ADAPTTM Colibri

image

Contents

1. Ext Extension cable between box and air diffuser LINK Wa Network cable for Modbus complies with the Figure 4 ADAPT Colibri dimension figure EIA 485 standard l a 5 Swegon reserves the right to alter specifications 20121114 www swegon com
2. alter specifications 20 30 40 50 100 200 300 400 500 m h amy To r otr T Fa ae a a a a 0 2 03 04 0 5 1 2 3 4 5 10 lba m N p Pa D 1000 40 dB A r F 35 500 400 300 alt 200 z5 100 2 50 40 30 20 4 5 10 20 30 40 50 100 200 3001 s 400 T 1 4 T merr eT TTI 20 30 40 50 100 200 300 400 500 1000 m h amy ot Jt oe 0 2 03 04 0 5 1 2 3 4 5 10 bam 20121114 www swegon com WISE Dimensions and weights Size A B C D d 160 595x595 504 332 159 250 250 595x595 622 388 249 315 Size E F G H K Weight kg 160 314 201 214 450 100 8 5 250 395 300 247 575 140 113 CL Center line Swegon Ordering key Product Rectangular active air diffuser ADAPTC c bbb c for ceiling Version Connection dimensions M Master S Slave N B Specify absence min max airflows in your specification Standard range Size 160 250 Accessories DETECT Quality Temperature and CO sensor with set point selector knob TUNE Adapt Hand held terminal for reading changing settings TUNE Temp Temperature adjuster D LINK Modbus RJ12 cable for connecting up Modbus RTU Ck LINK Adapt RJ45 cable for connecting up in other lengths E SPLIT Link Split connector G FIX Link For securing cords to ducts etc POWER Adapt Transformer ACTUATOR Valve actuator on off VALVE Radiator valve ADAPT Relay Relay for light or heat control ADAPT TR Semi conductor relay for lighting or heat control CABLE
3. e The throw L is measured under isothermal discharge conditions e Recommended max permitted temperature below room temperature is 12 K e All technical data applies to 360 distribution pattern e For calculating the air stream propagation air velocities in the occupancy zone or sound levels in rooms with other dimensions we refer to our ProAir Web calculation program ProAir Web is available at www swegon com Sound data Sound power level L dB Table K Mid frequency Octave band Hz 63 125 250 500 1000 2000 4000 8000 160 0 7 5 2 6 10 13 7 250 1 5 2 1 3 9 12 10 Tol 2 2 2 2 2 2 2 2 Size Sound attenuation AL Table AL Mid frequency Octave band Hz 63 125 250 500 1000 2000 4000 8000 160 15 9 9 20 19 15 16 14 250 13 8 10 19 16 13 16 16 Tol 2 2 2 2 2 2 2 2 Size Swegon Engineering graphs Air flow Pressure drop Sound level Throw e The diagrams should not be used for commissioning e The dB C value is normally 6 9 dB higher than the dB A value e Sizing example size 160 Given airflow 10 50 I s at P 50 Pa Max sound level 27 dB A Throw 2 0 m ADAPT C 160 p Pa s E W 100 200 Vs 300 T Tov tt tt w a a So N w D J48 a e Ea E E tt Swegon reserves the right to
4. wise is mounted on a wall ceiling for wiring a 24 V supply voltage to the air diffuser and Modbus networks e Both air diffuser and junction box are equipped with RJ45 quick fit connectors for quick and fault free wiring e The device has provision for connection to a main control system BMS SCADA via MocBus e Accessory cable LINK Modbus RJ12 can be connected between air diffuser and junction box The air diffuser will then be ready for the main control system e From the junction box control functions for heating in sequence CO sensor and set point adjuster can also be connected Planning WISE Templates See separate documentation WISE Project manual available for download from www swegon se In addition Swegon sales personnel can supply WISE templates containing descriptions with detailed information regarding functionality flowcharts wiring diagrams and demarcation list for various constructions Figure 1 The sensor module of ADAPT Colibri with connection for TUNE Adapt 1 Temperature detector 2 In operation indicator green red and orange LED 3 Presence detector Figure 2 Junction box CONNECT Adapt Swegon reserves the right to alter specifications 20121114 www swegon com WISE Installation A detailed installation instruction is enclosed with each delivery and can also be downloaded from www swegon 1 The commissioning box can be suspended from a ceil
5. ADAPT Colibri Active communicative air diffuser for the WISE system ADAPT C Quick facts gt Supply air diffuser with an active damper gt Pressure dependent and cleanable gt Integrated sensor module gt Simple wiring Plug amp Play gt Communication via Modbus RTU gt Supplied complete with junction box CONNECT Adapt gt Complemented with the WISE templates containing detailed descriptions for planning gt Allows for control of Heat alternatively cooling valve max 3 actuators per master Slaves supply or extract air 3 pcs Lighting via relay Quick Selection AIR FLOW SOUND LEVEL COOLING EFFECT min g max q I s max p Size Vs 50Pa 30 dB A 150Pa 35dB A W 160 0 5 55 60 530 250 0 10 85 90 860 The first value indicates closed damper the second value indicates lowest adjustable air flow Max cooling effect is calculated at At 8K and for an air flow at 50 Pa and 30 dB A Swegon WISE Technical Description Design ADAPT is a series of flow controlled supply air diffusers for the Swegon WISE system e The air diffuser controls the airflow with an active damper inside the commissioning box see figure 1 e An ADAPT diffuser is always supplied with a commissioning box e Inside the air diffuser is a controller providing all the required set points and control functions as well as a multi functional sensor module see f
6. igure 1 Functions in the Master diffuser e Cools heats and ventilates with air e Two stage cooling with water in the second stage cannot be combined with heating e Controls airflow with regard to temperature and presence e Ventilation boost after longer periods of unoccupancy e Provision for wiring to a CO controller e Provision for manually setting set points e Has provision for connection to a main control system Modbus e Emergency functions for closing opening of the damper e Control of the heating in sequence unless 2 stage cooling has been selected e Indication via LED Indicates current operating mode and warns of malfunctions in the diffuser e Comfort control indicated by the LED if the room temper ature or CO value deviates too much from the set point not activated by default Sensor module A sensor module is integrated in all ADAPT supply air diffusers containing the following functions e A temperature sensor controls the airflow to maintain required temperature in the room e A presence detector makes it possible to save additional energy by lowering the airflow when there are no occu pants in the room e The presence signal from the air diffuser can be fetched for controlling the lighting for instance and in this way save more energy Connectivity In each delivery of a master diffuser a CONNECT Adapt junction box is included e The junction box replaces the coupling box which other
7. ing and connected to duct system Use hanger system A or B 2 Press the ADAPT Colibri air diffuser into the outlet of the commissioning box and secure it with screws or pop rivets Readjust the hanger rods of the commissioning box if needed so that the air diffuser sits tight against the ceil ing or the framework of the modular suspended ceiling wW Ss 252 a Swegon Maintenance e The ADAPT air terminals can be cleaned on the out side if necessary using lukewarm water with dish washing detergent added e The duct system is accessible without need for tools See the separate installation instruction Declaration Declaration of Construction Materials is available for down load from www swegon com Electrical data ADAPT is supplied with power via the junction box For more information about various wiring and room solu tions see the Technical Section Supply voltage 24V AC 10 Max power consumption 3 VA Cable rating 0 6 A Ambient temperature 0 C 50 C Forms of delivery e Some of the ADAPT products are available from stock with standard settings e At delivery a master air diffuser contains a complete air diffuser with commissioning box junction box CONNECT Adapt and 5 metre long RJ45 cable LINK Adapt e Delivery of a slave air diffuser contains a complete air dif fuser with commissioning box and 5 metre long RJ45 Standard settings Temperatures C Figure 3 Adapt Co
8. libri installation Presence 22 1K Absence 22 3 2K ee Night ti i 18 Commissioning E ees e Normally the ADAPT air terminals are preset from the Morning heat 25 factory based on design values Airflows l s Absence Min Max e The TUNE Adapt hand held terminal is used for manu airflow airflow ally checking the current air flow through the air dif The smallest size 0 5 10 60 fuser an for enema set pont if ce Thiet laresr s 0 10 15 90 e For more information see the installation Commis sioning Maintenance instruction as well as the TUNE Air quality ppm Min Max Adapt user manual CO 300 1000 Materials and finish Presence e ADAPT air terminals are made of galvanized sheet steel Switch on delay O sec with parts made of plastic rubber and also contain Switch out delay 20 min electronic components e The ADAPT air terminals are powder coated in Swe Communication Modbus RTU by RS 485 gon s white interior standard colour RAL 9010 both on Modbus ID 1 the inside and on the outside Speed 38 400 bps e The sensor module and junction box are made of ABS Bit length 8 bits piani ee Stop bits 1 bit e The commissioning box is made of galvanized sheet ae Parity None steel with internal insulation l TaS 3 Swegon reserves the right to alter specifications 20121114 www swegon com WISE Sizing e The specified sound levels dB A are applicable to rooms with an equivalent sound absorption area of 10 m 4 dB room attenuation

Download Pdf Manuals

image

Related Search

Related Contents

LC-Power LC5300AIOII  Oracle Financial Services Regulatory Reporting Administration Guide  Manual - Lowrance  Electro-Voice Musicaster II User's Manual  Rapport  Agilent 220 TapeStation System Troubleshooting Manual  Sony VAIO VPCEB16FD  Viper SC IP Router For Licensed Spectrum  MPLAB-PROMATE User's Guide  New Health-Experience  