        February 2015 Wayne Electric Shop Intrusion Page 1 of 17 WAYNE
         Contents
1.      The Contractor is to furnish and install new intrusion devices in the locations shown on  the attached drawings     The Intrusion System shall be non proprietary  The alarm equipment must be readily  available for purchase  installation and service  by any reputable contractor regularly  engaged in the burglar intrusion alarm installation and service business  Additionally   the equipment must be capable of being readily monitored  without losing type alarm   intrusion  supervisory  and trouble  and specific zone or point  by any non proprietary  receiver  Further  replacement parts and system training must be readily available at a  reasonable cost to whoever maintains the alarm equipment for SEPTA  This may  include SEPTA personnel or a third party contractor     If required  Contractor shall apply for permits with the City of Philadelphia     The Alarm contractor shall submit  for SEPTA approval  all of the specific Intrusion  Devices that will be used in this contract  The Contractor is expected to ensure high  quality in all components of the system that are specified     Wayne Electric Shop Intrusion Page 1 of 17    February 2015    1 02 REFERENCES  A  Underwriters Laboratories  UL    1  UL385   Grades A  AA Police Connect   2  UL609   Grade A Local Mercantile Premises and Mercantile Safe and Vault   3  UL611 UL610   Grades A  AA Central Station   4  UL684   Local  Central Station  and Remote Station     B  Federal Communications Commission  FCC    1  FCC Part 15  
2.  P  Wires shall be color coded and labeled to allow zone identification at terminal and  junction locations  Zone identification labels must be of high quality and equal to the  3M ScotchCode Wire Marking Tape     Q  If the installation is located where it has an increased potential risk of damage from  vehicle damage or vandalism this portion of the conduit shall be required to be rigid  steel  EMT will not be permitted in these situations   Review these locations with the  project manager prior to procuring and installing conduits  Project Manager has the  right to have any section of EMT changed to Rigid Steel even if EMT has already  been installed and at no additional cost to SEPTA     R  If the installation is located in an area that requires an explosion proof system  the  installation should be in accordance with NFPA 69     Wayne Electric Shop Intrusion Page 12 of 17    2 08    2 09    February 2015    SURGE PROTECTION MODULES    Provide surge protection for the incoming power to the intrusion alarm main panel and all  remote power supply panels  Protection device shall be mounted either in or adjacent to  each intrusion alarm panel and not at the electrical distribution panel serving the fire  alarm panel s      The surge protection shall be a Ditek Model DTK 120SR Module or SEPTA approved  equivalent for incoming fire alarm panel power circuits     Surge protection shall be UL 497B Listed and be compatible with the FACP     Surge protection shall be installed in ac
3.  labor  at no charge to SEPTA during the warranty period     C  All manufacturers    warranties shall be in SEPTA   s name  If the Contractor modifies any  equipment to void any manufacturers warranty  the Contractor shall provide a  warranty equivalent to that of the original manufacturer   s warranty     D    The Contractor shall provide a  maximum  two hour response time for service calls  during the warranty period     E  The Warranty period starts the day when the SEPTA 3  Party Burglar Intrusion Fire  Alarm Maintenance  Monitoring and Inspection Co  has accepted the intrusion alarm  system to their central monitoring station     PART 2 PRODUCTS  2 01 SYSTEM PERFORMANCE    A  The Main Burglar Intrusion Control Panel shall be an ADEMCO VISTA 128BPT or  SEPTA approved equal     1  The Control Panel must be an 8 partition unit  capable of supporting hardwire   hardwire expansion and wireless zones  Peripheral devices supported by the  Control Panel shall include bells  cellular communicator  dialers  telephone lines    keypads  RF receivers  and relays  The following minimum performance  requirements shall be met     a  Basic Hardwire Zones   A total of 9 style B hardwire zones shall be capable of  supporting the following   i    EOLR supervision supporting normally open  N O   or normally closed   N C   sensors   ii  Individually assignable to one of 2 partitions     iii  Individually assignable to bell outputs and or auxiliary relay     Wayne Electric Shop Intrusion Page 
4.  material  etc      INTRUSION ALARM MONITORING CUTOVER    Contractor shall be responsible for the payment to the current burglar intrusion alarm  monitoring company  TYCOIS  for the final installation of this intrusion alarm system to  their monitoring system and database     The Contractor shall be solely responsible for coordinating with TYCOIS and confirming  that their monitoring practices and protocols are compliant with the intrusion alarm  system design and final installation     Contractor shall be responsible for coordinating the installation with the SEPTA Project  Manager and the alarm monitoring company  TYCOIS      Wayne Electric Shop Intrusion Page 16 of 17    February 2015  3 08 INVOICING    A      Contractor shall submit payment at 100  of project completion to be approved by the  Project Manager and or their designee prior to final approval for payment  No interim  payments shall be permitted     B  Invoice shall be mailed to SEPTA  ATTN  Robert J  Tangi  12  Floor  1234 Market  Street  Philadelphia  PA 19107     END OF SPECIFICATION    Wayne Electric Shop Intrusion Page 17 of 17    
5.  plans and tested in accordance with the  manufacturer s specifications and the appropriate local code requirements    2  Provide a hardcopy and MSExcel versions of the zone list with its descriptions as   installed in the intrusion alarm system   NOTE  Final Zone list descriptions must   be approved by the Project Manager prior to being installed in the intrusion alarm  system     Provide a    Record of Alarm Inspection  Testing  and Certification       Provide a copy of any require permits and approvals by the City of Philadelphia if   applicable    Provide a copy of the final electrical inspection performed on this installation    Provide a copy of UL certificates or FM placards    Provide four sets of all keys to the Alarm system panel    Provide copies of the user manual   Provide a record of the installed Operating System Software  Sometimes referred   to as firmware  BIOS  or Executive Program  and site specific software  runs at a   level below the operating system software and is specific to the Alarm System   installation  version numbers    10  Provide two copies of the site specific software     A W    OOO Oo    Upon satisfactory completion of the acceptance requirements  the contractor shall  coordinate with SEPTA E  M  amp  C Contract Services  the exact date of cut over of  system monitoring to the current burglar intrusion fire alarm monitoring contractor   Successful programming of the system to the 3 party alarm monitoring contractor will  complete the accep
6.  whip     Floor  mounted contacts are not permitted     B  All equipment devices shall be installed in all locations as follows     2 06    2 07    1  Each overhead door throughout the building shall receive a single intrusion   contact    Each single man door shall receive a single intrusion contact    Each double door shall receive a single contact for EACH opening door    There shalll be a horn and strobe installed at each single man door and each   double door location    5  There shall be a horn and strobe installed half way between column line C 1  and C 17    6  Install an outdoor horn and strobe outside of the man door located at column line  G 1    7  There shall be a keypad installed inside the man door at column G 1 and a  second keypad installed on the door of the main intrusion panel     AON    INTRUSION SYSTEM PROGRAMMING    Entry Exit Delay     Man door at column line G 1 shall have a 30 second entry and exit  time delay   Intrusion detection    i  Each single man door and overhead contact shall have its own individual address   ii  Double man door shall have an individual address for both doors   Double door  contacts shall annunciate on a single address point    iii  If any one contact is breached activated all of the horn and strobes and keypad  tone devices shall activate     FIRE ALARM SYSTEM POWER  RACEWAY AND WIRING    Intrusion wiring shall be permit to be run    free air     only if it is installed no less than 10  feet above the finished floor  All fr
7. 2  FCC Part 68    1 03 SYSTEM DESCRIPTION  A  Provide a and Burglary Intrusion Alarm System that includes the following capabilities   Commercial UL listed system   Supporting up to 32 zones   Interfacing with  an alpha numeric paging device   Operating with a long range radio unit   Operating with an integrated security and access control systems   Supporting zone for supervision of peripheral devices     at Oe ee ee NS    A scheduling capability to allow for automated operations     1 04 SUBMITTALS  A  Submittals shall include manufacturer data sheets for all major system components     1 05 QUALITY ASSURANCE    A  The alarm manufacture shall be certified as being compliant with ISO900l1     1 06 VISIT TO JOB SITE    K  it is the contractor s responsibility to familiarize himself herself with the existing  conditions of the shops  The acceptance of this bid shall presuppose the contractor s  entire familiarity with the conditions  and no extra cost will be allowed due to the  contractor having failed to visit the sites and to note the conditions affecting the work     Wayne Electric Shop Intrusion Page 2 of 17    February 2015    1 07 SCHEDULING  A    Work shall commence immediately upon award of Notice To Proceed     1 08 NON PERFORMANCE BY CONTRACTOR    A  If the contractor fails to perform services in accordance with contract requirements   SEPTA shall obtain those services through other means including the use of internal  resources or issuing a contract or purchase ord
8. 4 of 17    February 2015    b  Polling Loop Expansion Zones   The Control Panel shall also be capable of  supporting up to 24 additional hardwire zones using a built in  2 wire  polling   addressable  loop interface  The polling loop shall provide power and data to  remote point modules  and constantly monitor the status of all zones on the    loop     The polling loop zones shall be capable of   Using Remote Point Module  RPM  devices     Providing individual point addresses for each intrusion point  unless  otherwise directed in the contract documents      iii  Supervision by the Control Panel     iv  Individually assignable to one of the partitions     Individually assignable to bell outputs and or auxiliary relay     vi  4 000 foot capability without shielded cable     C  Partitions   The independent partitions shall provide the following features     vi     A Common Lobby partition shall be capable of automatic arming  when the  last partition sharing the lobby is armed  and automatically disarmed when  the first partition sharing the common lobby is disarmed     A Master Partition shall be provided for assigning keypads capable of  simultaneously viewing the system status of both partitions     Both partitions shall be capable of having keypads assigned   Both partitions shall be capable of supporting relays     The ability to display burglary and panic and or trouble conditions at all  other partition keypads shall be optional     The ability to support selectable opti
9. February 2015    WAYNE JUNCTION CAR SHOP  INTRUSION DETECTION SYSTEM    PART 1 GENERAL    1 01    A     B     DESCRIPTION    All of the work within this project shall be at SEPTA   s Wayne Electric Car Shop located  at 4500 Germantown Ave   Philadelphia  PA     The Contractor shall design and install a completely functional Intrusion Alarm System   in full compliance with all codes  regulations  SEPTA Standards and guidance as  stated in this scope of work     The Fire Alarm System shall include but not be limited to  control panel  power supply   remote power supplies  alarm initiating and notification devices  connections to  supplementary systems  conduit  wire and accessories to provide a complete and fully  operational system     The intent of this project is to provide intrusion detection at all the exterior man doors  and overhead bay doors in the locations shown in the attached building drawing     Contractor shall thoroughly instruct and has the responsibility to fully inform all their  workers and agents of the fact that they are working next to adjacent active rail  maintenance shops  Proper safety precautions must be taken by the Contractor to  prevent accidents  Contractor employees and their supervisor must attend and  successfully complete Railroad  Track Safety  safety class prior to any work starting at  the railroad job sites     This maintenance shop building is occupied therefore work will need to be coordinated  with daily work activities in this location
10. The  trigger connector pins change state for different conditions in order to interface  with equipment such as long range radio equipment  LRR   remote keypad  sounders  and key switch ARMED and READY LEDs  or a system event log  printer     p  Event Log   The Control Panel shall contain a programmable event log capable  of the following   i  Storing up to 224 events   ii  Viewable at the keypad   iii    Printed on a serial printer   iv  Storing access control system events     v    Sending printed events to an alphanumeric pager     q  Scheduling   The Control Panel shall provide the following automated  scheduling capabilities     i    Open Close schedules used to control arming disarming and reporting     ii  Holiday schedules  which allow different time windows for open close  schedules     iii  Timed events which activate relays  auto bypassing  un bypassing  auto   arming and disarming     iv  Access schedules  which limit system access to users  by name     v  End User Output Programming Mode shall provide 20 timers for relay  control     r  Communication Formats   The Control Panel shall be able to communicate  Fire  Trouble  Supervisory and Contact ID signals back to the central  monitoring company  TycolS  without the use of a separate communicator  device     s  Audio Alarm Verification   The Control Panel shall support programmable audio  alarm verification  AAV  devices  capable of operating in conjunction with an  output relay  to permit two way voice dialog be
11. a relay command mode    v    Supervised by control panel    vi  Assigned an alpha descriptor     k  Ancillary Control   The Control Panel shall be capable of being programmed to  activate up to 16 control relays which could open doors  turn on off lights  etc        12 Volt Power Supply   The Control Panel shall have a 12 Volt power supply  transformer  The transformer shall supply a total of 2 3 amps total for both  panel notification circuits and ancillary functions     i  Alarm notification appliances  including but not limited to sirens and  strobes     ii  Power for relays  keypad annunciators  4 wire smoke detectors  access  control devices  etc     m  Telephone Dialers   The Control Panel shall be equipped with a built in  supervised telephone dialer for communications with the central station  It shall  also be capable of supporting a supervised backup dialer for connecting to a  second telephone line for commercial fire applications     n  Trigger Output Connector   The Control Panel shall contain an internal  connector equipped for a single input and seven outputs  The outputs shall  interface with    i  Remote keypad sounder    ii  UL  Listed key switch    iii  LED indicator module    iv  Auxiliary alarm signaling equipment    v  Event logging serial printer    vi    Computer used to direct wire downloading via a serial module     Wayne Electric Shop Intrusion Page 7 of 17    February 2015    o  Voltage Triggers   The Control Panel shall provide a trigger outputs  
12. bruary 2015    PART 3 EXECUTION    3 01    A     3 02    3 03    3 04    POWER WIRING    Contractor shall provide 120Volt volt power to the new intrusion alarm system main  panel and any other panel or devices as required to complete the system     SYSTEM COMMUNICATION   The intrusion alarm system will a single dedicated telephone line to communicate with  the Central Monitoring Station  Contractor shall provide conduit and wiring back to the  designated communications room or cabinet as required to allow the new intrusion  alarm system the capability to communicate with the central monitoring     MOUNTING OF EQUIPMENT AND DEVICES    All equipment and intrusion devices must be secured by using screws and hollow walls  anchors as required  Double Sided Tape of any kind will not be permitted to anchor  any device and or equipment to its mounting surface     Main Intrusion Alarm Panel shall be mounted in the second floor office area  immediately next to the existing fire alarm panel     Main Intrusion Alarm Panel shall have an independent keypad mounted on the door of  the main panel unless the Project Manager specifies it to be installed at another  location in the office area     MONITORING AND ACCEPTANCE    The contractor shall set this panel up to be monitored by individual zones  One zone  for intrusion entry exit by the main entrance  Further breakdown of the zones may be  requested by the project manager and if requested these zones shall be programmed  at no additional c
13. cordance with Manufacturer   s installation  instructions     Wire connections shall utilize screw terminal connections   REMOTE ANNUNCIATOR    Two remote annunciators shall be installed for the intrusion alarm system  One shall be  installed on the door of the main intrusion alarm panel  A second one shall be installed  at the at the main building entrance in the lobby at column line G 1     Remote annunciator shall be a Honeywell model 6160 or septa approved equal   Remote annunciator shall be UL Listed and FM Approved with the main intrusion panel     Remote annunciator shall indicate alarm  Trouble and Supervisory alarm status for each  monitored point     Remote annunciator shall have the ability to control the intrusion panel Acknowledge   Silence and Reset alarm functions     Must have a minimum of 32 character display screen with English language messages     SUPPLEMENTARY AND OTHER FIRE ALARM SYSTEM DEVICES    If remote power supply modules are required they should be of the same manufacturer  of the intrusion alarm system main panel     The power module must have 6 0 amps of output power     They must have sealed lead acid or gel type batteries capable of powering the  connected load and have spare capacity to power a fully connected load for a minimum  of 1 hour     They must have built in battery chargers for sealed lead acid or gel type batteries with  automatic switchover to standby battery when AC power fails    Wayne Electric Shop Intrusion Page 13 of 17    Fe
14. d  Total alarm current draw when using two NAC  outputs shall not exceed 2 3 amps for battery independent operation     h  Auxiliary Relay   A built in Form C relay shall be provided  The relay contacts  shall be rated at 28 VAC VDC  2 8 amps maximum  The relay shall support   i  Alarm activation   ii    Trouble supervisory activation   iii  Reset of 4 wire smoke detectors   iv  Battery saving feature     i  Output Relays   A total of 16 relay outputs shall be accommodated using relay  modules  Each relay module shall provide four Form C  normally open and  normally closed  relays for general purpose use or two Y style supervised bell  outputs  The relay characteristics shall be capable of being    i  Programmed to activate in response to system events   ii    Programmed to activate using time intervals     iii  Used for additional y style supervised be NAC outputs     Wayne Electric Shop Intrusion Page 6 of 17    February 2015    iv  Activated manually using a relay command mode   v    Supervised by control panel   vi    Assigned an alpha descriptor     i  Addressable Loop Output Relay   A total of 16 Form C  normally open and  normally closed  shall be accommodated using the addressable detection loop  single relay module  The relay characteristics shall be capable of being    i  Programmed to activate in response to system events   ii    Programmed to activate using time intervals    iii  Used for additional y style supervised be NAC outputs   iv  Activated manually using 
15. ded for End User convenience  The following shall be provided     i  A brief explanation of keypad functions shall be provided at the keypad  alphanumeric display     Access Control  i  In addition  the Control Panel shall be capable of being connected to an  integrated access control systems     ii    The panel shall be capable of supporting three different methods of  wiegand access control card readers  These are by use of the ECP bus  or the V Plex addressable loop     ENCLOSURE    The Control Panel shall be enclosed in a metal cabinet  suitable for wall mounting   The dimensions shall not exceed 18 inches in height  14 5 inches in width or 4 3  inches in depth     Wayne Electric Shop Intrusion Page 9 of 17    February 2015    2 03 ELECTRICAL POWER REQUIREMENT S    A  System Power   The Burglary Intrusion Alarm System main control panel shall operate  using standard 120 volts AC  60 Hz power     1   2     Control Primary Power   Transformer power shall be 18 VAC  17VA   Backup Battery   A rechargeable 12 VDC  gel type  lead acid backup battery shall  be provided  The battery shall be rated between 12 and 34 ampere hours  AH      Alarm Power  Maximum alarm output power shall be 12 VDC  1 7 amps for each  NAC output     4  Auxiliary Standby Power   Standby power shall be 12 VDC  1 amp maximum     5  Total Power   Combined auxiliary standby and alarm currents shall be 2 3 amps     Fusing   The battery input  auxiliary  and bell outputs shall be protected using PTC  circuit b
16. ee air cabling must be properly supported at least  every 10 feet  Any wiring installed below 10 feet must be installed in conduit per this  specification     Metal Conduit must be used for all device wiring where wiring is being brought down  from the main cable to the addressable module and final detection device s      Design Installation must provide for the complete labeling of the raceway and all  junction and pull boxes as    INTRUSION ALARM SYSTEM     Labels must be  waterproof  peal off type   Connection box labels should be octagon shaped and  measure 3    across  Conduit should be labeled at a minimum of every 20 feet  shorter  lengths of conduit between connection boxes should be labeled at the midway point   Conduit labels should be rectangular shaped and measure 3   4    wide by 5 12    long     Wayne Electric Shop Intrusion Page 11 of 17    February 2015    D  The raceway shall be installed in a manner that considers the effects of electrical and  Radio Frequency noise to prevent or minimize induced or electromagnetic  interference    E  Conduits and or wiring shall not be installed less than 12 inches from any conduit or    exposed electrical bus work and or distribution panel containing 480Volt or higher  voltage electrical conductors     F  Cast metal or plastic molded boxes  not sheet metal  shall be used for surface  mounting any device s  to any exposed wall surface or support beam  i e  in the  ceiling above shop areas  electrical substations  boiler roo
17. er to another contractor for the  services     B  Additionally  SEPTA s increased cost to have the service performed by other means  will be deducted from the Contractor s invoice     1 09 DUTY TO INFORM EMPLOYEES OF CONDITIONS    A      The contractor shall thoroughly instruct and has the responsibility to fully inform all  his her workers and agents of the fact that they are working adjacent to active rail  maintenance tracks and high voltage     B    Contractors employees  and their supervisor  who work on the job site must attend  SEPTA   s Roadway Worker track Safety Class  not required if workers already have  current certification  8 hours class time for an initial certification  4 hours class time if a  renewal  and attend a shop safety briefing  4 hours   Attendance at these classes and  in the SEPTA facility requires SEPTA approved vests and flashlights  Attendance and  equipment is at the Contractor   s cost     1 10 CLEARANCES    The contractor must conduct all of his operations in connection with this contract so  that no part of his equipment  including ladders  may foul an operating or maintenance  track  electrical transmission  or communication lines or damage any others     1 11 WORKMANSHIP    A  The contractor shall supply all necessary tools  equipment  and material required  for the accomplishment of this contract     B  Competent personnel under the supervision and employment of the contractor shall  perform all work  The contractor  and all parties empl
18. ms  etc       G  Standard sheet metal  1900 Style  back boxes shall be permitted for use on non   surface mounted devices for office areas     H  Existing conduits and or suspended ceiling support systems cannot be used to mount  new conduits or device back boxes        l  The distance between connection  junction  boxes for the Intrusion Alarm system  shall not exceed 100 feet     J  All conduit shall be a minimum of 3   4     EMT  with compression fittings  set screw type  connectors are not permitted  and appropriately sized for the cable it will carry and  allow for 25  expansion  Non fire alarm cable shall not be installed in any fire alarm    conduit    K  FMC  Flexible Metal Conduit  conduit shall be permitted to be used to connect all final  devices to a junction box or condelet box    L  Wiring to be mounted vertically on any wall within the building will need to be installed  in EMT conduit    M  Any all penetration into the building shall be properly and professionally sealed to    prevent water weather infiltration into the buildings     N  The Intrusion Alarm system notification circuit shall be a minimum of 16 gauge 2   conductor  the initiating circuit shall be a minimum of 18 gauge 2 pair single jacketed  cable  Outer cable jacket rating shall be a minimum of Riser jacket rating  classification  Outer jacket color shall be Dark Blue or SEPTA approved alternate     O  Conductors and Wiring material and methods shall meet all NEC and local code  requirements    
19. ons including entry exit delay and  subscriber account in formation     d  User Codes   The Control Panel shall accommodate 75 user codes  The  following characteristics shall be assigned to each user code     Authority level  Partitions operated by the user code  Optional opening closing central station reporting    Wayne Electric Shop Intrusion Page 5 of 17    February 2015    e  Peripheral Devices   The Control Panel shall support up to 16 addressable  devices  The devices shall include any combination of keypads  RF receivers   relay modules  notification circuit modules and access control modules   Peripheral devices shall have the following characteristics  Each device shall  be    i    Physically set to an individual address     ii  Enables using the Device Programming Mode     f  Remote Keypads   The Control Panel shall be compatible with remote keypads  and allow the user to   i  Arm and disarm the entire system or one partition in a multiple partition  system   ii    Bypass zones   iii    Display zone descriptors  alarm  trouble  bypass  etc   in the display  window     v  Individually silence notification circuits and or reset panel     g  Notification Output Circuits   The Control Panel shall internally provide two  supervised NAC outputs for operating fire and burglar alarm notification  appliances  It shall also support two additional supervised NAC outputs when  using a supervised NAC module  Each NAC output shall be rated at 10 14VDC   1 7 amp max power limite
20. ost to SEPTA  Each zone shall be required to report to the central  monitoring station independently     The contractor will be responsible for maintenance and response to alarms until the  newly installed Alarm system responsibility is turned over to SEPTA E M  amp C     Acceptance will not take place until the Intrusion Alarm system is completely and  satisfactorily installed  the facility work is completed and documentation as contained in  this specification is provided to the SEPTA Project Manager     The equipment transferred from the Contractor to SEPTA must be free of dust  dirt   metal shavings  etc     When ready for acceptance  the alarm contractor is to provide a separate overview  briefing to SEPTA management  to include but not limited to  User Group  representatives from E M  amp C Contract Services and Facilities  at a mutually agreed  time  This briefing will be followed by a    walk through    of the system to physically view  the system devices and an activation of the Intrusion Alarm     Wayne Electric Shop Intrusion Page 14 of 17    February 2015   At the above overview briefing  the contractor must supply SEPTA the below items and   documentation  All of the items must be formally and professionally presented to   SEPTA  Further  all items requiring signature must contain the printed or typed   signature block of the signatory    1  Provide installing contractor   s written statement stating that the system has been  installed in accordance with approved
21. oyed on the work  shall  perform their work in a good and workmanlike manner  The contractor must furnish  labor  which can work in harmony with all other elements of labor employed or to be  employed by the Authority     C  The contractor must take all steps necessary to minimize interference with the  normal operation of the station     D  The contractor must remove and dispose of all trash from the installation     E  Contractor shall clean up any construction related debris on the job site upon  completion of the individual task that generated the debris     F  Work area must be cleaned of all work debris at the end of each work day     Wayne Electric Shop Intrusion Page 3 of 17    February 2015    1 12 ACCIDENTS OR INCIDENTS    A  Any accidents or incidents occurring to the contractor s employees while  performing work for this contract on SEPTA premises must be immediately  reported to SEPTA s Project Manager or his designee  A follow up written report  must be submitted to the Project Manager or his designee within 24 hours of the  accident or incident     1 13 WARRANTY    A  All major Intrusion Alarm equipment shall be installed  adjusted and serviced by  authorized representatives of the equipment manufacturers     B  The Contractor shall warrant the entire system and each of the individual components  of the system  All system components warranty must be for a minimum of one  1  year   The warranty shall require the Contractor to provide all equipment  material  and
22. reakers  All outputs shall be power limited     2 04  ENVIRONMENTAL CONDITIONS    A  Environmental Conditions   The Burglary Alarm System shall be designed  to meet the following environmental conditions     1     Storage Temperature   The system shall be designed for a storage temperature of  100  C to 700  C     Operating Temperature   The system shall be designed for an operating  temperature of 0  C to 50  C  32  F to 120  F      Humidity   The system shall be designed for normal operation in an 85  relative  humidity environment     Electromagnetic Interference The system shall meet or exceed the requirements of  FCC Part 15  Class B devices  FCC Part 68  IEC EMC directive     2 05  EQUIPMENT    A  The following equipment shall be provided as part of the Burglary Intrusion Alarm  System     1     Horn     Honeywell  Ademco 748LC   Dual Tone Siren with Low Current Draw or  SEPTA approved equal    Strobes     Honeywell  Ademco 112 113 or SEPTA approved equal  Strobe shall  be clear in color    Outdoor Horn Strobe     Weather proof style Honeywell  Ademco  System Sensor   Wheelock or Gentex or SEPTA approved equal    Keypad Annunciators   Ademco Honeywell 6160 or SEPTA approved equal   Door Window Contact     Honeywell Heavy Duty style contacts or SEPTA  approved equal     Wayne Electric Shop Intrusion Page 10 of 17    February 2015    6    Overhead Garage Door Contacts     Sentrol 2300 Series  Wide Gap Style  or  SEPTA approved equal with a stainless steel armored cable   
23. tance process     Contractor shall provide qualified personnel to support the alarm system cut over to the  monitoring service     3 05 CUTTING AND PATCHING    A  Work included  This Section covers general requirements pertaining to cutting  including  excavating   fitting  and patching of the work required to     1     2     Make the installation fit properly in the existing structure  Installing conduits  Uncover work to provide for installing  inspecting  or both     Remove and replace work not conforming to requirements of the Contract  Documents  and    Removed and or replace defective or changed work   Coordinate the Work with other separate contractors     Repair holes and cracks caused by selective Demolition and or removal of  accessories and equipment     Wayne Electric Shop Intrusion Page 15 of 17    m    3 06    3 07    February 2015  Responsibilities  Contractor shall be responsible to perform their own cutting  fitting and  patching work for the components of this project     Request for Approval  Prior to cutting any element  submit written request to the SEPTA  Project Manager for permission to proceed with cutting  The request shall include  but  not limited to  the following     1 A description of the extent of cutting and patching required  the method for  performing the cutting and patching and an explanation for why cutting and patching  is required     2  Description of the anticipated results in terms of changes to existing construction   including rela
24. ted changes to structural elements and functional components as well  as changes in the structure s appearance and other significant visual elements     3  A list of products to be used and firms or entities that will perform work     Areas to be cut and or drilled that are exposed to publicly visible or in occupied spaces  shall not be cut or patched in a manner that would  in the opinion of SEPTA s Project  Manager  negatively affect the aesthetic qualities of the building s structural and  architectural elements or result in permanent  visual evidence of cutting and patching   The responsible Contractor shall remove and replace work cut and patched in a manner  deemed to be visually unsatisfactory by any of the above parties     Cut holes and slots neatly to the size required with minimum disturbance of adjacent  surfaces  Temporarily cover openings when not in use     Restore all patched areas in a manner to eliminate evidence of patching     Do not cut and patch operational elements or safety related components in a manner  that would result in a reduction of their capacity to perform in the manner intended  or  that would result in increased maintenance  or decreased operational life and or  decreased safety     SITE AND EQUIPMENT CLEAN UP    Contractor shall clean up any debris left at the site due to their construction efforts  i e   packing materials from products used  concrete dust from core drilling holes and or  anchors  metal shavings from drilling into metallic
25. tween a central station operator  and the premises     t  Cross Zoning Capability   In order to prevent false alarms  the Control Panel    shall prevent a zone from going into alarm  unless its cross zone is also faulted  within 5 minutes     Wayne Electric Shop Intrusion Page 8 of 17    2 02    February 2015    Exit Error False Alarm Prevention  The Control Panel shall be capable of  differentiating between an actual alarm and a false one caused by leaving an  entry exit door open  The Control Panel shall be capable of     i  Being arming while the faulted entry exit zone s  and or interior zones are  bypassed   ii  Generating an Exit Error report by user and zone     Downloading Features   The Control Panel shall be capable of uploading and  downloading at 300 baud  It shall also be capable of uploading ECP devices   their physical addresses  programmed addresses and firmware revision levels     Enhanced Walk Test Mode   The Control Panel shall provide the installer with  the following features     i  Automatic test of all integrated remote point module  RPM  devices   equipped with an automatic test feature     ii  While automatic test is in progress all zones that remain untested shall be  displayed     iii  An event log shall be capable of logging the results of tested and untested  zones     iv  The ability to report the result of tested and untested zones to the central  station     Built in User s Manual and Descriptor Review   A built in User s Manual shall be  provi
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Solo Windows 8.1  Peavey Axcelerator AX User's Manual    PLAN D`OCCUPATION DES SOLS MODIFICATION N°8  Návod na obsluhu Original brugsanvisning Instruction manual  Titres traités au catalogage sur demande pour la semaine du 29  ニュースリリース - Mad Catz マッドキャッツ    Sarpeco IF - Duo System  MANUAL DE INSTALACIÓN, USO Y    Copyright © All rights reserved. 