Home
Dynasonics DFX Manual
Contents
1. 5 9215 adid 081 HDS Ov L OZL HDS 001 HDS 08 HDS p S3SSV 12 15 3dld 13315 SSITNIVLS 13315 31901 06 DPP UM 00147 02 12 58 8100 7870 uL 0004 STY L vL9 S 19 1885 1 6 900 0520 Ov L O Z61 0 9 8 90 S 106 SL8 b 508 900 OST O 601 0 SZLO 09170 005 v _ 0 Ea V 0005 S OST O S600 5600 00S 657 Seve S8E E Ea 000 Szot 6796 Scot adig sseag dL 13 Aaddo gt ONIGNL 4934402 0067 Z90 1967 1062 0600 6170 2100 0600 601 0 000 00 STL E 0600 S900 0800 S600 0057 S 87 9 S797 STIT 29072 6007 S961 6S6 SLET 6717 05170 60 0 090 0 2100 891 1621 692 L SDT L ai Op L O ZvO 0 SS0 0 S900 vem 0991 151 SLE L SLE L do Z90 L 6601 Sco 5660 EH T O SE00 0600 5900 em SIEL Scil Scil 90 6960 1790 Ea E 80 8200 0 0 0 6 00 Ov8 0 6790 679 0 679 0 OE ONIGNL 4934402 VIVA 38 1 37901 u A c u 4 L L Ye uS s agadan 59 06 DPP UM 00147 02 12 Suju ss vs es 25 15 ee REESE 444 67
2. 13 FIGURE 2 2 UPSTREAM DOWNSTREAM PIPE REQUIREMENTS ecceeccccccocccccsoccccoooooooe0000000e00000e000ee 14 FIGURE 2 3 TRANSDUCER PLACEMENT eeeeecceccccccccoccccooocoooeoooooeseoooe00e000000000000000000000000000000000000000000 16 FIGURE 2 5 HOT TAP INSTALLATION eeeeeeccecccccococccccsocccooooooooe0ecooe0e0000000000000000000000000000000000000000000000000 18 FIGURE 2 4 INSTALLATION LOCATION G sccccccsssescscsssccsccscsssccccscssccccsessscccesesccesscsoscscsssoosssesessoseees 18 FIGURE 2 6 INSTALLATION MEASUREMENTS eeccccecccccococcccesovooe00ooo0000000000000000000000000000000000000000000000 20 FIGURE 2 7 FLOW DIRECTION ARROW 21 FIGURE 3 1 DFX TRANSMITTER INSTALLATION DIMENSIONS 24 FIGURE 3 2 TRANSDUCER CABLE INSTALLATION ecccececccccooccccooccccoooooeoe0e00000000000000000000000000000000000 25 FIGURE 3 3 TRANSDUCER CONNECTIONS ccceecccccooccccooocoooeoooooe0e0000000000000000000000000000000000000000000000000 26 FIGURE 3 4 DXF WIRING DIAGRAM eeeeeecccceccccccoccccesoooocoooooooesccoseseuooeosuooeoe0e00000000000000000000000000000000000 27 FIGURE 3 5 DFX AC POWER CONNECTION eecececcccccoccccooocccoeoovooesooooeoeoooeseseoeoe0000000000000000000000000000000 28 FIGURE 3 5 DC POWER CONNECTION ecceeecccococccccoocooooooooooe0ovooe0e0o0e000000000000000000000000000000000000000000000 29 FIG
3. 000 000 LX 0000001 X SYLW 13A 000 001X 000001 X 1333 13A HEEL LL Mm OU X 0001 X 581 eo H4 V8 YYW TIO 01 OL X ux LX 143uDV dida Su1153W 601310 Ld X aW linw 1421812 VOW suai SYLW 13A SNOTIV5 SDILSONDVIGC TWLOL 31Vu AULN3 5 WIN seu uj 18115 LULA EMETTE G 1 FIGURE A 1 1 MENU MAP 06 DPP UM 00147 02 12 SSaJd 1591 104 suouua MO13 pJomssed OL t PINOM L 1 PINOM Ljequinu Aejasayy u WLOL Ims m 3NON ajnpoyw wol4 2 MENU MAP 2 FIGURE 1 06 DPP UM 00147 02 12 56 ove e008 Foro ose reee cose e ozro seve srz se LIE D zere sooo sree sege t jane Feoro s900 zzi 0061 s Fono oi oser zwi 8900 esi oo Sti EE m NI x zor sooo seri stet 1 Bes BE ER A 88 Tower FPU apisin 9215 adid Ot HDS 415 0 HDS HDS pimo 5355712 15 3dld 13315 SSIINIVLS 13315 L E V 37871 57 06 00147 02 12 ar em a nem at vem a mm
4. 100 30m Maximum length 990 300m Maximum length 990 300m in 10 3m increments in 10 3m increments Cannot be used with hot tap assembly NOTE All DP7 probes include a seas fitting for mounting in 1 NPT ports Isolation valve kits are available for hot tapped ap plications 12 06 DPP UM 00147 02 12 PART 2 TRANSDUCER INSTALLATION UNPACKING After unpacking it is recommended to save the shipping carton and packing materials in case the instru ment is stored or re shipped Inspect the equipment and carton for damage If there is evidence of ship ping damage notify the carrier immediately MOUNTING LOCATIONS The transducers that are utilized by the DFX contain piezoelectric crystals for transmitting and receiv ing ultrasonic sound energy through the pipe wall in the case of the series DT9 transducer and from the probe tip of the series DP7 Placement of the ultrasonic transducer is the most critical step in achieving an accurate and reliable flow reading All flow meters of this type rely on a full pipe of fluid that is flowing symmetrically evenly in the pipe Flow in partially filled pipes and immediately downstream of elbows valves and pumps is unstable and will lead to unstable readings and non linearity Figure 2 1 illustrates five possible pipe configurations and recommends installation only in locations where it can be guaranteed that the pipe will be filled at all times when flow measurements are req
5. Some pipe materials such as concrete pressure pipe and some plastic lined pipes do not allow ultrasound to penetrate to the liquid inside For these applications the DP7 insertion probe will be needed The flow meter operates by transmitting an ultrasonic sound from its transmitting transducer through the pipe wall or from the probe tip into the moving liquid The sound will be reflected by useful sonic reflectors suspended within the liquid and recorded by the receiving transducer If the sonic reflectors are moving within the sound transmission path sound waves will be reflected at a frequency shifted Doppler frequency from the transmitted frequency The shift in frequency will be directly related to the speed of the moving particle or bubble This shift in frequency is interpreted by the instrument and converted to various user defined measuring units What makes a good Doppler reflector The four criteria are The scattering material must have a sonic impedance sound speed difference at least 1096 different from the fluid There must be some particles large enough to cause longitudinal reflection particles larger than 35 micron For a given pipe size the longitudinal reflection must have sufficient energy to overcome the Rayleigh energy wasting scattering caused by smaller particles The reflecting material must travel at the same velocity as the fluid for good accuracy APPLICATION VERSATILITY The DFX flow
6. TOTL MUL Flow Totalizer Multiplier Value 0 01 to 1 000 000 Utilized for setting the flow totalizer exponent This feature is useful for accommodating a very large accumulated flow The exponent is a x10 multiplier where n can be from 2 x0 01 to 6 x1 000 000 Table 4 1 should be referenced for valid entries and their influence on the DFX display EXPONENT DISPLAY MULTIPLIER x PT 01 2 x 0 01 x10000 4 x 10 000 x100000 5 x 100 000 x1000000 6 x 1 000 000 TABLE 4 1 EXPONENT VALUES 40 06 DPP UM 00147 02 12 FLUID SPECIFIC GRAVITY SP GRAV Fluid Specific Gravity Value Unitless Value Allows adjustments to be made to the specific gravity density relative to water of the liquid If Pounds LBS or Kilograms KGS is selected for either the RATE UNT or the TOTL UNT a specific gravity must be entered for the correct mass flow to be calculated A list of fluids and their associated specific gravities is located in the Appendix of this manual NOTE Specific Gravity only appears when LBS or KGS are selected in either Rate Unit or Total Unit LOW FLOW CUT OFF F C OFF Low Flow Cut off Value Unitless Value A Low Flow Cut off entry is provided to allow very low flow rates that can be present when pumps are off and valves are closed to be displayed as Zero flow The value entered is in actual rate units SCALE FACTOR SCALE F Scale Factor Value 0 500 to 5 000 This function can be used to make
7. Wire up to 14 AWG can be accommodated in the DFX terminal blocks a A switch or circuit breaker is required in the installation b The switch or circuit breaker must be in close proximity of the DFX and within easy reach of the operator C The switch or circuit breaker must be marked as the disconnect device for the DFX DC Power Connections 12 to 28 VDC 7 Watts Maximum FIGURE 3 6 DC POWER CONNECTION 06 DPP UM 00147 02 12 29 MULTIPLE METER INSTALLATIONS The DFX flow meter contains a provision for synchronizing multiple DFX flow meters together Synchro nization is required when more than one DFX flow meter is mounted on a common pipe or header sys tem If meters are not synchronized a phenomena called cross talk can occur between meters which can lead to erroneous readings or no readings at all Cross talk results from the small differences in trans mitted frequency generated from two or more different ultrasonic flow meters By synchronizing the transmitted ultrasonic energy cross talk caused by differences in transmitted frequency is eliminated The DFX synchronization circuit is designed to interconnect up to four DFX flow meters over a cable length of 100 feet 30 meters Utilize 20 22 AWG twisted pair shielded interconnection wire for this pur pose See Figure 3 7 TO SYNCHRONIZE MULTIPLE METERS 1 Remove power from the DFX flow meters 2 Daisy chain connect the EXTernal SYNChronization and GND term
8. be pushed in by hand to decrease the insertion time To Calculate Insertion Depth Measure and record the following linear dimensions E ProbeLength E C SealFitting to Pipe Wall B PipeWallThickness 0 125 x Pipe OD D E C B A D Insertion Measurement DP7 Probe Seal Fitting Full Port Ball Valve C Valve and Seal Stack DE DP7 lt lt C ON Pipe Wel Length 1 8 Pipe Internal Diameter Diameter FIGURE 2 6 INSTALLATION MEASUREMENTS 20 06 DPP UM 00147 02 12 Flow Direction Arrow FIGURE 2 7 FLOW DIRECTION ARROW PROBE CABLES Before inserting the probe into the pipe the sensor cables should be routed to the transmitter location Verify that the supplied cable length is sufficient to meet the installation requirements While transducer cable extension is not generally recommended if additional transducer cable length is required utilize cable and connectors of the correct type and impedance In many cases especially if a splice my be exposed to water or other liquids it may be more effective to replace the entire cable Transducers use RG59 75 ohm coaxial cable or Twinax Belden 9463 or Belden 9463DB 78 Ohm two conductor cable CAUTION The probe cables are designed to carry low level signals that are developed by the sensor Care should be taken in routing the cables Avoid running cables near sources of high voltage or EMI RFI Also avoid routi
9. filter for the measured velocity The control can be observed when the DISPLAY mode is set to DIAG See Figure 4 4 Frequency Gain Signal Strength Series DFX FIGURE 4 4 DIAGNOSTIC DISPLAY MANUAL OPERATIONS When NORMAL is selected the unit will automatically control the gain and front end hardware filter for optimum measurement of the Doppler signal Select HIGH for applications where the unit reads flow rates consistently but much lower than the actual flow rate This may be required when sound is not getting through the pipe as well Selecting HIGH will cause the unit to look for the signal strength to increase by 2 for every foot per second increase in flow rate Basically the gain is doubled but still automatically controlled For applications where the flow is constant but you may need to tune the unit to filter out extraneous noise select the MANUAL mode Typically this would only be required at very low flow rates When MAN UAL mode is selected the GAIN POT and FILTER settings are manually set Automatic control is disabled 06 DPP UM 00147 02 12 47 GAIN CONTROL GAIN POT DIGITAL GAIN POT 0 64 Using the arrow keys increase or decrease the numerical value to set the signal gain level Typically opti mum flow measurement is made when this value is between 10 and 50 Use the lowest value that pro vides an accurate and stable flow reading This adjustment must be made in conjunction with the FILTE
10. 3 Spread an even layer of coupling compound approximately 7 3 mm thick to the prepared transducer mounting areas of the pipe 16 06 DPP UM 00147 02 12 4 Spread an even layer of coupling compound approximately 3 mm thick to the flat face of the two transducers 5 Place each transducer under the strap with the flat face amber plastic window positioned towards the pipe The notch on the back of the transducer will provide a mounting surface for the strap The transducer cables must be facing in the same direction and downstream of the trans ducers for proper operation NOTE Large pipes may require two people for this procedure 6 Tighten the strap strong enough to hold the transducers in place but not so tight that all of the couplant squeezes out of the gap between the transducer face and pipe Ensure that the trans ducers are squarely aligned on the pipe and 180 apart If RTV is utilized avoid moving the trans ducers during the curing time typically 24 hours as bubbles may form between the transducer and pipe that can reduce ultrasonic signal transmission to unsatisfactory levels 7 Route the transducer cables back to the area where the transmitter will be mounted avoiding high voltage cable trays and conduits While transducer cable extension is not generally recom mended if additional transducer cable length is required utilize cable and connectors of the correct type and impedance In many cases especial
11. Linearization values have not been entered Verify that AGC is set to Normal Inaccurate Flow Reading Verify that the transducers are mounted square and 180 degrees apart on the pipe Relocate transducer to a pipe position with greater straight run length DP7 Probe not aligned in the pipe Verify 4 20 mA calibration Analog output does not Verify 4 mA and 20 mA flow settings match data collection Verify that the loop load is within the supply voltage range system Run 4 20mA TEST feature verify that mA outputs coincide with expected data collection system readings Display does not light up ERROR on the DFX Display Unstable Flow Reading 06 DPP UM 00147 02 12 51 1 Verify 0 Hz and Hz flow settings 2 Place oscilloscope or frequency counter on the Rate Pulse module outputs and verify frequency output 3 Run output TEST feature verify that the Hz output coincides with expected data collection system readings Rate Pulse output does 4 Verify that K factor has been calculated correctly not match data collection K factor Hz flow second system Example Max Hz 2 500 Hz 10 000 Gallons Minute K factor 2 500 Hz 166 7 Gallons Second K factor 15 pulses gallon 5 Verify that the data collection system is accepting the pulses from the DFX connect to Turbine out or OUT IN as required 1 When run in AUTO mode the DFX utilizes a series of filters that op timize readings for a particular flow range T
12. None Approvals N General Safety CE Approved Power Supply A 115 VAC Totalizer B 230 VAC Input Output 1 i iai C 100 VAC Eight Digit Resettable 12 28VDC None 1 4 20 mA 2 Dual Relay 3 Rate PUISE Input Output 2 N None 1 4 20 mA 2 Dual Relay 3 Rate Pulse DT9 CLAMP ON DOPPLER TRANSDUCER SET DT9 1 O LILILI N Transmitter Type ___ L Approvals 4 Std Temp Std Pipe N General Safety 5 Std 5 Pipe to US Canadian 6 High Temp Std Pipe standards 7 High Temp Small Pipe Cable Length Conduit Type Conduit Length 000 0 Om N None 000 0 Om 020 20 6m A Flexible Armored 020 20 6m 050 50 15m 050 50 15m 100 100 30m 100 100 30m Maximum length 990 300m Maximum length 990 300m in 10 3 increments in 10 3m increments Std Temp Maximum 250 F 121 C High Temp Maximum 400 F 204 C Std Pipe 1 25 mm and above Small Pipe 4 to 1 6 mm to 25 mm 06 DPP UM 00147 02 12 11 DP7 INSERTION DOPPLER PROBE 0 7 OUO O Probe Length _ L Approvals 1 8 203 mm N General Safety 2 18 457 mm to US Canadian 3 28 711 mm standards 4 38 965 mm B 11 2 RF flange 5 48 1220 mm General Safety EE for Cable Length Conduit Type Conduit Length 000 0 000 0 020 20 6m A Flexible Armored 020 20 6m 050 50 15m 050 50 15m 100 100 30m 100
13. in a manner not specified by the manufacturer the protection provided by the equipment may be impaired The DFX product retains all user configuration data and totalizer accumulations in non volatile FLASH memory indefinitely PRODUCT IDENTIFICATION The serial number and complete model number of the transmitter are located on the side of the moni tor enclosure Should technical assistance be required please provide the Customer Service Department with this information Dynasonics Model SN Date 0f Manufacture Rating 115VAC U 50 60 Hz 17 Scale Factor Pipe Size Output 4mA 20mA CAUTION Equipment must be isolated or disconnected from hazardous line voltage before opening enclosure ATTENTION Equipement doit tre isol ou d connect de la tension d alimentation dangereux avant d ourir la pi ce jointe AC ES E113055 10 Dynasonics Model SN Date Of Manufacture Rating 12 28 VDC 7W Scale Factor Pipe Size Output 4mA 20mA CAUTION Equipment must be isolated or disconnected from hazardous line voltage before opening enclosure ATTENTION quipement doit tre isol ou d connect de la tension d alimentation dangereux avant d ourir la pi ce jointe AC ES E113055 06 DPP UM 00147 02 12 PRODUCT MATRIX DDFXD DIGITAL DOPPLER ULTRASONIC FLOW TRANSMITTER DDFXD2 Transmitter _ Options 2 Rate and Totalizer N
14. pipe s line pressure is within the rated limits of the pressure drilling machine to be used 2 Grind off paint or other coatings from the pipe in the area where the DP7 Probe Assembly is to be installed 3 Tack weld a 1 NPT weld coupling to the pipe or install a ser vice saddle according to the supplier s instructions The coupling or saddle must be aligned perpendicular to the pipe axis and square to its plane 4 Complete welding A water tight 0 25 minimum weld bead is recommended 5 Install the close nipple supplied with assembly into the weld coupling Use appropriate pipe sealants 6 Install the isolating ball valve on the close nipple Verify that the valve is in fully open position 7 Install drill bit and adapter into the pressure drilling machine Then attach the machine to the isolation valve 8 Drill through the pipe wall in accordance with the instructions supplied with the drilling machine 9 Withdraw the drill bit through the isolating valve Close the valve and remove the drilling ma chine Check for leakage at valve and connections 10 Place pipe sealant on the 112 NPT threads of the insertion fitting assembly Screw the assembly into the isolation valve and tighten with a 212 pump wrench FIGURE 2 5 HOT TAP INSTALLATION 18 06 DPP UM 00147 02 12 PROBE INSERTION Before inserting the DP7 probe into the piping system it is necessary to calculate the probe insertion depth that will place the me
15. the DFX system agree with a different of reference flow meter or to compensate for an installation where there is inadequate straight pipe to obtain a laminar flow pro file by applying a correction factor multiplier to the readings and outputs A factory calibrated system should be set to 1 000 The range of settings for this entry is 0 5000 to 5 000 The following example describes using the SCALE F entry The DFX meter is indicating a flow rate that is 4 higher than another flow meter located in the same pipe line To make the DFX indicate the same flow rate as the other meter enter a SCALE F of 0 960 to lower the readings by 4 SYSTEM DAMPING DAMPING System Damping Value Relative Percent Entry 0 99 Flow Filter Damping establishes a maximum adaptive filter value Under stable flow conditions flow var ies less than 10 of reading this adaptive filter will increase the number of successive flow readings that are averaged together up to this maximum value If flow changes outside of the 10 window the Flow Filter adapts by decreasing and allows the meter to react faster Increasing this value tends to provide smoother steady state flow readings and outputs 06 DPP UM 00147 02 12 41 CONFIGURE I O MODULE 1 MOD1 Configure I O Module 1 Choice YES NO This prompt allows access to the setup parameters associated with installation of the optional ISO MOD interface modules If NO is selected the unit will skip ahead to
16. the DFX transmitter See Figure 3 4 for AC power supplies and Figure 3 5 for DC power supplies Utilize the conduit hole on the left side of the en closure for this purpose Use wiring practices that conform to local and national codes e g The National Electric Code Handbook in the U S CAUTION Any other wiring method may be unsafe or cause improper operation of the instrument DANGER To avoid serious injury or damage disconnect electrical power before servicing this meter NOTE This instrument requires clean electrical line power Do not operate this unit on circuits with noisy components i e fluo rescent lights relays compressors or variable frequency drives It is recommended not to run line power with other signal wires within the same wiring tray or conduit 26 06 DPP UM 00147 02 12 WIRING DIAGRAM CAUTION To avoid serious injury or damage disconnect electrical power before servicing this meter JP3 Connections 115 VAC MODULE 2 O 2 woc o2 9 28 VDC MODULE 1 1 2 Connections 2 1 115 230 O O VAC 2 1 2 s 9 AC 0 25 A 250V Delay DC 1 0 A 250V Delay olojo o o o y y X RED mE RED EARTH DC IGND EARTH SYNC SELECT 9 28 VDC FIGURE 3 4 DXF WIRING DIAGRAM 06 DPP UM 00147 02 12 POWER SUPPLY CONNECTIONS DANGER Line voltages may be present within the enclosure There is a risk of sho
17. totalizing pulse The relays are rated for 200 VAC maximum and have a current rating of 0 5 A resistive load 175 VDC 0 25 A resistive It is highly recommended that a secondary relay be utilized whenever the Control Relay ISO MOD is used to control inductive loads such as solenoids and motors Typical relay connections are illustrated in Figure 3 11A The reed relays located within the relay module can interface directly with small pilot lights PLCs electronic counters and SCADA systems Figure 3 11B describes the connection of an external power relay to the Relay ISO MOD It is recom mended that external power relays are utilized whenever the load to be switched exceeds the switch rating of the reed relays or if the load is inductive in nature FLOW OK INTERNAL 7 RE LAY 4 CU RCUIT P N D020 1045 102 SEU di v v 2 E S unc v a v Al EXTERNAL TOTALIZER SAMPLER FIGURE 3 11A TYPICAL RELAY CONNECTIONS 34 06 DPP UM 00147 02 12 POWER RELAY RELAY 4 0020 1045 102 000000 ISO MOD POWER SOURCE FIGURE 3 11B EXTERNAL RELAY CONNECTIONS RATE PULSE OUTPUT MODULE The Rate Pulse Output Module is utilized to transmit information to external counters and PID systems via a frequency output that is proportional to system flow rate The frequency output range of the Rate Pulse Module is 0 2 500 Hz This module has t
18. will be accepted for return The purchaser must determine the applicability of the product for its desired use and assumes all risks in connection therewith DYNASONICS assumes no responsibility or liability for any omissions or errors in connection with the use of its products DYNASONICS will under no circumstances be liable for any incidental consequential contingent or special damages or loss to any person or property arising out of the failure of any product component or accessory All expressed or implied warranties including the implied warranty of merchantability and the im plied warranty of fitness for a particular purpose or application are expressly disclaimed and shall not apply to any products sold or services rendered by DYNASONICS The above warranty supersedes and is in lieu of all other warranties either expressed or implied and all other obligations or liabilities No agent or representative has any authority to alter the terms of this war ranty in any way 62 06 DPP UM 00147 02 12 WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT WEEE DIRECTIVE In the European Union this label indicates that this product should not be disposed of with household waste It should be deposited at an appropriate facility to enable recovery and recycling For information on how to recycle this product responsibly in your country please visit www racinefed com recycle 06 DPP UM 00147 02 12 63 RETURN SALES INFORMATION CONTACTS AND
19. 0 PIS 910 170 ori orit orit orit eros SO cro seo oeo eco oro seo 069 oss 069 069 069 09 Suu 95 ss vs ES zs s ELW SEE ECL PIS SASSV1D 5 Jdid NOU 311120G V 31901 Kg DPP UM 00147 02 12 06 60 CL S3SSV12 AYVONVLS Jdid NOU LSVI 379VL 61 00147 02 12 06 DPP UM LIMITED WARRANTY AND DISCLAIMER DYNASONICS division of Racine Federated Inc warrants to the end purchaser for a period of one year from the date of shipment from the factory that all new transmitters and transducers manufac tured by it are free from defects in materials and workmanship This warranty does not cover products that have been damaged due to misapplication abuse lack of maintenance or improper installation DYNASONICS obligation under this warranty is limited to the repair or replacement of a defective prod uct at no charge to the end purchaser if the product is inspected by DYNASONICS and found to be defective Repair or replacement is at DYNASONICS discretion A returned goods authorization number must be obtained from DYNASONICS before any product may be returned for warranty repair or replace ment The product must be thoroughly cleaned and any process chemicals removed before it
20. 0 to 85 Out of direct sunlight Direct sunlight may increase transmitter temperature to above the maxi mum limit 3 Mounting Refer to Figure 3 1 for enclosure and mounting dimension details Ensure that enough room is available to allow for door swing maintenance and conduit entrances Secure the enclo sure to a flat surface with four appropriate fasteners 4 Conduit holes Conduit hubs should be used where cables enter the enclosure Holes not used for cable entry should be sealed with plugs NOTE Use NEMA 4 IP 65 rated fittings plugs to maintain the watertight integrity of the enclosure Generally the left conduit hole viewed from front is used for line power the center conduit hole for transducer connections and the right hole is utilized for ISO MOD I O wiring 5 If additional holes are required drill the appropriate size hole in the enclosure s bottom Use ex treme care not to run the drill bit into the wiring or circuit cards 06 DPP UM 00147 02 12 23 Series DFX 1 Li Power Transducer L Input Output Grane Concur Holes Connection Connection Connection WALL MOUNT OPTION PANEL MOUNT OPTION 0 07 1 8 Maximum Radius 6 25 158 8 5 19 gt 131 8 PANEL CUT OUT E 6 08 Panel Thickness 0 5 12 Max 1544 6 65 169 0 FIGURE 3 1 DFX TRANSMITTER INSTALLATION DIMENSIONS 24 06 DPP UM 00147 02 12 TRANSDUCER WIRING CONNEC
21. 0001 9999 con figuration parameters will not be accessible without first entering that value when prompted If the value is left at 0000 no security is invoked and unauthorized changes could be made Access to resetting of the Totalizer is also protected by this password ADVANCED SETUP AD SETUP ADVANCE SETUP MODE Advance setup mode allows access to the following parameters Select YES to access these parameters AGC MODE Automatic Gain Control GAIN POT Digital Gain Control FILTER Hardware Filter Control LINEAR 10 Point Linearization AGC MODE AGC MODE AUTOMATIC GAIN CONTROL MODE OF OPERATION NORMAL Standard Configuration HIGH Used for low signal strength MANUAL AGC disabled GAIN POT Digital Gain Control FILTER Hardware Filter Control Select the desired mode of operation A basic understanding of the AGC logic is required in order to know when to use any selection other than NORMAL 46 06 DPP UM 00147 02 12 When the unit is powered up there is a delay before the unit begins transmitting sound into the pipe During this time the signal strength is measured and a base signal level is obtained Typically this is a value of about 20 The unit measures flow by measuring the Doppler frequency shift The frequency shift is approximately 70 Hz per foot per second For every foot per second increase in velocity the signal strength should increase by 1 The unit automatically adjusts the gain and selects the proper hardware
22. ATION ssssssssssseccssssscsssnscccsssseccssnseccssssscsssssscesssneceess 13 Mast lc 13 PIPE PREPARATION Pet M M 15 ao mV rm M 15 DT9 CLAMP ON TRANSDUCER MOUNTING e eee eee eee ee e eoe eee esee eoe s eae eee e esee s sa e e eee eese esas Papas 15 DP7 PROBE TRANSDUCER MOUNTING e eee eee eee eene oo oes esee es eaae eaae sess sa e e esee sees s sooo aas 17 PART 3 TRANSMITTER INSTALLATION csssccsssssecsssssscsssnssccsssseccssnssecssssessssssecessenscesss 23 UNPACKING 23 MOUNTING LOCATION 23 TRANSDUCER WIRING CONNECTIONG ccsccccosssssssssssssccccccccccsssssssccccscccsssssssssccccsccccsssssssscccosscsssssceees 25 POWER SUPPLY WIRING CONNECTIONS e e eee ee eee ee eee oo nee eee eese ses e aee eese essa ss eae 26 MULTIPLE METER INSTALLATIONS cccisisssccsssesscoscisssccccsenscsscsscssescsebscesesesssesccebscstesesssoscsssscodssessesscsocscstene 30 ISO MODULES 31 PART 4 INSTRUMENT PROGRAMMING ssssccssssscsssssscsssnssecsssseccsssseccssssscsssssscessenecees 37 GENERAL 37 KEYPAD
23. CFG 2 If YES is selected configura tion and calibration of the module installed in the first position is accessible MODULE TYPE MOD TYPE Module Type Choice NONE No Module Installed 4 20MA 4 20mA Analog Output RATE Rate Pulse Output RELAY Relay Output Select the type of module installed from the list ISO MOD 4 20 mA ISO MOD 4 20 mA FLOW 4MA FLOW 20MA CAL 4MA CAL 20MA 4 20 TEST Configured via jumper selections for either a passive current sinking or active current sourcing trans mission mode see Part 3 for details the 4 20 mA Output Module interfaces with virtually all recording and logging systems by transmitting an analog current signal that is proportional to system flow rate Independent 4 mA and 20 mA span settings are established in memory using the flow measuring range entries These entries can be set anywhere in the measuring range of the instrument Output resolution of the module is 12 bits 4096 discrete points and the module can drive up to 800 Ohms of lead with its internal 24 V isolated power source 4 20 MA SPAN The FLOW 4MA and FLOW 20MA entries are used to set the span of the 4 20 mA analog output These entries are volumetric rate units that are equal to the volumetric units configured as Engineering Rate Units and Engineering Units Rate Interval For example to span the 4 20 mA output from 0 GPM to 100 GPM with 12 mA being 50 GPM set the FLOW 4MA and FLOW 20 values as follo
24. Dynasonics DDFXD Doppler Ultrasonic Flow Meter FORM 06 DPP UM 00147 Series STEREO 2 d 00g 4 Tel 262 639 6770 Toll Free 800 535 3569 TABLE OF CONTENTS SYMBOL EXPLANATIONS csssccssssscssssscssssscssseccssseccssseccssseccsnseccssseccsssccesssccessscesssscessseeessss 6 QUICK START OPERATING INSTRUCTIONS ssssccsssssssssssscssssssccsssscccssssecessnsecesssseccssssess 7 T TRANSDUCER LOCATION e 7 2 PIPE PREPARATION AND TRANSDUCER MOUNTING s cccssssssssccccccccssssscssscccccccccssscssssccccscccssssccses 7 3 TRANSDUCER CONNEC TIONS iscisscsessccccsasssescsecscssccosssecsocsssessscscosssessesscdecscesesedsessccssscobesecssosssesscesesexe 8 STARTUP M 8 PART 1 INTRODUCTION ssssccssssscssssscssssccssssccssssccssssccssnsccssssccssssccssssccssnscsssnsccssssecsssecccs 9 GENERAL HH 9 APPLICATION VERSATILITY ssvccssciscccccssocsesscassscscssesscsscsesscscssetscescsesscocesecsvavcssescoscsedscesssesssssssccsseuessssessesess 9 USER SAFETY 10 DATA INTEGRITY 10 PRODUCT IDEN TIFICATION civsitesscccssccssssacsssccctescesosscsdesvacsccecossssccbsecsscecsss sccsssdsecesesssocccessseceseesesssevessess 10 PRODUCT MATRIX fone M H 11 PART 2 TRANSDUCER INSTALL
25. ON AND TRANSDUCER MOUNTING 1 The piping surface where the transducers are to be mounted needs to be clean and dry Remove loose scale rust and paint to ensure satisfactory acoustical bonds 2 Connect the mounting straps around the pipe Leave the strap loose enough to slip the transduc ers underneath 3 Apply a liberal amount of couplant grease onto the transducer faces 4 Place each transducer under the mounting strap 180 apart on the pipe Ensure that the trans ducer cables are facing the same direction on the downstream side of the flow See Figure 1 2 5 Route the transducer cable back to the DFX monitor avoiding conduits that contain high voltage AC supply wires 06 DPP UM 00147 02 12 7 of Pipe FIGURE 1 2 TRANSDUCER DIRECTION 3 TRANSDUCER CONNECTIONS 1 Mount DFX monitor within the length of the transducer cables While transducer cable extension is not generally recommended if additional transducer cable length is required utilize cable and connectors of the correct type and impedance In many cases especially if a splice my be exposed to water or other liquids it may be more effective to replace the entire cable Transducers use RG59 75 ohm coaxial cable or Twinax Belden 9463 or Belden 9463DB 78 Ohm two conduc tor cable 2 Route the transducer cables through the center conduit hole in the bottom of the DFX enclosure and connect to terminal block J4 The terminal blocks a
26. OPERATION e 37 PART 5 STARTUP AND TROUBLESHOOTING sssccssssssccsssssscsssseecssssescssssecsssssscssssnscees 50 DEX START UP REQUIREMENT SS siccscssccossessssoccscscsescsesscesccesssocssesesesscecsseussesesssssecssesscesesesssescsasssssesessoosess 50 el LINEA ergo 51 06 DPP UM 00147 02 12 3 APPENDIX eem 53 SPECIFICATIONS isi ck ri D AREE RA sts 53 MENU MAPS A QUSS ERASI ERMR DIA QUE AK EDU IN I RR RUNE NEN MUR UR 55 PIPE TABLES iiam nd cn i ak o coi d c X Ko KI OR RT E E dE Ga CI cU KR o EX Ko DOR RR id 58 LIMITED WARRANTY AND DISCLAIMER ecccccccccceccoooooocoe0000000000000000000000000000000000000000000 62 WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT WEEE DIRECTIVE 63 RETURN SALES INFORMATION CONTACTS AND 64 4 06 DPP UM 00147 02 12 FIGURES FIGURE 1 1 TRANSDUCER LOCATIONS eeceeeccccccoccccoeococoeoooooesocooeseovooeseuooeessooeseseueeee00000000000000000000000000 7 FIGURE 1 2 TRANSDUCER DIRECTION eceeeccccccoccccocococoeoocooosocooooeoocooeseuooeeeso0esese0000000000000000000000000000000 8 FIGURE 2 1 PIPE CONFIGURATIONS AND INSTALLATION RECOMMENDATIONS
27. PROCEDURES CUSTOMER SERVICE APPLICATION ENGINEER If you have a question regarding order status placing an order reviewing applications for future purchases or wish to purchase a new flow meter please contact our national sales and marketing headquarters DYNASONICS Division of Racine Federated Inc 8635 Washington Avenue Racine WI 53406 PHONE 800 535 3569 or 262 639 6770 FAX 262 639 2267 SERVICE REPAIR DEPARTMENT If you already purchased equipment and have an operational problem require service or need to schedule field service please contact our service department DYNASONICS Division of Racine Federated Inc 8635 Washington Avenue Racine WI 53406 PHONE 800 535 3569 or 262 639 6770 FAX 262 639 2267 RETURN GOODS AUTHORIZATION When returning equipment it is necessary to contact our service department at 800 535 3569 or 262 639 6770 to obtain an RGA number for the authority and proper tracking of your material and its prompt inspection and return The RGA number should be noted on the outside of the box All returns of equipment go to the following address DYNASONICS Division of Racine Federated Inc 8635 Washington Avenue Racine WI 53406 Attn RGA 64 06 DPP UM 00147 02 12 Division of Racine Federated Inc 8635 Washington Avenue Racine WI 53406 3738 Toll Free in U S and Canada Tel 800 535 3569 Fax 800 732 8354 Tel 262 639 6770 Fax 262 639 2267 www dynasonics com RFD Racine Flow Met
28. R setting and may be an iterative process HARDWARE FILTER FILTER HARDWARE FILTER SELECTION NONE No Filter LOW 1600 Hz Cutoff MEDIUM 350 Hz Cutoff HIGH 250 Hz Cutoff Select the hardware filter with a cutoff frequency that is above the Doppler shift frequency to be mea sured The Doppler shift frequency is found by multiplying the flow velocity in FPS by 80 For example if the flow velocity is 4 FPS then the cutoff frequency is 4 x 80 or 320 Hz The filter with the next highest frequency would be 350 Hz TRANSDUCER TYPE TYPE TRANSDUCER TYPE DT9 Clamp on Transducers PROBE DP7 Insertion Probe Transducer Select the appropriate transducer type to be connected to the DFX transmitter The selection invokes optimum hardware and software settings unique to the transducer architecture CORRECTION FACTOR C FACTOR TRANSDUCER TYPE 0 01 5 00 This value is established at the factory during calibration If a new set of transducers or insertion probe is connected the new correction factor should be entered The correction factor values can be found on transducers or probes labels 48 06 DPP UM 00147 02 12 LINEARIZATION LINEAR ENTRY OF LINEARIZATION DATA The Linearization feature allows for correction of flow readings caused by non linear flow measurement This typically occurs when there is insufficient straight piping before or after the location where the transducers are mounted Up to 10 l
29. TIONS To access terminal strips for electronic connectors loosen the two screws in the enclosure door and open the door 1 Guide the transducer terminations through the transmitter conduit hole located in the bottom center of the enclosure Secure the transducer cable with the supplied conduit nut See Figure 3 2 Transducer Connections FIGURE 3 2 TRANSDUCER CABLE INSTALLATION 2 The terminals within the DFX are of a removable type they can be unplugged wired and then plugged back in Connect the appropriate wires to J4 at the corresponding screw terminals in the transmitter See Figure 3 3 or the Wiring Diagram located on the inner door of the transmitter NOTE The transducer cable carries low level high frequency signals While transducer cable extension is not generally recom mended if additional transducer cable length is required utilize cable and connectors of the correct type and impedance In many cases especially if a splice my be exposed to water or other liquids it may be more effective to replace the entire cable Transducers use RG59 75 ohm coaxial cable or Twinax Belden 9463 or Belden 9463DB 78 Ohm two conductor cable Cables to 990 feet 300 meters are available 06 DPP UM 00147 02 12 25 lt Grounding Wire Lock Nut FIGURE 3 3 TRANSDUCER CONNECTIONS POWER SUPPLY WIRING CONNECTIONS Connect power to the screw terminal block marked J2 in
30. URE 3 7 METER SYNCHRONIZATION DETAIL eceeeccccceccccccoccccesocooeoeoooooe0e000e0000000000000000000000000000000 30 FIGURE 3 8 DFX SYNCHRONIZATION CONNECTIONS eeeccccceccccccoccccoooooe000000000000000000000000000000000000000 31 FIGURE 3 9 TWO ISO MOD I O MODULES 32 FIGURE 3 10A MAXIMUM 4 20 MA LOADS ecececccccocccccccocccceoococesecooeooooveoe0e0ooe0000000000000000000000000000000 32 FIGURE 3 10B INTERNALLY POWERED 4 20 mhA eccecccccccccccccoccccesocoooo0e000e000000000000000000000000000000000000000 33 FIGURE 3 10C EXTERNALLY POWERED 4 20 eccecccccccccccccoccccesocoooo0oo0e000000000000000000000000000000000000000 34 FIGURE 3 11A TYPICAL RELAY CONNECTIONS ccceeccccccocccccoococesooooe00e00e000000000000000000000000000000000000000 34 FIGURE 3 11B EXTERNAL RELAY CONNECTIONS eeeeeccccccocccccoococesocooooouooeoe0e0e000000000000000000000000000000000 35 FIGURE 3 12 RATE PULSE MODULE aka aig aru senio aus RYE nx Tuc 36 FIGURE 4 1 KEYPAD LAYOUT eccceecccccooccccooococoeoooooeoeoooeo0o0e00e0000000000000000000000000000000000000000000000000000000000 37 FIGURE 4 2 4 20 MA CALIBRATION SETUP cceeccccccoccccocococoe0eooo0000000000000000000000000000000000000000000000000000 43 FIGURE 4 3 SINGLE POINT ALARM OPERATION 4er eere neret eaten sae etta sae et
31. al Seconds minutes hours days Totalizer Exponents from E 100 to x1 000 000 Response Time Flow User selectable 6 to 60 seconds 4 20 mA 800 Ohms max internal or external power supply 12 bit resolution optically isolated Dual Relay Independently configured Form C 200 VAC Q 0 5 A resistive rate alarm error alarm totalizer pulse Rate Pulse Two types Both 2 500 Hz max 12 bit resolution 1 500 mVAC 500 mVAC into 2K Ohm minimum 2 Open Collector Open Collector 100 V maximum Engineering Units Input Output Synchronization provision included utilized for multiple meter single pipe manifold sys tem Up to four meters may be interconnected up to 100 feet 30 meters apart Keypad Four keys tactile Ambient Conditions 40 F to 185 F 40 C to 85 C 0 to 95 96 relative humidity non condensing Std General safety U S and Canada certified to UL 61010 1 and CSA C22 2 61010 1 complies with EMC directive 2004 108 EC Multiple Meters Approvals 06 DPP UM 00147 02 12 53 TRANSDUCERS Housing Materials Cable Length 54 Compression mode Ultrasonic 625 kHz Standard Clamp on NEMA 6 IP 67 40 F to 250 F 40 C to 121 C CPVC Ultem Nylon PVC Cable Jacket Aluminum small pipe High Temperature Clamp on NEMA 4 IP 65 40 F to 400 F 40 C to 204 C Vespel Anodized Aluminum Nickel plated Brass Teflon Cable Jacke
32. asuring electrodes at the proper position in the pipe In order to complete this calculation some knowledge of the piping system must be known Refer to the paragraphs that fol low and Figure 2 6 for information regarding this process The variables required are The overall probe length Pipe internal diameter I D Pipe wall thickness The length of the valve stack Amount of straight pipe diameters in the system Using this information and referring to Figure 2 6 proper insertion depth can be determined Measurement A The typical depth that the DP7 probe tip is inserted into the piping system is 12 5 of the pipe internal diameter Measurement B Pipe wall thickness This information can be obtained from standard pipe wall charts See the Appendix of this manual or ideally can be measured using an ultrasonic wall thickness gauge Measurement C Measure the distance that is going to be taken up by the pipe tap nipple full flow ball valve and the insertion fitting DP7 probes utilize 17 NPT hardware and the insertion fitting is approximately 2 5 in height Measurement E This is the overall length of the probe measured from the black mea surement tip to the top flange on the probe Measurement D This is the length of DP7 probe that will be protruding from the inser tion fitting after it is inserted to the proper depth in the fluid stream 1 Lubricate the O rings located within the DP7 probe seal fitting s
33. ck sparks A and death if this product is handled in an unsafe way Service should only be done by quali fied personnel 1 Verify that the jumpers at JP3 are properly oriented for the power supply See Figure 3 4 Verify that the jumpers at JP1 and JP2 are not present 2 Connect L1 L2 and EARTH to the terminals referenced in Figure 3 4 Phase and neutral connec tions to L1 and L2 are not polarized Do not operate without an earth ground connection 3 See Figure 3 5 for AC connection schematic Wire gauges up to 14 AWG can be accommodated in the DFX terminal blocks a A switch or circuit breaker is required in the installation b The switch or circuit breaker must be in close proximity of the DFX and within easy reach of the operator C The switch or circuit breaker must be marked as the disconnect device for the DFX AC Power Connections 50 60 Hz 17 Watts Maximum FIGURE 3 5 DFX AC POWER CONNECTION 28 06 DPP UM 00147 02 12 POWER SUPPLY CONNECTIONS The DFX may be operated from a 12 28 VDC source as long as the source is capable of supplying 7 Watts 12 VDC Supply 600 mA minimum 24 VDC Supply 300 mA minimum 1 Verify that the jumpers are properly placed See the wiring diagram located on the inside door of the DFX enclosure or see Figure 3 4 The jumpers at JP3 should not be present and the jumpers at JP1 and JP2 will be in place 2 Connect the DC power source as illustrated in the schematic in Figure 3 6
34. ctile iron pipe do not need to be removed Thoroughly dry the mounting surfaces so that the couplant grease will properly bond to the surface NOTE Small pits in the piping surface typically do not significantly impact ultrasonic transmission or signal reception COUPLANT To assure an acoustically conductive path between the transducer face and the prepared piping surface a coupling compound is employed Clamp on ultrasonic meters will not operate without coupling com pound mounted between the pipe wall and the transducer face Enclosed with the DFX system is a tube of coupling compound that is adequate for general purpose applications Dynasonics prefers silicone based valve grease or RTV Room Temperature Vulcanizing products or grease for Doppler installations as they operate over a very wide temperature range In some installations such as automotive silicone is not permitted Alternate petroleum based products can be utilized but verify that the grease is rated not to flow at the maximum surface temperature anticipated on the pipe In general utilize the following couplants with these transducers DT90 DT91 DT94 DT95 Dow 732 or Dow 111 or equivalent DT92 DT93 DT96 DT97 Krytox LVP DP7 Not applicable DT9 CLAMP ON TRANSDUCER MOUNTING Clamp on transducers should be mounted on the pipe 180 apart and facing each other on the pipe with the cables on the downstream side of the transducers If the pipe is horizontal the pref
35. display only the Flow Rate select RATE To display only the Flow Total select TOTAL To alternately display the Flow Rate and the Total select BOTH By selecting BOTH the display will switch between RATE and TOTAL every 7 seconds The DIAG selection places the display in the diagnostics mode When selected the display will show the measured frequency the gain setting and the signal strength ENGINEERING UNITS FOR RATE RATE UNT Engineering Units for Flow Rate Choice Velocity in Linear Feet VEL FEET CUBIC ME Velocity in Linear Meters VEL MTRS Millions of Metric Liters MEGLTRS GALLONS ACRE FT OIL BARR Millions of Cubic Feet Select a desired engineering unit for flow rate measurements When Pounds LBS or Kilograms KGS is selected the specific gravity for the fluid type must be netered for the SP GRAV setup parameter 06 DPP UM 00147 02 12 39 ENGINEERING UNITS FOR RATE INTERVAL RATE INT Time Interval for Flow Rate Choice MIN Minutes HOUR Hours DAY Days SEC Seconds Select a desired engineering unit for flow rate measurements ENGINEERING UNITS FOR TOTALIZER TOTL UNT Engineering Units for Flow Totalizer Choice Velocity in Linear Feet VEL FEET CUBIC ME Velocity in Linear Meters VEL MTRS Millions of Metric Liters MEGLTRS GALLONS ACRE FT LBS Millions of Cubic Feet Select a desired engineering unit for flow accumulator totalizer measurements TOTAL MULTIPLIER
36. e at the terminals labeled on the ISO MOD 4 20 mA module see Figure 4 2 2 Using the arrow keys increase the numerical value to increase the current in the loop to 20 mA Decrease the value to decrease the current in the loop to 20 mA Typical values range between 3700 3900 counts 3 Re connect the 4 20 mA output circuitry as required 06 DPP UM 00147 02 12 43 4 20TEST 4 20 MA OUTPUT TEST Allows a simulated value to be output from the 4 20 mA output By incriminating this value the 4 20 mA output will transmit the indicated current value ISO MOD RATE PULSE FLOW OHZ Value FL MAXHZ Value RATE TST The Rate Pulse Output Module is utilized to transmit information to external counters and PID systems via a frequency output that is proportional to system flow rate Independent Zero and Span settings are established in memory using the flow measuring range entries Output resolution of the module is 12 bits 4096 discrete points and the maximum output frequency setting is 2 500 Hz The module has two output modes turbine meter simulation and open collector The turbine meter simulation sources a non ground referenced saw tooth waveform with a maximum peak amplitude of approximately 500 mV p p The open collector output utilizes a 0 21 Ohm MOSFET output that is rated to operate at 100 V and 1A maximum If the open collector output type is utilized an external voltage source and limit resistor must be present See Part 1 of th
37. e body or tip of the probe is most likely not above the ball Attempting to force the valve into the closed position may result in dam age to the probe 22 06 DPP UM 00147 02 12 PART 3 TRANSMITTER INSTALLATION UNPACKING After unpacking it is recommended to save the shipping carton and packing materials in case the instru ment is stored or re shipped Inspect the equipment and carton for damage If there is evidence of ship ping damage notify the carrier immediately MOUNTING LOCATION The enclosure should be mounted in an area that is convenient for servicing calibration and for observa tion of the LCD readout 1 Locate the transmitter within the length of transducer cable that was supplied with the DFX sys tem If this is not possible it is recommended that the cable be exchanged for one that is of prop er length While transducer cable extension is not generally recommended if additional trans ducer cable length is required utilize cable and connectors of the correct type and impedance In many cases especially if a splice be exposed to water or other liquids it may be more effective to replace the entire cable Transducers use RG59 75 ohm coaxial cable or Twinax Belden 9463 or Belden 9463DB 78 Ohm two conductor cable 2 Mount the DFX transmitter in a location that is Where little vibration exists e Protected from falling corrosive fluids e Within ambient temperature limits 40 to 185 F 4
38. ectrical Caution Refer to accompanying documents FLOW METER INSTALLATION IS KNOWN TO BE NON HAZARDOUS AVERTISSMENT RISQUE D EXPLOSION NE PAS DEBRANCHER TANT QUE LE CIRCUIT EST SOUS TENSION A MOINS QU IL NE S AGISSE D UN EMPLACEMENT NON DANGEREUX IMPORTANT NOTE Not following instructions properly may impair safety of equipment and or personnel WARNING A DO NOT CONNECT OR DISCONNECT EITHER POWER OR OUTPUTS UNLESS THE AREA ELECTRICAL SYMBOLS Direct Alternating Earth Protective Chassis Current Current Ground Ground Ground pet gt 6 06 DPP UM 00147 02 12 QUICK START OPERATING INSTRUCTIONS This manual contains detailed operating instructions for all aspects of the DFX flow instrument The following condensed instructions are provided to assist the operator in getting the instrument started up and running as quickly as possible This pertains to basic operation of the clamp on transducer only If specific instrument features a hazardous area installation or an alternate transducer style are to be used or if the installer is unfamiliar with this type of instrument refer to the appropriate section in the manual for complete details 1 TRANSDUCER LOCATION 1 Determine the appropriate mounting location for the transducers by referring to Figure 1 1 Pipe must be filled with liquid to ensure proper operation Top View of Pipe FIGURE 1 1 TRANSDUCER LOCATIONS 2 PIPE PREPARATI
39. ed to control inductive loads such as solenoids and motors TOTALIZER RELAY TOTAL mode configures the relay to output a 50 mSec pulse contact changeover each time the display totalizer increments FLOW RATE RELAY Flow Rate Relay configuration permits relay changeover at two separate flow rates allowing operation with an adjustable switch deadband Figure 4 3 illustrates how the setting of the two set points influ ences Rate Alarm operation A single point flow rate alarm would place the ON gt setting slightly higher than the OFF lt setting allow ing a switch deadband to be established If a deadband is not established switch chatter rapid switch ing may result if the flow rate is very close to the switch point Minimum Maximum Flow Flow gt i O O A a Output ON Output OFF L Deadband FIGURE 4 3 SINGLE POINT ALARM OPERATION 06 DPP UM 00147 02 12 45 When a relay is to ERROR mode the relay will activate when any error occurs in the flow meter that has caused the meter to stop measuring reliably See the Appendix of this manual for a list of potential error codes CONFIGURE I O MODULE 2 CFG MOD2 CONFIGURE I O MODULE 2 The configurations for MOD2 are identical to those detailed in CFG MOD1 CHANGE PASSWORD PASSWORD CHANGE THE SECURITY PASSWORD 0 9999 By changing the Security Password from 0000 to some other value any value between
40. er Group Dynasonics Flo tech PRESO racine DYNASONICS is a registered trademark of Racine Federated Inc Ultra and Ultralink are trademarks of Racine Federated Inc Belden is a registered trademark of Belden Technologies Inc BACnet is a registered trademark of American Society of Heating Refrigerating and Air Conditioning Engineers ASHRAE Windows Vista and Excel are registered trademarks of Microsoft Corporation National Electrical Code is a registered trademark of the NFPA Ultem is a registered trademark of General Electric Company Krytox is a registered trademark of DuPont Nemours and Company Vespel is a registered trademark of DuPont Nemours and Company UL is a registered trademark of Underwriters Laboratories Specifications are subject to change without notice 06 DPP UM 00147 02 12
41. er before servicing this met 9 P 21 115 4 5 2sovac b 9 o 9 28voc 9 P pag 2 JP1 JP Connections 2 1 o gt 2 1 28 VDC FIGURE 3 9 TWO ISO MOD 1 MODULES INSTALLED 4 20 MA OUTPUT MODULE The 4 20 mA Output Module interfaces with most recording and logging systems by transmitting an analog current signal that is proportional to system flow rate The 4 20 mA ISO MOD may be configured via jumper selections for either an internally powered Figure 3 10B or externally powered Figure 3 10C mode Care must be exercised to not exceed the maximum load for a particular supply voltage See Figure 3 10A Supply Voltage 7 VDC Maximum Loop Resistance 0 02 1100 1000 900 a 800 700 600 E 500 Sa Operate in the Shaded Regions 200 100 12 14 16 18 20 22 24 26 28 Supply Voltage VDC FIGURE 3 10A MAXIMUM 4 20 MA LOADS 32 06 DPP UM 00147 02 12 INTERNAL POWER CONFIGURATION Ensure that jumpers are in place at JP1 and JP2 on the module reference Figure 3 10B In this configu ration the 4 20 mA output is driven from a 24 VDC source located within the DFX flow meter The 24 VDC source is isolated from DC ground and earth ground connections within the DFX instrument The module can accommodate loop loads up to 800 Ohms in this configuration NOTE The 24 internal supply if configured t
42. erred mount ing orientation is 3 and 9 o clock with 12 o clock being the top of the pipe See Figure 2 3 Orientation on vertical pipes does not matter 06 DPP UM 00147 02 12 15 FIGURE 2 3 TRANSDUCER PLACEMENT PROCEDURE 1 Large pipe installations utilize stainless steel straps to secure the transducers to the outside of the pipe The DFX system is shipped with four 36 900 mm straps which are suitable for pipes up to 39 1000 mm diameter Select the proper number of transducer straps to allow a com plete strap to go around the circumference of the pipe If a pipe is larger than 39 1000 mm it is recommended that a single strap buckle arrangement be utilized to reduce the number of strap connections See Table 2 1 The straps can be connected together to make a continuous length Small pipe installations do not utilize straps but use an integral clamping mechanism built into the transducer 1 to 9 25 mm to 225 mm 10 to 19 250 mm to 480 mm 20 to 29 500 mm to 740 mm 30 to 39 760 mm to 1000 mm TABLE 2 1 STRAPS REQUIRED VS PIPE SIZE 2 Wrap the strap around the pipe in the area where the transducers are to be mounted Leave the strap loose enough to allow the transducers to be placed underneath If multiple straps are being used it can be beneficial to wrap electrical tape around all but one strap connection to secure the strap worm screws in place
43. for resolution 50 06 DPP UM 00147 02 12 TROUBLESHOOTING Insufficient power to DFX monitor measure voltage at J2 Power supply not properly wired to J2 See Part 3 Fuse F1 is open or not installed Power supply jumpers are not installed properly See Part 3 Ribbon cable between the door and enclosure back is not fully en gaged into the two sockets 1 Transducers not properly coupled to the pipe couplant not present or pipe not properly prepared 2 Transducer not properly wired to the Terminal block inside the DFX review the Wiring Diagram on the inside door of the DFX 3 More than one DFX installed on the piping system See Part 3 Mul tiple Unit Installation 4 Insufficient particles over 35 microns inject air upstream of the transducers 5 Too many particles that are smaller than 35 micron ultrasonic me ters likely will not operate 6 Transducer failure unplug transducer cable from measure itance between blue clear or red black Receive and Transmit Verify that the capacitance on each set is approximately 2 nF nano Farads and within 0 02 nF of each other Relocate transducer to a pipe position with less hydraulic disturbance Increase Damping value Ensure that ground connection is properly connected to meters earth ground See Figure 3 2 Verify that pipe ID is entered correctly Verify that an erroneous Scale Factor has not been entered Verify that erroneous
44. he flow meter will take several seconds to adjust to a step change in flow To make the flow meter respond quickly to changes in flow decrease DAMPING place the meter into MANUAL AGC and lock the FILTER at NONE DFX does not capture short flow pulses 52 06 DPP UM 00147 02 12 APPENDIX SPECIFICATIONS SYSTEM Measuring Principle Doppler Ultrasonic Velocity Range 0 15 to 30 FPS 0 05 to 9 MPS minimum calibrated span 0 15 to 5 FPS 0 05 to 2 MPS Accuracy 2 full scale over calibrated span Liquids containing a minimum of 100 ppm of useful sonic suspended reflectors greater than 35 micron Liquid Types in size and at least 25 of the overall particle volume is larger than 100 microns See Product Applica tions page for details TRANSMITTER NEMA 4X IP 66 Polycarbonate Stainless Steel Brass Plated Steel Mounting Brackets 7 00 H x 5 75 W x 3 88 D inches 178 H x 146 W x 99 D mm Power Supply 115 100 230 VAC 50 60 Hz 15 17 VA max 12 28 VDC 7 Watts max 2 line x 8 character LCD LED backlight Top Row 7 segment 0 7 18 mm high numeric Display Bottom Row 14 segment 0 35 9 mm high alpha numeric Flow Rate Indication 8 digit positive 7 digit negative max auto decimal lead zero blanking Flow Totalizer 8 digit positive 7 digit negative resettable Enclosure User configured gal liters million gal f m acre ft oil barrels 42 gal liquor barrels 31 5 gal ft m Ib kg Rate Interv
45. inal blocks together between the meters to be synchronized utilizing the twisted pair cable described previously The terminal block is located on the circuit board that is mounted on the door of the DFX monitor See Wiring Diagram Figure 3 4 the decal on the inner door of the DFX monitor or schematic 3 At a single point connect the shield drain wire from the interconnection cable to earth ground 4 Configure the SYNC SELECT jumpers on the DFX flow meters One DFX should be configured for INT and the remaining units configured for EXT see below 5 Apply power to the DFX system JP1 JP2 Connections 2 1 2 4 PES 9 2 39 FusBl5x20mm m 25 A 250V Delay A 250V Delay RED BUR BK RED AC am V lt gt wu v GN D EARTH SYNC SBLECT ui JEXT GNI EXT SYNC Ex RS 43 ME Twisted Pair Synchronization Shield Connect One End Selection Only to Earth Ground FIGURE 3 7 METER SYNCHRONIZATION DETAIL 30 06 DPP UM 00147 02 12 Master Meter Slave Meter Slave Meter TiN od E e ANS 21 rons E ES PRR I5 E v GND eaRTi A i CoS i i__ Twisted Pair i Twisted Pair Master Meter oniytoFarth Ground Slave Meters Wire Slave Meters Set to Internal Set to External Set to External Synchronization Synch
46. inearization points may be entered The microprocessor will perform a linear interpolation between data points entered in the linearization table and apply the associated correction factor to the measured flow rate Start by entering the number of linearization points to be entered at the NUM PTS prompt If a value of 00 is entered linearization is disabled The unit will then prompt for FREQ 1 to be entered Enter the measured frequency corresponding to the flow rate for the first point This can be obtained by running actual flow with the DISPLAY mode set to DIAG and reading the measured frequency or by calculating the frequency if the flow rate in feet per second is known using the following formulas DT9 Clamp On Transducer Freq Velocity FPS 80 Hz DP7 Insertion Probe Transducer Freq Velocity FPS x 80 Hz The unit will then prompt for COEFF 1 to be entered This is the value that the measured flow rate will be multiplied by at this point Enter the coefficient or correction factor to be applied The value entered must be between 0 5 and 1 5 Repeat this procedure for all of the linearization points When all of the points have been entered the unit will return to the NUM PTS prompt Press the Menu key to return to the main menu LINEAR prompt Then using the arrow keys move to the next setup parameter 06 DPP UM 00147 02 12 49 PART 5 STARTUP AND TROUBLESHOOTING DFX START UP REQUIREMENTS NOTE The DFX flow meter sys
47. is manual for connection information RATE PULSE SPAN The FLOW 0HZ and FL MAXHZ entries are used to set the span of the 0 2 5 kHz frequency output These entries are volumetric rate units that are equal to the volumetric units configured as Engineering Rate Units and Engineering Units Rate Interval For example to span the 0 2 5 kHz output from 0 GPM to 100 GPM with 1 25 kHz being 50 GPM set the FLOW 0HZ and FL MAXHZ values as follows FLOW 0 2 0 FL MAXHZ 100 0 RATE PULSE TEST RATE TST RATE PULSE OUTPUT TEST Allows a simulated value to be output from the rate pulse output By incrementing this value the rate pulse output will transmit the indicated frequency in terms of percentage of the maximum output fre quency For example if the maximum output frequency is 2500 Hz increment the displayed value to 50 to output a test frequency of 1250 Hz 44 06 DPP UM 00147 02 12 ISO MOD DUAL RELAY CONFIGURATION DUAL RELAY RELAY 1 AND RELAY 2 NONE TOTAL FLOW OFF lt ON gt ERRORS Two independent SPDT single pole double throw Form C relays are contained in this module The re lay operations are user configured via the keypad to act in either a total pulse output flow rate alarm or error alarm mode The relays are rated for 200 VAC maximum and a have current rating of 0 5 A resistive load 175 VDC 0 25 A resistive It is highly recommended that a secondary relay be utilized whenever the Control Relay ISO MOD is us
48. ly if a splice my be exposed to water or other liquids it may be more effective to replace the entire cable Transducers use RG59 75 ohm coaxial cable or Twinax Belden 9463 or Belden 9463DB 78 Ohm two conductor cable 8 If the transducers are to be permanently mounted using Dow 732 the RTV must be completely cured before proceeding to Instrument Start up Ensure that no relative motion between the transducer and pipe occurs during the 24 hour curing process If Dow 111 grease was used for temporary operation of the DFX system proceed with the Instrument Start up procedures DP7 PROBE TRANSDUCER MOUNTING The DP7 insertion transducer that is utilized by the DFX contains piezoelectric crystals for transmitting and receiving ultrasonic sound energy The black Ultem plastic tip of the DP7 contains these crystals which are designed to be inserted just into the path of the flowing liquid Select a transducer mounting location that will be completely filled with liquid when flow measurements are to be made See Figure 2 1 and with adequate straight runs without disturbances of pipe both upstream and downstream to achieve stable and accurate readings Examples of minimum upstream and downstream requirements are included in Figure 2 2 Note that if adequate straight piping cannot be provided the DFX system will operate repeatably but will probably not achieve ideal accuracy When installing the DP7 transducer in a horizontal pipe the prefe
49. meter can be successfully applied on a wide range of metering applications The easy to program transmitter allows the standard product to be used on pipe sizes ranging from 1 120 25 mm 3050 mm pipe 1 With the small pipe transducer option the pipe size range is 0 25 1 6 mm 25 mm A variety of liquid applications can be accommodated sewage river water plant effluent mining slurries sludge others Because the transducers are non contacting and have no moving parts the flow meter is not affected by system pressure fouling or wear Standard transducers are rated to a pipe surface temperature of 250 F 121 C Optional high temperature transducers are rated to operate to a pipe surface temperature of 400 F 204 C 06 DPP UM 00147 02 12 9 USER SAFETY The DFX employs modular construction and provides electrical safety for the operator The enclosure is constructed from rugged polycarbonate plastic with UV inhibitors The enclosure does not contain any conductive materials that can become energized while the door is closed The keypad is also manufac tured from polycarbonate and is designed for outdoor use The AC power transformer provides 4 000 Volts of isolation from the power supply mains The display face contains voltages no greater than 24 VDC Output modules are optically isolated from external power supplies and provide a great degree of immunity to ground loops DATA INTEGRITY CAUTION If the DFX is used
50. na 45 FIGURE 4 4 DIAGNOSTIC DISPLAY ecceecccccoccccccoccccesocccesoooooseooeoeseuooeesecoeee0e000e000000000000000000000000000000000 47 FIGUHEA T I MENU MAP T oscissci cossccecescccescseccccisscccecssseviccscsrssecccesccccvsstccevssscccessssevcscscescsevccsssccevsssovs 55 FIGURE A 1 2 MENU 2 2aeeeceecccccccccccccoccccoeocoocesocooosecooeeeoooseseuooe00e00e00000000000000000000000000000000000000000 56 06 DPP UM 00147 02 12 5 TABLES TABLE 2 1 STRAPS REQUIRED VS PIPE SIZE ccssesvcasiscsscsccsassacenssacannsseneusesansectasesssadscesasnaesaessensesssaansee 16 TABLE 4 1 EXPONENT VALUES ecceeeecccccoccccooococoesovooosocoooeeooeoeseuooe0000000000000000000000000000000000000000000000000000 40 TABLE A 1 1 SPECIFICATIONS eceeeccccecoccccocococcesovoceseccoceseccoseseuooeseuoooessooeoessuooees0e0e000e000e0000000000000000s0 54 TABLE A 2 1 FLUID PROPERTIES essssseeescooececoocececcocccecoocceccooececcoocceccocecccoceccccocccecoooecccococcecoocececoseceeooe 58 TABLE A 3 1 STEEL STAINLESS STEEL PIPE se ssssseescooecccoooececoocececooeccccooceccoooececoooccecoocececooeceeose 60 TABLE A 3 2 TUBE m 62 TABLE A 3 3 DUCTILE IRON PIPE STANDARD CLASSES s sseseosoosessossossosoesossocsossosoesossoesossecsesoesoe 63 TABLE A 3 4 CAST IRON PIPE STANDARD CLASSES s csecssssssossscssscscssscsssscsscsccsecesecesesesessnesees 64 SYMBOL EXPLANATIONS Caution Refer to accompanying documents El
51. ng the cables in cable tray configurations unless the trays are specifically used for other low voltage low level signal cables CAUTION The internal DP7 probe wiring is epoxy encapsulated to seal it from moisture The DP7 probe is provided with two coaxial cables to shield the low level signals and must be continuous to the DP7 probe transmitter Excess wire may be cutoff or simply coiled near the DFX instrument PROBE RETRACTION PROCEDURE 1 Retract the probe by loosening the upper jam nuts counterclockwise as viewed from the top of the probe using the proper size wrench If the pipe is under pressure the nuts must be turned alternately about two turns at a time to prevent binding as a result of non equal seal loading In many cases the line pressure will cause the probe to retract Should the probe bind use the re traction nuts on the lower side of the probe flange to assist in the probe retraction Continue this procedure until the probe is fully retracted into the isolation valve 06 DPP UM 00147 02 12 21 CAUTION Do not run the drive nuts off the rods until the isolation valve is fully closed 2 After the probe is retracted past the ball in the isolation valve the isolation valve may be closed to isolate the probe from the line and the probe can be removed entirely CAUTION If the insertion probe is not above the ball of the isolation valve the valve can not be closed If the valve will not close smoothly th
52. o power the 4 20 mA output shares acommon ground with another ISO MOD if installed If another module is connected to earth ground a ground loop may occur The solution to this problem is to configure the 4 20 mA module for external power and utilize an external isolated supply to power the 4 20 mA loop EXTERNAL POWER CONFIGURATION Remove the two jumpers located at JP1 and JP2 on the module reference Figure 3 10C In this con figuration the 4 20 mA module requires power from an external DC power supply The voltage of the external power source must be sufficient to power the module and drive the loop load The loop loss attributed to the ISO MOD is 7 VDC so the minimum voltage required to power a loop can be calculated using the following formula Loop voltage min loop load Ohms x 0 02 7 1 0 4 20 mA 00 P N 0020 1045 100 OUT INT PWR EXT PWR 2 ee 150 JP14 SA Use Both Jumpers FIGURE 3 10B INTERNALLY POWERED 4 20 mA 06 DPP UM 00147 02 12 33 1 0 4 20 mA 0 P N 0020 1045 100 OUT IN INT PWR EXT PWR JP25 1 ISO MO M Remove 1 1 Jumpers 4 FIGURE 3 10C EXTERNALLY POWERED 4 20 mA CONTROL RELAY OUTPUT MODULE Two independent SPDT single pole double throw Form C relays are contained in this module The relay operations are user configured via the front panel to act in either a flow rate alarm error alarm or
53. o that the seals are not damaged during probe insertion 2 Run the lower jam nuts down to a point that approximates the final insertion position or at least far enough to allow insertion into the insertion fitting Using the threaded rods as a guide posi tion the probe in the insertion fitting Continue to insert the probe as far into the isolation assem bly as possible The probe tip will come in contact with the closed ball in the isolation valve CAUTION Do Not Force the Probe Tip Against the Ball as damage to the probe tip may result 3 Replace the upper jam nuts 2 on each rod and the cotter pins The nuts should be run down to the top side of the retaining collar and the cotter pins replaced Orient the probe in the direction of flow as indicated by the FLOW direction arrow located on the top of the probe flange See Fig ure 2 8 Lock the probe in position with the enclosed Allen wrench CAUTION The nuts on both ends of the retaining rods must always be in place as a safety measure to prevent possible probe blow out Inserting cotter pins is a further safety measure 4 Slowly open the isolation valve When the valve is fully open use the proper size wrench on the insertion nuts alternately tightening each nut about two complete turns to avoid uneven seal loading 06 DPP UM 00147 02 12 19 NOTE For some low pressure low temperature applications less than 30 PSI 2 1 Bar and less than 100 F 38 C the probe may
54. ontains a four key tactile feedback keypad interface that allows the user to view and change configuration parameters used by the DFX operating system FIGURE 4 1 KEYPAD LAYOUT The DFX allows two basic sets of programming procedures list item selection and numeric value entry NOTE While in RUN mode pressing both the UP and DOWN arrow keys will display the current firmware version installed in the meter LIST ITEM SELECTION PROCEDURE NOTE If you are already in PROGRAM mode and the selection to be viewed or changed is already displayed proceed to step 3 below If you are in PROGRAM mode and the selection to be viewed or changed is not displayed press the UP or DOWN arrow keys and repeat pressing until the desired selection appears Proceed to step 3 1 Press MENU PROGRAM appears in the lower left hand corner and ID UNITS appears on the lower line of the display 2 Press the DOWN arrow key to move to the desired selection 3 Press ENTER to view the current selection 4 If the current selection is desired press ENTER to confirm The unit will automatically advance to the next selection 5 If the current selection must change press the UP arrow key and repeat pressing to scroll through the available choices Press ENTER to confirm your selection The unit will automatically advance to the next selection 6 To exit programming mode press the MENU key Depending on your position in the program ming mode up to three MENU ke
55. re a removable and can be disconnected to simplify wiring access A wiring diagram is located on the inner door for reference 4 STARTUP INITIAL SETTINGS AND POWER UP 1 Verify that the DFX power supply jumper settings are properly configured for the power supply that will be utilized A wiring and jumper selection diagram is located on the inner door for refer ence NOTE Power supply selection is specified during order placement and appropriate jumpers are placed at the factory If power is changed from AC to DC or vice versa the fuse requirement will change Fuse ratings are listed on the transmitter s door 2 Route power connections through the conduit hole farthest to the left and in the DFX enclosure Then connect power to the J2 terminal block See Figure 3 2 3 Apply power 4 On initial power up the DFX conducts a series of self diagnostic tests and buffering operations that take approximately 30 seconds 5 Enter pipe internal diameter Pipe ID measuring units and output configuration 8 06 DPP UM 00147 02 12 PART 1 INTRODUCTION GENERAL The DFX ultrasonic flow meter is designed to measure volumetric flow of solids bearing or aerated liquid within closed conduit Transducers are available as non contacting DT9 or insertion probe DP7 types DT9 non contacting transducers are strapped to the outside of a pipe and are suitable for most instal lations where the pipe material supports the transmission of ultrasound
56. ronization Synchronization FIGURE 3 8 DFX SYNCHRONIZATION CONNECTIONS ISO MODULES The DFX utilizes ISO MODs for input and output functions ISO MODs are epoxy encapsulated electronic input output modules that are simple to install and replace in the field See Figure 3 9 All modules are 2 500 V optically isolated from DFX power and earth grounds This eliminates the potential for ground loops and reduces the chance of severe damage in the event of an electrical surge Three ISO MOD options are available including 4 20 mA dual relay and rate pulse The DFX supports any two ISO MOD input output modules All modules are field configurable by utilizing the keyboard interface Field wiring connections to ISO MODs are quick and easy using removable wiring terminals Configuration and connection of the various ISO MODs are described on the following pages ISO MODULE REPLACEMENT To remove an ISO MOD remove the two machine screws that secure the module in place and pull the module straight out of the enclosure A 10 pin connection is on the bottom of the module that mates with the circuit board underneath Installation of a module is simply the reverse operation of removal 4 20 mA modules will require calibration parameters to be entered if the module is replaced See Part 4 of this manual for instructions on entry of calibration parameters 06 DPP UM 00147 02 12 31 VPP12 800 3 casse 9 b NO 4W b 6 A 12 i electrical pow
57. rred orientation is at least 20 degrees from the top or bottom of the pipe See Figure 2 4 Ensure that the mounting location allows for ad equate clearance to install and retract the probe fully from the pipe The following instructions also cover hot tapping installations where it is required to install or remove the transducer probe without shutting down the process pressure If the product is being installed with out an isolation valve ignore the steps that pertain to its installation Figure 2 5 illustrates an exploded view of an isolation valve assembly and names the various components 06 DPP UM 00147 02 12 17 If the Bronze Hot Tap p n D030 1006 001 or Stainless Steel Hot Tap Kit p n D030 1006 002 accessory kits were ordered with the DP7 probe a hot tapped installation can be complet ed The kits include an isolation valve assembly and are de signed for installation in pipes under pres sure up to 700 psi 48 Bar at 70 F 21 C All items required for installation are provid ___ Seal ed with the kit except Fitting for the 11 2 NPT weld coupling or service saddle and the drilling and welding equip ment These instruc _____ Full Port tions call for the use of a drilling machine designed for opera tions under pressure for example Mueller FIGURE 2 4 INSTALLATION LOCATIONS Nipple Co Water Products Division SS PROCEDURES ARE AS FOLLOWS 1 Verify that the
58. t Aluminum small pipe Doppler Probe NEMA 6 IP 67 700 PSI 48 Bar maximum 40 F to 210 F 40 C to 99 C 316 Stainless Steel Ultem Viton Nylon PVC Cable Jacket Optional Flexible Armored Conduit Zinc plated steel PVC Tested to a depth of 1 meter for 30 minutes Standard Clamp on 1 inch 25 mm and larger Small Pipe Clamp on 1 4 inch to 1 inch 6 mm to 25 mm Insertion Probe 4 inches to 120 inches 101 mm to 3050 mm Up to 990 ft 300 meters Standard lengths 20 50 100 ft 6 15 30 meters 78 ohm Twinax cable Optional lengths to 990 feet 297 meters 75 ohm RG59 cable TABLE A 1 1 SPECIFICATIONS 06 DPP UM 00147 02 12 ajnpoyy 1 HUN eio JO 93e UI papajas 10 5871 i sieadde Aquo Ajireig yi eds i 55 MENU MAPS SHA 00 LX QOL X 1333 13A S5 581 eo zr sul 2181025 13 21802 TWOW syal SNOTIVD Aaquy uasoup sjulod jeaui Jequunu ay uo Hulpuadap 912 gt 01 0 dn asinbas SHA SHA WANVW HDIH TVWHON 0100 13u3 NIW 235 ajnpow oL
59. tem requires a full pipe of flowing liquid before a successful startup evaluation can be completed Do not attempt to make adjustments or make Manual configuration changes until a full pipe of flowing liquid is verified NOTE If an RTV sealant was utilized to couple the transducers to the pipe the sealant must fully cure before power is applied to the instrument Most RTVs require 24 hours to cure satisfactorily It is very important that the transducers are not moved during the curing process air bubbles can form between the transducer and the pipe wall and influence performance If silicone grease was utilized as a couplant the curing time is not required PROCEDURE 1 Verify that the 9 or DP7 transducer has been properly installed and wired See Part 2 2 Verify that the DFX power supply jumper settings are properly configured for the power supply that will be utilized See Part 3 3 Verify that the DFX is properly programmed See Part 4 4 Apply power 5 On initial power up the DFX microprocessor conducts a series of self diagnostic tests base line measurements and begins to buffer liquid velocity data During this start up approximately 30 seconds flow rate readings and outputs will be inhibited 6 After the start up routine has completed running the meter will begin to display flow rate and or total as configured 7 If an ERROR appears on the DFX lower display pleaser refer to the following Troubleshooting pages
60. uired The two locations illustrated in the top two drawings may allow the meter to operate but it is unlikely that stable and accurate flow readings will be realized over a very large range of flow Since products like the DFX have software algorithms that assume a full pipe of liquid partially filled pipes can lead to very large flow measurement errors and should be avoided 9 y FIGURE 2 1 PIPE CONFIGURATIONS AND INSTALLATION RECOMMENDATIONS 06 DPP UM 00147 02 12 13 Select a transducer mounting location with adequate straight runs of pipe both upstream and down stream to achieve stable readings Examples of minimum upstream and downstream requirements are included in Figure 2 2 Piping Configuration and Transducer Positioning FIGURE 2 2 UPSTREAM DOWNSTREAM PIPE REQUIREMENTS The DFX system will provide repeatable measurements on piping systems that do not meet these requirements but the accuracy may be influenced to various degrees 14 06 DPP UM 00147 02 12 PIPE PREPARATION Before the transducer heads are mounted to the pipe surface an area slightly larger than the flat surface of the transducer face must be prepared If pipe insulation is present it must be peeled back to expose the pipe surface Typical preparation involves wire brush removal of loose paint rust scale or dirt Paint if bonded well to the pipe surface does not need to be removed The bumps present on du
61. vance to the next selection 6 To exit programming mode press the MENU key Depending on your position in the program ming mode up to three MENU key presses may be required to exit The display will change to RUN mode MENU STRUCTURE The DFX software is structured using menus A menu map of the user interface is included in the Appendix of this manual The map provides a visual path to the configuration parameters that users can access This tool should be employed each time configuration parameters are accessed or revised TOTALIZER RESET Press both the ENTER and the MENU keys when in the RUN mode to reset the totalizer The message TOTAL RST will be displayed for a few seconds to indicate that the totalizer had been cleared If a pass word has been set the user must enter the correct password for the totalizer to be cleared The following sections define the configuration parameters accessible in the program mode UNITS SELECTION ID UNITS Measurement Units Selection Choice INCH MM Selects unit of measure for pipe ID entry The choices are either inches English or millimeters Metric unites 38 06 DPP UM 00147 02 12 PIPE INSIDE DIAMETER PIPE ID Pipe Inside Diameter Entry Value ENGLSH Inches METRIC Millimeters Enter the pipe inside diameter in inches if INCH was selected as ID UNITS in millimeters if MM was se lected DISPLAY MODE DISPLAY Display Mode Selection Choice RATE TOTAL BOTH DIAG To
62. wo types of outputs one simulates the output of the coil of a turbine flow meter and the other is an open collector type that does not source voltage at its output Both outputs may be connected simultaneously The turbine meter output creates a 500 mV peak to peak saw tooth waveform that is not referenced to ground This output can be run to electronic monitors that are compatible with variable reluctance outputs from coils such as those found in turbine and paddle wheel flow meters The input impedance of the receiving device should not be smaller than 2 000 Ohms The standard pulse output does not output a voltage but acts as an open collector output requiring an external power source and pull up resistor See Figure 3 12 The MOSFET in the Rate Pulse Module can support loads of 100 V Q 1 A Resistor selection is based on the input impedance of the receiving device Select a resistor that is a maximum of 1096 of the input impedance of the receiving device but does not exceed 10k Ohms 06 DPP UM 00147 02 12 35 500 0 0 2 5KHz 4 0020 1045 207 TURBINE TURBINE A 2 V FIGURE 3 12 RATE PULSE MODULE 36 06 DPP UM 00147 02 12 PART 4 INSTRUMENT PROGRAMMING GENERAL The DFX is configured through the keypad interface All entries are saved in non volatile FLASH memory and will be retained indefinitely in the event of power loss KEYPAD OPERATION The DFX c
63. ws FLOW 4MA 0 0 FLOW 20MA 100 0 42 06 DPP UM 00147 02 12 4 20 CALIBRATION The 4 20 mA ISO MOD is factory calibrated and should not require adjustment unless it is replaced NOTE The CAL 4MA and CAL 20MA entries should not be used in an attempt to set the 4 20 mA range Utilize FLOW 4MA and FLOW 20MA detailed above for this purpose ny CAL 4MA CHOICE The 4 20CAL entry allows fine adjustments to be made to the zero and span of the 4 20 mA output re Select YES to access adjustment To adjust the 4 mA T m Em output a milliammeter or reliable reference must be 9 connected to the 4 20 mA output us PROCEDURE 1 Disconnect one side of the current loop and connect the milliammeter in series disconnect either wire at the terminals labeled on the ISO MOD 4 20 mA module see Figure 4 2 2 Using the arrow keys increase the numerical value to increase the current in the loop to 4 mA Decrease the value to decrease the cur rent in the loop to 4 mA Typical values range between 40 80 counts ye ee 3 Re connect the 4 20 mA output circuitry as Q V required OUT CAL 20MA VALUE ibd gt Calibration of the 20 mA setting is conducted much JPi o same way as the 4 mA adjustments PROCEDURE FIGURE 4 2 4 20 mA CALIBRATION SETUP 1 Disconnect one side of the current loop and connect the milliammeter in series disconnect either wir
64. y presses may be required to exit The display will change to RUN mode NOTE The DFX firmware revision can be displayed by pressing both arrow keys simultaneously 06 DPP UM 00147 02 12 37 NUMERIC VALUE ENTRY PROCEDURE NOTE If you are already in PROGRAM mode and the selection to be viewed or changed is already displayed proceed to step 3 below If you are in PROGRAM mode and the selection to be viewed or changed is not displayed press the UP or DOWN arrow keys and repeat pressing until the desired selection appears Proceed to step 3 1 Press MENU PROGRAM appears in the lower left hand corner and ID UNITS appears on the lower line of the display 2 Press the DOWN arrow key until the desired selection displays The current numeric value for this selection appears on the upper line of the display 3 If the current value is desired press ENTER The left most programmable number begins to flash Press ENTER again to confirm and keep the current numeric value The unit will automatically advance to the next menu selection 4 If the current selection must be changed press ENTER The left most programmable number be gins to flash Use the UP arrow key to scroll through the digits 0 9 and change the flashing digit to the desired value Use the DOWN arrow key to move the active digit to the right Continue using the UP and DOWN arrow keys until all digits are selected 5 Press ENTER to confirm your selection The unit will automatically ad
Download Pdf Manuals
Related Search
Related Contents
H27.1.1 (PDF形式 : 1MB) Le contrat d`apprentissage (en ) Sony CDX-2500R User's Manual Istruzioni d`uso CANADA - MODE D`EMPLOI (9782742434428) 16 CUP 4 QT. FOOD PROCESSOR a40 variteam Copyright © All rights reserved.
Failed to retrieve file