ProfiHub B2FO2+ User Manual

image

Contents

1. v Transparent v Latest RS 485 technology v Max 12 Mbps v Auto baudrate detection v Redundant power supply VY Digital glitch filtering v No limit in cascading v Integrated switchable termination v Diagnostic LEDs v DB9 connector for measurements v IP 20 with DIN rail mounting www procentec com profihub b1 en
2. EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual 2 10 Baudrate switch The ProfiHub B2FO2 recognizes the transmission speed by default If it is required that the ProfiHub B2FO2 is locked to a certain transmission speed the baudrate switch should be set to the required value Fig 16 PROCENT ProfiHub B2 PRION JUE 12 24VDC POW 1 POW 2 Fig 16 Baudrate speed switch To set the rotary switch use a 3 mm screwdriver Switch values 0 Normal repeating Auto detect default 1 9 6 kbps 2 19 2 kbps 3 45 45 kbps 4 93 75 kbps 5 187 5 kbps 6 500 kbps 7 1500 kbps 8 3000 kbps 9 6000 kbps A 12000 kbps B Robust repeating Auto detect C Robust repeating redundancy on copper channel 1 and 2 D F Reserved for future use Please note that the position of the rotary switch is only sampled during start up Changing the position of the switch will not have effect during operation The auto baudrate detect feature will search for the correct baud rate within 10 seconds of receiving the first telegram This baud rate lock will be lost after 50 seconds of incorrect or no message reception Version 1 0 July 2014 Page 19 40 ProfiHub B2FO2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual 2 11 Robust Repeating mode The B2
3. Industrial Control 8 Hamlacha St New Industrial Zone Netanya 42170 Israel Tel 972 9 8357090 Fax 972 9 8350619 Email info instrumetrics ic co il Internet www inst ic co il ITALY C S M T Gestione S C A R L via Branze n 43 45 25123 BRESCIA Italy Tel 39 030 6595111 Fax 39 030 6595000 Email profibus csmt it Internet profibus csmt it Genoa FIELDBUS Competence Centre Via Greto di Cornigliano 6R 38 16152 GENOVA Italy Tel 39 010 86 02 580 Fax 39 010 65 63 233 Email procentec gfcc it Internet www gfcc it Page 24 40 PROCENTEC 2014 Copyright all rights reserved PROCENTEG JAPAN TJ Group C O Japanese PROFIBUS Organisation West World Building 4F 3 1 6 Higashi Gotanda Shinagawa ku TOKYO Japan Tel 81 3 6450 3739 Fax 81 3 6450 3739 Email info profibus jp KOREA Hi PRO Tech Co Ltd 2802 U Tower 1029 Youngduk dong Giheung gu Yongin Si Kyunggi do 446 908 KOREA Tel 82 82 31 216 2640 Fax 82 82 31 216 2644 Email chays hiprotech co kr Internet www profibus co kr LEBANON Industrial Technologies S A L ITEC Point Center Boulevard Fouad Chehab Sin EI Fil BEIRUT Tel 961 1 491161 Fax 961 1 491162 Email sales iteclb com Internet www iteclb com NETHERLANDS PROCENTEC B V Klopperman 16 2292 JD Wateringen Tel 31 0 174 671800 Fax 31 0 174 671 801 Email info procentec com Internet www procentec com N
4. selectable with rotary switch Transmission speed switch 0 Normal repeating Auto detect default 1 9 6 kbps 2 19 2 kbps 3 45 45 kbps 4 93 75 kbps 5 187 5 kbps 6 500 kbps 7 1500 kbps 8 3000 kbps 9 6000 kbps A 12000 kbps B Robust repeating auto detect C Robust repeating redundancy on channel 4 and 5 D F Same as 0 Transmission speed detection time lt 10 s if it is set to auto detect Data delay time At baudrate Normal mode Robust mode 9 6 93 75 kbps lt 1 7 Tbit lt 13 25 Tbit 187 5 500 kbps lt 1 8 Tbit lt 13 30 Tbit 1 5 Mbps lt 1 9 Tbit lt 13 40 Tbit 3 Mbps lt 2 2 Tbit lt 13 60 Tbit 6 Mbps lt 3 0 Tbit lt 14 00 Tbit 12 Mbps lt 4 0 Tbit lt 15 00 Tbit Delay time jitter Max 74 bit time Cascading depth No limits Version 1 0 July 2014 Page 21 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual Technical Data ProfiHub B2FO2 PROFIBUS Fiber Optic cable specifications Cable types Fiber Optic type Cable lengths Connectors Redundancy G62 5 125 ISO IEC 11801 OM1 IEC 60793 2 10 type A1b TIA EIA 492AAAA ITU 651 1 G50 125 ISO IEC 11801 OM2 or better IEC 60793 2 10 type A1a TIA EIA 492AAAB A ITU 651 1 Multimode 850 nm G62 5 125 3000 m baud rate independent G50 125 to be defined 4x ST BFOC No PROFIBUS copper cable specifications Ca
5. 10 02 2016 Certificate number NL 6313 On behall of Stichting Lu MityMasters WW d A WK LL pd Version 1 0 July 2014 Page 31 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROGCENTEG ProfiHub B2FO2 User Manual PROFIBUS PROFINET Certificate for a PI Competence Center FI confirms that PROCENTEC Klopperman 16 2292 JD Wateringen THE NETHERLANDS is a fully accredited PI Competence Center for PROFIBUS basic and PROFIBUS PA This certificate is granted according to the Quality of Services Agreement for PI Competence Centers and is valid for 2 years until December 31 2015 Holo y 5 yd Official in harge Chairmen of PI Kersten Schneider Chairman patet Michael J Bryant Deputy Chairman Version 1 0 July 2014 Page 32 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual PROFIBUS PROFINET Certificate Authorization as PI Test Laboratory ant dated March 20 2013 and the The execution of the tests aimed in the PROFIBUS certification shall be conform to the PROFIBUS Standard and the valid guidelines This authorization is valid until December 31 2014 Version 1 0 July 2014 Page 33 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub
6. 63 Esc B Planta 1 Rubi BARCELONA 08191 Tel 34 93 588 67 67 Email xavier cardena logitek es Internet www logitek es SWEDEN P amp L Nordic AB Box 252 S 281 23 HASSLEHOLM Sweden Tel 46 451 74 44 00 Fax 46 451 89 833 Email hans maunsbach g pol se Internet www pol se profibus SWITZERLAND Berner Fachhochschule f r Technik und Informatik PROFIBUS Kompetenzzentrum Jlcoweg 1 CH 3400 BURGDORF Switzerland Tel 41 0 34 426 68 32 Fax 41 0 34 426 68 13 Email max felser bfh ch Internet www profitrace ch Version 1 0 July 2014 PROCENTEC 2014 Copyright all rights reserved ProfiHub B2FO2 User Manual TAIWAN Full Data Technology 6F No 200 Gangqian Rd Neihu District Taipei City 114 Taiwan Tel 886 2 87519941 9097 Fax 886 2 87519533 Email sales fulldata com tw Internet www fulldata com tw TURKEY Emikon Otomasyon DES Sanayi sitesi 103 sokak B 7 blok No 16 Yukari Dudullu Umraniye Istanbul 34776 Turkey Tel 90 216 420 8347 Fax 90 216 420 8348 Email tolgaturunz emikonotomasyon com Internet www emikonotomasyon com UNITED ARAB EMIRATES Synergy Controls 907 IT Plaza Silicon Oasis DUBAI UAE Tel 971 4 3262692 Fax 971 4 3262693 Email sales synergycontrols ae UNITED KINGDOM Verwer Training amp Consultancy 5 Barclay Road Poynton Stockport Cheshire SK12 1YY Tel 44 0 1625 871199 Email andy verwertraining com Int
7. B2FO2 User Manual 8 Revision History Version 1 0 First release Version 1 0 July 2014 Page 34 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual 9 Next versions Version 1 0 July 2014 Page 35 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual 10Notes Version 1 0 July 2014 Page 36 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual Version 1 0 July 2014 Page 37 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual Version 1 0 July 2014 Page 38 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual Version 1 0 July 2014 Page 39 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved Other PROCENTEC products IP 66 Compact PROFIBUS repeater v Single channel PROFIBUS repeater v IP 66 v Transparent V Max 12 Mbps v Auto baudrate detection V Digital glitch filtering v No limit in cascading v On board switchable termination v Diagnostic LEDs v M12 connector for measurements Compact PROFIBUS Repeater Y Single channel PROFIBUS repeater
8. EC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual 6 Glossary Address Unique number of a device connected to the network With PROFIBUS this can be 0 to 126 127 is a broadcast address Analyzer Software tool to observe the protocol traffic Combi Analyzers can also inspect the signal quality Other term Bus Monitor Example ProfiTrace Backbone The primary bus cable Most of the time only the control systems ProfiHubs and fiber optic couplers are connected to this cable The field devices are connected behind the ProfiHubs and fiber optic couplers Bit Time Tbit The bit time Tbit is the time which elapses during the transmission of one bit It depends on the baudrate and is calculated as follows Tbit 1 bit baudrate bps Examples 12 Mbps gt Tbit 83 ns 1 5 Mbps gt Tbit 667 ns Busparameters Settings that define the timing behaviour on the bus They are defined in the master Examples Tslot MaxTSDR C Capacitance DGND Digital Ground DIN German Institute for Standardization www din de DP VO DP VO is the basic stage of the PROFIBUS DP communication protocol DP VO devices master and slaves perform the following basic functionalities Cyclic exchange of I O data between controlling and slave devices Device Identifier module and Channel related Diagnosis Parameterization of DP slaves Configuration of DP slaves DP V1 DP V1 is the first stage of exten
9. FO2 has two repeating modes normal default and Robust Repeating In normal mode the bits are transferred directly on the other channel with a minimal delay see delay times in the Technical Data chapter In Robust mode the first byte is checked to verify if the following bits are a real PROFIBUS message If the byte is illegal the message will not be transferred to the other channel This helps network stability in EMC sensitive environments 2 12 Channel Redundancy To use the Redundancy option of the B2FO2 set the rotary switch to the C position This enables the two copper channels 1 and 2 to be one redundant path to another B2FO2 a B2 to a redundant COMbricks or to any other supporting product See Fig 17 for an example ProfiHub B24F02 sr m Zeg THGIBHIE EFORCE Elk EE en gt oe wir 1 m sl o 1 Fe AE Kell e er ous TE 8 8 0 ous we gl p ML b d kb ProhHubB4s F02 lef E i slots IH HU mn mmm mue a aa eem EE Ai W Die 6 H E sl BR 9 V D an 21 8 gp i as i aS DL E TI gy ee BR a HAR ia H e b T AAHH sms MILL gt e bS S ee mmm We aa nm an Ge COMbricks Fig 17 Redundant path between multiple ProfiHubs The telegrams are transferred onto both redundant channels The logic inside the ProfiHub determines which telegram is used to be transferred onto the other channels A message received by a redundant channel is repeated on all other channels except the other red
10. ORWAY AD Elektronikk AS Boks 641 N 1401 SKI Norway Tel 47 64 97 60 60 Fax 47 64 97 60 70 Email kai ade no Internet www ade no POLAND INTEX Sp z o o ul Portowa 4 44 102 GLIWICE Poland Tel 48 32 230 75 16 Fax 48 32 230 75 17 Email intex intex com pl Internet www intex com pl ROMANIA S C SVT Electronics S R L Br ila 7 540331 Tg Mure Romania Tel 40 365 809 305 Fax 40 365 809 305 Email sajgo tibor svt ro Internet www svt ro ProfiHub B2F O2 Plus Manual EN docx SAUDI ARABIA ASM Process Automation Al Zahra Dist Attas st cross section with helmy Kutby St Villa no 25 JEDDAH 21553 Tel 966 2 691 2741 Fax 966 2 682 8943 Email info asmestablishment com Internet www asmestablishment com SINGAPORE Allegro Electronics 236 Serangoon Avenue 3 07 98 550236 Singapore Singapore ISEP S Pte Ltd Blk 3015A 07 12 Ubi Road 1 Singapore 408705 Tel 65 6356 4237 Fax 65 6844 4265 Email stevenkee ise p com Internet www ise p com SLOVAKIA ControlSystem s r o Sturova 4 977 01 BREZNO Tel 421 486115900 Fax 421 486111891 Email jan snopko controlsystem sk Internet www controlsystem sk SOUTH AFRICA IDX ONLINE CC 1 Weaver Street Fourways JOHANNESBURG South Africa Tel 27 11 548 9960 Fax 27 11 465 8890 Email sales idxonline com Internet www idxonline com SPAIN and PORTUGAL LOGITEK S A Ctra de Sant Cugat
11. ProfiHub B2F O2 Plus Manual EN docx PROCENTEG ProfiHub B2FO2 User Manual User Manual ProfiHub B2FO2 Copper and FO DP Redundant Spur and Repeater component 2 Isolated outgoing copper Channels 2 Fiber Optic Channels Transparent for all PROFIBUS DP protocols RS 485 specifications for each channel Cable Redundancy Digital glitch filtering Max 12 Mbps Max 31 devices per channel Max 1200 m spur line length No limit in serial placement No address required Integrated termination facilities Configurable grounding system IP 20 classification Extended temperature range Version 1 0 July 2014 Page 1 40 PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual Safety Guidelines This manual contains notices which you should observe to ensure your own personal safety as well as to protect the product and connected equipment These notices are highlighted in the manual by a warning sign and are marked as follows according to the level of danger D Draws your attention to important information on handling the product a particular part of the documentation or the correct functioning of the product Warning This device and its components may only be used for the applications described in this manual and only in connection with devices or components that comply with PROFIBUS and an RS 485 interface This product can only function correctly and safely if it is transported
12. able Fig 8 Cables with different protection sheaths Version 1 0 July 2014 Page 10 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG 1 8 Status LEDs ProfiHub B2FO2 User Manual The Status LEDs on the ProfiHub are very useful for diagnostics POWER 1 2 Power is not switched on or an internal error READY Power is not switched on or an internal error 3 No communication detected on this channel FO ERROR No problem has been detected Channel RX OK There is no communication detected on this channel Channel ERROR No problem has been detected Blinking 3 Power supply not stable redundant power supply interrupted or an internal failure Trying to detect the transmission speed but has not locked it yet 1 or more devices communicating on this channel Gi Problem in the cabling has been detected 1 or more devices communicating on this channel C3 Problem in the cabling has been detected Power supply OK The transmission speed has been detected C3 Internal error Gi Problem in the cabling has been detected 3 Internal error Gi Problem in the cabling has been detected Termination for this channel is ON INT TERM Termination for this 3 Internal error channel is OFF Version 1 0 July 2014 Page 11 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights re
13. act is open As soon as one of the power supplies fails the contact will close and the Power Indicator LED will blink In the case of an interrupted power supply you can reset the contact by pressing the Reset button The contact will open and the LEDs will stop blinking The maximum power to be connected to the alarm contact is 24 VDC The maximum switching current is 500 mA Version 1 0 July 2014 Page 15 40 ProfiHub B2FO2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual 2 7 Fiber optic backbone Use the FO channels to create a fiber optic backbone to other ProfiHubs with FO channels Connect the DP copper cable from the master or DCS to one of the two copper channels Fig 13 SETTINGS amp powen 1 Ge r carm mer PROCENTEC ProfiHub B2FO 2 Fig 13 PROFIBUS DP backbone connection Pin layout of the screw terminals Pin A Green wire Pin B Red wire Pin I Indirect cable shielding Note Connecting the Indirect cable shielding is not required when the ground clips are used Testing f a channel recognizes valid PROFIBUS messages from one or more connected devices the RX OK LED of the corresponding channel should be blinking Version 1 0 July 2014 Page 16 40 ProfiHub B2FO2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual 2 8 Spur Segmen
14. ax 86 10 84766722 Email info procentec net Internet www procentec net CZECH REPUBLIC FOXON e shop Poln 367 460 01 Liberec 12 Czech Republic Tel 420 484 845 555 Fax 420 484 845 556 Email foxon foxon cz Internet www foxon cz DENMARK ProSaiCon Jernbanegade 23B DK 4000 Roskilde Denmark Tel 45 70 20 52 01 Fax 45 70 20 52 02 Email hfjprosaicon dk Internet www prosaicon dk FINLAND Hantekno Oy Kalliotie 2 FIN 04360 Tuusula Finland Tel 358 40 8222 014 Email info hantekno com Internet www hantekno fi FRANCE AGILICOM B timent B 1 rue de la Briaudi re Z A La Ch taigneraie 37510 BALLAN MIRE France Tel 33 247 76 10 20 Fax 33 247 37 95 54 Email jy bois agilicom fr Internet www agilicom fr Version 1 0 July 2014 GERMANY PROCENTEC GmbH Benzstrasse 15 D 76185 Karlsruhe Germany Tel 49 0 721 831 6630 Fax 49 0 721 831 66329 Email info procentec de Internet www procentec de INDIA U L ELECTRODEVICES P LTD NIRMAN CLASSIC KATRAJ KONDHWA ROAD KATRAJ PUNE 411046 India Tel 91 202 696 0050 Fax 91 202 696 2079 Email dileep miskin ulepl com Internet www ulepl com IRELAND PROFIBUS Ireland Automation Research Centre University of Limerick National Technology Park Plassey LIMERICK Ireland Tel 353 61 202107 or 35361240240 Fax 353 61 202582 Email info profibus ie Internet www profibus ie ISRAEL Instrumetrics
15. ber optic backbone increases network reliability and network overview It is also possible to mix ProfiHubs with COMbricks Version 1 0 July 2014 Page 7 40 ProfiHub B2FO2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual 1 4 Channel Structure Each copper channel is electrically isolated and internally connected to the transparent intelligent backbone The termination is switchable and powered by the ProfiHub The shielding of the PROFIBUS cable can be directly grounded or indirectly grounded see the next paragraph Indirect grounding To direct grounding of other Channels Fig 5 Channel structure 1 5 Grounding System The ProfiHub B2FO2 can be grounded by 3 methods 1 Direct grounding on the Ground Rail 2 Indirect grounding through a capacitor 3 Combination of direct and indirect The power supply must be grounded directly on the Ground Rail The shielding of the PROFIBUS cables can be directly or indirectly grounded If you do not want to ground all or some cables to the common ground i e compensating current the cable shielding must be connected to pin I which stands for Indirect grounding A capacitor with a parallel high value resistor will separate the 2 potentials Fig 5 ensuring protection of the signal against non DC disturbances If by accident on 1 channel the Direct Grounding is connected with the Indirect Grounding the conne
16. ble lengths Cable thickness Wire diameter Wire type Number of devices Termination Redundancy ProfiHub B2F O2 Plus Manual EN docx Version 1 0 July 2014 1200 m at 9 6 kbps to 93 75 kbps 1000 m at 187 5 kbps 400 m at 500 kbps 200 m at 1 5 Mbps 100 m at 3 Mbps to 12 Mbps 10 mm when the ground rail is used lt 2 5 mm Stranded or Solid core Maximum 31 per Channel including ProfiHubs OLMs etc Integrated and switchable Powered according to IEC 61158 390 220 390 Ohms All Channels default on Yes copper channel 1 and 2 Page 22 40 PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual Technical Data ProfiHub B2FO2 Power supply specifications Power source For UL Limited Power Source LPS or NEC Class 2 or CEC Class 2 according to UL 60950 1 regulations Nominal supply voltage 12 to 24 VDC Redundant power supply Yes Current consumption Min 275 mA at 12 V power supply all Channels fully loaded Reverse polarity protection Yes Cable thickness 10 mm when the ground rail is used Wire diameter lt 25mm Alarm contact Voltage Max 24 V DC Current MTBF T b d Version 1 0 July 2014 Page 23 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG 4 Sales offices and Distributors ProfiHub B2FO2 User Manual HEADQUARTERS PROCENTEC Klopperman 16 2292 JD WATERINGEN Nethe
17. ction to the Direct Grounding bypasses the capacitor in the Indirect Ground connection The current on the shield will flow to Direct Ground Version 1 0 July 2014 Page 8 40 ProfiHub B2FO2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROGCENTEG ProfiHub B2FO2 User Manual 1 6 Cable lengths for PROFIBUS DP The copper cables on Channels 1 and 2 must comply with the PROFIBUS DP cable specifications for RS 485 Fig 6 BN 3940 3940 3940 3940 3280 1310 ee us senp Example 1000 m cable per channel at 187 5 kbps TNT SE Maximum 31 devices BR Device E Device Other channels With the same Cable length Fig 6 Cable lengths for PROFIBUS DP Device Version 1 0 July 2014 Page 9 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual 1 7 Cable types for PROFIBUS DP The cable type must comply with the PROFIBUS DP cable specifications for RS 485 Fig 7 Parameter Value Wires 2 twisted 135 165 Ohm at 3 to 20 MHz Capacity lt 30 pF m Fig 7 PROFIBUS DP cable specifications The ProfiHub B2FO2 can handle cables based on multiple protection sheaths with an overall cable diameter between 6 to 12 mm Fig 8 Flexible cable mp 25 y Robust cable Food cable Shipboard cable Trailing cable Festoon cable FRNC c
18. e segments PROFIBUS DP is a high speed communication bus that must comply with strict rules concerning spur lines because of possible reflections that could lead to communication disturbances If spur lines or star segments are required costly investments in repeaters have to be done The innovative ProfiHub B2FO2 is the perfect component for such applications It is an economic solution to realise reliable spur lines in high speed DP networks They have the functionality of 2 galvanic isolated transparent repeaters and an Optical Link Module OLM in one device This allows network structures with extended spur lines that individually can handle a maximum of 31 devices and a length equal to the main bus The ProfiHub B2FO2 refreshes a received message on one Channel and transfers it to all the other Channels chicken foot topology Because the ProfiHub B2FO2 creates isolated segments the devices can now be removed and added during operation Also most electrical bus problems and EMC disturbances in a spur do not spread to the other segments The intelligent logic and isolation circuits of the ProfiHubs do not change the bit width This means the ProfiHubs do not have limitations in serial placement The logic also detects the transmission speed automatically i To assist the installation work termination is integrated and can be switched on off The grounding concept is also selectable direct or capacitive grounding The ProfiHubs are pow
19. ered by a 12 to 24 DC Voltage For troubleshooting maintenance and commissioning the ProfiHubs are equipped with LEDs on the outside which indicate the status of each Channel Data and Error Version 1 0 July 2014 Page 5 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual 1 1 Product Features Gm 2 Galvanic isolated outgoing channels repeater segments gt 2 Fiber Optic channels Transparent for all PROFIBUS DP protocols gt DP RS 485 specifications for each channel Power supply 1 gt Cable redundancy for copper channel 1 2 Power supply 2 gt 9 6 Kbps to 12 Mbps FO Channel 1 and 2 Copper Channel 1 and 2 31 devices per channel Fig 2 ProfiHub connections 3000 m cable length for FO channel 1 and 2 1200 m spur line length for copper channel 1 and 2 depends on transmission speed Redundant power supply No limit in serial placement or cascading of ProfiHubs Alarm contact with manual reset button No address required Integrated termination facilities switches Configurable grounding system direct or capacitive P 20 classification gt Increased temperature range amp m mpm p zm es spem FS e t gt Paco tty PF SOT ATTE Tr Peat El ez Ell en wegl o gx ge LA ge TI T T DP Fiber Optic Backbone 1 IM Each spur
20. ernet www verwertraining com Hi Port Software Limited The Hub 2 Martin Close Lee on Solent Hampshire PO13 8LG Tel 44 0 8452 90 20 30 Fax 44 0 2392 552880 Email sales hiport co uk Internet www hiport co uk iTech Unit 1 Dukes Road Troon Ayrshire KA10 6QR Tel 44 0 1292 311 613 Fax 44 0 1292 311 578 Email sales itech troon co uk Internet www itech troon co uk Parkelect Ltd 84 Dargan Road Belfast BT3 9JU N Ireland Tel 44 2890 777743 Fax 44 2890 777794 Email jgillan parkelect co uk Internet www parkelect co uk Page 25 40 PROCENTEG ProfiHub B2FO2 User Manual UNITED STATES and MEXICO Grid Connect Inc 1630 W Diehl Road Naperville Illinois 60563 USA Tel 1 630 245 1445 Fax 1 630 245 1717 Email sales gridconnect com Internet www gridconnect com procentec html VIETNAM Bavitech Corporation 42 Truong Son Street Ward 2 Tan Binh District Ho Chi Minh City Tel 84 8 3547 0976 Fax 84 8 3547 0977 Email hai hoang bavitech com Internet www bavitech com Version 1 0 July 2014 Page 26 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual 5 Order codes Component Order code Remarks ProfiHub B2FO2 With Alarm contact With redundant power input ProfiHub B2FO2 Version 1 0 July 2014 Page 27 40 ProfiHub B2F O2 Plus Manual EN docx PROCENT
21. esesese siae sesesese sse eser sa ese esses enses 13 2 2 Hoemton eene Rhen neemer eren mememer isis esesesese sese eres sese eser esee se eser sensere rans 13 2 3 Jules IN NER 13 2 4 gore REr 14 2 5 Grounding of the Dower nennen menn nnne nnn nnne nnne nnns na n nnne n nnn n ans 15 2 6 FAN FST CONAC geen WEE EE 15 2 1 Fiber optic backbone cccccccscccescecseeecseecceeceucecausecsueecaeessueeceessueeceueeseueeseeeesaeeseasesseeess 16 2 8 SEET 17 2 9 E inge MENTI 18 2 10 ESdudrate e NEEN 19 2 11 Robust Repeating mode uk 20 2 12 Channel Kedundoarey uiis votre De aniio aAa R Genitivo Ga dud ana do eege gd 20 3 Technical Data ProfiHub B2FO2 NNN NEEN NNN 21 4 Sales offices and Distributors leeeeeeeeeeeeeeeeene nnne nnn nnnm nene nnne hern NEEN ENEE 24 5 Iar CodeS ERREUR 27 6 GIOS SIY TR 28 7 Sr uud reci NETS 31 8 eege MT 34 9 VIS wl ce IEN 35 10 NOS not ce 36 Version 1 0 July 2014 Page 4 40 ProfiHub B2FO2 User Manual ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual 1 Product Description ProfiHub B2FO2 is an advanced flexible and robust network component for PROFIBUS DP installations to create fiber optic backbone structures and long multi device star tre
22. example lt 2 13 potes oc NT a Gowen Tie H RS L3 SA e loti PNEU t Fig 9 Rubber studs on backside of housing Version 1 0 July 2014 Page 13 40 ProfiHub B2FO2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROGCENTEG ProfiHub B2FO2 User Manual 2 4 Power Supply The two 2 pin screw type power connectors are located on the left of the ProfiHub B2FO2 Fig 10 1 left 2 right Fig 10 Power connectors and LEDs Both power connectors are linked 1 on 1 to the internal power supply of the B2FO2 If one power supply fails the other takes over without delay time When redundancy is not required it is sufficient to use one power connector Please note that when using only one power supply a voltage of max 0 25 V will exist on the other unconnected power connector like shown in Fig 11 If only one power supply is used the alarm contact is closed If two power sources are connected the contact is open As soon as one of the power supplies fails the contact will close and the Power Indicator LED will blink mus oum t 1 POW 1 POW 2 POW 1 POW 2 Fig 11 Maximum voltage on unconnected Power Connector The power supply must comply with the following specifications Limited Power Source LPS or NEC Class 2 or CEC Class 2 Voltage 12 24 VDC Current min 275 mA Wire diameter lt 2 5 mm Procedure To connect the 24V supply to the 2 pin
23. ichleitung Version 1 0 July 2014 Page 29 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG Stub line Tbit Termination Topology PI PNO Drop cable Reflection ProfiHub B2FO2 User Manual See Spur line See Bit Time A powered resistor network at both ends of a segment to prevent reflections with PROFIBUS DP the termination must be powered In a communications network the pattern of interconnection between network nodes e g bus ring star configuration PROFIBUS International The International PROFIBUS Organization based in Karlsruhe PROFIBUS Nutzer Organization The German PROFIBUS Organization based in Karlsruhe See Spur line Part of the original signal that is transmitted back along the cable It corrupts the original signal Version 1 0 July 2014 Page 30 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROGCENTEG ProfiHub B2FO2 User Manual 7 Certificates QualityMasters eU ISO Certificering QualityMasters hereby declares that Procentec B V Wateringen i has a management system that meets the requirements of the standard ki NEN EN ISO 9001 2008 WH for the scope Providing training courses technical support product development and the exploitation of the best laboratory Date of original approva 10 02 2003 Date of issue 10 04 7013 Valid until
24. ine Wiring problems do not spread to can be 200m x En at 1 5 Mbps other spur lines Fig 3 Long spur lines to instruments and the possibility to remove insert them during operation Short circuit protection on each spur line is automatically provided Version 1 0 July 2014 Page 6 40 ProfiHub B2FO2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual 1 2 Application areas Create Fiber Optic backbones Dynamic spur lines to actuators flow meters and pH analyzers Removable drives and motors Pull Plug motor control centers drawers Roof mounted devices in tank farms Barrier for non galvanic isolated equipment Networks with requirement for High Availability uptime Large star tree structured networks VV VV VV ON WV 1 3 Additional Benefits Hot slave insertion and removal during operation Short circuit protection on each Channel Option to create a redundant path to other supporting Hubs or COMbricks Compact and robust construction Status and error display per Channel Suitable for all DP cables Conveniently arranged networks Easy extendable installations On board DB9 female connector on each channel for maintenance activities Cost Savings VV VV VV VV ON ON ProftiHub B2 FO2 rs ts j s t 3 E gu our 9 e 2 At Ba ededi ww T w C e EA P PE D s Ba o a B TE p li Fig 4 Creating a fi
25. product standards A Hub refreshes a signal and passes the information on to all nodes which are connected to the Hub Data frames which were received on one port are transferred to all the other ports chicken foot topology Multiple Protocol Interface Protocol defined by Siemens which uses the layer 1 and 2 of PROFIBUS FDL Printed Circuit Board Acronym for PROFIBUS for Decentralized Peripherals Specification of an open fieldbus system with the following characteristics Polling master slave system cyclic communications MSO Flying masters with robin round token passing coordination MM Connection based MS1 and connectionless MS2 MS3 acyclic communication between masters and slaves Options e g Data exchange broadcast DXB i e slave to slaves communication Isochronous mode of slaves Clock synchronization Redundancy PROFIBUS DP is standardized within IEC 61158 and IEC 61784 communication profile families 3 1 and 3 2 The term PROFIBUS DP also is a synonym for the RS485 based deployments within factory automation Active physical layer device that receives and retransmits all signals over a different port to increase the distance and number of devices for which signals can be correctly transferred for a given medium A cable attached to a bus segment with a T connection Spurs are not recommended with PROFIBUS DP They are prohibited with 12 Mbps and PROFIsafe operations German term is St
26. rlands Tel 31 0 174 671800 Fax 31 0 174 671801 Email info procentec com Internet www procentec com ARGENTINA eFALCOM Alcorta 2411 B1744 Moreno Buenos Aires ARGENTINA Tel 54 237 46 31 151 Fax 54 237 46 31 150 Email santiago falcomer efalcom com Internet www efalcom com ar AUSTRALIA IS Systems Pty Limited 14 Laverick Ave Tomago NSW Australia 2322 Tel 61 2 4964 8548 Fax 61 2 4964 8877 Email fritz woller issystems com au Internet www issystems com au Pentair Flow Control Pacific Unit 4 57 Pine Road Yennora NSW Australia 2161 Tel 61 2 9612 2323 Fax 61 2 9612 2324 Email rkoeniq typac com au Internet www profibuscentre com au BELGIUM and LUXEMBOURG Bintz Technics N V Brixtonlaan 25 1930 ZAVENTEM Belgium Tel 32 2 720 49 16 Fax 32 2 720 37 50 Email bloemen bintz be Internet www bintz be BRAZIL Westcon Instrument Indl Ltda Rual Alvaro Rodrigues 257 Sao Paulo SP Brazil CEP 04582 000 Tel 55 11 5561 7488 Fax 55 11 5093 2592 Email paolo wii com br Internet www wll com br ProfiHub B2F O2 Plus Manual EN docx CHILE RP Ingenieria Limitada Tucapel 92 oficina 52 Concepci n Chile Tel 56 0 41 2469350 Fax 56 0 41 2522592 Email rodrigopinto rpingenieria cl Internet www rpingenieria cl CHINA PROCENTEC Beijing Room E 1115 WangJingYuan YouLeHui ChaoYang Beijing CHINA Tel 86 10 84766911 or 84787311 F
27. screw type terminal proceed as follows Strip the insulation from the cable or the conductors for the 24V power supply Add cable crimp terminals wire ferrules to the conductors Secure the crimp terminals in the screw type terminal To connect the power supply you need a 3 mm screwdriver Version 1 0 July 2014 Page 14 40 ProfiHub B2FO2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCGCENTEG ProfiHub B2FO2 User Manual Testing If the power is switched on it can be diagnosed by the following indicators LEDs should be blinking in a circular animation for a short time The POWER LED of the respective power connector 1 2 or both is ON The READY LED is ON or Blinking depending on baud rate lock 2 5 Grounding of the power D It is recommended to use a power supply with a ground lead 3 wire Connect the ground lead of the power lead to the Ground Rail of the ProfiHub B2FO2 Connect the Ground Rail to the common ground with a separate ground lead See Fig 12 for an example Fig 12 Connection to Ground Rail 2 6 Alarm contact The ProfiHub B2FO2 features a potential free relay contact This alarm contact can be used to monitor the power supplies Example applications are Connect a LED tower alarm buzzer SMS server or use it as a digital signal for the PLC If only one power supply is used the alarm contact is closed If two power sources are connected the cont
28. served PROCENTEG ProfiHub B2FO2 User Manual 1 9 Comparison table BENE ProfiHub B5 ProfiHub B2 ProfiHub B2FO2 Redundant power NO Yes supply Temperature range 20 to 60 Celsius 25 to 70 Celsius 25 to 70 Celsius 4 to 140 Fahrenheit 13 to 158 Fahrenheit 13 to 158 Fahrenheit PROFIBUS connectors Screw terminals and Screw terminals and DB9 ST BFOC screw DB9 connectors connectors terminals and DB9 connectors Version 1 0 July 2014 Page 12 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual 2 Installation Instructions ProfiHub B2FO2 2 1 Location The ProfiHub B2FO2 can be installed everywhere in a non hazardous area that complies with IP 20 DIN 40 050 and the specified temperature range of 25 to 70 Celsius or 13 to 158 Fahrenheit 2 2 Position The ProfiHub B2FO2 can be installed in every position but it is recommended to install it with the cables pointing down In this position it is also easier to read the status LEDs 2 3 Mounting The ProfiHub B2FO2 can be mounted on 35 mm DIN rail with a minimum width of 130 mm Mounting brackets are available for mounting the B2FO2 directly on a wall The supplied rubber studs need to be placed on the back of the housing of the ProfiHub B2FO2 for extra fixation This is to prevent the product to potentially slide off the DIN rail See Fig 9 for an
29. sion of PROFIBUS DP after DP VO DP V1 devices shall comply with the following features Device related diagnosis is replaced by status and alarms The first three octets of the user parameterization data are now standardized Optionally these devices may support Acyclic communication MS1 MS2 f alarms are used MS1 shall be supported Version 1 0 July 2014 Page 28 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG DP V2 Electromagnetic Compatibility EMC Hub MPI PCB PROFIBUS DP Repeater Spur line ProfiHub B2FO2 User Manual DP V2 is the second stage of extension of PROFIBUS DP after DP V1 DP V2 devices shall comply with the following features Data Exchange Broadcast DxB for slave to slave communication publisher subscriber principle lsochronous Mode time tick synchronized operating slaves e g drives Up and or download of Load Region Data domains Clock Control synchronization within slaves and Time Stamping Redundancy See EMC The extent to which an electric or electronic device will tolerate electrical interference from other equipment immunity and will interfere with other equipment Within the European Community as well as in other countries it is regulated by law that electric and electronic components and equipment comply with basic standards such as IEC 61000 6 2 or IEC 61326 or corresponding individual
30. stored set up installed operated and maintained as recommended Qualified Technicians Only qualified technicians should be allowed to install and work with this equipment Qualified technicians are defined as persons who are authorized to commission to ground to tag circuits and systems in accordance with established safety practices and standards It is recommended that the technicians carry a Certified PROFIBUS Installer or Certified PROFIBUS Engineer certificate Disclaimer of Liability We have checked the contents of this manual as much as possible Since deviations cannot be precluded entirely we cannot guarantee full agreement However the content in this manual is reviewed regularly and any necessary corrections included in subsequent editions Suggestions for improvement are welcomed Copyright 2014 PROCENTEC All rights reserved No part of this publication may be reproduced stored in a retrieval system or transmitted in any form or by any means electronic mechanical photocopying recording or otherwise without the prior written permission of the publisher PROCENTEC Tel 31 0 174 671800 Klopperman 16 Fax 31 0 174 671801 2292 JD WATERINGEN Email info procentec com The Netherlands Web www procentec com Version 1 0 July 2014 Page 2 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual Important Information Purpose of
31. the Manual This manual explains how to put the ProfiHub B2FO2 into operation Recycling and Disposal The parts of the ProfiHub can be recycled For further information about environment friendly recycling and the procedure for disposing your old equipment please contact PROCENTEC Klopperman 16 2292 JD WATERINGEN The Netherlands Tel 31 0 174 671800 Fax 31 0 174 671801 Email info procentec com Document Updates You can obtain constantly updated information on PROCENTEC products on the Internet at www procentec com You can also contact PROCENTEC Customer Support by phone at 31 0 174 671800 by fax at 31 0 174 671801 by email at support procentec com Version 1 0 July 2014 Page 3 40 ProfiHub B2F O2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG Contents 1 Product RT OM MOERS OP 5 1 1 Product Features EEN 6 1 2 Applicaton are dS erroni ERA E A ERAAN AERE T 1 3 Additional Benefits ccccccccecececececccececececececucucucucucucucecueeeceaeauauauauauaeaeneneaeneneneneneneneneeenens T 1 4 Silke fl EEN 8 1 5 Grounding SYSTE EE 8 1 6 Cable lengths for PROFIBUS DP atari Eo aiaa aN RAAE anth ani eg eege 9 17 Cable types for PROFIBUS D 10 1 8 EUR AR REENEN 11 1 9 edere MI eT TTE 12 2 Installation Instructions ProfiHub B2FO2 leeeeeeeeeeerennnnnennn nnnm nnne nnn nnne ner n nnne nan 13 Locatnon mem ememe e nene erre ememer isis es
32. ts Connect the spur segments to the connectors of Channel 1 to 5 Fig 14 The second method is to place a PROFIBUS standardized plug on the DB9 connector of the specific Channel PIRIOLFL DOE Fig 14 PROFIBUS DP spur connectors Pin layout of the screw terminals Pin A Green wire Pin B Red wire Pin I Indirect cable shielding for reducing EMC and noise in demanding areas Note Connecting the Indirect cable shielding is not required when the ground clips are used Testing f a Channel recognizes valid PROFIBUS messages from one or more connected devices the RX OK LED of the Channel should be blinking Version 1 0 July 2014 Page 17 40 ProfiHub B2FO2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual 2 9 Termination The termination of the Channels have been set to ON by default because it is assumed that the new segment is started at the ProfiHub Fig 15 aam RESET PROCENTEC ProfiHub B2FO2 The termination LED of the correspondina Channel is activated when the termination switch is set to Fig 15 Termination Switches D When the DB9 connector is used and the cable starts at the ProfiHub it is recommended to use the termination on the DB9 plug and NOT the ProfiHub This way the connector can be removed while maintaining termination on the bus Version 1 0 July 2014 Page 18 40 ProfiHub B2FO2 Plus Manual
33. undant channel A message received by a normal channel is repeated on all other channels When one redundant cable breaks the other cable ensures safe delivery of the telegram In this event the built in alarm contact will close The red ERROR LED will blink with an interval of 100ms When the redundant path is fixed press the ALARM RESET pushbutton to reset the alarm ATTENTION Using the ProfiHub B2FO2 in Redundancy mode causes a delay in processing the telegrams When used together with COMbricks in redundancy mode it is required to increase the default MinTSDR in the PLC bus parameters slightly Recommended is to increase the MinTSDR with a value according to the delay time table in the Technical Data chapter Version 1 0 July 2014 Page 20 40 ProfiHub B2FO2 Plus Manual EN docx PROCENTEC 2014 Copyright all rights reserved PROCENTEG ProfiHub B2FO2 User Manual 3 Technical Data ProfiHub B2FO2 Technical Data ProfiHub B2FO2 Dimensions and weight Dimensions L x W x H mm with screws 128 x 111 x 38 mm Weight 375 gr Ambient conditions 25 to 70 Celsius 13 to 158 Fahrenheit Operating temperature Isolation class IP 20 DIN 40 050 Protocol specifications Supported Protocols DP VO DP V1 DP V2 FDL MPI FMS PROFIsafe PROFIdrive and any other FDL based protocol Transmission speed 9 6 kbps to 12 Mbps including 45 45 kbps Transmission speed detection Auto detect default or