        L series 1-1_220VAC_ - sine wave inverter,online UPS
         Contents
1.                                                                        30  6 4  Connection INSpeCtION                                                                                                               33   7  Operation and management                                                                                                              33  7 1  Preparations before turning on the machine                                                                                    33  7 2  The first time turn on the UPS                                                                                                       34  7 3  Test in AC mode operatiOn                                                                                                           34  7 4  Test in battery mode operation                                                                                                 34  7 5  Daily operation management                                                                                                       34   8  Daily maintaining                                                                                                                            35  8 1  Defance maintenance                                                                                                                 35  8 2  Battery maintaining                                                                                                                     35  8 3  The explan
2.                                   8  3 2  4 20KVA UPS  6 20KVA UPS                                                                                                    8  3 3  Front panel operation iNStrUCtION                                                                                                    9   4  Brief introduction of UPS configuration                                                                                                11  4 1  Rectifier                                                                                                                                    11  4 2  INVErtEr                                                                                                                                   11  So aa aaa              12  4 4  SWitCh                                              a 12  4 5  Dispalying and touching screen operation                                                                                       12  4 6  L series 1 1 large screen LCD display and operation                                                                         13  4 7  RS232 intelligent communication                                                                                                  23  4 8  RS485 intelligent communication                                                                                                   24  4 9  Communication of SNMP and distant web                                                                       
3.                          045 Turn off UPS manually   051 User sends distant count down UPS turning off command from the  monitor end   052 User sends distant count down UPS turning on command from the  monitor end   053 Count down time till turning off the UPS   054 Count down time till turning on the UPS   055 User sends distant count down UPS turning on canceling command from   the monitor end   056 Send battery testing command from the display panel   057 Send alarming canceling command from the display panel   058 Send turning on command from the display panel   059 Send turning off command from the display panel   061 Rectifier re works   062 Rectifier stops working   other Unknown error or wrong error record             4 7  RS232 intelligent communication    End definition adopts DB9 standard port    NC                                1  RXD                              2  TXD                              3  NC                                4  Signal GND                    5  NCG                                6  NC                                7  NCG                                8  NC                                9    2 pin  receiving end  receive computer RS 232 communication data in the UPS   3 pin  sending end  send computer RS 232 communication data in the UPS    5 pin  communication    GND       Other pins  no connect     RS 232 communication provides the following functions  Monitor UPS current power supplying status   Monitor UPS current alarming status  
4.                24  4 10  Dry connect state communication                                                                                                25   5  UPS Working principle                                                                                                                      26  5 1  Working principle of complete machine                                                                                          26  5 2  Mains operational mode                                                                                                              28  5 3  Battery inverter operational mode                                                                                                 28  5 4  Bypass operational Mode                                                                                                            28  5 5  Manual maintenance bypass mode                                                                                               28   6  UPS installation                                                                                                                               29  6 1  Disassemble and inspect                                                                                                            29  6 2  UPS positioning                                                                                                                             30  6 3  UPS wires Connection                                          
5.     3  UPS appearance introduaction    3 1  1 3KVA UPS                                                                                        LED display 6 ee 4 45232 port  cooling fan CE RS485 port         LCD display  ee  2  C2 SNMP card     control switch o e      switch mark  g m g g g p power swtich                                        D cooling holes    connections                                                    wheel                                                                               3 2  4 20KVA UPS  6 20KVA UPS          PDF XE  pdfFactory Pro  WHARE eit www  fineprint  cn             RS232 port  Ia  LOGO WORKING LED parallel port RSL85 port    SNMPcard         SWITCH   i Li    z  N                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                   ew   m    fan holes  m  zZ  U y   power switch     ojojojJo  e   e   e     onon d  mi ololoklo tlo Flo Flo  2  hardwire  a   wheel  3 3  Front panel operation instruction  3 3 1  Single phase in and out front panel operation instruction  FERA  a        ou   ERRA SREB   E
6.     lightens when UPS inputs    Wrong phase order    lighten when input AC   s phase order has error    Working status    lightens when controlling circuit of the whole machine works normally    Battery normal    lightens when battery   s voltage works normally    Low voltage    lightens when the voltage of the battery is low    Overloaded input    lightens when the input is overloaded     Nes Ne Nes Nee NE Me SE NE Se Me SE    Screen plus LCD    y Touch screen    you can touch directly on the screen board and enter into the corresponding menu   y LCD    show the status and figures     Detailes please refer to the part of display and communication        _ Rectifier switch    the breaker controls the rectifier   s input  Meanwhile it protect the rectifier  the breaker cuts  when the rectifier is over current    y Bypass switch    the breaker controls the bypass   s input and protect the bypass meanwhile  The breaker  cuts when bypass circuit is over current    y   Battery   s switch    the breaker controls the battery   s input and protects the battery group meanwhile  The  breaker cuts when battery group is over current    y Input switch    the breaker controls the UPS   s AC output and protects the output meanwhile  The breaker  cuts when input over current or short circuit    y Maintain switch    it is used for maintain UPS with uninterruptible power  it will turn off when working  normally  Please refer to correct flow when using this swift  otherwise it will cause the fa
7.    enter into management setting optional interface     see chart 9  In this interface the selected content reverse video  use the up key  f  change the selectable content     use the left key finish the selec  Use the scroll key  j   exit this interface back to the flow interface 4 6 2     1  System management  2  System setting             PDF XE  pdfFactory Pro  WHAREKAI www  fineprint  cn       Chart 9  4 6 11  Management select interface    In the management setting interface select 1  system management  Then the LCD enter into management select    interface  see chart 10  In this interface the selected content reverse video  use the up key  f  change the select    content  use the left key finish the select  use the scroll key     exit back to the previous interface 4 6 10     1  Shut down UPS   2  System information  3  System record   4  LED testing       Chart 10    When UPS in working status  the first option is  1  turn off UPS  When UPS in turn off status the first option is 1   start UPS     4 6 12  Input password interface    In management select interface select 1  turn off UPS and enter into  This operation need input password  So the  LCD enter into the password interface  see chart 11  In this interface the select content reverse video  use left key    remove cursor  use up key  t  increase the value or finish the select  use the scroll key a  back to the    previous interface 4 6 11     Password        Chart 11    When move the cursor to OK  press up key  f
8.    s A  B and G  use communication wires to connect the interfaces of computer s RS485 and  UPS   s RS485  The longest linking distance should be less than 4 000 m  or it can not communicate normally     6 3 6  Connection method of SNMP card    The international standard of producing twisted pair  EIA TIA568A and EIA TIA568B  Both ends of plug should  follow 568 A or 568 B standard     Network cable production      1  Cut  use knife edge scissor of press line pliers to cut network cables with appropriate length      2  Peel  use knife edge of press line pliers to shear cables orderly  then put wire heads on peeling blade  make  wire heads touch baffle  then slightly clench pliers and slowly rotate it  let knife rip off the protecting rubber skin of  twisted pair  peel off the skin  note  strip as long as thumb   s length       Tip    The length between baffle and peeling blade of press line pliers usually is just same length as plug   s  which  can effectively avoiding peeling too long or too short  If peel too long  the network cable will look ugly  meanwhile  it  can not be stuck by plug  the connection point can easily get to loose  if peel too short  because of the existing of  protecting skin  cables become too thick to plug into the bottom of plug  which results in plug can not contact perfectly  with cable cores  Production can not be success as well      3  Sort  after removing outer protecting skin  you can see four pairs of twisted pair   s eight cores  and each pai
9.    the LCD display R mark  it means the system enter into count down turn on status    10  Output switch  display the output switch status  when this mark flicker  it means the output switch cut off    11  Count down time  display the remaining time of count down to turn on off    12  System time  display real system time   13  Current working mode  if this mark displays eco  it means the system working in ECO mode  if display  UPS     it means the system working in UPS mode  if no display then it means the system working in UPS mode                 4 6 3  UPS current operation status interface    UPS current operation status display likes chart 3  In flow chart interface press the the scroll key  j   and enter  into operation status display interface  In this interface can see the UPS current operation status     On Off status abnormal   Phase sequence failure   Input abnormal     Inverter output        Chart 3  4 6 4  UPS input information display interface    When the UPS in operation status press the scroll key on the front panel  on the front panel then enter into  UPS input information display interface  see chart 4  In this interface you can see the UPS current input information           PDF XE  pdfFactory Pro  iF peAS et www  fineprint cn       UPS Input   Voltage  220V  Frequency  50 0Hz       Chart 4    4 6 5  Inverter information display interface    In UPS input information display interface press the scroll key    on the front panel then enter into the inverter 
10.   4    lt  5  0 lt      100  load   characteristics  Recover time  lt 10ms  Overload 125  1 minute  150  1s  Inverter efficiency 295   load 100    Baypass parameters  Type L1K   L2K   L3K   L4K   L6K   L8K   L10K   L15K   L20K   L30K  Phase Single phase  Voltage 220VAC 25  UPS mode   220VAC 10  ECO or UPS mode   50Hz 10   60HZ 10  UPS mode   Frequency  50Hz 5   60Hz 5  ECO orUPS mode   Transfer time  lt 1ms  inverter    bypass               5  Systerm parameters       Type    LIK   L2K   L3K L4K L6K   L8K L10K L15K   L20K   L30K                                  Efficiency     gt 80  100  load        Communication    RS232 RS485   SNMP option           Temperature       0 40  C             PDF SCHEER  pdfFactory Pro  WHAREKAI www  fineprint cn                   Relative                                                                            humidit no 30   90   coagulation   Height Max   lt 1000M a 1  decrease against 100 meters    rise  altitude 4000M Max   Cooling down ae  Compulsive ventilation with temperature control   method  Noise dB 40 50 50 55 55 60  Cabinet colors Grey option other colours   Input place Under back  Easy to  RA   Top left or right side open  maintain  Cabinet size        210x495x500 210x580x540 380x680x900 430x750x1050  WxDxH mm    Weight Kg  38 45 60 105 138 155 185 215 245 318  Input mode With the line connection  Output mode With the line connection       All the above parameters are reference only  any difference please refer to the actual UPS 
11.   Temperature error means temp high       005    Phase order error  Phase order error  wrong input phase order       006    Inverter error       007    System error       008    Bypass output incident  means the UPS switch to bypass output       009    Inverter output incident means the UPS switch to inverter output       010    Rectifier error       011    Maintaining bypass switch is turning on       012    DC fuse is off       013    Rectifier switch is cut down       014    Bypass switch is turning on       015    Output switch is turning off       016    Battery switch is cut down       020    Batter switch is turning on       021    AC returns to normal       022    Battery voltage returns to normal       023    Load returns to normal       024    UPS temperature recover normal       025    UPS phase order returns to normal       026    Maintaining bypass switch is turning off       027    AC insurance returns to normal       028    Rectifier switch turning on       029    Battery switch turning on       030    Output switch turning on       031    Transmission error       032    Transmission returns to normal       041    Turning off automatically  means the machine is automatically shut down  because of low UPS voltage or other error  and switch to bypass output       042    UPS restart       043    UPS enter battery testing status       044          Cancel buzzer alarming manually             PDF XE  pdfFactory Pro  WHARE est www  fineprint cn                        
12.   breaker  Please replace the breaker                                 Alarm 2  input error    When the buzzer alarms 1 second with 3 seconds intermission  please check     1  Input phase voltage is not within 165 275VAC range  2  Input frequency is not within 47 5 52 5Hz range   3  Commutate switch is not turned on    4  Bypass switch is not turned on      Alarm 3  wrong phase order   If buzzer alarms please check the following    Main input power error or commutate input switch is cut down  Input main phase order errors    Bypass input phase order errors  Main power input some of the phase fault    PON  gt       Alarm 4  low battery voltage    If buzzer alarms 1 second with 1 second   s intermission please check     1  Low battery voltage  2  The battery running time is less than set schedule time      Alarm 5  inverter running errors  If buzzer alarms please check   1  The loose connection of the inverter part leads to its abnormal work    2  Breaker is cut off and there is no AC input in the inverter  3  Inverter output is short circuit or output overload          PDF SCHEER  pdfFactory Pro  iF AeA est www  fineprint cn       PDF SCHEER   pdfFactory Pro  iF AeA eet www  fineprint cn    4  Inverter output voltage beyond the prescribed range  5  Transmission errors    a  Connection cable between display panel and main panel leads to abnormal communication   b  Main panel works abnormal and the display panel can not receive the data back from it  Please check whether  the con
13.   finish input password  If the password correctness will turn    off start  meanwhile back to the previous interface 4 6 11  if the password failure  the LCD will not alarm  and also  clear the wrong password and reposition the cursor  UPS will in execution any operation  The nominal password of  the system is  1234           PDF XE  pdfFactory Pro  WHAREKAI www  fineprint cn       4 6 13  System information interface    When manage the select interface choose 2  system information  The LCD will enter system information  see chart    12  In this interface will display the rated information of the system  use the scroll key  j   back to the previous  interface 4 6 12     UPS capacity  OOOKVA  BAT No  00 pcs  BAT capacity  OOOAH       Chart 12  4 6 14  System record interface    In the management select interface choose 3  system record then the LCD will enter into the system record    interface  see chart 13  In this interface will display all the record of the events  Use the up key  f  read the next    record  use the left key read the next nine records  use the scroll key  amp l back to the previous interface 4 6 11     Serier No   001 Code  002  Time  2007 01 01 00 00 00  Description  Battery low voltage       Chart 13    4 6 15  LED testing function    In the management select interface  choose 4  LED testing and enter  Testing the LED and the beeper for 6 mS on  the front panel  during the testing period the LED light and the beeper beep     4 6 16  Setting the select i
14.   freauencv       Abnormal 2  Change or replace the input power             PDF XE  pdfFactory Pro  WHAIA et www  fineprint cn            Input voltage    Abnormal 1  Input voltage within the rated range    Change or replace the input power              Abnormal 1  Checking whether the sampling single connection  reliable  Also checking the insulation  2  Checking the adjusting whether the varisto  excursion  3  Checking whether the connector of insert  components on the circuit reliable       Input current  date    Restart function recover    x Phase sequence not correct    Wrong phase  sequence  1  Checking the O P current  over load and short circuit    Rectifier 2  Turn on the rectifier witch  switch    Turn on    1  Input phase sequence not correct    Input lack phase    Replace phase sequence       Input phase Abnormal    sequence    1  Checking whether the sampling single connection        Abnormal       reliable  Also checking the insulation   ip  Checking the adjusting whether the varisto  excursion   Normal   Checking whether the connector of insert    Restart function recover      Battery low voltage    Input display  date    omponents on the circuit reliable       PDF SCHEER  pdfFactory Pro  iF pA est www  fineprint cn             Battery low voltage    The wires connection in        1  Cut off battery  fasten all fasteners  2  Turn on the battery switch         good condition        Turn on       Abnormal 1  Battery damage or leakage  2  Battery failure or low ca
15.   the rectification will be done automatically  After that low voltage battery indicator  light will extinguish and inverter indicator will lighten  automation will become inverter running    Turn off the battery switch  and battery will be tested by UPS  After that battery will be rectified again  when it  becomes normal  use the concurrent ammeter to test charging current     7 4  Testing in battery mode operation    Turn off the rectifier switch to simulate the inversion of battery and check whether the supply is normal   Close the rectifier switch to change the inverter of city electricity and charge the battery     7 5  Daily operation management  7 5 1  The opening procedures of UPS    Although the battery switch is equipped in UPS  it still must follow the following steps to open UPS     If the commutate switch does not be turned on with 10 seconds after UPS got the power  it will alarm for wrong  phase order  Please press F1 to cancel the alarm and meanwhile operate the UPS starting program as above     7 5 2  No AC input  the battery is in inverter mode    Turn on the battery switch and press the BAT button on the panel  The panel lamp will light and UPS will be in  inverter running mode  Turn on the output switch after normal inverter then it can be add load     7 5 3  Urgency turning off program    This program only suggested to be started when fire  electricity attaching and electricity is arcing     Cut down all the switches           PDF SCHEER  pdfFactory Pro  
16.  Monitor UPS current running parameters     To control the UPS time turning on ff and set the system     RS 232 communication data format    Baud rate                        2400bps  Byte                             8bit  Over NO                          1bit          PDF XE  pdfFactory Pro  WHARE est www  fineprint  cn       Parity check                      NO    Connection of computer RS 232 and UPS RS232    Computer                                                             RXD  2 pin                                                            TXD  3 pin                                                              GND  5 pin                                                              4 8  RS485 intelligent communication  Port definition  from left to right     1 pin  RS 485 communication port A DATA   port   2 pin  RS 485 communication port B DATA   port   3 pin  RS 485 Communication GND   4 pin  RS 485 communication port A DATA   port  5 pin  RS 485 communication port B DATA   port   6 pin  communication GND     UPS   TX  3 pin   RX  2 pin   GND  5 pin     RS 485 communication method provides the same function with RS 232  RS 485 communication data format provides the same function with RS 232    How to connect UPS with RS 485    How to Connect                                                   UPS   DATA   port                                                       A port  1 pin    DATA    port                                                       B port  2 pin    GND po
17.  ag dB a       O  yr O O  ww   Su  w  EAR ITET EWER Fa th 1 TE ih it  O O O            ak  J   er  A  Slol Ajte   UNINTERRUPTIBLE POWER SUPPLY             8     is function key  take the key for 5 seconds as the ups turning off then you can enter the seting status   e the    dy  at the same time is turning off the UPS  UPS will be bypass    is ON key  take it for 2s  UPS will turn on and from bypass to inverter normallyafter 1 minute    is ON key with BAT  pls take the key for 1s when you want to start the ups without the mains    is reset key  take the key for restart the UPS    is up the number key  when the seting status pls use it    is moving the cursor key  when the seting status pls use it   is turning over the screen key  mainly use to turn over the screen for looking the UPS working status     D  D                                                          Pt  Joale    3 3 2  Led display introducations       PDF XE  pdfFactory Pro  WHARE et www  fineprint cn       A     Working status lamp    indicate each part of the circuit working status when it works     Bypass input    lightens when bypass input power   s voltage and frequency are within normal range   Bypass operation    lightens when static switch is bypass working status    Main power input    lightens when main input power   s voltage and frequency are within normal range   Rectifier normal    lightens when rectifier works normally    Inverter normal    lightens when inverter works normally    Input indication
18.  circumstance temperature  change    he working temperature           Normal        Abnormal 1  Checking the heat sink intake  make sure good  entilation conditions  Reduce the load  reduce the contacto  emperature    Change the environment temperature       Inverter  connector         Normal         Restart function recover      Transportation failure       Transportation failure          PDF SCHEER  pdfFactory Pro  iwtFo pA et www  fineprint cn           Abnormal           Communicati 1  Checking the connection wires between display  on wires board and he main board connection      Replacement the connection port        Abnormal 1  Checking whether the connection of the MCU in  good condition    Checking whether the connection of the main  board in good condition    Normal  3  Replacement the connection port         Restart function recover                            9  Packing list  S N Name Quantity Notice  1 UPS 1 pc  2 Manual 1 pc  3 Qualification 1 pc  4 Installation guider 1 pc  5  6                         If can not understand the manual or any more detail please contacted the distributor or our company  We will  zealously provide our service     Notice  Any changing of the manual will not be informed specially           PDF SCHEER  pdfFactory Pro  iF peAS est www  fineprint cn       
19.  display interface see chart 2  In standby interface press the scroll key  j   enter into flow chart  display interface  In this interface will see the UPS working working and operation statues display  The meaning for  each part of the interface as following          Chart 2          PDF SCHEER  pdfFactory Pro  iF peAS eet www  fineprint cn       1  Subordinative unit mark  when the screen displays this mark  it shows that in parallel system this UPS in  subordinative status    2  Thin real line  connect the no working module with thin real line shows this module already stop working    3  Thick real line  connect the working module with thick real line shows this module in working mode    4  Rectifier and input mark  in flow chart interface  it means rectifier module  If this mark flickers  it means input   switch cut off    5  Battery batch and battery switch mark  in flow chart interface it means battery batch  if this mark flicker it means   the battery switch cut off    6  Maintainence bypass switch  display the maintainence bypass switch status  if this mark flicker it means turn on   the manual bypass    7  Bypass switch  display the bypass switch status  if this mark flicker it means bypass switch cut off    8  Inverter and DC fuse mark  in flow chart interface it means inverter module  if at the same time this mark flicker  it   means DC fuse cut off    9  Count down turn on mark  when the LCD display S mark  it means the system enter into turn turn off status  when
20.  information display interface  see chart 5  In this interface you can see the inverter mode current information     INV status   Voltage  220V  Frequency  50 0Hz       Chart 5    4 6 6 UPS output information display interface    In inverter display interface press the scroll key  j   enter into the UPS output information display interface  see    chart 6  In this interface you can see the UPS current output information     UPS Output   Voltage  220V  Frequency  50 0Hz  Current  00 0A       Chart 6    4 6 7  Temperature information display interface    In UPS output information display interface press the scroll key  amp l then enter into the temperature information  display interface  see chart 7  In this interface you can see the UPS current temperature information           PDF 4EM  pdfFactory Pro  WHAREI www  fineprint  cn    Temperature   1  00  C  2  00  C       Chart 7  4 6 8  Battery information display interface    In the temperature information display interface press the scroll key     enter into the battery information display  interface  see chart 8  In this interface you can see the battery batch current information     Battery    Voltage  000V  Current  00 0A  Backup time  00h 00m       Chart 8  4 6 9  Back to standby interface    In battery information display interface press the scroll key ais on the front panel then back to the standby  interface     4 6 10  Management setting optional interface    In the above any interface press the up key    Tl  left key 
21.  the other one connects to the switch or  hub of LAN  local area network      6 4  Connection inspection  After connecting all the wires and cables  check the following items   Whether all of battery cables are connected correctly and in a good contacting status  whether all of input  output     grounding wires have been properly connected to corresponding connation field on equipment  whether UPS s input  voltage  frequency  and phase sequence are consistent with UPS   s bypass voltage  frequency  and phase sequence     7  Operation and management       7 1  Preparations before turning on the machine    Test tool   Millimeter   Ammeter   Computer for communication test          PDF SCHEER  pdfFactory Pro  iF AeA eet www  fineprint cn       Load  actual load   7 2  The first time turn on the UPS    Wiring inspections  Check the input line to make sure all of them meet the requirements     Input supply test   Use millimeter to test input voltage and frequency  to make sure whether they are in the input range   Load test   Check the output load by millimeter to make sure if there is short circuit  And calculate the loads   Battery polarity test    Check whether the polar is right or not by millimeter and the voltage of battery belongs to the input range of UPS   7 3  Testing in AC mode operation  Procedures of turning on the machine   Turn off the bypass switch and output switch and check whether the machine bypass is in the normal condition    Turn off the rectification switch
22.  twisted pair  into plug  each wire can well contact plug   s pin  which avoids bad connection  If the former skin is peeled too long   then it can be cut shorter at this stage  Except outer insulation skin  the remained part is about 14 mm  which length  can rightly insert each thin wire into corresponding trucking  If this part is too long  for one hand it can increase  mutual crosstalk  because allied wires ate no longer twist together  for the other hand  owing to the plug can not pin  the sheathes  cables derail from plug  which can cause bad connection or even Interruption      5  Insert  use one hand   s thumb and middle finger to nip plug  the plastic shrapnel of plug faces downside  its pin  towards the opposite direction of yourself  using your forefinger to hold it  Other hand nips the rubber skin which is  outside of twisted pair  slowly inserts eight wires along RJ 45   s eight trunkings with proper force until reaching the top  of trucking      6  Press  when all wires are in place  and all wires    sequence is correct after thoroughly checking over through  connectors  then you can use press line pliers to make RJ 45 plug  Push one head of RJ 45  from the side without  teeth  into the trough of press line pliers  then clench pliers at full tilt  if your strength is not enough  you can use both  hands to press   press pins which are prominent outside into plug     Network cable connection     One end of a well pressed network cable connects to UPS   s SNMP card 
23. L series 1 1 online UPS  1KVA 20KVA        User   s Manual                 SQ    PDF 3c  pdfFactory Pro  iA WAS Gus www  fineprint cn          Table of contents    1  Importance indication                                                                                                                         3  1 1  Applied condition                                                                                                                        3  1 2  Working entironment                                                                                                                    3  1 3  Safety MotG  te ere eE ee eash ie e eae e e e aa ee aei e e aea 3   2  Product information                                                                                                                           4  2 1  How to name the UPS                                                                                                                  4  2 2  Main featUreS                                                                                                                               5  2 3  Technology parameterS                                                                                                                6   3  UPS appearance introduCtiON                                                                                                             8  3 1  1 3KVA UPS                                                                                           
24. ation of alarm                                                                                                             35   9  Packing liSt                                                                                                                                     42          PDF XE  pdfFactory Pro  WHARE et www  fineprint cn       1  Importance indication    This manual contains the guidance of UPS and accumulator when installation and application  also includes the  guidance of problem setting and maintenance     Please read this user manual carefully before using or installing the machine   This manual must be read to and conserved by a professional person    This manual does not introduce the specified technologies    This manual applies to the L series 1 1 online UPS     Wi ker a ui    This manual provides the reference when using and guidance when alarming and working     1 1  Applied condition    This UPS provides AC power supply  which is the basic power of your equipment  Please carefully check whether  the input and output pressure and frequency can meet the using requirements     UPS input AC capacitor must be as requested  Otherwise the UPS will work improperly or even occur security  accident  when the UPS input is generator  generator capacity should be 3 multiple more than UPS      1 2  Working environment    The working environment and maintain methods also influent the using age and failure rate of the UPS  Therefore   please avoid the following wo
25. bring in the sixth generation low exhaust and  big power IGBT and static switch as power components  L series 1 1 UPSs combine world   s newest control spare  parts and the most advanced software  and apply broadly to industrials such as building lighting  road traffic lighting   electricity  industry and other industrial and mining enterprises fields     2 1  How to name the UPS        Single phase in and out  Rating capacity  KVA   Low frequency    PDF XE  pdfFactory Pro  WHAIA et www  fineprint cn                UNINTERRUPTIBLE POWER SUPPLY    Name  UPS   Type  L  K   Input voltage  220VAC 20   50Hz  Output voltage  220VAC 2    50Hz  Battery voltage  192VDC    Production date   Production number  PCUPSTT400K060508001    ANT TA    PC1215400K9H060508       Name      UPS    Type      it means the UPS s rating capacity  please refer to the product naming regulation   Input pressure      rating input pressure and frequency   Output pressure      rating output pressure and frequency   Battery pressure      rating battery pressure   Production date      leave factory date   Production number      production serial number   Code number      CODE 39 standard    2 2  Main features    l Online working pattern and prompt static switch    Intelligent digital control technology   It adopts 3 high speed microprocessor controlling system and operation parameters which make its operation  amp   management more perfect and its self diagnosis and self detect function stronger  You can also f
26. ch signal is the COM port of relay  22 pin  Maintain switch signal is the NC port of relay  23 pin  Fuse signal is the COM port of relay   24 pin  Fuse signal is the NC port of relay    Dry connect state communication function    Rectifier status   signal relay turns on at the rectifier working normally  Bypass status   signal relay turns on at the bypass working normally  Inverter status   signal relay turns on at the inverter working normally   DC input status   signal relay turns on at the DC inverter working normally  BAT voltage low status   signal relay turns on at the BAT voltage low          PDF SCHEER  pdfFactory Pro  iF peAS est www  fineprint cn       System fault status   signal relay turns on at the system fault   Rectifier switch status   signal relay turns on when the rectifier switch is turned on  Bypass switch status   signal relay turns on when the bypass switch is turned on  Output switch status   signal relay turns on when the output switch is turned on   DC input switch status   signal relay turns on when the DC input switch is turned on  Maintain switch status   signal relay turns on when the maintain switch is turned on  Fuse status   signal relay turns on when the fuse is broken    5  UPS working principle    5 1  Working principle of complete machine    Diagram of complete machine working principle    Manual maintenance bypass         attery input        Static switch            __  Main power in Rectifier Inverter                   nmunication un Dis
27. consisted of the power slot  plastic crust   the cathode plate  the negative electrode  separator   electrolyte  inter unit bridge  terminations  safety valves and other components  It is a power and chemical energy  conversion devices  The working principle is  when AC is normal the charger will charge and the battery will convert  the power to chemical energy which will be stored in the battery  when the AC works abnormally the battery will  convert the chemical energy to power to UPS     4 4  Switch  Static bypass switch  Bypass switch         Output switch    Inverter e    gt     Static inverter switch    The UPS pattern is dual mode transformation  When the inverter does not start it is bypass mode  after turning on  the inverter it will high speedily switch from static bypass switch to static inverter output switch  As static switch is  electronic switch so there is no mechanical switching time     4 5  Displaying and touching screen operation  4 5 1  Touching screen information    Touch screen LCD monitors is our company   s latest invention of the UPS modules  using today s most popular and  intuitive graphical operation interface  Comparing with the traditional button LCD display modules  the touch screen  display module shows a more rich content which avoids frequent page turning  At the same time because the user  can get corresponding information by directly press the button on the display screen  It is easy to use easy to get   Meanwhile touch screen display modu
28. e 220VAC 25  UPS mode   220VAC 10  ECO or UPS mode        50Hz 10   60Hz 10  UPS mode                       ERUR 50Hz 5   60Hz 5  ECO or UPS mode   THDi  lt 5   Soft start 0 100  5s  Output voltage 55 VDC 220VDC  Set the DC  voltage by 42 60VDC 200 232VDC change them by the professional engineer with the soft   soft              2  Battery and charge parameters       Type LIK   L2K   L3K   L4K   L6K   L8K   L10K   L15K   L20K L30K       Max current  discharge A     24 48 71 24 36 48 60 90 120 179                                                 PDF XE  pdfFactory Pro  WHAREKAI www  fineprint cn             Battery type Maintenance free lead acid battery  Battery numbers 4pcs 16pcs  DC voltage 48VDC 192VDC          Float voltage    55VDC 220VDC once of three months charge  charge votage 56 8 232VDC              Charge power    Rated powerX20   automatically change follow the batteries         3  Inverter parameters     4                                                                                                  Type LiK   L2K   L3K   L4K   L6K   L8K   L10K   L15K   L20K   L30K  Rated power  Capacity x0 8 KW  Cos 0 8 ay ie  Phase Single phase L N G   Voltage 220 1  state load  220 5  fluctuate load    Frequency 50Hz 0 5   60Hz 0 5  with battery   Output frequenc  Pare T y  lt  0 5  no in phase   stability  Input frequency 50Hz 5   Crest factor 3  1  Wave Pure sine wave  Output waveform      pe i X Pure sine wave  linear load lt 3   non linear load lt 5   distortion  Dynamic
29. efore installing UPS  turn off all switches  According to left part of the above plan  A  B  C  N connect three phase   separately to the fire wire and middle wire of main power input  A  B  C  N on bypass connect three phase  separately  to the fire wire and middle wire of bypass input when one power inputs  link the main power input and bypass input  together   According to right part of the above plan  A  B  C  N connect to three phase  separately to the fire wire and  middle wire of AC output   E is connected to the safe protecting ground wire       are connected to the anode and  cathode of battery     6 3 3  Battery connection    1  Before connecting battery  please check manufacturers of each battery  specifications and models  and  terminal voltage to make sure whether they are in consistent  because different manufacturers    battery  internal resistances are different  When battery pack run in series  because of uneven voltage  the whole  battery pack can be damaged  meanwhile  the old and new batteries from same manufacturers cannot be  mixed as well     2  The input battery voltage of UPS is voltage of battery pack in series  the labeled voltage is a standard value   and it is the summation of all batteries    standard values in the battery pack running in series  For example   the standard value of a single 100AH 12VDC is 12VDC rather than measured value  The input voltage of  L10K1 1 battery is 384VDC  namely  12VDCx32   384VDC    3  Series and parallel connecti
30. erter is closed  or fell  MCU controlled high speed static switch will automatically switch into bypass electricity  without interrupt  loaded power supply    Bypass and main power can be a same group of power supply  it also can be a different AC  altering current        Display communication unit    Display unit is to show operational status and data of entire machine through LCD and LED  and through RS232   RS485  dry contact signal  SNMP card  etc   realize long distance monitor with background software     L series 1 1 adopts large screen LCD  320x240  and touch screen design  graphical manipulative interface   tabular data display  With 256 long records of incident  L series 1 1 can provide great help to your power supply  status   s analysis and management     POCASA styled UPS highly integrates digital technology  improves MTBF and reliability  its independent main control  board controls the whole system   s work  Meanwhile  it is controlled by a high speed microprocessor  which ensures  the stability of equipment and the reliability of operation     witch sampling    use sampling       Besides the above chart  other components of UPS include  inverter transformer  input inductance  IGBT  SCR   switches  etc        PDF SCeRERY  pdfFactory Pro  WAIWAI www  fineprint co       5 2  Mains operational mode      Manual maintenance bypass        Auto bypass                      nmunication t              The input AC will be transformed into DC through rectification and fil
31. es 1 1 UPSs can automatically adjust battery charge parameters according the user   s battery configuration   and can achieve battery float and boost conversion  temperature compensation and battery charge amp  discharge  management according to the power supply environment  It prolongs the battery   s lifetime and reduces the operator   s  burden     Optional battery detecting module   It is able to test the single parameter  and display on the LCD  If battery failure it will alarm to runner     Intelligent detection function   The system microprocessor will continuously detect on line all power   s supply working status  breaker status  and  all circuits working status  Any failure occurs  the detecting system will immediately alarm to the runner     Intelligent communication   RS232 and RS485 interface realizes multi communication and long distance monitor    The choice SNMP card 100  carries out long distance supervision and network management  the optional dry  contact connection  adopting no have no the source  efficiently carries out the supervision and control of the UPS  status    l Characteristic setting  As per different power supply  the UPS can adjust the input parameters     2 3  Technology parameters     1  Rectifier parameters                                                 Type L1K L2K L3K L4K L6K L8K L10K L15K L20K L30K  Range KVA  1 2 3 4 6 8 10 15 20 30  Input    6 12 18 24 35 45 57 86 114 172  capacity A   Working Pure sine wave  Phase 1 phase N G  Voltag
32. ill operate in constant current  mode  At this time  MCU will calculate and control the feedback of charge current from battery and the information of  battery capacity set by user  when battery is charged into floating voltage  then rectifier will change into constant       PDF SCHEER  pdfFactory Pro  iF peAs est www  fineprint cn       voltage charging mode  Meanwhile  basing on the temperature of battery  MCU will charge battery in a temperature  compensation style  maintain and manage battery in a regular time on the basis of its using situation  when battery  hasn   t been charged or discharged for a very long time  MCU will automatically transfer into an equalized charging  mode in order to activate the activity of battery   thus it will extend battery   s lifetime and reduce user   s burden of  management       IGBT inverter unit    When DC bus is normal  if MCU issues inverter control signal  inverter circuit will drive IGBT Inverter Bridge by  SPWM driving signal  through inverter   s isolation  voltage transformation and wave filtration  produce out pure sine  AC  altering current   Through adjusting driving signal   s pulse width  Inverter can raise output voltage from OV to  rated degree  and control stability of output through its feedback  Meanwhile  check voltage and current of output in  order to protect inverter       Automatic and manual bypass unit   Bypass circuit can directly convert input electricity into output electricity through switch circuit  If inv
33. ilure of UPS or  output cut     The process of cut off the maintainence switch  turn on the bypass switch  meanwhile turn off the inverter by  manual  then turn off the output switch  the cut off the maintainence switch  and then turn off the rectifier switch and    battery switch    D  Connection end    cables connect the input  output and battery    E  Dry connection point connections   F  RSS232 communication meet end    connect the RS232 meet end in the computer  It will monitor the UPS in  background through monitor software    G  RS485 communication meet end    connect the RS485 meet end in the computer  It will monitor the UPS in  background through monitor software    H  SNMP card    connect the Intel website and operate the web long distance monitor       Boarding    open it and screw and connect lines   J  Idler wheel    to move the UPS when installing  Should be fixed after installation           PDF SCHEER  pdfFactory Pro  WHAREKAI www  fineprint cn       4  Brief introduction of UPS configuration    4 1  Rectifier    Convert the 1 phase   s input AC electricity into stable DC through the rectifier and charge the battery meanwhile  Its    consisted parts are as following   6 or 12 pulse rectifier  Rectifier circuit  Batteries    MCU  Input voltage and frequency Battery voltage and charging circuit    Inverter                   surew   seyd   YOUMS 191 1 99H  1       OJuowJeH    JOU SNQ OG       dall SN       inspection inspecbtion    Input voltage frequency defaul
34. is output overloaded or short circuit     PDF SCHEER  pdfFactory Pro  WHAIA www  fineprint cn                            Switch the LCD screen to output menu to examine the output circuit  if displayed data are within prescribed range  please re start battery switch  The alarm will be cleaned automatically  The LCD displays and if change   to   the UPS gets right  Check the LCD battery displaying column for the battery voltage and charging circuit   They should be accord with battery capacity   s setting                                                  4  Output switch is turned off  the LCD displays and if changed to please check whether the output   s  switch is off automatically  If switch off please check whether there is output overloaded or short circuit  Carefully  check the load and after confirm it is normal please re turn off the output switch  Switch the LCD screen to output  menu to examine the output circuit  if displayed data are within prescribed range please re start rectifier switch  The  alarm will be cleaned automatically  The LCD displays and if change to   the UPS gets right                                                           5  Breaker switch is turned off  the LCD displays and if changed to please check whether the  commutate switch is normal  If it is normal please press F1  After cleaning the alarm please switch to inverter column  and press the F2 on the panel to check whether inverter works normal  If it is also normal it is the problem of the
35. it FA peas est www  fineprint cn       8  Daily maintaining    8 1  Defence and maintenance  sasamane the preventing maintaining will protect the UPS liability and long term performance       Regularly check whether any of the UPS cables insulation parts is aging or broken  If yes it should be  maintained immediately to avoid any safety accident      UPS  Check whether the intakes are jam  There should be enough heat sink room  otherwise the UPS lifetime  will be shorten even the UPS will be damaged    l Use the dry dishcloth  do not use wet dishcloth or liquid cleaner  to clean the UPS external dust  Should be   processed without wires nearby to avoid electrical shock    Check whether all the lamps work normally  The lamps status should be accordant with LCD displaying status    Check whether LCD displays normally  enquiry UPS incidents records and analysis the power supply status    AC work status testing   Battery inverter running testing   Battery charging testing   Check whether all the fasteners are fixed and whether the wires are over hot with the power cut off     8 2  Battery maintaining             good maintaining towards the battery could prevent any loss when electricity is cut down accidentally or  battery is low       Open the battery cabinet to check whether the battery liquid is leaked and whether the port connection is  loose      Use the millimeter to test whether each battery voltage is accordant with each other  If any battery voltage is  abnormal  it sho
36. l    onnection reliable  Cut off   Checking the O P current  overload and short circuit  Rectifier   Checking charge voltage and current  switch   Testing whether contact single normal                Turn on    1  Checking whether the bypass switch damage  amp  the        onnect reliable    Testing output current  overload and short circuit    Testing whether the contact normal    Rectifier  switch             Cut off         Turn on  1  Checking whether the output switch damage  amp  the  connect reliable   2  Testing output current  overload and short circuit   3  Testing whether the contact normal        Rectifier  switch        Cut off       1  Checking whether the battery switch damage  amp  the  onnect reliable    Checking the output current  overload and short         Rectifier as  switch ircuit    Checking whether the battery normal   4  Checking whether the contact normal    Cut off            Turn on    1  Checking whether the inverter damage  amp  the  Rectifier onnect reliable  switch Cut off   Checking the output current  overload and short            ircuit    Checking whether the battery normal    4  Checking whether the contact normal    Turn on the switch     restart the UPS         Input abnormal    Input abnormal        1  Checking whether the input wires reliable and  reasonable  Abnormal 2  Checking whether the input phase and the phase        Input phase  sequence           sequence correct    Turn on    1  Input frequency within the rated range    Input
37. le comes with real time clock and memory and can be recorded 256 incidents  and other information  which is more humanize     4 5 2  Operation and introducation    Stand by screen shown in chart 1  UPS will start up in the show this standby screen  When the touch screen  interval of about four minutes not to touch  shows CPU will automatically cut off power       touch screen backlight  can be extended so the backlight life  and return to the standby interface  if UPS is in the police state  the touch  screen will be Priority information shows that the police box  police information to repeal or abolish manual alarm will  not be cut off before the show CPU touch screen backlight back to standby power supply interface         PDF cer  pdfFactory Pro  ihe AS Guz www  fineprint cn       4 6  L series 1 1 large screen LCD display and opteration  4 6 1 Standby interface    Standby interface see chart one  When turn on the UPS it will display the standby interface  When the LCD around  1 minute no one operation  the display CPU will automatically cut off the display back light    so as to enlarge the  lifetime of back light  meanwhile back to the standby interface  if the UPS in alarm statuts  the display will prior to    display the alarm information  before the alarm information withdraw or manual withdraw the alarm the display CPU  will not cut off the LCD back light and back to the standby interface      Green  Power    Chart 1  4 6 2  Flow chart display interface    Flow chart
38. led operations process reference to 4 6 12  After input correct password the system will clean all the records of  the events  see chart 16  And the record is beyond retrieve  so the user should be more careful  When finish the  delete  the LCD will automatically back to the management setting interface 4 6 16           PDF XE  pdfFactory Pro  wWHWeA Git www  fineprint  cn       Cleaning out the record     050        Chart 16  4 6 20  The interface of language setting    In the setting select interface choose 4  system language  The LCD enters into language select interface  see chart  17  In this interface the select content reverse video  Use the up key  f  change the select content  use the left key    finish the select  use the scroll key  j   back to the previous interface 4 6 16     1  Chinese  2  English       Chart 17  4 6 21  The interface of BAT code setting    When UPS in bypass mode press after 5 ms will enter into battery setting status  once the UPS enter into battery  setting status  the LCD will automatically skip to this interface  see chart 18  In this interface the selected content    reverse video  Use the let kept removes the cursor  Use the up key  t  increase the value or finish the select        Chart 18    When the cursor on OK  press the up key  f  finish input the password  If the password correct  the LCD will    automatically ship to the next previous 4 6 22  If the password is wrong  the LCD not displays  but cleans all the input  password and re
39. maintain sufficient time  Replacement the battery must be operated by authorized    technologists     1 3 8  If no use it long time  UPS must be stored in dry environment  the host  without batteries  the storage  temperature range   40    C  70    C     1 3 9  In term of no use the UPS for long time  it is advised to charge it by AV for more than 12 hours every 3 months   To avoid any battery damage for long time no using     1 3 10  Please do not open the battery cabinet in case that the electrolyte injury the skin and eye  If incaution the  body contact the electrolyte  please wash it with plenty of water and then go to the hospital     1 3 11  Please do not open the cabinet by yourself because there are many high voltage accumulator spare parts   Otherwise any accident arisen should at your peril     1 3 12  Please do not disassembly any connection cable by yourself without permission     1 3 13  Because this UPS is very big and heavy  please do not move and shake it violently  Also good ventilation is  necessary     1 3 14  Do not exhaust the dust when it is electrophorus  Do not use wet washrag to clean the dirt     1 3 15  The battery must be replaced by professional technologist  Replaced battery should be send to special  recycling agencies  Battery belongs to toxic waste     2  Products information    L series 1 1 UPSs are with a power range from 1KVA to 20KVA  L series 1 1 UPSs adopt high speed MCU and  CPLD programmed and controlled by software  L series 1 1 UPSs 
40. nection wires of the main panel is loose or the MCU of mail panel connect bad       Alarm 6  UPS overload   Buzzer alarms 3 seconds with 1 second   s intermission  and the overload lamp on the panel is lighted  It means the  load power is bigger than rating output power  that is  the percentage value is bigger than 100   When overload  peak value is too big  the UPS alarms  When UPS alarms  it need to lessen the load capacity  Otherwise the UPS will  automatically switch to bypass power supplying  time span is calculated accord to overload value   s inverse ratio       Alarm 7  temperature error  When buzzer alarms please check the following   1  Cabinet airway is jam and can not  2  The installation environment   s temperature is too high and beyond the machines  It protects itself   3  Heat sink fan does not work  which leads to too hot power part     Alarm 8  system error  When buzzer alarms please check the following   1  Loose main board connection cable leads to abnormal working  2  Main board setting error leads to wrong MCU receiving data   3  Low battery voltage  4  Power board abnormality leads to controlling circuit abnormal     Alarm 9  commutate error  Bypass voltage error or bypass fuse SCR error  alarming when   1  Bypass input voltage error  2  Bypass switch input switch break up    3  Bypass SCR fuse break up or be burned because of short circuit      On off status abnormal    On off status abnormal    1  Checking whether the rectifier switch damage  amp  the
41. nterface    In the management setting interface choose 2 system setting  The LCD enters into setting interface  see chart 14     In this interface the selected content reverse video  use the up key T  change the optional content  use the left key    finish the select  use the scroll key  j   back to the previous interface 4 6 10           PDF SCHEER  pdfFactory Pro  WHAREKAI www  fineprint cn       1  Time setting  2  Change password  3  Clean record  4  System language       Chart 14    4 6 17 Clock setting interface    In the setting interface  choose 1 time setting  The LCD enters into clock setting  see chart 15  use the up key T     change the select content  use the left key     Finish select  use the scroll key     Back to the previous interface 4 6 16           Chart 15    Use the cursor to OK     Press the up key T  finish the clock setting  input the correct time format  the LCD will update the time  also back    to the previous interface 4 6 16   if the time format not correct  the LCD will not display but clean all the input numbers  and the cursor will reposition  LCD is inexecution any operation     4 6 18  Change password interface    In the setting select interface 2  change password  The LCD enter into input password interface  the LCD enter into  input password interface  The detailed operations see 4 6 12     4 6 19  Leaning record interface    In the setting select interface choose 3 cleaning record  The LCD enters into input password interface  The  detai
42. on of battery    When the capacity of a single battery pack meet required backup time  then all the batteries should be  connected in series  or couples of series connected batteries should be connected in parallel  the bus  voltage of battery must be the same when connecting in parallel  capacity is equivalent to the summation of  parallel battery pack        When connecting in series  the first battery   s anode is connected to the second battery   s cathode  the second  battery   s anode is connected to the second battery   s cathode  and so is the other battery   s connection     When connecting in parallel  the battery pack   s anodes are connected together  the battery pack   s cathodes are  connected together           PDF XE  pdfFactory Pro  iF pA est www  fineprint cn       y Open the chassis of battery box connect according the above methods    y Install battery on the appropriate position  connect battery wire rightly according to the above connecting  methods    y Connect the cable of battery to UPS   s battery terminal board     6 3 4  RS232 cable connections    Connect one end of DB9 signal cable which is distributed from UPS to the serial port of computer   s DB9  connect  the other end to the interface of UPS   s RS232  If the distance is too far to connect  then you can increase the  standard length of communication wire of D89  however  it should not exceeded 30 meters  or it can not  communicate normally     6 3 5  RS485 cable connection    According to UPS
43. pacity  3  Replacement battery        Normal       Aangrma 1  Frequently AC failure  battery not completely charge      Battery capacity not setting right  charge current not  right    Charger failure  battery not charge       Normal    Restart function recover      Inverter failure    Inverter failure    1  Checking the output current  overload and short  Output load ircuit      Turn on the rectifier              Turn on         Abnormal       1  Cut whether all the power connection reliable  also        Connection  wires         Fasten all fasteners    Connection the power        Abnormal       1  Checking whether the sampling single connection  reliable  Also checking the insulation   Checking the adjusting whether the varistor  excursion   Checking whether the connector of insert  omponents on the circuit reliable    Inverter display  date         Restart function recover             PDF SCHEER  pdfFactory Pro  iF peAs est www  fineprint cn         Output overload    Output overload    1  Checking output current or short circuit  Output load Abnormal Ing Outpu  2  Reduce the output load    Normal                Abnormal       1  Cut whether all the power connection reliable  also  hecking the insulation    Fasten all fasteners    Connection the power    Output  displav date            Normal    Restart function recover    x Temperature    Temperature failure            Abnormal       Environment 1  Checking the hot fountain  far away hot fountain  temperature   Reduce the
44. play unit      Working principle of complete machine    MCU control center    UPS is multi lay protected alternating current supply equipment  When the main power is normal  firstly  to rectify  the main current and transfer it into pure direct current and filter the disturbance in main power  then charge up the  accumulator and output the main power  When the main power is abnormal  to invert the direct current stocked in  accumulator into alternating current and output it to ensure the high quality power supply of user load  The Manual  Maintenance Bypass ensures the maintenance  examination and repair of UPS on the condition of no power cut       MCU control center    MCU high speed operates such data as input  output  battery and environment  then control the running and  protection of rectifier  inverter and static switch to respond the external operation instruction       Rectify and charge unit    Main power input examines the circuit and send the voltage  frequency and phase of main power input to MCU for  operating  When the voltage  frequency and phase of main power input are within the normal range  MCU delivers  the rectified control signal  rectified voltage slowly raised to rated voltage from OV so as to minus the strike on the  input surge current     As battery pack and DC direct current  bus is operating in parallel  rectifier is charging the battery at the same time   therefore  when battery   s voltage is lower than floating battery   s voltage  rectifier w
45. position the cursor  LCD is inexact any operation  The nominal password is  6666           PDF XE  pdfFactory Pro  iH hea  www  fineprint  cn       4 6 22  The interface of BAT capacity setting    The battery capacity setting interface  see chart 19  In this interface the select content reverse video  use the left key  move the cursor  use the up key finish the select     BAT capacity        Chart 19    The user move the cursor to OK  press the up key  f  finish input the battery capacity  LCD will skip to the next  interface 4 6 23     4 6 23  The interface of working mode setting    Working mode setting interface  see chart 20  In this interface the selected content reverse video  use the up key   f  to move the cursor  use the left key to finish the select   Working mode    1  UPS  2  ECO    3  UPS       Chart 20    When the user move the cursor to the needed option  press the left key to make sure the input setting  working mode     4 6 24  The interface of alarm  No matter what interface  once the UPS alarm  the LCD will prior to display alarm content  unless alarm withdraw    or the user eliminate the beeper  The alar m interface display  see chart 21  Use the scroll key  j   to eliminate UPS  alarm        PDF iE  pdfFactory Pro  WHAREI www  fineprint  co       A    BAT voltage is low  OK       Chart 21       Code    Detail incident description       000    Blank  no record       001    Mains error       002    Battery voltage Low       003    UPS overloaded       004  
46. r   s  color is different  Each pair of two allied core wires consists by one core wire stained with a corresponding color and  one core wire stained with white and little corresponding color  The colors of four panchromatic core wires are  brown   orange  green and blue  Each pair is entangled with each other  When produce network cable  these four pairs of  eight thin cores should be disassembled  tidied up  straightened and sorted in sequence according to the following  wire order regulation     Put the side with plastic spring of plug down  up the side with pin  make the end with pin towards to the opposite    direction of yourself  the end with square hole towards to yourself  simultaneously  the far left is the first wire  the far  right is the eighth wire  followed by the remaining order      Standard  1 2 3 4 5 6 7 8             PDF XE  pdfFactory Pro  WHAREKAI www  fineprint cn       White White White  T568A Green White orange Blue Orange Brown  green blue brown       White White White  T568B Orange White green Blue Green Brown             orange blue brown  Same alignment Same alignment  Alignment   Same alignment Same alignment Same alignment  with 6 with 3    T568A standard and T568B standard wire order table                             4  Cut  straighten wires as right as possible  do not wrap   press to flat  do not overlap   tighten and tidy up  lean  against each other in one direction   and then use press line pliers to cut flush  In this way  after inserting
47. re and high temperature Avoid rot gas                                                 Level off Do not place on unsmooth ground Do not place on oblique ground    6 2 2  Installation location    Distance of machine back from wall or any object should be at least 800 mm   At the top of UPS should not be placed any object   The front  right and left sides of Equipment should be prepared enough space for maintenance operation  Equipment battery should be installed in the right hand side of machine  and reserve sufficient space for battery  overhauling    MGs K  Ns Ee    6 3  UPS wires connection    6 3 1  Single phase in and out UPS series 1 30KVA recommended cable specifications   unit  mm                                          Input eee Battery  Capacity output   L N E L N      L1K 1 5 1 5 1 1 5   1 5 8 8  L2K 4 4 2 5 4 4 16 16  L3K 6 6 4 6 6 25 25  L4K 6 6 4 6 6 8 8  L6K 10 10 6 10   10 10 10  L8K 12 12 8 12   12 16 16  L10K 16 16 10 16   16 20 20  L15K 25 25 16 25   25 30 30  L20K 35 35 16 35   35 35 35  L30K 50 50 16 50   50 50 50                                  6 3 2  Single phase in and out UPS series UPS cable connect          PDF SCHEER  pdfFactory Pro  iF peAs est www  fineprint cn                                                                                                                                                                                                                                4  t t    E L N L N L N     E  g Input Bypass Output Battery g    B
48. rking environment in long term     Q Places over demand of specifications  temperature 0  C  40  C  relative humidity 30  95     Q Places with bare sunshine    Q Places near by the heat sources  Over heat will speed up the external battery self discharge   O Places liable to shaking and shoving    O Places have powder  corrosive substances and combustible gas        1 3  Safety notice    1 3 1  Generally the UPS is in connection with batteries  So that there might still be voltage in the output end even  without AC input     1 3 2  When UPS need to be moved or re wiring  you must ensure that all UPS stop working  electricity input and  batteries input is off  Otherwise  there may still be risk of electric shock in the output end     1 3 3  To ensure the person   s safety  this series UPS must be of good grounding protection and of reliable grounding  before the using     1 3 4  Please keep the air intake and exhaust open  Poor ventilation will increase the internal temperature of the UPS  and therefore short the lifetime of UPS spare parts     1 3 5  Liquid and other objects should not be leaked into the inside UPS inside box           PDF SCHEER  pdfFactory Pro  WHAREKAI www  fineprint cn       1 3 6  In case of fire broken out around  please use dry powder fire extinguisher  Liquid fire extinguisher will be  danger of electric shock     1 3 7  The life time of product will decrease by the increasing of temperature  Regular replacement could guarantee  UPS work normally and 
49. rt                                                          Communication source  3 pin     How to connect UPS with UPS RS485    How to connect                                                    UPS   DATA  port                                                         A port  1 pin    DATA  port                                                          B port  2 pin    GND por t                                                             Communication source  3 pin     4 9  Communication of SNMP and distant web  Port definition    T568A standard and T568B standard    y  1568A standard description order from left to right is  1 white  amp  green  2 green  3 white amp orange  4 blue     5 white amp blue  6 orange  7 white amp brown  8 brown        1568B standard description order from left to right is  1 white and brown  2 orange  3 white amp green  4 blue     5 white amp blue  6 green  7 white amp brown  8 brown    SNMP card has the following function          PDF SCHEER  pdfFactory Pro  WHAREKAI www  fineprint cn       Provide SNMP MIB to monitor the UPS status    Automatically detect and transform the 10 100M fast ETHERNET SPEED   Set the functions through internet  web browser or NMS   Support TCP IP  UDP  SNMP  TELNET  SNTP  PPP  HTTP  SMTP agreements    Provide facility installation and updating tools which applied to MS windows  No need the time costing   RS232 traditional way to set    Send SNMP TRAP  EMAIL and pager to inform the operator when battery errors    Can be se
50. t  phase Rectifier controlling    Charging voltage and circuit controlling  BUS  protection       As the above chart  controlled by input through rectifier switch  the main power was rectified to DC firstly by  harmonic filter and secondly the 6 or 12 pulse rectifier  At last it was rectified to stable DC bus by harmonic again   Though measuring the input voltage and frequency and DC bus and controlling the rectifier  the commutating control  circuit input stable DC to inverter and battery group  Meanwhile it starts protection when I P wrong phase  be lack  phase and over limited     4 2  Inverter    Filter IGBT    Transformer Output filter    DC input C7   m  m  m    Load                                     Sampling         Reactive circuit       Sampling Sampling          CPU       Reactive circuit    Be consist of sampling circuit  single chip controlling circuit  IGB driving circuit  IGBT module  inverter isolating  transformer  filter inductance and protecting circuit  Microprocessor firstly produce the SPWM signal through  computing the sampling signals  and meanwhile drive the IGBT module bas AC and change it into high frequency  SPWM waves  Secondly it output pure sine AC through inverter isolating transformer  inverter filter  At the same time  it adjust the output voltage and waves    shape via the feedback of sampling signals such as voltage  current and  temperature     4 3  Battery          PDF XE  pdfFactory Pro  iF peAS Gt www  fineprint cn          Battery is 
51. t of sending daily history record via email       Able to match shutdown software to protect computer system to save documents safely and turning off the  machine    y Net Agent 3 ports generation  able to link out NETFEELER LITE environment detecting system and external   modems  Also able to use the dial up methods     lt     M    lt     lt   x     rugi ME     4 10  Dry connect state communication  Port definition    1 pin  Rectifier signal is the COM port of relay   2 pin  Rectifier signal is the NC port of relay   3 pin  Bypass signal is the COM port of relay   4 pin  Rectifier signal is the NC port of relay   5 pin  Inverter signal is the COM port of relay   6 pin  Inverter signal is the NC port of relay   7 pin  DC input signal is the COM port of relay   8 pin  DC input signal is the NC port of relay   9 pin  BAT low signal is the COM port of relay   10 pin  BAT low signal is the NC port of relay   11 pin  System fault signal is the COM port of relay  12 pin  System fault signal is the NC port of relay   13 pin  Rectifier switch signal is the COM port of relay  14 pin  Rectifier switch signal is the NC port of relay  15 pin  Bypass switch signal is the COM port of relay  16 pin  Rectifier switch signal is the NC port of relay  17 pin  Inverter switch signal is the COM port of relay  18 pin  Inverter switch signal is the NC port of relay  19 pin  DC input switch signal is the COM port of relay  20 pin  DC input switch signal is the NC port of relay  21 pin  Maintain swit
52. tation  y At the same time  make sure all the switches are cut off  UPS inside should include  warranty card  instruction   installation manual  RS232 CD ROM  RS232 cable    6 2  UPS positioning  6 2 1  Environmental requirements of installation    Temperature  0  C  40  C   Relative humidity  30  90    Height  less than 1000 M  if height exceeds 1000M  reduce 10  usage per 1000M   The size of installation environment should be larger at least 800 mm than the front and back  left and right size  of equipment in order to convenient thermal dispersion and routine maintenance  floor force requirement  1500  KG M       lt     K    lt   x     Ensure installation has following indoor environment     y     No dust  y A proper indoor temperature  UPS can operate under 0 40  C indoor environment  but to open it  it needs  temperature to be higher than 0  C  the ideal temperature is 25  C   y Have a good cooling system  there are some feasible methods as followings   A  Natural ventilation system  only apply to low heat and broad space   B  Artificial ventilation system  when temperature of machine shell  TA  higher than exterior temperature  TE    then it is necessary to install an air condition  When these two temperatures are close  the capacity of ventilation  system needs to be increased relatively     UPS is forbidden to locate at any of following conditions       PDF XE  pdfFactory Pro  WHAREKAI www  fineprint cn       Avoid direct sunlight Avoid raining and humidity Far from fi
53. tering  and then through SPWM Inverter  DC  outputs AC supply  through static inverter switch  AC reaches user  At the same time  DC can charge the battery  pack     MCU control center    5 3  Battery inverter operational mode  Manual maintenance bypass         Auto bypass                   mmunication ur        When mains become abnormal  battery will supply AC through SPWM Inverter  put it out through static inverter  switch     5 4  Bypass operational mode    Manual maintenance bypass    al Auto bypass           pass input                      nmunication    When inverter is not open or abnormal  then system will convert into bypass operational mode  AC inputs through  bypass circuit  and outputs through static switch     MCU control center    5 5 Manual maintenance bypass mbde       PDF SCeRERA  pdfFactory Pro  WAIWAI www  fineprint  cn       Manual maintenance bypass    Auto bypass  o C o    Rectifier _           mmunication 1    When asked on wire maintenance without cutting power  the switch on maintenance bypass needs to be turned on   cut off the output switch and auto bypass switch  this will completely separate UPS s circuit from input and output   without interrupting users    output           VICU control center    Note  when using maintenance bypass switch  must accord with operational procedures of maintenance switch     6  UPS installation    6 1  Disassemble and inspect    y   When open up packages  and take out UPS  check if it has any damage during transpor
54. uld be replaced immediately in order to avoid the damage of whole battery group     8 3  The explanation of alarm      Alarm 1  switch status abnormal  If buzzer alarms and the LCD displays switch are abnormal  please check the following           1  Rectifier switch is turned off  the LCD displays and if changed to please check whether the  rectifier   s switch is off automatically  If switch off please check whether there is output overloaded or short circuit   Switch the LCD screen to output menu to examine the output circuit  if displayed data are within prescribed range  please re start rectifier switch  The alarm will be cleaned automatically  The LCD displays and if change  to   the UPS gets right                                                                          2  Bypass switch is turned off  the LCD displays and if changed to _  please check whether the bypass  is switched off automatically  If switch off please check whether there is output overloaded or short circuit  Switch the  LCD screen to output menu to examine the output circuit  if displayed data are within prescribed range please re start  bypass switch  The alarm will be cleaned automatically  The LCD displays bypass status change from  to   the UPS gets right                                                                 3  Battery switch is turned off  the LCD displays and if changed to please check whether the    battery   s switch is off automatically  If switch off please  amp   whether there 
55. ully trust the sine  wave which was converted by figure voltage to operate perfectly and meet your demand     Efficient IGBT inverter AB technology    High speed switch feature of IGBT  high voltage and large current  adopt voltage drives  only needs little control   power  With lower saturation voltage of the fifth IGBT  the inverter AB works more efficiency and reliable      Superior load   It is completely capable to load from 0 100  while no need to change to bypass  which make sure the output  reliable     Intuitive view of the LED working state and work flow    Humanized big touch screen LCD in both Chinese and English   It provides intuitive view of intelligent icon status of the flow chat  tabular data  events records and menu operation  in both Chinese and English     Perfect protection   It has output over low load protection  input surge protection  phase sequence protection  battery over  charge discharge protection  short circuit protection  over temperature protection and so on  as well as alarming  function     High dynamic performance   Adopting kinds of feedback control such as instantaneous control method and valid date  it achieves high dynamic  adjustment and reduces the output THD     Adopt 6 pulse rectifier  option 12 pulse and input harmonic filter     Effectively restrain the input THD  raise UPS input 6 factor  reduce the input THD current     PDF SCHEER  pdfFactory Pro  iF AeA et www  fineprint cn               Intelligent battery management   L seri
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
WINDOWS VISTA  Regency Illusion owners and installation manual  Samsung ES SBS with Digital Inverter Technology, 512 L, Silver Käyttöopas  RIM-1000 Quick Start Guide 60101  le Mode d`emploi.  Low-Voltage Power Module For Motor Control User`s Manual  Istruzione d`uso  Emtec C200 Pro 32 GB  Samsung TC240 Lietotāja rokasgrāmata  Manual    Copyright © All rights reserved. 