Instruction Sheet 1042-563A
Contents
1. 4 1042 563A 10 23 03 S amp C Electric Company EnergyLine 5801 SC IntelliTEAM Gateway Automation Systems Division for Telegyr 8979 Protocol Introduction This document describes the S amp C Electric Company EnergyLine Model 5801 SC IntelliTEAM Gateway for Landis amp Gyr Telegyr 8979 protocol The gateway lets a SCADA master station that uses Telegyr 8979 protocol communicate with a team of Switch Controls that use DNP protocol The gateway maintains a database with information about each Switch Control and about team related parameters and it updates the records at regular intervals The master station can control or receive information about each team member via the gateway It can also receive information about the overall team status When the gateway receives a request for information it responds with the data in its database The information for a single Switch Control and for the team database are collected independently At any given moment the entries may not be synchronized When the gateway receives an operate command for another remote Switch Control it accepts or rejects the packet based on the information in its database It then creates a matching DNP packet to pass along The gateway has two communications ports Port A for Telegyr 8979 protocol and Port B for DNP protocol Each port can be connected to a variety of communications hardware such as a radio modem or fiber optic transceiver They can also be
2. This is the amount of time that the gateway monitors control operation requests to remote Switch Controls During this period if the gateway receives a response from the remote Switch Control indicating success monitoring of the request ends If the gateway receives a response indicating a failure or no response at all it generates an exception report for SBO Failure Scan Delay After Control Operation sec The gateway normally updates its database of status and analog points in other team members at regular intervals typically rotating among them every 60 seconds Special updates are forced from a particular RTU after a control request has been issued to that RTU This provides faster feedback after a control request This setpoint determines the delay between a scheduled control request and a subsequent scheduled database update If this value is too small the feedback may come before the status has actually changed as a result of the control operation You can usually leave this at the factory default value CB 10425638A 10 23 03 S amp C Electric Company EnergyLine 5801 SC IntelliTEAM Gateway Automation Systems Division for Telegyr 8979 Protocol View the Third SETUP Communications Screen The third SETUP Communications screen Figure 2 contains communications related setpoints for Port B the port using DNP protocol zioz Q Fie Connection Data Window Help la xi Setup Trouble Overcurrent Data Menu Operation s
3. Ifa Select is received without errors and an Operate follows it without errors a control operation is executed for the selected point The point also operates if an Immediate Execute is received correctly If the selected point is for the local Switch Control the operation occurs as if it were a stand alone Switch Control A response is immediately generated for the Operate command If a problem is then seen during the operation exception reports are generated see Table 4 and included with the next response Function Not Allowed The switch is not ready and Failure Override is not set Invalid Parameter The timer count is zero or the Trip Close bit is set to Trip when only Close is valid Table 4 Errors During Local Control Point Operation Remote Control Point Operation Process Ifa Select is received without errors and an Operate follows it without errors a control operation is executed for the selected point The point also operates if an Bo 404 9 563A 10 23 03 S amp C Electric Company EnergyLine 5801 SC IntelliTEAM Gateway Automation Systems Division for Telegyr 8979 Protocol Immediate Execute is received correctly If the selected point is for one of the remote Switch Controls the operation is slightly different than for a stand alone Control A response is immediately generated for the Operate command problems are again checked during the operation but then the gateway monitors t
4. 1042 563A 10 23 03 85 EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division Analog Point Definition 112 Device average 3 phase current Position B This is the average 3 phase current for Device 1 on team Position B 113 Device 2 average 3 phase current Position B As above Device 2 114 Device 3 average 3 phase current Position B As above Device 3 115 Device 4 average 3 phase current Position B As above Device 4 116 Device 5 average 3 phase current Position B As above Device 5 117 Device 6 average 3 phase current Position B As above Device 6 118 Device 7 average 3 phase current Position B As above Device 7 Pulse Accumulator Points Pulse Definition Accumulator Point 0 Dev1 Operation Counter This is the number of switch operations The 1 Dev2 counter is incremented on each Close operation This is a 16 bit 2 Dev3 counter and will overflow back to zero On a pad mount dual 3 Dev4 switch this point refers to switch 1 4 Dev5 5 Dev6 6 Dev7 7 Sidelinel Operation Counter This is the number of switch operations The 8 Sideline2 counter is incremented on each Close operation This is a 16 bit 9 Sideline3 counter and will overflow back to zero On a pad mount dual 10 Sideline4 switch this point refers to switch 1 11 Sideline5 12 Sideline6 13 Sideline7 14 Devl Operation Counter This is the number of
5. 04 02 16 25 SnapShot Figure 6 First SETUP Control Points List Clear Entire Map Use this parameter to clear the entire point map if the team you are configuring is significantly different from the default team provided The default is a full point map for a team of seven S amp C ScadaMate switches NOTE This action will immediately clear all configured point mapping from the control points table status and analog point tables will not be affected Device Num This column contains the number of the device for which that control point is associated The device numbers for each team member are found on the SETUP Team Configuration screen page 1 normal team members and page 2 sideline team members NOTE Associating Telegyr points with the correct device number for the intended field device is critical to correct operation between the Switch Control team and your SCADA communications system Control Point This column contains the control points you may configure with each team device Each point is defined below Where points may apply to more than one switch position if the team device is an overhead switch only the Switch 1 point applies 1042 563A 10 23 03 S amp C Electric Company EnergyLine 5801 SC IntelliTEAM Gateway Automation Systems Division for Telegyr 8979 Protocol Point Not Configured You should use this selection for point numbers that will not be defined in the finished points list Note that
6. C Pad mount Switch Control The bit is set if the switch has detected an overcurrent fault Switch 1 Sectionalizer Tripped Switch 2 Sectionalizer Tripped These bits are set if the associated switch has been opened due to any automatic control function The bits are cleared when the switch is closed for any reason Fault Interrupter Tripped Vista This bit applies only to S amp C Vista team members If the switchgear is equipped with fault interrupting positions this bit is set if one or more of the fault interrupting positions have tripped open due to a fault This bit remains set until the fault interrupting position has been manually closed Maintenance Required This bit is set when some form of maintenance other than battery replacement is required Switch 1 Open Close Switch Position Sensor Failure Switch 2 Open Close Switch Position Sensor Failure These bits are set if the contacts of the associated switch are either both closed or both open Control Power Failure This bit is set if AC power is not available to the battery charger It indicates that the Switch Control is operating on battery backup VO 1042 563A 10 23 03 S amp C Electric Company EnergyLine 5801 SC IntelliTEAM Gateway Automation Systems Division for Telegyr 8979 Protocol Operator Failure Override Set This bit is set after the operator has executed the Failure Override Close command to let the switch be operated even if the batt
7. Dev4 129 Dev5 155 Dev6 181 Dev7 The following status points are team summaries 182 Team operational The team is operational no communications error alarms or special conditions are present 183 Team ready to transfer The team is ready to perform an automatic transfer This indicates that the team is presently in its normal state any Return to Normal is complete 1042 563A 10 23 03ti i lt CO 8 EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division Status Point Definition 184 Transfer event taking place The team is presently in a reconfiguration mode responding to a fault or voltage loss 185 Return to Normal event taking place The team is presently in the process of returning to its normal configuration 186 Alarm s present There are active alarms in the team 187 Special conditions This point indicates special operating conditions for the team 188 Synchronization OK The team is synchronized If this bit is not set the database update sequence packets are out of sync between the Switch Controls and an error condition occurs 189 Communication errors There are communication errors between the gateway and one or more team members 190 Device not in use This bit is set when the slot for Device is not in use Any team with fewer than 7 members will have one or more available slots 191 Device 2 not in use As above
8. These point numbers will continue to be returned in a complete scan of the points list but will always indicate a zero value Note that the points list does not need to be contiguous You may leave undefined points at any location within your points list Switch 1 2 3 Ground Current This is the vector sum of the phase currents on Phases A B and C of the associated switch Switch 1 2 3 Phase A B C Current These are the currents measured on each phase of the associated switch reported in units of 1 count equal 1 ampere Switch 1 2 Phase A B C Voltage These are the voltages measured on each phase of the associated switch reported in units of 1 sensor count equals 0 1 VAC RMS Switch 1 2 Phase A B C Phase Angle These are the phase angles measured on each phase of the associated switch reported in units of 1 count equals one eighth of a degree with an offset of 90 degrees Switch 1 2 Phase A B C kKVARs These are the KVARs measured on each phase of the associated switch reported in units of 1 count equals 8 kVARs a value of zero corresponds to 16376 kVARs leading Cabinet Temperature This is the most recent cabinet temperature reading This value is in units of degrees F with a 50 degree offset Battery Voltage The battery voltage is updated only during battery testing if AC power is on If AC power is off this value is continuously updated One count equals 0 035 VDC V
9. To arrange access to the Information Center and obtain your password please contact an S amp C Electric Company Customer Service representative at 510 864 6850 or info energyline com 2 1042 563A 10 23 03 S amp C Electric Company EnergyLine 5801 SC IntelliTEAM Gateway Automation Systems Division for Telegyr 8979 Protocol Contents Introduction 5 Applicable Software 5 Manual Conventions 6 Cautions 6 Gateway Setup Screens 7 View the Second SETUP Communications Screen 7 View the Third SETUP Communications Screen 9 View the Fourth SETUP Communications Screen 11 Telegyr Points Setup Screens 14 View the SETUP Status Points Screen 14 View the SETUP Analog Points Screen 18 View the SETUP Control Points Screen 19 Gateway Troubleshooting Screen 22 Telegyr 8979 Points List Factory Default 24 Status Points 24 Analog Input Points 33 Pulse Accumulator Points 36 Control Points 37 Telegyr 8979 Protocol Functions Implemented 39 Telegyr 8979 Implementation 42 Status and Analog Points 42 Control Points 42 Errors During Select Function 42 Errors During Operate Function 43 Errors During Immediate Execute 43 Local Control Point Operation Process 44 Remote Control Point Operation Process 44 Remote Local 45 1042 563A 10 23 03 3 EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division Notes
10. for Device 2 192 Device 3 not in use As above for Device 3 193 Device 4 not in use As above for Device 4 194 Device 5 not in use As above for Device 5 195 Device 6 not in use As above for Device 6 196 Device 7 not in use As above for Device 7 197 Device 1 in Team mode This bit is set when Device 1 is operating as part of the team 198 Device 2 in Team mode As above for Device 2 199 Device 3 in Team mode As above for Device 3 200 Device 4 in Team mode As above for Device 4 201 Device 5 in Team mode As above for Device 5 202 Device 6 in Team mode As above for Device 6 203 Device 7 in Team mode As above for Device 7 204 Device 1 in Manual mode This bit is set when automatic operation in Device 1 is disabled This causes the team to be inoperable 205 Device 2 in Manual mode As above for Device 2 206 Device 3 in Manual mode As above for Device 3 0 11042563A 10 23 03 S amp C Electric Company EnergyLine 5801 SC IntelliTEAM Gateway Automation Systems Division for Telegyr 8979 Protocol Status Point Definition 207 Device 4 in Manual mode As above for Device 4 208 Device 5 in Manual mode As above for Device 5 209 Device 6 in Manual mode As above for Device 6 210 Device 7 in Manual mode As above for Device 7 211 Device 1 switch status This bit is set when the switch connected to Device 1 is closed O
11. least the programmed period of time Switch 1 2 Phase A B C Reverse Current These bits are set if the current on the indicated phase of the associated switch is flowing in the direction opposite to the normal direction configured in the Switch Control 1042 563A 10 23 03sss lt i s A EnergyLine 5801 SC IntelliTEAM Gateway for Telegyr 8979 Protocol S amp C Electric Company Automation Systems Division View the SETUP Analog Points Screen This screen contains analog points that may be configured for the team 18 Eitnergytine Intelil INK tm IntelliTEAM R Gateway IntelliTEAM 4Comm Setup aloj x l l x Setup Trouble Overcurrent Data Telegyr Menu puana shooting Fault Logging Points SETUP Analog Points List Page 1 of 7 Clear Entire Map 0 Device 1 Switch 1 Ground Current 1 Device 1 Switch 1 Phase A Current 2 Device 1 Switch 1 Phase B Current Device 1 Switch 1 Phase C Current Device 1 Switch 1 Phase A Voltage Device 1 Device 1 Switch 1 Phase B Switch 1 Phase C Voltage Voltage 3 4 5 6 7 8 Device 1 Device 1 Device 1 Switch 1 Phase A Switch 1 Phase B Switch 1 Phase C Phase Angle Phase Angle Device 1 Switch 1 Phase A KVARs Device 1 Switch 1 Phase B KVARs Device 1 Switch 1 Phase C KVARs Cabinet Temperature Battery Voltage Switch 1 Ground Current Device 1 Dev
12. setup strings are provided for the listed modems see Setup String below After changing this setpoint press lt F1 gt to exit editing mode and view the default setup string Setup String This is the string of commands sent to initialize the modem before communication begins In general you can leave the setup string at the factory default value for each factory supported modem see Modem above You can also enter a new value if needed To return to the default setup string change the Modem parameter back to the desired modem Then press lt F1 gt to exit editing mode and view the default string Reinitialize Modem If you change the Setup String setpoint set this field to Init to reinitialize the modem You must also initialize the modem the first time you enable the Call Home feature Pulse or Tone Dialing This setpoint selects pulse or tone dialing at the Switch Control s modem Set it to the value required by your telephone service provider Phone Number This is a list of up to 10 phone numbers that the Switch Control dials when attempting to contact the master station You may enter any number along with any Hayes compatible dialing commands Examples of dialing commands are to pause 2 seconds during dialing to wait for silence and W to wait for a second dial tone You can add or delete numbers as needed The numbers do not need to be consecutive in the list Nu
13. the gateway is in Local mode you cannot operate the control points in the gateway via SCADA However you can still operate the control points for other team members Similarly even if the gateway is in Remote mode you cannot operate remote Switch Controls that are in Local mode 1042 563A 10 23 03 45
14. AL position operation of the switch from the SCADA 108 Dev5 master station is blocked 134 Dev6 160 Dev7 5 Dev1 Overcurrent fault detected This bit is set if the Switch Control 31 Dev2 detects an overcurrent condition For a normally closed switch the 57 Dev3 bit is cleared when all of the following are true eo Dera e Three phase line voltage has been sensed 109 Dev5 135 Dev6 e The switch is closed 161 Dev7 e Forty five minutes have elapsed or someone toggles the faceplate REMOTE LOCAL switch or clears the bit via SCADA For the normally open switch you can toggle the REMOTE LOCAL switch or send a SCADA command to clear the bit while the line switch is open or closed NOTE If you reinitialize the Switch Control using the Setup software the bit is cleared whether or not the conditions above are met 1042 563A 10 23 03 ss 25 EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division Status Point Definition 6 Devl Sectionalizer tripped This bit is set if any automatic control 32 Dev2 function has opened the switch The bit is cleared when the switch 58 Dev3 is closed for any reason 84 Dev4 NOTE If you reinitialize the Switch Control using the Setup 110 Dev5 software the bit is cleared whether or not the switch has closed 136 Dev6 162 Dev7 7 Devl Battery Trouble Summary This bit is identical to status poi
15. EnergyLine 5801 SC Intelli TEAM Gateway for Telegyr 8979 Protocol Supplement October 23 2003 S amp C Electric Company Automation Systems Division 1042 563A 10 23 03 EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division Proprietary Notice This document contains information which is proprietary to S amp C Electric Company and is provided under the terms and conditions of a Purchase Order Terms and Conditions Agreement between S amp C Electric Company and each of its customers Disclosure of information contained in this document to third parties without prior written permission from S amp C Electric Company is strictly forbidden Information in this document is subject to change without notice and does not represent a commitment on the part of the vendor Copyright 2003 S amp C Electric Company All Rights Reserved Printed in the USA The EnergyLine logo and IntelliTEAM are registered trademarks of S amp C Electric Company Hayes is a trademark of Hayes Microcomputer Products Inc UtiliNet is a registered trademark of Schlumberger Inc All other trademarks are the property of their respective holders S amp C Electric Company 1135 Atlantic Avenue Alameda CA 94501 USA Tel 510 864 6850 FAX 510 864 6860 EnergyLine Website The latest document revision has been posted online at the EnergyLine Information Center accessed at www energyline com
16. Intelli EAM Gateway Automation Systems Division for Telegyr 8979 Protocol Analog Point Definition 11 Devl Single phase kVARs measured on Phase B As above for Phase B 26 Dev2 41 Dev3 56 Dev4 71 Dev5 86 Dev6 101 Dev7 12 Devl Single phase kVARs measured on Phase C As above for Phase C 27 Dev2 42 Dev3 57 Dev4 72 Dev5 87 Dev6 102 Dev7 13 Devl The most recent cabinet temperature reading This value is in units 28 Dev2 of F with a 50 degree offset a value of zero corresponds to 43 Dev3 50 F 58 Dev4 73 Dev5 88 Dev6 103 Dev7 14 Devl Battery voltage nominally 24 VDC If AC power is on this value 29 Dev2 is updated only during battery testing If AC power is off this 44 Dev3 value is continuously updated One count equals 0 035 VDC 59 Dev4 74 Dev5 89 Dev6 104 Dev7 The following Analog points are team summaries 105 Device average 3 phase current This is the average 3 phase current for Device 1 On a pad mount dual switch this point refers to load seen on team Position A 106 Device 2 average 3 phase current As above for Device 2 107 Device 3 average 3 phase current As above for Device 3 108 Device 4 average 3 phase current As above for Device 4 109 Device 5 average 3 phase current As above for Device 5 110 Device 6 average 3 phase current As above for Device 6 111 Device 7 average 3 phase current As above for Device 7
17. N You can usually leave this at the factory default value Data Link Layer Confirmations When this field is set to Enabled a data link layer function of 1 suppresses losses and duplicate messages to a Switch Control receiving requests This function only affects messages that originated from a Switch Control not responses You can generally leave this field enabled Output Block Point Select Timeout This is the timeout duration of the Select function on control points See Appendix A If the timeout duration is too short between the Select and the Operate functions during a Select Before Operate sequence the Switch Control disables the point and reports a failure to the master station if applicable Inter Sync Transmit Delay sec This delay provides some spacing in seconds between successive transmits from a single Switch Control You can usually leave this at the factory default value TO 1042 563A 10 23 03 S amp C Electric Company EnergyLine 5801 SC IntelliTEAM Gateway Automation Systems Division for Telegyr 8979 Protocol Peer to Peer Message Retry Time sec The Switch Control waits this amount of time in seconds to receive a response from another Switch Control If it does not receive the response within this time period it sends the message to that Switch Control again It continues sending the message until it receives a response or reaches the Peer to Peer Message Retry Count Peer to Peer M
18. SBO Select FC 21 The timer count must be non zero e SBO Operate FC 22 e Accumulator Freeze FC 24 e SBO Immediate Execute FC 28 The timer count must be non zero e Restart RTU FC 30 This function will only restart the gateway No other team members will be affected e RTU Configuration FC 31 While the Switch Control does not have an RTU configuration in the standard sense when it responds to an RTU Configuration request the gateway returns data that the master station may find useful In support of standard RTUs the gateway s configuration is 119 analog points 8 points per card 15 cards 253 status points 16 points per card 16 cards 42 control points 8 points per card 6 cards 42 accumulator points 8 points per card 6 cards With 16 cards per chassis there are 3 chassis Chassis 0 is the 15 analog cards and an empty slot Chassis 1 is the 16 status cards Chassis 2 is the 6 control cards then filled out with empty slots e Time Synchronization FC 32 A time synchronization to the gateway 1042 563A 10 23 03 S 8g EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division causes the time to be set in the local UtiliNet radio if applicable The rest of the team will automatically synchronize to this time though it may take approximately 30 minutes for this to occur If the time changed by more than 1 sec
19. and to the switch e i Rev NOTE This command is ignored if the Battery Low Switch E ae Disabled condition is active due to battery problems and the 24 Dev5 Failure Override command has not been issued These 30 Dev6 commands are ignored and return an exception report if the 36 Dev7 REMOTE LOCAL switch is not in the REMOTE position 1 Dev1 Issue the Shot s to Lockout command to the switch Only a 7 Dev2 Close command is valid for this point i D NOTE This command is ignored if the Battery Low Switch 25 Devs Disabled condition is active due to battery problems and the 3t Dev6 Failure Override command has not been issued These 37 Dev7 commands are ignored and return an exception report if the REMOTE LOCAL switch is not in the REMOTE position 1042 563A 10 23 03 i i i lt lt CO 7 EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division Control Point Definition 2 Devl Reset clear any outstanding overcurrent fault conditions present 8 Dev2 Only a Close command is valid for this point The fault condition 14 Dev3 otherwise remains active for 45 minutes after the switch is closed 20 Dev4 and AC power is fully restored or until the REMOTE LOCAL 26 Dev5 switch is toggled 32 Dev6 38 Dev7 3 Devl Begin a battery test cycle Only a Close command is valid for 9 Dev2 this point If AC power is on the
20. call Call Retry After Call Failure This is the amount of time that the Switch Control waits after receiving an error indication from the modem before attempting another call You can set this value to a longer time to reduce the number of call attempts when a problem exists in the telephone system or at the master station Number of Calls Per Phone Number This is the number of call attempts that the Switch Control makes to each phone number in the Phone Number list before moving to the next number Time to Wait for Connect This is the amount of time in seconds that the Switch Control waits for the modem to report a Connect If it does not connect to the master station s modem within this period the Control considers the attempt failed When setting this value be sure to take into account dialing commands ring time and modem connection time Time to Wait for Master Poll This is the amount of time that the Switch Control waits for the master station to make an indication change poll after a connection has been made with the master DP 1042 563A 10 23 03 S amp C Electric Company EnergyLine 5801 SC IntelliTEAM Gateway Automation Systems Division for Telegyr 8979 Protocol station s modem If a poll is not requested within this time the Switch Control hangs up the connection and schedules another call attempt Modem This setpoint lists factory supported modems While other modems may be compatible default
21. ch Control 42 Dev2 enclosure is ajar When the door is closed this bit is cleared and 68 Dev3 all power to the faceplate LEDs is turned off 94 Dev4 120 Dev5 146 Dev6 172 Dev7 1042 563A 10 23 03 i lt i lt CO 8 EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division Status Point Definition 17 Devl Temperature sensor bad The temperature sensor in the Switch 43 Dev2 Control is reading out of range When the sensor is reading 69 Dev3 incorrectly various temperature related correction factors will not 95 Dev4 be accurate 121 Dev5 147 Dev6 173 Dev7 18 Devl Phase A overcurrent fault This bit is set if the peak current 44 Dev2 measured on Phase A has exceeded the programmed threshold 70 Dev3 level continuously for at least the programmed period of time 96 Dev4 You can adjust these values using the Setup software or a 122 Dev5 SCADA command For a normally closed switch the bit is 148 Dev6 cleared when all of the following are true 174 Dev7 e Three phase line voltage has been sensed e The switch is closed e Forty five minutes have elapsed or someone toggles the faceplate REMOTE LOCAL switch or clears the bit via SCADA For the normally open switch you can toggle the REMOTE LOCAL switch or send a SCADA command to clear the bit while the line switch is open or closed NOTE If you reini
22. charger is disconnected for 15 Dev3 several minutes while the test is in progress If AC power is off a 21 Dev4 brief battery impedance test evaluates the battery condition 27 Dev5 33 Dev6 39 Dev7 4 Devl Enable or disable the Failure Override status This allows 10 Dev2 Trip and Close commands to be processed even if the switch 16 Dev3 Not Ready condition is active 22 Dev4 28 Dev5 34 Dev6 40 Dev7 5 Dev1 Enable or disable Automatic operation In Automatic mode 11 Dev2 the Switch Control automatically opens the switch if a 17 Dev3 preconfigured recloser sequence is recognized after a detected 23 Dev4 fault 3 ee NOTE Automatic operation is not disabled by the faceplate T B REMOTE LOCAL switch being in the LOCAL position Booo 1042 563A 10 23 03 S amp C Electric Company EnergyLine 5801 SC IntelliTEAM Gateway Automation Systems Division for Telegyr 8979 Protocol Telegyr 8979 Protocol Functions Implemented The following Telegyr 8979 protocol functions have been implemented e Analog Change Report FC 0 e Analog Force Report FC 1 e Analog Group Change Report FC 2 e Analog Group Force Report FC 3 e Analog Reference Force Report FC 5 e Indication Change Report FC 6 e Indication Force Report FC 7 e Digital Input Force Report FC 11 e Accumulator Change Report FC 12 e Accumulator Force Report FC 13 e
23. directly connected to another communicating device such as another team Switch Control For more information about the setup and operation of Intelli TEAM Switch Controls see the User s Manual Applicable Software This document was prepared for use with software version SNCD2A4X Rev 2 25 and PADD2A4X Rev 2 26 For questions regarding the applicability of information in this document to future software releases please contact S amp C Electric Company 1042 563A 10 23 03 5 EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division Manual Conventions The following conventions are used in this document BOLD UPPER CASE Labels on faceplates assemblies and switch positions Italic Names of books manuals manual sections and software screens Quotes Names of fields on software screens lt Brackets gt Names of computer keyboard keys Courier Characters to be typed at the DOS prompt and commands issued from the SCADA master station Square Brackets Displays on the LCD Cautions All Cautions are clearly marked with the notation A CAUTION Please read all cautions carefully before attempting to install or operate this equipment CC 4042 563A 10 23 03 S amp C Electric Company EnergyLine 5801 SC IntelliTEAM Gateway Automation Systems Division for Telegyr 8979 Protocol Gateway Setup Screens This section describes the setup screens that are d
24. directly connected to Port A If this setpoint does not match the baud rate for the device SCADA communications will not operate 1042 563A 10 23 03 7 EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division Transmitter Keying Delay Time This is the amount of time in milliseconds that must elapse from the moment the transmitter is turned on until the data transmission begins You can usually leave this at the factory default value Transmit Turn Off Delay Time This is the amount of time in milliseconds that the transmitter should remain on after the second to last character transmission has begun You can usually leave this at the factory default value Output Point Select Timeout This is the timeout duration for Telegyr 8979 of the Select function on control points If the timeout duration is too short between the Select and the Operate functions during a Select Before Operate sequence the Switch Control disables the point Allow RTU Memory Write Operations For security reasons table writes FC 48 Table Write are by default disabled in the IntelliTEAM Switch Controls This feature is implemented for diagnostic purposes and only provides access to tables within the gateway itself Use care when enabling this feature and disable it when you are done to prevent inadvertent changes to Switch Control parameters Monitor Timeout for Control Operation sec
25. er 09 04 02 16 19 SnapShot Figure 3 Fourth SETUP Communications Screen 1042 563A 10 23 03 4 EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division This screen includes the following fields Unsolicited Call Home Feature When the Call Home feature is enabled if applicable the Switch Control initiates a call to the master station in response to a change in any status point The Switch Control uses the setpoints on this screen to determine when to call and how often to call The Switch Control attempts calls to the master until it makes a successful connection and the master has polled for the indication change report NOTE Before enabling the Call Home feature be sure the Switch Control is properly equipped with a land line or cellular phone modem Call Delay After First Event This is the amount of time that the Switch Control waits after the first indication change event before initiating a call This delay prevents the Control from making numerous consecutive calls for related events Enter a time long enough for a related sequence of events to be completed such as a transfer event but short enough for you to receive a timely notification Call Retry After Busy or No Answer This is the amount of time that the Switch Control waits after receiving a busy or no answer indication from the modem before attempting another
26. ery power is low Battery Trouble Summary Scada Mate Pad mount This bit applies to the S amp C ScadaMate and S amp C Pad mount Switch Controls Unless the Switch Control is operating or has recently been operating on battery power this bit indicates that maintenance is required probably battery replacement Battery System Low This bit is set if the battery voltage is too low to operate the switch reliably Battery System Bad This bit is set if the battery voltage is too low to operate the switch This condition blocks the operation of the switch unless the Failure Override bit is set Battery Charger Has Failed This bit is set if the charging voltage applied the battery system was too high when the charger was connected and the charger has been turned off Battery Test In Progress This bit is set if the Switch Control is performing a test procedure on the battery Cabinet Door Open This bit is set if the door to the Switch Control enclosure is ajar When the door is closed this bit is cleared Temperature Sensor Bad This bit is set if the temperature sensor in the Switch Control is reading out of range AC Power Failure This bit is set if at least one of the three phases has lost voltage Switch 1 2 Phase A B C Ground Overcurrent Fault These bits are set if the peak current measured on the indicated phase of the associated switch has exceeded the programmed threshold level continuously for at
27. essage Retry Count This is the number of times that the Switch Control retries sending a message to a Switch Control that does not respond within the Peer to Peer Message Retry Time NOTE Decreasing the Peer to Peer Message Retry Time or increasing the Peer to Peer Message Retry Count may have an adverse affect with some communications systems due to increased traffic Be sure to take this into account when changing these values You can usually leave these at the factory default values if the Switch Controls are communicating through a UtiliNet communications network View the Fourth SETUP Communications Screen The fourth SETUP Communications screen Figure 3 contains setpoints for the Call Home feature if applicable to your SCADA system Ff inergyline Intelil INK tm Intelli TEAM R Gateway Intel TEAM 1Comm Setup3 5 x Q Fle Connection Data Window Help nla x Setup Trouble Overcurrent Data Menu Operation shooting Fault Logging SUITES SETUP Communications Page 4 of 4 Port A Telegyr 8979 Parameters Present Factory Unsolicited Call Home Feature Disabled Disabled Call Delay After First Event 2 Min 2 Min Call Retry After Busy or No Answer 20Sec __208ec Call Retry After Call Failure Number of Calls per Phone Number Time to Wait for Connect seconds Time to Wait for Master Poll seconds Modem Aprotek 7524 Setup String ATEOQoVOx4s0 28C1awo Reinitialize Modem Phone Numb
28. gs Voltage is reported in units of 1 sensor count equals 0 1 VAC RMS 1042 563A 10 23 03 S 88 EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division Analog Point Definition 5 Devl Single phase voltage measured on Phase B As above for Phase B 20 Dev2 35 Dev3 50 Dev4 65 Dev5 80 Dev6 95 Dev7 6 Devl Single phase voltage measured on Phase C As above for Phase C 21 Dev2 36 Dev3 51 Dev4 66 Dev5 81 Dev6 96 Dev7 7 Devl Phase angle on Phase A Each count equals one eighth of a degree 22 Dev2 with an offset of 90 degrees a value of zero corresponds to a 37 Dev3 leading power factor and a phase angle of 90 degrees 52 Dev4 67 Dev5 82 Dev6 97 Dev7 8 Dev1 Phase angle on Phase B As above for Phase B 23 Dev2 38 Dev3 53 Dev4 68 Dev 83 Dev6 98 Dev7 9 Devl Phase angle on Phase C As above for Phase C 24 Dev2 39 Dev3 54 Dev4 69 Dev5 84 Dev6 99 Dev7 10 Devl Single phase kVARs measured on Phase A kVARs volt amperes 25 Dev2 reactive are calculated from single phase true RMS voltage and 40 Dev3 current sensor values and the respective voltage current phase 55 Dev4 angle Each count equals 8 kVARs a value of zero corresponds to 70 Dev5 16376 kVARs leading 85 Dev6 100 Dev7 4 10425663A 10 23 03 S amp C Electric Company EnergyLine 5801 SC
29. he request sent to the remote Switch Control If a problem is found before a request is sent to the remote Switch Control the gateway does not generate the request If no problems are found the gateway sends the DNP request to the remote Control to perform the action The gateway monitors this request to see if it receives a response from the remote Switch Control A timer counts down during this time If the timer expires before the gateway receives a response or if the response indicates that the control command failed the gateway generates an SBO Failure exception report If the gateway receives a response indicating success monitoring ends Further status point polling is the only way to insure that the control operation took place A data scan from the gateway to the remote Control is scheduled soon after the control request is issued This is done to satisfy the subsequent polls in a timely manner If a problem is then seen during the operation exception reports are generated see Table 5 and included with the next response Function Not Allowed The switch is not ready and Failure Override is not set Invalid Parameter The timer count is zero or the Trip Close bit is set to Trip when only Close is valid Table 5 Errors During Remote Control Point Operation Remote Local The operation of control points at each Switch Control depends on the position of the REMOTE LOCAL faceplate switch at that Control If
30. he type of connection for this port The setpoint defines how the Switch 1042 563A 10 23 03 9 EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division Control handles communications None There is no connection to this port Non Relay Messages received on this port are not intended for the entire team This setting also prevents the Switch Control from recording errors if this port receives a message not addressed to the local Control SCADA This port is used for protocol conversion and is connected to a SCADA master station Direct This port is connected directly to another team Switch Control or to a DNP master station Team Radio This port is connected to a radio used for communication within the team RTS Active Before Transmit Duration This is the amount of time in milliseconds that RTS request to send is active for this port before a transmission takes place If a team radio is connected to this port the delay also provides some spacing for packets on the local Control to Radio LAN You can usually leave this at the factory default value RTS Active Following Transmit Duration This is the amount of time in milliseconds that RTS request to send is active after a transmission has taken place If a team radio is connected to this port the delay also provides some spacing for packets on the local Control to Radio LA
31. hooting Fault Logging STEED SETUP Communications Page 3 of 4 Port B DNP Parameters Present Factory SCADA Communication Baud Rate 4800 4800 Half Full Duplex Full Full Connection Type Team Radio Team Radio RTS Active Before Transmit Duration ms 19 RTS Active Following Transmit Duration ms 19 Data Link Layer Confirmations Enabled Output Block Point Select Timeout 30 Sec Inter Sync Transmit Delay sec Peer to Peer Message Retry Time sec Peer to Peer Message Retry Count 09 04 02 16 18 SnapShot Figure 2 Third SETUP Communications Screen This screen includes the following fields SCADA Communication Baud Rate This is the baud rate between the directly connected device and the Switch Control For a UtiliNet radio leave this setpoint at the factory default value of 4800 If another device is connected be sure to match the baud rate between the Switch Control and that device Half Full Duplex Set this value to match the communication device modem radio master station another Switch Control etc connected to this port Set it to Full Duplex when this port is connected to another Control in the team a UtiliNet radio without an intermediate communications buffer board or other full duplex device Use Half Duplex when connected to a device using an intermediate comm buffer board or other half duplex communications device Connection Type This is t
32. ice 1 Device 2 Figure 5 First SETUP Analog Points List Screen Clear Entire Map Use this parameter to clear the entire point map if the team you are configuring is significantly different from the default team provided The default is a full point map for a team of seven S amp C ScadaMate switches NOTE This action will immediately clear all configured point mapping from the analog points table status and control point tables will not be affected Device Num This column contains the number of the device for which that analog point is associated The device numbers for each team member are found on the SETUP Team Configuration screen page 1 normal team members and page 2 sideline team members NOTE Associating Telegyr points with the correct device number for the intended field device is critical to correct operation between the Switch Control team and your SCADA communications system Analog Point This column contains the analog points you may configure with each team device 1042 563A 10 23 03 S amp C Electric Company EnergyLine 5801 SC IntelliTEAM Gateway Automation Systems Division for Telegyr 8979 Protocol Each point is defined below Where points may apply to more than one switch position if the team device is an overhead switch only the Switch 1 point applies Point Not Configured You should use this selection for point numbers that will not be defined in the finished points list
33. iew the SETUP Control Points Screen This screen contains control points that may be configured for the team 1042 563A 10 23 03 ss lt i sSsSsSS 8 EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division Eitnergytine Intelil INK tm IntelliTEAM R Gateway IntelliTEAM SComm Setup 5 xj Fie Connection Data window Help ale x Setup Trouble Overcurrent Data Telegyr Menu puao shooting Fault Logging Points SETUP Control Points List Page 1 of 3 20 PointNum DeviceNum_ Control Point gt gt O 0 Device 1 Issue the Trip Close Command to Switch 1 1 Device 1 Issue the Shots to lockout Command to Switch 1 2 Device 1 Reset Outstanding Overcurrent Fault Conditions Device 1 Begin a Battery Test Cycle Device 1 Enable or Disable the Failure Override Status Device 1 Enable or Disable Automatic Operation Device 2 Issue the Trip Close Command to Switch 1 Device 2 Issue the Shots to lockout Command to Switch 1 Device 2 Reset Outstanding Overcurrent Fault Conditions Device 2 Begin a Battery Test Cycle Device 2 Enable or Disable the Failure Override Status Device 2 Enable or Disable Automatic Operation Device 3 Issue the Trip Close Command to Switch 1 Device 3 Issue the Shots to lockout Command to Switch 1 Device 3 Reset Outstanding Overcurrent Fault Conditions Device 3 Begin a Battery Test Cycle 09
34. ifferent for the IntelliTEAM gateway View the Second SETUP Communications Screen The second SETUP Communications screen Figure 1 contains communications related setpoints for Port A the port using Telegyr 8979 protocol Fieneraytinee Intelit INK tm IntelliTEAM R Gateway IntelliTEAM 1Comm Setupt 5 x Q Me Connection Data Window Help alaj x Setup Trouble Overcurrent Data Menu Operation shooting Fault Logging Communications SETUP Communications Page 2 of 4 Port A Telegyr 8979 Parameters Present Factory IntelliTEAM Gateway RTU Address SCADA Communication Baud Rate Transmitter Keying Delay Time ms Transmitter Turn Off Delay Time ms Output Point Select Timeout Allow RTU Memory Write Operations Monitor Timeout for Control Operation sec Scan Delay After Control Operation sec Pg U Pg Dn 09 04 02 16 14 SnapShot Figure 1 Second SETUP Communications Screen This screen includes the following fields IntelliTEAM Gateway RTU Address In addition to the RTU address for IntelliTEAM communications this is the RTU address for all Telegyr 8979 gateway activity Through this address the SCADA master station has access to all status analog and control points related to the team SCADA Communication Baud Rate This is the baud rate between the communications device and Port A of the Switch Control Set it to the baud rate used by the communications device
35. ilable at all times Control Points Control points are not available for the gateway until a valid local record is defined in the address database Control points are not available for the remote Switch Controls until the team is configured and successful polling begins If a failed communication results in bad data for that remote Switch Control control points are not available for that Control until the gateway receives good data again Errors During Select Function Table 1 shows the meaning of errors that can occur while using the Select function They are reported in an exception report A 1042 563A 10 23 03 S amp C Electric Company EnergyLine 5801 SC IntelliTEAM Gateway Automation Systems Division for Telegyr 8979 Protocol Error Error Reported C Existent Point The control point o is greater than the maximum number of control points Function Not Allowed There is no local record defined or the request was received with a broadcast address SBO Select is not allowed Or The Switch Control is not in Remote mode SBO Failure The remote data is not good possibly due to lost communications Invalid Parameter The timer count is zero Table 1 Errors During Select Errors During Operate Function Table 2 shows the meaning of errors that can occur while using the Operate function They are reported in an exception report Function Not Allowed There is no local record defined SBO Operate is n
36. is bit is set after the operator has 37 Dev2 executed the Failure Override Close control command to 63 Dev3 let the switch be operated even if battery power is low The bit 89 Dev4 remains set until the override is disabled using the Failure 115 Dev5 Override Trip command 141 Dev6 167 Dev7 12 Devl Battery system low The battery voltage is too low to operate the 38 Dev2 switch reliably This condition blocks the operation of the switch 64 Dev3 unless the Failure Override bitis set 90 Dev4 116 Dev5 142 Dev6 168 Dev7 13 Devl Battery system bad The battery voltage is too low to operate the 39 Dev2 switch This condition blocks the operation of the switch unless 65 Dev3 the Failure Override bitis set The bad battery status is 91 Dev4 only set when the battery voltage is definitely too low to activate 117 Dev5 the switch operating solenoid 143 Dev6 169 Dev7 14 Devl Battery charger has failed The charging voltage applied to the 40 Dev2 battery system was too high when the charger was connected and 66 Dev3 the charger has been turned off 92 Dev4 118 Dev5 144 Dev6 170 Dev7 15 Devl Battery test in progress The Switch Control automatically 41 Dev2 performs a test procedure on the batteries at periodic intervals 67 Dev3 During the test the battery voltage fluctuates 93 Dev4 119 Dev5 145 Dev6 171 Dev7 16 Devl Cabinet door open This bit is set if the door to the Swit
37. itch Control team and your SCADA communications system Status Point This column contains the status points you may configure with each team device Each point is defined below Where points may apply to more than one switch position if the team device is an overhead switch only the Switch 1 point applies Point Not Configured You should use this selection for point numbers that will not be defined in the finished points list These point numbers will continue to be returned in a complete scan of the points list but will always indicate false or off Note that the points list does not need to be contiguous You may leave undefined points at any location within your points list Switch 1 Open Contact Status Switch 2 Open Contact Status Switch 3 Open Contact Status These bits are set if the associated switch is open Switch 1 Closed Contact Status Switch 2 Closed Contact Status Switch 3 Closed Contact Status These bits are set if the associated switch is closed Switch 1 Grounded Contact Status Vista Switch 2 Grounded Contact Status Vista These bits apply only to S amp C Vista team members The bits are set if the associated switch is in the grounded position Switch 1 Disabled Status Switch 2 Disabled Status These bits are set when the operation of the associated switch is disabled This may occur when bad battery voltage is present low pressure is detected if applicable external local is se
38. llowing Telegyr 8979 protocol functions and commands are not supported an Invalid Function Code exception report is generated e SOE Change Report FC 8 e SOE Force Report FC 9 e SOE Log Change Report FC 14 e Analog Output FC 20 e Digital Output FC 23 e Pulse Output FC 25 e Pulse Train Output FC 26 AO 4042 563A 10 23 03 S amp C Electric Company EnergyLine 5801 SC Intelli EAM Gateway Automation Systems Division for Telegyr 8979 Protocol e Accumulator Preset FC 36 1042 563A 10 23 03 41 EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division Telegyr 8979 Implementation The following section provides more information on the Telegyr 8979 implementation for the gateway Status and Analog Points Status and analog points are not available for the gateway until a valid local record is defined in the address database A valid local record means that an RTU address in the address database matches the RTU address on the first SETUP Communications screen Status and analog points for remote Switch Controls are not available until the team is configured and polling has begun by the gateway If good data exists then goes away for example from failed communications the gateway generates exception reports for both an Analog Failure and an Indication SOE Failure Status and analog points for the team summary are ava
39. mbers are dialed consecutively starting at the first number in the list If the first number is not reachable after the configured number of tries see Number of Calls per Phone Number the Switch Control moves to the next number in the list When it reaches the end of the list it begins again with the first phone number 1042 563A 10 23 03 ss B EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division Telegyr Points Setup Screens The SETUP Telegry Points menu screen provides access to a series of setup screens These screens allow you to configure the Telegyr 8979 points list to match the requirements of the Switch Control team View the SETUP Status Points Screen This screen contains status points that may be configured for the team Eitnergytine Intelil INK tm IntelliTEAM R Gateway IntelliTEAM 3Comm Setup aloj x Q Fle Connection Data Window Help x Setup Trouble Overcurrent Data Telegyr Menu praan shooting Fault Logging Points SETUP Status Points List Page 1 of 12 Clear Entire Map _DeviceNum StatusPoint Z O Z o O oo Device 1 Automatic Operation Enable Device 1 Remote Local Faceplate Switch Position Device 1 0 Device 1 Switch 1 Open Contact Status 1 Device 1 Switch 1 Closed Contact Status 2 Device 1 Switch 1 Disabled Status switch 1 Overcurrent Fault Detected Vista Sw 1 2 Switch 1 Sectionali
40. n a pad mount dual switch this point refers to the switch associated with team Position A of Device 1 212 Device 2 switch status As above for Device 2 213 Device 3 switch status As above for Device 3 214 Device 4 switch status As above for Device 4 215 Device 5 switch status As above for Device 5 216 Device 6 switch status As above for Device 6 217 Device 7 switch status As above for Device 7 218 Device normal switch status This bit is set when the normal position for the switch connected to Device 1 is closed Each team should have no more than one normally open switch 219 Device 2 normal switch status As above for Device 2 220 Device 3 normal switch status As above for Device 3 221 Device 4 normal switch status As above for Device 4 222 Device 5 normal switch status As above for Device 5 223 Device 6 normal switch status As above for Device 6 224 Device 7 normal switch status As above for Device 7 225 Device 1 voltage loss This bit is set when Device is detecting a voltage loss 226 Device 2 voltage loss As above for Device 2 227 Device 3 voltage loss As above for Device 3 228 Device 4 voltage loss As above for Device 4 229 Device 5 voltage loss As above for Device 5 230 Device 6 voltage loss As above for Device 6 231 Device 7 voltage loss As above for Device 7 232 Device 1 faults present This bit is set when Device 1 is detecting a fault 233 Device 2 faults prese
41. n for Telegyr 8979 Protocol Analog Input Points Analog Point Definition 0 Dev1 Neutral current taken as the vector sum of the phase currents on 15 Dev2 Phases A B and C Current is measured using true RMS 30 Dev3 techniques and reported in units of 1 count equals 1 ampere 45 Dev4 60 Dev5 75 Dev6 90 Dev7 1 Devl Single phase current measured on Phase A Current is measured 16 Dev2 using true RMS techniques and reported in units of 1 count equals 31 Dev3 1 ampere 46 Dev4 61 Dev5 76 Dev6 91 Dev7 2 Devl Single phase current measured on Phase B Current is measured 17 Dev2 using true RMS techniques and reported in units of 1 count equals 32 Dev3 1 ampere 47 Dev4 62 Dev5 77 Dev6 92 Dev7 3 Devl Single phase current measured on Phase C Current is measured 18 Dev2 using true RMS techniques and reported in units of 1 count equals 33 Dev3 1 ampere 48 Dev4 63 Dev5 78 Dev6 93 Dev7 4 Devl Single phase voltage measured on Phase A Voltage is measured 19 Dev2 using true RMS techniques and scaled to yield a nominal value of 34 Dev3 120 VAC Configuration of the Switch Control at installation time 49 Dev4 provides the scaling factors such as voltage transformer turn ratio 64 Dev5 etc In cases where loads are connected in a delta phase to phase 79 Dev6 configuration the Switch Control s Sensor Conditioning module is 94 Dev7 jumpered to yield phase to phase voltage readin
42. nt As above for Device 2 1042 563A 10 23 03 ssi 8 EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division Status Point Definition 234 Device 3 faults present As above for Device 3 235 Device 4 faults present As above for Device 4 236 Device 5 faults present As above for Device 5 237 Device 6 faults present As above for Device 6 238 Device 7 faults present As above for Device 7 239 Device 1 alarms present This bit is set when one or more alarm conditions are present in Device 1 240 Device 2 alarms present As above for Device 2 241 Device 3 alarms present As above for Device 3 242 Device 4 alarms present As above for Device 4 243 Device 5 alarms present As above for Device 5 244 Device 6 alarms present As above for Device 6 245 Device 7 alarms present As above for Device 7 246 Device team Position B status This bit is set when the switch associated with Position B of Device 1 is closed 247 Device 2 Position B status As above for Device 2 248 Device 3 Position B status As above for Device 3 249 Device 4 Position B status As above for Device 4 250 Device 5 Position B status As above for Device 5 251 Device 6 Position B status As above for Device 6 252 Device 7 Position B status As above for Device 7 BO 1042 563A 10 23 03 S amp C Electric Company EnergyLine 5801 SC Intelli EAM Gateway Automation Systems Divisio
43. nt 2 33 Dev2 Battery Status Unless the Switch Control is operating or has 59 Dev3 recently been operating on battery power this bit indicates that 85 Dev4 maintenance is required probably battery replacement 111 Dev5 137 Dev6 163 Dev7 8 Devl Maintenance required This bit is set when some form of 34 Dev2 maintenance other than battery replacement is required It is set 60 Dev3 when the battery charger has failed due to overvoltage or when the 86 Dev4 switch Open Close contacts are not mutually exclusive It is 112 Dev5 also set when a problem prevents a team of switches configured 138 Dev6 for automatic transfer from doing so This is a summary bit The 164 Dev7 exact cause of the failure can be determined from the inspection of other status points 9 Dev Open Close switch position sensor failure This bit is set if 35 Dev2 either both contacts are closed or both contacts are open 61 Dev3 87 Dev4 113 Dev5 139 Dev6 165 Dev7 10 Devl Control power failure This bit is set if AC power is not available 36 Dev2 to the battery charger It indicates that the Switch Control is 62 Dev3 operating on battery backup 88 Dev4 114 Dev5 140 Dev6 166 Dev7 6 1042 563A 10 23 03 S amp C Electric Company EnergyLine 5801 SC IntelliTEAM Gateway Automation Systems Division for Telegyr 8979 Protocol Status Point Definition 11 Devl Operator failure override set Th
44. nterrupt e First character of packet not FF e Packet length illegal e Packet contains bad characters framing e Timeout on control select operation e Modem receive buffer overrun e Phone number list is empty e Modem reset failed e Setup string rejected e Dialing the phone failed e Connect to master failed e Poll was not received from master e Hang up failed 1042 563A 10 23 03s s lt ssSsSSS 8 EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division Telegyr 8979 Points List Factory Default This section describes the factory default Telegyr 8979 points for the Intelli TEAM gateway The DNP points are described in Appendix A of the User s Manual The factory default point list contains all the points needed for a seven member team of S amp C Scada Mate Switch Controls You may modify this list to match the requirements of your Switch Control team and your SCADA system For accessing the Model 5801 SC IntelliTEAM Gateway the Telegyr 8979 master station should define the Switch Control with the following I O Point Count Status Points 253 Analog Input Points 119 Pulse Accumulator Points 42 Control Points 42 The points are defined in the tables below Unless otherwise noted each bit is set if the condition is logically true or active Status Points Status Point Definiti
45. on 0 Devl Switch Open contact status This bit is set if the switch circuit 26 Dev2 is open 52 Dev3 78 Dev4 104 Dev5 130 Dev6 156 Dev7 l Dev1 Switch Closed contact status This bit is set if the switch 27 Dev2 circuit is closed 53 Dev3 79 Dev4 105 Dev5 131 Dev6 157 Dev7 Ao 10425663A 10 23 03 S amp C Electric Company EnergyLine 5801 SC IntelliTEAM Gateway Automation Systems Division for Telegyr 8979 Protocol Status Point Definition 2 Devl Battery status switch disabled This bit is set when low or bad 28 Dev2 battery voltage is present See status points 12 and 13 below to 54 Dev3 determine which condition is causing the bit to be set A low 80 Dev4 battery condition prevents the switch from being operated 106 Dev5 remotely unless the Failure Override control command has been 132 Dev6 set see below The Battery Low condition does not prevent the 158 Dev7 switch from being operated from the faceplate switches 3 Dev1 Automatic operation enable This bit is set if automatic control 29 Dev2 functions have been enabled via either the faceplate switches or 55 Dev3 SCADA control command 81 Dev4 107 Dev5 133 Dev6 159 Dev7 4 Devl REMOTE LOCAL faceplate switch position This bit is set when 30 Dev2 the switch is in the REMOTE position In the REMOTE position 56 Dev3 local operation of the switch from the faceplate is blocked In the 82 Dev4 LOC
46. ond during this 30 minutes the team will not be in sync and will not be able to perform automatic transfers NOTE Setting the time in one UtiliNet radio will eventually change the time in all UtiliNet radios within the reachable network e Time Bias FC 33 e Analog Deadbands FC 34 When setting the deadband values for remote Switch Controls be sure to take into account the relatively slow update of analog points for these Controls If the change in the analog value delta was high when the remote Switch Control reported to the gateway then a high delta is integrated by the gateway once per second until the next scan interval This is true even if the actual analog value is fluctuating up and down This may cause the deadband value to be reached sooner than it normally would e Analog Group Define FC 35 e Continue Request FC 37 Repeat Last Message FC 38 e Firmware Configuration FC 39 e Table Read FC 47 Table reads are implemented for the local gateway Switch Control but are not intended for access to other team members e Table Write FC 48 Table writes are implemented for the local gateway Switch Control but are not intended for access to other team members Before a Table Write command is accepted a value of 15 hex must have been written to location 1006 hex or writes must have been enabled on the second SETUP Communications screen e Exception Report FC 63 The fo
47. onological listing of communications problems for Port A the Telegyr 8979 protocol port For data related to the DNP protocol on Port B see the TROUBLESHOOTING Communications screen in the Troubleshooting chapter The DNP screen includes its own log and a status of the IIN bits for the most recent transaction Eqtnergytine Intelil INK tm Intelli TEAM R Gateway IntelliTEAM Comm Error Log sloj x Q Fle Connection Data Window Help 18 x Trouble Overcurrent Data shooting Fault Logging Operation TROUBLESHOOTING Communications Page 1 of 2 Port A Telegyr 8979 Date Time Msec Reason for Communications Failure 09 04 02 16 32 SnapShot Figure 7 First TROUBLESHOOTING Communications Screen The log can hold 10 entries Once the log is full each new event over writes the oldest event in the log To find the most recent event look for the message with a timestamp that is older than the time for the message above it This screen includes the following fields Date Time MSec This is the date and time to the nearest 6 25 milliseconds when the event occurred 2o 10425663A 10 23 03 S amp C Electric Company EnergyLine 5801 SC Intelli EAM Gateway Automation Systems Division for Telegyr 8979 Protocol Reason for Communications Failure This is the reason that communications failed One of the following messages appears e Packet CRC Error e Internal Bad UART i
48. ot allowed Or The Switch Control is not in Remote mode SBO Failure The remote data is not good possibly due to lost communications Select Execute The selected point number and the operate point number do Mismatch not match or Select is not enabled Table 2 Errors During Operate Errors During Immediate Execute The operation of an Immediate Execute is similar to the operation of the standard Select Before Execute sequence It uses many of the same error checks and adds some special error checks Table 3 shows the meaning of errors that can occur while using the Immediate Execute function They are reported in an exception report 1042 563A 10 23 03 43 EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division Non Existent Point The control point requested is greater than the maximum number of control points Function Not Allowed The team is not configured or the address database is not valid SBO Immediate Execute is not allowed Or The Switch Control is not in Remote mode SBO Failure The remote data is not good possibly due to lost communications Select Execute The point number does not match its complement Mismatch Invalid Parameter The timer count does not match its complement or the timer count is invalid Table 3 Errors During Immediate Execute Local Control Point Operation Process
49. switch operations on 15 Dev2 switch 2 The counter is incremented on each Close operation 16 Dev3 This is a 16 bit counter and will overflow back to zero 17 Dev4 18 Dev5 19 Dev6 20 Dev7 21 Sidelinel Operation Counter This is the number of switch operations on 22 Sideline2 switch 2 The counter is incremented on each Close operation 23 Sideline3 This is a 16 bit counter and will overflow back to zero Eoo 1042 563A 10 23 03 S amp C Electric Company EnergyLine 5801 SC Intelli EAM Gateway Automation Systems Division for Telegyr 8979 Protocol 24 Sideline4 This is a 16 bit counter and will overflow back to zero 25 Sideline5 26 Sideline6 27 Sideline7 28 Devl Operation Counter This is the number of switch operations on 29 Dev2 switch 3 The counter is incremented on each Close operation 30 Dev3 This is a 16 bit counter and will overflow back to zero 31 Dev4 32 Dev5 33 Dev6 34 Dev7 35 Sidelinel Operation Counter This is the number of switch operations on 36 Sideline2 switch 3 The counter is incremented on each Close operation 37 Sideline3 This is a 16 bit counter and will overflow back to zero 38 Sideline4 39 Sideline5 40 Sideline6 41 Sideline7 Control Points All points may be operated using either the Select Before Operate sequence or the SBO Immediate Execute function Control Point Definition 0 Devl Issue the Trip Close comm
50. t if applicable the switch is in the grounded position if applicable or visual disconnect is open if applicable Low Pressure Detected Vista Universal This bit applies only to S amp C Vista and Universal Switch Control equipment This bit is set if low pressure is detected in the switch load break mechanism Automatic Operation Enable This bit is set if automatic control functions have been enabled via either the faceplate 1042 563A 10 23 03 45 EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division switches or SCADA control command Remote Local Faceplate Switch Position This bit is set when the switch is in the REMOTE position In the REMOTE position local operation of the switch from the faceplate is blocked In the LOCAL position operation of the switch from the SCADA master station is blocked External Local Override Status Pad mount Vista This bit applies only to the S amp C Pad mount and S amp C Vista Switch Controls This bit is set if the switchgear is placed in local override in the switch motor operator cabinet Switch 1 Overcurrent Fault Detected Vista Sw 1 2 This bit applies to the S amp C ScadaMate S amp C Pad mount and both switch 1 and 2 of the Vista The bit is set if the associated switch has detected an overcurrent fault Switch 2 Overcurrent Fault Detected S amp C Pad mount This bit applies only to the S amp
51. the points list does not need to be contiguous You may leave undefined points at any location within your points list Issue the Trip Close Command to Switch 1 2 3 This is the command to open or close the associated switch Issue the Shots to lockout Command to Switch 1 2 This is the command to close the associated switch using the Shots to lockout feature Only a Close command is valid Reset Outstanding Overcurrent Fault Conditions This is the command to clear any outstanding overcurrent fault indications Only a Close command is valid for this point Enable or Disable the Failure Override Status This command allows Trip and Close commands to be processed even if the switch Not Ready condition is active Enable or Disable Automatic Operation In Automatic mode the Switch Control automatically opens the switch if a preconfigured recloser sequence is recognized after a detected fault In Automatic mode Intelli TEAM will also work to restore service to all the unaffected load Begin a Battery Test Cycle This is the command to force a battery test sequence to begin Only a Close command is valid for this control point 1042 563A 10 23 03 sss 8d EnergyLine 5801 SC IntelliTEAM Gateway S amp C Electric Company for Telegyr 8979 Protocol Automation Systems Division Gateway Troubleshooting Screen There is an additional TROUBLESHOOTING Communications screen for the IntelliTEAM gateway This screen shows a chr
52. tialize the Switch Control using the Setup software the bit is cleared whether or not the conditions above are met 19 Devl Phase B overcurrent fault As above for Phase B 45 Dev2 71 Dev3 97 Dev4 123 Dev5 149 Dev6 175 Dev7 20 Devl Phase C overcurrent fault As above for Phase C 46 Dev2 72 Dev3 98 Dev4 124 Dev5 150 Dev6 176 Dev7 OB 1042 563A 10 23 03 S amp C Electric Company EnergyLine 5801 SC Intelli EAM Gateway Automation Systems Division for Telegyr 8979 Protocol Status Point Definition 21 Devl Overcurrent ground fault As above for ground 47 Dev2 73 Dev3 99 Dev4 125 Dev5 151 Dev6 177 Dev7 22 Devl AC power failure At least one of the three phases has lost voltage 48 Dev2 74 Dev3 100 Dev4 126 Dev5 152 Dev6 178 Dev7 23 Devl Phase A reverse current This bit is set if the current on Phase A 49 Dev2 is flowing in the direction opposite to the normal direction 75 Dev3 configured in the Switch Control The Switch Control identifies 101 Dev4 reverse current when the voltage current phase angle deviates 127 Dev5 more than 90 degrees from the value set during installation for 153 Dev6 unity power factor 179 Dev7 24 Devl Phase B reverse current As above for Phase B 50 Dev2 76 Dev3 102 Dev4 128 Dev5 154 Dev6 180 Dev7 25 Devl Phase C reverse current As above for Phase C 51 Dev2 77 Dev3 103
53. zer Tripped Device 1 Device 1 Device 1 3 4 5 6 Device 1 7 8 Battery Trouble Summary ScadaMate Padmount Maintenance Required Switch 1 Open Close Switch Position Sensor Failure Device 1 Control Power Failure Device 1 Operator Failure Override Set Device 1 Battery System Low Device 1 Device 1 Device 1 Battery System Bad Battery Charger Has Failed Battery Test In Progress 09 04 02 16 23 SnapShot Figure 4 First SETUP Status Points List Screen Clear Entire Map Use this parameter to clear the entire point map if the team you are configuring is significantly different from the default team provided The default is a full point map for a team of seven S amp C ScadaMate switches NOTE This action will immediately clear all configured point mapping from the status points table analog and control point tables will not be affected Device Num This column contains the number of the device for which that status point is associated The device numbers for each team member are found on the SETUP 4 4042 563A 10 23 03 S amp C Electric Company EnergyLine 5801 SC Intelli EAM Gateway Automation Systems Division for Telegyr 8979 Protocol Team Configuration screen page 1 normal team members and page 2 sideline team members NOTE Associating Telegyr points with the correct device number for the intended field device is critical to correct operation between the Sw