Home
        View/Open - Oregon State University
         Contents
1.                PUC_TORT  CEREN  isplay   CHI   i     Clock Operation Filter    ane Offset en    Figure 5 29  AWG test setup     three phase 480Hz capacitor switching transient     5       i I     Figure 5 30  Output of programmable source     three phase 480Hz capacitor switching transient     65    5 3 2  11kVA ASD  Internal Power Supply from DC Bus    This test setup consisted of an 11kVA  460V line to line  ASD supplying a four pole  10hp  induction motor  The rest of the test setup remained the same as in the previous two ASD ride   through tests  Similar to the 5 5kVA ASD with internal power supply from the dc bus  most of  the ASD configurations and settings were kept to the factory preset conditions  The same  operating parameters were changed as in the 5 5kVA ASD test setup     5 3 2 1 9596 Single Phase Voltage Sag    Table 5 11 shows the results of the 95  single phase voltage sag test  For the three load  conditions  the ASD did not trip offline  For the test at full load  the ASD input voltage  current  and dc bus voltage are shown in Appendix E  It can be seen that during the voltage sag  the  ripple voltage on the dc bus increases and the motor load speed reduces slightly  The results are    very close to the 5 5kVA ASD 90  and 100  single phase voltage sag results     Table 5 11  95  single phase voltage sag results                 100  Load    AppliedTorque Nm        0   2   4    Speed  during sag     Reduction    5 3 2 2 100  Single Phase Voltage Sag    Table 
2.    V    2662120     V    450V rms  636V peak     Table 5 2  Data from a 5  single phase sag               Description of Input Current in N A Single pulsed Largely unbalanced   Sagged Phase two pulsed    5 2 2 1 No Load                 Similar to the case for a 2  single phase voltage sag  a 5  single phase voltage sag on phase     a    during a no load condition results in the sagged phase current dropping out  At no load  the    sagged phase current drops out for any single phase voltage sag with a magnitude greater than  2      5 2 2 2 50  Load    For a 5  single phase voltage sag on phase    a     the input current drawn during a 50  load  condition is shown in Fig  5 9  The current in phase    a     sagged phase  has reduced to a single  pulse pattern  This is because the average dc bus voltage at 50  load  636 6V  is very close to  the peak value of the sag affected line to line voltage  636V   Since the average dc bus voltage is  636 6V  taking the ripple into account  the minimum voltage is less than 636V and the maximum  voltage is greater than 636V  Again  current pulse i   Va  is the highest and the dc bus voltage is  charged to its peak value  The next current pulse  i   Va   has dropped out because the dc bus    46    voltage has not yet discharged below 636V  The following current pulse  i   Vac  is lower  because Vac is sagged  636V   The next current pulse  i   Vi   is again the highest current pulse  since Vy  is not sagged  In this load condition  the double
3.   00 i i  600  09 0  00000 0  02000 0  04000 0  06000 0  08000 0 10000    Seconds    Figure 5 3  ASD dc bus voltage  2  single phase sag  no load  at 0 02 seconds      i   MJ    not shown     i   X         L  X        0 00000 0 02000 0 04000 0 06000 0 08000 0 10000    Seconds    Figure 5 4  Input current  2  single phase sag  no load  phases    a    and    c    shown           E de bus       average    656 25          637 50 1   A  637 50   n   618 75  618 75             N Y    4     603  ag 0 00000 0 02000 0 04000 0 06000 0 08000 0 10000    Seconds    Figure 5 5  ASD dc bus voltage  2  single phase sag  50  load     i   X   not shown     i   Wa      not shown     i  V  da  Me         10 789    13    JL    i i e   J T      0 00000 0 02000    12       0 04000 0 06000 0 08000 0 10000    Seconds    Figure 5 6  Input current  2  single phase sag  50  load  phases    a    and    c    shown             dc bus    average  Los SEEN os ria        6 a  60 jo  20 0 00000 0 02000 0 04000 0 06000 0 08000 0 10000    Seconds    Figure 5 7  ASD dc bus voltage  296 single phase sag  full load            l NW A ll    nn     Figure 5 8  Input current  2  single phase sag  full load  phases    a    and    c                15 714          c  shown      45    5 2 2  5  Single Phase Voltage Sag    For a 5  single phase voltage sag on phase    a     the corresponding input phase and line to line  voltages are     V    25320         450V rms  636V peak   V   2662240    V     460V rms  650V peak   5 2
4.   13  single phase sag  50  load     51       0 00000 0 02000 0 04000 0 06000 0 08000 0 10000 7    Seconds    Figure 5 14  Input current  13  single phase sag  full load     5 2 5  17  Single Phase Voltage Sag    For a 17  single phase voltage sag on phase    a     the corresponding input phase and line to     line voltages are     V   22120    V    422V rms  597V peak   V   2662240    V    460V rms  650V peak   5 5   V   2662120    V    422V rms  597V peak     Table 5 5  Data from a 17  single phase sag              100  Load  ENE s       N  Description of Input Current in N A N A N A  Sagged Phase             52    5 2 5 1 5096 Load    For a 17  single phase voltage sag on phase    a     the input current drawn during a 50  load  condition is shown in Fig  5 15  Again  the input current on the sagged phase has completely  dropped out and only two of the six line to line voltage pulses are conducting current meaning  the three phase rectifier is operating as a single phase rectifier  The average dc bus voltage    during the voltage sag  636 1V  is higher than the peak sagged line to line voltage  597V      5 2 5 2 100  Load    The input current for a 17  single phase voltage sag on phase    a     during a 100  load  condition is shown in Fig  5 16  The current drawn by the sagged phase now has completely  dropped out and the three phase rectifier is operating as a single phase rectifier  The average dc   bus voltage during the voltage sag  620 7V  is much higher than the pea
5.   4 12     In the case of an unbalanced voltage sag  the motor terminal voltages are significantly less  affected than the supply terminal voltages  and the unbalance is dependent on the size of the dc   bus capacitor and the motor speed  The motor voltages for a dc bus voltage V   t  are the product    of the required motor voltage and the per unit dc bus voltage     V   V  t  XV  cos 22f 1   V    V   t  XV  cos 27f t     120     4 13   V      V   t  XV  cos 2zf  t   120       If the motor frequency is not equal to the system frequency  the ripple in the dc bus voltage is not  synchronized with the motor voltages  possibly leading to unbalances and interharmonics in the  motor terminal voltages  It was shown in  2   that for most unbalanced voltage sags  even a  small dc bus capacitance significantly reduces voltage unbalance and the motor frequency only  contributes to voltage unbalances and interhamonics over a small range  Therefore  it is  reasonable to assume that in most cases of voltage unbalance at the supply terminals  the voltage  at the motor terminals is relatively balanced  especially for ASDs with larger dc bus capacitances   The calculations for motor slip with balanced voltage sags are then still applicable for unbalanced  voltage sags  In cases where there is a serious voltage unbalance at the motor terminals  the  motor slip approximation should be calculated with positive sequence voltages  In general  the  affect of unbalanced voltage sags on motor speed 
6.   5 16 65  single phase voltage sag  phase    a     regular configuration  st 69  5 17 100  single phase voltage sag  phase    a     regular configuration  70  5 18 30  two phase voltage sag  phases    a    and    b     regular configuration  71  5 19 20  two phase voltage sag  phases    b    and    c     regular configuration     71  5 20 20  three phase voltage sag  regular configuration a  12  5 21 50  two phase voltage sag  phases    b    and    c     modified configuration        72  5 22 30  three phase voltage sag  modified configuration    LLL 73  5 23 Summary of ASD Ride Through Results 75    LIST OF APPENDICES    Page   Appendix A     Procedure to Operate Program AWG      LLL 87  Appendix B     LabVIEW Individual Function Blocks LLL 93  Appendix C     LabVIEW Instrument Driver Profile Blocks  Ls 95  Appendix D     Procedure to Create New Instrument Driver Profile Blocks ose  105  Appendix E     ASD Ride Through Characterization Figures ooo eee eee cee 109  El  11kVA ASD   Internal Power Supply Derived from DC Bus    109   E2  5 5kVA ASD   Internal Power Supply Derived from 1 Phase Transformer      114   E3  5 5kVA ASD   Internal Power Supply Derived from 3 Phase Transformer    122    LIST OF APPENDIX FIGURES    Figure  C1 1 Front panel window for Query Internal Memory profile block  C2 1 Front panel window for Upload All Waveform Files profile block  C3 1 Front panel window for Upload Waveform File profile block  C4 1 Front panel window for Upload All Sequence Equat
7.   Square D  ALTIVAR 58 Adjustable Speed Drive Controllers Installation Guide  Bulletin  No  VVDED397048US  Revision 4  April 1999     Jose L  Duran Gomez  Prasad N  Enjeti and Byeong O  Woo     Effect of Voltage Sags on  Adjustable Speed Drives     A Critical Evaluation and An Approach to Improve its  Performance     IEEE APEC Conference  pp  774 780  June 1999     Powerex  Inc   Three Phase Diode Bridge Modules  ME701603 Datasheet     Mark McGranaghan     Power Quality Standards  An Industry Update     Power Quality  Assurance  vol  12  no  3  pp  34 40  March 2001     43     44     45     46     47     48     49     85    Doug Dorr     Resolving Voltage Problems with AC Induction Motors   Power Quality  Assurance  vol  12  no  3  pp  41 45  March 2001     J  Duncan Glover and Mulukutla Sarma  Power System Analysis and Design  PWS  Publishing Company  1994     E  R  Collins  Jr  and R  L  Morgan     A Three Phase Sag Generator for Testing Industrial  Equipment   JEEE Transactions on Power Delivery  vol  11  no  1  pp  526 532  January  1996     Abdurrahman Unsal  4 DSP Controlled Resonant Active Filter for Current Harmonic  Mitigation in Three Phase Power Systems  Ph D  thesis  Oregon State University  2000     Marcel Merk  Active Power Filter for the Cancellation of Harmonic Line Current  Distortion  M S  thesis  Oregon State University  2000     Christopher J  Melhorn  Aubrey Braz  Peter Hofmann  and Ralph J  Mauro     An  Evaluation of Energy Storage Techniques for Improv
8.   phase to phase voltages is not affected  the dc bus voltage is able to maintain a voltage above  typical undervoltage trip levels  Therefore  under no condition will the dc bus voltage of an ASD  fall below the undervoltage trip point due to a single phase voltage sag  The reason then  that  ASDs trip offline during single phase voltage sags has to do with the internal power supply and  other external circuits that interface with an ASD to control its functions and operations  In many  cases  the internal power supply and external circuitry is powered by single phase sources that are  susceptible to single phase voltage sags  31 34   The relationship between input voltage sag  magnitude and dc bus voltage level will be analyzed in more detail in the next section     28    43  Voltage Sags and DC Bus Voltage    In some cases  ASDs trip offline due to a low voltage on the dc bus  The dc bus voltage is  maintained from the three input ac voltages through the diode rectifier  The dc bus capacitance  acts to smoothen the ripple voltage seen on the dc bus  The dc bus capacitor is charged by the  three phase rectifier six times in every cycle  Fig  4 2 shows the dc bus voltage during normal  operation for various capacitor sizes  The dc bus voltage ripple is larger for a smaller dc bus  capacitance  The solid line shows the dc bus voltage for a large dc bus capacitance  and the  dashed line shows the dc bus voltage for a small dc bus capacitance  The largest ripple voltage  shown 
9.  0   10   2    Drive Trip  Y N        With the modified ASD configuration that replaced the single phase internal power supply  transformer with a three phase transformer  it was determined that the ASD can ride through a  complete single phase voltage sag on any of the three input phases  The test results for a  complete single phase sag on any phase with the modified ASD configuration match very closely  with the results in Table 5 17     5 3 3 2 Two Phase Voltage Sags     Regular Configuration    The test results for a 30  two phase voltage sag on phases    a    and    b    supplying the ASD  are shown in Table 5 18  For the three load conditions  the ASD did not trip offline  For the test  at full load  the ASD input voltage  current and dc bus voltage are shown in Appendix E  For this  magnitude of voltage sag  the drop in speed and dc bus voltage is greater than for any magnitude  single phase voltage sag  When either a 25  or a 30  two phase voltage sag was applied to  phases  b  and  c   the ASD tripped offline due to a    control power low    error  Also  when a  50  two phase voltage sag was applied to phases    a    and    b     the ASD tripped offline due to a       control power low    error     71    Table 5 18  30  two phase voltage sag  phases    a    and    b     regular configuration                Nolo   50  Load   Applied Torque Wm    o   10       20          The test results for a 20  two phase voltage sag on phases    b    and    c    supplying the ASD  
10.  8  2001  Commencement June 2002    Master of Science thesis of Evelyn Matheson presented on June 8  2001       APPROVED     Redacted for privacy    Major Prdfessor  reprefenting Electrical and Computer Engineering    Redacted for privacy       Head of Department of Electrighl and Computer Engineering    Redacted for privacy    Dean of Grad  te School    I understand that my thesis will become part of the permanent collection of Oregon State  University libraries  My signature below authorizes release of my thesis to any reader upon  request     Redacted for privacy    7   Evelyn Matheson  Author    ACKNOWLEDGMENT    First  I would like to thank my major professor  Dr  Annette von Jouanne  for her guidance   support  and enthusiasm during the time that I have been a part of the energy systems group  I  would also like to thank Dr  Alan Wallace for providing me with the opportunity to be involved  in numerous research and testing projects in the MSRF  I would also like to thank the other  members of my program committee  Dr  Molly Shor and Dr  Roger Graham    I would like to express my gratitude to the American Association of University Women  Educational Foundation for substantially funding my first year of graduate studies through a  Selected Professions Fellowship    I would like to thank energy systems group my fellow peers in the who have given me much  assistance  motivation  and friendship during the past several years  especially Manfred Dittrich   Richard Jeffryes  An
11.  Commercial Facilities     Power Quality  Assurance  vol  11  pp  48 54  July August 2000     Mark McGranaghan and Jeff Smith     Controlling Harmonics on the Distribution  System     Power Quality Assurance  vol  11  pp  40 44  May June 2000     William E  Brumsickle  Robert S  Schneider  Glen A  Luckjiff  Deepak M  Divan  and  Mark F  McGranaghan     Dynamic Sag Correctors  Cost Effective Industrial Power Line  Conditioning     IEEE Transactions on Industry Applications  vol  37  no 1  pp  212 217   January February 2001     Square D  REACTIVAR Power Quality Protection  www squared com     Behlman Electronics Inc   Operating Manual  PA Plus Series AC Power Source   Revision B  July 1996     Jaye Killian     Using the AWG2005 with the Behlman PA Plus Series Amplifiers     June  1999     IOtech Inc   PowerVista 312 User s Manual  August 1998   Sony Tektronix Corporation  User Manual  AWG2005 Arbitrary Waveform Generator   National Instruments Corporation  LabVIEW User Manual  January 1998     Sony Tektronix Corporation  Programmer Manual  AWG2000 Series Arbitrary  Waveform Generator  1994     29     30     31     32     33     34     35     36     37     38     39     40     41     42     84    Annette von Jouanne and Ben Banerjee     Ride Through Alternatives for AC and DC  Drives Including Medium Voltage Multi Level Inverters     PQA Conference  May 2000     Math H  J  Bollen and Lidong D  Zhang     Analysis of Voltage Tolerance of AC  Adjustable Speed Drives for Three Phas
12.  Table 5 20  20  three phase voltage sag  regular configuration              No Load    L       MeasuredParameter     T NoLoad T ss Load    100 Load_     AplidToqe N          0   0    20    Speed  during sag     Reduction 1798  0 0     5 3 3 4 Two Phase Voltage Sag     Modified Configuration    The test results for a 5096 two phase voltage sag supplying the ASD are shown in Table 5 21   This two phase voltage sag was applied to phases    b    and    c    under the modified configuration  which has improved the ride through capability of the ASD and prevented it from tripping offline  due to a  control power low  error for the three load conditions  For the test at full load  the ASD  input voltage  current and dc bus voltage are shown in Appendix E  The drop in speed and dc   bus voltage is greater than for any of the two or three phase voltage sags tested in the previous  sections  Under the full load condition  the average dc bus voltage falls to 73  of its nominal  value  The speed of the motor during the voltage sag also decreased by a significant amount     dropping by over 4  from its nominal value     Table 5 21  50  two phase voltage sag  phases    b    and    c     modified configuration                Applied Torque Nm      0   1    20    Drive Trip  Y N        73    5 3 3 5 Three Phase Voltage Sag     Modified Configuration    The test results for a 30  three phase voltage sag supplying the ASD are shown in Table  5 22  The modified configuration has improved the r
13.  a subsystem VI in the Load All Channels profile  block     102    12  Set AWG Operation Mode    error out error in  no error        Figure C12 1  Front panel window for Set Operation Mode profile block     The Set Operation Mode profile block selects the output file operation mode of the AWG     The options are     e Continuous Mode    e Waveform Advance Mode    Continuous Mode is used when waveform files are loaded into channels 1 through 4 and a  continuous repetition of the waveform files is desired  common for simulating steady state  conditions   Waveform Advance Mode is used when sequence files are loaded into channels 1  through 4  The first waveform in each sequence file is repeated continuously and the following  waveforms are executed in consecutive order when the trigger is pushed or started  When the last  waveform in the sequence file has been executed  the first nominal waveform is again repeated    continuously  Waveform Advance Mode is commonly used to simulate transient conditions     103    13  Set AWG Channel Output    error in  no error     Copy to Filepath    Hard Copy To     selected port Continuous mode Master Running  computer       Figure C13 1  Front panel window for Set Channel Output profile block     The Set Channel Output profile block turns the output of the four AWG channels    on    or     off     For all testing configurations  the output of channels 1  3  and 4 should be turned    on     as  is shown in Fig  C13 1  when using the AWG to pro
14.  conditions  the ASD did trip offline  nearly immediately due to an undervoltage error  The 50  load and full load tests were  performed with and without the    regenerate the kinetic energy from the machine inertia     parameter set and in all cases the ASD immediately tripped offline  For the test at no load  the  ASD input voltage  current and dc bus voltage are shown in Appendix E  Again  the increase in    the ripple voltage on the dc bus and the decrease in motor load speed are more dramatic than for    67    the single phase voltage sags and the results are similar to the 5 SkVA ASD 50  three phase    voltage sag results     Table 5 14  50  three phase voltage sag results                  Applied Torque Nm    o         2      4      Speed  during sag     Reduction               5 3 2 5 Three Phase Capacitor Switching Transient    The capacitor switching transient test was also performed on the 11kVA ASD  The output  voltage of the programmable source recorded at the input of the ASD as well as the input current  and dc bus voltage waveforms are shown in Appendix E  Again  the peak phase voltage value of  the transient was approximately 450V  The ASD was not at all affected by the capacitor  switching transient  under all load conditions  The dc bus voltage and the motor speed were both  maintained at their normal levels  similar to the 5 5kVA ASD capacitor switching transient test    results     5 3 3  5 5kVA ASD  Internal Power Supply from AC Input    The test setup c
15.  have been inserted and wired together  parameter ranges   default values  and help files can be created  In the front panel window  by right clicking on any  parameter  a written description can be given  default value set  and range of possible inputs  specified    A new profile block VI should be saved as a  vi file in same directory as the subVIs contained  within the profile block  Currently  the AWG005 instrument driver library is located at    C  Program Files National Instrument LabVIEW  Instr lib Tek2005  Additional detail on the LabVIEW programming environment and the construction of instrument  driver VIs is provided in the LabVIEW User Manual  Additional detail on the AWG2005  command syntax and processing conventions is provided in the AWG2000 Series Programmer    Manual     109    APPENDIX E  ASD RIDE THROUGH CHARACTERIZATION FIGURES    1  11kVA ASD   Internal Power Supply Derived from DC Bus    MAU                  v        0 00000 0 02000 0     0 10000    Figure E1 1  ASD input voltage   95  single phase voltage sag           E1          Zone      489 00   gt   432  0C 0 00000 0 03799 0 07599 0 11398 0 15198 0 18997    Figure E1 3  ASD dc bus voltage     full load     110       i   oomed      0 00000 0 01799 0 03599 0 05398 0 07198 0 08997       i A S N om    6 60   0 00000 0 02245 0 04490 0 06734 0 08979 0 11224    Seconds    Figure E1 6  ASD dc bus voltage     full load        4    355 00      cored   gt   355 00 0 00000 0 04474 0 08948 0 13422 0 17896 0 223
16.  high impedance at its tuned  frequency  thereby blocking the flow of harmonic currents into the power system  Passive filters  must be carefully designed and derated to allow for harmonics also absorbed from the power  system as well as possible resonance problems with power factor correction capacitors  Active  filters monitor the load current to be filtered and use pulse width modulation inverter technology  to inject compensating current equal to the load harmonic current  but with the opposite phase  in  order to cancel the harmonic currents flowing in the power system  Hybrid filters use a  combination of both passive and active filters to cancel load harmonics with the goal of reducing    initial costs and component rating requirements enabling their use for high power nonlinear loads     14  Research Project    With the increased attention on high efficiency and controllability of industrial processes  as  well as reduced weight  volume and cost of consumer products  the applications of power  electronic converters such as adjustable speed drives  ASDs   switch mode power supplies  and  programmable logic controllers  PLCs  are showing a rapid rise  Investigating and mitigating  power quality issues pertaining to the input supply of power electronic equipment are extremely    important in maintaining a high level of reliability and productivity  In response to these    1 5  Organization of Thesis    The thesis is organized according to the following description of cha
17.  link PWM Inverter  Input 3ph  Source       Figure 4 1  Topology of an ac adjustable speed drive     26    An ASD is considered a nonlinear load because the diode rectifier front end draws non   sinusoidal current when supplied with a balanced sinusoidal input voltage  Typical ASD input    currents contain odd harmonics which can be determined by     h kg k   4 1     The order of the harmonic is A  k is an integer beginning with k 1  and q is the number of pulses  of the rectifier system  The topology of the ASD shown in Fig  4 1 has a conventional    six   pulse    rectifier because the dc bus voltage is defined by portions of the line to line input voltage  that repeat with a 60   duration  one 360   cycle contains six pulses of the input voltage   13 14    Power quality problems associated with harmonics and harmonic mitigation technologies were    discussed in Chapter 1     4 2  ASD Susceptibility    As a critical component of manufacturing processes  ASD downtime due to offline tripping  caused by power quality disturbances contributes substantially to lost productivity and revenue  for industrial customers  Voltage sags  transients  and momentary interruptions of power together  constitute 92  of the power quality problems encountered by typical industrial customers   according to a study sponsored by the Electric Power Research Institute  EPRI   in collaboration  with 24 utilities  Productivity loss due to deep voltage sags and brief power interruptions has  been calle
18.  much of the driver VI modification involved  incorporating additional functionality and changing the programming syntax that was different  between the two models  28      Action Status       Figure 3 1  Tree of AWG2041 instrument driver VIs     3 4  LabVIEW Virtual Instrument Overview    LabVIEW is a general purpose programming system with extensive libraries of functions and  development tools specifically designed for data acquisition and instrument control  LabVIEW  uses its own graphical programming language  G  to create programs in a block diagram form   27   Each VI consists of three main parts  the front panel  the block diagram  and the icon  connector  The front panel is the user interface and can be designed to simulate the instrument  front panel  The front panel can contain knobs  push buttons  graphs and other controls and  indicators where information is entered and displayed  The block diagram consists of executable  source code that is created using nodes  terminals  and wires  The VI receives instructions from  the block diagram in the form of function blocks  routines  and control elements that constitute  the VI code  A VI within another VI is called a subVI  The icon connector of a VI is a graphical  parameter list so that other VIs can pass data to a subVI  Figs  3 2  3 3  and 3 4 show the front    18    panel  block diagram  and icon connector windows  respectively  for the AWG initialization VI   This VI initializes communication with the AWG by writ
19.  normal 120 or 240 degrees between  three phase voltages  10   Voltage and phase unbalance is caused by unequal loading of single     phase loads on a three phase system     Waveform Distortion  Waveform distortion is a steady state deviation from an ideal sine wave   Four primary types of waveform distortion are dc offset  harmonics  interharmonics  and  notching  Voltage harmonic distortion is usually less than 20   while current harmonic  distortion is usually less than 100   The main contribution to harmonic voltage and current  distortion is due to nonlinear loads which draw a nonsinusoidal current  Some of the effects of  voltage and current harmonics are heating losses  interference leading to misoperation of solid  state devices  and additional stresses on system capacitors  Interharmonics are caused by  equipment such as cycloconverters and arc furnaces  Normally  they do not cause significant  problems  but sometimes can lead to saturation of transformers  resonances between transformers    and capacitors  and subsynchronous resonance in synchronous generators     Voltage Fluctuations  Voltage fluctuations are systematic variations of voltage or a series of  random voltage changes of relatively small magnitude  typically less than 0 lpu  Voltage  fluctuations are also referred to as flicker and noise  Loads creating continuous  rapid variations    in the load current magnitude cause voltage fluctuations     Power Frequency Variations  Power frequency variations are 
20.  points  With a set sampling rate of 128  points per cycle  225 cycles at 60Hz can be recorded to a data file  The number of event capture  data files is only limited by the laptop PC hard drive disk capacity  25      16    3  LABVIEW INSTRUMENT DRIVER FOR AWG    3 1  Introduction    Initially  all of the programming setup for the arbitrary waveform generator  AWG  was  performed manually through the front panel interface  Most of the functionality available through  the front panel interface can be programmed remotely through the AWG s GPIB communication  port  National Instruments  LabVIEW was chosen as the software interface for programming the  AWG remotely  LabVIEW has a descriptive front panel graphical user interface and is used as a  standard data acquisition and control program for most instrumentation in the MSRF at OSU   LabVIEW also has the capability for remote data acquisition and control over the internet     enabling future coordination work with other research facilities and universities     3 2  LabVIEW Instrument Driver Objectives    Three main goals existed in the development of a LabVIEW driver database for the AWG  and programmable source  First  since the AWG has limited storage capabilities and has its  internal memory cleared whenever reset  the driver must provide a method for storing waveform   equation  and sequence profiles and transferring these profiles to and from the AWG as they are  needed  Second  the driver must have the capability to creat
21.  pulse pattern current in phase    c     non     sagged phase  is more unbalanced than for the 2  single phase voltage sag     5 2 2 3 100  Load    The input current for a 5  single phase voltage sag on phase    a     during a 100  load  condition is shown in Fig  5 10  This case is similar to the 2  single phase voltage sag during a  50  load condition  The current drawn by the sagged phase is highly unbalanced and still has a  double pulsed pattern  The average dc bus voltage during the voltage sag  630V  is still lower  than the peak value of the sagged line to line voltage  636V      i   V    would be here   dropped out        0 00000 0 02000 0 04000 0 06000 0 08000 0 10000    Figure 5 9  Input current  5  single phase sag  50  load     47       0 00000 0 02000 0 04000 0 06000 0 08000 0 10000    Figure 5 10  Input current  5  single phase sag  full load     5 2 3  10  Single Phase Voltage Sag    For a 10  single phase voltage sag on phase    a     the corresponding input phase and line to line  voltages are     V    23920  IV      438V rms  619V peak   V    2662240     V    460V rms  650V peak   5 3   V    2667120  Wal   438V rms  619V peak     Table 5 3  Data from a 10  single phase sag            Input Current in Sagged Phase    N           N  Y O    in N  Description of Input Current in N A N A Single pulsed  Sagged Phase        48    5 2 3 1 5096 Load    For a 10  single phase voltage sag on phase    a     the input current drawn during a 50  load  condition is shown 
22.  see Fig  5 26  voltage  sags  both at 50  of nominal voltage  In all cases the voltage sag disturbance sequences were  generated for 300 cycles  or 5 seconds  The ASD was also tested with a three phase transient  waveform similar to a three phase capacitor switching transient operation  see Fig  5 30   The    switching transient had a frequency of 480Hz  and was four cycles  therefore 8 33ms in duration     5 3 1 1 9096 Single Phase Voltage Sag    Table 5 7 shows the results of the 90  single phase voltage sag test  This test  and all tests   was performed at no load  50  load and at full load  For the three load conditions  the ASD did  not trip offline  For the test at full load  the ASD input voltage  current and dc bus voltage are  shown in Figs  5 17  5 18  and 5 19  respectively  It can be seen that during the voltage sag  the  ripple voltage on the dc bus increases  the motor load speed reduces slightly and the input current    drawn by the non sagged phases increases     Table 5 7  90  single phase voltage sag results          L AppiedToqe N    0       10    20          Sped apm             180   1785   1769         58    382 00              v3    DH       v2             A    0 00000 0 02000 0 04000    Figure 5 17  ASD input voltage   9096 single phase voltage sag        0 00000 0 02000 0 04000 0 06000 0 08000 0 10000    Figure 5 18  ASD input current     full load  two phases shown         Figure 5 19  ASD dc bus voltage     full load     59    5 3 1 2 100  Single P
23.  the light  dotted line   approximately 0 13pu  shows the dc bus voltage when there is no  dc bus capacitance  When one or more phases of the input ac voltage drops below the dc bus  voltage  constituting a voltage sag  one or more branches of the diode rectifier stops conducting  and the dc bus is supplied by the dc bus capacitor during this time  Since the dc bus capacitor  has limited energy content  it will not be able to supply the load for much longer than a few    cycles     o o   amp  8 Ld    DC bus voltage in pu  e  o e   amp  S       e  S       e  R    0 0 2 0 4 0 6 0 8 1  Time in cycles    Figure 4 2  ASD dc bus voltage during normal operation     It is a common misconception in industry that single phase voltage sags cause ASDs to trip  offline due to a dc bus undervoltage condition  Since single phase voltage sags are the most  common type of power quality disturbance  it is important to characterize ASD operation under  this type of disturbance  In this thesis  it will be demonstrated through experimental testing that  the dc bus voltage supplied by a three phase diode bridge rectifier does not fall below the  undervoltage trip level for any magnitude of single phase voltage sag     29    The majority of voltage sags that result in electronic equipment malfunction are caused by  either short circuit faults or the starting of large induction motors  2  9  30   There are three types  of voltage sags that are most commonly seen by ASDs including balanced and unbala
24.  to either of the two phases from which control power was derived  would cause the ASD to trip offline for single phase sags greater than 63  and for two and three   phase sags greater than 20   On the other hand  even with a complete single phase outage  applied to the line from which control power was not derived  the ASD did not trip offline  It was  also shown  that for a simple modification of feeding the internal power supply through a three   phase transformer  the ride through capability of the ASD was improved to withstand complete  single phase outages  two phase sags of 50  magnitude and three phase sages of 30   magnitude    It was seen that the ride through capabilities of the two ASDs  5 5kVA and 11kVA  with  internal power supplied by the dc bus was more substantial than ride through capabilities of the  5 5kVA ASD with internal power supplied from the ac input  The 5 5kVA and 11kVA ASDs  were able to ride through complete single phase sags and two phase sags of 50   The two ASDs  did trip offline due to an undervoltage fault for a 50  three phase voltage sag     5 5    AWG Equation to Waveform Test    The equation to waveform test setup included a three phase 460V line to line  Shp induction  motor which was directly supplied by the programmable source  Shown in Fig  5 31 is the output  of the programmable source where the AWG was set up in the continuous mode with 10  total  harmonic distortion on the voltage  consisting of 5  and 7  harmonics  This test was 
25. 0  Seconds    Figure E2 6  ASD dc bus voltage     full load     ASD tripped offline     116    400 00      W    0 00000 0 02000 0 04000 0 06000 0 08000 0 10000    200 00    0     e  eo       Vv     200 00      l    Seconds    Figure E2 7  ASD input voltage     65  single phase voltage sag phase    a           000 i    0 00000 0 04000 0 08000 0 12000 0 16000 0 70000    Figure E2 8  ASD input current     full load  two phases shown      ASD did not trip offline        559 00 0 00000 0 04000 0 08000 0 12000 0 16000 0 20000    Figure E2 9  ASD dc bus voltage     full load     ASD did not trip offline     117       200 00        v3       Don    v2                  Figure E2 10  ASD input voltage     100  single phase voltage sag on phase    a              04000 0 08000 0 10000    Seconds       0 08000 0 10000         350 06 0 00000 0 02000 0 04000 0 06000 0 08000 0 10000    Figure E2 12  ASD dc bus voltage     full load     ASD did not trip offline     118       Ju    Seconds    Figure E2 13  ASD input voltage     30  two phase voltage sag on phases    a    and    b           0 00000 0 06000 0 12000 0 18000 0 24000 0 30000    Seconds    Figure E2 14  ASD input current     full load  two phases shown      ASD did not trip offline        450 00 i i i  450 00 0 00000 0 06000 0 12000 0 18000 0 24000 0 30000    Figure E2 15  ASD dc bus voltage     full load     ASD did not trip offline     119       200 41    v3       v2     200 41          MOM    Seconds    Figure E2 16  ASD input vol
26. 000    Seconds    Figure E3 3  ASD dc bus voltage     full load     ASD did not trip offline     123    400  00     HARA    7400 00    v3    e  ce       v2    0 00000 0 02000 0 04000 0 06000 0 08000 0 10000    Seconds    Figure E3 4  ASD input voltage     5096 three phase voltage sag        0 00000 0 04000 0 08000 0 12000 0 16000 0 20000 7  Seconds    Figure E3 5        400 00  400 006 0 00000 0 04000 0 08000 0 12000 0 16000 0 20000  Seconds    Figure E3 6  ASD dc bus voltage     full load     ASD did not trip offline     
27. 1  1  U  LI  LI  U        1  1  H Source Torque Speed  i  1     U     U  LI  1  U  1  Li  1  1  1  t  1  1  1  U  L    Lee ee e A       1  1  1  1  1  1    500 hp Test Bed  1  LI  1  1  LI  1  1  1          Transducer    System Under Test   1  Test Loads   ASDs  motors  etc      Figure 2 1  Schematic of MSRF including the Power Quality Test Platform     12    A more detailed representation of the PQTP is shown in Fig  2 2  The main hardware and  instrumentation comprising the PQTP includes the three phase programmable source with an  integrated arbitrary waveform generator  AWG   a PC for remote control of the AWG  and a  three phase power analyzer with event capture data logging capabilities     2 2  Three Phase Programmable Source    The 120kVA three phase programmable power source is a one of a kind unit made by  Behlman Electronics Inc  that enables a flexible  variable amplitude and frequency output  23    The programmable source is composed of three solid state converters  one per phase  supplied  from a multi tapped input transformer to provide a wide range of output capabilities  Each power  amplifier has an output range of 0 132Vac rms  The output of the power amplifiers is stepped up  through a transformer that enables a rated output voltage range of 0 305Vac rms  line to neutral   a current limit of 144A rms per phase  and a frequency range of 45Hz to 2kHz  Peak voltage  capabilities are 0 460V instantaneous line to neutral and peak current capabilities are 2 9 tim
28. 1 ASD input current     no load  two phases shown   E1 12 ASD dc bus voltage     no load    Figure    E1 13  E1 14  E1 15  E2 1  E2 2  E2 3  E2 4  E2 5  E2 6  E2 7  E2 8  E2 9    E2 13  E2 14  E2 15  E2 16  E2 17  E2 18  E2 19  E2 20  E2 21  E2 22  E2 23  E2 24  E3 1   E3 2   E3 3   E3 4    LIST OF APPENDIX FIGURES  Continued     ASD input current     full load  two phases shown      ASD did not trip offline  ASD dc bus voltage     full load     ASD did not trip offline    ASD input voltage     50  two phase voltage sag on phases    b    and    c     ASD input current     full load  two phases shown      ASD did not trip offline  ASD dc bus voltage     full load     ASD did not trip offline  ASD input voltage     50  three phase voltage sag     Figure    Page  E3 5 ASD input current     full load  two phases shown      ASD did not trip offline  123  E3 6 ASD dc bus voltage     full load     ASD did not trip offline l 123    LIST OF APPENDIX FIGURES  Continued     LIST OF APPENDIX TABLES    Table Page  Al 1 AWG channel configuration  87  Bl   AWG2005 Individual query function blocks  93    A REMOTELY CONTROLLED POWER QUALITY TEST PLATFORM  FOR CHARACTERIZING THE RIDE THROUGH CAPABILITIES OF  ADJUSTABLE SPEED DRIVES    1  INTRODUCTION    1 1  What is Power Quality     Power quality has become an issue of increasing concern to both electric utilities and end  users of electrical power since the 1970s  The term    power quality    is applied to a wide range of  electromagnetic ph
29. 5   Files in the above  mentioned library path that do not begin with    TKAWG2005    are instrument profile blocks that    contain one or more individual function blocks as subsystems     Table B1  AWG2005 Individual query function blocks     Individual Query Function Block  TKAWG2005 Query Clock vi  TKAWG2005 Query Date Time vi             TKAWG2005 Query Waveform Settings vi            Table B2  AWG2005 Individual action function blocks             Individual Action Function Block        TKAWG2005 Close vi    TKAWG2005 Comment File vi  TKAWG2005 Compile Waveform File vi    TKAWG2005 Copy File vi  TKAWG2005 Define Equation File vi  TKAWG2005 Delete File vi  TKAWG2005 Download Equ or Seq File vi  TKAWG2005 Download Wfm File vi  TKAWG2005 Error Message vi  TKAWG2005 Initialize vi  TKAWG2005 Load Save File vi  TKAWG2005 Lock Unlock File vi  TKAWG2005 Make Hard Copy vi  TKAWG2005 Rename File vi  TKAWG2005 Reset vi   TKAWG2005 Revision Query vi  TKAWG2005 Seif Calibration vi  TKAWG2005 Self Test  vi  TKAWG2005 Set Clock vi  TKAWG2005 Set Date Time vi  TKAWG2005 Set Debug vi  TKAWG2005 Set Disk Drive vi  TKAWG2005 Set Display vi  TKAWG2005 Set Function Generator vi  TKAWG2005 Set Mass Memory vi  TKAWG2005 Set Output Channels  vi  TKAWG2005 Set Trigger Mode vi    TKAWG2005 Set Trigger Settings vi  TKAWG2005 Set Waveform Points vi  TKAWG2005 Start Stop Trigger vi  TKAWG2005 Upload Equ Seq File vi  TKAWG2005 Upload Wfm File vi          94    95    APPENDIX C  LABVIEW INSTRUMENT DRIV
30. 5 12 shows the results of the 100  single phase voltage sag test  Again  for the three  load conditions  the ASD did not trip offline  For the test at full load  the ASD input voltage   current and dc bus voltage are shown in Appendix E  It can be seen that during the voltage sag   the ripple voltage on the dc bus increases and the motor load speed reduces by about the same  amount as the previous test  The results are very similar to the previous 95  single phase    voltage sag results as well as the 5 5kVA ASD 90  and 100  single phase voltage sag results     66    Table 5 12  100  single phase voltage sag results            NoLoad   Applied Torque Nm    o   20   40      5 3 2 3 50  Two Phase Voltage Sag    Table 5 13 shows the results of the 50  two phase voltage sag test  For the three load  conditions  the ASD did not trip offline  For the test at full load  the ASD input voltage  current  and dc bus voltage are shown in Appendix E  It can be seen that during the voltage sag  the  ripple voltage on the dc bus increases and the motor load speed decreases more so than in the    5 5kVA ASD 50  two phase voltage sag results     Table 5 13  50  two phase voltage sag results             50  Load  100  Load     Applied Torgue Nm    0   20   4      491V 465V 442V  Drive Trip  Y N        5 3 2 4 50  Three Phase Voltage Sag    Table 5 14 shows the results of the 50  three phase voltage sag test  For the test at no load   the ASD did not trip offline  For the 50  load and full load
31. 5 3 1 3 50  Two Phase Voltage Sag    Table 5 9 shows the results of the 50  two phase voltage sag test  For the three load  conditions  the ASD did not trip offline  For the test at full load  the ASD input voltage  current  and dc bus voltage are shown in Figs  5 23  5 24  and 5 25  respectively  The increase in the  ripple voltage on the dc bus and the decrease in motor load speed are more dramatic than for the    single phase voltage sags  The input current is unbalanced and more current is drawn by the non     sagged phase     61    Table 5 9  50  two phase voltage sag results          50  Load 100  Load  Applied Torque  Nm 10        EE ee 20    Speed rpmy   179    177   172        m  lala                 va              gt   0 08000 0 10000    Figure 5 23  ASD input voltage     50  two phase voltage sag        Figure 5 24  ASD input current     full load  two phases shown      62         p cored  x  380   47 0  00000 0 04000 0 08000 0 12000 0 16000 0 20000    Figure 5 25  ASD dc bus voltage     full load     5 3 1 4 5096 Three Phase Voltage Sag    Table 5 10 shows the results of the 50  three phase voltage sag test  For the test at no load   the ASD did not trip offline  For the 50  load and full load conditions  the ASD did trip offline  nearly immediately due to an undervoltage error  The 50  load and full load tests were  performed with and without the    regenerate the kinetic energy from the machine inertia     parameter set and in all cases the ASD immediately trip
32. 70    Figure E1 9  ASD dc bus voltage   full load     111       d 1 Zoomed  x   gt   365 99 0 00000 0 16000 0 32000 0 48000 0 64000 0 80000    Figure E1 12  ASD dc bus voltage     no load     112    113       emed 5  0 00000 0 01000 0 02000 0 03000 0 04000 0 05000              0 00000 0 01000 0 02000 0 03000 0 04000 0 05000       Seconds    Figure E1 14  ASD input current     full load  two phases shown         E     ned Z    50 99 0 00000 0 01000 0 02000 0 03000 0 04000 0 05000    Seconds    Figure E1 15  ASD dc bus voltage     full load     114    S SkVA ASD   Internal Power Supply Derived From Single Phase Input  Transformer    AN           AAA    400 00  200 00   0 00  200 00     gt   0 00000 0 02000 0 10000    Seconds    Figure E2 1  ASD input voltage     63  single phase voltage sag on phase    a           s 0 00000 0 02000 0 04000 0 06000 0 08000 0 10000    Seconds    Figure E2 2  ASD input current     full load  phases    b    and    c    shown         550 02   v  ssc 69 0 00000 0 02000 0 04000 0 06000 0 08000 0 10000  5    Seconds    Figure E2 3  ASD dc bus voltage     full load     115       200 00    v3       v2     200 00              DU    Figure E2 4  ASD input voltage     65  single phase voltage sag on phase    c            i    0 00000 0 06000 0 12000 0 18000 0 24000 0 30000    Seconds    Figure E2 5  ASD input current     full load  phases    b    and    c    shown      ASD tripped offline        E1       550 00 0 00000 0 06000 0 12000 0 18000 0 24000 0 3000
33. AN ABSTRACT OF THE THESIS OF    Evelyn Matheson for the degree of Master of Science in Electrical and Computer Engineering    presented on June 8  2001  Title  A Remotely Controlled Power Quality Test Platform for  Characterizing the Ride Through Capabilities of Adjustable Speed Drives     Redacted for privacy       Abstract approved     MOM      Annette R  von Jouanne    With the increased attention on high efficiency and controllability of industrial processes  as  well as reduced weight  volume and cost of consumer products  the applications of nonlinear  power electronic converters such as adjustable speed drives  ASDs  are showing a rapid rise   Power Quality  PQ  is becoming an increasing concern with the growth of both sensitive and  disturbing nonlinear loads in the residential  commercial and industrial levels of the power  system  where PQ related disruptions can cause system malfunction  product loss  and hardware  damage resulting in costly data loss and downtime  Investigating and mitigating PQ issues  pertaining to the input supply of ASDs and other sensitive power electronic equipment is  extremely important in maintaining a high level of productivity    In response to these concerns  this research focuses on the development of a power quality  test platform  PQTP  that has been implemented at Oregon State University  OSU   in the Motor  Systems Resource Facility  MSRF   The central component of the PQTP is a 120kVA  programmable ac power source with an integra
34. ER PROFILE BLOCKS    1  Query AWG Internal Memory    List Files of Type  Bytes Used Bytes Free error in  no error   E    lumber of Files    Catalog Information  filename   DC 10KT WFM     file date file size       Figure C1 1  Front panel window for Query Internal Memory profile block     The Query Internal Memory profile block returns a catalog listing including the name  date   and size of all files stored in the internal memory of the AWG  The type of file to be searched  for  specified in the List Files of Type parameter  should be selected prior to running the VI  profile block     2  Upload All Waveform Files From AWG to Computer    error in  no error     Directory in Computer Upload Files of Type    EiEveymyest    BWAVEFORM JB     Catalog Information  filename  DC_10KT WFM     file date file size       Filename Being Uploaded ber of Files Unloaded  ie      Figure C2 1  Front panel window for Upload All Waveform Files profile block     96  The Upload All Waveform Files profile block transfers all  WFM files from the internal  memory of the AWG into a specified directory in the computer  The Directory in Computer and    Upload Files of Type parameters should be specified before running the profile block     3  Upload Waveform File From AWG to Computer    error in  no error     Filename in AWG    Filename in ComputerfilC  Evelyn  TekAWG       Figure C3 1  Front panel window for Upload Waveform File profile block     The Upload Waveform File profile block transfers a singl
35. FM  file is open in the Edit  Menu  the marker signal is shown at the bottom of the screen  The marker can be set either  HIGH  1  or LOW  0  at any of the waveform points  Every  WFM file used as a transient  waveform  including the transient trigger channel waveform  should have the marker signal set  HIGH  1  near the beginning of the waveform  not at the first waveform point  but within the first  50 waveform points  and the marker signal set LOW  0  near the end of the waveform  not at the    last waveform point  but within the last 50 waveform points   The nominal waveforms used in    91    the transient operation should NOT have markers set  The markers for these waveforms should  always be LOW  0   Also  the waveforms used in steady state operation should NOT have  markers set    The transient waveform for the trigger channel should again have the same number of  waveform points as the phase channel waveforms and should maintain a constant dc level  throughout  Keep in mind the waveform amplitude of the phase channel transient waveforms  during their creation  During transient waveform operation  the amplitude parameters for the  AWG channels cannot be changed  The sequence feature of the AWG can only step through  waveforms  it cannot vary the output amplitude multiplier or the clock frequency  In most cases   the output amplitude of the AWG channels will be maximized at 10 0V peak  The magnitude of  the transient waveforms should be scaled such that the desired AWG 
36. Quality Control  Techniques  Van Nostrand Reinhold  1993     Jih Sheng Lai and Thomas S  Key     Effectiveness of Harmonic Mitigation Equipment for  Commercial Office Buildings     IEEE Transactions on Industry Applications  vol  33  no   4  pp  1104 1110  July August 1997     Mark McGranaghan     Questions and Answers for Applying IEEE 519 1992     Part 1      Power Quality Assurance  vol  9  no  5  pp  50 58  May June 1998     Ned Mohan  Tore M  Undeland  and William P  Robbins  Power Electronics  Converters   Applications  and Design  John Wiley  amp  Sons  Inc   2nd edition 1995     20     21     22     23     24     25     26     27     28     83    Annette von Jouanne and Alan Wallace  A Short Course on Adjustable Speed Drives and  Utility Applications Issues for Eugene Water and Electric Board  March 2001     Mark McGranaghan     Applying IEEE 519     Part 2  Controlling Harmonic Distortion  Levels     Power Quality Assurance  vol  9  no  6  pp  55 61  July August 1998     John A  Houdek     Reactors Maximize Drive System Reliability     Power Quality  Assurance  vol  11  no  2  pp  22 28  February 2000     Robert Arthur     Harmonic Canceling Transformers  Part 1     Industrial Applications      Power Quality Assurance  vol  10  no  8  pp  44 50  November 1999     Robert Arthur     Harmonic Canceling Transformers  Part 2     Commercial Applications      Power Quality Assurance  vol  10  no  9  pp  46 51  December 1999     Mark McGranaghan     Sizing Active Filters for
37. Sagged Phase   Description of Input Current in N A Single pulsed    Sagged Phase                    50    5 2 4 1 5096 Load    For a 13  single phase voltage sag on phase    a     the input current drawn during a 50  load  condition is shown in Fig  5 13  Again  the input current on the sagged phase has completely  dropped out and only two of the six line to line voltage pulses are conducting current  meaning  the three phase rectifier is operating as a single phase rectifier  The average dc bus voltage    during the voltage sag  635 8V  is higher than the peak sagged line to line voltage  609V      5 2 4 2 10096 Load    The input current for a 13  single phase voltage sag on phase    a     during a 100  load  condition is shown in Fig  5 14  This case is similar to the 1096 single phase voltage sag during a  full load condition  The current drawn by the sagged phase still has a single pulsed pattern with  now a lower magnitude  Even though the average dc bus voltage during the voltage sag  622 4V   is higher than the peak value of the sagged line to line voltage  609V   the ripple of the dc bus  capacitor still causes the instantaneous dc bus voltage to drop below the sag affected line to line  input voltage  This is considered the boundary between operating with a sagged phase current in    a single pulsed pattern or with the sagged phase current completely dropped out     0 000       0 00000 0 02000 0 04000 0 06000 0 08000 0 10000 T    Seconds    Figure 5 13  Input current
38. ad  60  5 23 ASD input voltage     50  two phase voltagesag LLL 61  5 24 ASD input current     full load  two phases shown   61  5 25 ASD dc bus voltage     full load  62  5 26 ASD input voltage     50  three phase voltage sag  63  5 27 ASD input current     no load  two phases shown    63  5 28 ASD dc bus voltage     no lond    63  5 29 AWG test setup     three phase 480Hz capacitor switching transient    64  5 30 Output of programmable source     three phase 480Hz capacitor switching transient  64    LIST OF TABLES    Table Page  2 1 Measurement display formats for PQ power analyzer  13  3 1 AWG data transfer driver profile blocks  22  3 2 AWG file creation driver profile blocks      LLL 23  3 3 AWG setup and operation driver profile blocks  23  5 1 Data from a 2  single phase sag    39  5 2 Data from a 5  single phase sag     LLL 45  5 3 Data from a 10  single phase sag     LLL 47  5 4 Data from a 13  single phasesag      LLL 49  5 5 Data from a l7 6single phasesag      LLL 51  5 6 Summary of single phase sag testing  LLL 54  5 7 90  single phase voltage sag results 57  5 8 100  single phase voltage sag results occ LLL 59  5 9 50  two phase voltage sag results      Lu 61  5 10 50  three phase voltage sag results 62  5 11 95  single phase voltage sag results  65  5 12 100  single phase voltage sag results  66  5 13 50  two phase voltage sag results  66  5 14 50  three phase voltage sag results 67  5 15 63  single phase voltage sag  phase    a     regular configuration    69
39. and ride through  characterization  The experimental results have in some cases reinforced known operational  behaviors of ASDs while also exposing new trends due to the PQ voltage disturbances tested   Most of the PQ voltage disturbances generated and applied to the ASDs were single  two  and  three phase voltage sags since these are the most prevalent voltage disturbances experienced by  commercial and industrial customers    The ASD diode bridge rectifier operation analysis involved supplying the ASD with  relatively small magnitude   lt  20   single phase voltage sags to observe the transition between  operation as a three phase rectifier and as a single phase rectifier  It was found that the input  three phase rectifier does not immediately change to operation as a single phase rectifier during a  single phase voltage sag  Instead  for increasing single phase voltage sag magnitudes  the normal  three phase balanced double pulse phase current waveform on the sagged phase  changes to an  unbalanced double pulsed waveform  then to a single pulsed waveform  and finally drops out  completely  When the current in the sagged phase does drop out completely  the three phase  rectifier operates as a single phase rectifier and the dc bus falls to the same level for any greater  magnitude single phase sag  including a complete single phase outage  From the experimental  results  it was determined that the sag magnitude at which the three phase rectifier converts to  operations as a 
40. are shown in Table 5 19  For the three load conditions  the ASD did not trip offline  For the test  at full load  the ASD input voltage  current and dc bus voltage are shown in Appendix E  As  expected for this magnitude of voltage sag  the drop in speed and dc bus voltage is not as great as  for the 30  two phase voltage sag on phases    a    and    b     Again  it is shown that the ability of  the ASD to ride through two phase voltage sags is limited by requirements for the internal power  supply voltage     Table 5 19  20  two phase voltage sag  phases    b    and    c     regular configuration         Applied Torque Nm   0   10      lag S6 Reduction                 5 3 3 3 Three Phase Voltage Sag     Regular Configuration    The test results for a 2096 three phase voltage sag supplying the ASD are shown in Table  5 20  This is the largest magnitude three phase sag that the ASD can ride through since as was  shown in the previous section  phases    b    and    c    of the ASD cannot ride through a sag greater  than 20  of nominal voltage  For the three load conditions  the ASD did not trip offline  For the  test at full load  the ASD input voltage  current and dc bus voltage are shown in Appendix E  As  expected for this magnitude of voltage sag  the drop in speed and dc bus voltage is greater than    72    for any of the two phase voltage sags tested in the previous section  Under the full load    condition  the average dc bus voltage falls to 80  of its nominal value    
41. armonics and enable  regenerative braking  Disadvantages of a controlled rectifier are increased cost due to more  expensive hardware and additional control logic and the ASD would need to be derated to ride   through extended sags     4 5 4  Internal Power Supplied From the DC Bus Voltage    The ride through capability of an ASD can be significantly improved by specifying that the  internal power be supplied from the dc bus voltage  As will be shown in Chapter 5  this  configuration will enable ASDs to ride through single phase voltage sags of any magnitude and  duration  This ride through alternative is fairly simple and inexpensive when compared with the  previously mentioned ride through solutions since no additional hardware or control logic is  required  The cost of an ASD with the internal power supplied from the dc bus voltage may be  slightly higher than the cost of an ASD with the internal power supplied form two of the three  input phases since a dc dc converter power supply must be implemented instead of a more simple    linear power supply     38    5  EXPERIMENTAL RESULTS    5 1    PQTP Experimental Test Plan    The ability of the programmable source and integrated AWG to simulate PQ disturbances  such as voltage fluctuations  which is useful in characterizing ASD operation  was demonstrated  with a series of tests  The first series of tests involved applying single phase voltage sags of a  relatively small magnitude   lt  20   to an ASD under different load con
42. as five measurement display and data logging formats     Table 2 1 gives a short description of the different measurement formats  25      Table 2 1  Measurement display formats for PQ power analyzer     Phasor Diagram Single cycle measurement with real    time    display update of all fundamental and rms  Detailed Harmonics    quantities  good for quick viewing   Spectrum Analyzer    Cycle by Cycle Capture    The event capture mode of the PQ power analyzer is very useful for capturing power quality               Captures 10 cycles of waveform data and then  performs a harmonic decomposition of the data  for all signals                    Performs spectral decomposition on a single  waveform captured from a selected input  channel        Cycle by cycle measurement and data logging  of all fundamental and rms quantities enabling  detailed trending of all quantities                  Continuously monitors all channels and  captures sub cycle events while continuously  logging information     disturbances simulated with the PQTP  In this mode  the PQ power analyzer saves data when  triggered according to pre selected setpoints  The event capture mode of the PQ power analyzer    15    2 6  PQTP Operation    The programmable source can be operated with or without the AWG controlling the output  voltage  Without the AWG    programming    the source output  the balanced sinusoidal three   phase voltage magnitude and frequency can be manually adjusted  The output is applied to the  te
43. ation    The test results for a 63  single phase voltage sag on phase    a    supplying the ASD are  shown in Table 5 15  For the three load conditions  the ASD did not trip offline  For the test at  full load  the ASD input voltage  current and dc bus voltage are shown in Appendix E  The two  phase currents shown in the input current figure  and all subsequent input current figures  are  phases    b    and    c     the two phases that supply the internal power supply through the single phase  transformer   Similar to the ASDs tested with an internal power supply from the dc bus  both the  input current in the non sagged phases and the dc bus ripple increase  A 63  single phase    voltage sag on phases    b    and    c    produces the same results as for the sag on phase    a        69    Table 5 15  63  single phase voltage sag  phase    a     regular configuration                Applied Torque Nm        0   10   20    621 3V  Drive Trip  Y N            The test results for a 65  single phase voltage sag on phase    a    supplying the ASD are  shown in Table 5 16  For the three load conditions  the ASD did not trip offline  For the test at  full load  the ASD input voltage  current and dc bus voltage are shown in Appendix E  The  resulting drop in dc bus voltage and motor speed are the same as for the 63  single phase  voltage sag  However  a 65  single phase voltage sag on phases    b    or    c    causes the ASD to    trip offline under all load conditions due to a    cont
44. ause different unbalance conditions seen at ASDs based on the type of load connection and the  type of possible transformer connections present between the fault and the ASD    In a single phase fault  one phase voltage drops and the other two voltages remain unchanged  and can be described by  35 36     F  y    a Ss    V     pA   A A8  pu   4 8   V       Mo jN3    Fig 4 5 shows the dc bus voltage of an ASD  for varying dc bus capacitance sizes  during a  typical voltage sag caused by a single phase fault  2   Similar to Fig  4 2  the solid line shows the  dc bus voltage for a large dc bus capacitance  The dashed line shows the dc bus voltage for a  small dc bus capacitance  and the light  dotted line shows the dc bus voltage with no dc bus    capacitance     DC bus voltage       0 0 5 1 1 5 2 2 5 3    Time in cycles    Figure 4 5  ASD dc bus voltage during a single phase fault     In a phase to phase fault  two phase voltages move towards each other and the third phase  voltage remains unchanged and can be described by  35 36      V      a    1  pe e  V jV N3  pu   4 9   V       Vo jV N3    33    Fig 4 6 shows the dc bus voltage of an ASD  for varying dc bus capacitance sizes  during a  typical voltage sag caused by a phase to phase fault  2   Again  similar to Figs  4 2 and 4 5  the  solid line shows the dc bus voltage for a large dc bus capacitance  The dashed line shows the dc   bus voltage for a small dc bus capacitance  and the light  dotted line shows the dc bus voltag
45. capacitors  9  15     Another method is to purchase equipment with reduced harmonic generation  This is usually  an initial option that is difficult and costly to implement with pre existing equipment  An  example of this is the application of line reactors  inductive chokes  in series with the ac input of  nonlinear loads such as adjustable speed drives  ASDs   9  16   Adding a line reactor in series  with the ASD will reduce current harmonics and provide transient protection benefits  However   a slight voltage drop is then seen at the input of the ASD rectifier  Sometimes  a reactor is added  to the dc link of an ASD which then eliminates the ac voltage drop  but does not provide as much  overvoltage transient protection  Other examples of equipment with reduced harmonic generation  are ASDs with higher pulse numbers  A six pulse ASD generates predominantly fifth and  seventh harmonics  Whereas a twelve pulse ASD generates predominantly eleventh and  thirteenth harmonics  and the magnitudes of these harmonics are much lower  9     Applying technologies that cancel harmonics from different loads is another method for  eliminating harmonics  This is commonly achieved with standard transformer connections  17   18   Transformers can reduce harmonics in two ways  through harmonic attenuation and by  harmonic cancellation  Transformers have a reactive impedance which increases directly with    frequency  naturally attenuating harmonics  Harmonic cancellation occurs when two or 
46. d    the most important concern affecting most industrial and commercial customers   21      The most common voltage sags are caused by single line to ground faults  These types of  faults are caused by weather conditions  tree branches  animal contact  insulation failures   automobile accidents or other human activity  A few customers near a fault may see a deep  voltage sag  followed by a complete interruption when utility circuit breakers clear the fault   Most other customers connected through the same distribution or transmission system will see a  smaller voltage sag with the magnitude based on the customer s distance to the fault location as  well as intervening transformer connections that further isolate customers from the fault  2  21    Once the fault has been cleared or isolated  the system will return to nominal voltage    The IEEE has developed a recommended standard that helps industrial power electronic  equipment users evaluate the impact of voltage sags at their facility  IEEE 1346 1998  This    standard describes a method for combining predictions of voltage sag magnitude  duration  and    27    rate of occurrence  with a characterization of equipment susceptibility to voltage sag events  to  determine the cost of voltage sag related downtime  The cost of incorporating either power  conditioning equipment or new process equipment with greater voltage sag tolerance can also be    compared with voltage sag related downtime costs  21      Circumstances that ca
47. d in kV and the time  has units of milliseconds  ms   For a given capacitance connected to the dc bus of an ASD   typically between 75 and 360 uF kW   4 6  can be used to approximate the maximum voltage sag  ride through time for a given voltage sag magnitude  Figure 4 4 shows the voltage tolerance  curve of ASDs for different capacitance sizes  It can been seen that even for relatively small  balanced three phase voltage sags  the ASD will trip offline due to a low dc bus voltage within a    few cycles        Figure 4 4  Voltage tolerance curve for ASDs based on dc bus capacitances of 754F kW  solid  line   1654F kW  dashed dotted line   360uF kW  dotted line   and 670F kW  dashed line      One way to improve the voltage tolerance curve of an ASD is to lower the undervoltage trip  setting parameter  Some ASD manufacturers do not allow this parameter to be changed for  smaller ASDs  e g   lt  25kVA   Also  the undervoltage trip parameter should be set to protect  against malfunction of the load process or damage to the ASD components  especially due to high  currents  Another way to improve the ASD voltage tolerance curve is to increase the amount of  dc bus capacitance  The amount of capacitance needed to obtain a voltage tolerance with a    specific Vmin and tmar is given by  2  30      2Pt ax  0 min    32    4 3 2  Unbalanced Voltage Sags     Single Phase and Phase to Phase Faults    Single phase and phase to phase faults resulting in unbalanced three phase voltage sags  c
48. ditions and analyzing the  input three phase diode bridge operation  A second set of tests involved characterizing the ride   through capabilities of ASDs by simulating single  two  and three phase voltage sags  as well as  transient disturbances and applying these PQ disturbances to an ASD driving a motor load  These  tests involved two sizes and configurations of ASDs  A third test involved demonstrating the  flexible equation to waveform programming ability of the AWG by generating a voltage    harmonic distortion condition and applying the waveforms to a line operated motor load     5 2  Single Phase Voltage Sag Affects on ASD Diode Bridge Rectifier Operation    The experimental tests were performed on a 5 5kVA ASD with a conventional six pulse  diode bridge rectifier supplying the dc bus  The nominal input line to line voltage was 460V  rms  and the nominal corresponding input phase voltage was 266V rms  Several magnitudes of  single phase voltage sags were generated including a 2  sag  261V rms   5  sag  253V rms    10  sag  239V rms   13  sag  231V rms   and 17  sag  221V rms   These sag magnitudes  were chosen because they demonstrated input current transition operating conditions  For each  single phase sag magnitude  a test was performed at no load  5096 load  and full load  For each  test  the dc bus voltage was recorded before the sag and during the sag    Three phase diode bridge rectifier operation is altered in three different patterns when  relatively low magn
49. dre Ramme  Abdurrahman Unsal  and Marcel Merk    And finally  I would like to thank my family  Mom  Dad  Don  and Karen  for their ongoing    encouragement  and especially my fianc  e Russell for his support     1     TABLE OF CONTENTS    Page  INTRODUCTION   lt  sats cutee tele esa tt eal et Leere eee A i See  1  1 1  What is Power Quality  1  1 2 Harmonic Distortion  4  1 3  Harmonic Distortion Mitigation Techniques LLL 7  1 4 Research Project tat rant a cA e tle A oe 8  1 5  Organization of Thesis  10  POWER QUALITY TEST PLATFORM LLL 11  2 1  Equipment Set  p  4 4 eon A A een ies Lo sucha Tex 11  2 2  Three Phase Programmable Source    12  2 3  Three Phase PQ Power Analyzer      LLL 13  24 AWG Op mlO see enen eran e it ere ae t e E T ac 14  2 5  LabVIEW Instrument Driver    14  2 0  PTP Operation  6  ToT cR Ld ATE net cree cec ot nre Rey ae 15  LABVIEW INSTRUMENT DRIVER FOR AWG       s 16  Sob  IntroductioB  teren ene cte a pt ra asco Petr TE ita 16  3 2  LabVIEW Instrument Driver Objectives      ss 16  3 3  Pre Existing Instrument Driver    16  3 4  LabVIEW Virtual Instrument Overview  17  3 5  LabVIEW Profile Block Virtual Instruments      n 20  3 6  New Instrument Driver for AWG    21  3 7  Limitations in AWG Programming Functions 24    3 8  Programmable Source Range of Operation Limits for AWG 24    TABLE OF CONTENTS  Continued     4  ADJUSTABLE SPEED DRIVE PROPERTIES    4 5 1  Energy Storage Methods  4 5 2  Functional Operation Modes of ASDs  4 5 3  ASD Topology Modif
50. e    lightning strikes and capacitor switching operations     Short Duration Variations  A short duration variation is either a temporary voltage drop  sag   dip   voltage rise  swell   or complete loss of voltage  interruption   An interruption occurs when  the supply voltage or load current decreases to less than 0 1pu for less than one minute  A sag is  a decrease in rms voltage or current at the nominal frequency to between 0 1 and 0 9pu     Conversely  a swell is an increase in rms voltage or current at the nominal frequency to between    1 1 and 1 8pu  Voltage sags and swells typically last anywhere from under a cycle up to a couple  of minutes  Short duration variations are typically caused by system fault conditions  short  circuits  circuit breaker reclosure operations  overloads  the energizing of large loads that require    high starting currents  or intermittent loose connections in power wiring     Long Duration Variations  A long duration variation is a sustained overvoltage  undervoltage   brownout   or interruption lasting longer than two minutes  Long duration variations are caused  by load variations on the system  system switching operations  and voltage regulation equipment    such as tap settings on transformers     Voltage and Phase Unbalance  Voltage unbalance is the maximum deviation from the average  of the three phase line to line voltage  divided by the average of the three phase line to line  voltage  Phase angle unbalance is the deviation from the
51. e    with no dc bus capacitance     DC bus voltage          0 0 5 1 1 5 2 2 5 3  Time in cycles    Figure 4 6  ASD dc bus voltage during a phase to phase fault     4 4  Motor Deceleration    In some circumstances  ASDs can ride through voltage sags  In such a case  the drop in  system voltage at the ac input of the ASD usually causes a drop in the voltage at the motor load  terminals  A voltage sag at the motor terminals causes a drop in torque and thus a drop in speed   It is possible to estimate the drop in motor speed for balanced and unbalanced voltage sags based  on a simplified motor model where the electrical torque is proportional to the square of the  voltage and the mechanical torque is constant  It is assumed that for a balanced voltage sag  all  three phase voltages at the motor terminals drop by the same amount  Following a derivation  given in  2   the increase in motor slip As due to a voltage sag of magnitude V  in per unit  and    duration Af can be given by   ds 1 py     As     At  At  4 10   at 2H       In  4 10   H  is the inertia constant of the motor load combination and is expressed as the ratio of    the kinetic energy and the mechanical output power     34        pu   4 11     It can be seen that the voltage tolerance of an ASD can be improved by adding inertia to the load   If the maximum acceptable slip increase is equal to Asma  then the minimum acceptable three     phase sag magnitude  Vmin  for a given duration T can be expressed by     Vin    Em
52. e  WFM file from the internal  memory of the AWG into a specified directory in the computer  The Filename in AWG   Filename in Computer  and Source parameters should be specified prior to running the profile  block VI  The Source parameter indicates where the file to be uploaded is located  Available    options are the internal memory  and channels 1 through 4     4  Upload All Sequence Equation Files From AWG to Computer    error in  no error   Directory in Computer Upload Files of Type     ed    File Type  Catalog Information H equation    sequence  filename    DC 30 SEQ   file date file size    Br  BI    IC  Evelyn test PHC_10K SEQ       Filename Being Uploaded lumber of Files Uploaded       Figure C4 1  Front panel window for Upload All Sequence Equation Files profile block     97    The Upload All Sequence Equation Files profile block transfers either all  SEQ or all  EQU  files from the internal memory of the AWG into a specified directory in the computer  The    Filename in Computer  Upload Files of Type  and File Type parameters should be specified prior  to running the profile block VI     5  Upload Sequence Equation File From AWG to Computer    error in  no error     Filename in AWG     FPHA_10K2 SEQ  File Type FT code  H equation eo    sequence    Filename in Computera C Evelyn TekAWG PHA_10K2 SEQ       Figure C5 1  Front panel window for Upload Sequence Equation File profile block   The Upload Sequence Equation File profile block transfers either a  SEQ or a  EQU 
53. e Balanced and Unbalanced Sags     IEEE  Transactions on Industry Applications  vol  36  no  3  pp  904 910  May June 2000     Rick Langley and Arshad Mansoor     What Causes ASDs to Trip During Voltage Sags       Part 1     Power Quality Assurance  vol  10  no  6  pp  12 15  September 1999     Rick Langley and Arshad Mansoor     What Causes ASDs to Trip During Voltage Sags       Part 2     Power Quality Assurance  vol  10  no  7  pp  44 50  October 1999     Rick Langley and Arshad Mansoor     What Causes ASDs to Trip During Voltage Sags       Part 3     Power Quality Assurance  vol  10  no  8  pp  36 39  November 1999     Rick Langley and Arshad Mansoor     What Causes ASDs to Trip During Voltage Sags       Part 4     Power Quality Assurance  vol  10  no  9  pp  32 35  December 1999     L D  Zhang and Math H  J  Bollen     A Method for Characterizing Unbalanced Voltage  Sags with Symmetrical Components     JEEE Power Engineering Review  vol  18  no  7   pp  50 52  July 1998     Math H  J  Bollen     Characterisation of Voltage Sags Experienced by Three Phase  Adjustable Speed Drives     IEEE Transactions on Power Delivery  vol  12  no  4  pp   1666 1671  October 1997     Rick Langley  Arshad Mansoor  Tom Geist  and Ben Banerjee     Advanced  Electrochemical Capacitors for ASD Ride Through     Power Quality Assurance  vol  11   no  2  pp  46 50  February 2000     Toshiba International Corporation  Toshiba G3 TOSVERT 130 Transistor Inverter  Operation Manual  September 1996   
54. e and modify the several types of  waveform  equation  and sequence files that are necessary to produce simulated voltage  disturbance conditions from the programmable source  And third  the driver must be able to  perform the control functions necessary to load  configure  execute  and trigger simulated voltage    disturbance conditions     3 3  Pre Existing Instrument Driver    A LabVIEW basic function driver database has been developed by National Instruments for a  similar Tektronix AWG  model AWG2041  LabVIEW driver databases consist of virtual  instruments  VIs   each of which executes a specific function  27   The VIs for a particular  device are grouped together in a library that is located within the LabVIEW instrument library  folder  instr lib   The AWG2041 instrument driver library consists of approximately fifty VIs  which are separated into five different categories  One category initializes and closes    communication with the AWG  The other four categories include system configuration  action    17    and status  data collection and transmission  and utility functions  Fig  3 1 shows a tree  containing all of the VIs in the AWG2041 instrument driver library    To begin creating a LabVIEW driver database for the AWG2005  each of the VIs from the  AWG2041 database was modified and reconfigured for the AWG2005  One difference between  the two AWG models is that the AWG2005 has four output channels compared to the AWG2041  which has two output channels  Therefore 
55. e error occurred  If an error occurs   subsequent VIs will not execute and the error cluster will be passed on    Progressing from left to right  the Initialize VI is executed first  followed by the Define  Equation VI  the Set Waveform Points VI  the Compile Equation VI  and finally ended with the  Close VI    To insert a subVI into a new profile block VI  open the Instrument Drivers window in the  Function menu  All instrument driver folders located in the following path will be displayed    C  Program Files National Instrument LabVIEW Instr lib  Choose the Tek2005 driver which will open up a window listing icons for all of the individual  function block VIs and profile block VIs in the AWG2005 driver database  Selected the desired  Vl and drag the icon into the new block diagram window    The second common profile block structure consists of multiple command strings  concatenated together in series and written to the AWG as shown in Fig  D2 2  This program  diagram window example is from the Load Channel Phase A VI  In this VI  the Initialize VI is  followed by multiple command strings which are grouped together in a particular order with input  data from the front panel  The concatenated command string is then sent to the AWG through the  VISA write function block  The Make Hard Copy and Close VIs follow the VISA write function    107    block  Another commonly used VISA command is the VISA read function block which is used    in several of the information query VIs     i
56. e estimated to cost the company  1 million per minute due to lost  production  Overall  EPRI estimates that lost productivity and downtime  ranging from system  malfunction  product loss  and hardware damage to costly data loss  due to power outages  costs  the United States  50 billion annually  7   In an effort to better understand the link between  power reliability and economic productivity and to demonstrate technological solutions to current  problems that threaten this linkage  EPRI began operation of the Consortium for Electric  Infrastructure to Support a Digital Society  CEIDS  in January 2001  CEIDS membership  includes utilities  equipment manufacturers and representatives of industrial groups that are  particularly sensitive to power quality  A main task of CEIDS will be to determine which    combination of technologies is likely to be most cost effective in optimizing power quality  5    Power quality disturbances can be described according to the following categories  1 2  8 9      Transients  A transient is a power system variation that is undesirable but momentary in nature   A transient is characterized by a sudden change in the steady state condition of voltage  current   or both that follows an impulsive or oscillatory behavior  Transients can last anywhere from just  a few nanoseconds up to 30 cycles in duration  oscillate in a frequency range from a few kHz up  to a few MHz  and peak in magnitudes of up to 5 per unit  pu   Typical causes of transients ar
57. e ride through capabilities of industrial  processes  The PQTP also enables a controlled environment where tests can be performed  In  addition to research benefits  the PQTP is also used as a practical educational tool  enabling  hands on demonstrations for undergraduate and graduate level classes as well as for industry and  utility short courses offered in the MSRF    The LabVIEW instrument driver library created for the AWG enables the programming and  operation functionality of the AWG to be controlled remotely  With National Instruments GPIB  internet technology  it is feasible for a large portion of the PQTP to be configured  monitored  and  even controlled from remote locations outside of the MSRF  This capability enables the    possibility of future collaborative research with other universities     6 2  Summary of Experimental Results    A LabVIEW instrument driver has been developed that enables remote creation and storage  of PQ voltage disturbance files as well as setup and operation of the AWG output to the  programmable source  The LabVIEW instrument driver library consists of individual function  virtual instrument  VI  blocks and combined subsystem profile block VIs  As new PQ voltage  disturbance tests evolve  additional profile block VIs can be easily created from existing VI    subsystems     79    The ability of the programmable source to simulate power quality voltage disturbances has  been demonstrated with ASD diode bridge rectifier operation analysis 
58. ency and channel amplitudes of the AWG  while the output of the programmable source is ON  This has not been tested  Refer to supplied  Behlman literature on AWG programming  or contact Jaye Killian at Behlman Electronics for    more information     5  Transient Waveform Operation    The generation of transient waveform conditions with the AWG is somewhat complicated  In  a transient operation scenario  a set of nominal waveforms is continuously output until a trigger  signal is sent to the AWG  also can be manually triggered from the AWG front panel   When a  trigger signal is executed  the AWG switches from the set of nominal waveforms  and outputs a  set of transient waveforms and then automatically returns to the steady state waveform set output  at the end of the transient waveform cycle s   For an entire transient waveform operation  a set of  eight waveforms must be generated  six waveforms for the three output phases and two  waveforms for the trigger channel  For each of the four channels  a nominal waveform and a  transient waveform must be generated    Instead of loading  WFM files into the four AWG channels  as was done for steady state  operation   SEQ files will be loaded into the four AWG channels  Each  SEQ file will consist of a  nominal case waveform  the first waveform in the  SEQ file  and one or more transient  waveforms to be executed in sequence when the trigger signal is executed  EVERY transient  case waveform must include MARKERS  When a waveform   W
59. enomena that cause voltage and current non idealities to occur on a power  system  1   A description of a power quality problem is defined in  1  as  A power quality  problem is any power problem manifested in voltage  current  or frequency deviations that results  in failure or misoperation of customer equipment  A definition of power quality is also given by  the IEEE Recommended Practice for Powering and Grounding of Sensitive Electronic  Equipment  IEEE Standard 1100 1992  as  Power quality is the concept of powering and  grounding sensitive equipment in a manner that is suitable to the operation of that equipment  2     There are several reasons for the heightened interest in power quality issues both by utilities  and consumers  The use of electronic and power electronic equipment has proliferated in both  industrial and commercial applications  In addition to becoming more widely used  this  equipment is increasingly sensitive to voltage disturbances  leading to loss of production time and  thereby a reduction in company profit margins  Power electronic equipment also causes voltage  and current disturbances for other customers and equipment  In particular  an increased use of  converter type  nonlinear load equipment  ranging from computer power supplies to adjustable  speed drives  has increased the level of current and voltage distortion seen on the power system   2 4   Interest in power quality is also more important under the deregulation of the electric  utility 
60. es  the rms rating  23 24   A Sony Tektronix model AWG2005 arbitrary waveform generator   AWG  has been custom integrated with the programmable source  The AWG has four output  channels  three of which are used to represent the desired three output power phases  while the  fourth channel is used as a trigger source  The AWG channels have an output range from 0 10V  that are amplified and correspond to a 0 326Vac rms line to neutral  0 564V rms line to line     output range of the programmable source  24              PC with  LabVIEW  instrument driver    GPIB interface          120kVA  Programmable  Source    Test Loads   ASDs  motors  etc      Figure 2 2  Block diagram of the Power Quality Test Platform  PQTP      JOtech ESA  three phase  power analyzer       2 3  Three Phase PQ Power Analyzer    The PQTP includes a three phase power analyzer  model PowerVista 312 by IOtech  Inc   The power analyzer consists of a data acquisition box  laptop PC  and EasyPower Measure  Windows software developed by ESA  Inc  The power analyzer monitors and captures voltage  and current information and can calculate and display all relevant quantities  V  I  kW  kVAR   kVA  pf  THD  etc   in a waveform  phasor  or Fourier analysis format  The power analyzer has  four differential voltage channels as well as four external shunt current channels enabling three   phase power measurements as well as two additional parameter measurements at important test  points    The EasyPower Measure software h
61. file from    the internal memory of the AWG into a specified directory in the computer  The Filename in    Computer  Filename in AWG  and File Type parameters should be specified prior to running the  profile block VI     6  Download Waveform File From Computer to AWG    error in  no error     ile to Download 3 C  Evelyn  TekAWG PHA NOM WFM       Figure C6 1  Front panel window for Download Waveform File profile block     98  The Download Waveform File profile block transfers a  WFM file from a specified directory  in the computer into the internal memory of the AWG  The File to Download and Filename in    AWG parameters should be specified prior to running the profile block VI     7  Download Sequence Equation File From Computer to AWG    error in  no error     File Type    equation  sequence    ile to Download 3 C  Evelyn TekAWG DC_30 SEQ       Figure C7 1  Front panel window for Download Sequence Equation File profile block     The Download Sequence Equation File profile block transfers either a  SEQ or a  EQU file  from a specified directory in the computer into the internal memory of the AWG  The File to  Download  Filename in AWG  and File Type parameters should be specified prior to running the  profile block VI     8  Define and Compile an Equation File    error in  no error   Equation File     FTESTEQU  Cd    Byte Count Number of Characters       Figure C8 1  Front panel window for Define Compile Equation profile block     99    The Define Compile Equation profile bl
62. gram the source output  The AWG picture  capture VI is also included as a subsystem VI in the Set Channel Output profile block     14  Start Stop AWG Trigger    error out error in  no error     status         source i       Figure C14 1  Front panel window for Execute Trigger profile block     The Execute Trigger profile block executes the AWG trigger function  The trigger function  is used in Waveform Advance Mode when simulating a power quality transient disturbance   When the trigger is started  the AWG output switches from the continuously output nominal  waveform to the sequence of transient waveforms  After the transient waveforms have been    executed  the output of the AWG returns to the continuous output of the nominal waveform     105    APPENDIX D  PROCEDURE TO CREATE NEW INSTRUMENT DRIVER  PROFILE BLOCKS    1  Standard Profile Block Subsystems    All instrument driver profile blocks should contain a few standard subsystem components   These standard subsystems include the Initialize VI and the Close VI  If the profile block to be  created involves some configuration or setup of the AWG  the Make Hard Copy VI is useful if  inserted at the end of the VI since it captures the AWG display screen and can be imported into  the LabVIEW front panel window  Figs  D1 1 and D1 2 show the front panel window and block  diagram window of a blank template VI which just includes the standard subsystems for a profile  block        Figure D1 2  Block diagram window of standard subs
63. hase Voltage Sag    Table 5 8 shows the results of the 100  single phase voltage sag test  These test results are  extremely similar to the results of the 90  single phase voltage sag test  This is because for any  single phase voltage sag greater than 17   the three phase diode bridge rectifier operates as a  single phase rectifier for any load condition  Again  for the three load conditions  the ASD did  not trip offline  For the test at full load  the ASD input voltage  current and dc bus voltage are  shown in Figs  5 20  5 21  and 5 22  respectively  It can be seen that the increased dc bus voltage  ripple  slight drop in motor speed  and increase in input current are all the same as for the 90     single phase voltage sag test     Table 5 8  100  single phase voltage sag results        50  Load   100  Load         Applied Torque  Nm    09   EG CEE BORE 1    Speed rpm    1799 1788 1773  DC Bus Voltage 647V 643V 640V    Speed  during sag     Reduction 1799  0 0  1787  0 06  1769  0 23   DC Bus Voltage  during sag 645V 633V 610V        n        WA    0 08000 0 10000    386 60                      380 00    v2             Seconds    Figure 5 20  ASD input voltage     100  single phase voltage sag     60       0 00000 0 02000 0 04000 0 06000 0 08000 0 10000 7    Seconds    Figure 5 21  ASD input current     full load  two phases shown               ec x    590 00 i    ac  cg 0  00000 0 02398 0 04797 0 07195 0 09594 0 11992    Figure 5 22  ASD dc bus voltage     full load     
64. ications  4 5 4 Internal Power Supplied From the DC Bus Voltage    5 2 1  2  Single Phase Voltage Sag  5 2 2  5  Single Phase Voltage Sag  5 2 3  10  Single Phase Voltage Sag  5 2 4  13  Single Phase Voltage Sag  5 2 5  17  Single Phase Voltage Sag  5 2 6  Summary of Results  5 2 7  Diode Rectifier Stresses Due to Single Phase Voltage Sags    5 3 1  5 5kVA ASD  Internal Power Supply from DC Bus  5 32  11kVA ASD  Internal Power Supply from DC Bus  5 3 3  5 5kVA ASD  Internal Power Supply from AC Input    LIST OF FIGURES    Figure Page  1 1 Power system showing location of the PCC where other customers can be supplied        5  2 1 Schematic of MSRF including the Power Quality Test Platform    11  2 2 Block diagram of the Power Quality Test Platform  PQTP  s 12  3 1 Tree of AWG2041 instrument driver VIs Ls 17  3 2 Front panel window for initialization VI  Ln 18  3 3 Block diagram window for initialization VI LLL LLL  18  3 4 Icon connector for initialization VI 18  3 5 Front panel window for AWG screen capture VI  19  3 6 Program diagram window for AWG screen capture VI  20  3 7 Front panel window for Load All Channels profile block k 21  3 8 Program diagram window for Load All Channels profile block ecco cence 21  4 1 Topology of an ac adjustable speed drive  25  4 2 ASD dc bus voltage during normal operation  sss 28  4 3 One line diagram of a three phase short circuit fault  29  4 4 Voltage tolerance curve for ASDs based on various dc bus capacitances  a  31  4 5 ASD dc bus v
65. ide through capability of the ASD and  prevented it from tripping offline due to a    control power low    error for the three load conditions   For the test at full load  the ASD input voltage  current and dc bus voltage are shown in Appendix  E  The drop in speed and dc bus voltage is greater than for any of the two or three phase voltage  sags tested in the previous sections  Under the full load condition  the average dc bus voltage  falls to 69  of its nominal value  The speed of the motor during the voltage sag also decreased    by a significant amount  dropping by over 5  from its nominal value     Table 5 22  30  three phase voltage sag  modified configuration                AplidToqe N   0    10   20    447 5V  Drive Trip  Y N        A 50  three phase voltage sag was also applied to the input of the modified configuration  ASD  For all three load conditions  the ASD tripped offline due to a    control power low    error   For this ASD  even if the dc bus undervoltage protection fault had been turned on  the ASD  would not have tripped offline during the 30  three phase voltage sag  The undervoltage  protection fault is programmed to trip the ASD offline if the dc bus voltage falls below 395V   which is approximately 62  of the normal full load dc bus voltage     5 3 3 6 Three Phase Capacitor Switching Transient    The capacitor switching transient test was also performed on the S SkVA regular  configuration ASD  The output voltage of the programmable source recorded a
66. igger button and watch to see that the  highlighted position markers cycle through the transient waveform sequences as expected  for each channel     e Go back to the Setup Menu and turn the output of CH1  CH3  and CH4 ON     92    e Place the programmable source in PROGRAM  right side frequency selector switch   available options are VAR  400  60  50  and PROG     e Press the RESET button on the programmable source    e Press the OUTPUT ON OFF button on the programmable source    e Press the manual trigger button whenever a transient operation is desired  The manual  trigger button can also be executed remotely through the Execute Trigger VI in  LabVIEW     More detailed information concerning the operation and programming of the AWG is  given in the AWG2005 User Manual  More detailed information concerning the interface  between the AWG and the programmable source is given in the technical paper titled Using  the AWG2005 with the Behlman PA  Series Amplifiers by Jaye Killian     93  APPENDIX B  VIRTUAL INSTRUMENT FUNCTION BLOCKS    Given in Table B1 is a listing of the individual query function blocks for the AWG2005  LabVIEW instrument driver  Table B2 contains a listing of the individual action function blocks  for the AWG2005  The individual function blocks are stored in the Tek2005 instrument library  that can be found in the following path     C  Program Files National Instruments LabVIE W Instr lib Tek2005     Each individual function block title begins with  TKAWG200
67. igher voltage are performed     10     13     82    BIBLIOGRAPHY    Roger C  Dugan  Mark F  McGranaghan  and H  Wayne Beaty  Electrical Power Systems  Quality  McGraw Hill  1996     Math H  J  Bollen  Understanding Power Quality Problems  IEEE Press  2000     Tony Hoevenaars     A New Solution for Harmonics Generated by Variable Speed  Drives     Power Quality Assurance  vol  10  no  10  pp  24 30  December 1999     Richard A  Epperly  Frederick L  Hoadley  and Richard W  Piefer     Considerations When  Applying ASD   s in Continuous Processes     IEEE Transactions on Industry Applications   vol  33  no  2  pp  389 395  March April 1997     John Douglas     Digital Society     EPRI Journal  vol  25  no  4  pp  18 25  Winter 2000     Mark P  Mills and Peter W  Huber     Silicon Demand and the End of Power Quality      Power Quality Assurance  vol  11  no  10  pp  18 19  December 2000     Tekla S  Perry     Fueling the Internet     IEEE Spectrum  vol  38  no  1  pp  80 84  January  2001     Christopher J  Melhorn and Mark F  McGranaghan     Interpretation and Analysis of  Power Quality Measurements     IEEE Transactions on Industry Applications  vol  31  no   6  pp  1363 1370  November December 1995     Electric Power Research Institute  Power Quality Mitigation Technology Demonstration  at Industrial Customer Sites  Industrial and Utility Harmonic Mitigation Guidelines and  Case Studies  Palo Alto  CA  2000  1000566     Wilson E  Kazibwe and Musoke H  Sendaula  Electric Power 
68. in Fig  5 11  In this case  the input current on the sagged phase has  completely dropped out and only two of the six line to line voltage pulses are conducting current   meaning the three phase rectifier is operating as a single phase rectifier  This is because the  average dc bus voltage during the voltage sag  636 1V  is higher than the peak sagged line to line  voltage  619V      5 2 3 2 10096 Load    The input current for a 10  single phase voltage sag on phase    a     during a 100  load  condition is shown in Fig  5 12  This case is similar to the 596 single phase voltage sag during a  50  load condition  The current drawn by the sagged phase now has a single pulsed pattern   The average dc bus voltage during the voltage sag  624 5V  is only slightly higher than the peak  value of the sagged line to line voltage  619V         0 00000 0 02000 0 04000 0 06000 0 08000 0 10000    Figure 5 11  Input current  10  single phase sag  50  load     49       0 000             0 00000 0 02000 0 04000 0 06000 0 08000 0 10000    Figure 5 12  Input current  10  single phase sag  full load     5 2 4  13  Single Phase Voltage Sag    For a 13  single phase voltage sag on phase    a     the corresponding input phase and line to line  voltages are     V       23120        431V rms  609V peak   V   2662240     V    460V rms  650V peak   5 4   V   2662120     V    431V rms  609V peak     Table 5 4  Data from a 1396 single phase sag             5096 Load 100  Load  622 4V    Input Current in 
69. industry  In an open competition market  customers can choose their supplier of power   With no clear definition of responsibility for power quality and reliability  utilities are striving to  deliver power with a high reliability to meet customer expectations  yet do so in an economical  manner  2  5     Among consumers  power quality is important to sensitive and disturbing loads of all levels   including residential  commercial  and industrial users  One area of particular interest  termed the     digital economy     has been the development and growth of microprocessor based integrated    circuit applications  ranging from computers to phones to programmable logic controllers  PLCs      Many of these microprocessor based products are part of a larger infrastructure such as digital  networks  the internet  and broadband telecommunications which demonstrate just a few  examples of customers with increasingly exacting demands for power  5   According to the  Electric Power Research Institute  EPRI   information technology accounts for 13  of the  electricity consumption in the U S   and they believe that it may grow to 50  in the next twenty  years  5 6     The main motivator behind improving power quality is economic  An increased reliability of  electrical power  ideally for microprocessors  to 9 nines reliability  or 99 9999999  reliability   equates to increased productivity and profit margins  As an example  at Sun Microsystems Inc  in  Palo Alto  California  outages ar
70. ing Ride Through Capability for  Sensitive Customers on Underground Networks   IEEE Transactions on Industry  Applications  vol  33  no  4  pp  1083 1095  July August 1997     Mark Stephens  Chuck Thomas  Tom Paudert  and Bill Moncrief     PLC Basics and  Voltage Sag Susceptibilities     Part 1     Power Quality Assurance  vol  12  no  1  pp  43   47  January 2001     APPENDICES    86    87    APPENDIX A  PROCEDURE TO PROGRAM OPERATE AWG    1  Hardware Connections    The AWG is connected to the programmable source such that three of the four available  output channels drive the three PROGRAM inputs of the programmable source  Table A1 1 lists  the AWG channels and their specific configurations     Table A1 1  AWG channel configuration     AWG Channel Description   Connection To    Channel 1 AWG front panel   Programmable source Phase A 50 Ohm  PROGRAM input     EEN qmeenmene      Channel 3 AWG front panel   Programmable source Phase B 50 Ohm  PROGRAM input   Channel 4 AWG front panel   Programmable source Phase C 50 Ohm  PROGRAM input   Trigger Ipput   AWG front panel   Channel 2 MARKER output 50 Ohm   located on AWG rear panel     The AWG Channel 2 was chosen as a transient envelope generator for voltage transients   The Channel 2 MARKER OUTPUT is connected to the TRIGGER INPUT to be used in the    generation of transients               2  Programmable Source AWG Configuration    In PROGRAM mode  each phase of the programmable source is capable of generating a  maximum outpu
71. ing the correct GPIB address in the  appropriate command string  An instrument reset can also be executed in this VI  Common to all  VI front panel windows are the    error in    and    error out    dialog boxes that help to troubleshoot    problems when multiple subsystems are used within a VI                  VISA Session VISA Session  for class     Instrument Descriptor     GPIB0 20 INSTR    ID query Reset   pe Hres error in  no error   no no EE     status code   Iz Rp        source   m                 error out    status code      a  source      m          Figure 3 2  Front panel window for initialization VI                     Query ID and device type registers l   Open instrument Reset instrument Send default setup    default setup string  EAD OFF  VERB ON    e    L8  VISA Session  Es   5 7  error out       Figure 3 4  Icon connector for initialization VI     Another example of a very useful VI is the AWG picture capture VI  The front panel and  program diagram windows of this VI are shown in Figs  3 5 and 3 6  respectively  This VI takes  a snapshot image of the AWG front panel display and sends the image in a specified format back    19    to the computer  The image can then be imported into the VI front panel window  In Fig  3 5  the  imported image shows the AWG setup menu screen where file and configuration information  pertaining to the four output channels is displayed  In addition to determining which waveforms  are programmed into what channels of the AWG  the 
72. ion Files profile block  C5 1 Front panel window for Upload Sequence Equation File profile block  C6 1 Front panel window for Download Waveform File profile block  C7 1 Front panel window for Download Sequence Equation File profile block  C8 1 Front panel window for Define Compile Equation profile block  C9 1 Front panel window for Define Sequence File profile block  C10 1 Front panel window for General Command profile block  C11 1 Front panel window for Load All Channels profile block  C12 1 Front panel window for Set Operation Mode profile block  C13 1 Front panel window for Set Channel Output profile block  C14 1 Front panel window for Execute Trigger profile block  D1 1 Front panel window of standard subsystems in a profile block  D1 2 Block diagram window of standard subsystems in a profile block  D2 1 Program diagram window of a multiple subsystem profile block  D2 2 Program diagram window of a command string to write profile block  D3 1 Example icon connector  E1 1 ASD input voltage   95  single phase voltage sag  E1 2 ASD input current     full load  two phases shown   E1 3 ASD dc bus voltage     full load  El 4 ASD input voltage     100  single phase voltage sag  E1 5 ASD input current     full load  two phases shown   E1 6 ASD dc bus voltage     full load  El 7 ASD input voltage     50  two phase voltage sag   E1 8 ASD input current     full load  two phases shown   El 9 ASD dc bus voltage     full load  E1 10 ASD input voltage     50  three phase voltage sag   E1 1
73. is small due to the fact that most sags of this  type have at least one phase of the ac supply that does not significantly drop in voltage  thereby  helping to maintain the dc bus voltage     35    4 5  Improving ASD Ride Through Capabilities    Costly production downtime losses can be avoided by using ASDs with ride through  capabilities  There are several areas of focus for improving ASD ride through  These areas can  be grouped into the following classifications  4  29     e Energy storage methods   e Functional operation modes of ASDs   e ASD topology modifications   e Internal power supplied from the dc bus voltage    4 5 1  Energy Storage Methods    A number of energy storage technologies are available that can be configured to provide dc   bus power for an ASD PWM inverter in the event of a voltage sag or power interruption  These  storage systems can include battery backup systems  supercapacitors  or ultracapacitors   motor   generator sets  and Superconducting Magnetic Energy Storage  SMES   4  29  37   Only a  limited amount of additional stored energy needs to be supplied to the dc bus to improve ASD  ride through for the most common type of single phase faults    Battery backup systems can be installed as an add on module on the dc bus of an ASD  They  have a much higher energy per volume ratio than standard capacitors  Advantages are that they  can provide ride through for deep voltage sags  have a nearly instantaneous transfer time  and are  easily obtained  Di
74. is the THD of the current  using a 15 30 minute averaging  measurement period  normalized to the maximum rms value demand load current 7   fundamental  component  60Hz   The TDD allows harmonic currents to be evaluated over a wide range of load  conditions with a constant base value  Additional expressions commonly used to describe    measures of power quality in a power system are displacement power factor  DPF  and true    power factor  PF      DPF  cos   1 3     PF   c0s9  2  DPF  1 4     I     7 SP T  1 5     h i    In the above equations  J  is the rms value of the fundamental component of the current  J is  the total rms value of the current  and   is the phase angle between the voltage and current   Another expression used to indicate the additional eddy current heating losses in a transformer    due to current harmonics is the K factor  9  14      S HR  dno  1 6     The K factor equation  1 6  indicates that transformer heating losses are proportional to the    square of the load current and the square of the frequency     1 3  Harmonic Distortion Mitigation Techniques    Harmonic distortion in a power system can be controlled and negatively affected equipment  can be protected according to several different methods  One method involves resizing or adding  components to protect sensitive equipment  Examples of this are the use of larger phase and  neutral conductors  derating of transformers and motors  use of K rated transformers  and proper  sizing and de tuning of 
75. itude signal phase voltage sags     2096  are applied at the input  In normal  operation of a three phase diode bridge rectifier  each current phase has a double pulse as can be  seen in Fig  5 1 which shows the full load input current when a balanced 460V rms  line to line  voltage is applied at the input to the ASD  Each pulse corresponds to the period of time when the  input line to line voltage is higher than the dc bus voltage  causing a diode branch in the rectifier  to be forward biased  It will be shown that for relatively small single phase voltage sags     depending on the loading condition  which affects the average dc bus voltage   the input current    39    may have either a double pulse pattern that is unbalanced  a single pulse pattern  or a sagged  phase current that drops out completely     Input Current  A        7200 220 240 260 280 300  Time  ms     Figure 5 1  Input current drawn by an ASD at 100  load  one phase shown      5 2 1  296 Single Phase Voltage Sag    For a 2  single phase voltage sag on phase    a     the corresponding input phase and line to   line voltages are     V    26120   V    456V rms  645V peak   V    2662240     V    460V rms  650V peak   5 1   V   2662120    VV    456V rms  645V peak        Table 5 1  Data from a 2  single phase sag                    DC Bus Voltage  during sa 646 1V 640 2V 637 4V       Input Current in Sagged Phase   Description of Input Current in N A Largely unbalanced  Unbalanced  two  Sagged Phase two pulsed pu
76. k value of the sagged  line to line voltage  597V         0 10000       0 00000 0 02000 0 04000 0 06000 0 08000    Seconds    Figure 5 15  Input current  17  single phase sag  50  load     53       oamed    0 00000 0 02000 0 04000 0 06000 0 08000 0 10000         Seconds    Figure 5 16  Input current  17  single phase sag  full load     5 2 6  Summary of Results    A summary of the results of the single phase voltage sag affects on ASD three phase diode  bridge rectifier operation is presented in Table 5 6  For each single phase voltage sag magnitude  and under each load condition  a comparison is made between the average nominal dc bus  voltage  the peak value of the sag affected line to line input voltage  and the resulting input  current waveform pattern  As the sag magnitude increases and the loading factor decreases  the  input current on the sagged phase drawn by the ASD progresses from a balanced double pulsed  pattern  to an unbalanced double pulsed pattern  to a single pulsed pattern  and finally drops out  completely  For this specific 5 5 kVA ASD tested  for a single phase voltage sag of any  magnitude over 17   and for any loading factor  the three phase diode rectifier operates as a    single phase diode rectifier     54    Table 5 6  Summary of single phase sag testing                          Single Phase Voltage  Sag Percentage        DC Bus Voltage   during sag     Peak Value of  Voltage Envelope Current  Affected by the Sag Pattern    2  50  load 640 2V 645V 
77. le to Load in Phase A   abc       CHTAMPL    aks       CLOCKFREQ    Lats  i opy to Filepath       Errori  no Bro ront Panel Display Image  tu    Figure D2 2  Program diagram window of a command string to write profile block     3  Subsystem Icon Properties    The icon connector for the Load Channel Phase A Vl is shown in Fig  D3 1  Icon connectors  are used to implement subVIs into a profile block VI  The subVI parameters can be wired into  the profile block VI through the connector terminals  To set the terminal pattern connections for  the icon  open the subVI and right click on the icon and select Show Connector  The wiring tool  can then be used to assign control and indicator parameters from the front panel of the VI to the    specific terminals on the icon     108                  Amplitude  VISA Session et dup VISA session  File to Load in Phase A error out  error in  no error     Figure D3 1  Example icon connector     4  General Functionality and Setup    In addition to subVIs and commands concatenated into strings  other functionality for  programming profile block VIs is available in the LabVIEW environment  The Function menu  includes a section divisions for structures  string operations  Boolean logic  numeric operations   arrays  I O commands  data comparison  data acquisition  instrument drivers  clusters  and data  analysis  The blocks available in the Function menus enable specific monitor and control  commands to be executed    After profile block components
78. lies   e Silicon controlled rectifier  SCR  drives   e Arc furnaces and welders   e Air conditioners and compressors  HVAC    e Elevators   e Fluorescent lighting  electronic ballasts    Most of these harmonic generating loads consist of solid state rectifiers at their inputs  connected to a dc bus maintained by capacitors  Solid state rectifiers draw current in pulses  when the input ac line voltage is higher than dc bus voltage across the capacitors  As current  harmonics are injected back into the system  voltage drops are caused at the corresponding  harmonic frequencies  creating voltage distortion in the power system  The voltage distortion is  directly proportional to the current harmonic magnitudes and the impedance in the system  cables  and transformers   9      Some common effects of harmonic distortion are listed below  1 3 9 11      Harmonic voltage stress on system capacitors and equipment capacitors  Resonance and overloading problems with power factor correction capacitors    Additional heating and losses in conductors  transformers as well as induction and    synchronous machines  Interference with communications circuits  Misoperation of circuit breakers  PLCs  computers  and other sensitive solid state loads    Voltage distortion at the PCC    According to IEEE 519     IEEE Recommended Practices and Requirements for Harmonic    Control in Electrical Power Systems  harmonic limits are meant to be applied at the point of    common coupling  PCC  between the u
79. load Waveform File vi Transfers a file with a  WFM extension from the  internal memory of the AWG to a specified directory    in the computer              Upload Sequence Equation File vi Transfers a file with either a SEQ or  EQU extension  from the internal memory of the AWG to a specified    directory in the computer             Download Waveform File vi Transfers a file with a  WFM extension from a  specified directory in the computer to the internal  memory of the AWG  file must have been previously    uploaded from the AWG                Download Sequence Equation File vi   Transfers a file with either a  SEQ or  EQU extension  from a specified directory in the computer to the  internal memory of the AWG  file must have been    previously uploaded from the AWG                Query Internal Memory vi Returns to the VI front panel window a catalog of  each file contained in the internal memory of the    AWG          23    Table 3 2  AWG file creation driver profile blocks     Virtual Instrument Profile Block Functional Description    Define Compile Equation File vi Creates a  EQU file from a given equation  expression  and also compiles the  EQU file into a   WFM file according to an input number of  waveform points     Create Sequence File vi Creates a  SEQ file from a given combination of   WFM files and each associated number of repeat  cycles     General Command vi Can be used to execute any combination of  waveform edit functions     Table 3 3  AWG setup and operatio
80. lock executes a general command to the AWG  The  Command to Execute parameter must be in all caps and should be formatted according to the    AWG2005 programmer s manual  The General Command profile block also includes the AWG    101    picture capture VI  also shown in Figs  3 4 and 3 5  as a subsystem  The AWG picture capture VI  is useful for ensuring that the AWG has been setup as expected after running a profile block and  is therefore included as a subsystem in several profile blocks  The Copy to Filepath  Hard Copy  To  and Image Format parameters all pertain to the AWG picture capture VI  The AWG screen  image must be imported into the Front Panel Display Image window  after the profile block has  been executed  After running the VI  select Edit     Import Picture from File  Select the saved    bitmap file and click Open  Then right click on the Front Panel Display Image window and  select Import Picture     11  Load All AWG Channels    Copy to Filepath  IRIC Evelyn TekAWG testbmp    selected port  computer      D    Continuous mode Master Running       ile to Load in DC Trigger           PDC NOM WFM  PHA NOM NT N    Amplitude  DC Trigge    Filter  Amplitude  Offset       Figure C11 1  Front panel window for Load All Channels profile block     The Load All Channels profile block loads either  SEQ or  WFM files into each of the four  channels of the AWG  The filename and amplitude for each AWG channel must be specified     The AWG picture capture VI is also included as
81. ls  and transfer files back and forth between the  computer and the AWG  A complete listing of the individual function VIs for the AWG2005  instrument driver library is provided in Appendix B     22    The profile blocks created can be divided into three groups as were defined in the main  objectives for the driver database  The first group of profile blocks includes storage and transfer  functionality to download and upload complete voltage disturbance event files to and from the  AWG  The second group of profile blocks includes the functionality to create new equations   sequences and waveforms as well as modify existing files  The third group of profile blocks  includes setup and control functionality to load a voltage disturbance event  configure the mode  of operation settings  set the channel output  and control transient waveform generation  Tables  3 1  3 2  and 3 3 show a listing and description of the profile blocks created for the AWG   separated into the three main functionality groups     Table 3 1  AWG data transfer driver profile blocks     Virtual Instrument Profile Block Functional Description    Upload All Waveform Files vi Transfers all files with a  WFM extension from the  internal memory of the AWG to a specified directory  in the computer                       Upload All Sequence Equation Files vi   Transfers all files with either a  SEQ or  EQU  extension from the internal memory of the AWG to a    specified directory in the computer                  Up
82. lsed       41    highest value  The next current pulse in the cycle  i   V4   is low  causing an unbalance in the  phase current pulses  because V is sagged  645V peak  and the dc bus voltage has not had much  time to discharge from its peak value  The following current pulse  i   Vac  is higher than the  previous pulse since the previous pulse did not recharge the dc bus voltage to its peak value  This  current pulse is still smaller than the i   Va  current pulse since Vac is also sagged  645V peak    The next current pulse i   Vi  is again the highest current pulse since Vy  is not sagged  This    cycle continues and results in an unbalanced phase current pattern     5 2 1 3 100  Load    The input current drawn during a 2  single phase voltage sag on phase    a    during a full load  condition is shown in Fig  5 8  Similar to the case for a 5096 load condition  the double pulse  current pattern is unbalanced  but not as drastically as in the 50  load condition  This is because  during full load  more current is required by the load and the average dc bus voltage is lower   637 4V   Because the average dc bus voltage is lower  the i   Va  current pulse will charge the    dc bus for a longer time     phase a     205 00    0 0    e     205  VAAN       UVVU VUV LUV VU   0 00000 0 02000 0 04000 0 06000 0 08000 0 10000    Seconds    Figure 5 2  Input phase voltage  2  single phase sag on phase    a        42    675 00 f  gt  de bus       average     646 1V        E1          600
83. m points as the other three    channels  1000  and is a constant nonzero dc value     4  Basic Steady State Operation    With the default conditions configured according to the previous section  a continuously  repeated three phase sine waveform at a nominal voltage of 266V rms L N can be output from  the programmable source  The following steps describe steady state operation of the  programmable source    e Place the AWG2005 in Setup Menu  Check to make sure the correct output waveforms  are loaded for each channel  the clock frequency and channel amplitudes are set correctly   and that the outputs of CH1  CH3  and CHA are turned ON  turn CH1  CH3  CH4 output  ON by pressing the buttons above the output BNC connectors   DO NOT TURN THE  AWG OUTPUTS ON OR OFF WHEN THE PROGRAMMABLE SOURCE OUTPUT  IS ON     90    e Place the programmable source in PROGRAM  right side frequency selector switch   available options are VAR  400  60  50  and PROG   This step assumes that the  programmable source itself has already been powered up    e Press the RESET button on the programmable source    e Press the OUTPUT ON OFF button on the programmable source    If changes to the output of the AWG are desired  turn the output of the programmable source off   switch the frequency selection back to one of the other positions  VAR  400  60  50  and press the  RESET button  Then make any configuration parameter changes to the AWG and repeat the  process  It may be possible to change the clock frequ
84. m possible programmable source output is 326V rms  although  the rated maximum  output voltage is 305V rms   Therefore  the maximum peak voltage output of the programmable  source is 460V L N  800V L L      3  Default Conditions    All setup of the AWG must be completed BEFORE the output of the programmable source is  turned ON  The default settings of the AWG Setup Menu are listed below     e CLOCK  60kHz  e WAVEFORM SEQUENCE  CHI  PHA NOM WFM  CH2  DC NOM WFM  CH3  PHB NOM WFM  CH4  PHC_NOM WFM  e CHI OPERATION  Normal  e FILTER  CHI  Through  CH2  Through  CH3  Through  CH4  Through  e AMPLITUDE  CHI  10 0V  CH2  1 0V    CH3  10 0V   TRACK CHI    89    CH4  10 0V   TRACK CHI  e OFFSET   CHI  0 0V   CH2  0 0V   CH3  0 0V   CH4  0 0V  e OUTPUT   CHI  ON   CH2  OFF   CH3  ON   CH4  ON    In addition to these default Setup Menu settings  the operation mode  specified in the Mode  Menu   should be set to Continuous mode  Each  WFM file should have a standard of 1000  waveform points  The actual output frequency of the AWG  60Hz  is equivalent to the clock  frequency  60kHz  divided by the number of waveform points  1000   The three phase  waveforms are each single cycles of a sine wave  with a common amplitude  0 815 peak   and  where each waveform is shifted by the proper phase angle  120 degrees  to supply a balanced  three phase output  The DC NOM WFM in channel 2 serves no real purpose in a steady state  operation condition  For simplicity  it has the same number of wavefor
85. more    three phase loads are phase shifted from one another through various types of three phase  transformer connections  The sum of the current drawn is then less distorted than the original  nonlinear current drawn by each individual load  For example  in a system with several ASD  loads  some loads can be supplied by delta delta connected transformers and other loads can be  supplied by delta wye connected transformers  If the loads on each drive isolation transformer  are balanced  harmonic current distortion can be significantly reduced  In some applications  where a neutral point for grounding is desired  a delta zigzag transformer provides the same  harmonic cancellation effect when used with loads also supplied by a delta wye connected  transformer    Filtering is another method for reducing harmonic currents in a power system  Many  topologies of harmonic filters are used with three general categories being passive  active  and  hybrid filters  3  9  15  19 20   Passive filters consist of tuned LC filters which can be connected  in shunt or in series at a point where nonlinear loads are concentrated or at an individual  nonlinear load  They can be tuned to block or trap single frequencies or multiple stages can be  used for more than one frequency  A shunt passive filter creates a low impedance path for  harmonic currents at its tuned frequency  thereby trapping or diverting the harmonic current from  flowing into the power system  A series passive filter creates a
86. n cause ASDs to trip offline are as follows  2  14  29 34      e The ASD controller may be programmed to trip the drive offline upon detection of a sudden  change in operating conditions    e A voltage sag which leads to a drop in the dc bus voltage may cause the ASD controller or  the PWM inverter to trip the drive offline    e A voltage sag which leads to insufficient voltage for maintaining the ASD   s internal power  supply voltage used for powering control logic may cause the ASD to trip offline    e A voltage sag which leads to insufficient voltage for maintaining the ASD   s external interface  and control circuitry such as contactors  relays  and PLCs    e A voltage sag can lead to an ASD overcurrent trip due to increased ac current drawn during  the voltage sag or due to high current spikes that charge the dc bus capacitor immediately  following the voltage sag    e An ASD may trip due to motor changes such as a drop in speed or torque variations that the    load process cannot tolerate     Of the six circumstances listed above that cause ASDs to trip offline  the two main causes are  reduced dc bus voltage and reduced internal power supply and external circuitry voltage  During  voltage sag conditions  the motor load power level  dc bus capacitance  internal power supply  design  and dc bus undervoltage trip level all affect whether or not the drive will trip offline  For  single phase voltage sags  two of the phase to phase voltages are affected  Because one of the
87. n driver profile blocks     Virtual Instrument Profile Block Functional Description    Load All Channels vi Loads either  WFM or  SEQ files into each of the  four AWG channels  Also sets channel parameters  including clock frequency  and amplitude        Set Operation Mode vi Sets the AWG operation mode to either continuous   used for steady state waveform tests  or waveform  advance mode  used to simulate transient    disturbances      Set Channel Output vi Turns the output of each of the four AWG channels  on or off     Start Stop Trigger vi Executes a trigger start operation  This is used in  waveform advance mode to trigger the transient  waveforms in the  SEQ files to execute and then  return to the nominal waveform set        Each of the profile blocks described in Tables 3 1  3 2  and 3 3 is more thoroughly referenced in  Appendix C  Appendix C shows the front panel windows for each profile block and gives an  explanation of how to configure the parameters in each profile block to execute power quality    disturbance simulations     25    4  ADJUSTABLE SPEED DRIVE PROPERTIES    4 1  Adjustable Speed Drive Topology    Induction motors are the workhorse of industry due to their low cost and rugged construction   Over the years  the integration of adjustable speed drives  ASDs  is increasing due to improved  efficiency  process control  and productivity  Earlier applications of ASDs were largely in fan  and pump loads where speed control resulted in significant energy con
88. nced  voltage sags  Balanced three phase voltage sags can be caused by the starting of large induction  motors or three phase short circuit faults  Two common types of unbalanced three phase voltage    sags can be caused by single phase short circuit faults or phase to phase short circuit faults     4 3 1  Balanced Three Phase Voltage Sags    A balanced three phase short circuit fault can be depicted in a one line diagram as shown in  Fig  4 3  All three phases drop in magnitude by the same amount and all six voltage pulses per  cycle of the dc bus voltage will drop in magnitude  The phase voltages for a three phase fault can  by expressed as  35 36      V   V   V   My  Miv v3  pu   4 1   V   Vv      iv v3    Fault       Figure 4 3  One line diagram of a three phase short circuit fault     In  4 1   V  is the per unit magnitude of the sag voltage  The three phase short circuit fault results    in a voltage sag that can be approximated by     Z  V         _ E u 4 2  sag 3o Z  n 2   p          30    It can be assumed that the pre fault source voltage  E  is equal to lpu  Zs is the source impedance  at the point of common coupling and Zr is the impedance between the point of common coupling  and the fault  The results are very similar for a three phase voltage sag caused by the starting of a    large induction motor  The voltage sag magnitude can be approximated by     Zu             4 3  sag  3   Ze   Zi  pu         In  4 3   a source voltage of 1pu has been assumed  Zs is the 
89. nctionality    The development of a LabVIEW driver database for the AWG which creates and executes  multiple types of voltage disturbances to be amplified and output by the programmable source is  an ongoing project  The functionality of the driver database can continue to expand as more  power quality research and testing projects occur  One proposed remotely operated testing  capability has been suggested by local utility companies  In this proposed addition  voltage  disturbance events would be captured in the field by event monitoring equipment  These events  would then be downloaded and converted into waveform data files for the AWG  enabling the  programmable source to reproduce events and anomalies that occur in a power system    As mentioned in an above section  the capability to program  monitor  and control the PQTP  over the internet will open up a wide range of collaborative research efforts  For the purposes of  this thesis work  all LabVIEW control was performed over the GPIB interface through a direct  connection between the AWG and PC  With new National Instruments GPIB to Ethernet  controller hardware available  multiple instruments including the AWG  can be remotely  controlled over the internet through LabVIEW  In addition to configuring the hardware to control  the AWG over the internet  other monitoring instrumentation could be configured for ethernet  access through LabVIEW as well  It would then be possible to monitor the output of the  programmable sou
90. ng portions of every cycle  The transition  point at which the dc bus voltage is always higher than the peak value of the sag affected line to   line voltage is different for every ASD and for different load conditions of the ASD  since  different load conditions affect the size of the dc bus ripple   For the 5 5kVA ASD tested  a  17  single phase voltage sag was the transition point where for all load conditions  the dc bus  voltage was always higher than the sag affected line to line voltage  causing the three phase  rectifier to operate as a single phase rectifier    Through the results of this testing it has been determined that the method of deriving control  logic power for an ASD is a critical factor in the ride through capability of many ASDs  The  control logic power supply supports the control electronics so the drive can perform calculations   make decisions and control the inverter switches creating the variable frequency  variable voltage  output to the motor and the load  Many ASD topologies use linear power supplies powered from  two phases of the ac input voltage to derive control logic power for the ASD  31 34   as was the  case with the second 5 5kVA ASD tested  It was determined that ASDs with control logic power  derived directly from the input power in general  and a single phase  line to line  in particular   are extremely sensitive to voltage disturbances and are much more likely to trip off line due to a     control power low    condition  Many ASD man
91. ock creates a specified  EQU file in the internal  memory of the AWG  A  WFM file is generated from the  EQU file according to the time range   equation expression  and number of Waveform Points specified  The Equation File  Byte Count   Number of Characters  Waveform Points  and Equation Data parameters should be specified  prior to running the profile block VI  A  WFM file will be generated with the same name that is  specified in the Equation File parameter  Data for Equation File must be written in ASCII code  with each expression separated by a Line Feed   lt LF gt    each expression should be created on a    new line  The first line should be the waveform range  listed in the following format   e range Equation Starting Time  Equation Ending Time   The following lines consist of the equation where   e x  variable taking on a value from 0 0 to1 0 within the range    statement  e v   variable showing the current value of the waveform data at that position  used to  begin a new line in the equation    The Number of Characters parameter sets the number of characters used in the Equation Data  input box  Characters include letters  numbers  punctuation marks  and line feeds  new lines      The equation example in Fig  C8 1 has 30 characters and a byte count of 2     9  Define Sequence File    Reset  Overwrite    Sequence File Yes existing  error out     l TEST sEQ    No  yes  no    Byte Count Number of Characters    error in  no error        Figure C9 1  Front panel window f
92. of the 5 5kVA ASD with the internal  power supplied from two of the three input phases  a modified configuration of the ASD was  tested and the ride through capabilities compared with the original  regular configuration of the  ASD  As was demonstrated in this case  the PQTP can be used to test different ASD ride through  improvement technologies    The PQTP is not limited to power quality voltage disturbance testing of ASDs  Many other  types of commonly used power electronic equipment are sensitive to voltage sags and other  disturbances  and would benefit from thorough ride through characterization testing  Two  examples of sensitive power electronic equipment are switch mode power supplies and    programmable logic controllers     6 3 3  Additional Proposed PQTP Functionality    Currently  the maximum peak output voltage capability of the programmable source is  approximately 460V line to neutral  In program mode  the output of the AWG is passed through  a set of amplifiers and then fed through a step up transformer to the output of the source  The  maximum peak output voltage of the source is limited by the step up transformer ratio  In some  cases  it may be desirable to simulate very high voltage transients  For extended peak voltage  capabilities  the step up transformer can be multi tapped or a second step up transformer can be  installed  Since the amplifier switch ratings would still be the same  the overall power output    rating would be smaller when tests at a h
93. oltage during a single phase fault     32  4 6 ASD dc bus voltage during a phase to phase fault  ss 33  5 1 Input current drawn by an ASD at 100  load  one phase shown    39  5 2 Input phase voltage  2  single phase sag on phase  0  eee eee 41  5 3 ASD dc bus voltage  2  single phase sag  no load  at 0 02 seconds  Bee ey enal Kee 42  5 4 Input current  2  single phase sag  no load  phases    a    and    c    shown   we 42  5 5 ASD dc bus voltage  2  single phase sag  50  load  43  5 6 Input current  2  single phase sag  50  load  phases    a    and    c    shown     43  5 7 ASD dc bus voltage  2  single phase sag  ull load 44  5 8 Input current  2  single phase sag  full load  phases    a    and    c    shown     ee  44  5 9 Input current  5  single phase sag  50  load  46  5 10 Input current  5  single phase sag  full load 47  5 11 Input current  10  single phase sag  50  load  48  5 12 Input current  10  single phase sag  full load    49  5 13 Input current  13  single phase sag  50  load  50    LIST OF FIGURES  Continued     Figure Page  5 15 Input current  17  single phase sag  50  load  52  5 16 Input current  17  single phase sag  full load 53  5 17 ASD input voltage   90  single phase voltage sag  LLL 58  5 18 ASD input current     full load  two phases shown  ss 58  5 19 ASD dc bus voltage     full load  58  5 20 ASD input voltage     100  single phase voltage sag j 59  5 21 ASD input current     full load  two phases shown  kkk 60  5 22 ASD dc bus voltage     full lo
94. onsisted of a 5 5kVA  460V line to line  ASD supplying a four pole  Shp  induction motor  The internal power supply of the second 5 5kVA ASD is derived from two  phases of the three input phases to the ASD  Again  the motor was loaded by a 15hp dc generator  where the dc power was dissipated in a 25kW resistive load bank  All of the ASD configurations  and settings were kept to the factory default conditions  The PWM inverter switching frequency  was set to 2 2kHz  Similar to the previous ASDs tested  there are a few ride through options  available with this ASD  One option is a regeneration power ride through control that uses  regenerated energy from the rotating motor when a momentary power failure occurs  The  maximum regeneration power ride through time can also be specified  Another option is auto     restart which determines the speed of the motor and outputs a matching frequency and voltage    68    when input power returns to enable a smooth restart of the motor  Both of these options were  turned off during testing  The ASD also has an undervoltage trip selection parameter with a  factory set undervoltage trip level  When the undervoltage trip selection is    on     an undervoltage  detection time parameter can also be specified  During the testing  the undervoltage trip selection  parameter was turned    off       As is shown in the testing results  the ASD internal power supply is highly susceptible to  voltage sags that cause the ASD to trip offline due to a    c
95. ontrol power low    condition  In order  to improve the ride through characteristics of the ASD  the single phase transformer and rectifier  used to step down the input ASD voltage to the internal power supply was replaced with a three   phase transformer and rectifier  The regular configuration experimental results in this section  refer to the ASD configured with a single phase transformer front end to the internal power  supply  The modified configuration experimental results refer to the ASD configured with a  three phase transformer front end to the internal power supply  In the regular configuration  the  two of the three input phases that supply the internal power supply through the single phase  transformer shall be referred to as phases    b    and    c     Therefore  phase    a    input to the ASD  does not affect the magnitude of the internal power supply voltage    The ASD was tested with several magnitudes of single  two  and three phase voltage sag  disturbances  Different magnitudes of voltage sags were applied to the regular and modified  configuration ASD  dependent on each configuration   s offline trip level sensitivity  In all cases  the voltage sag disturbance sequences were generated for 300 cycles  or 5 seconds  The ASD was  also tested with a three phase capacitor switching transient waveform  The switching transient    had a frequency of 480Hz  and was four cycles  therefore 8 33ms in duration     5 3 3 1 Single Phase Voltage Sags     Regular Configur
96. or Define Sequence File profile block     100    The Define Sequence File profile block creates a specified  SEQ file in the internal memory  of the AWG  The  SEQ is compiled with a set of  WFM files  each with a specific repetition  number  that are listed in the Sequence Waveforms and Repetition Numbers parameter  The  Sequence File  Byte Count  and Number of Characters parameters should also be specified prior  to running the profile block VI  Waveform data for sequence file must be written in ASCII code  with each expression separated by a Line Feed   lt LF gt    each waveform expression must be on a  new line  The first waveform entered in the sequence should be the nominal continuously output  waveform  Each successive waveform should be entered on a new line  After each waveform is  entered  the number of repetitions  number of times executed  of each waveform should be  separated by a comma and a space  The first waveform  nominal  is usually repeated once   Similar to the Define Compile Equation profile block  the Number of Characters parameter    includes letters  numbers  punctuation marks  spaces  and line feeds  new lines      10  General Command    Copy to Filepath  PIC  Evelyn TekAWG testbmp      Hard Copy To   selected port  computer 30 Apr 01 21 22 16    CH4     RC V  CR  Ed        OT    Advance       ntigure  Triggered  Gated  Waveform  autostep uiu  Slave    Figure C10 1  Front panel window for General Command profile block     The General Command profile b
97. output voltage will result  with a 10 0V amplitude setting    After the nominal and transient waveforms have been created for a specific transient  operation   SEQ files need to be created for each of the four AWG channels  The first  WFM file  in each sequence should be the nominal case waveform  Each successive  WFM  there can be  multiple  file should be a transient waveform with markers set accordingly  A general list of the  steps necessary to create a transient waveform operation is shown below    e Generate a nominal case waveform   WFM  file for each of the four AWG channels    e Generate a transient case waveform   WFM  file for each of the four AWG channels   Transient waveforms should be the same length as the nominal case waveforms and have  markers set HIGH near the beginning and LOW near the end of the waveform  The  amplitudes of the transient waveforms must be scaled to end up as desired according to  the amplitude factor set with the nominal case waveforms    e Generate a sequence   SEQ  file for each of the four AWG channels  The sequence files  should include the nominal case waveform as the first file  and the transient case  waveform as the second file  Multiple transient case waveforms can be entered    e In the Setup Menu  load the  SEQ files into each of the four AWG channels  Also  set the  appropriate clock frequency and amplitude factors    e Inthe Mode Menu  select WAVEFORM ADVANCE and RUN  CONTINUOUS    e While still in the Mode Menu  press the tr
98. ped offline  For the test at no load  the  ASD input voltage  current and dc bus voltage are shown in Figs  5 26  5 27  and 5 28   respectively  Again  the increase in the ripple voltage on the dc bus and the decrease in motor    load speed are more dramatic than for the single phase voltage sags     Table 5 10  50  three phase voltage sag results            Applied Torque Nm    0   1   20      Spedapm aR    1787   172      D  vTip YN            N   v    v                      gt   365 090 00000 0 20000 0 40000 0 60000 0 80000 1 00000    Figure 5 28  ASD dc bus voltage     no load     63    53 43 Three Phase Capacitor Switching Transient    Shown in Fig  5 29 is the AWG front panel display and test setup to simulate a three phase  480Hz capacitor switching transient  These waveforms were created in the AWG by  superimposing a damped high frequency  480Hz  sine wave with a nominal 60Hz sine wave  The  peak phase voltage value of the transient was approximately 450V  Fig  5 30 shows the output of  the programmable source recorded at the input of the ASD  It can be seen that the output of the  programmable source produces a very good representation of the input waveform sent from the  AWG  The ASD was not at all affected by the capacitor switching transient  under all load    conditions  The dc bus voltage and the motor speed were both maintained at their normal levels     GPIB  Wavelorm Advance mode Master Running  5 en aten Riera 18 Dec 00 13 26  24                            
99. performed  by creating a set of three equation files in the AWG that detailed the percentage of each harmonic  added to the fundamental component  The equation files were compiled into single cycle  waveform files which were then output by the programmable source  The benefits of conducting  this type of analysis are to determine the effects of pre existing harmonics on induction motors     This will likely be the focus of future graduate work        Figure 5 31  Output of programmable source with 10  voltage total harmonic distortion     77    78    6  CONCLUSIONS    6 1  Benefits of the POTP    A unique and versatile Power Quality Test Platform  PQTP  has been implemented in the  MSRF at OSU  The central component of the PQTP is a 120kVA programmable ac power source  that is interfaced with an AWG  When combined with the 500hp test bed  300hp dynamometer   and 750kVA dedicated lab transformer  the MSRF has the highest power rating and power quality  testing capabilities of any educational research facility in the U S  Until recently  most research  relating to the effects of power quality disturbances on sensitive power electronic equipment has  been based on theoretical analysis of equipment architecture  system simulation  industrial  customer surveys  and monitoring and recording of power quality disturbances in field  applications    The laboratory creation of realistic voltage disturbance conditions has the advantage of  producing a more accurate characterization of th
100. pter 6 is the concluding chapter where experimental and theoretical ASD ride   through results are discussed  Also future work and recommendations are made pertaining to    both the power quality test platform capabilities and ASD ride through research     11    2  POWER QUALITY TEST PLATFORM    2 1  Equipment Setup    The power quality test platform  PQTP  has been implemented in the Motor Systems  Resource Facility  MSRF  at Oregon State University as shown in Fig  2 1  The input of the  programmable source is protected through a 200A circuit breaker and the output is directly wired  to a three phase terminal connection box  The output terminal connection box consists of several  types of connectors enabling a variety of test loads to be fed from the programmable source  A  PQ power analyzer is configured between the output of the programmable source and the input of  the test load  The PQTP has been installed such that either of the MSRF test beds can be supplied  by the programmable source  in addition to several of the laboratories in the Dearborn Hall  basement  For the purpose of this thesis  all experimental work has been performed with the 15hp  test bed used as a test load for the PQTP     Dedicated    Utility Supply  750 kVA           Auto 480  0 to 600  Transformer       Motor Motor  500 h 50 h  Starter    B  Starter di    Torque Speed de supply  1 Transducer ot resistive  U load          System Under Test         120kVA  Programmabie    t  1  Li  LI  1     t  4  
101. pters  Chapter 1  provides background information on power quality and why it is an important issue among  electric utilities and end use consumers  Also discussed are the classifications of power quality  disturbances  causes and effects of waveform harmonics  and mitigation techniques for waveform  harmonics  The definition of the thesis research project is also summarized    In Chapter 2  the equipment configuration of the power quality test platform is described   The test capabilities of the power quality test platform are outlined and the general operation and  control of the test platform is explained    Chapter 3 provides a short overview of the LabVIEW programming environment  Also  presented is a detailed description of the development of a LabVIEW driver database which is  used to program  monitor  and control the power quality test platform   s arbitrary waveform  generator    Included in Chapter 4 is an explanation of the architecture of a three phase voltage source  inverter adjustable speed drive  Also described is the theoretical background behind the  susceptibility of ASDs to voltage sags  Additionally  methods for improving ASD ride through  capability are presented    Chapter 5 presents experimental results of ASD ride through characterization obtained from  testing with the power quality test platform  Comparisons are made between different  architectures of ASDs and ride through performance is evaluated for multiple types of voltage  sags    Finally  Cha
102. rce and other various parameters associated with a particular PQ testing    program through LabVIEW in local and remote locations     6 3 2  Additional Proposed Ride Through Testing    In this thesis  the ASD ride through characterization testing was performed on 5 5kVA and  l1kVA ASDs supplied from two different manufacturers  More supporting results can be  obtained by testing ASDs from other manufacturers  With the PQTP  ASDs can be tested with  ratings up to 100kVA and motor loads up to 100hp  It would be beneficial to characterize ASD  ride through performance over the entire range of 5 5kVA to 100kVA  In addition to testing the  affects that PQ voltage disturbances have on the ride through capabilities of ASDs  it may also be  beneficial to characterize the affects that PQ voltage disturbances have on ASD efficiency  A    research proposal is currently under review that would incorporate both the wide range of ASD    81    ride though testing as well as the characterization of PQ voltage disturbance affects on ASD  efficiency    DC output ASDs are still very common in many industrial applications requiring wide torque  and speed ranges  and are also susceptible to many of the same power quality voltage  disturbances as ac ASDs  The PQTP could be used to characterize the ride though capabilities of  a variety of sizes of dc drives    The ASDs tested in this thesis were standard  mass produced ASD models configured  without additional ride through protection  In the case 
103. rol power low    error     Table 5 16  65  single phase voltage sag  phase    a     regular configuration                Applied Torque Nm    0   10   2    Speed  rpm   Drive Trip  Y N        The test results for a 100  single phase voltage sag on phase    a    supplying the ASD are  shown in Table 5 17  For the three load conditions  the ASD did not trip offline  For the test at  full load  the ASD input voltage  current and dc bus voltage are shown in Appendix E  The  resulting drop in dc bus voltage and motor speed are again the same as for the 63  and 65   single phase voltage sags  Similar to the 65  single phase voltage sag  a 100  single phase  voltage sag on phases    b    or    c    causes the ASD to trip offline under all load conditions due to a     control power low    error  The dc bus voltage maintained during a complete single phase outage    for 5 seconds is high enough to support operation of the ASD as was also demonstrated with the    70    earlier tests involving the first 5 5kVA ASD and the 11kVA ASD with internal power supplied  from the dc bus voltage  However  this second 5 5kVA ASD configuration with the internal  power supply drawing from two of the three input phases  causes the ASD to trip offline due to a     control power low    error for any single phase sag greater than 63  of nominal on either of    66  5    phases    b    or    c     Table 5 17  100  single phase voltage sag  phase    a     regular configuration           AppledTorqe N       
104. sadvantages are that additional space is required  they have a relatively low  cycle life  and require more maintenance    Supercapacitors  commonly electrochemical capacitors  are similar to batteries in that they  use liquid electrolytes and can be configured to meet a wide range of power  energy  and voltage  requirements  While they don   t have quite the energy density of batteries  they do have the  highest energy density of any capacitor technology  a high cycle life  are maintenance free and  the lowest cost capacitor technology    A motor generator set  M G set  uses its rotating mass to supply energy to the dc bus during  a voltage sag or interruption  and a diesel engine can be used to supply energy to the generator  during sustained outages  M G sets are reliable  but require maintenance and are more expensive  than battery systems    A SMES system circulates a large amount of current in a superconducting coil or magnet that    can be supplied to the dc bus during a voltage sag or interruption  SMES systems are highly    36    efficient  and provide rapid response  but also require extensive refrigeration to cool the  superconducting system    Additional standard capacitors can also be added to the dc bus to improve ASD ride through   Calculations for additional capacitance needed to maintain a minimum dc bus level were shown  in a previous section and based on conservation of energy  Another approximation to calculate    additional capacitance needed to enable a 
105. sag and is automatically restarted when the dc bus voltage  recovers  However  the inverter is restarted at a user defined preset frequency which usually  leads to large drops in motor speed  This kind of restart feature is sometimes also referred to as    non synchronous restart     37    Flying restart is a more complex form of automatic restart that is also referred to as  synchronous restart  The flying restart feature attempts to resynchronize the spinning motor after    the dc bus voltage has been restored  resulting in only a limited drop in motor speed     4 5 3  ASD Topology Modifications    An ASD can be modified or a new drive can be designed to include a boost converter which  maintains the dc bus during a voltage sag or interruption  When the dc bus voltage falls below a  certain level  the boost converter transistor switch will adjust its duty cycle to regulate the dc bus  voltage to the minimum voltage required by the PWM inverter  A boost converter circuit can  provide ride through capabilities for voltages sags without additional energy storage  4  29  40    In order to provide ride through capabilities for outages  an energy storage device would need to  be integrated with the boost converter design    Another modification that can improve ASD ride through is to replace the front end  uncontrolled diode rectifier with a controlled rectifier enabling better regulation of the dc bus  voltage  A controlled rectifier would also reduce lower order input current h
106. servation  with reported  values up to 35   with very short payback times  and in these applications the dynamics of speed  control were not necessarily very fast or precise  More recently  the cost of ASDs has been  decreasing and their performance has been improving  Today  ASDs are used in many additional  industrial applications including semiconductor manufacturing  paper machines  winders   extruders  metal casters  and overhead cranes  4 29   Currently  18  of all new motor  installations and 12  of existing motor systems in the U S  are driven by ASDs  14     Speed control of induction motors is commonly achieved through voltage source inverter  adjustable speed drives  The typical configuration of an ac ASD is shown in Fig  4 1  At the  input is an uncontrolled three phase diode bridge rectifier that supplies the dc bus  The dc bus  ripple voltage is minimized by the dc bus capacitor  The dc bus voltage is inverted to a variable  frequency  variable magnitude ac voltage by a pulse width modulated  PWM  inverter  The  speed of an induction motor can be varied by controlling the voltage frequency  f  applied to the  stator  For the torque capability to equal the rated torque at any frequency  the airgap flux should  be kept constant and equal to its rated value by controlling the magnitude of the applied voltage   Vs  in proportion to the frequency  Over a large range of the motor torque speed characteristic   the V  frelationship is linear  13      Diode  Rectifier de
107. single phase rectifier is dependent on the parameters of the ASD  primarily the  dc bus capacitor size  and the load condition of the ASD  both of which affect the dc bus ripple  voltage    The ASD ride through characterization testing involved supplying ASDs under different load  conditions with increasing magnitude single  two  and three phase voltage sags until the ASD  tripped offline  Through the experimental testing  it was found that the architecture of an ASD  can withstand a continuous single phase outage without significantly affecting the speed of the  motor  even under a full load condition  The experimental testing results also substantiated the  significant differences in ride through capability of an ASD based on the configuration of the  internal control power supply  It was shown that ASDs with internal power supplied from two of  the three input phases to the ASD are much more susceptible to voltage sags than ASDs with  internal power supplied from the dc bus voltage  For two and three phase voltage sags  it was  found that ASDs can ride through relatively small two and three phase voltage sags with an  increase in the dc bus ripple voltage  However  for most two and three phase voltage sags  ASDs  under a full load condition can experience a significant decrease in motor speed  in some cases    greater than 5   which is unacceptable in some industrial processes     80    6 3  Recommendations for Future Work    6 3 1  Additional Proposed Instrument Driver Fu
108. snapshot picture also enables many other  parameters of the AWG to be seen  Some of the other parameters include the clock frequency   waveform operation mode  waveform amplitude  and output channel status  In this example  it  can be seen that nominal sinusoid waveforms have been loaded into the three output phase  channels  the clock frequency is set to 60kHz  the operation mode is set to continuous  the  amplitude of the three output phases is at 10 0V  and the output channels for the three phases are  turned on     Dup VISA Session    Format    HEMP JO    Hard copy to     selected port  computer    Continuous mode Master Running  30 Apr 01 16 57 03  waveform  Sequence    CHI  PHA  NOM  KEM    splay    Graphics    Text       Figure 3 5  Front panel window for AWG screen capture VI     20       Figure 3 6  Program diagram window for AWG screen capture VI     3 5  LabVIEW Profile Block Virtual Instruments    Since the AWG requires a specific order of instructions when operated remotely over a GPIB  interface  it is convenient to combine several of the common sequences of commands into profile  blocks  After several functional VI blocks had been created  it was possible to combine multiple  VIs together as subsystems and create profile blocks  Each profile block begins with an AWG  initialization VI and ends with an AWG close VI  In between are the functional VIs needed to  carry out a sequence of instructions  In most profile blocks  a snapshot image of the AWG screen  is di
109. source impedance and Zy is the  motor impedance during startup  Voltage sags due to induction motor starting do not typically  drop Vag lower than 85  of the nominal voltage  2  30     Consider an ASD with a motor load P  nominal dc bus voltage Vo  and capacitance C  In the  case of a balanced three phase sag  when the absolute value of the ac input voltage is less than the  dc bus voltage  the electrical energy supplying the load comes from the dc bus capacitor  In a  voltage sag condition  conservation of energy dictates that the capacitor energy at time    is equal    to the initial capacitor energy minus the energy consumed by the load  2  30      1 1  CH     CV   Pt 4 4   2  A m  As long as the dc bus voltage is greater than the absolute value of the ac voltage   4 4  holds true    and an expression for the dc bus voltage during the voltage sag can be given as     2P  VO   V  nu  4 5     It is assumed that the load power consumption remains constant during the voltage sag  This  assumption implies the inverter is ideal when in reality  as the dc bus voltage drops due to the  voltage sag  the output current increases thereby increasing the switching losses during the sag   Most ASDs that trip offline due to a voltage sag do so when the dc bus voltage reaches a certain    value Vmin  The times it takes for the dc bus voltage to reach the trip value can be given as     C  t  ogh P   4 6     31    In  4 6  the capacitance is expressed in UF kW  the dc bus voltage is expresse
110. specified ride through time can be given by  14      Cole  4 14   a  Vicario    In  4 14   Va is the nominal dc bus voltage  Z4 is the average dc link current  and     is the ride   through duration  Although this is a simple solution to improve ASD ride through  the cost and  additional space required is high     4 5 2  Functional Operation Modes of ASDs    Most ASDs have programming features that allow for voltage sag ride through capability   Some of the more common types of programming features are ride through using load inertia   automatic restart  and flying restart  4  29  38 39   For any of these features to be used  it is  important that the control power to the ASD remain online  This requires the control power to be  derived from the dc bus or from separate energy storage means such as batteries    Ride through using load inertia can be implemented when the dc bus voltage falls to a  minimum level  In that circumstance  the PWM inverter will operate at a frequency slightly  below the motor frequency  causing the motor to act as a generator  The energy generated is  transferred back to the dc bus and after the voltage sag  the motor is reaccelerated back to its  nominal operating point  This method is useful in applications that don t require precise speed  regulation and where the ASD internal power supply voltage is derived from the dc bus    Automatic restart is the most commonly used ASD programmable feature where the PVM  inverter is disabled during a voltage 
111. splayed on the VI front panel since it is useful to be able to see exactly what is displayed on  the front panel screen of the AWG after a series of instructions has been performed    Profile blocks were created to enable the AWG to simulate power quality disturbances  entirely by remote operation as defined in the main objectives above  Figs  3 7 and 3 8 show the  front panel and program diagram windows  respectively  of a simple profile block VI  The profile  block VI loads either waveform or sequence files into the four channels of the AWG and also  configures the file amplitude settings  The waveform or sequence files must already be stored in  the internal memory of the AWG  The front panel window shown in Fig  3 7 has control  indicators for inputting the files to be loaded and their amplitudes for each channel  as well as  control indicators for the clock frequency and front panel image parameters  The program    diagram window shown in Fig  3 8 contains subsystem VIs that load files and set parameters for  each AWG channel     21    ma       Figure 3 8  Program diagram window for Load All Channels profile block     3 6  New Instrument Driver for AWG    Once the existing VIs were all functioning correctly with the AWG2005  additional VIs were  created to expand primarily the action and status  and data transmission capabilities  This  included VIs to create and compile equation waveforms  create sequences of waveforms  load  files and operation mode setting into channe
112. st load and monitored by the PQ power analyzer  When the AWG is not programming the  source output  the source cannot be controlled via computer with the Lab VIEW GPIB interface    When the AWG does program the output voltage of the source  each of the three output phase  corresponding channels must have a different waveform or sequence file loaded and their output  turned on  In the continuous operating mode  the output of the AWG is amplified by the source  and output to the test load  In the waveform advance mode  a nominal waveform is continuously  output by the AWG  The nominal waveform is amplified by the source and output to the test load  until the trigger signal is applied to the AWG  The trigger signal can be executed manually or  remotely from the LabVIEW interface  The trigger signal causes the waveforms in the sequence  following the nominal waveform to each cycle one time in consecutive order  After the last  waveform in the sequence has been executed  the output of the AWG returns to the continuous  output of the initial nominal waveform  26     The entire cycle of a waveform advance mode sequence can be captured by the PQ power  analyzer  One or more event mode trigger parameters can be setup to match the particular power  quality disturbance programmed in the waveform advance mode sequence  The number of cycles  of data to capture and record after the triggered event can also be user defined  The maximum  possible event length recorded to a data file is 28800
113. t sine wave of 310V rms L N  Maximum peak voltage capabilities are actually  1 48 times the maximum rms voltage  Care must always be taken to ensure that the AWG does  not generate signals that are outside the operation range of the programmable source  This  includes dc signals and very high frequency signals   gt  2kHz   The peak current capabilities are  2 9 times the maximum rms rating of 144 amps per phase  The maximum rms current rating    should never be exceeded     88    The output voltage range of the AWG is 0 10V peak to peak  The AWG output voltage is  configured with the programmable source amplifier output such that for a sinusoidal waveform  a  9 5V peak to peak output voltage from the AWG corresponds to a 310V rms  maximum output  voltage  programmable source output voltage  A common nominal phase voltage used in testing  motors and power electronic equipment is 266V rms  460V L L   An AWG output voltage of  8 15V peak to peak corresponds to a 266V rms programmable source output voltage  When  creating a waveform file  the data point amplitude can range between    1 and  1  To create a  simple programming setup for the AWG  all nominal waveforms are created with a peak value of  0 815  Therefore  the maximum amplitude factor of 10V can be entered into the setup menu of  the AWG and the desired AWG output voltage of 8 15V peak to peak will result  Since an AWG  output voltage of 9 5V peak to peak corresponds to a 310V rms programmable source output  the  maximu
114. t the input of the  ASD as well as the input current and dc bus voltage waveforms are shown in Appendix E   Again  the peak phase voltage value of the transient was approximately 450V  The ASD was not    at all affected by the capacitor switching transient  under all load conditions  The dc bus voltage    74    and the motor speed were both maintained at their normal levels  similar to the first 5 5kVA and    11kVA ASD capacitor switching transient test results     5 4  Analysis of ASD Ride Through Testing    The ability to create power quality voltage disturbances  as just shown in the previous  sections  enabled a thorough analysis of the ASD operating and ride through characteristics  A  summary of the ASD ride through characterization is shown in Table 5 23  By conducting these  voltage sag and capacitor switching transient tests while monitoring the dc bus voltage and motor  speed  it was possible to determine under what conditions a particular ASD would ride through a  voltage disturbance and under what conditions an ASD would trip off line    The results of the lower magnitude single phase voltage sag testing show that the three phase  diode bridge rectifier does not always convert to single phase rectifier operation for any  magnitude of single phase sag  Depending on the parameters of the ASD  namely the size of the  dc bus capacitor  for some smaller magnitude sags  the peak value of the affected line to line  voltage may still be higher than the dc bus voltage duri
115. tage     20  two phase voltage sag on phases    b    and    c           i    0 00000 0 06000 0 12000 0 18000 0 24000 0 30000    Figure E2 17        Figure E2 18  ASD dc bus voltage     full load     ASD did not trip offline     120    400 00     0 00     200 00          00 2  7400 00 5000 0 02000 0 04000 0 06000 0 08000 0 10000       0 00000 0 04000 0 08000 0 12000 0 16000 0 20000      Figure E2 20  ASD input current     full load  two phases shown      ASD did not trip offline     577 50    528 75  528 75       480   86 00 0 00000 0 04000 0 08000 0 12000 0 16000 0 20000    Seconds    Figure E2 21  ASD dc bus voltage     full load     ASD did not trip offline     121          525 00   262 50  eo   gt    0 00     N     gt     262 50   525 00 5   0 00000 0 02198 0 02396 0 03594 0 04792 0 05990    Seconds    Figure E2 22  ASD input voltage     capacitor switching transient        0 00000 0 01198 0 02396 0 03594 0 04792 0 05990         615 00 0 00000 0 01193 0 02385 0 03578 0 04771 0 05964  Seconds    Figure E2 24  ASD dc bus voltage  full load      capacitor switching transient     122    3  S SkVA ASD     Internal Power Supply Derived From Three Phase Input  Transformer    409 00     JUA     400 09  0    vi          00000 0 02000 0 04000 0 06000 0 08000 0 10000    Seconds    Figure E3 1  ASD input voltage     50  two phase voltage sag on phases    b    and    c           0 00000 0 04000 0 08000 0 12000 0 16000 0 20000          469 000  00000 0 04000 0 08000 0 12000 0 16000 0 20
116. ted arbitrary waveform generator  AWG  which  creates realistic voltage disturbance conditions that can be used to characterize ride through  capabilities of industrial processes in a controlled environment  Also presented is a command  driver database that has been created and tested  using LabVIEW  which contains the  functionality necessary to conduct a wide range of power quality research and testing projects by  remotely configuring and controlling the AWG    The power quality research and testing capabilities of the POTP are demonstrated with ASD  diode bridge rectifier operation analysis and ride through characterization  This research shows  the transition of an ASD   s three phase diode rectifier into single phase diode rectifier operation  when relatively small single phase voltage sags are applied to the input  Also shown are ride   through characterizations of varying sizes and configurations of ASDs when subjected to single   two  and three phase voltage sags as well as capacitor switching transients  In addition  ASD    topologies providing improved ride through capabilities are determined       Copyright by Evelyn Matheson  June 8  2001  All rights reserved    A Remotely Controlled Power Quality Test Platform  for Characterizing the Ride Through Capabilities of  Adjustable Speed Drives    by  Evelyn Matheson    A THESIS  submitted to  Oregon State University    in partial fulfillment of  the requirements for the  degree of    Master of Science    Presented June
117. the deviation of the power    system fundamental frequency from its nominal value  typically 60 Hz   Power system frequency    is directly related to the speed of the generators supplying the system  Therefore  significant  frequency deviations on a large power system are rare  Frequency deviations could be caused on    an isolated generator load system due to inadequate governor response to abrupt load changes     The main goal of electric utilities and end use customers is to minimize the number of power  quality problems  This can be achieved by limiting the amount of power quality disturbances  caused by equipment  by improving the performance of the power system  and by making    equipment less sensitive to power quality disturbances     1 2  Harmonic Distortion    Harmonic distortion of voltage and current results from the operation of nonlinear loads and  devices in a power system  A nonlinear load is one in which the current is not proportional to the  applied voltage  Nonlinear loads draw currents whose frequencies differ from the frequency of  the source  Nonlinear loads that cause harmonics can often be represented as current sources of  harmonics  The system voltage appears stiff to individual loads and the loads draw distorted  current waveforms  3  8   Harmonic generating loads that are commonly used in residential   commercial  and industrial applications are listed below    e Adjustable speed drives   e Switch mode power supplies   e Uninterruptible power supp
118. tility system and multiple customers  Fig  1 1   12   A    two way responsibility has been proposed for controlling harmonic levels on the power system     Customers must limit harmonic currents injected into the power system   Utilities must control the harmonic voltage distortion by making sure system resonant    conditions do not cause excessive magnification of the harmonic levels     Utility System  4 L       Other Utility  Customers    Utility System       Other Utility  Customers    Customer Under Study        Figure 1 1  Power system showing location of the PCC where other customers can be supplied     The following expressions are commonly used to indicate the harmonic distortion of a    waveform  13   The total harmonic distortion  THD  can be calculated as a percentage for either    a voltage or current waveform   b  25  THD          x 100      1 1     The magnitude of the individual harmonic components is Z   where A is the harmonic order   and 7  is the rms value of the fundamental current component  In some cases THD may not be a  very good indicator of the amount of current waveform distortion in a system  This is true for  circumstances where the current distortion of a light load may be very high  yet would not have a  significant impact on the power system  IEEE Standard 519 1992 uses total demand distortion to    evaluate the level of distortion in voltage and current waveforms     h     n  TDD    TE x100     L     1 2     The total demand distortion  TDD  
119. two pulsed   unbalanced  2  100  load 637 4V 645V two pulsed   unbalanced    5  50  load 636 6V 636V single    pulsed  5  100  load 630 0V 636V two pulsed   unbalanced  50  load 636 1V 619V dropped out    10  100  load 624 5V 619V single   pulsed  50  load 635 8V 609V dropped out    pulsed    Input                   dropped out       5 2 7  Diode Rectifier Stresses Due to Single Phase Voltage Sags    Single phase voltage sags induce additional stresses on the three phase diode bridge rectifier  of an ASD  The input current supplied by the phases not affected by the voltage sag is increased  in order to continue supplying the motor load and also re charge the dc bus capacitance  The    increase in input current passing through the diode branches is maximum when the three phase    57    e Fault Menu Parameter  Controlled stop   set to    NMS     maintenance of dc bus by  regenerating the kinetic energy from the machine inertia  during the three phase voltage  sag testing only  When set to    no     the drive did immediately trip with due to an  undervoltage fault for three phase voltage sag disturbances under all load conditions    The ASD was tested with several types of voltage sag disturbances including single phase  voltage sags at both 90   see Fig  5 17  and 100   see Fig  5 20  of nominal voltage  This  means that during the voltage sag  there was 10  and 0   respectively  remaining voltage on the  sagged phase  Also tested were two phase  see Fig  5 23  and three phase 
120. ufacturers are now designing ASDs with dc dc  switch mode power supplies that are powered off the dc bus which are less susceptible voltage    disturbances     75    Table 5 23  Summary of ASD Ride Through Results     S SkVA ASD   10kVA ASD   5 5kVA ASD                Parameter S SkVA    Description Modified ASD                  Internal Power Supply dc bus dc bus ac input ac input   Configuration voltage voltage  single ph  TX     three ph  TX   en EE  e  ae   Maximum Sag Ride  100        Through Capability    100  100  63   95 3  89 6  97     0 23  0 68  0 2  0 1     50  50  30  50     72  69 6  83 1  72 9   B E i    DC Bus Voltage         During Full Load    Motor Speed Drop  During Full Load    Two Phase Sags    Maximum Sag Tested  Did ASD Trip Offline                     DC Bus Voltage  During Full Load    Motor Speed Drop  During Full Load    Three Phase Sags    Maximum Sag Tested         Did ASD Trip Offline            DC Bus Voltage 7196 69 4               load condition   no load   no load   full load         full load              Motor Speed Drop 27 5  44 7        2 1         5 1               load condition   no load   no load         full load   full load           76    With the AWG and programmable source it was possible to accurately pinpoint the  circumstances under which a 5 5kVA ASD with control logic power derived from the input  would trip off line  By alternating the phase to which a single voltage sag was applied  it was  seen that a voltage sag applied
121. ystems in a profile block     106    2  Common Profile Block Structures    Two common profile block structures can be used to implement most functionality for  controlling the AWG2005  Both profile block structures include the three standard subsystems   Initialize vi  Close vi  and Make Hard Copy vi  The first common profile block structure consists  of multiple subVI profile blocks connected together in series as shown in Fig  D2 1  This  program diagram window example is from the Define Compile Equation VI  To create a new VI   place the subVIs in the block diagram in the desired order of execution and then wire the subVIs  together using the VISA session and error cluster parameters    The Initialize VI opens a VISA session  VISA is the standard I O Application Programming  Interface  API  for instrument drivers throughout the instrumentation industry  VISA can control  GPIB instruments  making the appropriate driver calls depending on the type of instrument being  controlled  The LabVIEW instrument driver blocks consist of VISA function calls  The VISA  session establishes a link with the AWG and allows for other commands to be executed  The  VISA session and error signals are connected in series to each subsystem  Each of the VISA  commands contains error input and error output terminals to pass error clusters from one VI to  another  An error cluster contains an indication of whether an error has occurred  a numeric  VISA error code  and the location of the VI where th
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
  ITA  políticas de uso del espacio  User Manual - ADFWeb.com  Tripp Lite PowerVerter APS INT 2400W 24VDC 230V Inverter/Charger with Auto Transfer Switching, Hardwired  Addonics RAID Tower IV    User Manual    Copyright © All rights reserved. 
   Failed to retrieve file