at a level which maintains full EMAX and then remain at this voltage for the charge This voltage FLTV should be below the set equalisation time ETIM This equalisation is gassing voltage to avoid excessive electrolyte done every days Typically 30 60 days loss If charge is drawn from the battery the Equalisation will begin at 9am on the appropriate Dingo will allow charging to resume until the day If ETIM is 0 then equalisation will not occur battery returns to FLTV To prevent the controller being trapped in equalise mode for a long time because there is inadequate charge current to reach the equalise voltage the Dingo terminates equalise after 4 days e Dingo 2020 Reference Manual Rev 1 5 4 02 13 2 0 CHRG Menu CHRG The CHRG screen gives the real time total charging current Amps This total is the sum of solar charge current CINT and any external charge current This may be current from an external switchblock or MPPT device connected to the bus or an external current measured using a current shunt and a DSA CINT From the charge screen a long push displays CINT Charge Internal This is the real time solar charge current flowing into the SOL terminal measured in amps External Charge From the CINT screen a short push displays the current reading from any external device attached which can measure current If the device is a maximum power point tracker MPPT
53. nal Installation Notes Ensure that you have followed the installation instructions on pages 3 5 of the User Guide The Dingo can be used for system voltages up to 48V It is safe to connect the power before setting the system voltage even with a 48 volt battery Always mount the Dingo vertically with clear airflow around the bottom and top of the case In hot conditions do not put it in a sealed enclosure as this will restrict the airflow around it Do not install the Dingo in direct sunlight in hot conditions Please consult section A 4 to determine the performance that can be expected in hot conditions The Dingo is specified for up to 60 C ambient temperature At full power in high temperature ambients the LCD display may occasionally reach a high enough temperature to become darker and may become unreadable It will return to normal when it cools down DINGO Charge Controller Alarm led Button Low level High current connections Mounting holes connections plug in terminal block Serial bus Test port terminal Cable tie posts Rev 15 4 02 13 Features The Dingo series of solar controllers is exceptionally versatile They give the user unparalleled capability to adjust the function of the controller and to monitor the performance of the energy system To cater for non technical users the Dingo has four preset programs which can be used without needing
54. ng STRT and STOP irrelevant The STRT Y Whether event is on E ON or off EOFF condition will always be on and the STOP condition will never happen In practice the EMOD condition will determine whether the event is on or off Because it is set to 2 it will be on at night If a light is wired to the LOAD terminal and LSET 4 then the light will turn on at night The light would also turn off if the battery voltage drops low enough for the LBD function to operate 2 Pushing a button turns a light on at night for 10 minutes STRT TIME STOP RUN EMOD TMOD e lo jn jo o If a momentary ON push button is wired up between B F sense and BAT the STRT condition will turn on with the push button input the time will always be greater than O It will stop after 10 minutes due to the STOP and RUN settings EMOD 2 makes sure that this will only happen at night during the day pressing the push button will have no effect Note The user also needs to set BSET 2 amp LSET or GSET 4 3 Pump water if battery is fully charged until tank is full i e switch in tank turns off TRT_ STOP TIME EMOD TMOD 5 jo jo The STRT condition is always true The STOP condition becomes true when a float switch in the tank wired between the Dingo s and B sense terminals switches off open i e the tank is full To add the fully charged condition EMOD is set to This requires the controlle
55. night and can be used for night lighting It will turn off when the battery is low Low Battery Disconnect PROG 3 Use with sealed gel lead acid batteries The LOAD terminal is set for night lighting with low battery disconnect PROG 4 Enables customised adjustment of all settings Installation instructions for programs 0 3 are on pages 8 9 of the User Guide Dingo 2020 Reference Manual Rev 1 5 4 02 13 Settings Used in Programs 0 3 When programs 0 3 are selected the Dingo automatically uses the values below in its regulation These are not visible on the screen and are not adjustable by the user For adjustable settings choose program 4 The voltage settings are shown correct for 12V operation For higher voltages scale these up eg for a 24V system multiply each voltage figure by 2 ojij 2 11 5 13 8 CHRG Parameter GMOD G ON V GOFF V GDEL Min GEXD Day GRUN Hr w e 3 o LOAD Parameter LOFF V L ON V LDEL Min Setting for program n 12 8 LOAD Parameter Bor o _ LDEL Min SET REG Parameter Setting for program number o ETIM Hr EFRQ day ABSV V ATIM Hr HYST V BRTN V CLIM A Day TCMP 3 ec Parameter 0 2 3 user er jalas ESET see below seebelow O O 2 j 2 SET MODE Default Settings ESET see section 7
56. ome inverter chargers such as the SP PRO can communicate to the charge controller when they want to export power to the grid Selecting BSET 3 enables this Push Button Switch Input To use the B sense input as a switch event input wire a switch or other voltage free contact closure device between the B terminal O S B L S B L green terminal block and the Bat terminal and set BSET 2 See Figure 7 5 3B 9 This is an example of using push button switch to turn on a light see section 7 6 Event controller example 2 for setting details SET MODE BSET Selection Summary Ap EL input used for battery positive voltage sensing 2nd battery voltage sensing F external input VEXT used by event controller Light 3 force equalise when connected to BAT Push Button o Dingo 2020 Reference Manual Rev 1 5 4 02 13 2nd Solar Solar Battery 2 Secondary Battery 1 Primary E Solar Array B sense input Relay shown in non energised state 7 5 4 BAT2 Second battery control On many afternoons there is power available from the solar panels but it is wasted because the batteries are already full by then This power could be used to charge a second or reserve battery
57. r to be in the 15 4 02 13 float condition i e almost fully charged before the EMOD condition will become active When the Dingo enters Float state EMOD will become active and as STRT is always true and TMOD is always true the pumping will start if the tank is not full Note BSET 2 LSET or GSET 4 4 Water garden for 5 minutes every 100 min from 2pm until nightfall STRT RATE STOP RUN EMOD TMOD TIME 4 14 5 s 7 140 The STRT condition is true every 100 minutes i e repeated start at 100 minute intervals The STOP condition causes the event to run for only 5 minutes after each event start This cycle will continue while it is daytime EMOD 3 and itis after 2pm TMOD 7 TIME 14 0 Note LSET or GSET 4 and BSET 0 8 0 Setting up a Larger System The Dingo can become a controller for a larger system By adding switching stages larger charge and load currents can be controlled Up to 12 external switch devices can be controlled These attach to the serial communication port This is a balanced 2 wire RS485 bus running a communication protocol compatible with Modbus systems As well up to 4 external current sensors can be added to allow measurements from other charge sources or loads to be included in the total system measurements This might be a backup generator or an inverter 8 1 Reading External information The charge or load currents from devices plugged
58. s particularly 48V because the inductance of the wiring to the photovoltaic panels can Dingo 2020 Reference Manual Rev 1 5 4 02 13 7 5 7 BCAP BCAP setting tells the Dingo the effective Amp hour capacity of the battery being charged This is used by the State of Charge data screen Long push on BCAP to set this value Set the battery capacity actually expected as discussed in Section 6 4 SOC BCAP s range is 20Ah 20 000Ah Short pushes will increment BCAP by 20Ah until it reaches 1000 Ah At this point the increment increases to and the display changes to thousands i e 1000 is displayed as 1 0 and 1100 as 1 1 When the display reaches 20 000Ah shown as 20 0 it will cycle back to 20Ah shown as 20 It s important to notice the difference If it is intended to set 20 000Ah be careful not to set 20 Ah instead The two appear one after the other on the Dingo display during setting The only visible difference is the decimal point to show 20 000 Ah 7 5 7 ALRM Long push here to set the alarm voltage If the battery voltage falls below the alarm voltage the Dingo will activate its internal Alarm function This will cause the alarm led to light see A 5 If the LSET GSET settings have been configured appropriately this can be used to enable an Example Battery Low Alarm Output BOOST Resistor R1 X Red LED Indicator Fig 7 5 7A
59. s 0 3 prisoner on 18 Settings for Program ttn un e 18 7 4 REG menu Customising Regulation Settings 19 7 4 1 HYST Hysteresis EFI Rat 19 7 4 2 Charge Current Limit 20 7 4 3 TCMP Temperature compensation 20 Connecting a Temperature Sensor 21 7 5 MODE Menu Adjusting Configuration Settings 22 7 5 1 LSET amp GSET Controlling the load outputs 22 7 5 2 ESET Controlling external switches esses 24 7 5 3 BSET Configuring B Sense Input uscire bte etn 24 7 5 4 BAT2 Second battery control 26 7 5 5 PWM and Slow Switching 27 7 5 6 BCAP Setting battery Capacity enirn 28 7 5 7 ALRM Setting alarm point 28 7 5 8 RSET 8 Reseting and setting factory defaults 28 7 6 EVNT Menu Using the Event Controller 29 32 8 0 Setting up a larger system ecce eee eee eene eee 33 AO sp ra T 35 Accessories
60. s are met The numeric figure shows the state of each of these conditions The first digit shows the status of the STRT and STOP conditions If the event is off EOFF the first digit shows the state of the STRT condition 0 inactive active If the event is on E ON the first digit shows the state of the STOP condition In the example above this figure will be 0 during the day i e STRT condition is inactive then at dusk when the solar panel voltage drops to the pre set SOLV value If the battery was fully charged the event will start the display will change to ON and the first digit will flick back to 0 to show that the STOP condition is inactive If the battery was not fully charged the event will not start the display will stay on EOFF and the first digit will remain on until either the Dingo enters the Float state when the event will start or comes when it will flick to 0 until next evening The second digit shows the state of the EMOD condition In the example above this digit will be when the battery is in the Float state and 0 if it is in the Boost Equalise or Absorption states The third digit shows the state of the TMOD condition In the example above TMOD was not used and this digit will always be Examples To turn a light on all night STRT STOP EMOD TMOD o jo The first two conditions have the effect of maki
61. s to run generator 2nd battery on when battery 2 charge control should charge charge control should charge T charge control should charge alarm setting ol voltage alarm setting alarm setting Shunt control off when function wants to disconnect shunt load ON for regulation Alarm output off when battery voltage alarm setting Shunt control off when function Must be selected wants to disconnect for PWM control the shunt load of the LOAD ON for regulation terminal Shunt control on when function wants to disconnect shunt load OFF for regulation Note PWM is not available Terminal Shunt control on when function PWM must not wants to disconnect be set to 2 or 3 shunt load OFF for regulation Don t use LSET with PWM as design does not allow inversion of PWM signal The LSET setting allows the user to choose If LSET is set to 9 then the load switch would which function controls the electronic switch turn when the battery voltage goes below the connected to the LOAD terminal The user can ALRM setting This could be used to turn off a also select whether that switch is on or off when load to reduce the drain the battery the function is active i e select normally open or normally closed 7 For example if LSET is set to 8 then the load The GSET setting allows the user to choose switch would turn
62. s with STOP gt Set second condition for Event TMOD gt gt Set third condition for Event Setting gt Set value which goes with TMOD L EOFF EON View current state of Event Controller Revl 5 4 0213 Dingo 2020 Reference Manual SYSTEM SETTINGS Bue Regulator Model Customer Serial No Phone Battery Type E mail Battery Capacity Address No of Solar panels Wattage of panels State PostCode Total solar input watts Other Comments CHRG menu settings CHRG gt CINT gt CEXT LOAD menu settings GSET GMOD gt LOAD LEXT CON lt b Y GOFF gt Y LSET 3 GDEL gt LOFF gt SOC gt Y LDEL CRUN Y GDAY SET TIME VOLT gt PROG MODE EVNT Y Y Y m gt Getting gt ETIM gt STOP gt EERO gt Setting gt SET menu settings eee gt Mob gt gt gt EY gt Setting gt ner gt BRTN oi ESET Values Temperature Sensor fitted one gt 2 4 5 7 8 9 A b Ys gt Dingo 2020 Reference Manual Rev 1 5 4 02 13 History Data The following is the first 30 days of data stored each day in the history section of the DATA menu Comments yesterday
63. signed for common negative installations i e solar and load circuits are switched on the positive side It has a reverse blocking mosfet switch between the SOL terminal and the BAT terminal and mosfet switch between the LOAD terminal and the BAT terminal There is also an optically isolated low current bi directional mosfet switch between the G terminals Rev 1 5 4 02 13 Dingo 2020 Reference Manual 27 gt lt lt lt lt c c 1 eet 2 07 55 09 J rere 5 0 lt 8 lt 7 7 amp Block diagram and terminal layout I TEMPERATURE BAT SENSOR T T MICRO BATTERY SENSE B SENSE LOAD CONTROLLER SERIAL PORT PUSH BUTTON G RELAY REVERSE SOLAR BATTERY LOAD Dingo 2020 Reference Manual Rev 1 5 4 02 13 A 6 Mechanical Information Material Case Heatsink Weight in box Dimensions Width Heigth Depth Mounting hole spacing Mounting hole size 121mm 4 8 Polycarbonate Anodised Aluminium 482g IIb 137mm 5 4 121mm 4 8 45mm 1 8 116mm 4 67 5mm 3 16 Legal Statement The guarantee on this device extends to units operated within the limits described in the specification table Our liability under the guarantee is limited by the following conditions Limitations We reserve the
64. st be entered by the installer at the BCAP setting before SOC will be meaningful Ah balance counter BCAP SOC x 100 Over time a pure amp hour balance counter will drift out of line with the real battery state of charge To keep the counter better aligned with reality the Dingo automatically makes a number of corrections 1 When the controller state changes from boost to absorption SOC is set to 90 if it is lt 90 When the controller state changes from absorption to float SOC is set to 100 2 Charge current is corrected for loss due to gassing gt VMAX gt VMIN gt SOC TEMP SOLV HIST based on the battery Y voltage CHRG Y 3 Acorrection for self LOAD setting lockout discharge is made Y 099 selling ps ou daily at midnight IN showing means setting adjustable This is temperature OUT corrected D AT A 4 A slow correction i is applied where SET Fig 6A The DATA Menu Structure the SOC inferred Rev I 5 4 02 13 Dingo 2020 Reference Manual from the battery open circuit voltage can be Setting Lockout determined A temperature sensor must be attached for this correction to work accurately In some cases it is desirable to restrict the ability to adjust settings so as to prevent unwanted If you use a temperature sensor you will get a tampering more accurate SOC estimate To disable settings long push on the TEMP A long push on the SOC screen will allow the s
65. te of charge of the battery based on the amp hours in and the amp hours out A very rough fuel gauge see below for further details TEMP temperature being sensed by the external temperature sensor if attached SOLV _ solar panel voltage open circuit 5 HIST entry point for history data At midnight VMAX VMIN FTIM SOC IN and OUT are stored in the history data and cleared from the current day readings 6 1 amp 6 2 VMAX and VMIN VMAX and VMIN respond very slowly to changes in battery voltage This allows them to ignore short term voltage fluctuations A long push will reset the value to the current battery voltage 6 3 FTIM Float time Display FTIM indicates the time of day that the regulator changed from the ABSB Absorption state to the FLOT Float state This time will only be recorded if the regulator has done a transition into float that day A time will not be recorded if the controller did not reach the float state or stayed in float all day No float time displays as 6 4 SOC State of Charge Display SOC State Of Charge should be read as a percentage estimate of how full the battery is This estimate is based on the amp hour balance counter The counter keeps a running balance of amp hours in vs amp hours out The SOC display shows this balance as a percentage of the battery size Note that all system currents must be monitored by the regulator and the battery capacity mu
66. then this device is shown as MPTx where x is the device number Similarly for switchblocks the display is SWHx and for shunt adaptors SHNx The device number can be from to 4 for shunt adaptors and from to 12 for MPPT or Switchblocks To fit the display numbers greater than 0 are given letters So 10 is isb and I2 is This list also allows the user to check that the Dingo has found or discovered all the external devices attached to the bus This discovery process is automatic If a device is not on the list and should be then refer to section 8 4 for troubleshooting advice Generator Control The Dingo has a comprehensive generator controller built in It works in a similar way to the Low Battery Disconnect function It is designed to give a run or stop signal to an electronic start generator It does not handle the actual generator start up sequence this should be done by the generator itself Ir External Fig 2A Generator Control Menus PROG 4 only Y eu N LOAD M gt Toggle function status on off Set generator control mode ores DATA ora SET G G G ON GOFF ds n GDEL GDEL soc SEN GEXD GEXD GEXD GRUN GRUN GRUN GDAY Set Voltage SOC to start generator mp Set SOC to stop generator gt Set Voltage to stop generator gt Set delay before on off change State Of Charge SOC Long push to adjust
67. ting Solar panel voltage SOLV open circuit lt setting External voltage VEXT VEXT gt setting External voltage VEXT lt setting 6 PB is on and time gt setting TIME PB is off and time gt setting TIME VEXT Repeat start at 10 min intervals TIME if time gt setting Repeat start at 30 min intervals TIME if time gt setting Repeat start at Ihr intervals if TIME time gt setting Repeat start at 2hr intervals if TIME time gt setting Battery voltage gt setting VBAT Battery voltage lt setting VBAT 14 Repeat start at a set rate RATE 0 240 min 15 Repeat start at a set rate RATE 0 0 24 0h Note After up to min delay if the solar charge switch has not turned off Note The user can select where VEXT is measured If BSET is set to 2 then VEXT is the voltage measured by the B sense input relative to BAT the negative direction The maximum VEXT measurable this way is 27V If BSET is not 2 then VEXT can be measured by a bus accessory Note PB means a push button switch If you wish to use this option you can wire a switch or other contact closure device between the B sense terminal green terminal block and the BAT terminal and select BSET 2 Step 4 Select a STOP setting in this table to tell the Dingo what signifies the end of the event After setting the STOP value a short push will move you to the associated setting For example i
68. tions This is the running total of each external Ah input from MPPT Switchblock or current shunt measurements A long push will clear a total Dingo 2020 Reference Manual BATV Fig 4A IN Menu CHRG pipi don IN External OUT 4 Clear Clear zi m SET 5 0 OUT Menu OUT The OUT screen gives a running total of Amp hours Ah or energy that has been used during the day since midnight This total is the sum of Ah used by equipment connected to the LOAD terminal and any external devices OUT INT From the OUT screen a long push displays INT Internal Ah OUT This is the running total of Ah used by equipment connected to the regulator s LOAD terminal A long push will clear this total OUT External From the INT screen a short push displays any external load Ah Long push to clear Note the net battery Ah is the IN Ah OUT Ah The IN and OUT Ah counters are reset each day at midnight EM C jn LOAD Y IN Fig 5A OUT Menu E Clear Clear SET Dingo 2020 Reference Manual Rev 1 5 4 02 13 6 0 DATA Menu Retrieving Performance Data A long push on DATA enters the data menu This displays performance information for the current day The screens in the DATA menu have the following meanings maximum battery voltage since midnight VMIN minimum battery voltage since midnight SOC FTIM time of day the regulator entered the Float state estimated sta
69. to understand the details of its operation For those with a good understanding of solar regulation there is another program which allows all the settings to be adjusted if required Once the program has been selected it is possible to disable any further adjustment This prevents unauthorised adjustment of settings Although the Dingo is primarily a device to control the charging of batteries from solar electric photovoltaic panels it can also be used with other energy sources such as wind microhydro and fuel driven generators The Dingo supports a variety of regulation methods It supports slow speed switching and fixed frequency pulse width modulation PWM control in series and shunt modes Low battery voltage load disconnection is provided as are an alarm facility to control the charging of a second battery bank and control for a back up generator The event controller can be used to control lights pumping waste energy use and other timer functions A temperature sensor can be added to correct the regulation voltages for battery temperature There is an input for measuring external voltages A serial interface is provided for accessories including extra switch blocks remote current sensors and communication with a computer modem Using an external current shunt attached to a remote current sensor DSA allows the controller to see other current flows in the system The Dingo can control larger systems by add
70. y temperature sensor reading if attached or if it s not It is also used to adjust Setting Lockout see figure 6 66 95 Dingo 2020 Reference Manual Rev 1 5 4 02 13 These records are available for the past 99 days on the screen of the controller The controller actually keeps records for over one year but for practical reasons these can only be accessed via the computer interface The records are not lost if the power is disconnected At the start of each day record is the DAY screen This shows which day s data you are looking at DAY yesterday DAY 2 the day before yesterday etc For help with navigating through the History refer to Fig 6B Fig 6B The History Menu A long push on each of the screens except EXIT will move down to the next day or the next day s value Short pushes move between figures for the same day NEXT goes to the next day BACK goes to the previous day The day numbers wrap around when they reach the end A short push on the EXIT screen will take you back to the beginning of that day s record A long push will exit back to the DATA screen BATV Thin arrow short push CHRG Thick arrow long push Y e VMAX gt VMIN gt gt SOC gt TEMP gt SOLV gt HIST IN OUT Long push Toggle setting lockout Y to adjust showing means DATA settings adjustable SET DAY 1 IN OUT gt VMAX gt VMIN gt FTIM gt SOC gt NEXT gt BACK gt E
Download Pdf Manuals
Related Search
Related Contents
OWL-PC617 シリーズ取扱説明書 PHB-200 User Manual Excalibur electronic Docker 976 User's Manual La Première Nation de Campbell River Archer Field PC® Pricing Intel D915PLWDL Full report - ECE - Cornell University Aastra 9316CW User's Manual Copyright © All rights reserved.
Failed to retrieve file