        PVCB series Combiner Box User Manual
         Contents
1.      2  Checking PC monitor software whether the address setting is same with  the combiner box     3  Checking PC monitor software whether the baud rate setting is same with  the combiner box     4  Interference from communication lines  check if the communication bus  terminal is connected with 1200 matching resistor     6 1 2 Lighting protection device failure    Check if detection line is secure  If the contact is good  it means lighting  protection device failed  you should replace a good one immediately     6 1 3 The LED has no display    Click the button A1 or A2  if the LED does not display  it means something  wrong with the LED display circuit     6 1 4 Current sampling problems    If a channel s current sample display value is much larger or smaller than the  other one  Please check if the fuse or photovoltaic arrays is work normal     7 Quality Assurance    7 1 Warranty Policy     7      8    9     PV array combiner box provide 60 month warranty period  The   accessories have 24 month warranty period    Warranty period beginning  The date which you get the goods from our   dealer s    Warranty evidence  the product serial number and the local dealer   delivery invoice   Range  During the warranty period the occurrence of any damage will be   assessed by the dealer and our company defines its scope and   responsibilities    Warranty Policy  In order to provide better services to all users  all   authorized distributors of our company are required to respond to end 
2.   Only for smart type   DC positive fuse holder and fuse  One fuse in series each input string        DC negative fuse holder and fuse  One fuse in series each input string            9   N    oo    gt        N    T      Communication metering plate  Only for smart type   Lighting protection device  DC circuit breaker             e       auxiliary power  Only for smart type        Table 1       3 Installation and Operation    3 1 Basic Installing requirements      Although all models of combiner box have an IP65 degree of protection  and can be installed outdoors  it is also an electronic device  please try to  install the machine in a well ventilated  dry and dust proof place but not a  damp places      Install the combiner box as close as possible to the PV array to reduce the  use of cables and get a better convergence      Environment temperature  25      to  60     relative humidity of 0  to 99       Avoid direct rays of the sun  otherwise the high temperatures may reduce  the life of the combiner box      Forbidden to upside down the installation     3 2 Installation tool to prepare    Drill  screwdriver  adjustable wrench  socket wrench  M9  and so on     3 3 Mechanical installation methods and procedures    Combiner box wall mounted on solar panel bracket  you need to configure the   hex bolts  R4 5   flat washers  R4 5   spring washers  R4 5   Users can also   base on specific installation conditions to choose suitable bolts    Below taking 12 Way combiner box as an 
3.   users  warranty claim  During the warranty period   it will be replaced by  any authorized dealer in the design and production of defective products  and accessories    Under the following situations our company exempted from liability   Product design changes or modifications or replacement parts without  permission of our company    Modification  changes or attempted repair and the serial number has  been rubbed or without technicians  seal of our company    Incorrect installation and commissioning    Failure to comply with the appropriate safety regulations  CQC standards   etc      The product has been improperly stored and damaged while being stored  by the end user    Transportation damage  painting surface scratches cased by shipping  pumping  When unloading there is sufficient evidence should be reported  to the insurance company as soon as possible    Fails to comply with user manuals  installation guides  maintenance  procedures    Improper use or improper operation    Lack of ventilation equipment      10  Associated with this product or performing maintenance procedures not    followed an acceptable standard      11  Force majeure  such as lightning  overvoltage  storms  fires      7 2 Warranty and Claims Procedure      Claim principles  the principle of warranty claims beyond the authority cited   especially for defective equipment damage caused by direct or indirect  claims for damages or losses arising from the demolition and installation  requirements for co
4.  will loose  using a plier which insulated voltage is greater than  1000V to fix tight  to ensure a good contact with the base of fuse     5 Specifications      Smart combiner box type                                                          Model PVCB 8M PVCB 10M PVCB 12M PVCB 16M  Parameters  Max input current 9 6A 9 6A 9 6A 9 6A  Communication RS485 RS485 RS485 RS485  Max input voltage 1000V 1000V 1000V 1000V  Max input circuit 8 10 12 16  Degree of protection IP65 IP65 IP65 IP65  Dimension 400 200 420   460 200 470 460 200 470 460 200 590   W H L mm  Table 8    Non smart combiner box type  Model PVCB 8M PVCB 10M PVCB 12M PVCB 16M  Parameters  Max input current 9 6A 9 6A 9 6A 9 6A  Max input voltage 1000V 1000V 1000V 1000V  Max input circuit 8 10 12 16  Degree of protection IP65 IP65 IP65 IP65  Dimension 400 200 420 460 200 470 460 200 470 460 200 590   W H L mm          Table 9                   6 Troubleshooting    Attention    Before troubleshooting  please observe these steps to deal with it in order to   ensure safety      Before operating the combiner box  the DC breaker must be disconnected     Remove all fuses  at this time there are still high voltage on fuse s base      Recommended to wear insulated gloves which insulated voltage is greater  than 1000V     6 1 Common troubleshooting methods    6 1 1 RS485 communication failure     1  Check if the power supply is normal  RS485 chip supply voltage is 5V  voltage  If abnormal  please check the auxiliary power output
5. 6 3 Selection of machine                            14  3 7  STOP AND START COMBINER BOX lH  satire Eden 14   4 ROUTINE  MAINTENANCE 2 2 ne 15  4 T FUSE REPLACEMENT raten Hr eb e RER iin IR 15   5S SPECIFICATIONS 2 22 22 RI d ee 16   6 TROUBLESHOOTING 0   coceciecsetacaceacanceedessansdnecatssninssanecnecessteinsasinccoeseetesineduansedsccrssiaedadncciaeere 17  6 1 COMMON TROUBLESHOOTING METHODS sse e ener enne nennen 17   6 1 1 RS485 communication failure eene 17  6 1 2 LIGHTING PROTECTION DEVICE FAILURE                esee nennen enne A RA KA RA 17  6 1 3 The LED are not displayed                      nn ne 17  6 1 4 Current sampling problems kek kk kk k   kek kk k   kk KAKA 17       QUALITY ASSURANCE                                                                      18   TL ANARRANTY POEIGY  E 18    7 2 WARRANTY AND CLAIMS PDROCEDURE  kk kk k   kk kk ek kk k   kk k   KK KA KE KA KA KAKA KA KK KK KA 19    1 Product Description    1 1 Overview    In a solar photovoltaic system  between PV array and inverter  cables  connections  monitoring and maintenance are not convenient as well as other  reasons  generally it has to be equipped with a combiner box device     PVCB series combiner box includes both smart and non smart type  and  models range from 8 way  10 way  12 way to 16 way     Smart combiner box primarily by the DC circuit breakers  lightning protection   cable interface  the current sampling board  insurance board  communication  metering board and auxiliary power 
6. ED display  the front two LED display is used to display  pages  following three to sequentially display the current  voltage  temperature   combiner box communication address and combiner box type  Shown in  Figure 8  function of the key A1 is to page up  and the key A2 is to page down   can be recycled flip  the display content shown in Table 4    Description  LED display will automatically turn off after three minutes show  that only a decimal point  click the button A1 or A2  LED display will resume  so  when the LED light is not on  do not think it is abnormal     3 6 Communication parameter setting    Description  non smart combiner box type without this feature    Combiner box communication parameters can be set by the dips switches on  communication metering board  it includes communication address setting and  communication rate setting                           Figure 8  Description  non smart combiner box does not have this feature   Setting address cutline Binary decimal address  addres  S  1  0000  1291   0001  2  0000  1  21 0  21 2   0010  3  0000  1x2  1x2   3   0011  247  1111  1x27 1x26 1x25 1 x24 0x23 1x22 1x21 1x20 247    0111                Table 6  Communication addresses setting is shown in Table 5  This communication  metering board provides two keys to set communication parameters shown in  Figure 8  Function of the key A1 is to page up and the key A2 is to page down   when address set completion  using the keys turn to corresponding page  you  can vi
7. PVCB series Combiner Box  User Manual             Shenzhen JingFuYuan Tech  Co   Ltd    www jfy tech com    CONTENT    T PRODUCT DESCRIPTION    ege ege ENEE meer 3  TI OVERVIEM                   e E eb t elu        TU ee b recu ebe 3  1 2 SCOPE OE SUPPLY AR Eike 3  1 3  MODEL DESCRIPTION  1 24   22  ay   21 d  ye      ER en Haan dienes decane dene PRATER D   K  R  N 3  T4 FUSE RATING SELECT HELP   n ier dre E RE innen 4  1 5 DC CIRCUIT BREAKER RATING SELECT H  ELp   kk kk kk kek   k   kK kk kek KA KAK KA kk 4  AG FEATURES        Mez   He aM                 E ded eda sk   4  1 7 WORK ENVIRONMENT 552 eret P P Ka ba Hur   k   ka daa              eatis 5   2 BASIC STRUCTURE  4  5   caceiczcscsisecaancsiractasssacucncessnczassuecedncsinaateassezscnceinscvdassenceancsnt  nauesincennct 5      INSTALLATION AND                                                                            6  3 1 BASIC INSTALLING REQUIREMENTS                                   6  3 2 INSTALLATION TOOL TO                                         6  3 3 MECHANICAL INSTALLATION METHODS AND PROCEDURES mann 6  SA ELECTRICAL CONNECTION EE 7   3 4 1 Waterproof terminals and corresponding cable nnn 7  3 4 2 Preparation before               2    nennen nennen 9  3 4 3 DC input and output wiring            E    ener nnns 9  3 4 4 Communication VWimg                  10  3 5 VIEW COMBINER BOX MONITORING DATA    11  3 6 COMMUNICATION PARAMETER SETTING 2            12  3 6 2 Baud trate setting  er hereditarie dins 13  3 
8. ature     lt  With RS485 communication interface  communication protocol is  MODBUS protocol   Non smart type without this feature      PV power supply for the internal power supply  DC 250 1000V      The communication address can set by DIP switch  you can view the  current size of each channel  PV bus voltage  temperature  RS485  communication baud rate  combiner box mailing address and combiner  box type   Non smart type without this feature     1 7 Work Environment         gt   gt     Operation environment temperature   25  C    60   C   Storage temperature   40         70         Relative humidity  lt  99   non condensing    No severe vibration shock  vertical gradient  lt  5        2 Basic Structure    Figure 1 is a combiner box of the whole internal structure of miniature  each                                                                                                                                                                                                                                                                                                                                              t9   e INO  p 9 fofo  ud 8         2    oll el a D o     6  e Eza  E   EZS  o  15 2            ols  p               o                                            EEE   MEE    Figure 1    part of the name of the below table        Part Number    Description       DC positive output terminal       DC negative output terminal  Ground terminal  RS485 communication terminals
9. board  Current sampling board is using to  turn a large current to the small current signal  communication metering board  is using to sample each branch line current of combiner box  PV bus voltage  sampling  as well as lightning protection devices and circuit breakers state  monitoring  It can sample real time data send to the host computer so that we  can monitor the state of voltage and current  Communication metering board  provides DIP switches for address selection and the type of machine   non smart combiner box have not communication metering board  sampling  board and auxiliary power supply board  so it do not have the function of  sampling voltage  sampling current  lightning protection status detection and  the DC circuit breaker status detection     1 2 Scope of supply    Combiner box including   PV array combiner box   Chassis Intrusion keys   User manual    Warranty card   Certificate    Factory test report     ooo  gt   gt     1 3 Model description    PVCB XX M              Itrepresents the PV array combiner box     It represents the largest number of parallel inputs of combiner box    It represents combiner box has inspection and monitoring functions    1 4 Fuse rating select help    In any power system  the fuse is used to protect electronic devices from  over current damage  if without protection  over current may cause electronic  devices malfunction  overheat  damage and even fire  If the fuse rating is too  large  it cannot provide protection  if the fus
10. e rating is too small  then the circuit  cannot work properly  Therefore  we have to select the suitable fuse ratings  according to the level of PV array and related standards  The fuses ratings be  determined by the short circuit current Isc of the PV array  due to different  specifications of solar panels  the short circuit current Isc are various  the  different levels of the fuse have to be replaced to meet requirements of the PV  array    If no relevant requirements of local standards  we recommend the maximum  current flowing through the fuse is 1 56   Isc  For example  the PV array short  circuit current is 10A  then the maximum rated current of the fuse is 15 6A  and  voltage requirements of 1000V  then we can choose 16A 1000V fuse     1 5 DC circuit breaker rating select help    DC circuit breaker for selection depends on the input ones of combiner box  and the size of each of the input current  such as 12 way combiner box   assuming short circuit current Isc of the PV array is 10A  the size of the voltage  1000V  flowing through the DC circuit breaker current of 10 x 12   120A   Therefore  the level of the DC circuit breaker must be at least 120A 1000V     1 6 Features      Current measurement using hall sensors  isolation measurements      Special PV DC circuit breakers  lightning protection devices and fuses      Measuring voltage range 0 to 1000V It can detect lightning protection and  breaker status and cabinet temperature   Non smart type does not have  this fe
11. ew the address you have set  The address is displayed in decimal     3 6 2 Baud rate setting    Description  non smart combiner box type does not have this feature    Baud rate refers to the RS485 communication rate  while holding down the A1  and A2  then release the button  the LED display shows the current default  baud rate  and then passed through a separate press A1 select the baud rate  you want  and then press A2 to finish  The combiner box provides       2400 4800 9600 19200bps four kinds of baud rate for selection     Note    1 When the communication distance is far  select a lower baud rate   communication will be more stable    2 Combiner box baud rate must be same with the host computer monitoring  software baud rate setting     3 6 3 Selection of machine type    Description  non smart combiner box does not have this feature    PVCB series combiner box provides 8 way  10 way  12 way and 16 way  a  total of four models  if you want the content of LED display to be correct  you  must select the corresponding machine type by the DIP switch on  communicate metering board show in Figure 9                                     Figure 9  Different machine type setting method as following  switch1 switch2 switch3 Machine type   1 0 0 8 way   0 1 0 10 way   1 1 0 12 way   0 0 1 16 way  Table 7    Show in Table 7  1  stands for upward   0  stands for downward  For example   if combiner box type is 10 way  You just keep switch 1 and switch 3 downward  and switch 2 upward  if 
12. example to explain the steps to   install  other models of combiner box installation steps are same  but not the   same size    Installation steps     1  Combiner box installing to bracket of solar panel needs to meet the  following size  unit mm   shown in Figure 2                          Figure2   2  With a hex nut and hex bolts fix combiner box  it is the bolt  combiner box  hangers  brackets  flat washers  spring washers and nuts from bottom to  top by sequence    3  Check if the combiner box is installed correctly and firmly     3 4 Electrical connection    If the actual access of the PV array is smaller than the largest connected ones   the extra terminals need to use waterproof plug plugged    Each input string is equipped with a dedicated photovoltaic fuses  as the front  input protection device  testing each string between positive and negative  voltage is between 0   1000V before inserting the fuse  and ensuring that each  PV string has no fault to ground    3 4 1 Waterproof terminals and corresponding cable    Description  8 way  10 way  12 way smart and non smart combiner box  waterproof terminals and wiring cable specifications are the same  Except  16 way combiner box waterproof DC bus output terminal and the output of the  DC bus connection cables           N    6        V V    die  QQ      5           7 8 9    Hi    Figure3    PV  N         AAA  V el ei  900    1 8 9  AAA  999    Figure 3 is    12        smart combiner box waterproof terminals and the  corres
13. ground fault      Recommended wiring to bring an insulation gloves  insulated voltage  greater than 1000V    Connection steps     1  Loosen the lower end of the combiner box locking packing cap     2  The cables of line number PV1   through the PV array positive input  terminal  access combiner box corresponding to the PV1   terminals   Note line to leave a margin in order to fix     3  With a wire poke insulation stripper layer and shielding layer  partially  exposed copper wire about 12mm     4  Use a cross screwdriver to loosen the captive terminal  insert the cable into  the terminal  tighten the screws     5  By the same method to connect the remaining lines  the wiring preferably  correspond to the order to the corresponding terminals so that the  maintenance of late     3 4 4 Communication Wiring    Description  non smart combiner box have not this step   The network of combiner box by RS485 communication connecting is shown in    Figure 5   Combiner Combiner  box 1 box2       Monitor  center    Figure 5  Note  Figure 5 shows the final combiner box need to pick a 1200 resistor   just put J2 plug with the jumper on communication metering board   the 1200 resistor is connected to the RS485 bus        Figure 6                         Part Description   1 RS485 communication terminal  2 DC positive bus output terminal  3 Grid ground terminal   4 DC negative bus output terminal    Table 4   As Figure 6 shows the internal terminal block of combiner box  from left to right   
14. he  right PV IN is the wiring hole for DC negative of the PV array      In middle PV   OUT is the wiring hole for DC positive bus output  PV OUT  is the wiring hole for DC negative bus output  with earth symbol is the wire  hole for the grid ground      RS485 communication ports with RS485 label left one which is connected  to a previous combiner box  the right one is connected to the next  combiner box     3 4 2 Preparation before wiring     1  Open combiner box  All PV array combiner box offers a key to close and open it  Please put the  key into the lock  twisting the key as the direction shown in Figure 4   Clockwise twist close the box  counterclockwise twist open the box   Attention  you must turn on   off both up and down  in order to turn on or off  the box effectively        Figure 4   2  Off the circuit breaker in  OFF  position    3  Remove all fuses  if the fuse is not installed by factory  skip this step    4  Using a dedicated pliers pull out all the fuses  electrical pliers insulation  voltage greater than 1000V     3 4 3 DC input and output wiring    Attention  The PV strings presence of high voltage  accidental exposure may  produce lethal electric shock or burns  need to pay attention the following  security when wiring      While wiring  please cover the PV arrays by opaque material      Please follow safety instructions of all solar panel manufacturers          Wiring must be correct  note the distinction between positive and negative   confirming that no 
15. mpensation  or not included in the warranty for loss of  profits  in these situations our company have not statutory obligations      Warranty and claims procedures  Please contact your local dealer of our  company with a simple description of the error report for defective  equipment  If we agree to replace  we generally depending on the model  and age  made an equivalent replacement device  The remaining warranty  rights will be transferred to the replacement device  In this case  because  of your authority has been filed at our company  you will not receive a new  certificate  Replacement products will be send in two working days  Defective equipment should return to the dealer  If the on site service is  necessary  the end user should consult in advance with the dealer  All  warranty service during the warranty period is free     Shenzhen JingFuYuan Tech Co  LTD     ADD 5th Floor  12th Block  Nangang Second Industrial Park  SongBai  Road  Xili Town  Nanshan District  Shenzhen  P R China  Tel   86 755 8179 5460 Fax  86 755 2650 5986    E mail  support jfy tech com  Website  www jfy tech com    
16. ponding cable diagram  non smart combiner box but less waterproof  RS485 communication terminals     8 way  10 way  12 way smart and non smart type combiner box  user can  choose the appropriate wiring cables according to Table 2        Terminal Description    Terminal Specification    Wiring Recommendation                               DC positive input  PV   IN  PG7 4mm    DC negative input  PV  IN  PG7 4mm    DC positive bus output  PV   OUT  PG21 50mm    DC negative bus output  PV   OUT  PG21 50mm    Ground terminal PG11 16mm    Communication Terminals PG7 1 5mm   low resistivity shielded twisted pair  Table 2    16 way smart and non smart type combiner box  user can choose the    appropriate wiring cables according to Table 3        Terminal Description    Terminal Specification    Wiring Recommendation                            DC positive input  PV   IN  PG7 4mm    DC negative input  PV  IN  PG7 4mm    DC positive bus output  PV   OUT  PG21 70mm    DC negative bus output  PV   OUT  PG21 70mm    Ground terminal PG11 16mm    Communication Terminals PG7 1 5mm   low resistivity shielded twisted pair  Table 3    Description  different cable manufacturers will have some differences   diameter is different according to the solar panel  but it should be  matched with the waterproof terminals           Shown in Figure 3  with 12 way combiner box as an example to explain the   terminal situations      onthe left PV   IN is the wiring hole for DC positive of the PV array    on t
17. they are RS485 communication terminals  DC positive bus output terminal   ground terminal  DC negative bus output terminal  Wiring must take on the  right line  or else will cause very serious consequences  RS485  communication terminals is divided into two groups  a total of six interface  shown in Figure 6  from left to right is A1 A2  B1  B2  G1  G2  in which A1   B1 G1 is a group  A2  B2  G2 as a group     3 5 View combiner box monitoring data    Description  non smart combiner box does not have this feature        Figure 7       LED display Introduction                                                                               page Display content  8 way smart 1 8 PV DC inputs 1   8 channel current size unit A   combiner box 9 Voltage  unit V   10 Temperature  unit C    11 RS485 communication address  12 Combiner box model  page Display content  10 way smart 1 10 PV DC inputs 1   10 channel current size unit A   combiner box 11 Voltage  unit V   12 Temperature  unit        13 RS485 communication address  14 Combiner box model  page Display content  12 way smart 1 12 PV DC inputs 1   12 channel current size unit      combiner box 13 Voltage  unit V   14 Temperature  unit        15 RS485 communication address  16 Combiner box model  page Display content  16 way smart 1 16 PV DC inputs 1   16 channel current size unit      combiner box 17 Voltage  unit V   18 Temperature  unit        19 RS485 communication address  20 Combiner box model  Table 5    Shown in Figure 7  5 L
18. you want to ensure you choice is correct  you can flip  through the key A1 and key A2 buttons scroll to the appropriate page  the  machine type will display on LED display    Description  In addition to the above table lists case  LED will display   Err  which indicate the type of machine is wrong     3 7 Stop and start combiner box    Combiner box run automatically after power on  automatically shutdown  after power off  you can stop the DC bus output by the DC circuit breaker     4 Routine Maintenance      Due to ambient temperature  humidity and dust factors  so there will be a  potential failure  combiner boxes require regular maintenance in order to  ensure normal operation and service life     lt  When maintenance is required  combiner box must be stop and ensure  that combiner box is total power off    Attention  Fuse has high voltage from solar panels and inverters  during  normal working it cannot be touched  Before checking and replacing the  fuse  you must disconnect the DC circuit breaker  Please note it is still in  high voltage across the DC circuit breakers  until confirm current of each  string is zero  we can remove the fuse from the solar panels or combiner  box for maintenance  We recommend to wear insulated gloves  insulated  voltage greater than 1000V to do the maintenance     4 1 Fuse Replacement    Broken fuse can not be recovered  only an operators with relevant  qualifications recommended to replace the fuse  After several plug fuse  the  base of fuse
    