1. Adira series 57 UPS Adira 6kVA 6kVA XL 10kVA Operation 10kVA XL 1 phase 7 3 3 Measurements Menu Out put 850w 1130VA Input PL Output anov 220V Out put e m 49A 75 ail 5400 W A Out put 230 4V 50 0Hz Event log AN QO A Line input xxxV xxHz Battery 54 2 V 100 DC Bus 360 1 V 359 9 V Temperature 22C Fig 7 15 Measurements Menu Adira series 58 UPS Adira 6kVA 6kVA XL 10kVA Operation 10kVA XL 1 phase Parameters Description Display Output Displays the power output of the UPS Left value active power Right value apparent power Display Output Displays the output current of the UPS Left value output current Right value output current in percent Display Output Displays the output voltage of the UPS Left value output voltage Right value output frequency Display Input Displays the input phases Display Battery Displays the battery voltage and the charging status of the UPS Display DC Bus Displays the DC bus voltage of the UPS Display Temperature Displays the temperature of the UPS Adira series 59 UPS Adira 6kVA 6kVA XL 10kVA Operation 10kVA XL 1 phase 7 3 4 Control Menu trout D Output 220V m 220V au I 5400 W Single UPS battery Status battery test test OK Start battery test no Clear EPO status Status EPO active A Cl
2. 10KVA Troubleshooting 10kVA XL 1 phase every 4 seconds Check if the input breaker is closed Emergency supply Batteries not fully charged Charge the batteries for at least period shorter than batteries defect 12 hours and then check capac nominal value ity Adira series 71 UPS Adira 6kVA 6KVA XL 10kVA Troubleshooting 10kVA XL 1 phase Adira series When you contact the service centre please provide the following information Model number serial number Date on which the problem occurred LCD LED display information Buzzer alarm status Mains power condition load type and capacity environment temperature ventilation condition The information battery capacity quantity of external battery pack if the UPS is S model Any additional information for a complete description of the problem 72 UPS Adira 6kVA 6kVA XL 10KVA Software 10kVA XL 1 phase 9 Adira series Software With a suitable software package the configurations and operating statuses of the UPS can be determined and processed via the communication interface The software packages are available from the manufacturer dealer or through the service hotline Through these channels you can receive useful information about the suitable software packages for your UPS to fit your needs See also our website http www effekta com The following basic functions are supported by all software packages
3. Adira series 18 UPS Adira 6kVA 6kVA XL 10kVA UPS Device Description 10kVA XL 1 phase 3 UPS Device Description This manual shall provide basic information about one phase UPS systems of the Adira series like the mode of operation utilization of the different functions and what to do in case of malfunctions In addition this operating manual con tains instructions for the proper transportation and storage as well as for the handling and installation of the UPS equipment The planning guidelines in this manual refer only to the specific requirements of UPS systems National and regional regulations for electrical installations have to be adhered to when installing the system The content of this device descrip tion may change due to technological developments We have made every ef fort to ensure that all content is accurate and presented in a clear and compre hensible manner In case of any errors we are grateful for advice and sugges tions We do not assume any liability for any errors in this manual or any conse quences resulting thereof The UPS system uninterruptible power supply is designed to protect sensitive electronic equipment like computers work stations electronic cash registers operations critical instruments telecommunication systems process controllers etc from interferences that can result from poor power quality or mains failures Sensitive equipment of this sort needs comprehensive protection from
4. Unauthorized persons should not have access to the accumulators Do not place accumulators in the vicinity of heat sources and do not throw them into a fire Explosion hazard Do not open or destroy accumulators The released electrolyte presents a great danger to health and the environment chemical burns to skin and eyes toxic 17 Safety Instructions UPS Adira 61 LAY 10kVA XL 1 p AY e Defective accumulators have to be disposed of in an environmentally compatible manner Fr x Never dispose of accumulators with regular household waste Local disposal regulations must be observed 2 8 Maintenance Service and Malfunctions Attention Danger of electric shocks Even after switching off the supply with the power button or after discon necting the accumulator feed respectively parts of the UPS can still carry high voltages ATTENTION Only trained electricians with sufficient knowledge of the required safety regulations may perform work on accumulators or supervise such work tasks Unauthorized persons should not have access to the accumulators The following precautions must be taken when working on the UPS or the accumulators Remove wrist watches rings and other metallic objects Use only isolated tools that comply with electrotechnical regulations Wear personal protective equipment safety glasses gloves face shield etc The UPS may not be disassembled
5. r UPS on UPS shut down 2 Mains failure 1 Neutral point Fig 6 1 Dry contact relay output contact ATTENTION The relay output contact may not be connected to circuits that are connected with the mains power supply Feeders must have reinforced insulation Adira series 43 UPS Adira 6kVA 6kVA XL 10kVA UPS Installation and Connection 10kVA XL 1 phase 6 4 2 Configuration of the EPO port Conductor Size of connecting wire function EPO 0 5 1 mm i Leave the EPO plug installed on the EPO port of the UPS even if the EPO function is not needed Fig 6 2 EPO plug Please see the information regarding the connection of the EPO contact in chapter 3 3 3 EPO port Adira series 44 UPS Adira 6kVA 6kVA XL 10kVA UPS Installation and Connection 10kVA XL 1 phase 6 5 Adira series Operating procedure for the connection with an external battery The nominal DC voltage of the external battery pack is 240VDC Each battery pack consists of 20 pieces of 12V maintenance free batteries in series To achieve a longer back up time several battery packs can be connected but the principle of same voltage same type has to be strictly observed The procedure for the installation of the battery bank must be strictly observed to avoid the risk of an electric shock e Use only the items listed under accessories This includes the compatible battery bank and the correspo
6. ser 34 System Description ne nee tigre ne ree n etre 38 UPS Installation and Connection nent 40 Notes on the installation 40 Connecting the UPS ire 41 Communication port of the UPS sise Connection sequence Operating procedure for the connection with an external battery Feedback protection sense Operations E AA E e ETE ne NEEE ne ee en etre enter ent 47 Op ration of the UPS anna nn 47 PS operating instructions urn une nn in anehun 52 Adira series 3 UPS Adira 6kVA 6kVA XL 10kVA Contents 10kVA XL 1 phase 7 3 MON on nette in end te tree Pre dose dre detre nor rte er nes entend pee oral un 56 8 TroubleShooting issssssssscssnemennseeenmennremesenneeescess sasnet rarats reset edesdnre ianeseu ses 68 8 1 Troubleshooting according to warning indication 68 8 2 Troubleshooting according to fault indication 69 8 3 Troubleshooting in other Cases sante ten ea na 70 9 SOMWANE AE S A EE EEE ere en qe ee ane ner need nie eme r res m ne rene nee enter nan nent nn 73 10 Maintenance and Service 74 10 1 Measuring the backup time support time 74 10 2 Replacing the AcCUMUIALO S cccccesccnseeeesssecensosonsenssseorsuscceascsesensnencusucceseusssensnenessesenens 75 10 3 Service LOQ s e 10 4 Service Hotline 10 5 Maintenance and service contracts us 77 Tt Technical Data 2 ee ner mere near nine nu mme rare rene 7
7. 4 Adira series General symbols This dot marks descriptions of activities that you should carry out This dash marks specification lists This arrow marks a cross reference If a cross reference to another chapter is necessary in the text this is short ened for clarity Example OM 2 Safety Instructions This means See Operating Manual Chapter 2 Safety Instructions If the cross reference refers to a page figure or position number this infor mation is added at the end of the cross reference Example Fig 4 4 Pos 1 This means See position number 1 in figure 4 in Chapter 4 of this manual Numbers in brackets refer to the positions in the figures Identifies instructions for recycling Identifies components that are subject to the Electronic Scrap Regulation Identifies components or parts that must be disposed of Do not throw these into the household waste Requirement that must be fulfilled V The DC circuit breaker is on OFF UPS Adira 6kVA 6KVA XL 10kVA Introduction 10kVA XL 1 phase 1 5 1 6 Adira series Information Obligation This operating manual must be read understood and all its points must be taken note of by all persons that are responsible for the Operation Cleaning and Disposal of the device EFFEKTA Regeltechnik GmbH is not liable for damage incurred or caused by staff who have not been trained or who have been insufficiently traine
8. 4 1 4 2 4 3 5 6 6 1 6 2 6 3 6 4 6 5 6 6 7 7 1 7 2 Introduction Intr duelionz 2 Ra a SR EE RNA PR NAN A ARS vu 2 Validity Storage Symbols in this Manual Information Obligationen Warranty Conditions Transport and Storage Positioningkea 2 22ER nina Safety Instr cti ns 22 22 42344 200 r sident eav paapaa areas Eeoa Siar darain aesan Eisra iaria 14 IMTOAUCIOR EE AEAEE A E E A A 14 Proper USB H nin ennemie tir E SADETE STEE rente qe ent niet einer ee 14 Avoiding Personal Injury Property Damage cceeceeneeeeeeneeeeeeeeeeeeeeseeeeeaeeseaeeeeeee 15 Protecting the Environment ea nr 15 CONNECTION PRRPEPERFRREFERTREFEFTERFECPERRFGERPERAHELFORFEROFFERTREREPSREFHFSSETTRRNSERTGFFHFEFEREATEFEFFHRTERFENENSERTE 16 Op rations sise an nn tenes ie eae ana 17 Working with Accumulators sisi 17 Maintenance Service and Malfunctions cccccccssssscceceecesssseeeeeeccsssssseeeeeeeessstseeeeeeess 18 UPS Device Description ssnnsnnnecennns 19 Elements on the front of the device oe ee eeeeeceneeeeeeeeeeeeeeeeeaeeeeeeeeeeeseaeesieeeeateneeeeeae 20 Elements on the back of the device 25 GOMPONCNtS sy cee ee Sen Rein tn te sn es rate Send i cts 31 Storage and Unpacking nnnnnnnnnnnennenennennnnnnens 34 Storage of th UPS nn ne en AR nent te 34 Moving the UPS to the installation site 34 Unpacking of the device
9. Adira series 67 UPS Adira 6kVA 6kVA XL 10kVA 10kVA XL 1 phase 8 Troubleshooting Troubleshooting If the UPS system does not operate correctly first check the operating informa tion on the LCD display Please attempt to solve the problem using the table below If the problem still persists consult your dealer 8 1 Troubleshooting according to warning indication Problem Displayed Possible cause Troubleshooting measures Read EEPROM Error UPS internal fault Consult dealer EPO Active EPO connector is open Check the EPO connector status On Maintain Bypass Maintain bypass switch is open Check the maintain bypass switch status IP softstart failed UPS internal fault Consult dealer Site Wiring Fault Phase and neutral conductor are reversed at input of UPS system Reverse mains power wiring Battery Disconnect Battery pack is not connected correctly Do the battery test to confirm Check if the battery bank is connected to the UPS Check if the battery breaker is turned on Battery low Battery voltage is low If an audible alarm sounds every second the battery is almost empty Output Overload Overload Check the loads and remove some non critical loads Check if some loads have failed Fan Failure Fan abnormal Check if the fan is running nor mally Charger Fail Charging fails Con
10. Detecting and displaying the UPS s power supply status Display of the UPS output status Detecting and displaying the charging status of the battery bank Closing of open applications in the case of a mains failure Shut down of the operating system Creating log files Basic monitoring of UPS data and condition diagnostic function For more information on the individual software packages like installation op eration and range of services see the respective software manuals In the chapter Scope of Delivery Optional Accessories you will find suitable and tested software packages 73 UPS Adira 6kVA 6kVA XL 10kVA Maintenance and Service 10kVA XL 1 phase 10 10 1 Adira series Maintenance and Service You may expect a long service life and interference free operation of your UPS at a minimum of maintenance effort However the reliability of the UPS is greatly dependant on the ambient condi tions The ambient temperature and humidity must remain within the given range In addition the area around the UPS should be kept clean and free of dust At an ideal ambient temperature of about 22 C the service life of the accumula tors is typically around 4 years Through the use of special accumulators the service life can be significantly increased about 8 10 years You should check periodically every 6 12 months whether the remaining backup time is sufficient for the intended purposes
11. all elec trical interference These may either be external interferences like e g light ning disruption of operations or interferences from other devices in its vicinity e g engines air conditioning processing machines welding facilities or the like Power interferences can be summarized as follows rapid or slow voltage peaks or fluctuations mains failure power overlaps or transients The UPS system monitors the above mentioned grid parameters and protects all connected appliances through appropriate countermeasures e g switching to bypass mode when temporary over or under voltage of the grid is detected to protect the end device Adira series 19 UPS Adira 6kVA 6kVA XL 10kVA UPS Device Description 10kVA XL 1 phase 3 1 Elements on the front of the device On the front side of the device are all operating and display elements necessary for the normal operation of the UPS 1 LCD Display Fig 3 1 Frontal view Adira UPS Adira series 20 UPS Adira 6kVA 6kVA XL 10kVA UPS Device Description 10kVA XL 1 phase 3 1 1 LCD Display NORMALI BATTERY BYPASS FAULT Status Display LCD Display Select button Menu Down Next button Menu Up Back button ON OFF button O OC BB ND Fig 3 2 Control panel The back lighting of the LCD Display changes its colour depending on the device status Colour Meaning blue normal operating mode red fault mod
12. measurements men tioned above for cables for the individual models and a yellow and green striped wire is to be used e Check after completing the installation if all the wiring is correct e Please install the output circuit breaker between the output terminal and the load and the circuit breaker should be equipped with a fault current protective function if that is required e To connect the load with the UPS first switch off all loads then establish the connections and then switch the loads on again one after the other e Regardless whether the UPS is connected to the mains power supply or not the output of the UPS may still be energized The parts inside the unit may still carry dangerous voltages even after the UPS has been turned off To ensure that the UPS does not emit any electric charge turn off the UPS and disconnect it from the power supply e We recommend that you charge the batteries for at least 24 hours before using the unit Turn the input breaker to ON after connecting the device The UPS charges the batteries automatically You can also put the UPS 41 UPS Adira 6kVA 6kVA XL 10kVA UPS Installation and Connection 10kVA XL 1 phase 6 3 6 3 1 6 4 Adira series into operation immediately without charging the batteries first however the backup time may be below its regular value Communication port of the UPS The UPS is equipped with a convenient communication interface to facilitate the e
13. series 61 UPS Adira 6kVA 6kVA XL 10kVA 10kVA XL 1 phase Operation Clear event log lt No gt lt Yes gt No The warning fault messages have not been reset Yes The warning fault messages have been deleted No Restore factory settings Reset lt No gt lt Yes gt No The UPS will not be reset to factory settings Yes The UPS will be reset to factory settings No Adira series 62 UPS Adira 6kVA 6kVA XL 10kVA Operation 10kVA XL 1 phase 7 3 5 Identification Menu Input Pa Output 230V 269V 230V UPS Status 50 Hz pen 50 Hz anal wow o e e e Identification Type Model 6000VA Online standard model Serial Number 130311 65920004 UPS Firmware 05570 0400 Fig 7 17 Identification Menu Parameters Description Display Type Model Displays the UPS type model Display Serial number Displays the UPS s serial number Display UPS firmware Displays the current UPS firmware Adira series 63 UPS Adira 6kVA 6kVA XL 10kVA Operation 10kVA XL 1 phase 7 3 6 Settings Menu User password lt disabled gt Input PL Output 230V 269V 230V A 50 Hz sonz UPS Status Audlo Alarm ill IA lt enabled gt Output frequency lt 50Hz gt r strategy jormal gt Ambient temperature warning lt enable gt Automatic battery tests perlod lt 7days
14. sure that the air openings cannot be covered e g through sucked in paper material etc 13 UPS Adira 6kVA 6kVA XL 10kVA Safety Instructions 10kVA XL 1 phase 2 2 1 2 2 Adira series Safety Instructions Introduction The UPS is a device that has been produced according to the rules and regulations of technology for an uninterruptible power supply The device is safe when used properly and under consideration of the safety requirements and instructions provided in this operating manual Proper Use The UPS and its related components may only be used for purposes in accordance with its design to provide a short term supply for electrical devices 230 V AC with the nominal power not exceeding the total Any other use is considered improper and can lead to personal injury or damage to the device Improper Use The device is not designed for use in explosive dusty radioactive or biologically or chemically contaminated atmospheres ATTENTION This class A equipment This equipment can cause radio interference in residential areas In this case the operating company may be requested to take appropriate measures 14 UPS Adira 6kVA 6kVA XL 10kVA Safety Instructions 10kVA XL 1 phase 2 3 Avoiding Personal Injury Property Damage e Please read this operating manual carefully to familiarise yourself with the device e In particular take note of the information regarding the
15. technical inno vations or regulations that occur after the purchase Inthe event of incompatibility or malfunctioning that was caused by product components we did not install Inthe event of developments that are related to the normal ageing process of the product wear parts Inthe event of defects that were caused by external fixtures The warranty period for replaced and or repaired parts as part of this warranty expires together with the original warranty for the product Devices that are supplied without accessories are replaced without accessories The return of the device is only accepted if this is done in the original packaging Incurred transport costs are generally not included in the warranty You shall bear the cost of repair and exchange and the company is not liable for damage whether directly unintentionally specifically or for subsequent damage even if it was caused by negligence or other errors EFFEKTA Regeltechnik GmbH does not provide either explicit or implicit war ranties related to this device and its quality performance saleability or suitability for a certain purpose In some countries the exclusion of implicit warranties is not permitted by law In this case the validity of all explicit and implicit warran ties is limited to the warranty period With the expiration of these periods all warranties lose their validity In some countries a limitation of the validity period of implicit wa
16. terminals even while disconnected due to device internally loaded capaci ties As soon as mains input voltage is present the loading unit is automatically activated l e the internal battery bank is already being charged even though the UPS has not been switched on Adira series 25 UPS Adira 6kVA 6kVA XL 10kVA UPS Device Description 10kVA XL 1 phase 3 2 1 Model 6kVA 1 phase 123 4 9 5 6 8 7 e 1 USB port 2 Dry Contact 3 EPO port 4 Communication interface 5 Parallel port 6 Bypass switch 7 Connection terminals mains input and UPS output 8 Circuit Breaker mains input 9 Fan Fig 3 3 Back panel 6kVA 1 phase Adira series 26 UPS Adira 6kVA 6kVA XL 10kVA UPS Device Description 10kVA XL 1 phase 3 2 2 Model 6kVA XL 1 phase 1 USB port 2 Dry Contact 3 EPO port 4 Communication interface 5 Parallel port 6 Bypass switch 7 Port for external battery banks 8 Connection terminals mains input and UPS output 9 Circuit Breaker mains input 10 Fan Fig 3 4 Back Panel Adira 6KVA XL Adira series 27 UPS Adira 6kVA 6kVA XL 10kVA UPS Device Description 10kVA XL 1 phase 3 2 3 Model 10kVA 1 phase 9 4 5 9 6 8 7 1 USB port 2 Dry Contact 3 EPO port 4 Communication interface 5 Parallel port 6 Bypass switch 7 Connection terminals mains input and UPS output 8 Circuit Breaker mains input 9 Fan Fig 3 5 Back panel Adira 10kVA Adira series 2
17. warning about dangers If accident prevention measures are not taken these dangers may result in serious irreversible injuries or even death UPS Adira 6kVA 6kVA XL 10KVA Introduction 10kVA XL 1 phase Adira series Text that is marked with WARNING provides a warning about hazards If accident prevention measures are not taken these hazards may result in serious irreversible injuries or even death Text that is marked with CAUTION provides a warning about hazards If accident prevention measures are not taken these dangerous situations can lead to slight or medium reversible injuries ATTENTION Text that is marked with ATTENTION contains very important instructions for situations that if accident prevention measures are not taken may re sult in damage to the product and or its functions or an object in its vi cinity This symbol indicates text that contains important instructions comments or tips N UPS Adira 6kVA 6kVA XL 10kVA Introduction 10kVA XL 1 phase 1 4 2 Warning information 1 4 2 1 Warning about danger spots A General warning about danger spots 1 4 2 2 Specific warning Warning about dangerous electrical voltage A Warning about proper handling of accumulators 1 4 3 Instruction symbols li Take note of the provided documentation and or instructions Disconnect before work Adira series 8 UPS Adira 6kVA 6kVA XL 10KVA Introduction 10kVA XL 1 phase 1 4
18. 8 UPS Adira 6kVA 6kVA XL 10kVA UPS Device Description 10kVA XL 1 phase 3 2 4 Model 10kVA XL 1 phase 4 10 5 6 7 9 8 1 USB port 2 Dry Contact 3 EPO port 4 Communication interface 5 Parallel port 6 Bypass switch 7 Port for external battery banks 8 Connection terminals mains input and UPS output 9 Circuit Breaker mains input 10 Fan Fig 3 6 Back panel Adira 10kVA XL Adira series 29 UPS Adira 6kVA 6kVA XL 10kVA UPS Device Description 10KVA XL 1 phase 3 2 5 Adira series External battery bank for 6kVA XL and 10kVA XL UPS 1 Fuses 2 UPS connection port 3 Port for additional battery banks Fig 3 7 Back panel of external battery bank for 6kVA XL and 10kVA XL 1 phase 30 UPS Adira 6kVA 6kVA XL 10kVA UPS Device Description 10kVA XL 1 phase 3 3 3 3 1 3 3 2 3 3 3 Adira series Components USB port The USB port serves to connect the UPS to a PC Dry Contact For information on the dry contact please see chapter 6 4 1 Configuration of the dry contact EPO port The EPO port serves for an emergency shut down of the connected appliances This function can be used to shut down connected appliances in the case of an emergency This circuit has to be separated from high voltage circuits by reinforced insulation The EPO port may not be connected to circuits that are directly connected with the mains power supply Feeders must have reinforced insulation
19. 8 12 Scope of Delivery Optional Accessories mines 80 12 2 Wearing parts Ist rer 81 13 Conformity Declarations sens 82 18 1 Adirai RVA nern een are nn rien eating TS22 atolle Re AVAD A E EE EE son sandgeseansidgenathnstapaaeapibiessesigncseatisenthastassonepibates 13 3 Adira 10kVA 13 4 Adira 10kVA XL Adira series 4 UPS Adira 6kVA 6kVA XL 10KVA Introduction 10kVA XL 1 phase 1 1 1 Adira series Introduction Introduction Dear Operator You are about to operate an uninterruptible power supply This operating manual should provide you with support for working responsibly and basic information about the uninterruptible power supply namely how it op erates its application and what you should do in the event of malfunctioning Furthermore this operating manual contains instructions for the transport and storage as well as the handling and installation of the uninterruptible power sup ply The plan guidelines in this operating manual only relate to special requirements for the uninterruptible power supply During installation make sure you follow the national and local requirements for electrical installations The content of this device description may change due to technological pro gress We have tried to present the content correctly and clearly If however we have made errors we would be grateful for information about this We do not assume any liability for errors in this operating manual o
20. Adira series 78 UPS Adira 6kVA 6kVA XL 10KVA 10kVA XL 1 phase Adira series Technical Data Battery banks Model 6kVA 10kVA Type and number 20x12V 7Ah 20x12V 9Ah of internal batteries Charging rate of a battery pack 32Amax 50Amax Standards LVD EN 62040 1 2008 EMC EN 62040 2 2006 79 UPS Adira 6kVA 6kVA XL 10kVA Scope of Delivery 10kVA XL 1 phase Optional Accessories 12 Scope of Delivery Optional Accessories Below you find a list of components that have been approved and tested by EF FEKTA Regeltechnik GmbH especially for this UPS Please check the delivery for completeness immediately after receiving the goods 12 1 1 Scope of Delivery Adira No Description Function View Article number Scope of de livery 1 x UPS electronics Adira 6kVA incl internal batter ACX11ADS6K000M06 ies Adira 10kVA ACX11ADS10K00M04 UPS electronics Adira 6kVA XL excl internal bat ACX11ADS6K00X000 teries Adira 10kVA XL ACX11ADS10K0X000 1 x Battery banks for Battery Bank UPS 6kVA XL and with 20 accumulators 10kVA XL ABADX120009XX600 with 40 accumulators ABADX220009XX600 Operating Manual Printed Operating Manual X UPS Adira 6kVA 6kVA XL 10kVA 10kVA XL 1 phase Scope of Delivery Optional Accessories English 1 x USB cable Interface connection PowerShut Plus ware Software
21. Once that is no longer the case the accumulators have to be replaced Measuring the backup time Support time Before you begin this procedure please make sure to save all open data Furthermore inform all affected employees Basically there are two different methods for measuring the back up time Method a measures the actual back up time which means that at the end of that backup time the appliances would be without a power supply Method b allows to determine the residual capacity after a defined backup period In this case the appliances will usually not be without power in the end To use either method you have to force the UPS into backup mode by simulating a mains failure e g trip the fuse of the building Do not under any circumstances remove the mains connection as that would also dis connect the protective earth conductor After the measurement has been carried out turn the circuit breaker back on and turn on the UPS as usual with the ON button 74 UPS Adira 6kVA 6kVA XL 10kVA Maintenance and Service 10kVA XL 1 phase Remember that after the measuring the accumulators of the system will be dis charged l e the UPS system must operate in line mode or charging mode re spectively for several hours min 5 h before it will again be operational at about 80 capacity If the backup time is not measured due to local conditions or instructions we recommend a prophylactic replacement of the accumulators e
22. PS internal fault Consult dealer Bus Softstart Fail UPS internal fault Consult dealer Inv Over Voltage UPS internal fault Consult dealer Inv Under Voltage UPS internal fault Consult dealer Inv Softstart Fail UPS internal fault Consult dealer Negative Power Fault The load is pure inductive and Capacitive Remove some non critical loads Bypass supplies the load first ensures there is no overload then turns on UPS Cable male and female Loss fault The parallel cable is discon nected Check the parallel cable Fan lock fault Fan blocked or disconnected over time Check the fan status Back Feed Output voltage is returned to Consult dealer input 8 3 Troubleshooting in other cases Problem Possible cause Troubleshooting measures No display message no warning tone even though system is con nected to mains power supply No input voltage Check the building wiring and input cable Check if the input breaker is closed BYPASS LED lights up even though the power supply is available Inverter not switched on Press On Switch I to turn on UPS BATTERY LED lights up and audible alarm sounds of 1 beep in Adira series Input voltage and or frequency are outside the tolerated range Check input power source Check the building wiring and input cable 70 UPS Adira 6kVA 6kVA XL
23. The load capacity of the EPO switch must be at least 24 V DC 20 mA and it must be designed as a special snap switch without any connection to any other Circuit The EPO signal must remain active for at least 20 ms to ensure proper opera tion UPS Adira 6kVA 6kVA XL 10kVA UPS Device Description 10kVA XL 1 phase 3 3 4 Communication interface After unscrewing the cover various additional expansion cards can be installed e g a relay card INTELLIGENT SLOT Fig 3 8 Network port SNMP mini slot card 3 3 5 Parallel port This function is not supported 3 3 6 Bypass switch The manual bypass can be useful if the UPS needs to be deactivated but the connected appliances still have to be supplied with electricity e g UPS failure malfunctions etc This procedure may only be carried out by a trained electrician authorized by the manufacturer 3 3 7 Port for external battery banks External battery banks can be connected to the UPS to increase backup time Adira series 32 UPS Adira 6kVA 6kVA XL 10kVA UPS Device Description 10kVA XL 1 phase 3 3 8 UPS output and mains input Connection terminals to connect appliances and the mains supply input SH 123 45678 Terminal supply input PE Terminal supply input N Terminal supply input L Terminal jumper 1 Terminal jumper 2 Terminal appliance N Terminal appliance L Terminal appliance PE NN Oa BR ND Fig 3 9 Connection terminals T
24. UPS Uninterruptible Power Supply Adira 6KVA 6kVA XL 10kVA 10kVA XL 1 phase Operating Manual V 1 1 Article number ACX11ADS6K000MO6 ACX11ADS6K00X000 ACX11ADS10K00M04 ACX11ADS10K0X000 ABADX120009XX600 ABADX220009XX600 Translation of the original Operating Manual UPS Adira 6kVA 6kVA XL 10kVA Legal notice 10kVA XL 1 phase Adira series Legal notice CE by EFFEKTA Regeltechnik GmbH EFFEKTA Regeltechnik GmbH 78628 Rottweil retains the copyright to this documentation This documentation is solely intended for the operator and his staff The con tent of this documentation texts figures drawings graphics plans etc may not be copied or distributed in part or in full without our consent in writing nor can it be used without authorisation for competitive purposes or given or made accessible to third parties EFFEKTA Regeltechnik GmbH RheinwaldstraBe 34 D 78628 Rottweil Germany Phone 49 0 741 1 7451 0 Fax 49 0 74 1 1 7451 22 E mail ups effekta com Internet www effekta com Manual Operating manual Language English Release date 10 2013 We reserve the right to make changes to the design and the system that will im prove the system the production process or the product UPS Adira 6kVA 6kVA XL 10KVA Contents 10kVA XL 1 phase Table of contents 1 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 2 2 1 2 2 2 3 2 4 2 5 2 6 2 7 2 8 3 3 1 3 2 3 3 4
25. a 10kVA EFFEKTA EC Declaration of Conformity Address EFFEKTA Regeltechnik GmbH Rheinwaldstr 34 D 78628 Rottweil Germany Product description UNINTERRUPTIBLE POWER SYSTEMS Model ADIRA 1 1 10 kVA The above mentioned product is in delivered condition compliant with the following guidelines 2004 108 EC Council directive on the approximation of the laws of the member states relating to electromagnetic compatibility 2006 95 EC Council directive on the approximation of the laws of the member states concerning electrical equipment for use within certain voltage limits The conformity with the guidelines is guaranteed under application of following standards Safety Electromagnetic compatibility EMC Class C3 Number Issue Number Issue EN62040 1 2008 EN62040 2 2006 Rottweil 2014 03 07 hee Peter Androt Managing Director UPS Adira 6kVA 6kVA XL 10kVA Conformity Declarations 10kVA XL 1 phase Adira 10kVA XL EFFEKTA EC Declaration of Conformity Address EFFEKTA Regeltechnik GmbH Rheinwaldstr 34 D 78628 Rottweil Germany Product description UNINTERRUPTIBLE POWER SYSTEMS Model ADIRA 1 1 10 kVA XL The above mentioned product is in delivered condition compliant with the following guidelines 2004 108 EC Council directive on the approximation of the laws of the member states relating to electromagnetic compatibility 2006 95 EC Council directive on the approximation of the laws of the
26. atus menu Input Pa Output 23v 26v 23v 50 Hz 50 100 ath co 8 F Battery Volt 269 V Battery floating Charge Level 90 Status Line mode Para Num 1 Running time 0000 03 37 19 Fig 7 13 UPS status menu Parameters Description Display Alarm The status messages menu displays the latest error messages listed together with the count of the operating hours counter the alarm code and the plain text of the error message For further details on fault warnings see chapter 8 Display Battery voltage The menu displays the condition of the battery and Load Status Display Status and The menu displays the operating mode and the hours of operation Running time of the UPS The value Para Num shows how many devices are connected in parallel Adira series 56 UPS Adira 6kVA 6kVA XL 10kVA Operation 10kVA XL 1 phase 7 3 2 Event Log Menu Input 230V 50 Hz 269V 100 il PL Output 230 V A UPS Status 1900 W 8 0000 03 37 19 Event Log Event 51 UPS Control Power On 1150 0000 03 37 19 Event 02 Utility abnormal 0000 03 37 19 Event 52 UPS On from Panel 3 50 Fig 7 14 Event Log Menu Parameters Description Display Event Log The menu displays up to 50 warning fault messages and re sults In the event of more than 50 entries the old entries will be over written
27. ces USB standard Emergency stop contact EPO standard 39 UPS Adira 6kVA 6kVA XL 10kVA UPS Installation and Connection 10kVA XL 1 phase 6 6 1 Adira series UPS Installation and Connection ATTENTION The system may only be installed and connected by trained authorized electri cians in accordance with respective safety rules and regulations All requirements listed in the technical specifications concerning ambient and operating conditions must be met to ensure proper operation of the UPS Please note the following during set up installation of the UPS Avoid extreme temperatures and humidity Ensure proper vertical set up as predefined Allow adequate space for ventilation of the device Ensure a proper flow channel Pay attention to the system layout When installing the device in superordi nate systems e g machine switchboard it has to be ensured that the UPS is operated within the specified temperature range In case of a heat build up in the installation room it must be removed through adequate powered ventilation The device may only be mounted on castors and a solid weight bearing and horizontal surface Notes on the installation The UPS must be installed in a well ventilated environment far away from wa ter flammable gas and corrosive agents Ensure that the fans on the front and back side of the UPS are not ob structed by anything There should be at least half a mete
28. d Warranty Conditions The receipt of delivery is considered as the record for the initial purchase and should be kept in a safe place It will be necessary for making use of the war ranty If the product is passed on to another user he has the right to the war ranty for the remainder of the warranty period The purchase receipt as well as this declaration should also be given to the new owner if the device is passed on We guarantee that this device upon delivery is in a functional state and techni cally conforms to the descriptions in the appended documentation The warranty period for special devices corresponds to the minimum periods stipulated by law The warranty ceases to apply in the following cases In the event of defects caused by freight damage accident natural catastro phes misuse vandalism improper use defective maintenance or incorrect re pair by third parties Inthe event of changes unauthorised intervention incorrect operation an other device or accessories false installation or other modifications not ap proved by us Improper use such as plugging the device into unsuitable energy sources attempts to overload the UPS use in an unsuitable environment etc Inthe event of failure to follow instructions in the provided documentation 10 UPS Adira 6kVA 6kVA XL 10KVA Introduction 10kVA XL 1 phase Adira series Inthe event that the product is incompatible due to possible
29. e Adira series 21 UPS Adira 6kVA 6KVA XL 10kVA 10kVA XL 1 phase UPS Device Description Colour Name Function green Inverter LED If it is turned on constantly it shows that the load current is supplied from utility power or battery via the inverter yellow Battery LED If it is turned on constantly it shows that the UPS is in battery mode and the load current is from battery via the inverter yellow Bypass LED If it is turned on constantly it shows that the auto bypass is activated If it is flashing it shows that the auto bypass is deactivated red Fault LED If it is turned on constantly it shows that the UPS is in fault mode If it is flashing it shows that the UPS is in warning status Adira series 22 UPS Adira 6kVA 6kVA XL 10kVA 10kVA XL 1 phase LED action summary UPS Device Description LED Display No Status normal LED battery LED bypass LED fault LED green yellow yellow red 1 power on mode A A A A activation 2 bypass mode t without output 3 bypass mode 8 T with output 4 line mode t 5 battery mode 2 T 6 battest mode A A A A battery test mode 7 HE mode T high efficiency mode 8 warning T T i 9 Fault mode t Remarks permanently lit A 1 4 lightened circularly x flashing 1 depended on the fault warnin
30. ear no Reset fault Status Status fault active Reset fault no Clear event log Total events 50 Clear event log no Restore factory Reset no settings Fig 7 16 Control menu Adira series 60 UPS Adira 6kVA 6kVA XL 10KVA 10kVA XL 1 phase Operation Menu Parameters Settings Factory set ting Buzzer mute Buzzer mute lt No gt lt Yes gt No The keypad tones of the UPS are turned on Yes The keypad tones of the UPS are turned off No Single UPS battery test Status battery test The status of the latest battery tests is displayed here Start battery test lt No gt lt Yes gt No No battery test is performed Yes A battery test is performed You can configure the cycle for a battery test in the menu automatic battery test period chapter 7 3 6 Settings Menu No Clear EPO status Status Displays the EPO status Clear lt No gt lt Yes gt No If the EPO had been triggered it will not be reset Yes If the EPO had been triggered it will be reset No Reset fault status Status Displays whether the fault mode is active or inactive Reset fault lt No gt lt Yes gt No If a fault is pending on the UPS it will not be reset Yes If a fault is pending on the UPS it will be reset No Clear event log Total events Displays the number of messages Adira
31. g modes and signals 7 1 1 Operating mode Line mode Line mode is the regular mains power supply operating mode of the UPS The display for line mode looks as follows Input Output 230 V 269 V 230 V 50 Hz 50 Hz 1900 W Fig 7 1 Line mode Battery mode In the event of a mains failure the UPS switches to battery mode The display for battery mode looks as follows Input Output OV 269 V 230 V 0 Hz 50 Hz 100 wail ow Fig 7 2 Battery mode Adira series 47 UPS Adira 6kVA 6kVA XL 10kVA Operation 10kVA XL 1 phase The battery mode is marked by an acoustic signal in four seconds intervals Bypass mode ATTENTION The UPS has no backup function in bypass mode The UPS switches into bypass mode e g when there is an inverter problem The mains input and power output are bypassed via a relay The display for bypass mode looks as follows Input PL Output 230 V 269 V 230 V 50 Hz 50 Hz 100 1900 W Fig 7 3 Bypass mode with output Input ch Output 230 V 269 V OV 50 Hz 0 Hz 0 ow Fig 7 4 Bypass mode without output The bypass mode is marked by an acoustic signal in two minutes intervals Adira series 48 UPS Adira 6kVA 6kVA XL 10KVA Operation 10kVA XL 1 phase HE mode high efficiency In HE mode the UPS is initially in bypass mode The inverter is only activated in the event of a mai
32. g status of other status Adira series 23 UPS Adira 6kVA 6KVA XL 10kVA UPS Device Description 10kVA XL 1 phase 3 1 2 Button Selection Functions e Switching to the next sub menu By pushing this button for one second you switch to the sub menu of the currently active menu item Changes will not be saved e Opening of the current menu items By pushing the button for one second the currently selected menu will be opened e Saving Changes By pushing the button for more than one second you can edit the currently selected menu entry QO Menu down next Functions e By pushing the button for about one second you can scroll through the currently active menu A Menu up back Functions e Switching to main menu Push this button for more than one second to switch from the standard display to the main menu e Back Push this button for about one second to switch to the next higher menu or to go back step by step O ON OFF Functions By pushing this button you can turn the device on or off e If you push this button while you are in the main menu the display will switch to the standard display Adira series 24 UPS Adira 6kVA 6kVA XL 10kVA UPS Device Description 10kVA XL 1 phase 3 2 Elements on the back of the device The connecting terminals UPS Output and Mains Input are on mains potential when connected However there can still be a dangerously high voltage on the connecting
33. gt The menu structure is continued on the next page Adira series 64 UPS Adira 6kVA 6kVA XL 10KVA Operation 10kVA XL 1 phase Automatic overload HE voltage low restart limit lt enabled gt lt 5 218 5V gt gt yv Auto bypass HE voltage high limit lt 5 241 5V gt AN SZ Short circult clearance HE frequency low lt disabled gt limit lt 5 47 5Hz AN OY imit Bypass voltage low limit HE frequency high lt 184V gt li lt 5 52 5Hz gt Bypass voltage high limit 1 lt 264V gt Bypass frequency Low limit External battery module lt 45 0Hz gt lt gt Bypass frequency Set ing tii High limit Day 0001 oe lt 55 0Hz gt Time 00 00 00 LCD contrast lt 0 gt A 1 Only for models 6kVA and 10 kVA 2 Only for models 6kVA XL and 10kVA XL Fig 7 18 Settings Menu Adira series 65 UPS Adira 6kVA 6kVA XL 10kVA 10kVA XL 1 phase Operation Parameters Settings Default value User password lt enable gt lt disable gt disable If this value is set to lt enable gt you have to enter the password Audio alarm lt enable gt lt disable gt enable If this value is set to lt disable gt the UPS is silent and no alarm signals will sound Output voltage lt 208 gt lt 220 gt lt 230 gt lt 240 gt 230V Output frequency lt 50HZ gt lt 60HZ gt autosensing lt Autosensing gt On lt autosensing gt the output frequency is
34. he protective earth conductor must be connected Please always note the specified input voltage on the type plate or in the technical specifications in this operating manual respectively 3 3 9 Fan Fan to cool the device Adira series 33 UPS Adira 6kVA 6kVA XL 10kVA Storage and Unpacking 10kVA XL 1 phase 4 4 1 4 2 4 3 Adira series Storage and Unpacking Storage of the UPS In case the device is not being installed immediately please note the following e Always store the device and any accessories in their original packaging e The suggested ambiance temperature for the storage is between 0 40 C e Protect the device and packaging from moisture and liquids If the storage period exceeds four months the UPS and the corresponding bat tery bank optional have to be connected with the mains power supply for ap proximately 24 hours to avoid a total discharge of the accumulators Moving the UPS to the installation site The UPS is on castors to facilitate moving the device to the installation location after unpacking However if the receiving area is far from the installation site we recommend you to move the UPS by using a pallet jack or a lifter before you start to unpack the UPS Unpacking of the device e At the installation site the utmost care shall be taken when removing the packaging in order to avoid damaging the equipment Check all packaging materials to ensure that no items are
35. identical to the input frequency Power strategy lt normal gt Normal lt high efficiency gt lt converter gt DC start lt enable gt lt disable gt enable cold boot Site wiring alarm lt enable gt lt disable gt enabled If this value is set to lt enable gt a warning message appears in the display when the protective earth conductor is not connected or if phase and neutral have been swapped Ambient temperature lt enable gt lt disable gt enabled warning If this value is set to lt enable gt a warning message appears in the display when the ambient temperature reaches 45 C Automatic battery tests lt 0 gt lt 31days gt 7 days period If this value is 0 the automatic battery test is turned off Auto restart lt enable gt lt disable gt enable lt enable gt means that the UPS performs an automatic restart in normal operating mode if it was shut down due to a low battery charge status Automatic overload lt enable gt lt disable gt enable restart lt enable gt signifies that the UPS switches from bypass to line mode after the batteries have been charged to 70 Auto bypass lt enable gt lt disable gt disable Adira series 66 UPS Adira 6kVA 6kVA XL 10kVA 10kVA XL 1 phase Operation lt enable gt signifies that the UPS switches to bypass mode after start up lt disable gt signifies that the UPS does not start in bypass mode but switches to bypass mode
36. if a fault is detected or the batteries are over loaded The selected value gives the number of exter nal battery modules Short circuit clearance lt enable gt lt disable gt disable lt enable gt means the UPS stays in line mode and no warning message is displayed if a short circuit at the output last less than four sec onds lt disable gt means that the UPS switches to fault mode and displays a warning signal if a short circuit at the output lasts more than four seconds Bypass voltage low limit lt 167V gt lt 215V gt 176V Bypass frequency high lt 1 50 5HZ gt lt 10 55 0HZ gt 10 limit Bypass voltage high limit lt 245V gt lt 276V gt 264V Bypass frequency low lt 10 45 0HZ gt lt 1 49 5HZ gt 10 limit HE voltage low limit lt 10 207 0V gt lt 0 5 218 5V 5 HE voltage high limit lt 5 241 5V gt lt 10 253 0V gt 5 HE frequency low limit lt 10 45 0HZ gt lt 1 49 5HZ gt 5 HE frequency high limit lt 1 50 5HZ gt lt 10 55 0HZ gt 5 Battery quantity lt 19 gt lt 21 gt 20 Displays the number of internal integrated accumulators External battery module lt 0 gt lt 9 gt 0 Set running time Day 0000 9999 Hour 00 23 Minute 00 59 Second 00 59 Running Time LCD contrast lt 5 gt lt 5 gt The contrast ofthe LCD Display can be ad justed here between 5 and 5
37. ignal sounds twice per second The display in the event of an overload looks as follows Input 230 V 50 Hz Fig 7 9 Overload During a battery test the display looks as follows Output 230 V 50 Hz 6480 W Input 230 V 50 Hz Fig 7 10 Battery test Adira series Output 230 V 50 Hz 1900 W 51 UPS Adira 6kVA 6kVA XL 10kVA Operation 10kVA XL 1 phase 7 2 Adira series If a fault is detected in the battery like e g battery not connected or poor bat tery status the display looks as follows Input i Output 230 V 269 V 230 V 50 Hz 50 Hz 1900 W Fig 7 11 Battery fault UPS operating instructions The operator of the UPS system must always adhere to the instructions in this operating manual The operator may only carry out the following measures and must always exercise particular care e Use of the operating controls switching on starting and switching off the UPS e Reading of the display messages and interpretation of the acoustic warning signals e Triggering the test mode e Using the communication interface whereby the connection to the PC or other systems must already be established for UPS devices with permanent wiring Due to the extensive protective functions the UPS system performs in re lation to the appliance s the UPS operates fully automatically The opera tor only carries
38. in a parallel system Para Rate Power Differ There are different UPSs in parallel system UPSs with different capacity e g one 6KVA and one 10KVA are not permitted in a parallel system ECO In Para HE High Efficiency function HE High Efficiency function is is activated in a parallel sys not permitted in parallel system tem IP Fuse Open Input fuse break Check the input fuse status 8 2 Troubleshooting according to fault indication Problem Displayed Possible cause Troubleshooting measures Inv Overload Fault Byp Overload Fault Overload Overload Check the loads and remove some non critical loads Check if some loads have failed Check the loads and remove Adira series 69 UPS Adira 6kVA 6kVA XL 10kVA 10kVA XL 1 phase Troubleshooting some non critical loads Check if some loads have failed Output Short Circuit Output short circuit Remove all the loads Turn off the UPS Check if UPS output and loads is short circuit Ensure short circuit is removed before turning on again Heatsink Over Temperature Fault Inside temperature of UPS is too high Check the ventilation of the UPS and the ambient temperature Bus Over Voltage UPS internal fault Consult dealer Bus Under Voltage UPS internal fault Consult dealer Bus Unbalance UPS internal fault Consult dealer Bus short U
39. inst the initial purchaser In some countries the exemption or the limitation of concomitant or subsequent damage is not permitted by law so that the aforementioned declaration does not enter into force Transport and Storage The UPS may only be transported to the intended location in the original pack aging The same applies to moves or returns The packaging plays no role as fall protection so all fallen devices must be checked by EFFEKTA Regeltechnik GmbH before commissioning The device may not be transported or stored upside down 12 UPS Adira 6kVA 6kVA XL 10KVA Introduction 10kVA XL 1 phase 1 8 Adira series Positioning Do not install in an area in which combustible vapours arise e g from pet rol tanks engine compartments etc The UPS is designed for operation in ventilated rooms with an ambient tempera ture of 0 to 40 C If the UPS is exposed to severe and quick temperature changes there is danger of condensation Before you take additional steps an acclimatization period of at least 2 hours is to be observed Never place or operate the device in a moist environment Keep liquids away from the device The UPS may not be placed in the vicinity of heat sources The UPS may only be set up in a vertical position and on castors Ensure that the back side and the front side of the device are at least 10 cm from other objects for ventilation in order to prevent trapped air and too much warming Make
40. installation and commissioning of the device e Only operate the product in an appropriate and proper way and within the parameters stated in the technical data e Only perform maintenance and service work that is described in the docu mentation Observe the required steps Only use original replacement parts from EFFEKTA Regeltechnik GmbH 2 4 Protecting the Environment e Send the product back to EFFEKTA Regeltechnik GmbH after the end of its service life We will ensure environmentally friendly disposal Adira series 15 UPS Adira 6kVA 6kVA XL 10kVA Safety Instructions 10kVA XL 1 phase 2 5 Adira series Connection The UPS is connected via the connection terminals on the back of the de vice The PE protective earth conductor must be connected without fail The device may not be used without the PE under any circumstances Keep the cable length as short as possible During generator operations the pole correct connection of the UPS must be ensured For the connection of the UPS with the electricity grid only a power cable that is VDE approved and labelled CE may be used For the connection of the appliances with the UPS only a power cable that is VDE approved and labelled CE may be used The safeguarding of any appliance must always be immediately in front of an appliance and may never be done centrally in front of the UPS Never operate any household devices or tools like e g fan heaters vac uum clea
41. member states concerning electrical equipment for use within certain voltage limits The conformity with the guidelines is guaranteed under application of following standards Safety Electromagnetic compatibility EMC Class C3 Number Issue Number Issue EN62040 1 2008 EN62040 2 2006 Rottweil 2014 03 07 ee Peter Androt Managing Director 85 UPS Adira 6kVA 6kVA XL 10kVA Notes 10kVA XL 1 phase UPS Adira 6kVA 6kVA XL 10kVA Notes 10kVA XL 1 phase 87 EFFEKTA EFFEKTA Regeltechnik GmbH RheinwaldstraBe 34 D 78628 Rottweil
42. missing The shipping package contains AUPS A user manual AUSB cable 34 UPS Adira 6kVA 6kVA XL 10kVA Storage and Unpacking 10kVA XL 1 phase Remove the packaging following the sequence illustrated in Fig 4 1 to Fig 4 4 Tools Lifter Sa Phillips screw driver Scissors Wrench Spanner of Fig 4 1 Unpacking step 1 Adira series 35 UPS Adira 6kVA 6kVA XL 10kVA Storage and Unpacking 10kVA XL 1 phase Fig 4 2 Unpacking step 2 Ty gies mi Fig 4 3 Unpacking step 3 UPS Adira 6kVA 6kVA XL 10kVA Storage and Unpacking 10kVA XL 1 phase Fig 4 4 Unpacking step 4 LAY The shipping materials are recyclable After unpacking save them for later use 02 or dispose of them appropriately e Inspect the appearance of the UPS to see if there was any damage in curred during transportation Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or if any parts a missing Adira series 37 UPS Adira 6kVA 6kVA XL 10kVA System Description 10kVA XL 1 phase 5 System Description The UPS runs in continuous operation according to the double converter princi ple It serves for the processing of the mains current and provides an uninterrup tible and interference free one phase voltage for operations critical appliances In addition to providing power to the appliance it also maintai
43. nding connecting cable e Ensure that the output voltage of the battery bank is identical with the DC input voltage of the UPS Should this not be the case the units may not be connected with each other under any circumstances e You must make sure that the UPS is switched off and that the circuit breaker of the battery bank is removed before connecting the UPS with the battery bank e Connect the external battery pack with the UPS e Install the circuit breakers of the battery bank e Switch the input breaker of the UPS to ON Now the UPS begins to charge the battery bank 45 UPS Adira 6kVA 6kVA XL 10kVA UPS Installation and Connection 10kVA XL 1 phase 6 6 Backfeed protection On the customer side an additional external insulation device magnetic contac tor minimum shunt release must be provided see Fig 6 3 This insulation de vice must be designed to conduct the input voltage of the UPS see the corre sponding table in the general UPS operating manuals The insulation device must be installed in the UPS input line UPS main fuse Feedback protection magnetic contactor Mains input UPS Coil of the magnetic contactor Mains neutral conductor r2Z27aRPWON Mains phase conductor Fig 6 3 Feedback protection Adira series 46 UPS Adira 6kVA 6kVA XL 10KVA Operation 10kVA XL 1 phase 7 Operation 7 1 Operation of the UPS The operation of this equipment is characterized by various operatin
44. ners electric drills toasters etc with the UPS Do not connect any appliance to the UPS that could overload the device e g laser printer Keep the connecting cables as short as possible and always install them correctly Avoid hazards to the cable like tripping crushing clipping etc 16 UPS Adira 6kVA 6kVA XL 10kVA Safety Instructions 10kVA XL 1 phase 2 6 Adira series Operation Before the appliances are connected to the outlet the basic configuration must be completed Especially the output voltage is of high importance regarding the appliances The UPS system contains an energy storage accumulators This means that the outlet can be current carrying even when the UPS is not connected to the mains input terminal To completely shut down the UPS first disconnect the mains connection and then hold the OFF button pressed for more than 3 seconds Wait for the UPS to turn off before disconnecting the power connection feeder cable between the UPS and the appliance Ensure that no liquids or foreign matter enter the UPS Avoid a constant load of more than 80 on the output to protect the UPS The displayed output load should only be taken as a reference point separate measuring is necessary to determine the exact output load Working with Accumulators Attention Danger of electric shocks and burns Accumulators can cause electric shocks and have a high short circuit cur rent which can cause burns
45. ns failure This results in a brief switch over time in the milli second range The display for HE mode looks as follows Input Ze Output 230 V 269 V 230 V 50 Hz 50 Hz aB eow Fig 7 5 HE mode Converter mode In converter mode the frequencies of the input and output can be configured The display for converter mode looks as follows Input N Output 230 V 269 V 230 V 50 Hz 50 Hz 100 uni eow Fig 7 6 Converter mode Adira series 49 UPS Adira 6kVA 6kVA XL 10kVA Operation 10kVA XL 1 phase Adira series Warning In general warnings are no fatal faults but should be fixed as quickly as possi ble The UPS continues to operate when a warning occurs If there are any warnings pending at the UPS the display looks as follows Input x Output 230 V 269 V 230 V 50 Hz 50 Hz 100 1900 W Fig 7 7 Warning Fault A fault alarm signifies a fatal problem The UPS signals a fault through an alarm signal and switches either into bypass mode or shuts down depending on the configuration The background light of the LCD Display turns red The display for fault mode looks as follows Input AN Output 230 V 269 V ov 50 Hz 0 Hz 0 OW Fig 7 8 Fault 50 UPS Adira 6kVA 6kVA XL 10KVA 10kVA XL 1 phase Other signals Operation In the event of an overload the UPS emits an acoustic signal The alarm s
46. ns the internal ac cumulators in charged condition In the case of a mains failure or interference the UPS continues to provide a clean supply voltage from the UPS output with out interruption During the backup mode power is provided from the accumula tors On line UPS 1 mains input 8 voltage inverter 2 filter 9 control and monitoring 3 rectifier 10 control panel and display 4 inverter 11 ext battery bank optional 5 bypass switch 12 battery bank 6 filter 13 interface 7 UPS output 14 LAN RS232 Fig 5 1 Block diagram The block diagram visualizes the individual modules of the device and illustrates their interaction Adira series 38 UPS Adira 6kVA 6kVA XL 10kVA System Description 10kVA XL 1 phase Adira series If a mains failure continues beyond the backup time of the UPS the UPS shuts down to avoid a total discharge of the accumulators As soon as the mains power supply returns the UPS automatically turns on again supplies electricity to the appliance and controls the charging of the battery bank Prominent performance features of the UPS are No interruption or signal change when the primary mains supply fails Perfect sine wave voltage on the UPS output Process controlled bypass mode Power Factor correction on the input side gt 0 95 LCD Display for status and operation data display Outstanding performance factor of 0 9 Efficient and extensive communication interfa
47. nt in particular the accumulators as well as timely replacement and proper disposal of accumulators Inspection of the UPS installation Proper disposal of defective or degenerated components Environmentally acceptable disposal of accumulators You can find the complete range of our services on line at http www effekta com html service html or contact us directly at the addresses given above 77 UPS Adira 6kVA 6kVA XL 10kVA 10kVA XL 1 phase Technical Data 11 Technical Data Input Model 6kVA XL 10kVA XL Phase one phase Voltage 176 276VAC Frequency 45 55 54 66 Hz Current A 25 8 43 0 THDI lt 5 charged Performance factor 20 99 charged current at input voltage 230VAC Output Model 6KVA XL 10kVA XL Connected load 6KVA 5 4KW 10kVA 9kW Voltage 208 220 230 240x 121 VAC Frequency 50 60x 1 0 05 Hz Battery mode wave form sinusoidal Charging type PF 0 5 1 delay lt 2 full linear load TEDY lt 5 full non linear load In Line mode 10 min 105 125 1 min 125 150 10 s gt 150 Overload 100 ms gt 170 In Battery mode 2 min 105 125 30 s 125 150 100 ms gt 150 The load capacity would be derated to 90 automatically when the output volt age is adjusted to 208VAC The overload capacity would be derated automatically in Line mode while the circumstance temperature is larger than 35 degree
48. out the switching on and starting or switching off of the device In addition a data exchange can take place via the communication interface or the SNMP adapter however this is not absolutely necessary for the general operation of the system 52 UPS Adira 6kVA 6kVA XL 10KVA Operation 10kVA XL 1 phase 7 2 1 Switching the UPS on off Turning on the UPS with connected appliances e Before turning on the UPS make sure all appliances are connected cor rectly e Turn on the UPS The UPS is started up as the fan turns on and the LCD display shows a welcome message The UPS conducts a self test e Press the ON OFF button for more than one second until an acoustic signal sounds The UPS is now turned on A few seconds later the UPS will switch to regular operating mode and is now ready for operation e If a fault is present at the UPS it switches to battery mode and all outputs are deactivated Turning on the UPS without connected appliances e Check all connections before turning on the UPS e Turn on the UPS The UPS is started up as the fan turns on and the LCD display shows a welcome message The UPS conducts a self test e Press the ON OFF button for more than one second until an acoustic signal sounds The UPS is turned on after this procedure Turning off the UPS e Push the ON OFF button for more than three seconds The system switches into bypass mode Disconnect the UPS from the mains input to
49. package CD ROM network compatible shut down and diagnosis soft 1 license Windows Novell 1 license UNIX LINUX MAC 1 license RCCMD network remote client LAN PowerShut 12 1 2 Communication interfaces optional accessories Description Article number Type SNMP card GE cs121 SLBdget internal SNMP adapter budget version 12 2 Wearing parts list Adira series The following list of components that are related to regular wear and are there fore not subject to the warranty of the UPS Wearing part Function Article number XXXX XX XX Accumulator Battery 12 V xx Ah Energy storage Depending on the assembly see acces sories or on request For the wear part description of the accumulators please see the assembled accumulators or on contact us UPS Adira 6kVA 6kVA XL 10kVA Scope of Delivery 10kVA XL 1 phase Optional Accessories 13 Conformity Declarations 13 1 Adira 6kVA EFFEKTA EC Declaration of Conformity Address EFFEKTA Regeltechnik GmbH Rheinwaldstr 34 D 78628 Rottweil Germany Product description UNINTERRUPTIBLE POWER SYSTEMS Model ADIRA 1 1 6 kVA The above mentioned product Is in delivered condition compliant with the following guidelines 2004 108 EC Council directive on the approximation of the laws of the member states relating to electromagnetic compatibility 2006 95 EC Council directive on the approxima
50. r any conse quences resulting thereof The uninterruptible power supply is intended to protect sensitive electronic sys tems from interferences that could occur due to bad electric quality or grid fail ures Please read this operating manual carefully and take note particularly of the safety instructions If you have questions about the device the technical supervisor in your com pany or our employees will be glad to help you Your EFFEKTA Regeltechnik GmbH UPS Adira 6kVA 6kVA XL 10kVA Introduction 10kVA XL 1 phase 1 2 1 3 1 4 1 4 1 Adira series Validity The descriptions in this operating manual relate solely to the uninterruptible power supply defined in the technical data as a whole or as it refers to modules components and individual parts that were developed and built by EFFEKTA Regeltechnik GmbH 11 Technical Data Storage This operating manual for the device must be stored in the vicinity of the device at all times so it is immediately available if need be Symbols in this Manual The abbreviation UPS in this manual stands for uninterruptible power supply e Read this documentation carefully and make yourself familiar with the pro duct before using it e Store this operating manual in an easily accessible place to refer to it if necessary e Please pass this operating manual on to later users of the product Danger warning levels Text that is marked with DANGER provides a
51. r of free space on all sides If the UPS is unpacked in an environment with very low temperatures there is a danger of condensation and water droplets may form In this case you have to wait for the UPS to fully dry inside and out before you continue with the installation or commission the device as there may oth erwise be a risk of electric shocks 40 UPS Adira 6kVA 6kVA XL 10kVA UPS Installation and Connection 10kVA XL 1 phase 6 2 Adira series Connecting the UPS The installation and wiring must be carried out by professional technicians in accordance with local safety regulations and in adherence to the following in structions For safety reasons turn off the main power switch before you begin with the in stallation e Open the panel of the terminal block at the back of the UPS Please refer to the system diagram for this task e We recommend to use a 6 mm cable for a 6kVA UPS e We recommend to use a 10 mm cable for a 10KVA UPS ATTENTION Do not use a wall socket as input power source for the UPS as its nominal cur rent is below the maximal input current of the UPS The wall socket could burn and get destroyed e Connect the input and output cables with the respective input and output terminals e The protective earth conductor refers to the cable connection between the parts that consume electric energy and the earth wire The cable diameter of the protective earth wire should at least have the
52. rranties is not permitted by law so that the aforementioned limita tion does not take effect 11 UPS Adira 6kVA 6KVA XL 10kVA Introduction 10kVA XL 1 phase 1 6 1 1 7 Adira series Limitation of liability Claims to damage compensation are excluded unless they involve intent or gross negligence by EFFEKTA Regeltechnik GmbH or its employees This does not affect liability according to the Product Liability Act Under no circum stances are we liable for Claims that third parties make against you due to losses or damage Loss or damage of your records or data or the costs of recovering this data Economic subsequent damage including lost profits or savings or con comitant damage including in the event that we were informed of the pos sibility of such damage Under no circumstances is EFFEKTA Regeltechnik GmbH responsible for any accidental indirect specific subsequent or other damage of any kind including without any limitation damage related to a loss of profits interruption of busi ness loss of business information or any other losses that result from use of the device or are connected with the device whether they are based on the con tract damage compensation negligence strict liability or other claims even if EFFEKTA Regeltechnik GmbH was informed about the possibility of such damage in advance This exemption also includes any liability that can result from the claims of third parties aga
53. sult dealer Adira series 68 UPS Adira 6kVA 6kVA XL 10kVA 10kVA XL 1 phase Troubleshooting Battery Over Voltage Battery voltage is higher than normal value Check if the battery quantity is right Over Charge The battery is over charged The UPS will turn off the charger until the battery voltage is nor mal Model Pin Error UPS internal fault Consult dealer Ambient Over The ambient temperature is Check the environment ventila Temperature too high tion Heatsink Over The inside temperature of the Check the ventilation of the UPS Temperature UPS is too high and the ambient temperature Ambient NTC abnormal UPS internal fault Consult dealer Para Cable Male Loss The parallel cable is discon nected Check the parallel cable Para Cable Female Loss The parallel cable is discon nected Check the parallel cable Para Bat Differ The battery packs of some UPSs are disconnected Check if all the battery packs are connected Para Line Differ The mains input of some UPSs is disconnected Check the building wiring and input cable Check if the input breaker is closed Ensure the UPSs are connected to same input source Para Work Mode Differ There are different power strategy settings within a parallel system UPSs with different power strat egy settings e g one line mode and one converter mode are not permitted
54. switch it off completely Adira series 53 UPS Adira 6kVA 6kVA XL 10kVA Operation 10kVA XL 1 phase waco Input Output 7 2 2 UPS menu structure 230V 269 V 230V 50 Hz 50 Hz 100 sal 1900 W Q Battery Volt 269 V Battery floating Charge level 90 Status Line mode Para Num 1 Running time 0000 03 37 19 Fig 7 12 Menu structure Adira series 54 UPS Adira 6kVA 6kVA XL 10kVA Operation 10kVA XL 1 phase Button Description The description of this button can be found in chapter 3 1 2 J Buttons N The description of this button can be found in chapter 3 1 2 AN NZ Buttons EN The description of this button can be found in chapter 3 1 2 V7 Buttons The description of this button can be found in chapter 3 1 2 N Buttons Parameters Description Display Alarm The status messages menu displays the latest error messages listed together with the count of the operating hours counter the alarm code and the plain text of the error message Display Battery voltage and Load Status The menu displays the condition of the battery Display Status and Running time The menu displays the operating mode and the hours of operation of the UPS The value Para Num shows how many devices are connected in parallel Adira series 55 UPS Adira 6kVA 6kVA XL 10KVA Operation 10kVA XL 1 phase 7 3 Menu 7 3 1 UPS st
55. tion of the laws of the member states concerning electrical equipment for use within certain voltage limits The conformity with the guidelines is guaranteed under application of following standards Safety Electromagnetic compatibility EMC Class C3 Number Issue Number Issue EN62040 1 2008 EN62040 2 2006 Rottweil 2014 03 07 bl Peter Androt Managing Director UPS Adira 6kVA 6kVA XL 10kVA Conformity Declarations 10kVA XL 1 phase Adira 6kVA XL EFFEKTA EC Declaration of Conformity Address EFFEKTA Regeltechnik GmbH Rheinwaldstr 34 D 78628 Rottweil Germany Product description UNINTERRUPTIBLE POWER SYSTEMS Model ADIRA 1 1 6 kVA XL The above mentioned product is in delivered condition compliant with the following guidelines 2004 108 EC Council directive on the approximation of the laws of the member states relating to electromagnetic compatibility 2006 95 EC Council directive on the approximation of the laws of the member states concerning electrical equipment for use within certain voltage limits The conformity with the guidelines is guaranteed under application of following standards Safety Electromagnetic compatibility EMC Class C3 Number Issue Number Issue EN62040 1 2008 EN62040 2 2006 Rottweil 2014 03 07 sh R Ale Peter Androt Managing Director 83 UPS Adira 6kVA 6kVA XL 10kVA Scope of Delivery 10kVA XL 1 phase Optional Accessories Adir
56. very two years to avoid any risk of insufficient backup time because of degenerated accumulators 10 2 Replacing the accumulators Accumulators may only be replaced by the manufacturer Adira series 75 UPS Adira 6kVA 6kVA XL 10kVA Maintenance and Service 10kVA XL 1 phase 10 3 Service Log Please always enter all maintenance and service work conducted on the UPS into the service log Date Performed tasks Performed by Adira series 76 UPS Adira 6kVA 6kVA XL 10kVA Maintenance and Service 10kVA XL 1 phase 10 4 10 5 Adira series Service Hotline If unexpected problems occur with the photovoltaic solar inverter or you need safety information please contact our service hotline by phone or fax Phone 0049 0 741 17451 52 Fax 0049 0 741 17451 29 If you cannot reach us by phone or fax we have set up an e mail contact for you ups effekta com In addition you can contact the central area or branch office directly as listed on our website http www effekta com htmi kontakt html Maintenance and service contracts EFFEKTA Regeltechnik GmbH offers the related maintenance services to en sure the highest possible reliability and availability of the UPS system In addi tion we offer maintenance contracts to support and assist you in the following areas with our qualified staff Regular testing of the equipme
57. xchange of data with the UPS ATTENTION When connected with a USB cable the software can exchange data with the UPS The software collects detailed information about the status of the power supply from the UPS In the case of a supply emergency the software ensures that all data is saved and all appliances are shut down properly SNMP communication port Optionally the UPS can be equipped with a SNMP communication port Connection sequence e Connect the UPS with the mains power supply both the mains and the UPS must be safely switched off during this process e Before the appliances are connected to the outlet the basic configuration must be completed e Connect the appliance s with the UPS Make sure that all appliances are switched off 42 UPS Adira 6kVA 6kVA XL 10kVA UPS Installation and Connection 10kVA XL 1 phase 6 4 1 Configuration of the dry contact relay output contact The relay output contact has a maximum load bearing capacity of 12 VDC 1A The following figure shows the schematic structure of the potential free output and input contacts Pin Description VO Pin Description VO 1 UPS fault Output 6 Bypass active Output 2 Alarm Output 7 Battery under Output voltage 3 UPS shut down Input 8 UPS on Output earth 4 UPS shut down Input 9 Mains failure Output plus 5 Neutral point Output UPS fault Bypass active Battery under voltage