Home
        new kbmm manual - KB Electronics, Inc.
         Contents
1.      The value of RT  Q  can be calculated using the fol   lowing formula  RT    1 3 X VT X S    16000 Q  Where    VT    is the tach generator voltage  in Volts  per 1000 RPM  and    S    is the base speed of the  motor  in RPM            Example  If a 20 Volt per 1000 RPM tach generator  is to be used with a 3600 RPM motor              RT    1 3 X 20 X 3600    16000   77600 Q  Choose the closest 1 2 Watt resistor value  which is 75000 Q  75 kQ         7 SETTING SELECTABLE JUMPERS  The control has selectable jumpers which must be set before it can be used  See Figure 1  on page 10  for the  location of jumpers     7 1 AC Line Input Voltage Selection  Jumper J1  Model KBMM 225D Only     Jumper J1 is factory set to  the    230    position for 208 230 Volt AC line input  For 115 Volt AC line input  set Jumper J1 to the    115     position  See Figure 11  on page 20     Notes  1  Jumper J1 is installed on Model KBMM 225D only  2  When Jumper J1 is set to the    115    posi   tion  Jumper J2 must be set to the    90    position  or the    T    position if using a tach generator         20    7 2 Motor Voltage and DC Tach Generator Selection     FIGURE 11   AC LINE INPUT VOLTAGE SELECTION  Jumper J2 is factory set to the    90    position on Model  JUMPER 1    MODEL KBMM 225D ONLY  KBMM 125  for 90 Volt DC motors  and set to the J1 Set for J1 Set for     180    position  on Models KBMM 225  225D  for 180 20s aovo tac o q 115 Volt AC Line Input           Factory Setting   Volt DC mo
2.    Main Speed Potentiometer   Front View          Terminal  P3          Terminal  P2                          Terminal  P1     Open Collector   On to Run    Off to Stop        Main Speed Potentiometer   Front View        of the load     Inhibit Circuit Connection   The control can be stopped  and started with an Inhibit circuit  close to stop  open to run    Wire the switch or contact to Terminals    11    and    12     as  shown in Figure 7  When the switch or contact is closed  the  motor will coast to stop  When the switch or contact is  opened  the motor will accelerate to the Main Speed  Potentiometer setting  An open collector  NPN  can be wired    in lieu of a switch or contact      WARNING  The Inhibit Circuit is never to be used  as a Safety Disconnect since it is not fail safe  Use  only the AC line for this purpose        FIGURE 7   INHIBIT SWITCH OR CONTACT  WIRED TO THE INHIBIT TERMINALS       Terminal  1        Terminal  12              Inhibit Switch or Contact Open Collector   Open to Run   Off to Run    Close to Stop   On to Stop              17    6 9 DC Tach Generator Connection   A DC tach generator    can be used for load regulation of 1  of the set speed   Note  Jumper J2 must be set to the    T    position for  tach generator operation  Connect the tach generator  as follows     Application Notes   1  The tach generator input circuit is  designed for a 7 Volt or 50 Volt per 1000 RPM DC tach   generator used with an 1800 RPM motor  2  Initially set the  
3.   14    30    13 3 Reversing and Dynamic Braking   The optional patented APRM   provides anti plug    instant    reversing    and solid state dynamic braking  The APRME is built in as standard on Models KBCC R    and KBPB      Contact the Sales Department for more information     OPTIONAL ACCESSORIES    14 1    14 2    14 3    14 4    14 5    14 6    14 7    14 8    14 9    Auxiliary Heat Sink  Part No  9861    Doubles the horsepower rating of the control     Barrier Terminal Accessory Kit  Part No  9883    When used with the Auxiliary Heat Sink  it converts the  quick connect terminals of the control to a barrier terminal block     Barrier Terminal Board  Part No  9897    Converts the quick connect terminals of the control to a barrier  terminal block  Contains PC board mounted line and armature fuse holders  fuses supplied separately    Plugs onto the quick connect terminals of the control     SI 6 Signal Isolator  Part No  9444    Provides isolation between non isolated signal sources and the con   trol  Plugs onto the quick connect terminals of the control     Run Brake Module  Part No  9952    Used for applications that require rapid stopping of the motor   Contains a barrier terminal block     Dial Plate and Knob Kit  Part No  9832    Provides indication of the Main Speed Potentiometer   position  O   100       Finger Safe Cover  Part No  9564    Converts the control from open chassis to the IP 20 standard   Fuse  holders must be removed when installing the finger safe 
4.   3  which eliminates the need for recalibrating IR Comp and Current Limit when the control is used on  various horsepower motors  In addition  the rating of the control can be extended to 1 5 HP for controls with 90  Volt DC output and 3 HP for controls with 180 Volt DC output  by the use of KB   s Auxiliary Heat Sink4  Models  KBMM 225 and KBMM 225D also allow operation of 90 Volt DC motors when used on 208 230 Volt AC line  input  gt         The versatility of the control is confirmed by its extensive list of standard features  such as  selectable armature  and tach feedback and adjustment trimpots for minimum speed  maximum speed  current limit  IR compensation   and linear acceleration and deceleration  The control includes Auto Inhibit    which eliminates surging during rapid  AC line switching  pulse transformer triggering  which provides cogless operation at low speed  and superior noise  rejection circuitry  which eliminates false starts and blown SCRs  Enable  normally closed  and Inhibit  normally  open  functions provide electronic switching of control output     The output voltage of the control is a linear function of the Main Speed Potentiometer rotation  In addition  the  control can be used in a voltage following mode by supplying an isolated analog input signal to Terminals    P2         and    P1       6  The control is compact in size  only 4 30    X 3 64    X 1 25     and easily replaces all competitive speed  controls  The control is supplied with a 5 kQ
5.  0   Full Load  50 1 Speed Range     Base Speed  1      Tach Generator Feedback Load Regulation  0   Full Load  50 1 Speed Range     Set Speed  1      Line Voltage Regulation  at Full Load    10  Line Variation   Y Speed  0 5      Control Linearity    Output Voltage vs Signal Input Voltage  2      Acceleration  ACCEL  Trimpot Range  Seconds  0 2 10 2  Deceleration  DECEL  Trimpot Range  Seconds  0 2 10 2  Maximum Speed  MAX  Trimpot Range    Base Speed  50 110 100  Minimum Speed  MIN  Trimpot Range    Base Speed  0 30 0  Current Limit  CL  Trimpot Range    Full Load  0 200 150  IR Compensation  IR  Trimpot Range  at Specified Full Load   90  180 Volts DC Output   Volts DC  0 24  48 3 6          Notes  1  Step down operation  motor may have reduced brush life  Consult motor manufacturer  2  Performance is for SCR rated permanent magnet motors  only  Lower performance can be expected with other motor types  Factory setting is for 3  load regulation  To obtain superior regulation  see Section 11 6  on  page 27     FIGURE 1   CONTROL LAYOUT 8 GENERAL CONNECTION DIAGRAM  Model KBMM 225D Shown    Note  Control is set for 208  230 VAC line input  0 180 VDC output with armature feedback        Plug In                       AC Line Fuse  Supplied Separately    DON    A DOT E       Enable Switch   Close to Run    Open to Stop                                                             AC Line Main Speed Potentiometer    Input     Front View     Inhibit Switch   Open to Run    Close to 
6.  13 2     13 2 Armature Switching and Dynamic FIGURE 20   TYPICAL DYNAMIC BRAKE CIRCUIT CONNECTION  Braking   If the armature is to be dis   connected and reconnected with the AC  power applied  wire a relay  or contactor   and a brake resistor  RB  in the armature  circuit  The Inhibit Circuit must be simul  AC Line Input  taneously activated when braking  Wire a  double pole double throw  DPDT   mechanically ganged switch to the Inhibit  Terminals and the relay  or contactor   coil  as shown in Figure 20  The resist   ance and wattage of RB must be chosen  according to braking requirements        Speed Control         Motor  Armature       Double Pole Double Throw  Mechanically Ganged Switch    Relay or  Contactor Coil    When the switch is in the    Brake    posi   tion  the relay is deenergized and allows  the motor voltage  via the N C  contact  to be dissipated through RB and dynamically brake the motor   Simultaneously  the Inhibit is activated and the control output is electronically    extinguished     which elimi   nates arcing              When the switch is in the    Run    position  the N C  contact opens  the N  O  contact closes  the Inhibit is  deactivated  and the motor begins to accelerate  according to the setting of the ACCEL Trimpot  to the Main  Speed Potentiometer setting     WARNING  The Inhibit Circuit  Terminals    11    and    12     is never to be used as a Safety  Disconnect since it is not fail safe  Use only the AC line for this purpose     29  
7.  9      0 25    female crimp on termi   nals   4    0 11    female crimp on terminals  and an Enable harness   CE Approved Product Information Card  and  Warranty Registration Card     Items required to operate this control     Plug In Horsepower Resistor    AC Line Fuse and Armature Fuse  Supplied  through your distributor  See Sections 8 and 9  on pages 20 22  3    1    SIMPLIFIED INSTALLATION INSTRUCTIONS       IMPORTANT   Read these simplified installation instructions before proceeding  These instructions are to be  used as a reference only and are not intended to replace the detailed instructions provided herein  You must  read the Safety Warning  on page 6  before proceeding              Note  A Plug In Horsepower Resistor   and AC Line and   Armature Fuses  supplied separately  must be installed in   order for this product to operate  See Section 9  on page 21  Fuse Plug In Horsepower  Resistor         1 1    1 2    1 3    1 4    AC Line Connection   Wire the AC line to Terminals    L1     Line Fuse  and    L2     as shown in Figure 1  on  page 10 and as described in Section 6 1  on page 13     Model KBMM 125 is rated for 115 Volt AC line input only  Model KBMM 225 is rated for 230 Volt AC line  input only  Model KBMM 225D is rated for 115 Volt AC line input  Jumper J1 in the    115    position  and 230  Volt AC line input  Jumper J1 in the    230    position   See Section 7 1  on page 19     Notes  1  The rated AC line voltage  115  208 230  of the control must match
8.  CL to operate properly   Calibration of the CL Trimpot is normally not required when the proper Plug In Horsepower Resistor   is  installed     To Recalibrate the CL Trimpot     1    Disconnect the AC power and wire a DC ammeter in series with either motor armature lead   Note  If only an AC ammeter is available  wire it in series with either AC line input lead    Set the Main Speed Potentiometer to approximately 30   50   clockwise position    Set the CL Trimpot fully counterclockwise  The CL LED will illuminate red    Lock the motor shaft  be sure the CL Trimpot is set fully counterclockwise      Apply power and rotate the CL Trimpot clockwise until the desired current reading is observed on the DC  ammeter  Factory Current Limit setting is 1 5 times the full load rating of the motor  with a DC ammeter    wired in series with the motor armature   If using an AC ammeter wired in the AC line input  the factory  Current Limit setting will read 0 75 times the full load rating of the motor     Do not exceed 2 times motor current rating  maximum clockwise position    Note  On cyclical loads  it may be normal for the CL LED to momentarily flash     WARNING  Do not leave motor shaft locked for more than 2 3 seconds or motor damage       may result   11 6 IR Compensation Trimpot  IR    The IR Trimpot sets FIGURE 19   IR TRIMPOT RANGE  the amount of compensating voltage required to keep  the motor speed constant under changing loads  If  the load does not vary substantially  the IR 
9.  IR Compensation and Current  Limit based on motor horsepower and voltage  The Plug In Horsepower Resistor   eliminates the need to recali   brate IR Compensation and Current Limit in most applications  2  Be sure the Plug In Horsepower Resistor   is    inserted completely into the mating sockets     21       TABLE 6   PLUG IN HORSEPOWER RESISTORO SELECTION                                                 90   130 Volt DC Motors 180 Volt DC Motors Plug In Horsepower Resistor      HP   HP  Value  Ohms  Part No    1 100     1 50 1 50   1 25 1 9833   1 50   1 30 1 25 1 15 51 9834   1 30   1 20 1 15 1 10 35 9835   1 20   1 12 10   1 6 25 9836   112 118 1 6  1 4 18 9837   1 8  1 5 1 4  1 3 A 9838   1 4 1 2  05 9839   1 3 3 4 035 9840   1 2 1 025 9841   3 4 1  015 9842   1 2 01 9843   1  3  006 9850                     Indicates an Auxiliary Heat Sink  Part No  9861  or equivalent  must be used to achieve rating indicated     10 RECOMMENDED HIGH VOLTAGE DIELECTRIC WITHSTAND TESTING  Hi Pot Testing   Testing agencies such as UL  CSA  etc   usually require that equipment undergo a hi pot test  In order to prevent  catastrophic damage to the control  which has been installed in the equipment  it is recommended that the follow   ing procedure be followed  A typical hi pot test setup is shown in Figure 13 on page 23  Note  All controls have  been factory hi pot tested in accordance with UL requirements     MA WARNING  When performing the hi pot test  disconnect the AC power     22    FIG
10.  Main Speed Potentiometer and QD terminals  All models are UL  Listed  USA and Canada  and CE Approved     Notes  1  Short circuit protected at motor only  2  KB Limited Warranty applies  See page 32  3  Fuses and  Plug In Horsepower Resistor   supplied separately  See Sections 8 and 9  on pages 20   22  4  Part No  9867   See Section 14 1  on page 30  5  Step Down operation  6  If an isolated signal input is not available  or if using a  4   20 mA DC signal input  install the optional plug on SI 6 Signal Isolator  Part No  9444      3 1    Standard Features    1    10    11  12  13  14    Plug In Horsepower Resistor     Eliminates the need to calibrate the control for IR Compensation  and Current Limit when used on various horsepower motors     Auto Inhibit       Allows the control to be rapidly switched    on    and    off    using the AC line   Inhibit and Enable   Allows the control to be turned    on    and    off    using electronic switching     Trimpots   Minimum Speed  MIN   Maximum Speed  MAX   IR Compensation  IR   Current Limit  CL    Acceleration  ACCEL   and Deceleration  DECEL      Jumpers   AC Line Input Voltage Selection  J1  Model KBMM 225D only    Motor Voltage and DC  Tach Generator Selection  J2      Protection Features   MOV transient protection  Short Circuit protected  at motor only    Diagnostic LEDs     Power On  PWR ON  and Current Limit  CL    Model KBMM 125 operates on 115 Volt AC line input with 90 Volt DC motors     Model KBMM 225 operates on 23
11.  purchase  KB Electronics  Inc  will repair or replace  without  charge  devices which our examination proves to be defective in material or workmanship  This warranty is valid  if the unit has not been tampered with by unauthorized persons  misused  abused  or improperly installed and has  been used in accordance with the instructions and or ratings supplied  The foregoing is in lieu of any other war   ranty or guarantee  expressed or implied  KB Electronics  Inc  is not responsible for any expense  including instal   lation and removal  inconvenience  or consequential damage  including injury to any person  caused by items of  our manufacture or sale  Some states do not allow certain exclusions or limitations found in this warranty and  therefore they may not apply to you  In any event  the total liability of KB Electronics  Inc   under any circumstance   shall not exceed the full purchase price of this product   rev 2 2000              COPYRIGHT    2004 by KB ELECTRONICS  INC     All rights reserved  In accordance with the United States Copyright Act of 1976  no part of this publication may be repro   duced in any form or by any means without permission in writing from KB Electronics  Inc   8 22 02           KB Electronics  Inc   4   12095 NW 39th Street  Coral Springs  FL 33065 2516    954  346 4900 e Fax  954  346 3377    Outside Florida Call TOLL FREE  800  221 6570   E mail     info kbelectronics com  www kbelectronics com     A40209    Rev  A     8 2004    
12.  the actual AC line input  voltage  2  If one of the AC line inputs is a neutral  N   wire it to Terminal    L2        Ground Connection     Connect the ground wire  earth  to the control chassis     Motor Connection   Connect the motor to Terminals    A      Armature Fuse  and    A      as shown in Figure 1   on page 10  and as described in Section 6 3  on page 14     Jumper Settings   Jumper J1  on Model KBMM 225D only  and Jumper J2  all models  have been factory  set for most applications  as shown in Figure 1  on page 10  and as described in Section 7  on page 19        1 5    1 6    1 7    1 8    1 9    AC line Fusing   It is required that an AC line fuse  supplied separately  be installed in the AC Line Fuse  Holder  as shown in Figure 1  on page 10  Select the correct AC Line Fuse  as described in Section 8  on  pages 20 and 21  Fuse each conductor that is not at ground potential     Armature Fusing   It is required that an Armature Fuse  supplied separately  be installed in the Armature  Fuse Holder  as shown in Figure 1  on page 10  Select the correct Armature Fuse as described in Section 8   on pages 20 and 21     Plug In Horsepower Resistor     Install the correct Plug In Horsepower Resistor   according to armature  voltage and motor horsepower  as shown in Figure 1  on page 10  Select the correct Plug In Horsepower  Resistor    as described in Section 9  on pages 21 and 22     Trimpot Settings   All trimpots have been factory set for most applications  as shown i
13.  ture switching is required for reversing or dynamic braking  use Model KBMG  KBRG  KBPB  KBCC R     Step Down Transformer and AC Line Switching   When using a step down transformer  460 Volts AC to  230 Volts AC   be sure the output current rating of the transformer is at least 3 times the current rating of the  motor  Do not switch the primary side of the transformer to disconnect power or catastrophic failure can  result  Always disconnect the control from the secondary side of the transformer     MOUNTING INSTRUCTIONS   It is recommended that the control be mounted on a flat surface with adequate ventilation  Leave enough room to  allow for AC line  motor connections  and other wiring that is required  Care should be taken to avoid extreme  hazardous locations where physical damage can occur  When mounting the control in an enclosure  the enclosure  should be large enough to allow for proper heat dissipation so that the ambient temperature does not exceed   45   C  113   F  at full rating  See Figure 2  on page 11     6 WIRING INSTRUCTIONS          A       WARNING  Read Safety Warning  on page 6  before using this control  Disconnect the main power  when making connections to the control  To avoid electric shock be sure to properly ground control        Important Application Note  To avoid erratic operation  do not bundle the AC line and motor wires with  wires from signal following  start stop contacts  or any other signal wires  Also  do not bundle motor  wires from mul
14. 0  for the location of trimpots     24       y          Warning  If possible  do not adjust trimpots with the main power applied  If adjustments are  made with the main power applied  an insulated adjustment tool must be used and safety       glasses must be worn  High voltage exists in this control  Electrocution can result if caution is not exer   cised  Safety Warning  on page 6  must be read and understood before proceeding     Note  In order for the IR Compensation and Current Limit settings to be correct  the proper Plug In Horsepower  Resistor   must be installed for the particular motor and input voltage being used   See Section 9  on page 21  FIGURE 14    11 1 Acceleration Trimpot  ACCEL    The ACCEL Trimpot is provided to allow for a    ACCEL TRIMPOT RANGE       5  smooth start over an adjustable time period each time the AC power is applied      or the Main Speed Potentiometer is adjusted to a higher speed  The ACCEL 3n 8  Trimpot has been factory set to 2 seconds  which is the amount of time it will 2   take for the motor to accelerate from zero speed to full speed  To increase the 02    RE YA  10  acceleration time  rotate the ACCEL Trimpot clockwise  To decrease the accel   Factory Set to 2 Seconds        eration time  rotate the ACCEL Trimpot counterclockwise  See Figure 14           11 2 Deceleration Trimpot  DECEL    The DECEL Trimpot controls the amount of  ramp down time when the Main Speed Potentiometer is adjusted to a lower    speed  The DECEL Trimpot ha
15. 0 Volt AC line input with 180 Volt DC motors or 90 Volt DC motors   step down     Jumper Selectable     Model KBMM 225D can operate on 115 Volt AC line input with 90 Volt DC motors and 230 Volt AC  line input with 180 Volt DC motors or 90 Volt DC motors  step down     Jumper selectable     Armature or DC Tach Generator feedback   Built in AC line and armature fusing   Main Speed Potentiometer  5 kQ      SMT construction     TABLE 1   ELECTRICAL RATINGS                            AC Line Maximum Rating without Auxiliary Heat Sink  Maximum Rating with Auxiliary Heat Sink  Motor Field  Part Voltage AC Line DC Load AC Line DC Load  Model Voltage Voltage  No     215   50 60H2    yoyo  gt  Current Current   Horsepower   Current   Current   Horsepower  Volts a   Volts AC   RMS Amps     Avg  A  ile  Csr   UPS   ps     Avg  Amps   RMS Amps     Avg  Amps   KBMM 125   9449 115 0 90 12 0 8 0  75   6  24 0 16 0 1 5  1 1  50  100  0   180 12 0 8 0 1 5  1 1  24 0 16 0 3  2 3  100  200  KBMM 225   9450 230  0   90  12 0 8 0  75   6  24 0 16 0 1 5  1 1  100  115 0 90 12 0 8 0  75   6  24 0 16 0 1 5  1 1  50  100  KBMM 225D   9451 230 0   180 12 0 8 0 1 5  1 1  24 0 16 0 3  2 3  100  200  0   90  12 0 8 0  75   6  24 0 16 0 1 5  1 1  100                                       Step down operation   TABLE 2   GENERAL PERFORMANCE SPECIFICATIONS                                                 Description Specification Factory Setting  Speed Range  Ratio  50 1      Armature Feedback Load Regulation 
16. 0 and 90 Volt SCR rated motors  Use of motors with higher rated voltage will  result in a reduction of the available maximum speed  Also  if the motor is not an SCR rated type  the actual  AC line current at full load and full speed should not exceed the motor   s DC nameplate current rating     4 2 Torque Requirements   The motor selected for the application must be capable of supplying the necessary  torque  In order to ensure the motor is not overloaded  a DC ammeter should be connected in series with  the armature  Be sure the current under full load does not exceed the motor nameplate rating     4 3    4 4    4 5    4 6    Acceleration Start   The control contains an adjustable acceleration start feature which allows the motor to  smoothly accelerate from zero speed to full speed over a time period of 0 2   10 seconds  The acceleration  trimpot  ACCEL  is factory set for 2 seconds     Limitation In Use     The control is designed for use on machine applications     CAUTION  Consult our Sales Department before using this control on constant horsepower applica   tions such as saws and drill presses  Do not use this control in an explosive atmosphere  Be sure the  control is used within its ratings  Follow all instructions carefully     Armature Switching   Do not wire the control for armature switching without taking proper precautions   See Section 13 2  on page 29     WARNING  Do not switch the armature in and out of circuit or catastrophic failure will result  If arma  
17. AC    Armature Voltage  Volts DC  Field Voltage  Volts DC  Terminal Connections  100 F   F   KBMM 125 115 0 90  50 F   L1  0   180 200 F   F   KBMM 225 208   230  0   90  100 F   L1  100 F   F   115 0 90  50 F   L1  KBMM 225D  208   230 0   180 200 F   F   208   230 0   90  100 F   L1                        Step down operation        6 5    6 6    Remote Main Speed Potentiometer Connection     The control  is supplied with a Main Speed Potentiometer to control motor  speed  Wire the low side of the potentiometer to Terminal    P1      Wire the wiper of the potentiometer to Terminal    P2     Wire the  high side of the potentiometer to Terminal    P3     See Figure 3     Voltage Following Connection     An isolated 0   9 Volt DC ana   log signal input can be used to control motor speed in lieu of the  Main Speed Potentiometer  The control output voltage will linearly  follow the analog signal input  The signal input must be isolat   ed from the AC line  Connect the signal input positive lead     to  Terminal    P2    and the negative lead     to Terminal    P1     as  shown in Figure 4  The source impedance of the signal input  should be 10 kQ or less  The MAX Trimpot is not operational in  voltage following mode  Use the MIN trimpot to set an initial value  of input signal  If necessary  use auxiliary trimpots to scale and or  limit the input voltage     A CAUTION  Do not earth ground any input terminals     Notes  1  If an isolated signal input is not available  or if using 
18. Connection     Connect the ground wire  earth  to the control chassis     6 3    6 4    Permanent Magnet  PM  Motor Connection     Wire the motor armature positive lead     to Terminal    A       Armature Fuse  and the negative lead     to Terminal    A      as shown in Figure 1  on page 10  On Models  KBMM 225 and KBMM 225D  be sure Jumper J2 is set to the corresponding motor voltage  as described  in Section 7 2  on page 20  Be sure the correct Plug In Horsepower Resistor6 is installed  as described in  Section 9  on page 21     Motor Field Connection  Shunt Wound Motors Only     6 4 1 Full Voltage Field   Wire the field positive     lead to Terminal    F     and the negative lead     to  Terminal    F      as shown in Figure 1  on page 10  and as described in Table 4     6 4 2 Half Voltage Field   For 90 Volt DC motors with 50 Volt DC fields and 180 Volt DC motors with 100  Volt DC fields  wire the field positive lead     to Terminal    F     and the negative lead     to Terminal    L1      Line Fuse   as described in Table 4            Notes  1  Do not connect motor armature leads to Terminals    F     and    F      2  Do not use Terminals    F   and    F     for any purpose other than to power the field of a shunt wound motor  3  Shunt wound motors  may be damaged if the field remains energized without armature rotation for an extended period of time     TABLE 4   FIELD CONNECTION  Shunt Wound Motors Only                                Model AC Line Input Voltage  Volts 
19. E                 O      Factory Set to 0   of Base Speed        FIGURE 17  MAX TRIMPOT RANGE          Cy   50     KA 110     Factory Set to 100   of Base Speed        wise  To decrease the maximum speed  rotate the MAX Trimpot counterclockwise  See Figure 17     CAUTION  Do not set the maximum speed above the rated motor RPM since unstable motor    operation may occur     25          26          uy       Warning  If possible  do not adjust trimpots with the main power applied  If adjustments are  made with the main power applied  an insulated adjustment tool must be used and safety       glasses must be worn  High voltage exists in this control  Electrocution can result if caution is not exer   cised  Safety Warning  on page 6  must be read and understood before proceeding     11 5 Current Limit Trimpot  CL    The CL Trimpot sets the current limit FIGURE 18     overload   which limits the maximum current  torque  to the motor  The CL    CL TRIMPOT RANGE       also limits the AC line inrush current to a safe level during startup  The CL   7 150  Trimpot is factory set to 1 5 times the full load rating of the motor  To   increase the current limit  rotate the CL Trimpot clockwise  do not   exceed 2 times motor current rating  maximum clockwise position   I RJ 200  To decrease the current limit  rotate the CL Trimpot counterclockwise   Factory set to 150   of Full Load     See Figure 18              Note  The correct value Plug In Horsepower Resistor   must be installed for the
20. IR Comp Trimpot fully counterclockwise  Once the tach   generator is connected  the IR Comp Trimpot may be  increased for additional speed stabilization     6 9 1 Seven  7  Volt per 1000 RPM Tach Generator      Connect the tach generator positive lead     to  Terminal    T    and the negative lead     to Terminal     12     as shown in Figure 8     6 9 2 Fifty  50  Volt per 1000 RPM Tach Generator      Connect the tach generator positive lead     to  Terminal    B    and the negative lead     to Terminal     12     as shown in Figure 9     6 9 3 Other Tach Generator Voltages   The tach gener   ator input circuit is designed for a 7 Volt or 50 Volt  per 1000 RPM DC tach generator used with an  1800 RPM motor  For a tach generator other than 7  Volts or 50 Volts per 1000 RPM  or for a motor  other than 1800 RPM  an external 1 2 Watt resistor   RT  must be installed  Install RT in series with the    FIGURE 8   DC TACH GENERATOR CONNECTION   7 VOLTS PER 1000 RPM            Terminal  T                    Terminal  12        DC Tach Generator       FIGURE 9   DC TACH GENERATOR CONNECTION   50 VOLTS PER 1000 RPM           Terminal  B                    50V     1000    DC Tach Generator                   tach generator  Connect one end of RT to Terminal FIGURE 10   OTHER DC TACH GENERATOR     T     connect the other end of RT to the tach  CONNECTION   generator positive lead      and connect the negative  lead     of the tach generator to Terminal    12     See  Figure 10            
21. Installation and Operation Manual    KBMM     Surface Mount Technology    Solid State SCR  DC Motor Speed Controls    for Use with 1 100     3 HP  90 and 180 Volt  Permanent Magnet and Shunt Wound DC Motors   AC Line Input  115 and 208 230 Volts  50 60 Hz  This Manual Covers Models KBMM 125  225  225D    Ultra Fast Current Limit Circuit Prevents  Demagnetization in Permanent Magnet Motors       A See Safety Warning on page 6                                                                                                                                 amp                                            21     2       Mus  ce     See page 6    for CE  Information    PATENTED       A Plug In Horsepower Resistor   and AC Line  and Armature Fuses  supplied separately   must be installed for this product to operate               Auxiliary Heat Sink  Part No  9861  is required  to achieve maximum rating of control  See  Electrical Ratings  Table 1  on page 9           The information contained in this manual is intended to be accurate  However  the manufacturer retains the right  to make changes in design which may not be included herein     PENTA  E  POWER       Manufactured A COMPLETE LINE OF MOTOR DRIVES    2004 KB Electronics  Inc     in the USA     See back cover        TABLE OF CONTENTS       Section Page  fo SIMIPITSS  installato Instructions   senie gs ay ae EDI AA AA ae de 4  21    Safety  WANO Za rata A A A A A as eta ayn ee 6  SN teja A A O A A O soe pated i i 7  A  APICAL AOA
22. O ceso da Gs EAS AAA AN A EA 11  5  MOUNTING INStTUCIONS akioa AA A A A A A 12  VINILOS y IA AS A A A A Re NER A eee 13  T  Setting Selectable  Jumpers  ii A A LA a da la 19  8 ACLine and Armature Fusing        o  oo oococcccco ene nee tenes 20  9  Plug In  Horsepower ReSistor   ia sia bk ida edad eae Gadd la pa cid ra baa a 21  10 Recommended High Voltage Dielectric Withstand Testing  Hi Pot Testing                  0 0000000000 22  Ta APIMPOt AGIUSHINENIS di enc seit aa is e Goto ee land caches ae PEM OS RAN Aiea Pete    Hs Bort 24  12 Diagnostic EDS a A aa ee ae A AA a 28  he OWI CICUS A EN 28  14     Optional  ACCESSOrIES  gt    tae cetera sean aura db or aio deine dsc HAP De Ratton AAA 30  Limited Warranty Exts a oe Bee il LAG be  32  Tables   Ti    Electrical Ratings  ia la O A EA tale Dae e 9  2 General Performance Specifications       2 0    ec tenet ene 9  3 Minimum Supply Wire Size Requirements            0 00 ccc teen teens 13  4 Field Connection  Shunt Wound Motors Only     essea esasa aeaea 14  5 AC Line and Armature F  se Selec Mass nus arcos ene ea a ELVA USSR re eee OR EE EE ASS 21  6  Plug In Horsepower Resistor   Selection ce pans see dees eeu ay heehee SPER TIGRE ALN seb ee ea ee ee 22  T   BRA SCHON als foci dl Minas hee tad a ENE A TAGE wed ke De eae N 31    TABLE OF CONTENTS  Continued        Figures Page  1 Control Layout and General Connection Diagram usas risa rt ee AA A ai OS 10  24    Mechanical  Specifications o s cia a a SL Ea 11  3 Remote Main Sp
23. Stop                       Motor Field   Shunt Motors Only           Horsepower Resistor    Supplied Separately           TONS    Armature Fuse  Supplied Separately              For Plug In Horsepower  Resistor    Line Fuse   and Armature Fuse  Selection See Sections  8 and 9  on pages 20 22        ESS                   Motor Armature DC Tach Generator   Set J2 to  T  Position                 FIGURE 2   MECHANICAL SPECIFICATIONS  Inches mm                                                                                               MAIN SPEED OPTIONAL AUXILIARY HEAT SINK  se POTENTIOMETER cal     4    5 10   2  SUPPLIED  i ma  78 5 l   0  U U U  i    3 8  le 1 2 e  A a E    o 1 c 127  1   r MOUNTING  A   i CONTROL  6 SLOTS 1   i  MOUNTING  B  1 174  ROUND oo E S  15   TAPPED 10 32 1 SHAFT 7 00   8 PLACES    1a  3 00    4 30    762 109 Lo 3 8 32 mal    FUSE HOLDER  amp  FINGER SAFE o AN Tron BUSHING EN  150     COVER MOUNTING HOLES 126 PIN   6 6  381     TAPPED 6 32 aie 130    8     2 PLACES  546   a 14297 628 7  1   159     1 13 i  Lt 1 3 1 P3 125  o 1 25  i Y  N N i f l 95 le P P z   75 1 75  64 25 EIA 1 2  191 P 44 5 163 64 24 1     44 le 138 i  1 75   18    1 25 _  aa 34  Ped  z 445 ae 31 8 oe          4 APPLICATION INFORMATION    4 1 Motor Type   The control is designed for permanent magnet  PM  and Shunt Wound DC motors  Controls  operated on 115 Volt AC line input are designed for 90 Volt SCR rated motors  Controls operated on 230 Volt  AC line input are designed for 18
24. Table 5     8 1 AC Line Fuse   The AC Line Fuse protects the  control against catastrophic failure  If the AC Line  Fuse blows  the control is miswired  the motor is  shorted or grounded  or the control is defective     Note  Fuse each AC line conductor that is not at  ground potential     8 2 Armature Fuse   The Armature Fuse provides  overload protection for the motor and control  The  Armature Fuse required can be calculated by multi   plying the maximum DC Motor Current times 1 7     PLUG IN HORSEPOWER RESISTOR      TABLE 5   AC LINE  amp  ARMATURE FUSE SELECTION       Recommended Fuse Rating                                                       90   130 Volt 180 Volt  DC Motors DC Motors  Amps     HP   HP  AC Line Armature  1 100     1 50 1 50     1 25 12 1 3  1 50     1 30 1 25 1 15 12 1 2  1 30     1 20 1 15   1 10 12 3 4  1 20   1 12 1 0   1 6 12 1h  1 12   1 8 1 6     1 4 12 2   1 8   1 5 1 4   1 3 12 24   1 4 1 2 12 4   1 3 3 4 12 5   1 2 1 12 8   3 4 1  12 12   1  2  15 15   1  3  25 25   ed to    Plug In Horsepower Resistor     A Plug In Horsepower Resistor    supplied separately  must be insta  match the control to the motor horsepower and voltage  Plug In Horsepower Resistors   are available from your  distributor  Install the Plug In Horsepower Resistor    as shown in Figure 1  on page 10  Select the correct Plug In    Horsepower Resistor   as shown in Table 6  on page 22           Application Notes  1  The Plug In Horsepower Resistor   is used to calibrate the
25. Trimpot 3 6      may be set to a minimum level  approximately 1 4 of 0    REY     24  48  full clockwise rotation   The IR Trimpot is factory set  Factory set to 3 Volts DC for controls with 90 Volt DC Output   to provide 3 Volts of compensation for controls with  Factory set to 6 Volts DC for controls with 180 Volt DC Output   90 Volt DC output and 6 Volts of compensation for             controls with 180 Volt DC output  To increase the  amount of compensating voltage  rotate the IR Trimpot clockwise  To decrease the amount of compensating  voltage  rotate the IR Trimpot counterclockwise  See Figure 19     Notes  1  The correct value Plug In Horsepower Resistor   must be installed for the IR Compensation to  operate properly  Calibration of the IR Trimpot is normally not required when the proper Plug In Horsepower  Resistor   is installed  2  Excessive IR Compensation will cause the motor to become unstable  which caus   es cogging  3  For tach generator feedback applications  set the IR Trimpot fully counterclockwise  See  Section 6 9  on page 18     To Recalibrate the IR Trimpot     1 Set the IR Trimpot to approximately 25   rotation   27       Y 4 Warning  If possible  do not adjust trimpots with the main power applied  If adjustments are    made with the main power applied  an insulated adjustment tool must be used and safety  glasses must be worn  High voltage exists in this control  Electrocution can result if caution is not exer   cised  Safety Warning  on page 6  mus
26. URE 13   HI POT TEST SETUP    High Voltage Dielectric Withstand Tester  Hi Pot Tester                                       RETURN TEST VOLTAGE     e an ta  HV  RESET     Connect all Speed Control      O 1     Aj terminals together  ZERO MAX  7 Motor Speed Control  AC Line input          Motor Wires        Connect Hi Pot Tester  to both  AC Line inputs       Auxiliary Equipment        Chassis                         Machine or  equipment frame          10 1 Connect all equipment AC power input lines together and connect them to the H V  lead of the Hi Pot Tester   Connect the RETURN of the Hi pot Tester to the frame on which the control and other auxiliary equipment    are mounted   23    10 2 The Hi Pot Tester must have an automatic ramp up to the test voltage and an automatic    ramp down to zero voltage     Note  If the Hi Pot Tester does not have automatic ramping  then the hi pot output must be manually  increased to the test voltage and then manually reduced to zero  This procedure must be followed for each  machine to be tested  A suggested Hi Pot Tester is Slaughter Model 2550     CAUTION  Instantaneously applying the hi pot voltage will cause irreversible damage to the control     11 TRIMPOT ADJUSTMENTS   The control contains trimpots which have been factory set for most applications  Some applications may require  readjustment of the trimpots in order to tailor the control for a specific requirement  Readjust the trimpots as  described below  See Figure 1  on page 1
27. a  4   20 mA DC signal input  install the optional plug on SI 6 Signal  Isolator  Part No  9444   This will also allow direct connections to  process controllers and microprocessors  2  If multiple follower  motors are to be controlled from a single lead motor or a single  Main Speed Potentiometer  install the optional KBSI 240D Signal    FIGURE 3   REMOTE MAIN SPEED  POTENTIOMETER CONNECTION          Terminal  P3           Terminal  P2                 Terminal  P1     Main Speed Potentiometer   Front View           FIGURE 4   VOLTAGE FOLLOWING  CONNECTION          Terminal  P2                          Terminal  P1        v 0  9 Volts DC   Isolated              Isolator  Part No  9431   3  Terminal    F     may be used in lieu of Terminal    P1        6 7 Enable Circuit Connection   The control can be started and stopped with an Enable Circuit  close to run   open to stop   as described below     6 7 1    6 7 2    WARNING  The Enable Circuit is never to be used as a Safety Disconnect since it is not  fail safe  Use only the AC line for this purpose     Enable Switch or Contact Wired to the Enable Connector   Using the wired mating connector that  is supplied with the control  wire the switch or contact to the Enable connector  CONN1   as shown in  Figure 5  When the switch or contact is closed  the motor will accelerate to the Main Speed  Potentiometer setting  When the switch or contact is opened  the motor will decelerate to stop  An  open collector  PNP  can be wired in li
28. cover      DIN Rail Mounting Kit  Part No  9995     KBAP 240D Current Sensing Overload Protector  Part No  9106    Provides overload current sensing  and protection of DC motors and speed controls rated 1 8   3 HP by sensing armature current  Operates  on 115 or 230 Volt AC line input     14 10 KBEP 240D Electronic Potentiometer  Part No  9108    Provides digital type control of motor speed   Replaces a standard rotary potentiometer with a set of customer supplied momentary push buttons or    membrane switches  Operates on 115 or 230 Volt AC line input     14 11 KBET 240D Electronic Tachometer  Part No  9469    Provides an isolated tack feedback signal and an  isolated voltage follower signal from an open collector  Hall  magnetic  inductive  optical  or 2 wire inductive    pickup  encoder   Operates on 115 or 230 Volt AC line input    14 12 RFI Filters   Provide RFI and EMI suppression  Complies with CE Council Directive 89 336 EEC relating to  the Class A Industrial Standard and Class B Residential Standard  Filters are available in remote or under     mount types  See Table 7     TABLE 7   RFI FILTER SELECTION                                  Model Part No  Somer Mounting Class  KBRF 200A 9945C 24 Remote A   Industrial  KBRF 250 9509 10 Undermount A   Industrial  KBRF 300 9484 16 Remote B   Residential    KBRF 350 9511 10 Undermount B   Residential           Also meets Industrial Standard     31          LIMITED WARRANTY    For a period of 5 years from the date of original
29. eed Potentiometer Connectlon ok ba ee Pa eae cae 15  AY NGAGE POMO WI CONTEO oras ak ES AAA MEY Ral aterm E agii 15  5 Enable Switch or Contact Wired to the Enable Connector          00    eee 16  6 Enable Switch or Contact Wired to the Main Speed Potentiometer          0 0 0 0  eee eee 17  7 Inhibit Switch or Contact Wired to the Inhibit Terminals      0    sses asnes eee 17  8 DC Tach Generator Connection  7 Volts per 1000 RPM            0  ccc eects 18  9 DO Tach Generator Connection  50 Volts per 1000 RPM  ansiada re AD A 18  10 Other DC Tach Generator Connection  with Addition of RT     0 0    eect eee 19  11 AC Line Input Voltage Selection  Jumper J1  Model KBMM 225D Only      0 02    eee eee 20  12 Motor Voltage and DC Tach Generator Selection  Jumper J2  2    eee 20  The TEP OR Test Sep as A AA es seek eee Pedal aoa Seg bee eae 23  14  Acesielation Timpot  ACCEL RANGE is ar aan aa Lee O O AUN 24  15  Deceleration Thmpor  DECGEL  RANGE src tab add ad cd e pda ORS 25  10  MINIT Speed  Timp  t  MIN  Rate as sa ri A AAN E AAA 25  17 Maximum Speed Trimpot  MAX  Range coat E A AI ata ora 25  18  Ourrent  Limit Irimpot  CH Range anen da 26  19 IR Compensation Trimpot  IR  Range        0    cette DEAL E EA 27  20     Typical Dynamic Brake Circuit  Connections rss ex eae be EA ESA A e ei 29    Items Included in this package   KBMM    Speed Control  KBMM    Installation and Operation Manual  Hardware  Bag  contains Main Speed Potentiometer with insulator and mounting hardware  
30. eu of a switch or contact     Notes  1  To use  the Enable Circuit     FIGURE 5   ENABLE SWITCH OR CONTACT WIRED TO THE ENABLE CONNECTOR       remove the jumper Remove this jumper to install  that is factory the Mating Connector  installed on   CONN1  2  The                     deceleration time Enable Switch    Open Collector    can only be made or Contact  On to Run   longer than the  Close to Run   Off to Stop    Open to Stop     normal coasting  time of the load                 Enable Switch or Contact Wired to the Main Speed Potentiometer     Wire the switch or contact in  series with the Main Speed Potentiometer high side and Terminal    P3    on the control  as shown in  Figure 6  on page 17  Be sure the jumper is installed on the Enable Connector  CONN1   When the  switch or contact is closed  the motor will accelerate to the Main Speed Potentiometer setting  When  the switch or contact is opened  the motor will decelerate to the MIN Trimpot setting  factory set to O    6 8    Volts DC   If the MIN  Trimpot is set to other    FIGURE 6   ENABLE SWITCH OR CONTACT WIRED TO THE  MAIN SPEED POTENTIOMETER       than O Volts DC  the  motor will run at that  speed when the  switch or contact is  opened  An open col   lector  PNP  can be  wired in lieu of a  switch or contact                 This jumper must  be installed    Enable Switch or Contact   Close to Run    Open to Stop        Note  The decelera    tion time can only be  made longer than the  normal coasting time    
31. ial hazard  Proper shielding  grounding  and filtering of this product  can reduce the emission of radio frequency interference  RFI  which may adversely affect sensitive electronic  equipment  It is the responsibility of the equipment manufacturer and individual installer to supply this Safety  Warning to the ultimate end user of this product   SW effective 11 1992   Be sure to follow all instructions care   fully  Fire and or electrocution can result due to improper use of this product     Y  y                      This product complies with all CE directives pertinent at the time of manufacture  Contact the Sales  C     Department for Declaration of Conformity  Installation of a CE approved RFI filter is required  see  Section 14 12  on page 30   Additional shielded cable and or AC line cables may be required along with a sig   nal isolator  SI 6  Part No  9444                3    INTRODUCTION   Thank you for purchasing the KBMM       Standard of the Industry    full wave variable speed DC motor control  now  with SMT construction  The control offers the user the ultimate in reliability and performance at an affordable  price  The controls contain a unique patented super fast Direct Fed    current limit circuit that protects the SCR  power bridge against direct shorts     The reliability of the control is further enhanced with the use of high surge  25  Amp SCRs  and AC line and armature fusing2 3  The control is designed with KB   s exclusive Plug In Horsepower  Resistor 
32. n Figure 1  on page  10  The trimpots may be readjusted  as described in Section 11  on page 24     Diagnostic LEDs   After power has been applied to the control  observe the LEDs to verify proper control  operation  as described in Section 12  on page 28     1 10 Auxiliary Heat Sink  Part No  9861    Extends the horsepower rating of the control to 1 5 HP for controls    with 90 Volt DC output and 3 HP for controls with 180 Volt DC output     2 SAFETY WARNING   Please read carefully   Definition of Safety Warning Symbols        y y Electrical Hazard Warning Symbol   Failure to observe this warning could result in electrical shock    or electrocution              Operational Hazard Warning Symbol   Failure to observe this warning could result in serious injury  or death           This product should be installed and serviced by a qualified technician  electrician  or electrical main   tenance person familiar with its operation and the hazards involved  Proper installation  which includes  wiring  mounting in proper enclosure  fusing or other over current protection  and grounding can reduce the  chance of electrical shocks  fires  or explosion in this product or products used with this product  such as elec   ric motors  switches  coils  solenoids  and or relays  Eye protection must be worn and insulated adjustment tools  must be used when working with control under power  This product is constructed of materials  plastics  metals   Carbon  silicon  etc   which may be a potent
33. s been factory set to 2 seconds  which is the    amount of time it will take for the motor to decelerate from full speed to zero  speed  To increase the deceleration time  rotate the DECEL Trimpot clockwise        To decrease the deceleration time  rotate the DECEL Trimpot counterclock   wise  See Figure 15     Note  The deceleration time cannot be made less than the natural coast time    of the motor and actual load     11 3 Minimum Speed Trimpot  MIN      The MIN Trimpot sets the minimum  speed of the motor when the Main Speed Potentiometer is set fully coun   terclockwise  The MIN Trimpot is factory set to O   of base motor speed   To increase the minimum speed  rotate the MIN Trimpot clockwise  To  decrease the minimum speed  rotate the MIN Trimpot counterclockwise   See Figure 16     Note  Readjusting the MIN Trimpot will affect the maximum speed set   ting  Therefore  it is necessary to readjust the MAX Trimpot if readjusting  the MIN Trimpot  It may be necessary to repeat these adjustments until  both the minimum and maximum speeds are set to the desired levels     11 4 Maximum Speed Trimpot  MAX    The MAX Trimpot sets the maximum  speed of the motor when the Main Speed Potentiometer is set fully  clockwise  The MAX Trimpot is factory set to 100   of base motor  speed  To increase the maximum speed  rotate the MAX Trimpot clock     FIGURE 15  DECEL TRIMPOT RANGE          5       3  8       02    RKR_Y  10     Factory Set to 2 Seconds        FIGURE 16  MIN TRIMPOT RANG
34. t be read and understood before proceeding              2 Run the motor unloaded at approximately 1 3 speed and record the RPMs     3 Run the motor with the maximum load and adjust the IR Trimpot so that the motor speed under load  equals the unloaded speed recorded in step 2     4 Remove the load and recheck the RPMs     5 If the unloaded RPM has changed  repeat steps 2   4 for more exact regulation  The control is now  compensated to provide minimal speed change due to changing loads     12 DIAGNOSTIC LEDs  The control is designed with PC board mounted LEDs to display the control s operational status  See Figure 1  on    page 10  for the location of the LEDs   12 1 Power On  PWR ON    The PWR ON LED will illuminate green when the AC line is applied to the control     12 2 Current Limit  CL    The CL LED will illuminate red when the control goes into current limit  indicating that  the current limit set point has been reached  set by the CL Trimpot   See Section 11 5  on page 26     13 SWITCHING CIRCUITS    13 1 AC Line Switching   The control can be turned    on    and    off    using the AC line  no waiting time is  required   Auto Inhibit   circuitry automatically resets critical components each time the AC line is interrupted   This  along with Acceleration Start and CL  provides a smooth start each time the AC line is applied     28    WARNING  Do not disconnect and reconnect the motor armature with the AC line applied or cata   strophic failure will result  See Section
35. tiple controls in the same conduit  Use shielded cables on all signal wiring over 12     30  cm   The shield should be earth grounded on the control side only  Wire the control in accordance with  the National Electrical Code requirements and other local codes that may apply     TABLE 3   MINIMUM SUPPLY WIRE SIZE REQUIREMENTS                                   Minimum Wire Size  Cu   rai ce 90 i E Ma ak on ies Maximum 50 Ft  Maximum 100 Ft   AWG mm2 AWG mm   6 5 1 16 1 3 14 2 1  12 1 2 14 21 12 3 3  16 1 5 3 12 3 3 12 3 3                      6 1 AC Line Connection     Wire the AC line to Terminals    L1     Line Fuse  and    L2     as shown in Figure 1  on  page 10  If one of the AC line inputs is a neutral  N   wire it to Terminal    L2        CAUTION  The rated AC line voltage  115  208 230  of the control must match the actual AC line  input voltage  See Section 7 1  on page 19     Model KBMM 125 operates on 115 Volt AC line input only  Model KBMM 225 operates on 208 230 Volt AC    line input only  Model KBMM 225D operates on 115 Volt AC line input when Jumper J1 is set to the    115     position and operates on 208 230 Volt AC line input when Jumper J1 is set to the    230    position     AC Line On Off Switch   To remove power to the control  a separate AC line switch should be used  Use a    single pole switch for hot and neutral AC supply lines and a double pole switch for 2 hot AC supply lines   This switch can also be used as a    Safety Disconnect        6 2 Ground 
36. tors  To set Models KBMM 225  225D for  step down operation  208 230 Volt AC line input and S      90 Volt DC output   set Jumper J2 to the    90    posi  S   tion   To set the control for tach generator connection  al  set Jumper J2 to the    T    position  all models   See  Figure 12                 Notes  1  On Model KBMM  125  the    180    position is not available on Jumper J2  2  On Model KBMM   225D  do not set the output voltage to 180 Volts DC when the AC line input is set to 115 Volts     FIGURE 12   MOTOR VOLTAGE  amp  DC TACH GENERATOR SELECTION  JUMPER J2              Model KBMM 125 Models KBMM 225 and KBMM 225D  J2 Set for J2 Set for  oa a USO Wels Lisi Sie Sgt   Factory Setting   Factory Setting    S 5 5 S S  281  A  121    fe   iH  sip  Al sp sif  Pii  5   sl Sigl sifel                     Be sure jumper for 90 Volt DC output is installed in the two center pins  as shown     AC LINE AND ARMATURE FUSING   All fuses should be normal blow ceramic 3AG  MDA  or equivalent  On domestic 230 Volt AC lines  separate  branch circuit protection for each line must be used  The optional Barrier Terminal Board  Part No  9897  contains  prewired AC line and armature fuse holders  as described in Section 14 3  on page 30        An AC Line Fuse  supplied separately  must be installed  in the AC line Fuse Holder and an Armature Fuse  sup   plied separately  must be installed in the Armature Fuse  Holder  as shown in Figure 1  on page 10  Select the  correct fuses  as shown in 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Programming - Subalpina Vending  - AirOil.com    INSTRUCTION MANUAL M  Otterbox RBB2-PLYBK-20-E4OTR  Audiovox PRO-9051 User's Manual  VH-BS075SL Manual de usuario User Manual Manual de  Using the Reports Module - Douglas County School System  ASUS BP1AE DA8100 User's Manual  MANUEL D`UTILISATION DU SITE INTERNET (PUBLIER) • Chapitre    Copyright © All rights reserved. 
   Failed to retrieve file