1. TECHNICAL FEATURES IN TEMPERATURE Measuring range Unit of measurement Accuracy Response time Resolution Type of sensor Type of fluid Ambient model from 0 to 50 C Remote model with polycarbonate probe from 20 to 80 C Remote model with stainless steel probe from 40 to 180 C C F 0 3 of reading 0 25 C T 0 9 second for V 1 m s 0 1 C Pt100 1 3 as per DIN IEC 751 Air and neutral gases All the accuracies indicated in this technical datasheet were stated in laboratory conditions and can be guaranteed for measurements carried out in the same conditions or carried out with calibration compensation TECHNICAL FEATURES OF THE PROBE gt White polycarbonate probe Measuring range Length of standard probe Length of remote probe Cable From 20 to 80 C 100 mm 150 or 300 mm other on request Silicone 4 8 mm length 2 m other on request Polycarbonate probes are supplied with a flow through polycarbonate protection tip with a Stainless steel filter 25 u ref EPP2 gt 316 L stainless steel prone Measuring range Length of remote probe Cable gt Type of tips From 40 to 180 C 150 or 300 mm other on request Silicone 04 8 mm length 2 m other on request Stainless steel probes are supplied with a flow through stainless steel protection tip with a stainless steel filter 25 u ref EP125 TECHNICAL SPECIFICATIONS Power supply 24 Vac
2. Vdc 10 115 Vac or 230 Vac 10 50 60 Hz Output 2 x 4 20 mA or 2 x 0 20 mA ou 2 x 0 5 V ou 2 x 0 10 V 4 wires Maximum load 500 Ohms 0 4 20 mA Minimum load 1 K Ohms 0 5 10 V Galvanic isolation Inputs and outputs models 115 Vac 230 Vac Outputs models 24 Vac Vdc Consumption 5 VA Electromagnetical compatibility EN61326 Electrical connection Screw terminal block for cable 2 5 mm PC communication Kimo USB Mini Din cable Environment Air and neutral gases Type of fluid Air and neutral gases Operating temperature From 0 to 50 C Storage temperature From 10 to 70 C Part number EPP2 EPI25 EPI100 EPFI EPFT EPH202 Specifications Tip material Pc St steel St steel St steel PTFE MnO Filter material St steel St steel St steel St steel PTFE PTFE Filter type Meshed Meshed Meshed Sintered Sintered Sintered Maximum particle 25 u 25 u 100 u 10 u 50 u 50 u Maximum air velocity 25 m s 25 m s 20 m s 30m s 25m s 25 m s Maximum temperature 120 C 180 C 120 C 180 C 180 C 180 C Relative humidity maximum 95 RH 95 RH 100 RH 90 RH 90 RH 95 RH External aggression Length 30 mm 30 mm 30 mm ane Poni Tips protect agains the following external aggressions Application e Water droplets EPFT e Shaving EPI25 et EPFI HVAC air conditioning system X X Dust EPFI Cold storage room X x a product
3. 10 000 10 000 Pa Power supply Output 4 500 500 mbar B 24 Vac Vde 5 2000 2000 mbar a 119 0F230 vae TECHNICAL FEATURES Units of measurement CP211 212 213 Pa mmH O mbar inWG mmHG daPa kPa hPa CP214 mbar mmH O kPa inWG mmHG hPa daPa PSI CP215 mbar mmH O kPa inWG mmHG hPa daPa PSI bar CP211 212 213 214 215 temp rature Pt100 C F Accuracy CP211 212 0 5 of reading 2 Pa CP213 0 5 of reading 10 Pa CP214 0 5 of reading 0 5 mbar CP215 0 5 of reading 2 mbar CP211 212 213 214 215 Pt100 temperature 0 5 of reading 0 5 C Response time 1 e 63 0 3 s Resolution CP211 212 213 1 Pa 0 1 mmH O 0 01 mbar 0 01 inWG 0 01 mmHG 0 1 daPa 0 001 kPa 0 01hPa CP214 1 mbar 1 mmH O 0 1 kPa 0 1 inWG 0 01 mmHG 1 hPa 10 daPa 0 01 hPa CP215 1 mbar 1 mmH O 0 1 kPa 0 1 inWG 0 01 mmHG 1 hPa 10 daPa 0 01 hPa 0 001 bar Tolerated overpressure CP211 212 21 000 Pa CP213 69 000 Pa CP214 1400 mbar CP215 4100 mbar All the accuracies indicated in this technical datasheet were stated in laboratory conditions and can be guaranteed for measurements carried out in the same conditions or carried out with calibration compensation TECHNICAL SPECIFICATIONS Power supply Output Galvanic isolation Consumption Electromagnetical compatibility Electrical connection PC communication Environment Autozero Type of fluid Operating
4. C ambient model From 100 to 400 C model with terminal block Unit of measurement C F Accuracy 0 3 of reading 0 25 C Response time T 0 9 second for V 1 m s Resolution 0 1 C Type of sensor Pt100 1 3 as per DIN IEC751 Type of fluid Air and neutral gases All the accuracies indicated in this technical datasheet were stated in laboratory conditions and can be guaranteed for measurements carried out in the same conditions or carried out with calibration compensation SPECIFICATIONS TECHNIQUES Power supply 24 Vac Vdc 10 115 Vac or 230 Vac 10 50 60 Hz Output 2 x 4 20 mA or 2 x 0 20 mA ou 2 x 0 5 V or 2 x 0 10 V 4 wires Maximum load 500 Ohms 0 4 20 mA Minimum load 1 K Ohms 0 5 10 V Galvanic isolation Inputs and outputs models 115 Vac 230 Vac Outputs models 24 Vac Vdc Consumption 5 VA Electromagnetical EN61326 compatibility Electrical connection Screw terminal block for cable 2 5 mm PC communication Kimo USB Mini Din cable Environment Air and neutral gases Type of fluid Air and neutral gases Operating temperature From 0 to 50 C Storage temperature From 10 to 70 C TECHNICAL FEATURES OF THE TEMPERATURE PROBES Different Pt100 temperature probes are available on the range 100 to 400 C with different types of contact tip straight stainless Steel angled stainless steel with penetration tip Please contact us in order to define the type of probe that corresponds to your need
5. 0V 10 V 4 mA 20 mA OV 4mA 75 mm MOUNTING 37 5mm Te a a eee ee 40 To mount the transmitter mount the ABS plate on the wall drilling 6 mm screws and 7 pins are supplied Insert the transmitter on the fixing plate see A on the drawing beside Rotate the housing in clockwise direction until you hear a click which confirms that the transmitter is correctly installed 23 75 mm CALIBRATION Outputs diagnostic With this function you can check with a multimeter or on a regulator display or a PLC BMS if the transmitter outputs work properly The transmitter generates a voltage of 0 V 5 V and 10 V or a current of 4 mA 12 mA and 20 mA Certificate Class 210 transmitters are supplied with adjusting certificates Calibration certificates are available as an option MAINTENANCE Please avoid any aggressive solvent Please protect the transmitter and its probes from any cleaning product containing formalin that may be used for cleaning rooms or ducts OPTIONS AND ACCESSORIES e LCC S configuration software with USB cable e Calibration certificate e Pt100 temperature probes FTang transmitter_TM210 02 04 13 RCS 24 P rigueux 349 282 095 Non contractual document We reserve the right to modify the characteristics of our products without prior notice INSTRUMENTS Technical Data Sheet Pressure Temperature Humidity Air Velocity Airflow
6. 2 5 mm PC communication Kimo USB Mini Din cable Environment Air and neutral gases Type of fluid Air and neutral gases Operating temperature From 0 to 50 C Storage temperature From 10 to 70 C Hotwire probe Omnidirectional probe Class 210 transmitters have two analogue outputs which correspond to the two parameters displayed It is possible to activate one or two outputs and for each output to select between air velocity temperature and air flow Measuring ranges Units and resolutions Features Function Air flow From 0 to 100 000 m h according to air velocity and duct dimension 1m h 0 1 m s 0 1l s 1 cfm Pitot tubes Debimo blades etc are optional CONNECTIONS Analogue outputs a Type of power supply of the transmitter b DIP switc d Power supply terminal block c LCC S software connection a a ENN Cable glands Analogue output 1 Analogue output 2 out 1 out 2 c or c OF c ERLI For power supply 24 For power supply 24 For power supply 230 Vac 115 Vdc models Vac models Vac models Oo Qo Oc Ground Qo g Oo Neutral N Oo Neutral N Oe Co Phase L O Phase L GND Ground 0 4 20 mA Current 0 5 10 V Voltage 0 5 10 V Voltage GND Ground 0 4 20 mA Current ELECTRICAL CONNECTIONS as per NA 15 100 standard This connection must be made b
7. and grease Industry X X X X X e H O hydrogen peroxide Pharma plants Microelectronics X X X X X X EPH202 Dryer ji PC white polycarbonate Stainless steel 316 L Curing X PTFE white Teflon BE MnO manganese dioxide Swimming pool X 2 CONNECTIONS DIP switc d LCC S software connections a 32 ea Analogue outputs a Type of power supply of the transmitter b Power supply terminal block c Cable glands Analogue output 1 Analogue output 2 out 1 out 2 c Ca c ERLI For power supply 24 Vdc models Oo Oc Qo Qo Co Co GND Ground 0 4 20 mA Current 0 5 10 V Voltage 0 5 10 V Voltage GND Ground 0 4 20 mA Current ELECTRICAL CONNECTIONS as per NA 15 100 standard For power supply 24 Vac models Neutral N Qo Phase L Or Or c For power supply 230 Vac 115 Vac models Oo e Ground Neutral N Phase L This connection must be made by a qualified technician To make the connection the transmitter must not be energized Before making the connection you must first check the power supply indicated on the transmitter board see b on Connections part gt For transmitters with 24 Vdc power supply The selection of the output signal in voltage 0 10 V or 0 5 V or in current 4 20 mA or 0 20 mA is made via the DIP switch d of the electronic board of the transmitter pu
8. made via the DIP switch d of the electronic board of the transmitter put the on of switches as shown in the table below gt For transmitters with 24 Vdc power supply Configurations Power supply 24 Vac 123 4 123 4 123 4 23 4 class II O Vac N I gt Connection of the output gt Connection of output in 230 Vac VacL in current 4 20 mA voltage 0 10 V or 0 5 10 V 0 4 20 mA 0 5 10 V 0 4 20 mA 230 Vac L Power supply gt For transmitters with 115 or 230 Vac power supply 3 Regulator display or Ground PLC BMS passive PLC BMS passive type Neutral type Power supply S 115 230 Vac S Phase 4 20 mA output 0 10 V output CONFIGURATION OF THE TRANSMITTERS It is possible on the class 210 to configure all the parameters of the transmitter units measuring ranges outputs channels calculation functions etc via different methods e Keypad for models with display a code locking system allows to secure the installation See class 210 user manual e Software optional on all models Simple user friendly configuration See LCC SD user manual Configurable analogue output It is possible to configure your own intermediary ranges Caution the minimum difference between the high range and the low range is 20 Configure the range according to your needs outputs are automatically adjusted to the new measuring range 0 C 25 C 50 C 0 C New range
9. 4 20 mA 0 5 10 V 0 4 20 mA 0 5 10 V 0 4 20 mA PLC BMS passive type 0 10 V output PLC BMS passive type 4 20 mA output 100 0 100 100 0 50 100 New range So o 0V 10 V 4 mA 20 mA OV 10V 4mA 20 mA 75 mm MOUNTING A Once the transmitter is installed and powered up please make an autozero to AUTOZERO Auto calibration CP210 transmitters have a temperature compensation of the gain from 0 to 50 C and an auto calibration process that guarantees over the time an excellent stability and a perfect reliability of the measurement on low and high ranges Auto calibration principle the microprocessor of the transmitter drives a solenoid valve that compensates the possible drifts on the sensitive element over the time The compensation is performed by the permanent adjustment of the zero So the measurement of the differential pressure is then independent from the environmental conditions of the transmitter Advantage no drift Frequency of auto calibration resetable or from 1 to 60 minutes Autozero To perform an autozero unplug the 2 pressure connections tubes and press the Autozero key On CP211 and CP 212 transmitters it is not necessary to unplug the 2 pressure connection tubes When an autozero has been performed On green light turns off then turns on and on transmitters equipped with a display autoZ is displayed CONFIGURATION OF THE TRANSMITTERS It is possible on the class 210 to configu
10. INSTRUMENTS Pressure Temperature Humidity Air Velocity Airflow Sound level REEN Temperature transmitter eS TM 210 BJ E 2 ia ja Y a 26 1 N i bre 40 intel 29 o KEY POINTS 2 Configurable ranges from 0 to 50 C ambient model and from 100 to 400 C T model with terminal block Possibility of a second remote probe on terminal block _ B Display of the minimum and maximum values and trend indicator a4 j 4 wires analogue outputs 0 5 10 V or 0 4 20 mA Alimentation 24 Vdc Vac ou 115 230 Vac ABS V0 IP65 housing with or without display 4 turn system mounting with wall mount plate FEATURES OF THE HOUSING 59 2 mm 125mm 59 2 mm 115mm ww OO Ambient model PAR NUMBER To order just add the codes to complete the part number mmo Power supply Output B 24 Vac Vdc H 115 or 230 Vac Display O With display N Without display Example TM210 BOS Material ABS V0 as per UL94 Protection IP65 Display 75 x 40 mm LCD 19 digits 2 lines Height of digits Values 10 mm Units 5 mm Model with terminal block Cable gland For cables 0 8 mm maximum Weight 320 g Type of probe S Ambient Pt100 on terminal block B Two Pt100 on terminal block Temperature transmitter power supply 24 Vac Vdc with display et ambient probe TECHNICAL FEATURES Measuring range From 0 to 50
11. O Temperature difference TM210 transmitter can measure up to two temperatures temperature 1 and temperature 2 When two temperature probes are connected the transmitter can display the difference between both measured temperatures FUNCTION CONNECTIONS Analogue outputs a HHT DIP switc Us Sene SSi am ei d eae 7 d aS Tit Beck ere gt Bs n z 3 F E ES Rl es a s Type of power ne eh ei See aise supply of the nt J transmitter b Power supply terminal block E lt lt Cable gland Pt100 n 1 terminal Pt100 n 2 terminal LCC S software connection a block block a Pt100 wiring A o c c 1 2 2 Analogue output 1 Analogue output 2 For oie supply 230 Vac 115 out 1 out 2 For power supply 24 Vac models Vdc models Oo Ground Ge OF Co Neutral N o Phase L Oo g c O D S15 Oo For power supply 24 2 2o Vac models 5 O gt F gt Og gt Oc O TAE o2opnE Qo Neutral N Zg SF Co ba Phase L Terminal block 2 a ma a ase L ELECTRICAL CONNECTIONS as per NA15 100 standard f This connection must be made by a qualified technician To make the connection the transmitter must not be energized Before making the connection you must first check the power supply indicated on the transmitter board see b on Connections part The selection of the output signal in voltage 0 10 V or 0 5 V or in current 4 20 mA or 0 20 mA is
12. Sound level Humidity and temperature 1 CE transmitter 2 36 t TH 210 S F 54 ive KEY POINTS aG Configurable measuring ranges from 5 to 95 HR and from 40 to 180 C according the type ee of probe Functions relative and absolute humidity dew point wet and dry temperature and enthalpy 7 Stainless steel or polycarbonate probe 4 wires analogue output 0 5 10 V or 0 4 20 mA Power supply 24 Vdc Vac or 115 230 Vac Trend indicator ABS VO IP65 housing with or without display 4 turn system mounting with wall mount plate FEATURES OF THE HOUSING Remote model 59 2 mm Ambient model TECHNICAL FEATURES IN HUMIDITY Measuring range Unit of measurement Accu racy Repeatability linearity hysteresis Drift linked to temperature Resolution Factory calibration uncertainty Response time Type of sensor Type of fluid From 5 to 95 RH RH 1 5 RH if 15 C lt T lt 25 C 0 04 x T 20 RH if T lt 15 C or T gt 25 C 0 1 RH 0 88 RH lt 10 seconds from 10 to 80 RH V 2 m s Capacitive Air and neutral gases 125mm 190mm All accuracies indicated in this technical datasheet were stated in laboratory conditions and can be guaranteed for measurements carried out in the SS Material ABS V0 as per UL94 Protection IP65 Display 75 x 40 mm LCD 20 digits 2 lines Height of digits Values 10 mm Units 5 m
13. TEMPERATURE Measuring range Unit of measurement Accuracy Response time Resolution Type of sensor Type of fluid From 0 to 50 C C F 0 3 C T 0 9 second for V_ 1 m s 0 1 C NTC Air and neutral gases TECHNICAL FEATURES IN CO Measuring range Unit of measurement Accuracy Response time Resolution Type of sensor Type of fluid All the accuracies indicated in this technical datasheet were stated in laboratory conditions and can be guaranteed for measurements carried out in the same conditions or From 0 to 500 ppm ppm 3 ppm or 3 of the measured value T63 35s 0 1 ppm Electrochemical sensor Air and neutral gases carried out with calibration compensation TECHNICAL FEATURES OF THE PROBES gt Ambient probe Size Material gt Remote probe Length 112 mm Diameter 26 mm polycarbonate Size Length 158 mm without cable gland 183 mm with cable gland mm Diameter 26 mm Material polycarbonate Cable Length 2 m diameter 4 2 mm TECHNICAL SPECIFICATIONS Power supply Sortie Galvanic isolation Consumption Electromagnetical compatibility Electrical connection PC communication Environment Type of fluid Operating temperature Storage temperature 24 Vac Vdc 10 115 Vac or 230 Vac 10 50 60 Hz 2 x 4 20 mA ou 2 x 0 20 mA or 2 x 0 5 V or 2 x 0 10 V 4 wires Maximum load 500 Ohms 0 4 20 mA Minimum load 1 K Oh
14. ailable as an option MAINTENANCE Please avoid any aggressive solvent Please protect the transmitter and its probes from any cleaning product containing formalin that may be used for cleaning rooms or ducts OPTIONS AND ACCESSORIES e LCC S configuration software with USB cable e Calibration certificate 02 04 13 RCS 24 P rigueux 349 282 095 Non contractual document We reserve the right to modify the characteristics of our products without prior notice transmitter_COT212 FTang
15. es from 0 to 20000 ppm and from 0 to 50 B 4 wires analogue output 0 5 10 V or 0 4 20 mA oS Power supply 24 Vdc Vac or 115 230 Vac A Trend indicator a ABS VO IP65 housing with or without display w 4 turn system mounting with wall mount plate FEATURES OF THE HOUSING 59 2mm 3 3 E a 2 3 Remote model Ambient model Material ABS V0 as per UL94 Height of digits Values 10 mm Units 5 mm Protection IP65 Cable gland For cables 8 mm maximum Display 75 x 40 mm LCD 19 digits 2 lines Weight 320 g PART NUMBER To order just add the codes to 4 the part number C Display O with display N without display Example COT212 BOS Temperature and CO transmitter power supply 24 Vac Vde with display and ambient probe TECHNICAL FEATURES IN TEMPERATURE Measuring range Unit of measurement Accuracy Response time Resolution Type of sensor Type of fluid From 0 to 50 C C F 0 3 C T 0 9 second for V 1 m s 0 1 C NTC Air and neutral gases TECHNICAL FEAUTRES IN CO Measuring range Unit of measurement Accuracy Response time Resolution Type of sensor Type of fluid From 0 to 20000 ppm ppm 50 ppm or 3 of the measured value T63 35s 1 ppm Infrared sensor Air and neutral gases All the accuracies indicated in this technical datasheet were stated in laboratory conditions and can be g
16. for hotwire probe e LCC S configuration software with USB cable e Calibration certificate FTang transmitter _CTV210 02 04 13 RCS 24 P rigueux 349 282 095 Non contractual document We reserve the right to modify the characteristics of our products without prior notice Technical Data Sheet INSTR ENTS Pressure Temperature Humidity Air Velocity Airflow Sound level C CO and temperature transmitter gr sN COT 210 213 Oe me j 3 ory i KEY POINTS Configurable ranges from 0 to 500 ppm and from 0 to 50 C 4 wires analogue output 0 5 10 V or 0 4 20 mA Power supply 24 Vdc Vac or 115 230 Vac a Trend indicator ABS V0 IP65 housing with or without display 4 turn system mounting with wall mount plate FEATURES OF THE HOUSING 59 2 mm ww 8 L 115mm 202 mm ww SZ Remote model Ambient model Material ABS V0 as per UL94 Height of digits Values 10 mm Units 5 mm Protection IP65 Cable gland For cables 8 mm maximum Display 75 x 40 mm LCD 19 digits 2 lines Weight 320 g PART NUMBER To order just add the codes to TT the part number Power supply Output Type of probe B 24 Vac Vdc D remote H 115 or 230 Vac S ambient Display O with display N without display Example COT210 BOS Temperature and CO transmitter power supply 24 Vac Vdc with display and ambient probe TECHNICAL FEATURES IN
17. lling 6 mm screws and pins are supplied Insert the transmitter on the fixing plate see A on the drawing beside Rotate the housing in clockwise direction until you hear a click which confirms that the transmitter is correctly installed 0 mm 68 mm CALIBRATION Outputs diagnostic With this function you can check with a multimeter or on a regulator display or a PLC BMS if the transmitter outputs work properly The transmitter generates a voltage of 0 V 5 V and 10 V or a current of 4 mA 12 mA and 20 mA Certificate Class 210 transmitters are supplied with adjusting certificates Calibration certificates are available as an option MAINTENANCE Please avoid any aggressive solvent Please protect the transmitter and its probes from any cleaning product containing formalin that may be used for cleaning rooms or ducts OPTIONS AND ACCESSORIES e LCC S configuration software with USB cable e Calibration certificate FTang transmitter_COT210 02 04 13 RCS 24 P rigueux 349 282 095 Non contractual document We reserve the right to modify the characteristics of our products without prior notice Technical Data Sheet INSTR ENTS Pressure Temperature Humidity Air Velocity Airflow Sound level CO_ and temperature transmitter r a J BY COT 212 re ss ives bees hse Is ae a NC _____ Eo 3784 KEY PONTS 7 aS Configurable rang
18. m Cable gland For cables 8 mm maximum Weight 320 g FUNCTIONS Class 210 transmitters have two analogue outputs which correspond to both displayed parameters It is possible to activate one or two outputs and to select for each between humidity temperature and the functions described above Absolute humidity from 2 to 30 000 g kg unit 1 g kg Dew point from 60 to 100 Ctd unit 0 1 Ctd 0 1 F td Dry temperature from 20 to 102 C unit 0 1 C 0 1 F Enthalpy from 0 to 15 000 Kj kg unit 0 1 Kj kg same conditions or carried out with calibration compensation As per NFX 15 113 and the Charter 2000 2001 HYGROMETERS GAL Guaranteed Accuracy Limit which has been calculated with a coverage factor value of 2 is 2 58 RH between 18 and 28 C on the measuring range from 3 to 98 RH Sensor drift is less than 1 RH year The default configuration for the output 1 is 0 100 RH in hygrometry and 0 50 C in temperature for the output 2 Type of probe Probe length mm PART NUMBER To order just add the codes to complete the part number J E CI died peeps ly Output stainless steel 150 remote H ie a he Display Mounting ofthe P polycarbonate 300 remote O with display probe N without display D remote Example TH210 BNDP150 S ambient Temperature and humidity transmitter power supply 24 Vac Vdc without display with remote probe in polycarbonate of 150 mm length
19. m km h Standard model from 0 to 3 m s 3 of reading 0 03 m s from 3 to 30 m s 3 of reading 0 1 m s Omnidirectional model from 0 to 5 m s 3 of reading 0 05 m s Standard model from 0 to 3 m s 0 01 m s and from 3 to 30 m s 0 1 m s Omnidirectional model from 0 to 5 m s 0 01 m s All models 1 fom 0 1 km h Veg 1nd Clean air All the accuracies indicated in this technical datasheet were stated in laboratory conditions and can be guaranteed for measurements carried out in the same conditions or carried out with calibration compensation TECHNICAL FEATURES OF THE PROBES gt Hotwire probe Material of the probe Size Operating temperature Cable gt Omnidirectional probe Material of the probe Size Operating temperature Cable FUNCTION Stainless steel 316 L 8 mm length 300 mm From 0 to 50 C PVC 4 8 mm length 2 m Stainless steel 316 L Length 300 mm height 85 mm From 0 to 50 C PVC 24 8 mm length 2 m TECHNICAL SPECIFICATIONS Power supply 24 Vac Vdc 10 115 Vac or 230 Vac 10 50 60 Hz Output 2 x 4 20 mA or 2 x 0 20 mA ou 2 x 0 5 V ou 2 x 0 10 V 4 wires Maximum load 500 Ohms 0 4 20 mA Minimum load 1 K Ohms 0 5 10 V Galvanic isolation Inputs and outputs models 115 Vac 230 Vac Outputs models 24 Vac Vdc Consumption 5 VA Electromagnetical compatibility EN61326 Electrical connection Screw terminal block for cable
20. ms 0 5 10 V Inputs and outputs 115 Vac 230 Vac models Outputs 24 Vac Vdc model 5 VA EN61326 screw terminal block for cable 2 5 mm Kimo USB Mini Din cable Air and neutral gases Air and neutral gases From 0 to 50 C From 10 to 70 C CONNECTIONS DIP switc d LCC S software connection a SSS SS Analogue output 2 out 2 Analogue output 1 out 1 BPL 0 5 10 V Voltage GND Ground 0 4 20 mA Current 0 5 10 V Voltage GND Ground 0 4 20 mA Current Analogue outputs a Type of power supply of the transmitter b Power supply terminal block c Cable glands c OF c OF c For power supply 24 For power supply 24 For power supply 230 Vac 115 Vdc models Vac models Vac models Oc Oc Oo l Ground OQow Oc Neutral N Oo Neutral N Oe Co ja Phase L O t Phase L ELECTRICAL CONNECTIONS as per AC75 700 standard This connection must be made by a qualified technician To make the connection the transmitter must not be energized Before making the connection you must first check the power supply indicated on the transmitter board see b on Connections part gt For transmitters with 24 Vdc power supply Power supply 24 Vac class Il 230 Vac Power supply gt For transmitters with 115 or 230 Vac power supply Power supply S 115 230 Vac S Ground 3 Neutral The selecti
21. n functions etc via different methods e Keypad for models with display a code locking system allows to secure the installation See class 210 user manual e Software optional on all models Simple user friendly configuration See LCC SD user manual Configurable analogue output It is possible to configure your own intermediary ranges in CO and in temperature Caution the minimum difference between the high range and the low range is 20 Configure the range according to your needs outputs are automatically adjusted to the new measuring range 10000 15000 0 ppm 10000 ppm 20000 ppm 0 ppm o 20000 ppm New range T 0V 10 V 4 mA 20 mA 0V 10 V 4 mA 20 mA Lua C iny 75 mm To mount the transmitter mount the ABS plate on the wall drilling 6 mm screws and eo a gs pins are supplied Insert the transmitter on the fixing plate see A on the drawing beside Rotate the housing in clockwise direction until you hear a click which confirms that the transmitter is correctly installed 23 75 mm CALIBRATION Outputs diagnostic With this function you can check with a multimeter or on a regulator display or a PLC BMS if the transmitter outputs work properly The transmitter generates a voltage of 0 V 5 V and 10 V or a current of 4 mA 12 mA and 20 mA Certificate Class 210 transmitters are supplied with adjusting certificates Calibration certificates are av
22. o 0V 10 V 4 mA 20 mA 0V 10 V 4 mA 20 mA r 75 mm MOUNTING 375mm _ 40 mm To mount the transmitter mount the ABS plate on the wall drilling 6 mm screws and pins are supplied Insert the transmitter on the fixing plate see A on the drawing beside Rotate the housing in clockwise direction until you hear a click which confirms that the transmitter is correctly installed 0 mm 68 mm CALIBRATION Outputs diagnostic With this function you can check with a multimeter or on a regulator display or a PLC BMS if the transmitter outputs work properly The transmitter generates a voltage of 0 V 5 V and 10 V or a current of 4 mA 12 mA and 20 mA Certificate Class 210 transmitters are supplied with adjusting certificates Calibration certificates are available as an option MAINTENANCE Please avoid any aggressive solvent Please protect the transmitter and its probes from any cleaning product containing formalin that may be used for cleaning rooms or ducts OPTIONS AND ACCESSORIES e LCC S configuration software with USB cable e Sliding fittings e Protections tips e Calibration certificate e Connection fittings e Wall mounting support e Cable glands bracket for remote humidity probe FTang transmitter _TH210 02 04 13 RCS 24 P rigueux 349 282 095 Non contractual document We reserve the right to modify the characteristics of our products without prio
23. on you can check with a multimeter or on a regulator display or a PLC BMS if the transmitter outputs work properly The transmitter generates a voltage of 0 V 5 V and 10 V or a current of 4 mA 12 mA and 20 mA Certificate Class 210 transmitters are supplied with adjusting certificates Calibration certificates are available as an option MAINTENANCE Please avoid any aggressive solvent Please protect the transmitter and its probes from any cleaning product containing formalin that may be used for cleaning rooms or ducts OPTIONS AND ACCESSORIES e LCC S configuration software with USB cable Connection tube Straight connections e SQR 3 function square root for the measurement of air e Connection fittings e Spherical coupling nut velocity and air flow e Through connections e Calibration certificate 04 04 13 RCS 24 P rigueux 349 282 095 Non contractual document We reserve the right to modify the characteristics of our products without prior notice transmitter_CP210 FTang INSTRUMENTS Pressure Temperature Humidity Air Velocity Airflow Sound level Air velocity and temperature ac transmitter tay CTV 210 Se a R KEY POINTS r ad the SET TEETER Amsa Gf Configurable ranges from 0 to 30 m s model with hot wire probe and from 0 to 5 m s a a model with omnidirectional probe Configurable range from 0 to 50 C in temperature Airflow function Ze ig 4 wires analogue out
24. on of the output signal in voltage 0 10 V or 0 5 V or in current 4 20 mA or 0 20 mA is made via the DIP switch d of the electronic board of the transmitter put the on of switches as shown in the table below Configurations 4 20 mA 0 10 V 0 5 V 0 20 mA 1234 1234 1234 123 4 gt Connection of output in voltage 0 10 V gt Connection of the output in current 4 20 mA 0 4 20 mA 0 5 10 V 0 5 10 V 0 4 20 mA 4 20 mA output 0 10 V output Phase CONFIGURATION OF THE TRANSMITTERS It is possible on the class 210 to configure all the parameters of the transmitter units measuring ranges outputs channels calculation functions etc via different methods e Keypad for models with display a code locking system allows to secure the installation See class 210 user manual e Software optional on all models Simple user friendly configuration See LCC SD user manual Configurable analogue output It is possible to configure your own intermediary ranges in CO and in temperature Caution the minimum difference between the high range and the low range is 20 Configure the range according to your needs outputs are automatically adjusted to the new measuring range 0 ppm 250 ppm 900 ppm 0 ppm 250 ____375 900 ppm New range T 0V 10 V 4 mA 20 mA OV 10V 4mA 20 mA Saas 75 mm MOUNTING a 3 5 mm 40 mm _ To mount the transmitter mount the ABS plate on the wall dri
25. onfigurable analogue output It is possible to configure your own intermediary ranges from 0 5 m s to 0 30 m s Caution the minimum difference between the high range and the low range is 20 Configure the range according to your needs outputs are automatically adjusted to the new measuring range 0 m s 10 30 m s 0 mis 30 m s New range 0V 10 V 4mA 20 mA 0V 10 V 4 mA 20 mA L TT i i 75 mm To mount the transmitter mount the ABS plate on the wall drilling 6 mm screws and on a pins are supplied Insert the transmitter on the fixing plate see A on the drawing beside Rotate the housing in clockwise direction until you hear a click which confirms that the transmitter is correctly installed 23 75 mm 68 mm CALIBRATION Outputs diagnostic With this function you can check with a multimeter or on a regulator display or a PLC BMS if the transmitter outputs work properly The transmitter generates a voltage of 0 V 5 V and 10 V or a current of 4 mA 12 mA and 20 mA Certificate Class 210 transmitters are supplied with adjusting certificates Calibration certificates are available as an option MAINTENANCE Please avoid any aggressive solvent Please protect the transmitter and its probes from any cleaning product containing formalin that may be used for cleaning rooms or ducts OPTIONS AND ACCESSORIES e Sliding fittings e Mounting brackets e Clean spray
26. option with the SQR 3 function square root function allowing to calculate the air velocity and or air flow in a duct from a differential pressure e Air velocity calculation V C par p p Features Measuring ranges Units and resolutions Functions Air velocity From 3 to 100 m s according to model 0 1 m s 0 1 fom From 0 to 100 000 m h according to 1m h 0 1 m s Air flow air velocity and section 0 1I s 1 cfm Differential pressure device Pitot tube Debimo as option Po 287 1X 273 15 With C differential pressure device coefficient Pitot tube type L C 1 0015 Pitot tube type S C 0 84 Debimo blade C 0 8165 given temperature C P given atmospheric pressure Pa e Air flow calculation Air flow m h air velocity m s x surface m x 3600 Surface setting of duct type rectangular or circular and duct size mm or inch INTEGRATION OF PRESSURE MEASUREMENT The pressure measurement element is very sensitive and reacts to pressure changes When making measurements in unstable air movement conditions the pressure measurement may fluctuate The integration coefficient from 0 to 9 makes an average of the measurements and then helps avoid any excessive variations it guarantees a stable measurement CONNECTIONS DIP switch d as wpn Solenoid valve only on CP211 212 VV a LCC S software connection Autoze
27. put 0 5 10 V or 0 4 20 mA Power supply 24 Vdc Vac or 115 230 Vac Trend indicator ABS V0 IP65 housing with or without display 1 4 turn system mounting with wall mount plate FEATURES OF THE HOUSING 59 2 mm _ _ 125mm Material ABS V0 as per UL94 Protection IP65 Display 75 x 40 mm LCD 20 digits 2 lines Height of digits Values 10 mm Units 5 mm 115mm Cable gland For cables 8 mm maximum Weight 320g PART NUMBER To order just add the codes to complete the part number maj C O Power supply Output l B 24 Vac Vde Mounting of the probe H 115 or 230 Vac ene Display O omnidirectional O with display N without display Example CTV210 BOO300 Air velocity and temperature transmitter power supply 24 Vac Vdc with display and omnidirectional probe of 300 mm length TECHNICAL FEATURES IN TEMPERATURE Measuring range Unit of measurement Accuracy Response time Resolution Type of sensor Type of fluid From 0 to 50 C C F 0 3 of reading 0 25 C La 0 9 second for Vi 1 m s 0 1 C 0 1 F Pt100 1 3 as per DIN IEC751 Air and neutral gases TECHNICAL FEATURES IN AIR VELOCITY Measuring range Unit of measurement Accuracy standard and omnidirectional models Resolution Response time Type of fluid Standard model from 0 to 30 m s Omnidirectional model from 0 to 5 m s m s fo
28. r notice Technical Data Sheet INSTR ENTS Pressure Temperature Humidity Air Velocity Airflow Sound level Temperature and differential pressure CE transmitter SEED 2 KEY POINTS m UB Ph Range from 100 100 Pa to 2000 2000 mbar according to see Part number J E S Input Pt100 on terminal block for temperature measurement range from 100 to 00 1 400 C probes as option cp 210 o Configurable intermediate ranges i my DP 4 wires analogue output 0 5 10 V or 0 4 20 mA Power supply 24 Vdc Vac or 115 230 Vac iI a Trend indicator ABS V0 housing IP65 with or without display 4 turn system mounting with wall mount plate Solenoid valve for auto calibration only on CP211 and CP212 models FEATURES OF THE HOUSING 59 2 mm Material ABS V0 as per UL94 Protection IP65 Display 75 x 40 mm LCD 19 digits 2 lines Height of digits Values 10 mm Units 5 mm E Connection Ribbed 6 2 mm CP211 212 of Compression for tubes 4x6 mm CP213 214 215 Pass through for cables 6 mm maximum Cable gland for cables 8 mm maximum Weight 320g PART NUMBER To order just add the codes to complete the part number Example CP 211 HO Pressure transmitter 100 100 Pa measuring range with CP21 power supply 115 or 230 Vac with display Display Measuring range O with display 4 100 100 Pa N without display 2 1000 1000 Pa 3
29. re all the parameters managed by the transmitter units measuring ranges outputs channels calculation functions etc via different methods e Keypad for models with display a code locking system allows to secure the installation See class 210 user manual e Software optional on all models Simple user friendly configuration See LCC SD user manual Configurable analogue output Range with central zero 50 0 50 Pa with offset zero 300 0 70 Pa or standard range 0 100 Pa it is possible to configure your own intermediate ranges Caution the minimum difference between the high range and the low range is 20 Configure the range according to your needs outputs are automatically adjusted to the new measuring range To mount the transmitter mount the ABS plate on the wall drilling 6 mm screws and pins are supplied Insert the transmitter on the fixing plate see A on the drawing beside Rotate the housing in clockwise direction until you hear a click which confirms that the transmitter is correctly installed 23 75 mm guarantee the correct working of the transmitter in any position B14 mm 68 mm CALIBRATION Adjusting and calibration on site The professional configuration interface with a dynamic pressure calibration bench enables you to adjust and calibrate your transmitters directly on site or in laboratories Outputs diagnostic With this functi
30. ro lif Pressure connections Analogue outputs a Power supply type of the transmitter b Power supply terminal block c paua Cable glands Analogue output 1 Analogue output 2 CO0 For power supply 24 For power supply 24 For power supply 230 Vac 115 Vdc models Vac models Vac models v 2 E t Ground g pE Neutral N Neutral N E 7 BY Phase L Phase L gt Oc gt Oc l a 0o 2 90 3 Og 56 Ox oO ELECTRICAL CONNECTIONS as per NA15 100 standard gt For transmitters with 24 Vdc power supply Power supply 24 Vac class II 230 Vac Power supply gt For transmitters with 115 or 230 Vac power supply Ground Neutral Power supply S 115 230 Vac Phase A This connection must be made by a qualified technician To make the connection the transmitter must not be energized Before making the connection you must first check the power supply indicated on the transmitter board see b on Connections part The selection of the output signal in voltage 0 10 V or 0 5 V or in current 4 20 mA or 0 20 mA is made via the DIP switch d of the electronic board of the transmitter put the on of switches as shown in the table below Configurations 4 20 mA 0 10 V 0 5 V 0 20 mA 1234 123411234 1234 gt Connection of output in gt Connection of the output voltage 0 10 V in current
31. t the on of switches as shown in the table below Configurations 123 4 no 123 4 123 4 23 4 Power supply 24 Vac class Il Vac L in current 4 20 mA 0 5 10V 0 4 20 mA 230 Vac Power supply gt For transmitters with 115 or 230 Vac power supply Ground 3 PLC BMS passive Neutral type 4 20 mA output Power supply 115 230 Vac SQ Phase gt Connection of the output gt Connection of output in voltage 0 10 V 0 5 10 V 0 4 20 mA Regulator display or PLC BMS passive type 0 10 V output CONFIGURATION OF THE TRANSMITTERS It is possible on the class 210 to configure all the parameters of the transmitter units measuring ranges outputs channels calculation functions etc via different methods e Keypad for models with display a code locking system allows to secure the installation See class 210 user manual e Software optional on all models Simple user friendly configuration See LCC SD user manual Configurable analogue output Range with center zero 40 0 40 C with offset zero 30 0 70 C or standard range 0 100 C It is possible to configure your own intermediary ranges Caution the minimum difference between the high range and the low range is 20 Configure the range according to your needs outputs are automatically adjusted to the new measuring range 40 C 0 180 C 40 C 0 50 180 C New range SN
32. temperature Storage temperature 24 Vac Vdc 10 115 Vac or 230 Vac 10 50 60 Hz 2 x 4 20 mA or 2 x 0 20 mA or 2 x 0 5 V or 2 x 0 10 V 4 wires Maximum load 500 Ohms 0 4 20 mA Minimum load 1 K Ohms 0 5 10 V Inputs and outputs 115 Vac 230 Vac models Outputs 24 Vac Vdc models 5 VA EN61326 Screw terminal block for cables 2 5 mm Kimo USB Mini Din cable Air and neutral gases Manual by push button Automatic by solenoid valve only CP211 CP212 Air and neutral gases From 0 to 50 C From 10 to 70 C CONFIGURABLE INTERMEDIATE OR CENTER ZERO RANGES Transmitter Breese tand Aivclocine vance These air velocity ranges are given for information based on a 3 y Fang Debimo differential probe Cm 0 81 and do not take into account CP211 100 100 Pa From 3 to 10 m s temperature compensation CP212 1000 1000 Pa From 3 to 30 m s CP213 10 000 10 000 Pa From 3 to 100 m s CP214 500 500 mbar Not available CP215 2000 2000 mbar Not available AIR FLOW AND AIR VELOCITY FUNCTION available option on CP211 CP212 and CP2T3 instruments Class 210 transmitters have 2 analogue outputs that correspond to both displayed parameters It is possible to activate one or two outputs and select for each output between pressure air velocity and air flow functions as option Linked to a differential pressure device Debimo blade Pitot tube orifice plate they can be equipped as
33. uaranteed for measurements carried out in the same conditions or carried out with calibration compensation TECHNICAL FEATURES OF THE PROBES gt Ambient probe Size Material gt Remote probe Length 112 mm Diameter 26 mm polycarbonate Size Length 158 mm without cable gland 183 mm with cable gland mm Diameter 26 mm Material polycarbonate Cable Length 2 m diameter 4 8 mm TECHNICAL SPECIFICATIONS Power supply 24 Vac Vdc 10 115 Vac or Output Galvanic isolation Consumption Electromagnetical compatibility Electrical connection PC communication Environment Type of fluid Operating temperature Storage temperature 230 Vac 10 50 60 Hz 2 x 4 20 mA or 2 x 0 20 mA or 2 x 0 5 V or 2 x 0 10 V 4 wires Maximum load 500 Ohms 0 4 20 mA Minimum load 1 K Ohms 0 5 10 V Inputs and outputs 115 Vac 230 Vac models Outputs 24 Vac Vdc model 5 VA EN61326 Screw terminal block for cable 2 5 mm Kimo USB Mini Din cable Air and neutral gases Air and neutral gases From 0 to 50 C From 10 to 70 C CONNECTIONS Analogue outputs a Type of power supply of the transmitter b DIP switc d Power supply terminal block c LCC S software connection a P Cable glands Analogue output 1 Analogue output 2 Add For power supply 24 For power supply 24 For power supply 230 Vac 115 Vdc models Vac models Vac models 2 x o Oc Qo Oc Gro
34. und g 5 2 z Qo Qo Neutral N Qo Neutral N 1 amp 7 1 Oo Oo Phase L O Phase L O gt Oc o o J amp 00 2s Soo 56 Og oO ELECTRICAL CONNECTIONS as per NA 15 100 standard This connection must be made by a qualified technician To make the connection the transmitter must not be energized Before making the connection you must first check the power supply indicated on the transmitter board see b on Connections part The selection of the output signal in voltage 0 10 V or 0 5 V or in current 4 20 mA or 0 20 mA is made via the DIP switch d of the electronic board of the transmitter put the on of switches as shown in the table below gt For transmitters with 24 Vdc power supply Configurations Power supply 24 Vac 123 4 123 4 123 4 23 4 class II O Vac N I gt Connection of the output gt Connection of output in 230 Vac VacL in current 4 20 mA voltage 0 10 V or 0 5 10 V 0 4 20 mA 0 5 10 V 0 4 20 mA 230 Vac Power supply gt For transmitters with 115 or 230 Vac power supply Regulator display or PLC BMS passive type Neutral type Power supply S 115 230 Vac S Phase 4 20 mA output 0 10 V output Ground PLC BMS passive CONFIGURATION OF THE TRANSMITTERS It is possible on the class 210 to configure all the parameters of the transmitter units measuring ranges outputs channels calculatio
35. y a qualified technician To make the connection the transmitter must not be energized Before making the connection you must first check the power supply indicated on the transmitter board see b on Connections part The selection of the output signal in voltage 0 10 V or 0 5 V or in current 4 20 mA or 0 20 mA is made via the DIP switch d of the electronic board of the transmitter put the on of switches as shown in the table below gt For transmitters with 24 Vdc power supply Configurations Power supply 24 Vac 123 4 123 4 123 4 23 4 class II O Vac N I gt Connection of the output gt Connection of output in 230 Vac VacL in current 4 20 mA voltage 0 10 V or 0 5 10 V 0 4 20 mA 0 5 10 V 0 4 20 mA 230 Vac Power supply gt For transmitters with 115 or 230 Vac power supply Regulator display or PLC BMS passive type Neutral type Power supply S 115 230 Vac S Phase 4 20 mA output 0 10 V output Ground PLC BMS passive CONFIGURATION OF THE TRANSMITTERS It is possible on the class 210 to configure all the parameters of the transmitter units measuring ranges outputs channels calculation functions etc via different methods e Via keypad for models with display a code locking system allows to secure the installation See class 210 user manual e Via software optional on all models Simple user friendly configuration See LCC SD user manual C