2080-SG001C-EN-P Micro800 Programmable
Contents
1. Base analog 1 0 channels Four 24V DC digital inputs can be configured as 0 10V analog inputs DC input models only via Plug In Modules via Plug in modules and Expansion I O Base number of plug in modules 0 Publication 2080 SG001C EN P September 2012 Micro800 Programmable Controller Family Selection Guide 3 Features Attribute Maximum digital 1 0 Types of accessories or plug ins supported Micro810 Micro830 Micro850 12 point 10 point 48 point 12 26 e CD display with backup All plug in modules see page 43 memory module USB adapter Types of Expansion 1 0 supported All expansion 1 0 modules see page 25 Power supply Embedded 120 240V AC and 12 24V DC options Base unit has embedded 24V DC power supply optional external 120 240V AC power supply available Basic instruction speed Software 2 5 us per basic instruction 0 30 us per basic instruction Connected Components Workbench 1 For Micro830 controllers the number of maximum digital 1 0 assumes 8 point digital 1 0 plug ins for example 2080 I040B4 are used on all available plug in slots For Micro850 controllers the maximum number of digital I O supported between the base plug ins and expansion I 0 is 132 Micro800 Controller Programming Comparison with Connected Components Workbench Attribute Program steps Data bytes Micro810 12 point 2 KB 8 KB Micro850
2. Micro830 Micro830 Micro830 Micro850 10 16 point 24 point 48 point 24 point 48 point 20 KB 20 KB 20 KB 20 KB IEC 61131 3 languages Ladder diagram function block diagram structured text User defined function blocks Yes Floating point 32 bit amp 64 bit PID Loop Control Yes Yes Embedded serial port protocols None Modbus Master Slave ASCII Binary CIP Serial Server 1 Estimated Program and Data size are typical program steps and variables are created dynamically 1 Program Step 12 data bytes The number of bytes per instruction can vary greatly from program to program and from programming language to programming language Micro800 Communication Options Controller USB progamming port Embedded Serial Port Serial Port Plug In CIP Serial Modbus RTU Modbus TCP EtherNet IP ASCII Binary Micro810 Yes with adapter No Micro830 Yes Server Master Slave No No Yes Release 2 Micro850 Yes Server Master Slave Server Server Yes 1 Client will be available at later release Publication 2080 SG001C EN P September 2012 4 Micro800 Programmable Controller Family Selection Guide Micro800 Power Requirements Controller Module Power Requirement Micro810 12 point 3 W 5V A for AC module with or without LCD Micro830 and Micro850 without plug in expansion 1 0 10 16 point 5W 24 poin 8W 48 poin 11W Plug in modules each 1 44
3. C 167 F or greater 1 2 mm 3 64 in insulation max Wiring category 2 on signal ports Wire type Shielded Terminal screw torque 0 5 0 6 Nm 4 4 5 3 Ib in 7 Power dissipation total 1 7 W 37W 1 75 W Enclosure type rating Meets IP20 Status indicators 1 green health 1 green health 1 green health indicator indicator indicator 8 red error indicators Isolation voltage 50V continuous Reinforced Insulation Type channel to system and channel to channel Type tested 720V DC for 60 s North American temp T4 code 1 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 2 RTB hold down screws should be tightened by hand They should not be tightened using a power tool Input Specifications 2085 IF4 and 2085 IF8 Attribute 2085 IF4 2085 IF8 Number of inputs 4 8 Resolution 14 bits 13 bits plus sign bit Voltage 1 28 mV cnt unipolar 1 28 mV cnt bipolar Current 1 28 uA cnt Data format Left justified 16 bit 2s complement Conversion type SAR Update rate lt 2 ms per enabled channel without 50 Hz 60 Hz rejection 8 ms for all channel 8 ms with 50 Hz 60 Hz rejection Publication 2080 SG001C EN P September 2012 32 Micro800 Programmable Controller Family Selection Guide Input Specifications 2085 IF4 and 2085 IF8 Attribute 2085 IF4 2085 IF8 Step re
4. 2 5 mm 26 14 AWG solid copper wire or 0 14 1 5 mm 26 16 AWG stranded copper wire rated 90 C 194 F insulation max 0 2 2 5 mm 24 14 AWG solid copper wire or 0 2 2 5 mm 24 14 AWG stranded copper wire rated 90 C 194 F insulation max Wiring category 2 on signal ports 2 on power ports Wire type Use copper conductors only Terminal screw torque 0 6 Nm 4 4 Ib in max using a 2 5 mm 0 10 in flat blade screwdriver Power consumption 7 88W 12 32W 18 2W Power supply voltage range 20 4 26 4V DC Class 2 Insulation stripping length 7 mm 0 28 in Enclosure type rating Meets IP20 North American temp code T4 1 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Publication 2080 SG001C EN P September 2012 Micro800 Programmable Controller Selection Guide 11 Micro830 Controllers 10 and 16 Point Controllers Allen Bradley General Specifications 10 point controllers Attribute 2080 LC30 100WB Allen Bradley OO0000600006 Allen Bradley 2080 LC30 100VB Input circuit type 12 24V sink source standard 24V sink source high speed Output circuit type Relay 24V DC sink transistor standard and high speed Event input interrupt support Yes 1 0 rating I
5. 50V continuous Reinforced Insulation Type 1 0 to Aux and Network Inputs to Outputs Type tested for 60 s 720V DC 1 0 to Aux and Network Inputs to Outputs Publication 2080 SG001C EN P September 2012 Micro800 Programmable Controller Selection Guide 13 General Specifications 24 point controllers 2080 LC30 240WB 2080 LC30 240VB C300 R150 2080 LC30 24QWB only Attribute 2080 LC30 240BB Pilot duty rating Micro830 48 Point Controllers QD Allen Bradley SOW Saas str Sis 6 77 78 8 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 2627 N Q3 Allen Bradley Allen Bradley Allen Bradley Allen Bradley Allen Bradley y Gee Vale ae eoicie cece eeelcece ecco oes ON s C General Specifications 48 point controllers Attribute 2080 LC30 48AWB 2080 LC30 480WB 2080 LC30 480VB 2080 LC30 480BB Input circuit type 120V AC 24V DC sink source standard and high speed Output circuit type Relay 24V DC sink standard and 24V DC source standard and high speed high speed Event input interrupt Yes inputs 0 15 only support 1 0 rating Input 120V AC 16 mA Input 24V DC 8 8 mA Input 24V DC 8 8 mA Output 2 A 240V AC Output 2 A 240V AC Output 24V DC 1 A per point Surrounding air temperature 30 C general use general use 24 V DC 0 3 A per point Surrounding air temperature 65 C Pilot duty rating C300 R150 Isolation volt
6. Make Break 120V AC 15A 1800V A 240V AC 75A 0 75 A 24V DC 10A 1 0A 28V A 125V DC 0 22 A For relay life chart see the Specifications section of the Micro830 and Micro850 User Manual publication 2080 UMO002 Environmental Specifications Attribute Temperature operating Value 20 65 C 4 149 F IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock Temperature surrounding air max 65 C 149 F Temperature non operating Relative humidity 40 85 C 40 185 F 5 95 non condensing IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock IEC 60068 2 30 Test Db Unpackaged Damp Heat Vibration 2g Q 10 500 H IEC 60068 2 6 Test Fc Operating Z Shock operating 25g IEC 60068 2 27 Test Ea Unpackaged Shock Shock non operating DIN mount 25 g PANEL mount 35 g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions CISPR 11 Group 1 Class A Publication 2080 SG001C EN P September 2012 20 Micro800 Programmable Controller Family Selection Guide Environmental Specifications Attribute Value ESD immunity IEC 61000 4 2 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC
7. W Expansion 1 0 2085 1016 0 85 W system bus power consumption 2085 I1Q327T 0 95 W 2085 IA8 075W 2085 IM8 075W 2085 0A8 0 90W 2085 0B16 1 00W 2085 0V16 1 00W 2085 OW8 1 80W 2085 OW16 3 20W 2085 IF4 170W 2085 IF8 175W 2085 0F4 370W 2085 IRT4 2 00W 1 When setting up a Micro800 system veri y that total power consumption of the controller plug in and expansion 1 0 does not exceed the output power capacity of the power supply used See External Power Supply 2080 PS120 240VAC on page 50 for power supply specifications Micro800 Controller Analog 1 0 comparison Analog Accuracy Level Required Low Component Recommended Micro810 4 channel embedded analog 10 bit non isolated 0 10V inputs 2 accuracy with user calibration limited filtering each channel shared with digital input Medium Micro830 with plug ins 12 bit non isolated 0 10V 0 20 mA 1 Accuracy inputs and outputs 14 bit non isolated RTD TC 1 C accuracy 200 ms ch 50 60 Hz filtering High Publication 2080 SG001C EN P September 2012 Micro850 with expansion 1 0 input 14 bit isolated 0 10V 4 20 mA 8 ms update rate with or without 50 60 Hz rejection output 12 bit isolated 10 10V 0 20 mA 40 5 3 0 C accuracy for Thermocouple inputs 0 2 0 6 C accuracy for RTD inputs Micro800 Programmable Controller Fam
8. output 120 mA Q 24V 38mA 0 5 A 48V DC 5 28V DC 480V A for 240V AC resistive loads 0 22 A 125V DC 0 93 A steady state 60V A for 30V DC resistive loads 2A 125V AC 30V DC 24V A for 48V DC resistive loads 2 A 240V AC 0 5 A steady state 27 5V A for 125V DC resistive loads 48V DC 0 22 A steady state 125V DC 2 0 A steady state 15 A make 125V AC PF cos 0 0 4 2 0 A steady state 7 5 A make 240V AC PF cos 020 4 Publication 2080 SG001C EN P September 2012 Micro800 Programmable Controller Family Selection Guide 47 Catalog Output power inductive break max Pilot duty Minimum load per Initial contact Output delay time rating point resistance of relay max max 2080 OW4l 180 VA for 125V AC inductive loads C300 R150 10mA 30 mQ 10 ms ON or OFF 180 VA for 240V AC inductive loads 28 VA for 28 8V DC inductive loads 28 VA for 48V DC inductive loads 28 VA for 125V DC inductive loads Catalog Relay contact 0 35 power factor Volts max Amperes Amperes Volt Amperes Continuous Make Break Make Break 2080 OW4l 120V AC 15A 15A 20A 1800V A 180V A 240V AC 75A 0 75 A 24V DC 1 0 A 1 0 A 28V A 125V DC 0 22 A Catalog Operating Non operating Surrounding Relative Shock Shock temperature temperature air max humidity operating non operating 2080 0WAI ER 65 C 40 85 C 65 C 149 F 5 9
9. s o pr o eon oom A s eue pepe CXOX XE SSOHOVE Micro800 Programmable Controller Family Selection Guide 45 Micro800 Plug In Modules GB Alien Bradiey Digital Input Output Relay and Combination Plug Ins Specifications 2080 104 2080 1040B4 2080 1040V4 2080 0B4 2080 0V4 Catalog Input Output On state voltage On state current 2080 104 4 inputs DC DC 9 0V DC min 2 0 mA Q 9V DC min 30V DC max 3 0 mA Q 24V DC nom AC 5 0 mA max 10 25V AC rms min AC 30V AC rms max 2 0 mA 9V AC rms min 5 0 mA max 2080 I040B4 4 channel DC Input DC Input inputs source 9 0V DC min 2 0 mA 9V DC min outputs combination 30V DC max 3 0 mA Q 24V DC nom AC Input 5 0 mA max 2080 1040V4 SURE ipit 10 25V AC rms min AC Input Sut m OUTPUTS 30V AC rms max 2 0 mA 9V AC rms min combination Output 5 0 mA max 10V DC min Output 24V DC nom 5 0 mA 10V DC min 30V DC max 0 5 A max steady state 2 A surge 2 s min 2080 0B4 4 source outputs 10V DC min 5 0 mA 10V DC min 7 24V DC nom 0 5 A max steady state 2080 0V4 4 sink outputs 30V DC max 2 A surge 2 s min Publication 2080 SG001C EN P September 2012 46 Micro800 Programmable Controller Family Selection Guide Specifications 2080 104 2080 1040B4 2080 1040V4 2080 0B4 2080 0V4 Catalog Off st
10. six high speed counters HSC and choose from nine HSC operation modes HSC is supported on all Micro830 and Micro850 catalogs except on 2080 LCxx xxAWB PTO is only supported on Micro830 and Micro850 catalog numbers that end in BB or VB This selection guide serves to help you identify the right controller plug ins expansion I O and accessories based on your requirements 2 Select a Micro810 controller go to page 7 Select Micro800 l Select a Micro830 Plug Ins and Select Micro850 controller go to page 9 Accessories Expansion 1 0 go to page 43 go to page 25 Select a Micro850 controller go to page 15 Micro800 Controllers Comparison Micro810 Micro830 Micro850 12 point 10 point 16 point 24 point 48 point 24 point 48 point Communication ports embedded USB 2 0 with USB adapter USB 2 0 non isolated RS232 RS485 non isolated combo serial USB 2 0 non isolated RS232 RS485 non isolated combo serial 10 100 Base T Ethernet port RJ 45 Base programming port USB 2 0 with USB adapter Any standard USB printer cable will work Embedded USB 2 0 non isolated Any standard USB printer cable will work Embedded USB 2 0 non isolated Any standard USB printer cable will work 10 100 Base T Ethernet port RJ 45 Base digital 1 0 points see Number and Types of Inputs Outputs for Micro810 Micro830 and Micro850 Catalogs on page 5 24 48
11. supply plug in modules and four expansion 1 0 modules attached Micro850 controllers are suitable for applications that require more digital and analog I O or higher performance analog I O These controllers can support up to four expansion I O It comes in a 24 point and 48 point form factor with an embedded Ethernet port Micro850 controllers include e Expansion I O support e upto six High Speed Counter inputs Hsc e 100 kHz speed HSC available on 24V DC models e upto three embedded Pulse Train Outputs PTO for basic positioning e High speed input interrupts e Modbus RTU protocol serial port e Modbus TCP Server support e EtherNet IP Server support e CIP Serial Server e Embedded USB programming and serial port RS232 485 e Embedded 10 100 Base T Ethernet port RJ45 e Plug in slots to customize according to needs To help you select a Micro850 controller see the following specifications 1 2 HSC is supported on all Micro850 catalog numbers except on 2080 LC50 xxAWB PTO is supported on Micro850 catalog numbers ending in BB or VB Publication 2080 SG001C EN P September 2012 16 Micro800 Programmable Controller Family Selection Guide Micro850 Controllers Number and Types of Inputs and Outputs Catalog Number Inputs Outputs PTO HSC 120v 2av Relay 2av Jzay SUPPOE Support AC DC Sink Source VAC 2080 LC50 24AWB 14 10 2080 LC50 240BB 14 10 2 4 2080 LC50
12. 0 12 16 24 48 Input Type A 110V AC or 110 220V AC Q 24V AC DC D 12V DC 1 Available for Micro810 only Connected Components Connected Components Workbench is the programming and configuration software environment for the Micro800 controllers and our Connected Workbench Software Components products offering It simplifies setup and usage enabling applications ranging from simple Smart Relay up to Standalone Machine control Visit the website for the most up to date product information downloads and tools http ab rockwellautomation com Programmable Controllers Connected Co mponents Workbench Software Attribute Basic Delivery Download for FREE from the Connected Components Workbench web page at http ab rockwellautomation com Programmable Controllers Connected Components Workbench Software Packaging options Available on DVD orderable from Connected Components Workbench web page at http ab rockwellautomation com Programmable Controllers Connected Components Workbench Software Features e LD FBD and ST editors user defined function blocks No activation needed Optional registration during installation for product updates and notices Publication 2080 SG001C EN P September 2012 Number and Types of Inputs Outputs Select a Micro810 Controller 1 l i ececooooeoooo5 Micro810 Allen Bradley As the smallest of the Micro800 family the Micro810 controller is available i
13. 00 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions KC 1 See the Product Certifica Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 ion link athttp www rockwellautomation com products certification for Declaration of Conformity Certificates and other certification details Publication 2080 SG001C EN P September 2012 36 Micro800 Programmable Controller Family Selection Guide Publication 2080 SG001C EN P September 2012 Select Micro800 Plug in Modules and Accessories eee LN Input Micro800 plug in modules extend the functionality of embedded I O without increasing the footprint of the controller It improves performance by adding additional processing power or capabilities and adds additional communication functionality Micro830 controllers support plug in modules Micro800 accessories consist of an LCD with keypad a USB adapter and an expansion power supply Publication 2080 SG001C EN P September 2012 44 Micro800 Programmable Controller Family Selection Guide Micro800 Plug In Modules and Accessories Feature and Compatibility Plug in Accessory Supported by Micro810 Supported by Feature Micro830 Micro850 1 5 LCD and Keypad Yes No e backup modu
14. 1 Industrial Emissions EtherNet IP ODVA conformance tested to EtherNet IP specifications KC 1 See the Product Certifica Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 ion link at http Awww rockwellautomation com products certification for Declaration of Conformity Certificates and other certification details L 1 2 3 4 5 e 7 H s n a n i is n n n ms p a Select Micro850 Expansion 1 0 The 2085 I O expansion modules provide superior functionality in a small sized low cost package A variety of digital and analog modules complement and extend the capabilities of Micro850 controllers by maximizing the flexibility of I O count and type Micro850 expansion I O modules include high density discrete and analog I O modules including a high accuracy RTD and Thermocouple module There are available solid state output modules which are recommended to reduce switching noise and for applications which require more switching cycles than relays Triac outputs are available for AC loads Sink and source transistor outputs are available for DC loads The following section provides the list of available Micro850 expansion I O modules and their specifications Micro850 Expansion 1 0 Modules Catalog Number Type Description 2085 1A8 Discrete
15. 240VB 14 10 2 4 2080 LC50 240WB 14 10 4 2080 LC50 48AWB 28 20 2080 LC50 480BB 28 20 3 6 2080 LC50 480VB 28 20 3 6 2080 LC50 480WB 28 20 6 1 Maximum number of HSC supported Micro850 24 Point Controllers Alen Bradey lPexESCSCYCYCYOYCXCOYCYOYOYOYODIOD QD Allen Bradley Allen Bradley QD Allen Bradley m oen m uw ma NH once m ow 4567 8 9 OUT Micro850 e j DUOCOOQOCOOOOOOOOOULUCU d BE General Specifications 2080 LC50 24AWB 2080 LC50 240WB 2080 LC50 240VB 2080 LC50 240BB Attribute 2080 LC50 24AWB 2080 LC50 240BB Number of 1 0 24 14 inputs 10 outputs Dimensions HxWxD 90 x 158 x 80 mm 3 54 x 6 22 x 3 15 in Shipping weight approx 0 423 kg 0 933 Ib Publication 2080 SG001C EN P September 2012 Micro800 Programmable Controller Family Selection Guide 17 General Specifications 2080 LC50 24AWB 2080 LC50 240WB 2080 LC50 240VB 2080 LC50 240BB Attribute 2080 LC50 24AWB 2080 LC50 240WB 2080 LC50 240VB 2080 LC50 240BB Wire size Solid 0 2 mm2 24 AWG 2 5 mm 14 AWG rated 90 C 194 F insulation max Stranded 0 2 mm 24 AWG 2 5 mm 14 AWG Wiring category 2 on signal ports 2 on power ports 2 on communication ports Wire type Use copper conductors only Terminal screw torque 0 6 Nm 4 4 Ib in max using a 2 5 mm 0 10 in flat blade screwdriver Input circuit type 120V AC 24V DC sink source standa
16. 24V DC 1 6 A 38 4 W max Publication 2080 SG001C EN P September 2012 1 Any fluctuation in voltage source must be within 85V 264V Do not connect the adapter to a power source that has fluctuations outside of this range 2 When setting up a Micro800 system verify that total power consumption of the controller plug in and expansion I O does not exceed the output power capacity of the power supply used Micro800 Programmable Controller Family Selection Guide 51 For More Information Additional Resources Visit the Micro800 website at http ab rockwellautomation com Programmable Controllers Micro800 to learn more about Micro800 products and download Connected Component Workbench software and Micro800 firmware updates If you would like a manual you can download a free electronic version from the Internet http rockwellautomation com literature purchase a printed manual by contacting your local Allen Bradley distributor or Rockwell Automation representative P You can also visit the following websites for additional technical information Sample Code Library http samplecode rockwellautomation com idc groups public docume nts webassets sc home page hcst Technical Forums http www rockwellautomation com forums Connected Component Accelerator Toolkit http www rockwellautomation com components connected ccat html These documents contain additional information concerning relate
17. 5 2gQ10 500Hz 10g DIN rail 149 F 40 185 F noncondensing mounting 25 g Panel mounting 35g Analog Input and Output Plug ins A Allen Bradley Specifications 2080 IF2 2080 IF4 2080 OF2 Catalog Number of Voltage Current Power Input impedance Voltage inputs range range consumption resistive load 2080 OF2 outputs Tiene m e 2080 IF2 2 inputs unipolar 0 10V 0 20mA 60 mA Q gt 100 kQ for voltage non isolated 3 3V mode Pepe tee 250 Qfor current 2080 IFA 4 inputs unipolar mode non isolated 2080 0F2 2 outputs unipolar 60 mA Q 24V 1 KQ min non isolated Catalog Current Mounting Terminal screw Wire size Operating Non operating Surrounding North resistive torque torque temp temp air max American load temp code 2080 IF2 0 2 Nm 0 22 0 25 Nm Solid 20 65 C 40 85 C 65 C 149 F T4 1 48 Ib in 1 95 2 21 0 14 mm 26 AWG min 4 149 F 40 185 F 2080 IFA Ip in 1 5 mm 16 AWG max using a 2 5 mm Stranded 2000 OZ ae 0 10 in 0 14 mp 26 AWG min flat blade 1 0 mm 18 AWG max screwdriver rated 90 C 194 F insulation max Publication 2080 SG001C EN P September 2012 48 X Micro800 Programmable Controller Family Selection Guide 19 Allen Bradley 2080 RTD2 1 4 S E 8 CH1 CHI CHIL NC NC NC A CHO H1 CHIL NC NC NC COCOORSIOIO 6858606260 2080 TC2 EE ae ee et fe B CHISICH
18. 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 5096 Pulse 100 AM 900 MHz 10V m with 200 Hz 5096 Pulse 100 AM 1890 MHz 10V m with 1 kHz sine wave 8096 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 2 kV 5 kHz on power ports 2 kV 5 kHz on signal ports 1 kV 5 kHz on communication ports Surge transient immunity IEC 61000 4 5 1 kV line line DM and 2 kV line earth CM on AC power ports 1 kV line line DM and 2 kV line earth CM on signal ports 1 kV line earth CM on communication ports Conducted RF immunity Certifications Certification when product is marked 1 c UL us IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Value UL Listed Industrial Control Equipment certified for US and Canada See UL File E322657 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E334470 CE C Tick European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B European Union 2006 95 EC LVD compliant with EN 61131 2 Programmable Controllers Clause 11 Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions EtherNet IP ODVA conform
19. 8 point 120V AC input 2085 IM8 Discrete 8 point 240V AC input 2085 048 Discrete 8 point 120 240V AC Triac Output 2085 1016 Discrete 16 point 12 24V DC Sink Source Input 2085 1032T Discrete 32 point 12 24V DC Sink Source Input 2085 0V16 Discrete 16 point 12 24V DC Sink Transistor Output 2085 0B16 Discrete 16 point 12 24V DC Source Transistor Output 2085 0W8 Discrete 8 point AC DC Relay Output 2085 0W16 Discrete 16 point AC DC Relay Output Publication 2080 SG001C EN P September 2012 26 Micro800 Programmable Controller Family Selection Guide Publication 2080 SG001C EN P September 2012 Micro850 Expansion 1 0 Modules Catalog Number Type Description 2085 IF4 Analog 4 channel 14 bit isolated voltage current input 2085 IF8 Analog 8 channel 14 bit isolated voltage current input 2085 OF4 Analog 4 channel 12 bit isolated voltage current output 2085 IRT4 Specialty 4 channel 16 bit RTD and TC isolated input module 2085 ECR Terminator 2085 bus terminator 1 The 2085 ECR bus terminator should always be the last module on the system if any expansion 1 0 module is attached to the system 2 Refers to isolation from field side wiring to controller not channel to channel isolation Discrete Expansion I 0 2085 1016 and 2085 1032T DC Sink Source Input Modules Attribute Number of inputs 2085 1016 2085 1032T 16 sink source 32 sink source Dimensions HxWxD 44 5 x
20. 90 x 87 mm 1 75 x 3 54 x 3 42 in Shipping weight 220 g 7 76 oz approx Bus current draw max 170 mA 5V DC 190 mA 5V DC Wire size 0 25 2 5 mm 22 14 AWG solid or stranded copper wire rated 75 C 167 F or greater 1 2 mm 3 64 in insulation max Wiring category 2 on signal ports Terminal screw torque 0 5 0 6 Nm max 44 5 3 Ib in J9 Input circuit type 24V AC DC sink source Power dissipation total 4 5 W 7W Power supply 24V DC Status indicators 16 yellow indicators 32 yellow indicators Isolation voltage 50V continuous Reinforced Insulation Type channel to system Type tested 720V DC for 60 s Enclosure type rating Meets IP20 North American temp code T4 Operating voltage range 10 30V DC Class 2 21 6 26 4V AC Class 2 See Derating Curve for 2085 1016 and Derating Curve for 2085 I032T on page 27 Off state voltage max 5V DC Micro800 Programmable Controller Family Selection Guide 2085 1016 and 2085 1032T DC Sink Source Input Modules 21 Attribute 2085 1016 2085 1032T Off state current max 1 5mA 1 2mA On state current min 1 8 mA 10V DC On state current nom 6 0 mA 24V DC 5 2 mA Q 24V DC On state current max 8 0 mA Q 30V DC 7 0 mA Q 30V DC Input impedance max 3 9 KQ 4 6 KQ IEC input compatibility Type 3 Type 1 1 Meets IEC Type 1 24V DC Input Specifications 2 Use this Cond
21. I CJC NC NC NC AJCHO CHO CJC NC NC ve at uet OGON 632606 Catalog Type Common mode rejection ratio 2080 RTD2 2 channel 100 dB non isolated RTD 50 60Hz 2080 TC2 2 channel non isolated Thermocouple Catalog Wire size 2080 RTD2 Solid 0 14 mm 26 AWG min 2080 TC2 1 5 mm 16 AWG max Stranded 0 14 mm 26 AWG min 1 0 mm 18 AWG max rated 90 C 194 F insulation max AD Allen Bradley 2080 TRIMPOT 0 1 2 4 1 Publication 2080 SG001C EN P September 2012 Thermocouple and RTD 2080 TC2 2080 RTD2 Specifications 2080 RTD2 2080 TC2 Type Common mode rejection ratio 100 dB 50 60Hz Catalog 2080 RTD2 2 channel non isolated RTD 2080 TC2 2 channel non isolated Thermocouple Normal mode RTD types Thermocouple rejection ratio supported types supported 70 dB 50 60 Hz 100 Q Platinum 385 200 Q Platinum 385 500 Q Platinum 385 1000 Platinum 385 100 Q Platinum 392 200 2 Platinum 392 500 Q Platinum 392 1000 Q Platinum 392 10 Q Copper 427 20 Q Nickel 672 604 Q Nickel lron 518 J K N T E R S B Operating Non operating Surrounding air max temperature temperature 20 65 C 40 85 C 65 C 149 F 4 149 F 40 185 F Trimpot Analog Input 2080 TRIMPOT6 Specifications 2080 TRIMPOT6 Normal mode rejection ratio 70 dB 50 60 Hz Terminal screw t
22. Micro800 Programmable Controller Family Allen Bradley Bulletin 2080 Selection Guide THINK Rockwell SOLVE Allen Bradley Rockwell Software Automation Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls publication SGI 1 1 available from your local Rockwell Automation sales office or online at http rockwellautomation com literature describes some important differences between solid state equipment and hard wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software des
23. Outputs AC input filter setting 16 ms for all embedded inputs In Connected Components Workbench go to the Embedded 1 0 configuration window to re configure the filter setting or each input group 1 See the Micro810 User Manual publication 2080 UM001 for more Micro810 controller specifications For relay life chart see the Specifications section of the Micro810 User Manual publication 2080 UMO001 Publication 2080 SG001C EN P September 2012 Select a Micro830 Controller The Micro830 controller allows integration of as many as five plug in modules The plug in modules enable machine builders to personalize the controllers to increase functionality It also offers removable terminal blocks most models and simplified communication via serial port The controllers include up to six High Speed Counter inputs Hsc 100 kHz speed HSC available on 24V DC models up to three embedded Pulse Train Outputs PTO for basic positioning High speed input interrupts Modbus RTU protocol serial port CIP Serial to allow tighter integration with PanelView Component Embedded USB programming and serial port RS232 485 Plug in slots to customize according to needs To help you select a Micro830 controller check out the specifications for each catalog in the next section 1 HSC is supported on all Micro830 catalog numbers except on 2080 LC30 xxAWB 2 PTO is supported on Micro830 catalog numbers end
24. V DC Class 2 12 24V DC Class 2 Power consumption OVA 3W 0 rating Input 120 240V AC Input 24V DC 8 mA Input 12V DC 8mA Input 24V DC 8 mA Output Relay 00 amp 01 8 A 240V AC B300 R300 General Use Relay 02 amp 03 4 A Q 240V AC C300 R150 General Use Output 24V DC 1A 25 C 24V DC 0 5A 55 C Operating temperature 0 55 C 32 131 F Shipping weight approx 0 203 kg 0 448 Ib Wire size 0 32 2 1 mm 22 14 AWG solid copper wire or 0 32 1 3 mm 22 16 AWG stranded copper wire rated 90 C 194 F insulation max Wiring category 2 on signal ports 2 on power ports Wiring torque 1 085 Nm 8 Ib in Wire type use Copper Conductors only Fuse type Rated 250V 3 15 A RADIAL Enclosure type rating Meets IP20 North American temp code T5 Insulation stripping length 7 mm 0 28 in Isolation voltage 250V continuous Reinforced Insulation Type 0 to Aux and Network nputs to Outputs Type tested for 60 s 3250V DC 0 to Aux and Network nputs to Outputs 250V continuous Reinforced Insulation Type 1 0 to Aux and Network Inputs to Outputs Type tested for 60 s 720V DC Inputs to Aux and Network 3250V DC Outputs to Aux and Network Inputs to Outputs 50V continuous Reinforced Insulation Type 1 0 to Aux and Network Inputs to Outputs Type tested for 60 s 720V DC 1 0 to Aux and Network Inputs to
25. age 250V continuous 250V continuous 50V continuous Reinforced Insulation Type 1 0 to Aux and Reinforced Insulation Type Reinforced Insulation Type Network Inputs to Outputs Outputs to Aux and Network Outputs to Aux and Type tested for 60 s 720V DC 1 0 to Aux and Network Inputs to Outputs Network Inputs to Outputs Inputs to Outputs Type tested for 60 s Type tested for 60 s 3250V DC 1 0 to Aux and 720V DC Inputs to Aux and Network Inputs to Outputs Network 3250V DC Outputs to Aux and Network Inputs to Outputs For relay life chart see the Specifications section of the Micro830 and Micro850 User Manual publication 2080 UM002 Publication 2080 SG001C EN P September 2012 14 Micro800 Programmable Controller Selection Guide Embedded Serial Port Cables Embedded Serial Port Cable Selection Chart Connectors No Connectors 8 pin Mini DIN to 8 pin Mini DIN 0 5 m 1 5 ft 1761 CBL AMOQ 8 pin Mini DIN to 9 pin D Shell 0 5 m 1 5 ft 1761 CBL APoo 8 pin Mini DIN to 8 pin Mini DIN 2 m 6 5 ft 4761 cBL HMo2 8 pin Mini DIN to 9 pin D Shell 8 pin Mini DIN to 6 pin RS 485 terminal block 2 m 6 5 ft 30 cm 11 8 in 1761 CBL PMo2 1763 NC01 series A 1 Series C or later for Class 1 Div 2 applications Publication 2080 SG001C EN P September 2012 Select a Micro850 Controller rer Fa p ad JT A Micro850 controller with a power
26. amily Selection Guide 29 2085 1A8 2085 IM8 2085 0A8 AC Input Output Modules Attribute Status indicators 2085 IA8 8 yellow indicators 2085 IM8 2085 0A8 Isolation voltage 150V continuous Reinforced Insulation Type 240V continuous Reinforced Insulation Type channel to system Type tested 3250V DC for 60 s channel to system Type tested 1950V DC for 60 s North American temp code T4 1 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines p blication 1770 4 1 2 RTB hold down screws should be tightened by hand They should not be tightened using a power tool Input Specifications 2005 IA8 and 2085 IM8 Attribute 2085 1A8 2085 IM8 Number of Inputs 8 Voltage category 120V AC 240V AC Operating voltage range 74 120V AC 159 240V AC Off state voltage max 20V AC 40V AC Off state current max 25mA On state current min 5 0 mA Q 74V AC 4 0 mA Q 159V AC On state current max 12 5 mA Q 120V AC 7 0 mA Q 240V AC Input impedance max 22 2 KQ Inrush current max 450 mA Input filter time 20 ms Off to On On to Off IEC type compliance Type 3 Output Specifications 2085 0A8 Attribute 2085 0A8 Number of Inputs 8 Voltage category 120V 230V AC Operating voltage range 120 240V AC Output voltage min 85V AC Output voltage max 240V AC Of
27. ance tested to EtherNet IP specifications KC 1 See the Product Certifica Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 ion link at http Awww rockwellautomation com products certification for Declaration of Conformity Certificates and other certification details Publication 2080 SG001C EN P September 2012 Micro800 Programmable Controller Family Selection Guide 21 Micro850 48 Point Controllers MAC ID 7 wweccemmp 0123456789 10 11 12 13 14 15 16 17 18 19 2021 22 232425227 N MS Ks v m c mo mov 0123456789 30 11 12 13 14 15 16 17 18 19 our General Specifications 2080 LC50 48AWB 2080 LC50 480WB 2080 LC50 480VB 2080 LC50 480BB Attribute Number of 1 0 2080 LC50 48AWB 2080 LC50 480WB 2080 LC50 480VB 48 28 inputs 20 outputs 2080 LC50 480BB Dimensions HXWxD 90 x 238 x 80 mm 3 54 x 9 37 x 3 15 in Shipping weight approx 0 725 kg 1 60 Ib Wire size Solid rated 90 C 194 F insulation max 0 2 mm2 24 AWG 2 5 mm 14 AWG Stranded 0 2 mm2 24 AWG 2 5 mm 14 AWG Wiring category 2 on signal ports 2 on power ports 2 on communication ports Wire type Terminal screw torque Use copper conductors only 0 4 0 5 Nm 3 5 4 4 Ib in using a 0 6 x 3 5 mm flat blade screwdriver In
28. ate voltage Off state Power supply Mounting torque Status North American current voltage indicators temp code 2080 104 DC DC 0 2 Nm 4 yellow T4 5V DC max 1 5 mA max 1 48 Ib in 2080 I040B4 10 8V DC min 8 yellow AG 30V DC max 2080 1040V4 3 5V AC rms i 2080 0B4 2080 0V4 4 yellow Catalog Terminal base screw torque Isolation voltage Wire size 2080 104 0 22 0 25 Nm 50V continuous Basic Insulation Type Inputs to 0 2 2 5 mm 24 12 AWG solid or 1 95 2 21 Ib in Backplane stranded copper wire rated 90 C using a 2 5 mm 0 10 in Type tested for 60 s 720V DC Inputs to Backplane 194 F or greater insulation max 3 flat blade screwdriver 2080 I040B4 50V continuous Basic Insulation Type Inputs to P Outputs I Os to Backplane 2080 040V4 Type tested for 60 s 720V DC I Os to Backplane 2080 0B4 2080 0V4 Catalog Operating Non operating Surrounding Relative Vibration Shock Shock temperature temperature air max humidity operating non operating 2080 104 20 65 C 40 85 C 65 C 149 F 5 95 2g 10 500Hz 25g 25g 4 149 F 40 185 F noncondensing 2080 I040B4 2080 I040V4 2080 0B4 2080 0V4 Specifications 2080 0WA4l Catalog Input Output Inrush current Backplan Output current Output current Output power resistive max e power resistive inductive 2080 OW4l 4 channel 120 mA Q 3 3V 3 3 VDC 2A 5 30V DC 1 0A steady state 250V A for 125V AC resistive loads relay
29. cribed in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Throughout this manual when necessary we use notes to make you aware of safety considerations Identifies information about practices or circumstances that can cause an explosion in a hazardous environment which may lead to personal injury or death property damage or economic loss IMPORTANT Identifies information that is critical for successful application and understanding of the product ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death property damage or economic loss Attentions help you identify a hazard avoid a hazard and recognize the consequence SHOCK HAZARD Labels may be on or inside the equipment such as a drive or motor to alert people that dangerous voltage may be present BURN HAZARD Labels may be on or inside the equipment such as a drive or motor to alert people that surfaces may reach dangerous temperatures lala Allen Bradley Rockwell Automation Micro800 Micro810 Micro830 Micro850 Connected Components Workbench and TechConnect are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies Select a Micro800 Controller Micro800 controllers are designed for low cost standalon
30. d Rockwell Automation products Resource Description Micro810 Programmable Controllers A more detailed description of how to install and use your User Manual publication Micro810 programmable controller 2080 UMO01 Micro830 and Micro850 Programmable Controllers User Manual publication 2080 UM002 A more detailed description of how to install and use your Micro830 and Micro850 programmable controller Industrial Automation Wiring and Provides general guidelines for installing a Rockwell Grounding Guidelines publication Automation industrial system 1770 4 1 Product Certifications website Provides declarations of conformity certificates and other http Awww rockwellautomation com certification details products certification Publication 2080 SG001C EN P September 2012 52 Micro800 Programmable Controller Family Selection Guide Publication 2080 SG001C EN P September 2012 Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products At http www rockwellautomation com support you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect support pro
31. e machines These economical small size PLCs are available in different form factors based on the number of I O points embedded in the base with a range of features intended to address different requirements The Micro800 family shares programming environment accessories and plug ins that allow machine builders to personalize the controller for specific capabilities Micro810 controllers function as a smart relay with high current relay outputs but with the programming capabilities of a micro PLC The Micro810 controllers come in a 12 point form factor Micro830 controllers are designed for standalone machine control applications They have flexible communications and I O capabilities with up to five plug ins They come as a 10 16 24 or 48 point form factors Micro850 expandable controllers are designed for applications that require more digital and analog I O or higher performance analog I O They can support up to four expansion I O Micro850 controllers include additional communication connection options through an embedded 10 100 Base T Ethernet port Publication 2080 SG001C EN P September 2012 2 Micro800 Programmable Controller Family Selection Guide Choose a Micro800 Controller Select a Micro800 controller go to page 2 Features Attribute Several Micro830 and Micro850 controllers support basic positioning through embedded pulse train outputs PTO These controllers also allow you to configure up to
32. emperature Non operating Surrounding air max North American temperature temp code 20 65 C 4 149 F 40 85 C 65 C 149 F T4 40 185 F Publication 2080 SG001C EN P September 2012 50 Micro800 Programmable Controller Family Selection Guide Micro800 Accessories Micro800 LCD 2080 LCD operating surrounding air max nonoperating temp code 20 55 C 55 C 131 F 40 85 C 40 185 F T5 4 131 F Micro810 USB Adapter 2080 USBADAPTER USB cable Temperature Temperature Temperature North connector type operating surrounding air max non operating American temp code USB Type A B 20 55 C 55 C 131 F 40 85 C T5 Male Male 4 131 F 40 185 F External Power Supply 2080 PS120 240VAC Attribute Value Dimensions HxWxD 90 x 45 x 80 mm 3 55 x 1 78 x 3 15 in Shipping weight 0 34 kg 0 75 Ib Supply voltage range 100V 120V AC 1A 200 240V AC 0 5A Supply frequency 47 63 Hz Supply power 24V DC 1 6A Inrush current max 24 A Q 132V for 10 ms 40 A Q 263V for 10 ms Power consumption Output power Power dissipation Input power 38 4 W 100V AC 38 4 W 240V AC 45 1 W 100V AC 44 0W 240V AC Isolation voltage 250V continuous Primary to Secondary Reinforced Insulation Type Type tested for 60s 2300V AC primary to secondary and 1480V AC primary to earth ground Output ratings
33. f state current max 25mA On state current min 10 mA per output On state current max 0 5 A per output On state current per module max 4A Off state voltage drop max 1 5V AC 0 5 A 2 5V AC 10 mA Publication 2080 SG001C EN P September 2012 30 Publication 2080 SG001C EN P September 2012 Micro800 Programmable Controller Family Selection Guide Output Specifications 2085 0A8 Attribute Fusing 2085 0A8 to protect outputs Not protected A suitable rating fuse is recommended Output signal delay Off to On On to Off Surge current max 5A 9 3 ms for 60 Hz 11 ms for 50 Hz 9 3 ms for 60 Hz 11 ms for 50 Hz 2085 OW8 and 2085 OW16 Relay Output Module Attribute 2085 0W8 2085 0W16 Number of outputs 8 relay 16 relay Dimensions HXWxD 28 x 90 x 87 mm 44 5 x 90 x 87 mm 1 10 x 3 54 x 3 42 in 1 75 x 3 54 x 3 42 in Shipping weight 140 g 4 93 oz 220 g 7 76 02 approx Wire size 0 25 2 5 mm 22 14 AWG solid or stranded copper wire rated 75 C 167 F or greater 1 2 mm 3 64 in insulation max Insulation strip length 10 mm 0 39 in Wiring category 2 on signal ports Wire type Copper Terminal screw 0 5 0 6 Nm orque max 44 5 3 Ib in 7 Bus current draw max 5V DC 120 mA 5V DC 160 mA 24V DC 50 mA 24V DC 100 mA Load current max 2A Power dissipatio
34. ges 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 5096 Pulse 100 AM 900 MHz 10V m with 200 Hz 5096 Pulse 10096 AM Q 1890 MHz 10V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 2 kV Q 5 kHz on power ports 2 kV 5 kHz on signal ports 1 kV Q 5 kHz on communication ports Surge transient immunity IEC 61000 4 5 1 kV line line DM and 2 kV line earth CM on power ports 1 kV line line DM and 2 kV line earth CM on signal ports 1 kV line earth CM on communication ports Conducted RF immunity 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Certifications IEC 61000 4 6 Value Certification whe h product is marked C UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File E322657 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E334470 CE C Tick European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B European Union 2006 95 EC LVD compliant with EN 61131 2 Programmable Controllers Clause 11 Australian Radiocommunications Act compliant with AS NZS CISPR 1
35. grams For more information contact your local distributor or Rockwell Automation representative or visit http www rockwellautomation com support Installation Assistance If you experience a problem within the first 24 hours of installation review the information that is contained in this manual You can contact Customer Support for initial help in getting your product up and running United States or Canada 1 440 646 3434 Outside United States or Use the Worldwide Locator at http www rockwellautomation com support americas phone en html or contact Canada your local Rockwell Automation representative New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures United States Contact your distributor You must provide a Customer Support case number call the phone number above to obtain one to your distributor to complete the return process Outside United States Please contact your local Rockwell Automation representative for the return procedure Documentation Feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature Rockwell Otomas
36. ily Selection Guide 5 Number and Types of Inputs Outputs Number and Types of Inputs Outputs for Micro810 Micro830 and Micro850 Catalogs Controller Catalogs Inputs Outputs Analog In PTO HSC Family 120VAC 120 24V 12V Relay 2aVDC 2avoc 0 10V _ Support Support 24V AC DC DC Source Sink bnt with VAC Micro810 2080 LC10 120WB 8 4 4 2080 LC10 12AWA 8 4 2080 LC10 120BB 8 4 4 2080 LC10 12DWD 8 4 4 Micro830 2080 LC30 100WB 6 4 2 2080 LC30 100VB 6 4 1 2 2080 LC30 16AWB 10 6 2080 LC30 160WB 10 6 2 2080 LC30 16QVB 10 6 1 2 2080 LC30 240WB 14 10 4 2080 LC30 24QVB 14 10 2 4 2080 LC30 240BB 14 10 2 4 2080 LC30 48AWB 28 20 2080 LC30 480WB 28 20 6 2080 LC30 48QVB 28 20 3 6 2080 LC30 480BB 28 20 3 6 Micro850 2080 LC50 24AWB 14 10 2080 LC50 240BB 14 10 2 4 2080 LC50 240VB 14 10 2 4 2080 LC50 240WB 14 10 4 2080 LC50 48AWB 28 20 2080 LC50 480WB 28 20 6 2080 LC50 480BB 28 20 3 6 2080 LC50 48QVB 28 20 3 6 1 Maximum number of HSC supported Publication 2080 SG001C EN P September 2012 6 Micro800 Programmable Controller Family Selection Guide Micro800 Catalog Number Details 2080 LC 30 24 Q VB o L power Supply Bulletin Number Al 120 240V AC Base Unit ET D 12v DC LC10 Micro810 LC30 Micro830 LC50 Micro850 Output Type B 24V DC Source V 24V DC Sink Number of 1 0 W Relay 1
37. ing in BB or VB only Publication 2080 SG001C EN P September 2012 10 Micro800 Programmable Controller Selection Guide Inputs and Outputs Micro830 Controllers Number and Type of Inputs Outputs Catalog Number Inputs Outputs PTO HSC 12V AC 24VDCNAC Relay 24VSink 24VSource SUPPOrt Sup port 2080 LC30 100WB 6 4 2 2080 LC30 100VB 6 4 1 2 2080 LC30 16AWB 10 6 2080 LC30 160WB 10 6 2 2080 LC30 16QVB 10 6 1 2 2080 LC30 240BB 14 10 2 4 2080 LC30 240VB 14 10 2 4 2080 LC30 240WB 14 10 4 2080 LC30 48AWB 28 20 2080 LC30 480BB 28 20 3 6 2080 LC30 480VB 28 20 3 6 2080 LC30 480WB 28 20 6 1 Maximum number of HSC supported Micro830 Controllers General Features Attribute 10 point 16 point 24 point 48 point 2080 LC30 100WB 2080 LC30 16AWB 2080 LC30 240WB 2080 LC30 48AWB 2080 LC30 100VB 2080 LC30 160WB 2080 LC30 240VB 2080 LC30 480WB 2080 LC30 160VB 2080 LC30 240BB 2080 LC30 480VB Number of 1 0 10 6 inputs 4 outputs 16 10 inputs 6 outputs 2080 LC30 480BB 24 14 inputs 10 outputs 48 28 inputs 20 outputs Dimensions HxWxD 90 x 100 x 80 mm 90 x 100 x 80 mm 90 x 150 x 80 mm 90 x 230 x 80 mm 3 54 x 3 94 x 3 15 in 3 54 x 3 94 x 3 15 in 3 54 x 5 91 x 3 15 in 3 54 x 9 06 x 3 15 in Shipping weight approx 0 302 kg 0 666 Ib 0 302 kg 0 666 Ib 0 423 kg 0 933 Ib 0 725 kg 1 60 Ib Operating temperature 20 65 C 4 149 F Wire size 0 14
38. k nonoperating EC 60068 2 27 Test Ea Unpackaged Shock 25 g for DIN Rail Mounting 35 g for Panel Mounting Emissions CISPR 11 Group 1 Class A ESD Immunity IEC 61000 4 2 6 kV contact discharges 8 kV air discharges Radiated RF Immunity IEC 61000 4 3 OV m with 1 kHz sine wave 8096 AM from 80 2000 MHz OV m with 200 Hz 5096 Pulse 100 AM 900 MHz OV m with 200 Hz 5096 Pulse 10096 AM 1890 MHz OV m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B Immunity IEC 61000 4 4 2 kV Q 5 kHz on signal ports Surge Transient Immunity IEC 61000 4 5 1 kV line line DM and 2 kV line earth CM on power ports 2 kV line earth CM on shielded ports Conducted RF Immunity IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Certifications All Micro800 Expansion 1 0 Modules Certification when Value product is marked 1 c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File E322657 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E334470 Micro800 Programmable Controller Family Selection Guide 35 Certifications All Micro800 Expansion 1 0 Modules Certification when product is marked 1 CE Value European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 610
39. le for Micro810 controllers 2080 LCD e configure Smart Relay Function Blocks Micro810 USB Adapter Yes USB programming access 2080 USBADAPTER External Power Supply Yes Yes optional controller power supply 2080 PS120 240VAC RS232 485 Isolated Serial Port No Yes e adds additional serial communications with Modbus 2080 SERIALISOL RTU and ASCII RS232 only protocols isolated for increased noise immunity Digital Input Output Relay and No Yes e 4 channel inputs outputs or combination modules Combination Modules 2080 104 2080 I040B4 e configurable as voltage and current inputs 2080 I040V4 2080 0B4 2080 0V4 f 2080 OWAI e sink or source output e Achannel relay outputs Non isolated Unipolar Analog No Yes e adds up to 20 embedded analog 1 0 with 12 bit Input Output resolution with 48 point controllers 2080 IF2 2080 IF4 2080 OF2 e 2 channels for 2080 IF2 2080 OF2 e Achannels for 2080 IF4 on isolated Thermocouple No Yes e for temperature control when used with PID 2080 TC2 e 2channels for 2080 TC2 and 2080 RTD2 on isolated RTD No Yes 2080 RTD2 Memory Module with RTC No Yes backup project data and application code 2080 MEMBAK RTC i e high accuracy real time clock 6 Channel Trim Potentiometer Analog No Yes adds six analog presets for speed position and nput 2080 TRIMPOT6 Publication 2080 SG001C EN P September 2012 temperature control G Allen Bradley 2080 IQ40V4 Lies AOT ERI
40. m 2 mA Q 120V AC 7 6 mA Q 24V DC 6 15 mA Q 24V DC On state current max 16 mA Q 132V AC 12 0 mA Q 30V DC Nominal impedance 12 kQ 50 Hz 3kQ 3 74 kQ 10 kQ 60 Hz IEC input compatibility Type 3 Inrush current max 250 mA 120V AC Input frequency max 63Hz Output Specifications Attribute 2080 LC50 48AWB 2080 LC50 480WB 2080 LC50 480VB 2080 LC50 480BB Relay Output Hi Speed Output Standard Output Outputs 0 through 3 Outputs 4 and higher Number of outputs 20 4 16 Output voltage min 5V DC 5V AC 10 8V DC 10V DC Output voltage max 125V DC 265V AC 26 4V DC 26 4V DC Load current min 10 mA Publication 2080 SG001C EN P September 2012 Micro800 Programmable Controller Family Selection Guide 23 Output Specifications Attribute 2080 LC50 48AWB 2080 LC50 480WB 2080 LC50 480VB 2080 LC50 480BB Relay Output Hi Speed Output Standard Output Outputs 0 through 3 Outputs 4 and higher Load current max 2 0A 100 mA high speed operation 1 0A 30 C 1 0 A 30 C 0 3 A 65 C standard operation 0 3 A 65 C standard operation Surge current per point Refer to Relay Contacts Ratings on page 19 4 0 A for 10 ms every 1 s 30 C every 2 s 65 ect Current per common max 5A Turn on time 10 ms 25 us 0 1 ms Turn off time max 1 ms 1 Applies for general purpose operation only Does not apply for high speed operation Relay Contacts Ratings Maximum Volt
41. mp code T4 1 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Publication 2080 SG001C EN P September 2012 18 Micro800 Programmable Controller Family Selection Guide DC Input Specifications 2080 LC50 240BB 2080 LC50 240VB 2080 LC50 240WB Attribute Number of Inputs Voltage category High Speed DC Input Inputs 0 7 24V sink source Standard DC Input Inputs 8 and higher Input group to backplane isolation Verified by one of the following dielectric tests 720V DC for 2 s 50V DC working voltage IEC Class 2 reinforced insulation On state voltage range 16 8 26 4V DC Q 65 C 149 F 16 8 30 0V DC 30 C 86 F 10 26 4V DC 65 C 149 F 10 30 0V DC 30 C 86 F Off state voltage 5V DC max Off state current 1 5 mA max On state current 5 0 mA 16 8V DC min 7 6 mA 24V DC nom 12 0 mA 30V DC max 1 8 mA Q 10V DC min 6 15 mA Q 24V DC nom 12 0 mA Q 30V DC max Nominal impedance 3 kQ 3 74 KQ IEC input compatibility Type 3 AC Input Specifications 2080 LC50 24AWB Attribute Value Number of inputs 14 On state voltage 79V AC min 132V AC max On state current 5 mA min 16 mA max Input frequency 50 60 Hz nom 47 Hz min 63 Hz max Off state voltage 20V AC 120V AC max Off state cu
42. n 2 72 W 5 14 W otal Relay contact 0 35 power factor Max Amperes Amperes Volt Amperes Volts Make Break Continuous Make Break 120V AC 15A 15A 20A 1800VA 180VA 240V AC 75A 0 75 A 24V DC 1 0A 10A 28V A 125VDC 022A Minimum load per 10 mA per point point Off state leakage max 1 5mA Status indicators 8 yellow indicators 16 yellow indicators Isolation voltage 240V continuous Reinforced Insu Type tested 3250V DC for 60 s ation Type channel to system Pilot duty rating C300 R150 Enclosure type rating North American temp code Meets IP20 T4 Micro800 Programmable Controller Family Selection Guide 31 1 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 2 RTB hold down screws should be tightened by hand They should not be tightened using a power tool Analog Expansion 1 0 2085 IF4 2085 IF8 2085 OF4 Analog Input and Output Modules Attribute 2085 IF4 2085 0F4 2085 IF8 Number of 1 0 4 8 Dimensions HxWxD 28 x 90 x 87 mm 44 5 x 90 x 87 mm 1 1 x 3 54 x 3 42 in 1 75 x 3 54 x 3 42 in Shipping weight 140 g 4 93 oz 220 g 7 76 oz approx Bus current draw max 5V DC 100 mA 5V DC 160 mA 5V DC 110 mA 24V DC 50 mA 24V DC 120 mA 24V DC 50 mA Wire size 0 25 2 5 mm 22 14 AWG solid or stranded copper wire rated 75
43. n a 12 point version with two 8 A and two 4 A outputs that eliminate the need for external relays The Micro810 features embedded smart relay function blocks that can be configured from a 1 5 LCD and keypad The function blocks include Delay OFF ON Timer Time of Day Time of Week and Time of Year for applications requiring a programmable timer and lighting control Programming can also be done through a program download via USB programming port using Connected Components Workbench Software To help you select a Micro810 controller consult the specifications for each catalog in the next section Catalog Number Power Inputs Outputs Analog In 0 10V 120VAC 240V AC 12 24VDC VAC Relay 24V DC SRC Shared with DC In 2080 LC10 120WB 24V DC 8 4 4 2080 LC10 12AWA 120 240V AC 8 4 2080 LC10 120BB 12 24V DC 8 4 4 2080 LC10 12DWD 12V DC 8 4 4 Publication 2080 SG001C EN P September 2012 8 X Micro800 Programmable Controller Family Selection Guide Specifications Attribute 2080 LC10 12AWA 2080 LC10 120WB 2080 LC10 12DWD 2080 LC10 120BB Number of 0 8 Input 4 digital 4 analog digital configurable 4 Output Dimensions 91 x 75 x 59 mm HxWxD 3 58 x 2 95 x 2 32 in Supply voltage range 85 263V DC 20 4 26 4V DC 10 8V 13 2V DC 11 4V 26 4V DC Supply frequency range 47 63 Hz AC supply Voltage range 100 240V AC 50 60 Hz 24V DC Class 2 12
44. nput 24V DC 8 8 mA Output 2 A 240V AC general use Input 24V DC 8 8 mA Output 2 A 24V DC 1 A per point Surrounding air temperature 30 C 24N d 0 3 A per point Surrounding air temperature 65 Isolation voltage 250V continuous Reinforced Insulation Type Outputs to Aux and Network Inputs to Outputs Type tested for 60 s 720V DC Inputs to Aux and Network 3250V DC Outputs to Aux and Network Inputs to Outputs 50V continuous Reinforced Insulation Type 1 0 to Aux and Network Inputs to Outputs Type tested for 60 s 720V DC 1 0 to Aux and Network Inputs to Outputs Pilot duty rating C300 R150 General Specifications 16 point controllers Attribute 2080 LC30 16AWB 2080 LC30 160WB 2080 LC30 160VB Input circuit type 120V AC 12 24 sink source standard 24V sink source high speed Output circuit type Relay 12 24V DC sink transistor standard and high speed Event input interrupt Yes support Publication 2080 SG001C EN P September 2012 12 Micro800 Programmable Controller Selection Guide General Specifications 16 point controllers Attribute 2080 LC30 16AWB 2080 LC30 160WB 2080 LC30 160VB 0 rating Input 120V AC 16 mA Output 2 A 240V AC general use Input 24V DC 8 8 mA Input 24V DC 8 8 mA Output 2 A 240V AC general use ce utput 24V DC 1 A per point Surrounding air temperature 30 C 24 V DC 0 3 A per point Surrounding air tempera
45. or better Accuracy drift with temp Voltage terminal 0 0045 96 Full Scale C Current terminal 0 0069 96 Full Scale C Resistive load on mA output 15 500 ohm Q 24V DC Publication 2080 SG001C EN P September 2012 Micro800 Programmable Controller Family Selection Guide 33 Specialty Expansion 1 0 2085 IRT4 Temperature Input Module Attribute Number of inputs 2085 IRT4 4 Dimensions HxWxD 44 5 x 90 x 87 mm 1 75 x 3 54 x 3 42 in Shipping weight approx Bus current draw max 220 g 7 76 02 5V DC 160 mA 24V DC 50 mA Wire size 0 25 2 5mm 22 14 AWG solid or stranded copper wire rated 75 C 167 F or greater 1 2 mm 3 64 in insulation max Wiring category 2 on signal ports Terminal screw torque Input type 0 5 0 6 Nm 44 5 3 Ib in 2 Thermocouple type B C E J K TXK XK L N R S T RTD type 100 Q Pt 0 00385 Euro 200 Q Pt 0 00385 Euro 100 Q Pt 0 003916 U S 200 Q Pt 0 003916 U S 100 Q Nickel 618 200 Q Nickel 618 120 Q Nickel 672 10 Q Copper 427 mV range 0 100 mV Ohm input 0 500 Q Resolution Channel update time typical 16 bits 12 500 ms per enabled channel Input impedance gt 10MQ Accuracy 0 5 3 0 C accuracy for Thermocouple inputs 0 2 0 6 C accuracy for RTD inputs Power dissipation total Enclosure type rating 2W Meets IP20 Status indicator
46. orque 0 22 0 25 Nm 1 85 2 21 Ib in using a 2 5 mm 0 10 in flat blade screwdriver North American temp code T4 Numberof Mounting Operating Non operating Surrounding North inputs torque temperature temperature air max American temp code 6 channel 0 2 Nm 20 65 C 40 85 C 65 C 149 F T4 Trimpot 1 48 Ib in 4 149 F 40 185 F B Allen Bra Allen Bradley 2080 MEMBAK RTC Backup Status loQ A Allen Bradley 2080 SERIALISOL Ke 8 DCD RXD TXD 5 AjH85 GND RTS CTS Micro800 Programmable Controller Family Selection Guide 49 Memory Backup and High Accuracy RTC Plug In 2080 MEMBAK RTC Specifications 2080 MEMBAK RTC Mounting Terminal Operating Non operating Surrounding North torque screw torque temperature temperature air max American temp code 0 2 Nm 0 22 0 25Nm 20 65 C 40 85 C 65 C T4 1 48 Ib in 1 95 2 21 4 149 F 40 185 F 149 F Ib in using a 2 5 mm 0 10 in flat blade screwdriver RS232 485 Serial Port Plug in 2080 SERIALISOL Specifications 2080 SERIALISOL Mounting Terminal screw torque Wire size Isolation torque voltage 0 2 Nm 0 22 0 25 Nm Solid 500V AC 1 48 Ib in 1 95 2 21 Ib in 0 14 1 5 mm 26 16 AWG using a 2 5 mm Stranded 0 10 in flat blade 0 14 1 0 mm 26 18 AWG screwdriver rated 90 C 194 F insulation max Operating t
47. put circuit type 120V AC 24V DC sink source standard and high speed Output circuit type Relay 24V DC sink standard 24V DC source standard and and high speed high speed Power consumption 33 W Power supply voltage range 20 4 26 4V DC Class 2 1 0 rating Input 120V AC 16 mA Input 24V DC 8 8 mA Input 24V DC 8 8 mA Output 2 A 240V AC Output 2 A 240V AC 2 A 24V DC Output 24V DC 1 A per point Surrounding air 2 A 24V DC temperature 30 C 24V DC 0 3 A per point Surrounding air temperature 65 C Insulation stripping length 7 mm 0 28 in Enclosure type rating Meets IP20 Pilot duty rating C300 R150 Publication 2080 SG001C EN P September 2012 22 Micro800 Programmable Controller Family Selection Guide General Specifications 2080 LC50 48AWB 2080 LC50 480WB 2080 LC50 480VB 2080 LC50 480BB Attribute 2080 LC50 48AWB 2080 LC50 480WB 2080 LC50 480VB 2080 LC50 480BB Isolation voltage 250V continuous Reinforced 150V continuous Reinforced Insulation Type Input to Aux and Insulation Type Input to Aux and Network Network Type tested for 60 s 1950V DC Type tested for 60 s 720V DC Input to Aux and Network Inputs to Aux and Network 250V continuous Reinforced Insulation Type Output to Aux X Insulation Type 1 0 to Aux and and Network Inputs to Outputs Network Inputs to Outputs Type tested for 60 s 3250V DC Type tested for 60 s 3250V DC Outp
48. rd and high speed Output circuit type Relay 24V DC sink standard 24V DC source standard and high speed and high speed Power consumption 28W Power supply voltage range 20 4 26 4V DC Class 2 1 0 rating Input 120V AC 16 mA Output 2 A 240 V AC 24V DC Input 24V 8 8 mA Output 2 A 240 V AC 24V DC Input 24V 8 8 mA Output 24V DC Class 2 1 A per point surrounding air temperature 30 C 24 V DC Class 2 0 3 A per point surrounding air temperature 65 C Isolation voltage 250V continuous Reinforced nsulation Type Output to Aux and Network Inputs to Outputs Type tested for 60 s 3250V DC Output to Aux and Network nputs to Outputs 150V continuous Reinforced nsulation Type Input to Aux and Network Type tested for 60 s 1950V DC nput to Aux and Network 250V continuous Reinforced Insulation Type 1 0 to Aux and Network Inputs to Outputs Type tested for 60 s 3250V DC Output to Aux and Network Inputs to Outputs 50V continuous Reinforced Insulation Type Input to Aux and Network Type tested for 60 s 720V DC Inputs to Aux and Network 50V continuous Reinforced Insulation Type 1 0 to Aux and Network Inputs to Outputs Type tested for 60 s 720V DC 1 0 to Aux and Network Inputs to Outputs Pilot duty rating C300 R150 Insulation stripping length 7 mm 0 28 in Enclosure type rating Meets IP20 North American te
49. rrent 2 5 mA Q 120V AC max Inrush current 250 mA Q 120V AC max Inrush delay time constant max IEC input compatibility Output Specifications 22 ms Type 3 Attribute 2080 LC50 240WB 2080 LC50 24AWB 2080 LC50 240VB 2080 LC50 240BB Relay Output Hi Speed Output Standard Output Outputs 0 1 Outputs 2 and higher Number of outputs 10 2 8 Output voltage min 5V DC 5V AC 10 8V DC 10V DC Output voltage max 125V DC 265V AC 26 4V DC 26 4V DC Publication 2080 SG001C EN P September 2012 Output Specifications Attribute Load current min 2080 LC50 240 WB 2080 LC50 24AWB Relay Output 10 mA Micro800 Programmable Controller Family Selection Guide 19 Hi Speed Output Outputs 0 1 2080 LC50 240VB 2080 LC50 240BB Standard Output Outputs 2 and higher Load current continuous max Refer to Relay Contacts Ratings on page 19 100 mA high speed operation 1 0A Q 30 C 0 3 A Q 65 C standard operation 1 0A Q 30 C 0 3 A 65 C standard operation Surge current per point Refer to Relay Contacts Ratings on page 19 4 0 A for 10 ms every 1 s Q 30 C every 2 s 65 egit Current per common max 5A Turn on time 10 ms 2 5 us 0 1 ms Turn off time max 1 ms 1 Applies for general purpose operation only does not apply for high speed operation Relay Contacts Ratings Maximum Volts Amperes Amperes Volt Amperes Continuous Make Break
50. s 1 green health indicator Isolation voltage 50V continuous Reinforced Insulation Type channel to system Type tested 720V DC for 60 s North American temp code T4 1 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publica ion 1770 4 1 2 RTB hold down screws should be tightened by hand They should not be tightened using a power tool Publication 2080 SG001C EN P September 2012 34 Micro800 Programmable Controller Family Selection Guide Publication 2080 SG001C EN P September 2012 Environment Specifications Environment Specifications for Micro850 Expansion 1 0 Modules Attribute Value Temperature operating IEC60068 2 1 Test Ad Operating Cold IEC60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 20 65 C 4 149 F Temperature nonoperating IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Temperature surrounding air max 65 C 149 F Relative humidity EC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration EC 60068 2 6 Test Fc Operating 2g Q 10 500 Hz Shock operating EC 60068 2 27 Test Ea Unpackaged Shock 25g Shoc
51. s Amperes Amperes Volt Amperes Continuous Make Break 120V AC 15A 1800VA 180VA 240V AC 75A 0 75A 24V DC 10A 1 0A 28V A 125V DC 0 22A For relay life chart see the Specifications section of the Micro830 and Micro850 User Manual publication 2080 UMO002 Environmental Specifications Attribute Value Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 20 65 C 4 149 F Temperature 65 C 149 F surrounding air max Temperature non operating C 60068 2 1 Test Ab Unpackaged Nonoperating Cold C 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat C 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 0 85 C 40 185 F EC 60068 2 30 Test Db Unpackaged Damp Heat 95 non condensing Am Relative humidity on Vibration IEC 60068 2 6 Test Fc Operating 2 g 10 500 Hz Shock operating IEC 60068 2 27 Test Ea Unpackaged Shock 25g Shock non operating EC 60068 2 27 Test Ea Unpackaged Shock DIN mount 25 g PANEL mount 35 g Emissions CISPR 11 Group 1 Class A Publication 2080 SG001C EN P September 2012 24 Publication 2080 SG001C EN P September 2012 Micro800 Programmable Controller Family Selection Guide Environmental Specifications Attribute ESD immunity Value IEC 61000 4 2 4 kV contact dischar
52. sponse time up to 6396 4 60 ms without 50Hz 60 Hz rejection depends on number of enabled channel and filter setting 600 ms with 50 Hz 60 Hz rejection Input current terminal user 4 20 mA default configurable 0 20 mA Input voltage terminal user 10V configurable 0 10V Input impedance Voltage terminal gt 1 MQ Current terminal 100 Q Absolute accuracy 30 1096 Full Scale 25 C Accuracy drift with temp Voltage terminal 0 00428 96 Full Scale C Current terminal 0 00407 96 Full Scale C Calibration required Factory calibrated No customer calibration supported Overload max 30V continuous or 32 mA continuous one channel at a time Channel diagnostics Over and under range or open circuit condition by bit reporting Output Specifications 2085 OF4 Attribute 2085 OF4 Number of outputs 4 Resolution 12 bits unipolar 11 bits plus sign bipolar Voltage 2 56 mV cnt unipolar 5 13 mV cnt bipolar Current 5 13 uA cnt Data format Left justified 16 bit 2s complement Step response time up to 63 2ms Conversion rate max 2 ms per channel Output current terminal user 0 mA output until module is configured configurable 4 20 mA default 0 20 mA Output voltage terminal user 10V configurable 0 10V Current load on voltage output max 3mA Absolute accuracy Voltage terminal 0 133 Full Scale 25 C or better Current terminal 0 425 Full Scale 25 C
53. ture 65 C Isolation voltage Inputs to Outputs Inputs to Outputs 2080 LC30 16AWB Type tested for 60 s 3250V DC 1 0 to Aux and Network 2080 LC30 160QWB Type tested for 60 s 720V DC Inputs to Aux and Network 3250V DC Outputs to Aux and Network Inputs to Outputs 250V continuous Reinforced Insulation Type Outputs to Aux and Network 50V continuous Reinforced Insulation Type 1 0 to Aux and Network Inputs to Outputs Type tested for 60s 720V DC 1 0 to Aux and Network Inputs to Outputs Pilot duty rating C300 R150 Micro830 24 Point Controllers General Specifications 24 point controllers Attribute 2080 LC30 240WB e Allen Bradley e Allen Bradley e Allen Bradley 2080 LC30 240VB 2080 LC30 240BB Input circuit type 24V DC sink source standard and high speed Output circuit type Relay 24V DC sink standard and 24V DC source standard and high speed high speed Event input interrupt Yes support 1 0 rating Input 24V DC 8 8 mA Input 24V DC 8 8 mA Output 2 A 240 V AC general use Output 24V DC Class 2 1 A per point Surrounding air temperature 30 C 24V DC Class 2 0 3 A per point Surrounding air temperature 65 C Isolation voltage 250V continuous Reinforced Insulation Type Outputs to Aux and Network Inputs to Outputs Type tested for 60 s 720V DC Inputs to Aux and Network 3250V DC Outputs to Aux and Network Inputs to Outputs
54. uctor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 3 RTB hold down screws should be tightened by hand They should not be tightened using a power tool Derating Curve for 2085 1016 Input voltage V 30 26 4 Temp 30 C 65 C heap Derating Curve for 2085 1032T Input voltage V Number L X of inputs 18 24 32 45301 2085 0V16 Sink and 2085 0B16 Source DC Output Module Attribute 2085 0V16 2085 0B16 Number of outputs 16 sinking 16 sourcing Operating voltage range 10 30V DC On state voltage min 10V DC On state voltage nom 24V DC On state voltage max 30V DC On state current max 0 5 A Q 30V DC per output 8 A per module 44 5 x 90 x 87 mm 1 75 x 3 54 x 3 42 in Dimensions HXWxD Publication 2080 SG001C EN P September 2012 28 Micro800 Programmable Controller Family Selection Guide Publication 2080 SG001C EN P September 2012 2085 0V16 Sink and 2085 0B16 Source DC Output Module Attribute 2085 0V16 2085 0B16 Shipping weight approx 220 g 7 76 oz Bus current draw max 200 mA Q 5V DC Wire size 0 25 2 5 mm 22 14 AWG solid or stranded copper wire rated at 75 C 167 F or greater 1 2 mm 3 64 in insulation max Wiring category 2 on signal ports Terminal screw torque max 0 5 0 6 Nm 4 4 5 3 Ib in Output circ
55. uit type 24V DC sink 24V DC source Power dissipation total 5W Power supply 24V DC Class 2 Status indicators 16 Yellow channel indicators Isolation voltage 50V continuous Reinforced Insulation Type channel to system Type tested 720V AC for 60 s Enclosure type rating Meets IP20 North American temp code T4 1 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 2 RTB hold down screws should be tightened by hand They should not be tightened using a power tool 2085 1A8 2085 IM8 2085 0A8 AC Input Output Modules Attribute 2085 IA8 2085 0A8 Number of inputs 8 Dimensions HXWxD 28 x 90 x 87 mm 1 10 x 3 54 x 3 42 in Shipping weight approx 140 g 4 93 oz Bus current draw max 5V DC 150 mA 5V DC 180 mA Wire size Insulation stripping length 0 25 2 5 mm 22 14 AWG solid or stranded copper wire rated 75 C 167 F or greater 1 2 mm 3 64 in insulation max 10 mm 0 39 in Wiring category 2 on signal ports Wire type Copper Terminal screw torque max 0 5 0 6 Nm 4 4 5 3 Ib in Input output circuit type 120V AC input 240V AC input 120V 240V AC output Power supply 120V AC 240V AC 120V 240V AC Power dissipation total 2 36 W 2 34 W 5 19 W Enclosure type rating Meets IP20 Micro800 Programmable Controller F
56. ut to Aux and Network Output to Aux and Network Inputs Inputs to Outputs to Outputs 50V continuous Reinforced 50V continuous Reinforced Insulation Type 1 0 to Aux and Network Inputs to Outputs Type tested for 60 s 720V DC 1 0 to Aux and Network Inputs to Outputs North American temp code T4 1 Use this Conductor Category information for planning conductor routing Refer to Industrial Automation Wiri publication 1770 4 1 Input Specifications Attribute Number of Inputs 2080 LC50 48AWB 120V AC Input 28 High Speed DC Input Inputs 0 11 12 ng and Grounding Guidelines 2080 LC50 480WB 2080 LC50 480VB 2080 LC50 480BB Standard DC Input Inputs 12 and higher 16 Input group to backplane isolation Verified by the following dielectric tests 1950V AC for 2 s 150V working voltage IEC Class 2 reinforced insulation Verified by the following dielectric tests 720V DC for 2 s 50V DC working voltage IEC Class 2 reinforced insulation Voltage category 110V AC 24V DC sink source Operating voltage range 132V 60Hz AC max 16 8 26 4V DC Q 65 C 149 F 16 8 30 0V DC 30 C 86 F 10 26 4V DC 65 C 149 F 10 30 0V DC 30 C 86 F Off state voltage max 20V AC 5V DC Off state current max 1 5mA 1 5mA On state current min 5 mA Q 79V AC 5 0 mA 16 8V DC 1 8 mA Q 10V DC On state current no
57. yon Ticaret A Kar Plaza Is Merkezi E Blok Kat 6 34752 erenk y stanbul Tel 90 216 5698400 www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation NV Pegasus Park De Kleetlaan 12a 1831 Diegem Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 2080 SG001C EN P September 2012 Copyright 2012 Rockwell Automation Inc All rights reserved Printed in the U S A