Home
        SRI CHS11 CHUTE HEIGHT SENSOR
         Contents
1.                                                                     Notes   1  1 5 sq mm  16 AWG  insulated stranded copper wires   2  Use BELDEN 9841 cables    CASE POSITION  3  Use BELDEN 9539 cables                 SINGLE CHUTE          DUAL CHUTE                   Figure 2  Single chute installation wiring example    Installation Example     Dual Chute    CHUTE HEIGHT SENSOR  CHS        SEE TABLE X1 LINK    BELOW FOR POSITION  LINK    POSITION        24V INSTRUMENT PWR SUPPLY POWER    INSTRUMENT PWR SUPPLY RETURN DC  VOLTS                LEVEL INDICATING LEVEL INDICATING  CONTROLLER B CONTROLLER A                CHUTE      PUTS A  OUTPUTS Li                            see Note 2 le see Note 2    see Note 1 see Note 1    240V AC SUPPLY N 240V AC SUPPLY N  240V AC SUPPLY L 240V AC SUPPLY L                      1A 240 V 1A 240 V  FAST BLOW   FAST BLOW                                  RELAYS                                                                CHUTE B JUNCTION JUNCTION CHUTE A  BOX 3 BOX  see Note 1 see Note 3 see Note 3 see Note 1                                     SENSORS                                                                      Notes   1  1 5 sq mm  16 AWG  insulated stranded copper wires  CASE POSITION  2  Use BELDEN 9841 cables     3  Use BELDEN 9539 cables  SINGLE CHUTE          DUAL CHUTE                   Figure 3  Dual chute installation wiring example    sa     This section provides a concise guide on how to configure and adjust the CHS11 for a
2.                    Parameter Setting Single Chute Value   Dual Chute Value   Chute Configuration Chute A Only Chutes A and B  Num Sensors in A Enter the number of electrodes wired to electrode inputs 1 to 8  Num Sensors in B Enter the number of electrodes wired to electrode inputs 9 16  Detection Mode A Mode 0 Mode 0  Detection Mode B Mode 0  Damping Factor A 1 second 1 second  Damping Factor B 1 second  Threshold A 50  50   Threshold B 50   Hysteresis Low A 30  30   Hysteresis Low B 30   Hysteresis High A 70  70   Hysteresis High B 70   Zero Adjust A 50 50  Zero Adjust B 50  Span Adjust A 50 50  Span Adjust B 50   EN  NOTE    Ly If the CHS11 is put into single chute configuration  the  B  values will not apply              5 4 Adjusting the Trimpots to a Default Position    Adjust the trimpots so they are mid scale  i e  in the middle of the range of rotation   The trimpots  are located on the CHS11 module and are labelled    VR1     A  and  VR2   B   If the application is a single  chute  only the A trimpot needs to be adjusted     Observe the LCD which should display an output in per cent for either one or both chutes  and check  that the output is zero and the output graphic is showing that no sensors are ON     If the output is not 096  turn the trimpots slowly anticlockwise until the output shows that no sensors  are covered and the output 096     22       sa     5 5 Adjusting the Analog Output Zero and Span    Monitor the analog output A using a suitable instrument  In
3.                 ceeds 8   3 2 2 Non Insulated Electrodes a ree et eer rete m EU Pe Ve ra EU P e SEDE vn tte mn ee LU eR 8   3 2 3 Electrode Insulation    o nre po Gr rr ennemie et iere kien quere reae n reae teretes d reu 10   B A CHUTE FACE ic  aes D                                                                  11   3 2 5  Number of Electrodes       recorte te terreri vacetetdescderaneasaljeaceauiansmnateieeesscdecens Ea aaaea EE aiaa 12   3 2 6 Highest and Lowest Electrodes esse 12   3 2 7 Electrode Spacing and Position    ceret iere reete ee us Ene hunted Meet tete edes AL n 12   4 0 Electrical Installation    rrr or at o Dr ORO Dr e Feria cep eii et reir est korr aa teu inte br pe ates 15  4 1 General Information    iet cave etr teret rece e e cepere e Hr Oe red AN E ive eve RS 15  4 1 1 Power Supply and Internal Fuse iii 15  LEAL M                                                                   Q       tiess 15   4 2 Wiring CONMOCTIONS de                                                                                     16  423 Supply Voltage Inp  t       3 re e Pec o e ve e e mte voee ee te 17  4 2 2 4 20mA Analog Outputs  E           Se ag en 17   4 2 3 Relay Contact OUTPUTS arree                                                        17  4 2 4 Electrode CONNECTIONS iinr E E eet A N N eee leve NENA ES 17   4 3 Power Oh Checks  ase rent oat au Rd iem go P ne I eI ea nima gre 18  5 0  Commissioning         inr Dn e etie iate ess top rene bass de cain secuattse sce 
4.     2013 Sugar Research Institute page 6    sa     Details of the CHS11 dimensions  weight and mounting are provided in Section 1 1 of this manual   The CHS11 is designed for mounting in a control cabinet  must not be installed without appropriate  protection from the factory environment        l a   NOTE   1  The maximum cable length from any chute electrode to a CHS11 is 25 meters              3 1 Chutes and electrodes    The CHS11 functions by measuring conductivity between electrodes and the steel wall of the chute   The presence of material  e g   bagasse or prepared feed  touching both the steel wall and an array of  electrodes  positioned vertically in the chute  causes a low resistance path for electric current to  flow  This allows the CHS11 to determine that material is present  The low resistance of the bagasse  is mostly due to the presence of moisture     Each CHS11 can be used to monitor one or two chutes  It is possible to have sixteen electrodes in a  single chute because there is a limit of sixteen electrode inputs  When one CHS11 is used to measure  the level in two chutes  dual chute mode  then each chute may have a maximum of eight electrodes     The CHS11 requires an even number of electrodes for correct operation  For example  in single chute    mode 10  12  14 or 16 electrodes shouyld be used  In dual chute mode  each chute can have 2  4  6 or  8 electrodes     Copyright    2013 Sugar Research Institute page 7    sa     3 2 Electrodes    The CHS11 offer
5.     sa     9 3 10 Zero Adjust    The zero adjust parameter  see illustration below  is used to adjust the 4 milliamp output signal when  the output is at 0   Details are provided in Section 3 of this manual     9 3 11 Span Adjust    The span adjust parameter  see illustration below  is used to adjust the 20 milliamp output signal  when the output is at 100   More details are provided in Section 3 of this manual        9 3 12 Configuration Error    The CHS11 stores parameters in non volatile memory so they are maintained when the power is off    Parameters are verified when the CHS11 is powered up or when it enters configuration mode  If any   parameter is not valid then the CHS11 will display the    Config Error    message  see illustration below    When this occurs and the Enter button is pressed  the CHS automatically resets all invalid parameters  to a default value        43    sa     sa     10 0 Troubleshooting    Installation and operation of the CHS11 must be in accordance with the Specifications  Mechanical  and Electrical Installation sections of this manual     10 1 Self test Function    A self test function is provided to allow testing and checking of the electronics and connections  To  enter the self test mode press and hold the Enter button as power is applied to the CHS11  electronics  The self test function performs the following actions     e The relay outputs are turned on in a    staircase    sequence  16 steps      e The LCD shows the number of active rela
6.    e Providing a digital input to a control system  e g  a programmable controller  to display the state  of each sensor at an operator interface  Other logic processing  performed by the PLC DCS  could  be implemented to suit a specific application  The CHS11 would be in Mode 4  no logic  processing      e Controlling a row of lights near the chute or in a control panel  allowing factory operators to see  from a distance the level of material in the chute     e High and low alarm indication could be used for outputs to indicate  chute empty  chute low   chute high  and chute full     8 2 Material Presence Detection    The CHS11 comprises 16 sensors that can be used to detect the presence of material  When  configured for operation in Mode 4 there is no logic processing and the relay outputs show the state  of each sensor  For example  if sensors 1  3  7 and 15 are covered then relays 1  3  7 and 15 will be  active and the other relays will be inactive     It is therefore possible to use the CHS11 as a 16 channel sensor for level or presence detection   Some example applications are     e Electrodes are fitted in the walls of tanks with one electrode per tank  When the material rises to  a high level  the electrode becomes covered and the relay operates to provide an alarm indication  of the high tank level     e Electrodes are fitted in the walls of 8 tanks with each tank having two electrodes  one at the top  and one at the bottom  The relays can be used for high and low le
7.  CHS11 to be used in dual chute configuration where the  sensitivity in one chute may differ from that required on the second chute     It is possible to use separate sensitivity adjustments for single chute installations  An example where  this would be useful is where the lower eight electrodes require a low sensitivity but the electrodes  towards the top of the chute require more sensitivity  The limitation when used in single chutes is  that each trimpot A adjusts the sensitivity for sensor inputs 1 to 8 and trimpot B for sensor inputs 9  to 16     8 5 Irregular Electrode Spacing    The CHS11 produces an output signal that is linear with the number of electrodes covered  If the  electrodes are spaced at the same distance between electrodes  the output signal will be linear with  the vertical distance in the chute  It is possible to mount the electrodes at distances proportional to  the cross sectional area of the chute so that the CHS11 output signal is proportional to the chute  volume  In addition  it is possible to space the electrodes at irregular intervals to linearise the output  signal with another process variable     36    sa     9 1 Keypad    Three buttons are provided on the CHS11 module for setting options and adjusting parameters  The  position and names of the buttons are shown in Figure 13  The switches are placed at the bottom    right hand corner of the CHS11 module  see Figure 13   The configuration of the keypad functions is  provided in Table 6     CON
8.  Menu Reference section of this manual  Once in  configuration mode  the user must go through all configuration screens before returning to the  output screen  There is no automatic  timeout  return to the output screen  The entry to  configuration mode can be aborted by pressing the  Down  button     Section 4 of this manual provides a concise guide to setting the parameters for a typical installation   A more detailed description and guidelines for use of the parameters are provided in the Menu  Reference section     27    sa     6 2 Operation    The operation of the CHS11 can be monitored using the output screen which displays the analog  output values in per cent as well as a display of the sensors that are covered  Examples of output  screens for single and dual chute configuration are provided below        Single chute configuration       Dual chute configuration    The outputs are shown on the display as a percentage and as a graphical display of covered sensors   If in single chute configuration  only the    A    output will be displayed  In dual chute configuration both  A and B outputs will be shown  The graphical display resembles a bar graph which has more  functionality because it can be used to show the sensors that the CHS11 determines to be covered     6 3 Sensor Detection and Logic Processing    The operation of the CHS11 is described below with reference to the Figure 12 which illustrates a  functional block diagram     The CHS11 comprises 16 conductivity se
9.  compromised     3 2 7 Electrode spacing and position    A typical installation in a Donnelly chute has eight electrodes spaced at approximately 200mm  centres in the wall of the chute  The simplest method is to space the electrodes evenly between the  highest and lowest electrodes  although this is not the only option  Refer to the Applications Guide in  this manual for information on spacing the electrodes at irregular intervals     To avoid the effects of excess water in the chute  it is recommended to mount the electrodes ina  diagonal or staggered geometry so that dripping water corrupts only one electrode  Figure 5  illustrates some possible mounting positions     Copyright    2013 Sugar Research Institute page 12    sb                                                                                                                               Figure 5  Two suggested methods of mounting electrodes    Copyright    2013 Sugar Research Institute page 13    sb    Copyright    2013 Sugar Research Institute page 14    sa     4 1 General information   Section 1 1 of this user manual includes details of the power supply requirements  analog output  characteristics  including load resistance  and relay specifications  Please refer to the terms electrode  and sensor in the Glossary when reading this section    4 1 1 Power supply and internal fuse   The CHS11 requires a clean stable 24 VDC power source  Details of the input supply including the  current consumption and ripple are 
10.  each sensor is displayed as it is  measured by the detector  In other words  there is no logic processing  So if one sensor is not  covered with material  it will Show as not covered  The graphic display shows the output from the  logic processing of the sensors but is not a bar graph  The sensitivity adjustment may need to be  changed because some sensors do not properly detect material     Question  Where is the internal fuse of the CHS11 located and what spares are available   The CHS11 module has one resettable fuse that is soldered on the printed circuit assembly  It is not  field replaceable    Question  Why does the display not change when I hold down the Up or Down buttons   There is no automatic increase or decrease feature on the CHS11  To change a parameter value you  must push the button for every increase or decrease    Question  Why does the CHS11 display not show the output screen that is mentioned in  the manual     Make sure that the CHS11 is not in configuration mode  The CHS11 does not automatically return to  the output screen  Press the Enter button to return to the output screen     49    sa     Question  What does it mean when   get a    Config Error    message on the display     The CHS stores parameters in non volatile memory so they are maintained when the power is off   Parameters are verified when the CHS11 is powered up or when it enters the configuration mode  If  any parameter is not valid then the CHS11 will display the    Config Error    mess
11.  has the following effects     e The output state will change less rapidly if hysteresis low is decreased and or hysteresis high is  increased  This can be used to remove unwanted    chatter    in the digital outputs that may be  caused by momentary air pockets or material contact with the electrode     e Increasing hysteresis low and or decreasing hysteresis high means that the output state will be  less resistant to change and may improve the speed of detection  This may be useful in fast  flowing chutes where the reaction time of the CHS11 to changes in the chute level needs to be  short     7 2 Using the CHS11 for Materials other than Bagasse    The majority of CHS11 applications will not require knowledge of the following information  which  provides details that may assist with difficult or irregular installations and applications  Please refer  to Section 5 for a description of the CHS11 operation and background information on the CHS11  sensor detection and processing functions and terminology     32    sa     7 2 1 Characteristics of the Material for Reliable Detection    There are two main characteristics of materials that need to be considered in respect of suitability for  CHS11 applications     The first is the electrical conductivity  which is usually dependent on the amount of moisture and  presence of ionic compounds  such as salts  contained in the material  Since the CHS11 has a  conductivity detector that uses fixed values for threshold and sensitivity  the
12.  improve the mechanical connection of wiring to the electrodes  it is  recommended to terminate the screened cable inside a waterproof junction box mounted on or near  the chute  This allows more robust wires to be connected to the electrodes and the junction box    Copyright    2013 Sugar Research Institute page 17    sa     terminals  Examples of a single chute installation wiring and dual chute installation wiring are   provided in Figures 5 and 6  respectively    4 3 Power on checks   When the cable installation is complete  apply 24 volt power to the CHS11 and check the following   e The    PWR    LED on the CHS Module illuminates  showing that power is on  and    e The LCD illuminates  the LCD is back lit  and the output screen  refer to Menu Reference for  details  appears on the LCD screen     Copyright    2013 Sugar Research Institute page 18    Installation Example     Single Chute    CHUTE HEIGHT SENSOR  CHS        SEE TABLE  BELOW FOR X1 LINK  LINK    POSITION POSITION        24V INSTRUMENT PWR SUPPLY  INSTRUMENT PWR SUPPLY RETURN                RELAYS see Note      LEVEL INDICATING 24 7  CONTROLLER 240V AC SUPPLY N    e  240V AC SUPPLY L                mA  CHUTE  1A 240 V  mA  OUTPUT i          FAST BLOW                      see Note 2                   CHUTE A JUNCTION  see Note 1 Bre see Note 3 SENSOR    S COM  S16  S15  S14  S13  S12  S11  S10  s9  S8  S7  S6  S5  S4  S3  S2  SI                                                                                   
13.  sa     Table 4  Sensitivity Range for threshold setting    Threshold Effective Sensitivity                    Range  kQ    10 1 6 Minimum recommended setting   25 17 For wetter more conductive materials  50 50 Default setting for most applications  75 150 For drier less conductive materials                   7 1 3 Hysteresis Adjustment    A hysteresis algorithm is used to filter the results from the detector  For example  if one sensor was  covered with material but suddenly experienced an air pocket  the detector output may momentarily  change to    not covered     The hysteresis algorithm filters out the momentary change and prevents the  output state from    chattering    or changing too rapidly     Each time the CHS11 scans a sensor  the result from the detector is accumulated  The hysteresis  algorithm compares the accumulated value with the hysteresis high and hysteresis low parameters  to determine the detection state for the sensor     If the accumulated result is lower than hysteresis low  the detection state is uncovered  If the  accumulated result is greater than hysteresis high  the detection state is covered     The default settings for hysteresis low is 30  which means that the detector output must be ON for  less than 3 out of every 10 scans for the sensor to be    uncovered     The default for hysteresis high is  70  meaning that the detector output must be on for at least 70  of scans before the sensor is     covered        Changing the hysteresis parameters
14.  typical  application  More detail is available in other sections of this manual including Section 5     5 1 Overview    Prior to commissioning the CHS11  please check whether the mechanical and electrical installation is  complete and the power on checks were satisfactory as described in Section 3     The steps for commissioning a typical CHS11 installation include are       Setting the jumper link XT         Entering settings at the CHS11 user interface     Adjusting the trimpots to a default position      Adjusting the analog output zero and span      Viewing the operation in Mode 4  and     Setting the mode of operation     gum   ww ND PB    5 2 Setting the Jumper Link  The jumper link on the CHS11 selects one or two chutes as described in Table 1 below  If the CHS11 is    used in the single chute mode  the jumper X1 must be fitted adjacent to the    1    text shown on the  printed circuit board  For dual chute mode  fit X1 to the pins adjacent to    2        Table 1  Jumper link selections    Configuration X1 position    Single Chute T       Dual Chute 2                   21    sa     5 3 Entering Default Settings at the CHS11 User Interface  Please refer to the Menu Reference section of this manual for a concise reference to the user    interface buttons and LCD screens  Use the interface to set the following values in Table 2 before  commencing the commissioning process     Table 2  Default settings for CHS user interface                                                
15.  uos mg Sa Sel     00  000     00  Dno mW Heelies   lla na 6m mma oD pith    800  OOO BOONMO OF   Ta nor  nano    mma nonum   na   a  00 cm um an AODH Yp  lm 00 os oo   n nenne umma    a  00    og oa meme 0g 23099 Se  ang uhr Deenee      maroo  amp  oo      00 OOO   ano 2 na    meroa  noa   ano     mna    meroa  ma     mesoo 4 mna    8005 mma  EHE na ems umm     Mee Oo    00   ems nog     te 00 uma    00 OOO  e  onem 5 en eu ez ez 000000   seni    ALO MNO ON  S90 SO e  De ne   nan ct    SON 2  DOSANE On    0   0e     Monnet    Figure 4  Functional Block Diagram of CHS11    29    sa     sa     The installation and configuration of a typical CHS11 application is described in the preceding  sections of this manual  mechanical installation  electrical installation and commissioning      This section provides some guidelines and background information on the use of a CHS11 for  applications other than for monitoring the height of material in a feed chute  It also describes how to  use the damping  threshold and hysteresis parameters     7 1 Damping  Threshold and Hysteresis Parameters    7 1 1 Using the Damping Parameter    The analog outputs are proportional to the number of sensors  As one sensor turns on  the output  will increase by an amount equal to 100  the number of sensors  When the CHS11 is configured for  a single chute with 16 sensors and each sensor turns on  the output will change by around 6      In addition  each analog output has a resolution of 10 bits and includ
16. AD SUGAR RESEARCH INSTITUTE    SRI CHS11  CHUTE HEIGHT SENSOR    Instruction and Operation Manual       SRI provides a range of services to the sugar milling and sugar refining industry worldwide  These include  61  7  3138 9400 www sri org au  commercial research and development  operator and supervisor training  consulting  process control and    instrumentation  factory and plant design  boiler optimisation  CFD and DEM analysis  and chemical services   61  7  3138 9409 sugarresearch    Copyright    2013  Sugar Research Institute info sri org au sugar_research       Sugar Research Institute  PO Box 15758  City East  QLD 4002 Australia    Phone   61  7  3138 9400  Fax   61  7  3138 9409  Email  info sri org au       nRigcELCCclerlluugqprlme                                                          1  2 0 Specifications    seniri ienaa asunat na Sanie tea REM EE EA EREA Oarra Ria 3  2 1 Chute Height Sensor 11 Electronics Module orir E a A o E E AN ASETE 3  2 2 Optional AC Power SUpply          cccesccsscssssecsssecssesseecsaeecuecsseesseecsaeecueesesssseesneeeseessescsaeeseseseaeessseesaceseseeeeesseseeseneseeessneees 5  pEEESCuuadese tc c                                                            ain ee 5  EXT IERIBCIBRAGCIFEImMC                                                    7  31 dgoe ce R                                              etai 7  pad Iq DIM                                                           n 8  3 2 1Insulated Electrodes   21554                      
17. FIGURE CHUTE A  Up Down  Enter Sensitivity         Figure 13  Configuration switches on CHS11 module    Table 5  Configuration keypad functions    Button   Function    Enter Press to enter configuration mode and to scroll to the next menu item       Up Increase the displayed value or answer    Yes    to the question on the LCD  Also use  to toggle between two options  e g   single or dual chute configuration              Down   Decrease the displayed value or answer    No    to the question on the LCD          37    sa     9 2 Flowchart of LCD Screens    Figure 14 outlines a flowchart of the user interface display operation with detail of each screen             Denes  S 00 SA                                                            MIE XKL ON                      up  en   sim om    L___ lasse yen onan   hell S Ome   hoon S Sua Q   HOO  Ila OO yO oT 00e   S 1Q   I                                           19 p I                                                                                  Figure 5  Flowchart of LCD Screens    sa     9 3 LCD Screens    9 3 1 Output Screen    The output screen is shown after the CHS11 is powered up and is then the default display  If the  CHS11 is configured for single chute mode  the screen will appear like this     The first line of the screen shows that the output from the CHS11  which can range from 0   to  100   The second line shows a graphical representation of the sensors  In the example presented  above  the CHS11 has been configu
18. age  When this occurs  and the Enter button is pressed  the CHS11 automatically resets all invalid parameters to a default  value     50    sa     Damping     The CHS11 includes a first order low pass filter algorithm that is used to smooth the output signal   Damping refers to the time constant used for the analog outputs  which include a first order low pass  filter  For example  when damping is set to 30 seconds  the output signal will fall to 37  of the initial  value 30 seconds after the output state has changed     Detection State     The detection state Used describes which sensors are covered with bagasse and those that are not  covered  It is determined by comparing the signal from the detection electronics against the  threshold setting     Electrode     Steel electrodes are fitted to the chute and connected to the CHS11 electronics to detect the  material presence     Hysteresis     The method used by the CHS11 to determine if a sensor is covered with material includes scanning  the sensor a number of times  On each scan  the signal from the detection electronics is used to  update an algorithm that has programmable hysteresis for determining whether the sensor is on or  off  The output from this algorithm determines the detection state for each sensor    The CHS11 has two hysteresis values  hysteresis high and hysteresis low  A hysteresis high value of  100   means that the signal from the detection electronics must show that the sensor is covered for  every scan 
19. ay contact 16  N O   Relay contact 16  Common   Chute AmA    Analog Output A     Chute B mA  Analog Output B                    Chute AmA    Analog Common A Chute B mA  Analog Common B   24  24Vdc Supply Input   24  24Vdc Supply Input   0 Supply Common  0 Supply Common             Copyright    2013 Sugar Research Institute page 16    sa     4 2 1 Supply voltage input    Four terminals are provided for the connection of the 24VDC supply  Two are positive and two are  negative  or common   The voltage supply may be floating or ground referenced     4 2 2 4 20mA analogue outputs    There are two 4 20 milliamp analogue outputs referred to as    Output A    and    Output B     When in  single chute configuration  only the    A    output is used  The  B  output will be active but remain at  approximately 4 milliamps  When being in dual chute configuration  both outputs A and B are used     The analogue outputs of the CHS11 are isolated from the input supply but share a same common  negative for both outputs  There are two terminals for each output  One terminal is for the current  output and one for the signal return  common   The two common terminals are connected internally     A single or twin twisted pair cable with screen for individual pairs and an overall screen is  recommended for connection to the analog outputs  An example of a suitable cable type is Belden  9841  single pair  and Belden 9842  twin pair   For details please refer to www belden com     4 2 3 Relay contact 
20. before the detection state for the sensor is    covered     A hysteresis high value of 70   means that the detection state will be    covered    if 70   or more  scans show the sensor is covered   Similarly  a hysteresis low value of 20  means that if 20  of scans show that a sensor is covered  the  detection state for the sensor will be    not covered        Output State     The CHS11 includes algorithms to convert the detection state into an output state based on the  mode setting  The output state is used to control the relays and to generate the analog output  The  two output states are    on    and    off        51    sa     Parameter    A parameter in the CHS11 is a value which is stored in non volatile memory and used by the CHS11  during operation to perform specific operations  Parameters can be changed at the user interface   Examples include the number of sensors  the detection threshold and hysteresis    Scan Scanning    To determine the detection state  the CHS11 circuitry regularly scans each sensor in a continuous  sequence     Threshold     The CHS11 compares the conductivity of each sensor with a threshold value  If the measurement is  less than the threshold  the sensor detection state is    covered     If the measurement is above the  threshold  the detection state is    not covered        52    
21. continuous  2A    Recommended operating conditions    Input supply voltage 24 VDC  Input supply voltage ripple  lt 0 1V  Power supply rating  no derating  15 W  Ambient temperature 25 5  C  Ambient humidity 55   1096RH    Electrode interface and conductivity detector characteristics                            Specification Min Typical DEA Unit  Cable length from CHS to electrodes     25 metres  Detection signal frequency   1 92   kHz  Detection signal amplitude  no load    5   Vok pk  Threshold adjustment limits 0 5 Vok pk  Sensor scan rate   24   Hz  Detection signal source impedance  approx   360   50k Q  Sensitivity adjustment range   50k   Q  Bagasse moisture content 45                         Copyright    2013 Sugar Research Institute page 3                                                       Supply   Specification Typical  Operating supply voltage range 20 24 26 VDC  Allowable ripple and noise at input      0 2 V  Supply current at 24 VDC 0 05   0 4 A  Voltage protection  clamping voltage 31   45 VDC  Self resetting fuse break current at 20  C   1 8   A  Self resetting fuse hold current at 20 C   0 9   A  Analogue outputs   Specification Min Typical Max Unit  Source voltage  with supply voltage of 24 VDC    24   VDC  Load resistance 0 250 1000 Q  Limits of zero  4 mA  adjustment 3 3   4 9 mA  Limits of full scale  20 mA  adjustment 19   22 mA                   Relay outputs                   Specification Min Typical DEA  Rated contact current     2 A  Rated contact p
22. crease the Zero Adjust A parameter  refer  to Menu Reference section for details  until the instrument reads 4 0mA     Now connect an    earth    to the highest electrode in each chute and observe that all sensors are ON at  the LCD output screen  The earth may be connected at the CHS11 or to the electrode wiring  Finally  adjust the Span Adjust A parameter so that the output reads 20mA     Repeat this process for analog output B for a dual chute configuration and adjust the parameters  Zero Adjust B and Span Adjust B  In addition  remove the earth wire from the top electrode     5 6 Viewing Operation in Mode 4    Now use the user interface to set the mode to 4  for both chutes if in dual chute configuration   This  allows the detection state  see Glossary  to be viewed and problem sensors can be identified     At this stage in the commissioning process  there needs to be some method of observing the output   from the CHS11 and the level of material in the chute simultaneously  A basic way of achieving this is  to have an observer viewing the number of electrodes covered and a second person commissioning   the CHS11     When material is flowing through the chute  under normal operating conditions   observe the  graphical representation of the sensors on the LCD and compare it with the observed level in the  chute  As the chute fills and empties  the graphical representation should indicate sensors turning on  and off     5 7 Adjusting the Sensitivity Trimpots    Adjust the tr
23. eel wall may cause a low  resistance path when bagasse is not present  Excess water may be water that flows   condenses upon or collects on the inside or outside surface of the steel wall  It may also be  water that becomes trapped in the gaps between the electrodes  insulators and steel wall     The plastic widow should be approximately 200 mm wide and long enough to house the required  number of electrodes  The electrodes should be positioned along the centre line of the plastic  sheeting and fitted without insulators  In order to mount the electrodes  10 mm diameter holes must  be drilled in the sheeting     3 2 1 Insulated electrodes    Insulated electrodes may also be used but they are not preferred  as the electrical pathway between  electrode and chute is much shorter     Insulated electrodes are made from stainless steel and have a low profile inside the chute to prevent  unwanted material build up around the electrode  They allow simple direct to bulkhead mounting  and have two plastic insulation spacers for electrical isolation from the body of the chute  A crimp lug  and locknut are provided with the electrode for connection of the cable to the electrode  Figure 3  illustrates the mounting arrangement of electrode in the chute wall     Insulators are supplied with each electrode and are manufactured from a plastic that is resistant to  heat  moisture and mechanical stress  Mounting the electrodes using the spacers requires a 16 mm  diameter hole to be cut through t
24. es a damping algorithm that can  be adjusted  using the damping parameter  to reduce the effects of the step changes  The algorithm  is a first order low pass filter and hence increasing the damping time also delays the output response  from the analog outputs     As a result  it is normal to observe some minor  step changes  in the output signal as the chute level  changes  This will be most obvious when the output is recorded on a trend chart     7 1 2 Using the Thershold Parameter    The CHS11 conductivity detector functions by generating an AC signal that is fed to the electrode  inputs through the sensitivity trimpot  adjustable from 0 to 50k ohms   When material causes an  electrical contact between an electrode input and the    sensor common     a voltage divider is formed  by the sensitivity trimpot and the material  This divided voltage is measured by the CHS11 and when  it is reduced by an amount equivalent to the threshold  the conductivity detector will show that  material is present     Usually the threshold is set to 5096 which means that material will be detected when it is the same  resistance as the sensitivity trimpot setting  When the threshold is reduced  the material must be  more conductive to be detected  Increasing the threshold may allow less conductive material to be  detected     It is recommended that the threshold is set between 1096 and 9096  The effective detection sensitivity  range for a given threshold setting is provided in Table 5     31   
25. es to be fitted in the wall of  each chute  Using more than eight electrodes will give a better resolution of the output signal     When used in single chute mode a CHS11 can process inputs from up to sixteen electrodes in the  chute  When used in dual chute mode  a CHS11 can process inputs from up to eight electrodes in  each chute        NOTE   The CHS11 requires an even number of electrodes in each chute                 3 2 6 Highest and lowest electrodes  The positions of the highest and lowest electrodes in the electrode array depend on these factors     e The CHS11 will indicate that the chute is 100  full when all electrodes are covered  If the  highest electrode is placed too high in the chute it may be that the top electrode is never  covered and signal resolution is reduced     e If the highest electrode is placed too low the top electrode may be covered often  If the relay  output of that electrode is used for alarm purposes  e g   a high chute level alarm  there may  be too many false alarms     e The CHS11 will indicate that the chute is 0  full when no electrodes are covered  If the  lowest electrode is placed too low in the chute there may be an increased chance of false  detection of material  Thus lower areas of the chute may be prone to excess water or to  material not being cleared away when the chute is empty     e If the lowest electrode is placed too high in the chute the ability to use the output signal for  alarm purposes  low chute level alarm  may be
26. h is used to minimise level detection    errors if sensors are    stuck    or behave erratically  Please refer to the Menu Reference section of this    manual for a description of the modes of operation     The output from the logic processor is held in memory registers called the output state  The LCD  output screen shows the output state which is used by the analog and digital outputs  Each digital  output is turned on when the corresponding sensor is ON     The analog output block uses the number of sensors parameter to scale the output signal  The  output is proportional to the number of sensors that are ON  For example  if the number of sensors is  set to 12 and the output states for 6 sensors are ON then the analog output will be 12 milliamps     50                                                                                                                                                                                                                                                                                                                                                                                                                                  o Oeean  Oo  o  Oo  o  o  o   Ts 10336 2 ame mme 00 09000500 She Il  5 Gerh     ONE    AE nono  o S A AMON zx  o ZE o en  Oo       o Azo seo  Oo  Oo  o  SMO MMO Om   o4 0OO0O4   eon  ON   mm  Dno mo   swannenone D   nenas wo az O lt os Do   qas 00 om nga nano OOO     00  mung    00  0000  ums ums menm nnm  men s pma
27. he chute wall     Before fitting the electrodes  liberally coat the steel wall around the electrode mounting holes with a  sealing compound such as    Silastic     Coat the inside and outside surface of the wall to prevent  moisture collecting under the plastic insulator  Finally fit the electrode with the insulator and wipe  off the excess compound after tightening the nut     Copyright    2013 Sugar Research Institute page 10                                                                                     Figure 1  Mounting arrangement of electrode in the chute wall    3 2 4 Chute face    The choice of electrode positioning is determined by the feeding characteristics of the material into  the chute  The electrodes must be positioned in a face of the chute where the material firmly  contacts the chute wall  without air pockets  and is cleanly removed from the wall when the chute  level falls  Efforts should be made to try to locate the electrodes where water is not expected to flow  on either surfaces of the chute  Electrodes in the lower part of the chute should not be located  where material tends to build up and hang  Figure 4 provides examples of faces where electrodes  could be mounted and faces where electrodes should not be mounted                 Figure 4  Examples of possible electrode positions    Copyright    2013 Sugar Research Institute page 11    sa     3 2 5 Number of electrodes    To be effective  in mill control  a CHS11 typically requires eight electrod
28. he parameters for Chute B will not be displayed and cannot  be changed because they will have no effect on the operation of the CHS11     In addition  changing the configuration between single and dual chute configuration requires the X1  jumper selection on the CHS11 module to be changed  Please refer to Section 3 for more details     9 3 4 Number of Sensors    The number of sensors may be set for single and dual chute applications at the following screens     The number of sensors is adjustable in steps of 2 sensors with a minimum of 4 sensors  The  maximum number of sensors is 16 in a single chute configuration and 8 per chute for a dual chute    configuration     40    sa     9 3 5 Detection Mode    The effect of the detection mode setting is described in Section 5 of this manual  The illustration  below shows the current setting  the example shows Mode 1  in the second line and the range that  may be set  between 0 and 4   Table 7 provides the detection mode and respective logic processing     Table 7  Detection Mode and Logic Processing                               Mode Logic Processing   0 Scan from bottom sensor to top sensor  Find the first sensor not covered and then set the  output state for that sensor and all other higher sensors to OFF   1 Scan from top sensor to bottom sensor  Find the first sensor covered and then set the  output state for that sensor and all other lower sensors to ON   2 Scan from bottom sensor to top sensor  Find two consecutive sensors tha
29. impot and note that there is an    A    trimpot  VR1  and a  B  trimpot  VR2   For single  chute applications only adjust the  A  trimpot  For dual chute configuration adjust  A  first and  complete the commissioning before adjusting B     Adjust the sensitivity whilst monitoring the output screen and the level of material in the chute until  the CHS11 reliably shows the correct output  This should be performed over the entire range of  operating conditions  If the material is wet  less sensitivity is required and as the material becomes  drier  the sensitivity may need to be increased  The final sensitivity setting should accommodate both  the wet and dry conditions        i NOTE        Increasing the sensitivity means turning the trimpot anticlockwise and decreasing  the sensitivity means turning the trimpot clockwise              23    sb    5 8 Check for Problematic Sensors  An Example    The following example shows a dual chute application where Chute A was full of material and Chute  B was empty  Sensors 3 and 4 were found to be the problem in Chute A because some air pockets  have been formed in the material around the electrodes  In this scenario  Sensor 4 in Chute B was  observed to be always on  even when the sensitivity trimpot was turned almost fully clockwise  An  example of how to check for problematic sensors is provided below        For the example presented above  solutions were found for Chutes A and B     Chute A Solution     It was discovered that Chute A 
30. listed in Section 1 1  The CHS11 includes an internal self resetting  fuse for supply protection which is not field replaceable     4 1 2 Relays    There are 16 relay contact outputs that correspond to the 16 electrodes  see Figure 6   The maximum  contact current and voltage for the relay contacts are provided in Section 1 1 of this manual               CHS11    SUGAR RESEARCH INSTITUTE          Figure 6  Relay outputs       NOTE   Relay contacts are not suitable for mains level voltages  110 240 VAC   Use a  separate relay with the appropriate rating if switching mains level voltages              Copyright    2013 Sugar Research Institute page 15    sa     4 2 Wiring Connections    The CHS11 uses screw terminals for the connection of power supply input  relay contacts  analogue  outputs and electrode inputs  The terminal numbers and connections are shown in    Table 1  Terminal connections    Terminal Function    Terminal Function  S1 Electrode 1 Input  S2 Electrode 2 Input    S3 Electrode 3 Input    S4 Electrode 4 Input    Com    Electrode Common B    S5 Electrode 5 Input  S6 Electrode 6 Input          S7 Electrode 7 Input    Electrode 8 Input  Com    Electrode Common A                      Relay contact 1  N O     R1   Du fumer    R5    Relay contact 5  N O     Relay contact 9  N O     R9  R13    Relay contact 13  N O                 Relay contact 5  Common     5C   as eme      Relay contact 13  Common     13C      rs Relay contact 8  N O   Relay contact 8  Common     Rel
31. n of each individual sensor     The output will change erratically if the sensor detection does not operate  properly  For example if the sensitivity has not been adjusted to suit the  range of operating conditions  e g   bagasse moisture content   presence  may not be properly detected at some or all sensors  Refer to the       Commissioning section for more details        46    sa        Symptom    The LCD shows that all sensors are OFF even when the chute is full or the LCD  shows that some sensors are OFF even when material is contacting the  electrode       Possible Cause  and Remedy    If the sensitivity is too low  sensitivity trimpot is too far clockwise   material  may not be properly detected  Check whether the sensitivity adjustment has  been set as described in the Commissioning section of this manual     The electrode wiring may be faulty or incorrectly installed  Check whether  the electrode wiring is properly connected and the sensor common  connection is connected to the chute     The Threshold parameter may be set incorrectly  This will most likely be the  case if the setting is too low  A threshold of 50  is recommended for most  applications  For special applications please refer to the Applications section  of this manual for more details on the threshold parameter     The electrodes may not have good physical contact with the material  This  may occur if the electrodes are fitted in a location where the material has  large air pockets  or if the electrode
32. ngular opening is cut in the steel side of the  Donnelly chute     front  back or side surface     to suit the specific site conditions  This arrangement   shown in figure 3  gives good separation between the chute wall and the electrode  There is less  chance of  short circuiting  via water tracks or material buildup around the electrode     Typical electrode arrangement       _  MATERIAL  77 LEXAN MR 5  6mm Thick  or similar                 Figure 2  Arrangement of electrodes and polyacarbonate windows in a Donnelly chute           NOTE    2  A number of individual windows may be used in one chute in order to place the  electrodes in the best location  Using clear polycarbonate windows can help when  commissioning the CHS11 because the level of material can be observed and  compared with CHS11 output              Copyright    2013 Sugar Research Institute page 9    sa     3 2 3 Electrode insulation    Good insulation of the electrodes is very important because any path of electric current that flows  between the electrode and steel wall other than through the material may cause false detection  For  example     e Any metallic contact between an electrode and the steel wall will cause a very low resistance   The CHS will falsely indicate that material  bagasse  is present at that electrode  The CHS11  has no means to determine whether a low resistance is due to metallic contact or contact by  the bagasse     e Excess water around the electrode or between the electrode and st
33. nsing channels which may be used in a single chute  or split  into 8   8 channels for a dual chute configuration  When in dual chute configuration  the detection  state and output state registers are split into two groups of eight  and the logic processing and  outputs are independent for each group  For brevity  the following descriptions refer to only to single  chute configuration because the principle of operation is very similar for the dual chute  configuration     Each electrode is scanned in turn by connecting the electrode to the conductivity detector for a brief  period of time  The measured conductivity is compared with the threshold value  a parameter that is  normally set to 5096  and if the conductivity is greater than the threshold  the detector output is on   The recommended method of adjusting the detection is to change the sensitivity  using a trimpot   rather than the threshold parameter     A programmable hysteresis algorithm is used to filter any momentary changes in conductivity  A   sensor  is the combination of the electrode  sensitivity trimpot  detector and hysteresis algorithm   The output from the hysteresis algorithm is directed to memory registers that hold the detection  state for each sensor  The detection state can be either    covered    or  uncovered   The term    covered     means that material was detected and  uncovered  means that material was not detected     28    sa     The detection state is used as input for the logic processor whic
34. of this manual for more  details on the threshold parameter           47    sa     sa   11 0 Frequently Asked Questions  FAQ     Question  What are the cable specifications for the installation of the CHS11     Analog Outputs  single or twin twisted pair instrumentation cable with screens for individual pairs  and an overall screen is recommended  An example of suitable cable type is Belden 9841  single pair   and Belden 9842  twin pair   For details please refer to www belden com     Electrode connections  use a multi pair overall screened cable suitable for industrial environments   Recommended types include Belden 9539  9 conductors each of 24 AWG  which allows for  connection of eight electrodes plus one wire for sensor common  The length of the cable should not  exceed 25 meters  The screen at the chute end of the cable should be unconnected  The screen at  the CHS11 module end of the cable should be connected to the power supply common  To improve  mechanical connection of the wires to the electrodes it is recommended to terminate the screened  cable inside a waterproof junction box mounted on or near the chute  This allows more robust wires  to be connected to the electrodes and then to the junction box terminal  e g   1 5 mm  plastic  insulated stranded copper wire   Please refer back to the Electrical Installation for more details     Question  Why does the display show that some sensors are not covered     This may happen when the CHS11 is in Mode 4 which means that
35. or level indication and for chute height control   Sixteen SPST relay outputs  each corresponding to an electrode  provide a discrete indication of  chute height using lights or for connection to digital inputs of an automation system     The user interface consists of a liquid crystal display and three push button keypad  It shows the  output as a percentage and as a graphical representation of chute height and allows the CHS11 to be  configured by setting the number of electrodes  threshold  hysteresis  mode and other parameters     There are 16 electrode inputs for connection to sensors in one or two chutes  Up to 16 sensors may  be connected in one chute and 8   8 when connected to two chutes  The CHS11 includes two  independent sets of configuration parameters for independent operation when used to measure  level in two chutes  Aside from the user interface there are two manual adjustments  one per chute   required to set the sensitivity of the detection circuitry        f b  NOTE   The minimum moisture content of bagasse for consistent detection by the  CHS11 is 4596  Bagasse any drier than this cannot be reliably detected              Copyright    2013 Sugar Research Institute page 1    sb    Copyright    2013 Sugar Research Institute page 2    sb    Fr    2 0 Specifications    2 1 CHS11 processing unit    Absolute maximum ratings    Supply voltage input  continuous  28 VDC  Voltage on any sensor inputs 50 VDC  Voltage on current outputs 36 VDC  Relay contact current  
36. outputs    A single  normally open  dry  relay contact is available for each sensor  Each relay contact closes if its  corresponding sensor is covered        P  NOTE        There are no internal fusing on the relay outputs and external fuses required to  limit the current to the value listed in Section 1 1              4 2 4 Electrode connections    The physical arrangement of electrodes is illustrated in Section 2 of this manual  A crimp lug and  locknut are provided with the electrode for connection of 1 5 mm  plastic insulated multi strand  copper wires to the electrode  Each electrode requires one wire     A connection must also be made between the steel chute and the CHS11    sensor common    input   Two inputs are provided on the CHS11 for the sensor common for connections  If the CHS11 is used  in single chute configuration  only one sensor common input needs to be connected  For dual chute  configuration  both chutes need to be connected to the sensor common inputs  The sensor common  must be connected using one of the conductors in the screened cable     The wiring between the CHS11 and the electrodes should be multi pair overall screened cable  suitable for industrial environments  Recommended types include Belden 9539  9 conductors each of  24 AWG   The length of the cable should not exceed 25 meters  The screen at the chute end of the  cable should be left open circuit and the screen at the CHS11 end of the cable should be connected  to the power supply common  To
37. owchart of LCD SCrEONS Re Henri dlstt  nrestrrser   ter dnenea ea ot rene e este etes titre Rate tanins sente d   tan rene 38  9 3 LED SCheOINS evs                                                                                         39  eme UII                                            39  9 3 2 Config  re CHS11 SCr  en    tne ec rec eei terr e eer re teni vt eene ette ees 39   9 3 3 Number of Chutes Selectii rr m                             40   9 3 4 Number Of Sensots    cucine oed tne Re ree bed Ee oL n HR e ua Ie ni ea nca Mie Ra RE Tu Pr ee RM CR Sa EASE E Raa aE a geb RE RR pud 40  9 3 5iDetection  ofer 41   9 3 6 DE Lau  ee 41   3 7 Waits rollo APEA EDE AE ESTE AE A O sieste init sag suave lane sets chart delete etes ce ue vacd 42   QO SiS MACC                                                 42   9 3 9 Hysteresis High ce iet n etna ede RAISING BINE UN HEISE HIT 42  93 10 Z  ro  I                                                             rene es 43   DS TL Span Ao UE MESPE      n 43  93 12 Configuration EITOF        aii rer ir ne te en FELIS IHE IH PO GAR TEE Re ER HER Eee Roe ERE FREUE TERR vi Peces ide pee Ree Pe CERE 43   10 0 Troubleshootihg            eic etm eii ht c b eh dva re nt ben ee ee rte 45  10 1 Self test  dares                             45  10 2 Troubleshooting Guides m                                               Eneee Ent 45  11 0 Frequently Asked Questions  FAQ     sisi 49  12 0 ETSI r                                                51    Copy
38. ower     60 W  Rated contact voltage  AC      24 VAC  Rated contact voltage  DC      30 VDC                      NOTE              Relay contacts are not suitable for mains level voltages  110 240 VAC   Use a  separate relay with the appropriate rating if switching mains level voltages              Copyright    2013 Sugar Research Institute page 4    Environmental conditions                            Specification Min   Typical  Storage temperature range 0   70   C  Operating temperature range 5   50   C  Ambient humidity 20   70  RH  Vibration  10 to 60 Hertz      0 02 G  Shock Not permissible                Physical characteristics    Dimensions  Protection rating  Material   Mounting   Weight  approximate     2 2 AC power    210 x 90 x 60 mm  WxHxD   IPOO   Polycarbonate   35mm DIN   0 3 kg    The CHS11 is designed for a nominal 24 VDC input supply  If this is not available  a suitable modular  power supply unit is needed in close proximity to the CHS11  The following output specifications are    required     Specification                   Output voltage   24   VDC  Output voltage tolerance    10      Rated output current  no temperature derating  1     A  Output ripple at full load     0 2 VDC                      2 3 Processing unit enclosure    The CHS11 is a DIN rail mounted unit  designed for mounting in a control cabinet  If mounted in the    field  a suitable IP rated enclosure is required     Copyright    2013 Sugar Research Institute    page 5    sb    Copyright
39. proximately 4 mA  it is most likely that the wrong output has been  connected  Make sure that the Analog output A  not B  is connected for  single chute applications    e  f the CHS11 is configured for dual chute and the analog outputs appear  abnormal then check that the connections from the outputs to the user  equipment are not swapped    e The load resistance may be too high  outputs must be terminated with a  resistance in the range listed in the Specifications section of this manual    e 24 volt power may be disconnected to the CHS  inspect the power on the  LED at the CHS11 module     it should be on    e Check the analog output matches the output percentage displayed on the  LCD output screen    e Check that the connection is not reverse polarity    Symptom As the chute fills the output changes erratically          Possible Cause  and Remedy       It is normal to observe some minor  step changes  in the output signal as the  chute level changes  This is because the analog output is proportional to the  number of sensors  as one sensor turns on  the output will step up  The  damping adjustment is provided to reduce the effects of the step changes  but it also delays the response of the CHS11     If the electrode wiring is not connected in the correct sequence  the output  will behave erratically as the chute fills and empties  This can be checked by  following the procedures detailed in the Commissioning section where the  CHS11 is put into Mode 4 to check the operatio
40. re is a limit to the range  of conductivity that the material may have for good detection  If for example the material is  sometimes very wet and other times dry  it may be difficult to set the sensitivity adjustment that will  provide consistent detection     The second characteristic of importance is the physical characteristics of the material  Physical  contact needs to be made between the material and each electrode to allow the CHS11 to detect  conductivity between the material and to the chute  sensor common   The material also needs to fall  cleanly away from the electrode surface when the chute level falls     7 2 2 Electrode Surface Area   The CHS11 detects the conductivity between each electrode and the material in the chute  Increasing  the electrode surface area has the same effect as increasing the sensitivity  Some CHS11 applications  may require special electrodes with larger surface area  and therefore greater conductivity  so that  the material can be properly detected  Examples of materials that may require large surface area  electrodes include those comprised of spherical particles     7 2 3 Using the CHS11 with Non conductive Materials    The CHS11 may be used with other forms of detectors such as those described in Section 7 under     Interfacing with Proximity and Limit Switches        33    sa     sa     8 1 Using the Relay Outputs    There are 16 relay contact outputs that correspond to the 16 electrodes  Typical uses for the relay  outputs include  
41. re sometimes a problem  The problem can VV J      m  occur for more than one sensor at the same time    Excess water is sometimes a problem  The problem never   J m  T x  occurs for more than one sensor at a time    Excess water is sometimes a problem  The problem can   m T       occur for more than one sensor at the same time    Excess water and air pockets are sometimes a problem      x x x x vv                         TN  NOTE     pockets and excess water  In this case it is recommended that the electrodes    T   M The logic processing is not effective when trying to resolve the combination of air       should be relocated or the source of excess water removed        25          sa     sa     6 1 Configuration    The CHS11 is configured using the LCD and three button keypad which are located on the CHS11  electronics module board inside the enclosure  The LCD shows a number of parameter and options  that can be set to suit specific applications        m NOTE       Prior to the commissioning and configuration of the CHS11  the procedures  outlined in Section 3 of this manual must be completed              6 1 1 Entering Configuration Mode    The CHS11 enters configuration mode when the enter button is pressed at the configure CHS11  screen  see below      When the CHS11 is in configuration mode  parameters can be changed and adjusted  There is no  interruption to normal operation of the CHS11 in the configuration mode              The sequence of screens is explained in the
42. red with 16 sensors  Sensors 1 to 4 are ON and sensors 5 to 16 are  OFF     In dual chute mode the output screen will appear like this        The display shows that Chute A and Chute B are both configured for 8 sensors  Chute A is full  all  eight sensors are ON  and Chute B is empty  all eight sensors are OFF      9 3 2 Configure CHS11 Screen    By pressing the Enter button when the output screen is shown  the CHS11 configuration screen will  be displayed which allows the user to enter the configuration mode or return to the output screen   The Firmware Version is also displayed here  as show in the following example        By pressing the Up button  the CHS11 will enter the configuration mode  Note that the CHS11 will  continue to scan the sensors and produce outputs when the CHS11 is in configuration mode so there  is no interruption to the operation of the CHS11  Once being in configuration mode  the user must go  through all configuration screens before returning to the output screen  see Figure 14      Pressing the Down button will abort entry to the configuration mode and the output screen will be  displayed     39    sa     9 3 3 Number of Chutes Selection    This screen allows the user to select either single chute or dual chute configuration  Pressing the Up  button will toggle between the two options which appear as follows     Note that changing this option will change the way the configuration screens are displayed  If in  single chute mode  i e  Chute A Only   t
43. right    2013 Sugar Research Institute page ii    sa     The SRI CHS11 Chute Height Sensor measures the level of prepared cane or bagasse in a Donnelly  chute feeding a sugar cane crushing mill  Unlike other level sensors  the CHS11 does not require a  clear line of sight to the material surface  so accuracy is not affected by steam  vapor or material  feeding into the top of the chute     The CHS11 operates by measuring the electrical conductivity of an array of electrodes mounted in  the wall of the chute  The outputs are proportional to the number of electrodes covered with  material  A user interface is provided so that the CHS11 can be configured to suit a range of  applications  One CHS can be used to measure the level in one or in two chutes     Conductivity is detected when the bagasse comes in contact with metallic electrodes mounted within  the wall of the chute  The presence of the bagasse causes the electrodes to be electrically connected  to the body of the metallic chute  The CHS11 electronics measures a small electric current that is fed  to each electrode and detects if the current is greater than a threshold indicating that the electrode  is covered     The CHS11 includes a number of features to improve the reliability of detection including  programmable threshold and hysteresis  It also has a logic processor that can be configured to  ensure that the CHS11 provides the most faithful indication of chute height     The two 4 20mA current outputs can be used f
44. s Parameters                                      seen 31  7 11  Using the Dambping Pafaimetels        ie e eerte he heredi ent ix esas cessed AEAEE e ara aaia 31   7 1 2 Using the Thershold Parameter sise 31  7 1 3 Hysteresis AdjUStmieLit      5  6 x rrr beret E ve erdt ree A Bie Hd RS b RS 32   7 2 Using the CHS11 for Materials other than Bagasse rs 32  7 2 1 Characteristics of the Material for Reliable Detection    ss 33   7 2 2 Electrode Surface Area    centre RH saesae ranei aae eaa e tL A AEEA SE Oa bete SER ea LAT Ra ee LER e PEE SEN UR   s ua ER Eee Rn te 33   7 2 3 Using the CHS11 with Non conductive Materials    33   8 0 Application Briefs                   monere ricette Ri niaaa KE Nea ae e Te RADO enns dpi era aana Fea ed ieo AE note tnt ee 35  8 1 Using the Relay Outputs    eerie edt be etiarn ates re ade xia teste A EE Reese Te utere inu aas asic qa helene le 35  8 2 Material Presence Detection    sise 35  8 3 Interfacing with Proximity and Limit Switches sise 36  84 Split Sensitivity Adjustment    ede ice tec eco reda gerk nado asi cg a Aaea ANa A sme eraa sA ESEE ps andes Nai Eis gra 36  8 5 Irregular Electrode Spacing           cccscccssceesseesecsseecenecsseesssecsaeecsusesseesensesueesaeecuecsaeessaeesseesssesuaeeseaeeseesceaeesenesseessnsseneesenes 36  9 0 Keypad and LCD Reference    er eicere eter ite Le sdb anne ode tte ant eue ane coal ape cR e EE eva lee ane d  ni 37  LAN Taro                                                              M   37  9 2 Fl
45. s have been coated with some form of  insulating material  Check the installation with reference to the Mechanical  Installation section of this manual           Symptom    The LCD shows that all sensors are ON even when the chute is empty or the  LCD shows that some sensors are ON even when material is not contacting the  electrode          Possible Cause  and Remedy       This may occur if the sensitivity is too high  sensitivity trimpot is too far  anticlockwise   Check whether the sensitivity adjustment has been set as  described in the Commissioning section of this manual     The electrodes may be incorrectly installed or the electrode insulators may  have failed  Check the installation with reference to the Mechanical  Installation section of this manual     Material may be deposited on the electrodes  or water may have gathered  within the spaces between the electrode insulators and the steel chute  This  will cause an unwanted path for electric current to flow and will result in  false sensor detection     The electrode wiring may be faulty or incorrectly installed  Check that the  electrode wiring is connected properly and the sensor common connection  is connected to the chute  Check for short circuits between the electrode  wiring and sensor common and to earth     The threshold parameter may be set incorrectly  This will most likely be the  case if the setting is too high  A threshold of 50  is recommended for most  applications  Refer to the Applications section 
46. s wide sensitivity adjustment to cater for many different variations of electrode  placements and arrangements  If the CHS11 is to be used to replace an existing conductivity based  chute height system it is likely the existing electrodes may be reused     Nonetheless  SRI offers two types of electrodes for new installations  or for situations where existing  electrode arrays cannot be reused  Non insulated electrodes are preferred because they offer the  best insulation properties when mounted in a polycarbonate sheet  which in turn gives highest  adjustment and best height indication outcomes  If non insulated electrodes are not suitable  SRI can  also provide insulated electrodes suitable for direct mounting in the chute     The electrode array depends on     e The number of chutes to monitor  single chute or dual chutes     e The method of electrode insulation    e Which face of the chute to install the electrodes  sides  front or back    e The number of electrodes    e The positions of the highest and lowest electrodes in the chute  and   e The spacing and position of each electrode     3 2 1 Non insulated electrodes    The preferred non insulated domed electrode is shown in Figure 2                                               Figure 1  Preferred domed electrode    Copyright    2013 Sugar Research Institute page 8    sa     The preferred method of insulation is to use a 6mm polycarbonate sheet window to mount a series  of the domed electrodes shown in figure 2  A recta
47. t are not covered  and set the output state for those sensors and all higher sensors to OFF   3 Scan from top sensor to bottom sensor  Find two consecutive sensors that are covered and  set the output state for those sensors and all lower sensors to ON   4 No logic processing  the output state is the same as the detection state   9 3 6 Damping    The output signal damping  see illustration below  is described in Section 5 of this manual  The range  of setting is from 1 to 30 seconds  See the Application section of this manual for more detail     41    sa     9 3 7 Threshold    The detection threshold for the sensors  see illustration below  is described in Sections 5  6 and 7 of  this manual  It is normally set to a default value of 50   The sensor detection is adjusted using the  sensitivity trimpots  When the range of sensitivity adjustment is not sufficient it is possible to adjust  the detection threshold        9 3 8 Hysteresis Low  Hysteresis low is a parameter used by the sensor detection algorithm  Normally it is set to 30   see    illustration below  and this is the recommended setting for most applications  Please refer to the  Applications section of this manual for more details     9 3 9 Hysteresis High  Hysteresis high is a parameter used by the sensor detection algorithm  Normally it is set to 70   see    illustration below  and this is the recommended setting for most applications  Please refer to the  Applications section of this manual for more details     42
48. tutore deren een a ee Le e em EIE d 21  LN                                                                                         21  5 2  Setting the Jumper LINK   coit vet rr EE RR e Ree Dera tein este E encens dieses eve ivit veste citons el enon na 21  5 3 Entering Default Settings at the CHS11 User Interface sise 22  5 4 Adjusting the Trimpots to a Default Position sise 22  5 5 Adjusting the Analog Output Zero and Span ss 23  5 6 Viewing Operation in Mode 4    eene nennen enne eiaa aari anaa eet Aae enana tentes enn nnns entrent 23  5 7 Adjusting the Sensitivity Trimpots             rcs nrettnpeic dnte tento La une enoi eksais ek ra lean na annum une aea era aL a Eaa 23  5 8 Check for Problematic Sensors  An Example iii 24  5 9 Setting the Mode of OperatiOri        2   rin e t eerie seien rte vo ge e ente v Re es 25  6 0 Configuration and Operation                iere cette anten eene NECS ERA ange Ee ekia i snae abo nu Renan edge nin eu Gun Na pes praed 27  Gel Config  ratiOni soi ae edi RR eR EM Sun Rene E irm ere peti eH vU eie rper e ene  27  6 1 1 Entering Configuration Mode    ais ertet etr tte tee i te i te cree sien vv edt die com 27    Copyright    2013 Sugar Research Institute pagei    Mecum                                                                                   28  6 3 Sensor Detection and Logic Processing iii 28  7 0 nmi                                                                                   en bon 31  7 1 Damping  Threshold and Hysteresi
49. vel alarms for each tank     e Electrodes are fitted to 4 chutes with each chute having 4 electrodes fitted as described in Section  2 of this manual  The relay outputs are connected to the digital inputs of a control system which  converts the digital signals into levels of 0   25   50   75   100         di i NOTE       For each of the examples provided above  the analog outputs would not provide a  meaningful signal              35    sa     8 3 Interfacing with Proximity and Limit Switches    Because CHS11 electrodes detect conductivity  the sensor inputs can be connected to any circuitry or  sensing element that has low conductivity in one state  e g      ON     and high conductivity in another  state  e g      OFF      Please observe the specifications in Section 1 1 for the electrode inputs  Ideally   the external circuitry will be from a voltage free contact    Examples of devices that may be connected between the electrode inputs and electrode common  terminals include     e Relays    e Proximity switches  e g   capacitive  inductive or ultrasonic    e Photoelectric sensors with a volt free output    e Limit switches  and   e Push buttons  selector switches and other operator controls     8 4 Split Sensitivity Adjustment    As described in Section 3  the CHS11 module has a jumper link labelled    X1    and two trimpots  VR1  and VR2  that allow separate sensitivity adjustment for sensors 1 to 8 and 9 to 16  The intended use  of the separate adjustments is to allow the
50. was configured for Detection Mode 1  Thus new electrodes were  fitted to a different position at a later time in a location where the physical contact with the material  was improved     Chute B Solution   The chute was emptied and the inside and outside surfaces were inspected and found to be free of  excess water  Hence the electrode for Sensor 4 was removed and the insulator inspected in order to    check for direct metallic contact between the electrode and chute wall  The electrode was refitted in  accordance with the instructions in Section 2 of this manual and the problem was resolved     24    sa     5 9 Setting the Mode of Operation    For most applications  the mode of operation should be set according to the criteria presented in  Table 4 which usually requires viewing the operation in Mode 4  In the criteria below     air pockets     means that the CHS11 indicates that one or more sensors are OFF when the level in the chute is  above those sensors     Excess water    means that the CHS11 shows that one or more sensors are ON    when the level in the chute is observed to be lower than the sensors     Table 3  Mode of operation criteria                      Mode  gt  Criteria 0   1 2 3   4  All sensors properly detect the presence and absence of   material  There are no problems observed from excess water   Y Y v Y v x  or from air pockets    Air pockets are sometimes a problem  The problem never   VV m L    occurs for more than one sensor at a time    Air pockets a
51. ys     e The analog outputs are ramped to match the relay settings     e The sequence is repeated until the Enter button is pressed  and    e The speed of the sequence can be changed by pressing the Up or Down buttons     10 2 Troubleshooting Guides                         Symptom The LCD shows a    CONFIG ERROR    message   Possible e The CHS11 stores parameters in non volatile memory so they are maintained   Cause and when the power is switched off  If that memory is corrupted then the    Config   Remedy Error    message is displayed  Press the Enter button to automatically restore  the parameter to a default value    Symptom There is nothing shown at the LCD and the LCD backlight is not lit        Possible Cause  and Remedy          Check that voltage is present at the CHS by opening the cabinet and  checking the power on LED at the Module  If the LED is on then power is  available  check the LCD cable connections at the rear of the LCD and at the  Module connection  If the LED is off then power is not available at the input  of the CHS or there may be some fault within the input protection portion of  the Module  Remove power from the CHS and reapply whilst viewing the  power on the LED on the Module     Check that the 24 volt power connection is not reverse polarity           45    sa        Symptom    The 4 20 mA output does not function as expected       Possible Cause    If the CHS11 is configured for single chute and the analog output is always          and Remedy ap
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
FT TENSIOMETRE POIGNET DEC 2014  User Manual - CCTV Cameras  GALAXY S4用2ndバッテリ 充電スロット付きクレードル  Installation Instructions / User`s Manual NAXA00101DB  Samsung 763MB Computer Monitor User Manual  Digital Video Enhancer and Duplicator Model CT  Topspin User Guide CHs - Pascal-Man  Gembird KBS-P7-DE      Copyright © All rights reserved. 
   Failed to retrieve file