Home

Chapt1 IntroRef Man (Exp.)

image

Contents

1. pns o oo Figure 7 6 Three back to back 12 cycle waveform captures of a V sag 56 1999 Square D Company All Rights Reserved HIGH SPEED EVENT LOG ENTRIES Chapter 7 Disturbance Monitoring Note Whenever the 12 cycle waveform capture is configured for two or more back to back waveform captures a set of waveform captures can be triggered manually with POWERLOGIC application software However to retrieve the set the retrieve existing onboard 12 cycle waveform capture option should be used Event log entries 1 and 2 are detailed below and illustrated in figure 7 7 Event Log Entry 1 For high speed events the value stored in the event log at the end of the pickup delay is the furthest excursion from normal during the pickup delay period t1 This is calculated using 16 data point rms calculations Event Log Entry 2 The value stored in the event log at the end of the dropout delay is the furthest excursion from normal during both periods t1 and t2 from the start of the pickup delay to the end of the dropout delay The time stamps for the pickup and dropout reflect the actual duration of these periods Dropout Threshold Pickup Threshold eg Event Log i Entry 1 Value Event Log lt 5 Entry 2 Value Pickup Dropout Delay Delay Figure 7 7 High speed event log entries 1999 Square D Company All Rights Reserved 57 Chapter 8 C
2. ssus 44 Automatic Event Capture Initiated by a Standard Setpoint 46 Extended Event Capture Storage eee seen 47 Circuit monitor models CM 2250 and CM 2350 are equipped with waveform capture Circuit monitors use a sophisticated high speed sampling technique to sample 64 times per cycle simultaneously on all current and voltage inputs There are two ways to initiate a waveform capture Manually from a remote personal computer using POWERLOGIC application software Automatically by the circuit monitor when an alarm condition such as Alarm 55 Over value THD voltage Phase A B occurs Both methods are described below Using POWERLOGIC application software you can initiate a manual waveform capture from a remote personal computer To initiate a manual waveform capture select a circuit monitor equipped with waveform capture and issue the acquire command The circuit monitor captures the waveform and the software retrieves and displays it POWERLOGIC software lets you view all phase voltage and current wave forms simultaneously or zoom in on a single waveform that includes a data block with extensive harmonic data For instructions on performing manual waveform capture using POWERLOGIC software refer to the application software instruction bulletin The circuit monitor can detect over 100 alarm conditions such as metering setpoint exceeded and status input changes see Chapt
3. etcetera tatit titt deseen te tbe g rase eese Power factor register format aee tie teretes tiir td bete Ee tete Pa iri dno baee ee eve Default VAR Sign conven ton utem eut ue oett teta bedient Optional VAR sign convention Pulse demand metering example Summary of circuit monitor instrumentation ssas i eene eene ai 3 Class 3020 circuit MONTO Se oiii beue etre Erde EMG RITU SERE FR URE SSH EX tant RUINIS IRSE SACRA LER URS ORAE 3 Circuit monitor feature comparisOn ates TUE RE ee ti teb ener te rhe tede rie cb eerie da 3 Circuit monitor model numbers o tr tk tre PRINS e e xe eb ra leere ec een a e uae ebe te eee teen doavetnds 4 Memory upgrade kit part numbers 5 eniascet nte stestki ttti sette tert tne ta tinea bee de heck Series 2000 circuit monitor memory options Real time readings d e Ratio Ee EE DUE e rei dtd did deitatis Demand readings E lure lc M 14 Power analysis values eiie ient rere rect eeietrect itte ede eb Ke Ka Ea E aiats ensaia eb ebrei 16 Input Output Modules enceinte ttr rnbentt ettet etie ba cbe nea sisia teri ini se tbe oi Ede veil 17 Valuesst red in maintenance log eene eene nicae med 40 Circuit monitor electromagnetic phenomena measurement capability sss 51 Multiple 12 cycle waveform Capt te e een rrt tiene in ee rie Drei 54 CM 2350 and
4. 3 4 3 wire pulse train 3930 xAnaloe Dutp L examples nnn tb onantidieniei enciende dii detecte eeces 30 4 Sampl eventlop cny ode enne eo enit atiende deren 32 4 2 How the circuit monitor handles setpoint driven alarms sess 32 6 31 Flowchart illustrating automatic waveform capture sse ene eene 42 6 2 Status input 2 connected to external high speed relay sss 45 1999 Square D Company All Rights Reserved iii Bulletin No 3020IM9806 February 1999 6 3 7 1 7 2 7 3 7 4 7 5 7 6 7 7 9 1 9 2 9 3 9 4 9 5 TABLES 1 1 1 2 1 3 1 4 1 5 1 6 2 1 2 2 2 3 2 4 3 1 5 1 7 1 7 2 7 3 7 4 9 1 12 cycle event capture example initiated from a high speed input 82 sess 46 A fault near plant D that is cleared by the utility circuit breaker can still affect plants A B and C resulting in a voltage sag sse enne nennen Voltage sag caused by a remote fault and lasting 5 cycles sssssssssssseeeee POWERLOGIC System Manager SMS 3000 Onboard Data Storage dialog box POWERLOGIC System Manager SMS 770 Onboard Data Storage setup dialog box 60 cycle extended event capture displayed in SMS 3000 s sirena a innnan Three back to back 12 cycle waveform captures of a V44 sag sse eee High speed event log entries eroe e ODE o a ER te ride io a EE Dieter rete Memory allocation example CM 2350
5. The maximum allowable interval between pulses is 60 minutes Normal Demand Mode External Synch Pulse Demand Timing Billing Meter Billing Meter Demand Timing Demand Timing Utility Meter Synch Pulse Circuit Monitor Circuit Monitor Demand Timing Demand Timing Slaved to Master Figure 3 1 Demand synch pulse timing 1999 Square D Company All Rights Reserved 19 Bulletin No 3020IM9806 February 1999 ANALOG INPUTS 20 The circuit monitor supports analog inputs through the use of optional input output modules I O module IOM 4411 offers one analog input I O module IOM 4444 offers four analog inputs Table 3 1 on page 17 lists the available input output modules This section describes the circuit monitor s analog input capabilities For technical specifications and instructions on installing the modules refer to the appropriate instruction bulletin see list on page 6 of the Circuit Monitor Installation and Operation Bulletin Each analog input can accept either a 0 5 Vdc voltage input or a 4 20 mA dc current input By default the analog inputs accept a 0 5 Vdc input To change an analog input to accept a 4 20 mA signal the user must connect a jumper wire to the appropriate terminals on the input module The jumper wire places a calibrated 250 ohm resistor located inside the I O module into the circuit When a 4 20 mA current is run through the resistor the circuit monitor measures an input volta
6. Automatic Event Capture High Speed Trigger Automatic Extended Capture Initiated by a Standard Setpoint Extended Event Capture DLOfap aiii datio inui Ou open red tere niis CHAPTER 7 DISTURBANCE MONITORING Introduction Description Ope rata Onn e Multiple Waveform Setup sss SMS 3000 SMS 1500 or PMX 1500 5MS 770 5M 700 EXP 550 or EXP 500 5 5 1 eii cis een escena en te coe ekaiak aee bac e Doe Ye NU NONE EEG 54 Sag Swell Atia 55 Multiple Wavetorni Retrieval uite nee a tete St are ER EG Efe seit 56 SMS 3000 SMS 1500 or PMX 1500 essen eene nn nnne tnnt tnter inneren neni 56 SMS 770 SMS 700 EXP 550 or EXP 500 esee nennen ennt nnne tnter ennt nennen 56 High Speed Event Log Entries Je ouai OE EERCO R a Ea a E A 57 CHAPTER 8 CM 2450 CM 2452 WITH PROGRAMMING LANGUAGE ee eeereee eene n anneau 59 Introductionis c rne a EOD ERN ER ede REGN eI E NEN eevee ees 59 Descriptions iso aaa ped dpi tees etie cee eid 59 Application EXamples ue een A E EAE E eye UL R etse autores 60 Developer s Kit E 60 CHAPTER 9 ADVANGED TOPICS 21i da cts cock ananas scura enun cons EE eye a c Ck nano De CEPR A RSS io DR wu Eceh 61 The Command Interface ne eerte rte Eme detiene p EO eS
7. 0 010 to 1 000 to 0 010 Power Factor Displacement 3 Phase Total 0 010 to 1 000 to 0 010 Per Phase D 0 010 to 1 000 to 0 010 Frequency 50 60 Hz 23 00 to 67 00 Hz 400 Hz 350 00 to 450 00 Hz Temperature Internal Ambient 100 00 C to 100 00 C Via communications only 1999 Square D Company All Rights Reserved 9 Bulletin No 3020IM9806 February 1999 Min Max Values Power Factor Min Max Conventions The circuit monitor stores minimum and maximum values for all real time readings in nonvolatile memory In addition the circuit monitor except model CM 2050 stores the date and time associated with each minimum and each maximum Minimums and maximums for front panel values can be viewed on the circuit monitor s LED display All min max values including those not displayable from the front panel can be reset from the circuit monitor s front panel See Resetting Demand Energy and Min Max Values in Chapter 4 of the Circuit Monitor Installation and Operation Bulletin for reset instructions Using POWERLOGIC application software you can e View all min max values and their associated dates and times Upload min max values and their associated dates and times from the circuit monitor and save them to disk e Reset all min max values For instructions on viewing saving and resetting min max data using POWERLOGIC software refer to the instruction bulletin included with
8. 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 Reg No 4053 4054 4055 4056 4057 4058 4059 4060 4061 4062 4063 Phase A Current 4064 4065 4066 4067 4068 4069 4070 4071 4072 4073 4074 4075 4076 4077 4078 4079 4080 4081 4082 4083 4084 4085 4086 4087 4088 4089 4090 4091 4092 4093 4094 4095 4096 4097 4098 4099 4100 4101 4102 4103 4104 4105 4106 4107 Description H26 Va angle defined as 0 0 for H26 reference H27 magnitude as a percent of H1 magnitude H27 Va angle defined as 0 0 for H27 reference H28 magnitude as a percent of H1 magnitude H28 Va angle defined as 0 0 for H28 reference H29 magnitude as a percent of H1 magnitude H29 Va angle defined as 0 0 for H29 reference H30 magnitude as a percent of H1 magnitude H30 Va angle defined as 0 0 for H30 reference H31 magnitude as a percent of H1 magnitude H31 Va angle defined as 0 0 for H31 reference Reserved H1 magnitude as a percent of H1 magnitude H1 angle with reference to H1 Va angle H2 magnitude as a percent of H1 magnitude H2 angle with reference to H2 Va angle H3 magnitude as a percent of H1 magnitude H3 angle with reference to H3 Va angle H4 magnitude as a percent of H1 magnitude H4 angle with reference to H4 Va angle H5 magnitude as a percent of H1 magnitude H5 angle with reference to H5 Va angle H6 magnitude as a percent of H1 magnit
9. Alarm Type Alarm Description H Over Lagging Average P F Under Power J Over Reverse Power K Phase Reversal L Status Input Transitions Off to On M Status Input Transitions On to Off N End Of Interval Update Cycle O Power Up Reset P Over Analog 122 1999 Square D Company All Rights Reserved Alarm Operation The Over lagging 3 phase Average P F will occur when the test register is less leading than the pickup setpoint and remains less leading for the pickup delay period When the value becomes less lagging than the dropout setpoint and remains less lagging for the dropout delay the alarm will dropout If a leading P F is selected for the pickup setpoint that is a positive P F then the alarm will be active for any lagging P F or for any leading P F between the pickup setpoint and unity Pickup and Dropout setpoints can be positive or negative delays are in seconds Enter setpoints as integer values representing power factor in thousandths For example to define a dropout setpoint of 0 5 enter 500 Note This alarm condition is based on the average power factor over the last demand interval not instantaneous power factor The Under power alarm will occur when the test register s absolute value is below the pickup setpoint and remains below the pickup setpoint long enough to satisfy the pickup delay period When the absolute value rises above the dropout setpoint and remains above the setpoint long enough to
10. Chapter 9 Advanced Topics your specified offset time Incremental energy accumulation will then continue in this manner until the configuration is changed or a new interval is started by a remote master To set up incremental energy 1 Write a start date and offset time to registers 1863 1865 2 Write the desired interval length from 0 1440 minutes to register 2076 If incremental energy will be controlled from a remote master such as a programmable controller write a value of zero here To start a new incremental energy interval from a remote master E Write command code 6910 to register 7700 The circuit monitor can be configured to use one of three demand power calculation methods thermal demand circuit monitor default external pulse synchronized demand block interval demand with rolling subinterval block rolling For a description of the demand power calculation methods see Demand Power Calculation Methods in Chapter 2 The thermal demand method is the default To set up the circuit monitor for thermal demand simply define the demand interval See Setting the De mand Interval in Chapter 4 of the Circuit Monitor Installation and Operation Bulletin for instructions To change to the block rolling demand method the user must write to the command interface over the communications link For a description of the command interface and a list of command codes see The Command Inter face in this chapter
11. THD Total Harmonic Distortion THD is a quick measure of the total distortion present in a waveform It provides a general indication of the quality of a waveform The circuit monitor uses the following equation to calculate THD JH Hj H T eves H thd An alternate method for calculating Total Harmonic Distortion used widely in Europe The circuit monitor uses the following equation to calcu late thd THD x 100 JH Hj Hj Tasse Total rms thd x 100 K Factor K Factor is a simple numerical rating used to specify transformers for nonlinear loads The circuit monitor uses the following formula to calculate K Factor SUM L h D rms K 1999 Square D Company All Rights Reserved 15 Bulletin No 3020IM9806 February 1999 POWER ANALYSIS VALUES Displacement Power Factor For purely sinusoidal loads the power factor Cont calculation kW kVA is equal to the cosine of the angle between the current and voltage waveforms For harmonically distorted loads the true power factor equals kW kVA but this may not equal the angle between the fundamental components of current and voltage The displacement power factor is based on the angle between the fundamental components of current and voltage Harmonic Values The individual per phase harmonic magnitudes and angles through the 31st harmonic are determined for all currents and volt ages in model numbers 2350 and higher circuit mo
12. To change to the block rolling method complete the following steps 1 Write command code 5311 to register 7700 2 Write command code 1110 to command interface register 7700 This resets the circuit monitor causing it to recognize the new demand calculation method 3 Write a subinterval value in minutes into register 2078 If the subinterval is set equal to the demand interval the demand calculation will update once each demand interval block mode If the subinterval equals zero the demand calculation will update every 15 seconds sliding window 1999 Square D Company All Rights Reserved 75 Bulletin No 3020IM9806 February 1999 SETTING UP A DEMAND SYNCH PULSE INPUT CONTROLLING THE DEMAND INTERVAL OVER The external pulse synchronized demand method allows a circuit monitor equipped with an I O module to accept a demand synch pulse from another demand meter When this method is used the circuit monitor watches input S1 for a pulse that signals the start of a new demand interval This allows the circuit monitor s demand interval window to match the other meter s demand interval window For a detailed description of this feature see Demand Synch Pulse Input in Chapter 3 To set up the circuit monitor to accept a demand synch pulse input Set the demand interval to 0 from the circuit monitor front panel See Setting the Demand Interval in Chapter 4 of the Circuit Monitor Installa tion and Operation
13. kWH and kVARH Waveform amp event captures are stored in non volatile memory in the CM 2350 and CM 2450 The exact number of waveforms and event captures that can be stored depends on how much memory is allocated to event amp data logs G The standard CM 2150 2250 2350 and 2450 can store up to 51 200 values 100K amp The CM 2350 and CM 2450 can store up to 20 waveform captures or 8 twelve cycle event captures The standard CM 2452 can store over 180 000 values 356K including up to 60 waveform captures or 29 twelve cycle event captures Each power factor value occupies one register Power factor values are stored using signed magnitude notation see figure 9 2 Bit number 16 the sign bit indicates leading lagging A positive value bit 16 0 always indicates leading A negative value bit 16 1 always indicates lagging Bits 1 9 store a value in the range 0 1000 decimal For example the circuit monitor would return a leading power factor of 0 5 as 500 Divide by 1000 to get a power factor in the range 0 to 1 000 16 15 14 13 12 11 109 8 7 6 5 4 3 2 1 0 0 0 0 0 0 m aam cC EE a Sign Bit Unused Bits Power Factor O Leading Set to 0 in the range 1 1000 decimal 1 Lagging Figure 9 2 Power factor register format 1999 Square D Company All Rights Reserved 71 Bulletin No 3020IM9806 February 1999 CHANGING THE VAR SIGN CONVENTION When the power factor is lagging the circuit mon
14. kWH kVArH or kVAH Pulse Register Units kWH Pulse or kVArH Pulse or kVAH Pulse In 10ths None None Seconds kWH Pulse or kVArH Pulse or kVAH Pulse In 10ths None None Seconds kWH Pulse or kVArH Pulse or kVAH Pulse In 10ths None None Seconds kWH Pulse or kVArH Pulse or kVAH Pulse In 10ths Range 0 to 32 767 Alpha Numeric 4 Chars 2 Regs 0 to 9 0 to 32 767 0 to 32 767 Alpha Numeric 4 Chars 2 Regs 0 to 9 0 to 32 767 0 to 32 767 Alpha Numeric 4 Chars 2 Regs 0 to 9 0 to 32 767 0 to 32 767 Appendix B Abbreviated Register Listing Description This register specifies the KWH kVArH or kVAH per pulse for the KYZ output when in those modes Label for relay R1 Relay R1 Mode Register 0 Normal 1 Latched 2 Timed 3 Absolute kWH pulse 4 Absolute kVArH pulse 5 kVAH pulse 6 kWH in pulse 7 kVarH in pulse 8 kWH out pulse 9 kVArH out pulse This register specifies the time relay R1 is to remain closed for timed mode This register specifies the KWH kVArH or kVAH per pulse for relay R1 when in those modes Label for relay R2 Relay R2 Mode Register 02 Normal 1 Latched 2 Timed 3 Absolute kWH pulse 4 Absolute kVArH pulse 5 kVAH pulse 6 kWH in pulse 7 kVarH in pulse 8 kWH out pulse 9 kVArH out pulse This register specifies the time relay R2 is to remain closed for timed mode This register specifies the KWH kVArH o
15. 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 10 000 0 to 10 000 0 to 10 000 0 to 10 000 0 to 10 000 0 to 10 000 0 to 10 000 0 to 32 767 0 to 3 599 0 to 32 767 0 to 3 599 0 to 32 767 0 to 3 599 0 to 32 767 0 to 3 599 0 to 32 767 0 to 3 599 0 to 32 767 0 to 3 599 0 to 32 767 0 to 3 599 0 to 32 767 0 to 3 599 0 to 32 767 0 to 3 599 0 to 32 767 0 to 3 599 0 to 32 767 0 to 3 599 0 to 32 767 0 to 32 767 85 Bulletin No 3020IM9806 February 1999 Reg No Description 1102 1103 1104 1105 1106 1107 1108 1109 1110 1111 1112 1113 1114 1115 1117 Phase C Fundamental Real Power 3 Phase Total Fundamental Real Power Phase A Fundamental Reactive Power Phase B Fundamental Reactive Power Phase C Fundamental Reactive Power 3 Phase Total Fundamental Reactive Power Harmonic Factor Phase A Harmonic Factor Phase B Harmonic Factor Phase C Harmonic Factor 3 Phase Total Harmonic Power Phase A Harmonic Power Phase B Harmonic Power Phase C Harmonic Power 3 Phase Total Phase Rotation 0 Normal A B C 1 C B A ANALOG INPUT PRESENT VALUE REGISTERS 1191 1192 1193 1194 Analog Input 1 None 32767 to 32767 Present Value Analog Input 2 None 32767 to 32767 Present Value Analog Input 3 None 32767 to 32767 Present Value Analog Input 4 None 32767 to 32767 Present Value REAL TIME METERED VALUES MINIMUM 1200 1201 1202 1203 1204 1205
16. 1206 1207 1208 1209 1210 1211 1212 1213 1214 1215 1216 1217 1218 1219 1220 1221 Minimum Update Interval Minimum Freq Minimum Temp Minimum Current Phase A Minimum Current Phase B Minimum Current Phase C Minimum Current Neutral 14 Minimum Current Ground 15 Minimum Current 3 Phase Average Minimum Current Apparent rms Minimum Current Unbalance Phase A Minimum Current Unbalance Phase B Minimum Current Unbalance Phase C Minimum Current Unbalance Worst Minimum Volt Phase A to B Minimum Volt Phase B to C Minimum Volt Phase C to A Minimum Volt L L 3 Phase Average Minimum Volt Phase A to Neutral Minimum Volt Phase B to Neutral Minimum Volt Phase C to Neutral Minimum Volt L N 3 Phase Average 86 1999 Square D Company All Rights Reserved Units Range KW Scale Factor E 0 to 32 767 KW Scale Factor E 0 to 32 767 KW Scale Factor E 0 to 32 767 KW Scale Factor E 0 to 32 767 KW Scale Factor E 0 to 32 767 KW Scale Factor E 0 to 32 767 in 10ths 0 to 1000 in 10ths 0 to 1000 in 10ths 0 to 1000 in 10ths 0 to 1000 KW Scale Factor E 0 to 32 767 KW Scale Factor E 0 to 32 767 KW Scale Factor E 0 to 32 767 KW Scale Factor E 0 to 32 767 none 0 to 1 The present scaled value of analog input 1 The present scaled value of analog input 2 The present scaled value of analog input 3 The present scaled value of analog input 4 In 1000ths of a second Hertz Scale Factor F 0 to
17. 2251 2253 The definitions for registers 2251 2253 are the same as for 2230 2232 except that they apply to generic demand value 8 2254 2256 The definitions for registers 2254 2256 are the same as for 2230 2232 except that they apply to generic demand value 9 2257 2259 The definitions for registers 2257 2259 are the same as for 2230 2232 except that they apply to generic demand value 10 2260 2262 The definitions for registers 2260 2262 are the same as for 2230 2232 except that they apply to generic demand value 11 2263 2265 The definitions for registers 2263 2265 are the same as for 2230 2232 except that they apply to generic demand value 12 2266 2268 The definitions for registers 2266 2268 are the same as for 2230 2232 except that they apply to generic demand value 13 2269 2271 The definitions for registers 2269 2271 are the same as for 2230 2232 except that they apply to generic demand value 14 2272 2274 The definitions for registers 2272 2274 are the same as for 2230 2232 except that they apply to generic demand value 15 2275 2277 The definitions for registers 2275 2277 are the same as for 2230 2232 except that they apply to generic demand value 16 2278 2280 The definitions for registers 2278 2280 are the same as for 2230 2232 except that they apply to generic demand value 17 2281 2283 The definitions for registers 2281 2283 are the same as for 2230 2232 except that they apply to generic de
18. 60 10 128 1999 Square D Company All Rights Reserved Pulse counting example 78 Pulse demand metering via status input 78 R Reading and writing registers from the front panel 125 Readings demand 12 energy 14 real time 9 Real time readings 9 Register listing 83 analog input configuration analog input max 89 analog input min 86 analog input present value 86 analog output configuration 102 circuit monitor utility 104 CM configuration values 96 date time compressed 91 date time expanded 92 demand values 90 energy values 89 KYZ and relay outputs 94 neutral current 112 phase A current 107 phase A voltage 106 phase B current 109 phase B voltage 108 phase C current 111 phase C voltage 110 real time metered values maximum 88 real time metered values minimum 86 sag swell event 101 103 status input pulse demand metering 104 status inputs 93 Register listings spectral components 106 Registers reading and writing from front panel 125 Related documents 7 Relay setpoint controlled functions 33 Relay de energizinga 64 Relay energizinga 64 Relay output operating modes 22 Relay overriding an output 65 Relay releasing an overridden 65 Relay setting up for CM internal control Releasing and overridden relay 65 65 S Safety precautions 5 6 Sag swell alarms 55 Scaling alarm setpoints 117 Setpoint controlled relay functions 25 Setpoint controlled relay functions 33 Setting scale factors for exte
19. Day Month Yr Regs 700 705 The date and time in registers 700 705 are stored as follows Other dates and times through register 795 are stored in an identical manner Seconds Reg 700 0 59 Minutes Reg 701 0 59 Hours Reg 702 0 23 Day Reg 703 1 31 Month Reg 704 1 12 Year Reg 705 1900 2099 The date and time are mapped from CM Registers 1800 1802 Reg No Description 700 705 Last Restart Date Time 706 711 Date Time Demand of Peak Current Phase A 92 1999 Square D Company All Rights Reserved Units Sec Min Hour Day Month Yr Sec Min Hour Day Month Yr Range See above Same as Regs 700 705 Reg No Description 712 717 Date Time Demand of Peak Current Phase B 718 723 Date Time Demand of Peak Current Phase C 724 729 Date Time of Peak Demand Average Real Power 730 735 Date Time of Last Reset of Peak Demand Current 736 741 Date Time of last Min Max Clear of Instantaneous Values 742 747 Date Time of Last Write to Circuit Tracker Setpoint Register 748 753 Date Time when Peak Demand was Last Cleared 754 759 Date Time when Accumulated Energy was Last Cleared 760 765 Date Time when Control Power Failed Last 766 771 Date Time When Level 1 Energy Mgmt Setpt Alarm Period was Last Entered 772 777 Date Time When Level 2 Energy Mgmt Setpt Alarm Period was Last Entered 778 783 Date Time When Level 3 Energy Mgmt
20. Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No 201 202 203 204 205 206 207 208 209 210 211 212 213 214 1 ce 1000 0 10 11 12 13 14 15 16 17 18 19 20 21 22 23 23 25 26 27 28 29 30 81 32 33 34 35 36 37 38 39 40 41 Reg No Description 5821 5822 5823 5824 5825 5826 5827 5828 5829 5830 5831 5832 5833 5834 5835 5836 5837 5838 5839 5840 5841 5842 5843 5844 5845 5846 5847 5848 5849 5850 5851 5852 5853 5854 5855 5856 5857 5858 5859 5860 5861 5862 5863 5864 5865 5866 5867 5868 5869 5870 5871 5872 5873 5874 5875 1999 Square D Company All Rights Reserved Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Eve
21. Last Current B Swell Extreme Value Last Current B Swell Event Duration Last Current C Swell Extreme Value Last Current C Swell Event Duration Last Current N Swell Extreme Value Last Current N Swell Event Duration Units Scale Factor D Cycles Volts Scale Factor D Cycles Volts Scale Factor D Cycles Amps Scale Factor A Cycles Amps Scale Factor A Cycles Amps Scale Factor A Cycles Amps Scale Factor B Cycles 1999 Square D Company All Rights Reserved 0 32767 1 99999999 0 32767 1 99999999 0 32767 1 99999999 0 32767 1 99999999 0 32767 1 99999999 0 32767 1 99999999 0 32767 1 99999999 Range Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Description Voltage A swell extreme value Voltage A swell event duration Voltage B swell extreme value Voltage B swell event duration Voltage C swell extreme value Voltage C swell event duration Current A swell extreme value Current A swell event duration Current B swell extreme value Current B swell event duration Current C swell extreme value Current C swell event duration Current N swell extreme value Current N swell event durati
22. Register Reading Output Current 50 kW 4 mA 100 kW 4 mA 200 kW 8 mA 250 kW 10 mA 500 kW 20 mA 550 kW 20 mA Current output Current 20 MA raaa Minimum output Current 4 mA Real Power 3 Total from register 1042 100 kW 500 kW Lower Upper Limit Limit Figure 3 5 Analog output example 1999 Square D Company All Rights Reserved Chapter 4 Alarm Functions CHAPTER 4 ALARM FUNCTIONS SETPOINT DRIVEN ALARMS The circuit monitor models CM 2150 and higher can detect over 100 alarm conditions including over under conditions status input changes phase unbalance conditions and more See Alarm Conditions and Alarm Codes in Appendix D for a complete list of alarm conditions The circuit monitor maintains a counter for each alarm to keep track of the total number of occurrences These alarm conditions are tools that enable the circuit monitor to execute tasks automatically Using POWERLOGIC application software each alarm condition can be assigned one or more of the following tasks Force data log entries in up to 14 user defined data log files see Data Logging in Chapter 5 Operate one or more mechanical relays see Mechanical Relay Outputs in Chapter 3 Perform a 4 cycle waveform capture see 4 Cycle Waveform Capture in Chapter 6 Perform a 12 cycle waveform capture see Extended Event Capture in Chapter 6 Many of the alarm conditions includ
23. Sample event log entry Max2 Pickup Setpoint Dropout Setpoint Pickup Delay EV1 Circuit monitor records the date time that the pickup setpoint and time delay were satisfied and the maxi mum value reached Max1 during the pickup delay period AT Also the circuit monitor performs any tasks waveform capture 12 cycle event capture forced data log entries relay output operations assigned to the event EV2 Circuit monitor records the date time that the dropout setpoint and time delay were satisfied and the maximum value reached Max2 during the alarm period Figure 4 2 How the circuit monitor handles setpoint driven alarms 32 1999 Square D Company All Rights Reserved SETPOINT CONTROLLED RELAY FUNCTIONS Chapter 4 Alarm Functions A circuit monitor model CM 2150 or higher equipped with an I O module can mimic the functions of certain motor management devices such as phase loss undervoltage or reverse phase relays While the circuit monitor is not a primary protective device it can detect abnormal conditions and respond by operating one or more Form C output contacts These outputs can be used to operate an alarm horn or bell to annunciate the alarm condition Note The circuit monitor is not designed for use as a primary protective relay While its setpoint controlled functions may be acceptable for certain applications it should not be considered a substitute for
24. Some registers in this section apply only to circuit monitors with firmware version 17 009 or higher To determine a circuit monitor s firmware version from the front panel see Viewing Configuration Data In Protected Mode in Chapter 4 of the Circuit Monitor Installation and Operation Bulletin Step 3 tells how to determine the firmware version To determine the firmware version over comms follow these steps 1 Read register 2094 The two digits on the left in the 4 digit decimal value represent the reset code revision the two digits on the right represent the circuit monitor firmware version 2 Read register 2093 The decimal value represents the circuit monitor firmware sub revision level as in firmware version 16 001 1999 Square D Company All Rights Reserved 83 Bulletin No 3020IM9806 February 1999 Reg No Description Units Range 1000 Update Interval In 1000ths of a second 0 to 10 000 1001 Frequency Hertz Scale Factor F 2300 to 6700 50 60 3500 to 4500 400 1002 Temperature inside CM enclosure Degrees C in 100ths 10 000 to 10 000 1003 Current Phase A Amps Scale Factor A 0 to 32 767 1004 Current Phase B Amps Scale Factor A 0 to 32 767 1005 Current Phase C Amps Scale Factor A 0 to 32 767 1006 Current Neutral Amps Scale Factor B 0 to 32 767 1007 Current Ground Amps Scale Factor C 0 to 32 767 1008 Current 3 Phase Average Amps Scale Factor A 0 to 32 767 1009 Current Apparent rms Amps Scale Factor A
25. The alarm requires no pickup or dropout setpoints or delays The alarm will dropout when the status input changes back to on from off The pickup and dropout setpoints and delays do not apply The End of Interval alarms mark the end of an interval or update cycle The pickup and dropout setpoints and delays do not apply The Power Up Reset alarm marks any time the circuit monitor powers up or resets The pickup and dropout setpoints and delays do not apply The Over Analog alarms will occur whenever the test register value is more positive than the pickup setpoint or less negative and remains greater than the pickup long enough to satisfy the pickup delay When the value becomes less positive than the dropout setpoint or more negative and remains below the setpoint long enough to satisfy the dropout delay the alarm will dropout Pickup and Dropout setpoints can be positive or negative delays are in seconds AlarmType Alarm Description Q Under Analog R Voltage Current Swell S Voltage Current Sag T Suspended Sag Swell Appendix D Alarm Setup Information Alarm Operation The Under Analog alarms will occur whenever the test register value is less positive than the pickup setpoint or more negative and remains less than the pickup long enough to satisfy the pickup delay When the becomes more positive than the dropout setpoint or less negative and remains above the setpoint long enough to satisfy the dropout delay the a
26. e These transitions are alternate contact closures or flip flops of a Form C contact e In figure 3 4 the transitions are marked as 1 2 3 and 4 Each transition represents the time when the relay flip flops from KY to KZ or from KZ to KY At points 1 2 3 and 4 the receiver should count a pulse e na3 wire application the circuit monitor can deliver up to 10 pulses per second 2S oo amp NA lt Figure 3 3 2 wire pulse train uj iJ d J J N Qo A Figure 3 4 3 wire pulse train 1999 Square D Company All Rights Reserved 27 Bulletin No 3020IM9806 February 1999 Calculating the Watthour Per Pulse Value This section shows an example of how to calculate the watthour per pulse value To calculate this value first determine the highest kW value you can expect and the required pulse rate In this example the following assump tions are made e The metered load should not exceed 1500 kW The KYZ pulses should come in at about two pulses per second at full scale Step 1 Translate 1500 kW load into kWH second 1500 kW 1 Hr 1500 kWH 1500 kWH X KWH 1 hour 1 second 1500 KWH X kWH 3600 seconds 1 second X 1500 3600 0 4167 kWH second Step 2 Calculate the kWH required per pulse 0 4167 KWH second 0 2084 kWH pulse 2 pulses second Step 3 Round to nearest tenth since the circuit monitor only accepts 0 1 kWH incr
27. test register rises above the dropout setpoint long enough to satisfy the dropout delay period the alarm will dropout Pickup and Dropout setpoints are positive delays are in seconds The unbalance current alarm will occur when the percentage of the smallest phase current divided by the largest phase current is below the percentage pickup value and remains at or below the pickup value long enough to satisfy the specified pickup delay in seconds When the percentage of the smallest phase current divided by the largest phase current remains above the dropout value for the specified dropout delay period the alarm will dropout Pickup and Dropout setpoints are positive delays are in seconds The Phase Loss Voltage alarm will occur when any one or two phase voltages but not all fall to the pickup value and remain at or below the pickup value long enough to satisfy the specified pickup delay When all of the phases remain at or above the dropout value for the dropout delay period or when all of the phases drop below the specified phase loss pickup value the alarm will dropout Pickup and Dropout setpoints are positive delays are in seconds The Lagging Power Factor alarm will occur when the test register value becomes more lagging than the pickup setpoint i e closer to 0 010 and remains more lagging long enough to satisfy the pickup delay period When the value becomes equal to or less lagging than the dropout setpoint i e closer to 1 0
28. 0 1 O processing incomplete 1 processing complete Register 2036 shows the number of metering update cycles remaining before the next harmonic data update begins 2036 0 60 Number of metering update cycles remaining before the next update 1999 Square D Company All Rights Reserved 77 Bulletin No 3020IM9806 February 1999 STATUS INPUT PULSE DEMAND METERING Pulse Counting Example When equipped with an I O module the circuit monitor can count pulses from an external source such as a watthour meter equipped with a pulse initiator This allows the circuit monitor to keep track of demand information by counting pulses The circuit monitor provides ten input pulse demand channels see figure 9 5 Each channel maintains pulse count data taken from one or more status inputs assigned to that channel For each channel the circuit monitor main tains the following information Present Interval Pulse Count the number of pulses counted so far during the present interval Last Completed Interval Pulse Count the number of pulses counted during the last completed interval Peak Interval Pulse Count the maximum number of pulses counted during a completed interval since the last power demand reset Date Time of Peak the date and time of the peak interval pulse count described above since the last power demand reset For each channel utility registers are provided which can be defined by custom application softw
29. 100 Scale Group E kWattmeter kVarmeter kVA 3 scale by 001 2 scale by 0 01 1 scale by 0 10 O scale by 1 00 default 1 scale by 10 0 2 scale by 100 3 scale by 1000 4 scale by 10 000 5 scale by 100 000 Scale Group F Frequency Determined by CM 2 scale by 0 01 50 60 1 scale by 0 10 400 Front panel energy display can be configured for various resolutions max value illustrated for each selection Write a 0 999999 kilo 10 999999 kilo 11 99999 9 kilo 12 9999 99 kilo 13 999 999 kilo 20 999999 mega 21 99999 9 mega 22 9999 99 mega 23 999 999 mega Description None 0 to 9998 None 0 to 9998 None 0 to 9998 or 32 768 None 0 to F Hex None 0 to 17 Hex Full Access Front Panel Reset Password Limited Front Panel Reset Password When set to 32 768 the Configuration password is used to access Resets Limited Front Panel Reset Disable Bit Mask A 1 Disable Bit 1 Disable Demand Amps Reset Capability Bit 2 Disable Demand Power Reset Capability Bit 3 Disable Energy Reset Capability Bit 4 Disable Min Max Reset Capability Sag Swell Suspend Status A1 means condition exists Bit 1 Set if any other bit is set Bit 2 Sag Swell disabled Bit 3 CPML feature disabled Bit 4 Sag Swell Suspended Temporarily Bit 5 Sag Swell Suspended Permanently 1999 Square D Company All Rights Reserved 97 Bulletin No 3020IM9806 February 1999 Reg No Name Units 2040 2041 CM Label None
30. 108 Under Analog Input Channel 2 1192 Integer Value Q 109 Under Analog Input Channel 3 1193 Integer Value Q 110 Under Analog Input Channel 4 1194 Integer Value Q 111 120 Reserved 201 Voltage Swell A N A B Volts D R 202 Voltage Swell B N Volts D R 203 Voltage Swell C N C B Volts D R 204 Current Swell Phase A Amps A R 205 Current Swell Phase B Amps A R 206 Current Swell Phase C Amps A R 207 Current Swell Neutral Amps B R 208 Voltage Sag A N A B Volts D S 209 Voltage Sag B N Volts D S 210 Voltage Sag C N C B Volts D S 211 Current Sag Phase A Amps A S 212 Current Sag Phase B Amps A S 213 Current Sag Phase C Amps A S 214 Current Sag Neutral Amps B S 120 1999 Square D Company All Rights Reserved ALARM TYPE DEFINITIONS Alarm Type Alarm Description A Over Value Alarm B Under Value Alarm C Phase Loss Current D Phase Loss Voltage E Lagging P F F Leading P F G Over Power Demand Appendix D Alarm Setup Information Alarm Operation If the test register value exceeds the setpoint long enough to satisfy the pickup delay period the alarm condition will be true When the value in the test register falls below the dropout setpoint long enough to satisfy the dropout delay period the alarm will dropout Pickup and Dropout setpoints are positive delays are in seconds If the test register value is below the setpoint long enough to satisfy the pickup delay period the alarm condition will be true When the value in the
31. 1999 Square D Company All Rights Reserved 35 Bulletin No 3020IM9806 February 1999 Setpoint Controlled Relay Functions cont If all of the phase voltages are equal to or below the pickup setpoint during the pickup delay the phase loss alarm will not activate This is considered an under voltage condition It should be handled by configur ing the under voltage protective functions To release any relays that are in latched mode enter the circuit monitor s Alarm mode and select the Clear option For detailed instructions see Clearing the Priority 1 Log in Chapter 4 of the Circuit Monitor Installation and Operation Bulletin Reverse Power Pickup and dropout setpoints are entered in kilowatts Very large values may require scale factors Refer to Setting Scale Factors for Extended Metering Ranges in Chapter 9 for more information on scale factors The reverse power alarm occurs when the 3 phase power flow in the negative direction remains at or below the negative pickup value for the specified pickup delay in seconds When the reverse power alarm occurs the circuit monitor operates any specified relays Relays configured for normal mode operation remain closed until the reverse power alarm clears The alarm clears when the 3 phase power reading remains above the dropout setpoint for the specified dropout delay in seconds To release any relays that are in latched mode enter the circuit monitor s Alarm mode and s
32. 200 values Model CM 2452 stores up to 182 272 values With the 512k memory option models CM 2150 2250 2350 and 2450 store up to 313 344 values with the 1024k memory option models CM 2150 2250 2350 and 2450 store up to 575 488 values These numbers assume that you ve devoted all of the circuit monitor s logging memory to data logging and the series number of the circuit monitor is G4 or later Each defined data log file stores a date and time and requires some additional overhead To minimize storage space occupied by dates times and file overhead use a few log files that log many values as opposed to many log files that store only a few values each See Memory Allocation in Chapter 9 for additional storage considerations 1999 Square D Company All Rights Reserved 39 Bulletin No 3020IM9806 February 1999 MAINTENANCE LOG The circuit monitor stores a maintenance log in nonvolatile memory This log contains several values that are useful for maintenance purposes Table 5 1 below lists the values stored in the maintenance log and a short description of each The values stored in the maintenance log are cumulative over the life of the circuit monitor and cannot be reset You can view the maintenance log using POWERLOGIC application soft ware For specific instructions refer to the POWERLOGIC software instruc tion bulletin Table 5 1 Values Stored in Maintenance Log Value Stored Description
33. 2452 was factory equipped with 100K of memory and a 256K memory expansion card for a total of 356K of memory The 256K card can be removed and replaced with a 512K or 1024K expansion card for total memory of either 612K or 1124K The memory upgrade kit can be installed in Series G4 models CM 2150 and higher Memory upgrade kits are available with either the 512k or 1024k memory card see table 1 5 No special tools are required for installation Table 1 5 Memory Upgrade Kit Part Numbers Part Number Description 3020 CM MEM 512K 512K Memory Upgrade Kit for Series 2000 Circuit Monitors 3020 CM MEM 1024K 1024K Memory Upgrade Kit for Series 2000 Circuit Monitors Memory Options Summary Table 1 6 summarizes the memory options now available for Series 2000 Circuit Monitors To obtain price and availability on circuit monitors with expanded memory and circuit monitor memory upgrade kits contact your local sales representative Table 1 6 Series 2000 Circuit Monitor Memory Options Total Memory Capacity Model Number Series G3 or Earlier Series G4 or Later Standard 512K Expansion 1024K Expansion Standard 512K Expansion 1024K Expansion CM 2050 N A N A N A N A N A N A CM 2150 11K N A N A 100K 612K 1124K CM 2250 11K N A N A 100K 612K 1124K CM 2350 100K 612K 1124K 100K 612K 1124K CM 2450 100K 612K 1124K 100K 612K 1124K CM 2452 356K 612K 1124K Obsolete CM 2
34. 32 767 0 to 1000 0 to 1000 0 to 1000 0 to 1000 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 1000 0 to 1000 0 to 1000 0 to 1000 0 to 1000 0 to 1000 0 to 1000 0 to 1000 100 to 1000 to 100 100 to 1000 to 100 100 to 1000 to 100 100 to 1000 to 100 100 to 1000 to 100 100 to 1000 to 100 100 to 1000 to 100 100 to 1000 to 100 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 432 767 0 to 432 767 0 to 432 767 0 to 432 767 0 to 32 767 0 to 32 767 Appendix B Abbreviated Register Listing Reg No Description Units Range 1453 Maximum THD Phase C Current in 10ths 0 to 32 767 1454 Maximum THD Neutral Current in 10ths 0 to 10 000 1455 Maximum THD Phase A Voltage in 10ths 0 to 32 767 1456 Maximum THD Phase B Voltage in 10ths 0 to 32 767 1457 Maximum THD Phase C Voltage in 10ths 0 to 32 767 1458 Maximum THD A B Voltage in 10ths 0 to 32 767 1459 Maximum THD B C Voltage in 10ths 0 to 32 767 1460 Maximum THD C A Voltage in 10ths 0 to 32 767 1471 Maximum K Factor Phase A In 10ths 0 to 10 000 1472 Maximum K Factor Phase B In 10ths 0 to 10 000 1473 Maximum K Factor Phase C In 10ths 0 to 10 000 ANALOG INPUT MAX REGISTER 1591 Analog Input 1 None 32767 to 32767 Maximum Value 1592 Analog Input 2
35. 999 999 999 999 VAH Reactive Signed Absolute 0 to 9 999 999 999 999 999 VARH 999 999 MWh 000 000 kVAR to 000 000 MVARh Real In 0 to 9 999 999 999 999 999 WHR Real Out 0 to 9 999 999 999 999 999 WHR Reactive In 0 to 9 999 999 999 999 999 VARH Reactive Out 0 to 9 999 999 999 999 999 VARH Apparent 0 to 9 999 999 999 999 999 VAH Accumulated Energy Conditional Real In 0 to 9 999 999 999 999 999 WHR Real Out 0 to 9 999 999 999 999 999 WHR Not Not Reactive In 0 to 9 999 999 999 999 999 VARH Applicable Applicable Via communications only You can configure the resolution to display energy on the front panel or allow it to auto range default See Appendix B register 2027 page 97 14 1999 Square D Company All Rights Reserved GENERIC DEMAND CONT POWER ANALYSIS VALUES Chapter 2 Metering Capabilities The circuit monitor can accumulate these energy values in one of two modes signed or unsigned absolute In signed mode the circuit monitor considers the direction of power flow allowing the accumulated energy magnitude to both increase and decrease In unsigned mode the circuit monitor accumulates energy as positive regardless of the direction of power flow in other words the energy value increases even during reverse power flow The default accumulation mode is unsigned Accumulated energy can be viewed from the front panel display The resolution of the energy value will automatically
36. Abbreviated register listing 83 Advanced topics 61 76 Alarm conditions and numbers 118 setup information 117 type definitions 121 Alarm conditions and alarm numbers 118 Alarm Functions 31 Alarm setpoints scaling 117 118 Alarm setup 117 Alarm type definitions 121 Alarms sag swell 55 Setpoint driven 31 Alternate VAR sign convention 11 Analog inputs 20 Analog outputs 29 Block rolling command changing the 75 C CAB 102 CAB 104 81 CAB 107 81 CAB 108 81 Calculating log file sizes 115 CC 100 81 Changing the VAR sign convention 72 Circuit monitor configuration values 96 description 1 electromagnetic phenomena measurement 51 feature comparison 3 4 5 instrumentation 3 types 3 utility registers 104 waveform capture setting up for 42 CM 2452 application examples 60 Command codes 62 Command interface 61 control 73 Command interface control 73 Command interface operating relays using the 64 Index Communication cable pinouts 81 Communications link controlling demand interval 76 Conditional energy 73 D Data logging 38 alarm driven entries 38 organized files 38 storage considerations 39 Date and time setting using command interface 69 De energizing a relay 64 Default VAR sign convention 11 Demand calculation method changing the 75 Demand interval over the comms link controlling 76 Demand readings genericdemand 14 peak demand 13 predicted demand 13 voltage demand 14 Demand synch pul
37. B 1073 K Factor Phase C 1074 Crest Factor Phase A 1075 Crest Factor Phase B 1076 Crest Factor Phase C 1077 Crest Factor Neutral 1078 1079 1080 1081 1082 1083 1084 1085 1086 1087 1088 1089 1090 1091 1092 1093 1094 1095 1096 1097 1098 1099 1100 1101 Phase B Fundamental Real Power 1999 Square D Company All Rights Reserved Appendix B Abbreviated Register Listing Units in 10ths 96 in 10ths 96 in 10ths 96 in 10ths 96 in 10ths 96 in 10ths 96 in 10ths 96 in 10ths 96 in 10ths 96 in 10ths 96 in 10ths 96 in 10ths 96 in 10ths 96 in 10ths 96 in 10ths 96 in 10ths 96 in 10ths 96 in 10ths 96 in 10ths 96 in 10ths In 10ths In 10ths In 10ths In 100ths In 100ths In 100ths In 100ths Amps Scale Factor A In 10ths of degrees Amps Scale Factor A In 10ths of degrees Amps Scale Factor A In 10ths of degrees Amps Scale Factor B In 10ths of degrees Amps Scale Factor C In 10ths of degrees Volts Scale Factor D In 10ths of degrees Volts Scale Factor D In 10ths of degrees Volts Scale Factor D In 10ths of degrees Volts Scale Factor D In 10ths of degrees Volts Scale Factor D In 10ths of degrees Volts Scale Factor D In 10ths of degrees KW Scale Factor E KW Scale Factor E Range 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767
38. Bulletin Unbalance Voltage 34 1999 Square D Company All Rights Reserved Pickup and dropout setpoints are entered in tenths of percent based on the percentage difference between each phase voltage with respect to the aver age of all phase voltages For example enter an unbalance of 16 0 as 160 Setpoint Controlled Relay Functions cont Chapter 4 Alarm Functions The unbalance voltage alarm occurs when the phase voltage deviates from the average of the phase voltages by the percentage pickup setpoint for the specified pickup delay in seconds When the unbalance voltage alarm occurs the circuit monitor operates any specified relays Relays configured for normal mode operation remain closed until the unbalance voltage alarm clears The unbalance voltage alarm clears when the percentage difference between the phase voltage and the average of all phases remains below the dropout setpoint for the specified dropout delay in seconds To release any relays that are in latched mode enter the circuit monitor s Alarm mode and select the Clear option For detailed instructions see Clearing the Priority 1 Log in Chapter 4 of the Circuit Monitor Installation and Operation Bulletin Phase Loss Current Pickup and dropout setpoints are entered in tenths of percent based ona percentage ratio of the smallest current to the largest current For ex ample enter 50 as 500 The phase loss current alarm occurs wh
39. Bulletin for instructions on setting the demand interval using the circuit monitor s front panel OR Using application software write a value of zero to register 2077 the demand interval configuration register Using application software write command code 5311 to register 7700 to select block demand mode Using application software write command code 5320 to register 7700 to set the external synch source to S1 The circuit monitor s demand interval can be controlled over the communications link For example a programmable controller can signal the start of each new demand interval The circuit monitor s command interface is used to control the demand interval over the communications link For a description of the command interface and a list of command codes see The Command Interface in this chapter To set demand control to the command interface Using application software write a value of zero to register 2077 the demand interval configuration register Using application software write command code 5311 to register 7700 to select block demand mode Using application software write command code 5321 to register 7700 To start a new demand interval THE COMMUNICATIONS LINK i 2 3 E 76 1999 Square D Company All Rights Reserved Write command code 5910 to register 7700 SETTING UP INDIVIDUAL HARMONIC CALCULATIONS Chapter 9 Advanced Topics Circuit monitor models 2350 and higher
40. CM 2450 12 cycle waveform capture memory allocation sese 55 CM 2452 12 cycle waveform capture memory allocation Memory configuration example sierici ini ren ceti asii saeit 1999 Square D Company All Rights Reserved Chapter 1 Introduction CHAPTER 1 INTRODUCTION CHAPTER CONTENTS WHAT IS THE CIRCUIT MONITOR This chapter offers a general description of the circuit monitor describes important safety precautions tells how to best use this bulletin and lists related documents Topics are discussed in the following order What is the Circuit Monitor 0 0 ccccsseccesesseeseseseeseeeececesssssssnessesesescsnsneseecenensnans 1 Expanded MEMOY aries anen ritieni thease ai eee enda veio Ion 3 Requirements for Using rente neret oe eerte i etr geret 4 Identifying the Series and Firmware Revisions sss 4 Model IN mberts intret reete et rrr D o e dte rides aerae 4 Upgrading Existing Circuit Monitors sssssesssseeeeee 5 Memory Options Summary ccccscrsesseersressercesscenssssessenenenenesenssnenensenesensiees 5 Satety PrecautiOns idc ee denm tel eee erm pd 6 Using This Bulletin ent tite eret eee EE tete tees atte 6 Notational Conventions ccrte ro tpe EEEIEE 6 Topics Not Covered Hete cenonongan 7 Related DDOCHmIeDts oem aer rar pet ebrei sa oni omaes cartina 7 Fax On Demand eee eere prete nesini ere spe EUH 7 Installation and Operation Bulleti
41. Energy Reactive Accumulated Energy Apparent Bidirectional Readings Power Analysis Values Demand Readings Demand Current per phase present peak Demand Voltage per phase present peak Average Power Factor 3G total Demand Real Power 36 total Demand Reactive Power 3 total Crest Factor per phase K Factor Demand per phase Displacement Power Factor per phase 32 Fundamental Voltages per phase Fundamental Currents per phase Fundamental Real Power per phase Fundamental Reactive Power per phase Harmonic Power Unbalance current and voltage Phase Rotation Demand Apparent Power 3 total Coincident Readings Predicted Demands Harmonic Magnitudes amp Angles per phase Available via communications only Table 1 2 Class 3020 Circuit Monitors Type Description CM 2050 Instrumentation 1 accuracy CM 2150 Instrumentation 0 296 accuracy data logging alarm relay functions CM 2250 Waveform capture plus CM 2150 features CM 2350 Instrumentation waveform capture 0 2 accuracy CM 2450 Programmable for custom applications plus 2350 features Table 1 3 Circuit Monitor Feature Comparison Feature CM 2050 CM 2150 CM 2250 CM 2350 CM 2450 Full Instrumentation x x x x x RS 485 Comm Port x x x x x Front Panel Optical Comm Port x x x x x 1 Accuracy C
42. No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 105 Bulletin No 3020IM9806 February 1999 SPECTRAL COMPONENTS Reg No Phase A Voltage Description Units Note Registers 4000 4447 apply to circuit monitor models CM 2350 and higher only 4000 4001 4002 4003 4004 4005 4006 4007 4008 4009 4010 4011 4012 4013 4014 4015 4016 4017 4018 4019 4020 4021 4022 4023 4024 4025 4026 4027 4028 4029 4030 4031 4032 4033 4034 4035 4036 4037 4038 4039 4040 4041 4042 4043 4044 4045 4046 4047 4048 4049 4050 4051 4052 Reserved H1 magnitude as a percent of H1 magnitude H1 Va angle defined as 0 0 for H1 reference H2 magnitude as a percent of H1 magnitude H2 Va angle defined as 0 0 for H2 reference H3 magnitude as a percent of H1 magnitude H3 Va angle defined as 0 0 for H3 reference H4 magnitude as a percent of H1 magnitude H4 Va angle defined as 0 0 for H4 reference H5 magnitude as a percent of H1 magnitude H5 Va angle defined as 0 0 for H5 reference H6 magnitude as a percent of H1 magnitude H6 Va angle defined as 0 0 for
43. Number of Demand Resets Number of times demand values have been reset Number of Energy Resets Number of times energy values have been reset Number of Min Max Resets Number of times min max values have been reset Number of Output Operations Number of times relay output has operated This value is stored for each relay output Number of Power Losses Number of times circuit monitor has lost control power Number of Firmware Downloads Number of times new firmware has been downloaded to the circuit monitor over communications Number of Optical Comms Sessions Number of times the front panel optical communications port has been used Highest Temperature Monitored Highest temperature reached inside the circuit monitor Lowest Temperature Monitored Lowest temperature reached inside the circuit monitor 40 1999 Square D Company All Rights Reserved Chapter 6 Waveform Capture CHAPTER 6 WAVEFORM CAPTURE CHAPTER CONTENTS 4 CYCLE WAVEFORM CAPTURE Manual Waveform Capture Automatic Waveform Capture 4 Cycle Waveform Capture erar febres eene el esee pee rti e beg ione 41 Manual Waveform Capture sisi ressaire Ren 41 Automatic Waveform Capture sss 41 Wavetortn StOra ge uoo cepto cepi HO HERR o eid 43 Extended Event Captute ieeeter ier rne trennt ee HR ea rbi repe de 44 Manual Event Capture erect n ied erento E 44 Automatic Event Capture High Speed Trigger
44. Phase C 1012 Tenths A 12 Phase Loss Current 2122 Tenths 96 C 13 Over Voltage Phase A 1018 Volts D A 14 Over Voltage Phase B 1019 Volts D A 15 Over Voltage Phase C 1020 Volts D A 118 1999 Square D Company All Rights Reserved Alarm_No Alarm Description Test Register 16 Over Voltage Phase A B 1014 17 Over Voltage Phase B C 1015 18 Over Voltage Phase C A 1016 19 Under Voltage Phase A 1018 20 Under Voltage Phase B 1019 21 Under Voltage Phase C 1020 22 Under Voltage Phase A B 1014 23 Under Voltage Phase B C 1015 24 Under Voltage Phase C A 1016 25 Voltage Unbalance A 1026 26 Voltage Unbalance B 1027 27 Voltage Unbalance C 1028 28 Voltage Unbalance A B 1022 29 Voltage Unbalance B C 1023 30 Voltage Unbalance C A 1024 31 Voltage Loss Loss of A B or C but not all 2122 32 Over kVA 3 Phase Total 1050 33 Over KW Into the Load 3 Phase Total 1042 34 Over KW Out of the Load 3 Phase Total 1042 35 Over kVAR Into the Load 3 Phase Total 1046 36 Over kVAR Out of the Load 3 Phase Total 1046 37 Over Current Demand Phase A 1701 38 Over Current Demand Phase B 1702 39 Over Current Demand Phase C 1703 40 Over Current Demand 3 phase Total 1700 41 Over Frequency 1001 42 Under Frequency 1001 43 Lagging True Power Factor 1034 44 Leading True Power Factor 1034 45 Lagging Displacement Power Factor 1038 46 Leading Displacement Power Factor 1038 47 Suspended Sag Swell 48 Reserved 49 Over Value THD Current Phase A 1051 50 Over Value THD Cur
45. RE REGERE HERE ISES cannes 18 Demand Synch Pulse Input ttr ner reet retirees 19 Periodic M P9 20 Analog Input Example eee Pte egeret nee rente 21 Relay Output Operating Modes eei inueni 22 Mechanical Relay Outputs enne ttr ine errare intet 24 Setpoint Controlled Relay Functions sees 25 Solid State KY Z Pulse Output re een tron peer eripere euet 26 2 Wire Pulse InitiatoE iioii oit eei o nibns 26 Wire Pulse Inttatot Nesser manana am ada meines 27 Calculating the Watthour per pulse Value sse 28 Analog Outputs 29 Analog Output Example nni cerne ers Enui NEE dele 30 The circuit monitor supports a variety of input output options through the use of optional add on I O modules The I O modules attach to the back of the circuit monitor Each I O module provides some or all of the following Status Inputs Mechanical Relay Outputs Solid State KYZ Pulse Output Analog Inputs Analog Outputs Table 3 1 lists the available I O Modules The remainder of this chapter describes the I O capabilities For module installation instructions and detailed technical specifications refer to the appropriate instruction bulletin see list on page 6 of the Circuit Monitor Installation and Operation Bulletin Table 3 1 Input Output Modules Max Control Power Burden Class Type Description When IOM Present 120
46. Setpoint Controlled Relay Functions Chapter 3 Input Output Capabilities The circuit monitor can detect over 100 alarm conditions including over under conditions status input changes phase unbalance conditions and more see Chapter 4 Alarm Functions Using POWERLOGIC application software an alarm condition can be assigned to automatically operate one or more relays For example you could setup the alarm condi tion Undervoltage Phase A to operate relays R1 R2 and R3 Then each time the alarm condition occurs that is each time the setpoints and time delays assigned to Undervoltage Phase A are satisfied the circuit monitor automatically operates relays R1 R2 and R3 per their configured mode of operation See Relay Output Operating Modes in this chapter for a descrip tion of the operating modes Also multiple alarm conditions can be assigned to a single relay For example the alarm conditions Undervoltage Phase A and Undervoltage Phase B could both be assigned to operate relay R1 The relay remains energized as long as either Undervoltage Phase A or Undervoltage Phase B remains true Note Setpoint controlled relay operation can be used for some types of non time critical relaying For more information see Setpoint Controlled Relay Functions in Chapter 4 1999 Square D Company All Rights Reserved 25 Bulletin No 3020IM9806 February 1999 SOLID STATE KYZ PULSE OUTPUT 2 Wire
47. Square D Plants 10 05 A Figure 7 5 60 cycle extended event capture displayed in SMS 3000 You can retrieve and display the individual 12 cycle waveform captures which comprise the extended event capture using SMS 700 SMS 770 EXP 550 or EXP 500 You can also manually acquire a set of continuous 12 cycle waveform captures using the retrieve existing on board waveform capture option figure 7 6 3rd of 3 2nd of 3 1st of 3 PowerLogic System Manager salle il dit SetUp Control Display Reports Macro Window Help Online AR Data Directory C SMSV221 _Sampling Scheduled 5sec OV RES PTS E tE 83 d CM_Main Mon Aug 14 09 33 29 1995 ME CM_Main Mon Aug 14 09 33 29 1995 a Retrieve Phase A N Voltage Phase A Current Retrieve 165 s L a j E ze va J Jes 102 As CM Main Mon Aug 14 09 33 29 1995 sae Retrieve iss Phase A N Voltage e Phase A Current ee SARAAAAAAAAAA JA Retrieve Onboard Waveforms 3rd of 3 82 42 E E Onboard Data Waves ae es 14 Phase B N Voltage To Wave Number 1 08 14 95 09 33 29 AM sto m e Wave Number 2 08 14 95 09 33 29 AM 85 VVV 35 Wave Number 3 08 14 95 09 33 29 AM uum ag Wave Number 4 08 13 95 01 23 41 PM e Phase C N Voltage Wave Number 5 08 13 95 01 23 41 PM B D Wave Number 6 08 13 95 01 23 41 PM z 67 93 Eventlog Alarm List
48. Up the Circuit Monitor How it Works Chapter 6 Waveform Capture External Relay Circuit Monitor I O Module Figure 6 2 Status input S2 connected to external high speed relay Figure 6 2 shows a block diagram that illustrates the relay to circuit monitor connections As shown in figure 6 3 the relay must be wired to status input S2 on an IOM 18 or IOM 44 Status input S2 is a high speed input designed for this application or any of the status inputs on an IOM 4411 or IOM 4444 can be used for high speed event capture The circuit monitor must be set up for extended event capture using POWERLOGIC application software The following is an example of setting up the circuit monitor for event capture 1 When setting up the circuit monitor select the alarm condition Input S2 OFF to ON See Appendix D for a listing of alarm conditions 2 Select the number of cycles to be stored for the extended event capture For specific instructions on specifying an alarm condition for extended event capture refer to the POWERLOGIC application software instruction bulletin The circuit monitor maintains a data buffer consisting of 64 data points per cycle for all current and voltage inputs As the circuit monitor samples data this buffer is constantly updated When the circuit monitor senses the trigger that is when input 82 in the above example transitions from off to on the circuit monitor can transfer fro
49. aede e a e ERE Esa aiei 61 Command Codes ee tede a dece iti ein ree le A 62 Operating Relays Using the Command Interface cccccecssssseseessseseesessseseenesssesesnessssseeeessesseseensssseeeeesseseenees 64 ii 1999 Square D Company All Rights Reserved Contents Setting Up Relays for Remote External Control sse e eene 64 Energizing a RELAY 64 De Energ izing a Relay e 64 Setting Up Relays for Circuit Monitor Internal Control seen 65 Overriding an Output Relay aes tune ente eee eo elati eer ree pera roce erotica Pete ste ua Releasing an Overridden Relay Setting Scale Factors For Extended Metering Ranges Setting The Date and Time Using the Command Interface esse nene 69 Memory Allocation M aai 69 Memory Example d 71 How Power Factors Stored 1 usce teretes iva e dates Doe d AE a oe E be Doe Pe Lirie EEEE esed ied 71 Changing the VAR Sign CONVENON seisean enea ee tao iie baee Rie e ie iteteien 72 Conditional Energy sisses Command Interface Control Status Inp t COOL etie certet acutae Petitur ri dpt dee edits Incremental Energy M Using Incremental Energy ironion titt tee retitet lene eie aa asais einan
50. card memory or the 100K of memory standard on G4 circuit monitors Earlier versions of System Manager software will recognize only 11K the Series G3 and earlier memory capacity of available memory Also your circuit monitor must be equipped with firmware version 17 009 or later to take advantage of expanded memory The following section tells how to determine the firmware version shipped with your circuit monitor To determine if your circuit monitor firmware version has been updated with downloadable firmware see Viewing Configuration Data in Protected Mode in Chapter 4 of the Circuit Monitor Installation and Operation Bulletin To obtain the latest available firmware revision contact your local Square D representative see Note page 1 The circuit monitor series and firmware revision numbers are printed on a sticker on the top of the circuit monitor enclosure Figure 1 1 shows a sample sticker 63230 204 106 Series gt Series G2C U6 REV 16 16 007 Firmware Revision U33 REV 16 007 Figure 1 1 Circuit monitor series firmware revision sticker Circuit monitor models equipped with an optional memory expansion card are differentiated from standard models by a suffix either 512k or 1024k added to the model number table 1 4 As shown in the table the memory expansion option is available for model numbers CM 2150 CM 2250 CM 2350 and CM 2450 The CM 2452 circuit monitor is now obsolete and has been
51. change through the range of 000 000 kWh to 000 000 MWh 000 000 kVARh to 000 000 KV ARh or it can be fixed See Appendix B register 2027 on page 97 The circuit monitor provides additional energy readings that are available over the communications link only They are Directional accumulated energy readings The circuit monitor calculates and stores in nonvolatile memory accumulated values for energy kWH and reactive energy kVARH both into and out of the load The circuit monitor also calculates and stores apparent energy KVAH Conditional accumulated energy readings Using these values energy accumulation can be turned off or on for special metering applications Accumulation can be turned on over the communications link or acti vated from a status input change The circuit monitor stores the date and time of the last reset of conditional energy in nonvolatile memory Incremental accumulated energy readings The real reactive and apparent incremental energy values reflect the energy accumulated during the last incremental energy period You can define the increment start time and time interval Incremental energy values can be logged in circuit monitor memory models CM 2150 and up and used for load profile analysis The circuit monitor provides a number of power analysis values that can be used to detect power quality problems diagnose wiring problems and more Table 2 4 on page 16 summarizes the power analysis values
52. data logs or output relay operations For this example assume that automatic waveform capture has been assigned to the alarm condition When the circuit monitor sees that an alarm condition specified for automatic waveform capture has occurred it stores the four cycles of waveform data acquired at the beginning of the update cycle Start Circuit Monitor acquires data sample 4 cycles Circuit Monitor performs metering calculations Circuit Monitor checks for alarm conditions Circuit Monitor saves data from Alarm beginning of cycle and performs conditions any other actions assigned to the detected alarm condition Figure 6 1 Flowchart illustrating automatic waveform capture 42 1999 Square D Company All Rights Reserved Waveform Storage Chapter 6 Waveform Capture Circuit monitor model 2250 stores waveforms differently than model 2350 The lists below describe how each model stores waveforms CM 2250 Can store only one captured waveform Each new waveform capture either manual or automatic replaces the last waveform data Stores the captured waveform in volatile memory the waveform data is lost on power loss The captured waveform does not affect event log and data log storage space The captured waveform is stored separately CM 2350 and higher e Can store multiple captured waveforms Stores the captured waveforms in nonvolatile memory the waveform data is retained on p
53. defined as demand kW demand kVA for the peak demand interval Peak demand values can be reset from the circuit monitor front panel or over the communications link using POWERLOGIC application software To reset peak demand values from the circuit monitor front panel see Resetting Demand Energy and Min Max Values in Chapter 4 of the Circuit Monitor Installation and Operation Bulletin 1999 Square D Company All Rights Reserved 13 Bulletin No 3020IM9806 February 1999 Generic Demand Voltage Demand ENERGY READINGS The circuit monitor has the capability to perform a thermal demand calcula tion on 20 user specified quantities The user can select the demand interval from 5 60 minutes in 5 minute increments For each quantity the present minimum and maximum demand values are stored The date and time of the minimums and maximums for the first ten demand quantities are also stored To set up the demand calculation for a specific quantity write the corre sponding register number for that quantity in the register range of 2205 2224 The generic demand interval can be configured by writing the desired interval in register 2201 For a complete list of all registers and their descrip tions pertaining to generic demand see the register list in Appendix B beginning with register number 2200 For instructions on reading and writing to registers see the software instruction manual Minimum and maximum generic demand va
54. expires the relay will de energize and rapidly re energize this sequence will repeat until the alarm condition drops out 4 Absolute kWH Pulse This mode assigns the relay to operate as a pulse initiator witha user defined number of kWH per pulse In this mode both forward and reverse real energy are treated as additive as in a tie breaker 5 Absolute kVARH Pulse This mode assigns the relay to operate as a pulse initiator with a user defined number of KVARH per pulse In this mode both forward and reverse reactive energy are treated as additive as in a tie breaker 6 KVAH Pulse This mode assigns the relay to operate as a pulse initiator with a user defined number of kVAH per pulse Since kVA has no sign there is only one mode for kVAH pulse 7 kWH In Pulse This mode assigns the relay to operate as a pulse initiator witha user defined number of kWH per pulse In this mode only the kWH flowing into the load is considered 8 kVARH In Pulse This mode assigns the relay to operate as a pulse initiator with a user defined number of kVARH per pulse In this mode only the kVARH flowing into the load is considered 9 KWH Out Pulse This mode assigns the relay to operate as a pulse initiator with a user defined number of kWH per pulse In this mode only the kWH flowing out of the load is considered 10 KVAR Out Pulse This mode assigns the relay to operate as a pulse initiator with a user defined number of kVARH per pulse In t
55. proper circuit protection If the user determines that the circuit monitor s performance is acceptable the output contacts can be used to mimic some functions of a motor manage ment device When deciding if the circuit monitor is acceptable for these applications keep the following points in mind Circuit monitors require control power in order to operate properly Circuit monitors may take up to 5 seconds after control power is applied before setpoint controlled functions are activated If this is too long a reliable source of control power is required When control power is interrupted for more than approximately 100 milliseconds the circuit monitor releases all energized output contacts Standard setpoint controlled functions may take 2 3 seconds to operate even if no delay is intended A password is required to program the circuit monitor s setpoint con trolled relay functions A description of some common motor management functions follows For detailed instructions on setting up setpoint controlled functions from the circuit monitor s front panel see Setting Up Alarm Relay Functions in Chapter 4 of the Circuit Monitor Installation and Operation Bulletin and Appendix D Alarm Setup Information in this bulletin Undervoltage Pickup and dropout setpoints are entered in volts Very large values may require scale factors Refer to Setting Scale Factors for Extended Metering Ranges in Chapter 9 for more informat
56. pulse Peak Demand Pulse Count amp Input S1 lt q Input S2 Date Time of Peak Totalized Figure 9 5 Pulse demand metering example 1999 Square D Company All Rights Reserved 79 Appendix A Communication Cable Pinouts APPENDIX A COMMUNICATION CABLE PINOUTS CAB 107 Circuit Monitor Male DB 9 Terminal Connector CAB 108 IN 21 White 1 TXA White 1 IN 20 Green 2 TXB Green 2 OUT 23 Black 3 RXA Black 3 OUT 22 Red 4 RXB Red 4 5 5 L 6 L 6 7 7 L 8 L 8 SHLD 24 Shield 9 Shield Shield 9 CC 100 CAB 102 CAB 104 1 1 2 2 2 2 3 3 3 3 4 4 4 4 5 5 5 5 6 6 6 6 7 7 7 7 8 8 8 8 20 20 9 9 22 22 1999 Square D Company All Rights Reserved 81 Appendix B Abbreviated Register Listing APPENDIX B ABBREVIATED REGISTER LISTING This appendix contains an abbreviated listing of circuit monitor regis ters The following values are included in this register listing e Real Time Metered Values Real Time Meter Values Minimum Real Time Meter Values Maximum e Energy Values Demand Values Dates and Times Status Inputs Relay Outputs Circuit Monitor Configuration Values In this appendix the following information is provided for each register Register Number see note below Register Description Units Range Note
57. satisfy the dropout delay period the alarm will dropout Pickup and Dropout setpoints are positive delays are in seconds The over reverse power alarm will occur when the test register s absolute value exceeds the pickup setpoint and remains above the pickup setpoint long enough to satisfy the pickup delay period When the absolute value drops to below the dropout setpoint and remains below the setpoint long enough to satisfy the dropout delay period the alarm will dropout This alarm will only hold true for Reverse Power conditions i e any positive power value will not cause the alarm to occur Pickup and Dropout setpoints are positive delays are in seconds Once enabled the phase reversal alarm will occur whenever the phase voltage waveform rotation differs from the default phase rotation It is assumed that an ABC phase rotation is normal If a CBA normal phase rotation is normal the user should reprogram the circuit monitor s phase rotation from ABC default to CBA phase rotation The pickup and dropout setpoints and delays for phase reversal do not apply The Status Input transitions alarms will occur whenever the status input changes from off to on The alarm requires no pickup or dropout setpoints or delays The Alarm will dropout when the status input changes back to off from on The pickup and dropout setpoints and delays do not apply The Status Input transitions alarms will occur whenever the status input changes from on to off
58. that is equivalent to the maximum output current 1 mA or 20 mA Reg No Name Units ANALOG INPUT CONFIGURATION REGISTERS 2700 2702 Analog Input 1 None Units 2703 Analog Input 1 None Precision 2704 Analog Input 1 None Input Type 2705 Analog Input 1 in 100ths Offset Voltage 2706 Analog Input 1 None Lower Limit 2707 Analog Input 1 None Upper Limit The description for registers 2710 2717 is the same as 2700 2707 2710 2712 Analog Input 2 Units 2713 Analog Input 2 Precision 2714 Analog Input 2 Input Type 2715 Analog Input 2 Offset Voltage 2716 Analog Input 2 Lower Limit 2717 Analog Input 2 Upper Limit The description for registers 2720 2727 is the same as 2700 2707 2720 2722 Analog Input 3 Units 2723 Analog Input 3 Precision 2724 Analog Input 3 Input Type 2725 Analog Input 3 Offset Voltage 2726 Analog Input 3 Lower Limit 2727 Analog Input 3 Upper Limit The description for registers 2730 2737 is the same as 2700 2707 2730 2732 Analog Input 4 Units 2733 Analog Input 4 Precision 2734 Analog Input 4 Input Type 2735 Analog Input 4 Offset Voltage 2736 Analog Input 4 Lower Limit 2737 Analog Input 4 Upper Limit Range Alphanumeric 6 chars 3 to 3 O or 1 0 to 500 32767 to Upper Limit Lower Limit to 32767 Appendix B Abbreviated Register Listing Description A six character label used to identify this input The precision of the measured analog value Specifies whet
59. the software All running min max values with the exception of power factor are arithmetic minimums and maximums For example the minimum phase A B voltage is simply the lowest value in the range 0 to 3 276 700 V that has occurred since the min max values were last reset In contrast power factor min max values since the meter s midpoint is unity are not true arith metic minimums and maximums Instead the minimum value represents the measurement closest to 0 on a continuous scale of 0 to 1 00 to 0 The maximum value is the measurement closest to 0 on the same scale Figure 2 1 shows the min max values in a typical environment assuming a positive power flow In figure 2 1 the minimum power factor is 7 lagging and the maximum is 8 leading It is important to note that the minimum power factor need not be lagging and the maximum power factor need not be leading For example if the power factor values ranged from 75 to 95 then the minimum power factor would be 75 lagging and the maximum power factor would be 95 lagging Likewise if the power factor ranged from 9 to 95 the minimum would be 95 leading and the maximum would be 90 leading See Changing the VAR Sign Convention in Chapter 9 for instructions on changing the sign convention over the communications link 10 1999 Square D Company All Rights Reserved Chapter 2 Metering Capabilities Minimum Maximum Power Factor Pow
60. will be followed by a revision number for example R10 97 Q n some instances this toll free number may not work if dialed from outside of the United States In such instances phone 1 919 217 6344 to speak to the D Fax administrator 1999 Square D Company All Rights Reserved 7 Bulletin No 3020IM9806 February 1999 Installation and Operation Bulletin For information necessary to install and operate the circuit monitor see the POWERLOGIC Circuit Monitor Installation and Operation Bulletin No 3020IM9807 which includes information on the following topics Hardware Description Mounting and Grounding the Circuit Monitor Wiring CTs PTs and Control Power Communications Wiring Configuring the Circuit Monitor Setting up Alarm Relay Functions Viewing Active Alarms Circuit Monitor Dimensions Specifications Installing Terminal Strip Covers The installation and operation manual is included with each circuit monitor Additional copies can be obtained the following two ways 1999 Square D Company All Rights Reserved Download an electronic version Acrobat PDF format from the POWERLOGIC web site at www powerlogic com Order a printed copy from the Square D Literature Center at 1 800 888 2448 Ask for document 3020IM9807 Chapter 2 Metering Capabilities CHAPTER 2 METERING CAPABILITIES CHAPTER CONTENTS REAL TIME READINGS Real Iime Readings irte erre seadesvavssasestussesensnstaeedusn
61. 0 to 32 767 0 to 32 767 Same as Regs No 1800 1802 0 Slave to power demand interval must be block interval mode 1 Slave to incremental energy interval 2 Synch to status input 1 3 Ext comms synch to command interface Demand meter bit map specifying which status inputs totalize for this demand channel Bit 0 represents input 1 etc Bit 0 represents input 1 etc Ozexclude 1 include Default value is 0 Utility registers can be defined by custom applica tion software as storage locations for pulse constant scale factor unit code or other Total number of pulses counted on all specified inputs during present demand interval on this channel Total number of pulses counted during the last completed interval on this channel Peak value of last interval pulse count on this channel since last demand reset Date time of peak interval pulse count since last reset The definitions for registers 2910 2919 are the same as for 2900 2909 except that they apply to channel 2 The definitions for registers 2920 2929 are the same as for 2900 2909 except that they apply to channel 3 The definitions for registers 2930 2939 are the same as for 2900 2909 except that they apply to channel 4 The definitions for registers 2940 2949 are the same as for 2900 2909 except that they apply to channel 5 The definitions for registers 2950 2959 are the same as for 2900 2909 except that they apply to chann
62. 0 to 32 767 1010 Current Unbalance Phase A Percent in 10ths 0 to 1000 1011 Current Unbalance Phase B Percent in 10ths 0 to 1000 1012 Current Unbalance Phase C Percent in 10ths 0 to 1000 1013 Current Unbalance Worst Percent in 10ths 0 to 1000 1014 Voltage Phase A to B Volts Scale Factor D 0 to 32 767 1015 Voltage Phase B to C Volts Scale Factor D 0 to 32 767 1016 Voltage Phase C to A Volts Scale Factor D 0 to 32 767 1017 Voltage L L 3 Phase Average Volts Scale Factor D 0 to 32 767 1018 Voltage Phase A to Neutral Volts Scale Factor D 0 to 32 767 1019 Voltage Phase B to Neutral Volts Scale Factor D 0 to 32 767 1020 Voltage Phase C to Neutral Volts Scale Factor D 0 to 32 767 1021 Voltage L N 3 Phase Average Volts Scale Factor D 0 to 32 767 1022 Voltage Unbalance Phase A B Percent in 10ths 0 to 1000 1023 Voltage Unbalance Phase B C Percent in 10ths 0 to 1000 1024 Voltage Unbalance Phase C A Percent in 10ths 0 to 1000 1025 Voltage Unbalance L L Worst Percent in 10ths 0 to 1000 1026 Voltage Unbalance Phase A Percent in 10ths 0 to 1000 1027 Voltage Unbalance Phase B Percent in 10ths 0 to 1000 1028 Voltage Unbalance Phase C Percent in 10ths 0 to 1000 1029 Voltage Unbalance L N Worst Percent in 10ths 0 to 1000 1031 True Power Factor Phase A In 1000ths 100 to 1000 to 41009 1032 True Power Factor Phase B In 1000ths 100 to 1000 to 41009 1033 True Power Factor Phase C In 1000ths 100 to 1000 to 41
63. 00 and remains less lagging for the dropout delay period the alarm will dropout Pickup setpoint must be negative Dropout setpoint can be negative or positive Enter setpoints as integer values representing power factor in thousandths For example to define a dropout setpoint of 0 5 enter 500 Delays are in seconds The Leading Power Factor alarm will occur when the test register value becomes more leading than the pickup setpoint i e closer to 0 010 and remains more leading long enough to satisfy the pickup delay period When the value becomes equal to or less leading than the dropout setpoint i e closer to 1 000 and remains less leading for the dropout delay period the alarm will dropout Pickup setpoint must be positive Dropout setpoint can be positive or negative Enter setpoints as integer values representing power factor in thousandths For example to define a dropout setpoint of 0 5 enter 500 Delays are in seconds The over power demand alarms will occur when the test register s absolute value exceeds the pickup setpoint and remains above the pickup setpoint long enough to satisfy the pickup delay period When the absolute value drops to below the dropout setpoint and remains below the setpoint long enough to satisfy the dropout delay period the alarm will dropout Pickup and Dropout setpoints are positive delays are in seconds 1999 Square D Company All Rights Reserved 121 Bulletin No 3020IM9806 February 1999
64. 009 1034 True Power Factor 3 Phase Total In 1000ths 100 to 1000 to 41009 1035 Displacement Power Factor Phase A In 1000ths 100 to 1000 to 41009 1036 Displacement Power Factor Phase B In 1000ths 100 to 1000 to 4100 1037 Displacement Power Factor Phase C In 1000ths 100 to 1000 to 1009 1038 Displacement Power Factor 3 Phase Total In 1000ths 100 to 1000 to 41009 1039 Real Power Phase A kW Scale Factor E 0 to 32 767 1040 Real Power Phase B kW Scale Factor E 0 to 32 767 1041 Real Power Phase C kW Scale Factor E 0 to 32 767 1042 Real Power 3 Phase Total kW Scale Factor E 0 to 332 767 1043 Reactive Power Phase A kVAr Scale Factor E 0 to 332 767 1044 Reactive Power Phase B kVAr Scale Factor E 0 to 32 767 1045 Reactive Power Phase C kVAr Scale Factor E 0 to 32 767 1046 Reactive Power 3 Phase Total kVAr Scale Factor E 0 to 32 767 1047 Apparent Power Phase A kVA Scale Factor E 0 to 432 767 1048 Apparent Power Phase B kVA Scale Factor E 0 to 432 767 1049 Apparent Power Phase C kVA Scale Factor E 0 to 32 767 1050 Apparent Power 3 Phase Total kVA Scale Factor E 0 to 432 767 See How Power Factor is Stored in Chapter 13 for a description of the power factor register format 84 1999 Square D Company All Rights Reserved THD Phase Neutral Current thd Phase Neutral Current Phase A Current Fundamental rms Magnitude Phase A Current Fundamental Coincident Angle Phase B Current
65. 10 000 2300 to 6700 50 60 3500 to 4500 400 Degrees Cent 10 000 in 100ths Amps Scale Factor A 0 to 32 767 Amps Scale Factor A 0 to 32 767 Amps Scale Factor A 0 to 32 767 Amps Scale Factor A 0 to 32 767 Amps Scale Factor A 0 to 32 767 Amps Scale Factor A 0 to 32 767 Amps Scale Factor A 0 to 32 767 Percent in 10ths 0 to 1000 Percent in 10ths 0 to 1000 Percent in 10ths 0 to 1000 Percent in 10ths 0 to 1000 Volts Scale Factor D 0 to 32 767 Volts Scale Factor D 0 to 32 767 Volts Scale Factor D 0 to 32 767 Volts Scale Factor D 0 to 32 767 Volts Scale Factor D 0 to 32 767 Volts Scale Factor D 0 to 32 767 Volts Scale Factor D 0 to 32 767 Volts Scale Factor D 0 to 32 767 Reg No 1222 1223 1224 1225 1226 1227 1228 1229 1231 1232 1233 1234 1235 1236 1237 1238 1239 1240 1241 1242 1243 1244 1245 1246 1247 1248 1249 1250 1251 1252 1253 1254 1255 1256 1257 1258 1259 1260 1271 1272 1273 Description Minimum Volt Unbalance Phase A B Minimum Volt Unbalance Phase B C Minimum Volt Unbalance Phase C A Minimum Volt Unbalance L L Worst Minimum Volt Unbalance Phase A Minimum Volt Unbalance Phase B Minimum Volt Unbalance Phase C Minimum Volt L N Unbalance Worst Minimum True Power Factor A Minimum True Power Factor B Minimum True Power Factor C Minimum True Power Factor 3 Total Minimum Displ Power Factor A Minimum Displ Power Factor B Minimum Displ Power Factor C Minimum Displ
66. 12 Description H19 magnitude as a percent of H1 magnitude H19 angle with reference to H19 Va angle H20 magnitude as a percent of H1 magnitude H20 angle with reference to H20 Va angle H21 magnitude as a percent of H1 magnitude H21 angle with reference to H21 Va angle H22 magnitude as a percent of H1 magnitude H22 angle with reference to H22 Va angle H23 magnitude as a percent of H1 magnitude H23 angle with reference to H23 Va angle H24 magnitude as a percent of H1 magnitude H24 angle with reference to H24 Va angle H25 magnitude as a percent of H1 magnitude H25 angle with reference to H25 Va angle H26 magnitude as a percent of H1 magnitude H26 angle with reference to H26 Va angle H27 magnitude as a percent of H1 magnitude H27 angle with reference to H27 Va angle H28 magnitude as a percent of H1 magnitude H28 angle with reference to H28 Va angle H29 magnitude as a percent of H1 magnitude H29 angle with reference to H29 Va angle H30 magnitude as a percent of H1 magnitude H30 angle with reference to H30 Va angle H31 magnitude as a percent of H1 magnitude H31 angle with reference to H31 Va angle Reserved H1 magnitude as a percent of H1 magnitude H1 angle with reference to H1 Va angle H2 magnitude as a percent of H1 magnitude H2 angle with reference to H2 Va angle H3 magnitude as a percent of H1 magnitude H3 angle with reference to H3 Va angle H4 magnitude as a percent of H1 magnitude H4 angle with reference to H4 Va angle H5 magnitude a
67. 2042 2049 CM Nameplate None 2076 Incremental Energy Interval Minutes 2077 Power Demand Interval Minutes 2078 Power Demand Sub Interval Minutes 2079 Current Demand K Factor Minutes Demand Interval in minutes Reg No Name Units Range 2080 Energy Accum None Oori Mode Selections Bit map 2081 Operating Mode None 0 to 7F Selections Bit map 98 1999 Square D Company All Rights Reserved Range Any Valid Alpha Numeric Any Valid Alpha Numeric 0 to 1 440 minutes 0 to 60 5min Multiples 0 to 60 5min Multiples 0 to 60 5min Multiples Description Circuit Monitor Energy Accumulation Mode Selections Bit Map Bit 1 indicates real amp reactive energy accumulation method a 0 indicates absolute a 1 indicates signed Circuit Monitor Operating Mode Selections Bit Map Bit 1 indicates real amp reactive energy accumulation method 0 indicates absolute default 1 indicates signed Bit 2 indicates Reactive Energy and Demand accumulation method 0 specifies fundamental only default 1 specifies to include harmonic cross products displacement amp distortion Bit 3 indicates VAr PF sign convention 0 indicates CM1 convention default 1 indicates alternate convention Bit 4 indicates Demand Power calculation method 0 indicates Thermal Demand default 1 indicates a Block Rolling Interval Demand Bit 5 indicates external power demand synch driver source if applicable 0 Specifies Input 1 as the source default 1 Spe
68. 32 767 kVAr Scale Factor E 0 to 32 767 kVAr Scale Factor E 0 to 32 767 kVAr Scale Factor E 0 to 32 767 kVAr Scale Factor E 0 to 32 767 kVA Scale Factor E 0 to 32 767 kVA Scale Factor E 0 to 32 767 kVA Scale Factor E 0 to 32 767 kVA Scale Factor E 0 to 32 767 in 10ths 0 to 32 767 in 10ths 0 to 32 767 in 10ths 0 to 32 767 in 10ths 0 to 32 767 in 10ths 0 to 32 767 in 10ths 0 to 32 767 in 10ths 0 to 32 767 in 10ths 0 to 32 767 in 10ths 0 to 32 767 in 10ths 0 to 32 767 In 10ths 0 to 10 000 In 10ths 0 to 10 000 In 10ths 0 to 10 000 1391 Analog Input 1 None Minimum Value 1392 Analog Input 2 None Minimum Value 1393 Analog Input 3 None Minimum Value 1394 Analog Input 4 None Minimum Value 32767 to 32767 32767 to 432767 32767 to 432767 32767 to 432767 1999 Square D Company All Rights Reserved The minimum scaled value of analog input 1 since the last reset of min max values The minimum scaled value of analog input 2 since the last reset of min max values The minimum scaled value of analog input 3 since the last reset of min max values The minimum scaled value of analog input 4 since the last reset of min max values Bulletin No 3020IM9806 February 1999 Reg No Description REAL TIME METERED VALUES MAXIMUM 1400 Maximum Update Interval 1401 Maximum Freq 1402 Maximum Temp 1403 Maximum Current Phase A 1404 Maximum Current Phase B 1405 Max
69. 38 H23 magnitude as a percent of H1 magnitude 4239 H23 angle with reference to H23 Va angle 4240 H24 magnitude as a percent of H1 magnitude 4241 H24 angle with reference to H24 Va angle 4242 H25 magnitude as a percent of H1 magnitude 4243 H25 angle with reference to H25 Va angle 4244 H26 magnitude as a percent of H1 magnitude 4245 H26 angle with reference to H26 Va angle 4246 H27 magnitude as a percent of H1 magnitude 4247 H27 angle with reference to H27 Va angle 4248 H28 magnitude as a percent of H1 magnitude 4249 H28 angle with reference to H28 Va angle 4250 H29 magnitude as a percent of H1 magnitude 4251 H29 angle with reference to H29 Va angle 4252 H30 magnitude as a percent of H1 magnitude 4253 H30 angle with reference to H30 Va angle 4254 H31 magnitude as a percent of H1 magnitude 4255 H31 angle with reference to H31 Va angle Phase C Voltage 4256 4257 Reserved 4258 H1 magnitude as a percent of H1 magnitude 4259 H1 angle with reference to H1 Va angle 4260 H2 magnitude as a percent of H1 magnitude 4261 H2 angle with reference to H2 Va angle 4262 H3 magnitude as a percent of H1 magnitude 4263 H3 angle with reference to H3 Va angle 4264 H4 magnitude as a percent of H1 magnitude 4265 H4 angle with reference to H4 Va angle 4266 H5 magnitude as a percent of H1 magnitude 4267 H5 angle with reference to H5 Va angle 4268 H6 magnitude as a percent of H1 magnitude 4299 H21 angle with reference to H21 Va angle 4300 H22 magnitude as a percent o
70. 4 Chars 0 to 99 999 999 0 to 32 767 1999 Square D Company All Rights Reserved 93 Bulletin No 3020IM9806 February 1999 Reg No Description 2412 2413 Input 3 Label 2414 2415 Input 3 Count 2416 Input 3 On Timer 2417 2418 Input 4 Label 2419 2420 Input 4 Count 2421 Input 4 On Timer 2422 2423 Input 5 Label 2424 2425 Input 5 Count 2426 Input 5 On Timer 2427 2428 Input 6 Label 2429 2430 Input 6 Count 2431 Input 6 On Timer 2432 2433 Input 7 Label 2434 2435 Input 7 Count 2436 Input 7 On Timer 2437 2438 Input 8 Label 2439 2440 Input 8 Count 2441 Input 8 On Timer KYZ and RELAY OUTPUTS 2500 Output Status None 2501 Output Control None State Bit Mask 2502 2503 KYZ Output Label None 2504 KYZ Output None Mode Reg 2505 KYZ Output Seconds Parameter Register 94 Units None Counts Seconds None Counts Seconds None Counts Seconds None Counts Seconds None Counts Seconds None Counts Seconds 0000 to OOFF Hex 0000 to FFFF Hex Alpha Numeric 4 Chars 2 Regs 0 to 9 0 to 32 767 1999 Square D Company All Rights Reserved Range Alpha Numeric 4 Chars 0 to 99 999 999 0 to 32 767 Alpha Numeric 4 Chars 0 to 99 999 999 0 to 32 767 Alpha Numeric 4 Chars 0 to 99 999 999 0 to 32 767 Alpha Numeric 4 Chars 0 to 99 999 999 0 to 32 767 Alpha Numeric 4 Chars 0 to 99 999 999 0 to 32 767 Alpha Numeric 4 Chars 0 to 99 999 999 0 to 32 767 Bit Map o
71. 4132 4133 4134 4135 4136 4137 4138 4139 4140 4141 4142 4143 4144 4145 4146 4147 4148 4149 4150 4151 4152 4153 4154 4155 4156 4157 4158 4159 4160 4161 4162 Description H22 magnitude as a percent of H1 magnitude H22 angle with reference to H22 Va angle H23 magnitude as a percent of H1 magnitude H23 angle with reference to H23 Va angle H24 magnitude as a percent of H1 magnitude H24 angle with reference to H24 Va angle H25 magnitude as a percent of H1 magnitude H25 angle with reference to H25 Va angle H26 magnitude as a percent of H1 magnitude H26 angle with reference to H26 Va angle H27 magnitude as a percent of H1 magnitude H27 angle with reference to H27 Va angle H28 magnitude as a percent of H1 magnitude H28 angle with reference to H28 Va angle H29 magnitude as a percent of H1 magnitude H29 angle with reference to H29 Va angle H30 magnitude as a percent of H1 magnitude H30 angle with reference to H30 Va angle H31 magnitude as a percent of H1 magnitude H31 angle with reference to H31 Va angle Reserved H1 magnitude as a percent of H1 magnitude H1 angle with reference to H1 Va angle H2 magnitude as a percent of H1 magnitude H2 angle with reference to H2 Va angle H3 magnitude as a percent of H1 magnitude H3 angle with reference to H3 Va angle H4 magnitude as a percent of H1 magnitude H4 angle with reference to H4 Va angle H5 magnitude as a percent of H1 magnitude H5 angle with reference to H5 Va angle H6 mag
72. 452 256K memory expansion card removed and replaced with 512K or 1024K memory expansion card 1999 Square D Company All Rights Reserved 5 Bulletin No 3020IM9806 February 1999 SAFETY PRECAUTIONS A DANGER HAZARD OF BODILY INJURY OR EQUIPMENT DAMAGE Only qualified electrical workers should install this equipment Such work should be performed only after reading this entire set of instructions The successful operation of this equipment depends upon proper handling installation and operation Neglecting fundamental installation requirements may lead to personal injury as well as damage to electrical equipment or other property Before performing visual inspections tests or maintenance on this equipment disconnect all sources of electric power Assume that all circuits are live until they have been completely de energized tested grounded and tagged Pay particular attention to the design of the power system Consider all sources of power including the possibility of backfeeding Failure to observe this precaution will result in death serious injury or equipment damage USING THIS BULLETIN This document provides information on the circuit monitor s general to advanced features The document consists of a table of contents nine chap ters and several appendices Chapters longer than a few pages begin with a chapter table of contents To locate information on a specific topic refer to the table of contents a
73. 55 1657 Incremental Real Energy Out 3 Phase Total WH 1658 1660 Incremental Reactive Energy Out 3 Phase Total VArH 1661 1663 Incremental Apparent Energy 3 Phase Total VAH 0 to 9 999 999 999 999 999 0 to 9 999 999 999 999 999 0 to 9 999 999 999 999 999 0 to 9 999 999 999 999 999 0 to 9 999 999 999 999 999 0 to 9 999 999 999 999 999 0 to 9 999 999 999 999 999 0 to 9 999 999 999 999 999 0 to 9 999 999 999 999 999 0 to 9 999 999 999 999 999 0 to 9 999 999 999 999 999 0 to 9 999 999 999 999 999 0 to 999 999 999 999 0 to 999 999 999 999 0 to 999 999 999 999 0 to 999 999 999 999 0 to 999 999 999 999 1999 Square D Company All Rights Reserved 89 Bulletin No 3020IM9806 February 1999 Reg No Description DEMAND VALUES CURRENT DEMAND 1700 Present Current Demand 3 Phase Average 1701 Present Current Demand Phase A 1702 Present Current Demand Phase B 1703 Present Current Demand Phase C 1704 Present Current Demand Neutral 1705 Thermal K Factor Demand Phase A 1706 Thermal K Factor Demand Phase B 1707 Thermal K Factor Demand Phase C 1708 Peak Current Demand 3 Phase Average 1709 Peak Current Demand Phase A 1710 Peak Current Demand Phase B 1711 Peak Current Demand Phase C 1712 Peak Current Demand Neutral 1713 K Factor Demand Phase A Coincident Peak Product 1714 Current Demand Phase A Coincident Peak Product 1715 K Factor Demand Phase B Coincident Peak Product 1716 Current Demand Phase B Coincident Peak Pr
74. 6 Va angle H7 magnitude as a percent of H1 magnitude H7 angle with reference to H7 Va angle H8 magnitude as a percent of H1 magnitude H8 angle with reference to H8 Va angle H9 magnitude as a percent of H1 magnitude H9 angle with reference to H9 Va angle H10 magnitude as a percent of H1 magnitude H10 angle with reference to H10 Va angle H11 magnitude as a percent of H1 magnitude H11 angle with reference to H11 Va angle H12 magnitude as a percent of H1 magnitude H12 angle with reference to H12 Va angle 1999 Square D Company All Rights Reserved Appendix B Abbreviated Register Listing Units In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degre
75. 744 Real Power Demand for Peak Apparent 1745 Reactive Power Demand for Peak Apparent 1746 Predicted Real Power Demand 3 Phase Total 1747 Predicted Reactive Power Demand 3 Phase Total 1748 Predicted Apparent Power Demand 3 Phase Total 1749 Maximum Real Power 3 Phase Demand Over Last Inc Energy Interval 1750 Maximum Reactive Power 3 Phase Demand Over Last Inc Energy Interval 1751 Maximum Apparent Power 3 Phase Demand Over Last Inc Energy Interval 1752 Time Remaining in Demand Interval 90 1999 Square D Company All Rights Reserved In 1000ths kW Scale Factor E kVAr Scale Factor E kVA Scale Factor E kW Scale Factor E Percent in 1000ths kVAr Scale Factor E kVA Scale Factor E kVAr Scale Factor E Percent in 1000ths kW Scale Factor E kVA Scale Factor E kVA Scale Factor E Percent in 1000ths kW Scale Factor E kVAr Scale Factor E kW Scale Factor E kVAr Scale Factor E kVA Scale Factor E kW Scale Factor E kVAr Scale Factor E kVA Scale Factor E Seconds 100 to 1000 to 100 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 100 to 1000 to 100 0 to 32 767 0 to 32 767 0 to 32 767 100 to 1000 to 100 0 to 32 767 0 to 32 767 0 to 32 767 100 to 1000 to 100 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 3600 Reg No Description DATE TIME Compressed 3 register format Appendix B Abbreviated R
76. 999 Square D Company All Rights Reserved 123 Appendix E Reading and Writing Registers from the Front Panel APPENDIX E READING AND WRITING REGISTERS FROM THE FRONT PANEL The circuit monitor provides four setup modes Configuration mode Resets mode Alarm Relay mode and Diagnostics mode See The Setup Mode in Chapter 4 of the Circuit Monitor Installation and Operation Bulletin for a description of the first three of these modes This appendix tells how to use the Diagnostics mode The Diagnostics mode lets you read and write circuit monitor registers from the front panel This capability is most useful to users who 1 need to set up an advanced feature which cannot be set up using the circuit monitor s normal front panel setup mode and 2 do not have access to POWERLOGIC software to set up the feature For example the default operating mode for a circuit monitor relay output is normal To change a relay s operating mode from normal to some other mode for example latched mode you d need to use either POWERLOGIC software or the Diagnostics setup mode Note Use this feature with caution Writing an incorrect value or writing to the wrong register could cause the circuit monitor to operate incorrectly To read and or write registers complete the following steps 1 Press the MODE button until the red LED next to Setup is lit The circuit monitor displays ConFig 2 Press the down arrow SELECT METER Value b
77. A scale factor is the multiplier expressed as a power of 10 For example a multiplier of 10 is represented as a scale factor of 1 since 10 10 a multiplier of 100 is repre sented as a scale factor of 2 since 107 100 If the circuit monitor displays OFLO for any reading the scale factor may need to be changed to bring the reading back into range For example since a circuit monitor register cannot store a number as large as 138 000 a 138 kV system requires a multiplier of 10 138 000 is converted to 13 800 x 10 The circuit monitor stores this value as 13 800 with a scale factor of 1 since 10 10 The circuit monitor front panel would display the value as 138 00 with the KILO units LED lit Scale factors are arranged in scale groups The abbreviated register list in Appendix B shows the scale group associated with each metered value The command interface can be used to change scale factors on a group of metered values The procedure on the following page tells how Notes e It is strongly recommended that the default scale factors which are automati cally selected by POWERLOGIC hardware and software not be changed e When using custom software to read circuit monitor data over the communi cations link you must account for these scale factors To correctly read any metered value with a scale factor other than 0 multiply the register value read by the appropriate power of 10 e When you change a scale factor all min max v
78. Analog Output 2 Lower Limit Analog Output 2 Upper Limit The description for registers 2616 2621 is the same as 2600 2605 2616 2617 2618 2619 2620 2621 Analog Output 3 Label Analog Output 3 Enable Analog Output 3 Register Number Analog Output 3 Lower Limit Analog Output 3 Upper Limit The description for registers 2624 2629 is the same as 2600 2605 2624 2625 2626 2627 2628 2629 Analog Output 4 Label Analog Output 4 Enable Analog Output 4 Register Number Analog Output 4 Lower Limit Analog Output 4 Upper Limit 102 1999 Square D Company All Rights Reserved Range Description 0 32767 Voltage A sag extreme value 1 99999999 Voltage A sag event duration 0 32767 Voltage B sag extreme value 1 99999999 Voltage B sag event duration 0 32767 Voltage C sag extreme value 1 99999999 Voltage C sag event duration 0 32767 Current A sag extreme value 1 99999999 Current A sag event duration 0 32767 Current B sag extreme value 1 99999999 Current B sag event duration 0 32767 Current C sag extreme value 1 99999999 Current C sag event duration 0 32767 Current N sag extreme value 1 99999999 Current N sag event duration Description A four character label used to identify this output Enables or disables this output 0 Off 1 On The circuit monitor register number assigned to this analog output The register value that is equivalent to the minimum output current 0 or 4 mA The register value
79. Bulletin No 30201M9806 SQUARE ID February 1999 LaVergne TN USA Instruction Bulletin Replaces 30201M9301R10 97 dated January 1998 Flower ogic Circuit Monitor Series 2000 Reference Manual AMMETER A CT Primary VOLTMETER L L V PT Primary VOLTMETER L N V Sys Type WATTMETER W NU VARMETER VAr WH Pulse VA METER VA Address POWER FACTOR METER Baud Rato FREQUENCY METER Hz Wom Freq DEMAND AMMETER A Reset DEMAND POWER W Reset DEMAND POWER VA Reset WATTHOUR METER Reset VARHOUR METER Reset THD CURRENT Ret Min Max THD VOLTAGE Set Password K FACTOR Accept iz PowerLogic CIRCUIT MONITOR 1999 Square D Company All Rights Reserved NOTICE Read these instructions carefully and look at the equipment to become familiar with the device before trying to install operate or maintain it The following special messages may appear throughout this bulletin to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure A DANGER Used where there is hazard of severe bodily injury or death Failure to follow a DANGER instruction will result in severe bodily injury or death N WARNING Used where there is hazard of bodily injury or death Failure to follow a WARNING instruction can result in bodily injury or death N CAUTION Used where there is hazard of equipment damage Failure to follow a CA
80. Current Per Phase 3 Avg Neutral Present 0 to 32 767 A Peak 0 to 32 767 A Demand Voltage Per phase amp 30 Avg L N L L Present 0 to 32 767 V Minimum 0 to 32 767 V Peak 0 to 32 767 V Avg Power Factor True 30 Total Present D 0 010 to 1 000 to 0 010 Coincident w kW Peak Coincident w KVAR Peak Coincident w kVA Peak Demand Real Power 3 Total 0 010 to 1 000 to 0 010 0 010 to 1 000 to 0 010 0 010 to 1 000 to 0 010 Present 0 to 3 276 70 MW Predicted 0 to 3 276 70 MW Peak 0 to 3 276 70 MW Coincident kVA Demand Coincident KVAR Demand Demand Reactive Power 3 Total 0 to 3 276 70 MVA 0 to 3 276 70 MVAR Present 0 to 3 276 70 MVAr Predicted 0 to 3 276 70 MVAr Peak 0 to 3 276 70 MVAr Coincident kVA Demand Coincident kW Demand Demand Apparent Power 3 Total 0 to 3 276 70 MVA 0 to 3 276 70 MW Present 0 to 3 276 70 MVA Predicted 0 to 3 276 70 MVA Peak 0 to 3 276 70 MVA Coincident kW Demand Coincident kVAR Demand 0 to 3 276 70 MW 0 to 3 276 70 MVAR Via communications only To be compatible with electric utility billing practices the circuit monitor provides the following types of demand power calculations Thermal Demand Block Interval Demand with Rolling Sub Interval External Pulse Synchronized Demand The default demand calculation method is Thermal Demand The Thermal Demand Method and the Ext
81. Fundamental rms Magnitude Phase B Current Fundamental Coincident Angle Phase C Current Fundamental rms Magnitude Phase C Current Fundamental Coincident Angle Neutral Current Fundamental rms Magnitude Neutral Current Fundamental Coincident Angle Ground Current Fundamental rms Magnitude Ground Current Fundamental Coincident Angle Phase A Voltage Fundamental rms Magnitude Phase A Voltage Fundamental Coincident Angle Phase B Voltage Fundamental rms Magnitude Phase B Voltage Fundamental Coincident Angle Phase C Voltage Fundamental rms Magnitude Phase C Voltage Fundamental Coincident Angle Phase A B Voltage Fundamental rms Magnitude Phase A B Voltage Fundamental Coincident Angle Phase B C Voltage Fundamental rms Magnitude Phase B C Voltage Fundamental Coincident Angle Phase C A Voltage Fundamental rms Magnitude Phase C A Voltage Fundamental Coincident Angle Phase A Fundamental Real Power Reg No Description 1051 THD Phase A Current 1052 THD Phase B Current 1053 THD Phase C Current 1054 1055 THD Phase A Voltage 1056 THD Phase B Voltage 1057 THD Phase C Voltage 1058 THD Phase A B Voltage 1059 THD Phase B C Voltage 1060 THD Phase C A Voltage 1061 thd Phase A Current 1062 thd Phase B Current 1063 thd Phase C Current 1064 1065 thd Phase A Voltage 1066 thd Phase B Voltage 1067 thd Phase C Voltage 1068 thd Phase A B Voltage 1069 thd Phase B C Voltage 1070 thd Phase C A Voltage 1071 K Factor Phase A 1072 K Factor Phase
82. H6 reference H7 magnitude as a percent of H1 magnitude H7 Va angle defined as 0 0 for H7 reference H8 magnitude as a percent of H1 magnitude H8 Va angle defined as 0 0 for H8 reference H9 magnitude as a percent of H1 magnitude H9 Va angle defined as 0 0 for H9 reference H10 magnitude as a percent of H1 magnitude H10 Va angle defined as 0 0 for H10 reference H11 magnitude as a percent of H1 magnitude H11 Va angle defined as 0 0 for H11 reference H12 magnitude as a percent of H1 magnitude H12 Va angle defined as 0 0 for H12 reference H13 magnitude as a percent of H1 magnitude H13 Va angle defined as 0 0 for H13 reference H14 magnitude as a percent of H1 magnitude H14 Va angle defined as 0 0 for H14 reference H15 magnitude as a percent of H1 magnitude H15 Va angle defined as 0 0 for H15 reference H16 magnitude as a percent of H1 magnitude H16 Va angle defined as 0 0 for H16 reference H17 magnitude as a percent of H1 magnitude H17 Va angle defined as 0 0 for H17 reference H18 magnitude as a percent of H1 magnitude H18 Va angle defined as 0 0 for H18 reference H19 magnitude as a percent of H1 magnitude H19 Va angle defined as 0 0 for H19 reference H20 magnitude as a percent of H1 magnitude H20 Va angle defined as 0 0 for H20 reference H21 magnitude as a percent of H1 magnitude H21 Va angle defined as 0 0 for H21 reference H22 magnitude as a percent of H1 magnitude H22 Va angle defined as 0 0 for H22 reference H23 magnitude as a percent of H1 magnit
83. IOM 4444 20 0 1 mA for the IOM 4411 01 and IOM 4444 01 e Register Number The circuit monitor register number assigned to the analog output Lower Limit The register value that is equivalent to the minimum output current 0 or 4 mA e Upper Limit The register value that is equivalent to the maximum output current 1 mA or 20 mA The following are important facts regarding the circuit monitor s analog output capabilities When the register value is below the lower limit the circuit monitor outputs the minimum output current 0 or 4 mA When the register value is above the upper limit the circuit monitor outputs the maximum output current 1 mA or 20 mA N CAUTION HAZARD OF EQUIPMENT DAMAGE Each analog output represents an individual 2 wire current loop Therefore an isolated receiver must be used for each individual analog output from an IOM 4411 and IOM 4444 Failure to observe this precaution can result in equipment damage 1999 Square D Company All Rights Reserved 29 Bulletin No 3020IM9806 February 1999 Analog Output Example 30 Figure 3 5 illustrates the relationship between the output range and the upper and lower limit In this example the analog output has been config ured as follows Output Range 4 20 mA Register Number 1042 Real Power 3 Phase Total Lower Limit 100 kW Upper Limit 500 kW The list below shows the output current at various register readings
84. M 2450 CM 2452 CHAPTER 8 CM 2450 CM 2452 WITH PROGRAMMING LANGUAGE INTRODUCTION DESCRIPTION Circuit monitor models CM 2450 and CM 2452 are designed to run custom ized programs written in the circuit monitor programming language This programming language provides you with the application flexibility to adapt the CM 2450 or CM 2452 to your specialized needs Programs can be de signed to work with all other circuit monitor features extending the overall capabilities of the device A sample CM 2450 program is available from Square D that includes customized features for enhanced data logging Contact POWERLOGIC Engineering Services for information on using the CM 2450 for other applications The CM 2450 circuit monitor programming language uses an easy to understand set of programming commands similar to a compiled BASIC language The programming language includes capabilities such as scheduled tasks e event tasks based on undervoltage over kW math functions Add subtract multiply divide sine cosine square root support for various data types 16 bit signed registers longs floats power factor date time logical operations AND OR XOR NOT shift e for next loops nested IF Else statements gt lt gt lt gt e Subroutine calls 1000 nonvolatile SY MAX read write registers 2000 virtual registers for scratch pad area support for tables of up to 256 items The p
85. NEGATIVE VARS POSTIVE P F LAGGING Quadrant 3 REACTIVE POWER 1 WATTS POSITIVE VARS NEGATIVE P F LAGGING Quadrant 2 WATTS NEGATIVE VARS POSITIVE P F LEADING Normal Power Flow gt REAL POWER WATTS POSITIVE 4 VARS POSTIVE P F LEADING Quadrant 4 WATTS NEGATIVE VARS NEGATIVE P F LAGGING Quadrant 3 Reverse Power Flow REACTIVE POWER 1 WATTS POSITIVE VARS POSITIVE P F LAGGING Normal Power Flow gt REAL POWER WATTS POSITIVE VARS NEGATIVE P F LEADING Quadrant 4 Figure 9 3 Default VAR sign convention 72 1999 Square D Company All Rights Reserved Figure 9 4 Optional VAR sign convention CONDITIONAL ENERGY Command Interface Control Status Input Control Chapter 9 Advanced Topics Circuit monitor registers 1629 1648 are conditional energy registers Conditional energy can be controlled in one of two ways Over the communications link by writing commands to the circuit monitor s command interface OR Byastatus input for example conditional energy accumulates when the assigned status input is on but does not accumulate when the status input is off The following procedures tell how to set up conditional energy for command interface control and for status input control The procedures refer to register numbers and command c
86. None Maximum Value 32767 to 32767 1593 Analog Input 3 None Maximum Value 32767 to 432767 1594 Analog Input 4 None Maximum Value 32767 to 432767 ENERGY VALUES The maximum scaled value of analog input 1 since the last reset of min max values The maximum scaled value of analog input 2 since the last reset of min max values The maximum scaled value of analog input 3 since the last reset of min max values The maximum scaled value of analog input 4 since the last reset of min max values Each energy is kept in 4 registers except Incremental which is kept in 3 registers modulo 10 000 per register ACCUMULATED ENERGY 1601 1604 Real Energy In 3 Phase Total WH 1605 1608 Reactive Energy In 3 Phase Total VArH 1609 1612 Real Energy Out 3 Phase Total WH 1613 1616 Reactive Energy Out 3 Phase Total VArH 1617 1620 Apparent Energy 3 Phase Total VAH 1621 1624 Real Energy Signed Absolute 3 Phase Total WH 1625 1628 Reactive Energy Signed Absolute 3 Phase Total VArH CONDITIONAL ACCUMULATED ENERGY 1629 1632 Conditional Real Energy In 3 Phase Total WH 1633 1636 Conditional Reactive Energy In 3 Phase Total VArH 1637 1640 Conditional Real Energy Out 3 Phase Total WH 1641 1644 Conditional Reactive Energy Out 3 Phase Total VArH 1645 1648 Conditional Apparent Energy 3 Phase Total VAH INCREMENTAL ACCUMULATED ENERGY 1649 1651 Incremental Real Energy In 3 Phase Total WH 1652 1654 Incremental Reactive Energy In 3 Phase Total VArH 16
87. Power Factor 3 phase Total Minimum Real Power Phase A Minimum Real Power Phase B Minimum Real Power Phase C Minimum Real Power 3 Phase Total Minimum Reactive Power Phase A Minimum Reactive Power Phase B Minimum Reactive Power Phase C Minimum Reactive Power 3 Phase Total Minimum Apparent Power Phase A Minimum Apparent Power Phase B Minimum Apparent Power Phase C Minimum Apparent Power 3 Phase Total Minimum THD Phase A Current Minimum THD Phase B Current Minimum THD Phase C Current Minimum THD Neutral Current Minimum THD Phase A Voltage Minimum THD Phase B Voltage Minimum THD Phase C Voltage Minimum THD A B Voltage Minimum THD B C Voltage Minimum THD C A Voltage Minimum K Factor A Minimum K Factor B Minimum K Factor C ANALOG INPUT MIN REGISTERS Appendix B Abbreviated Register Listing Units Range Percent in 10ths 0 to 1000 Percent in 10ths 0 to 1000 Percent in 10ths 0 to 1000 Percent in 10ths 0 to 1000 Percent in 10ths 0 to 1000 Percent in 10ths 0 to 1000 Percent in 10ths 0 to 1000 Percent in 10ths 0 to 1000 In 1000ths 100 to 1000 to 100 In 1000ths 100 to 1000 to 100 In 1000ths 100 to 1000 to 100 In 1000ths 100 to 1000 to 100 In 1000ths 100 to 1000 to 100 In 1000ths 100 to 1000 to 100 In 1000ths 100 to 1000 to 100 In 1000ths 100 to 1000 to 100 kW Scale Factor E 0 to 32 767 kW Scale Factor E 0 to 32 767 kW Scale Factor E 0 to 32 767 kW Scale Factor E 0 to
88. Pulse Initiator This section describes the circuit monitor s pulse output capabilities For instructions on wiring the KYZ pulse output refer to the appropriate instruc tion bulletin Input Output modules IOM 11 IOM 18 IOM 44 IOM 4411 and IOM 4444 are all equipped with one solid state KYZ pulse output contact see table 3 1 on page 17 This solid state relay provides the extremely long life billions of operations required for pulse initiator applications The KYZ output is a Form C contact with a maximum rating of 96 mA Since most pulse initiator applications feed solid state receivers with very low burdens this 96 mA rating is generally adequate For applications where a rating higher than 96 mA is required the IOM 44 provides 3 relays with 10 amp ratings Any of the 10 amp relays can be configured as a pulse initiator output using POWERLOGIC application software Keep in mind that the 10 amp relays are mechanical relays with limited life 10 million operations under no load 100 000 under load The watthour per pulse value can be set from the circuit monitor s front panel When setting the kWH pulse value set the value based on a 3 wire pulse output basis See Setting the Watthour Pulse Output in Chapter 4 of the Circuit Monitor Installation and Operation Bulletin for instructions See Calculating the Watthour Per Pulse Value in this chapter for instructions on calculating the correct value The circuit monitor can be us
89. S cccccecceeeeeeeeeesessssnsescsccceseneecesseeeeeseseeseeaaeseaeasesseseseeaeoeceseesesessseenees Setpoint Driven Alarms isc osea verte ierit ge tas aga ee ati onn o Rie p d VET Leges Ve SIS ass Setpoint Controlled Relay Functions CHAPTER 5 LOGGING e Event OS SUNG sco tete ten decur iti oho eie aimdenigin b EE EEEa E abii ien Event Log Stofabe s eere eo EEE EEE E A hme emp D dap it ederet Data Logging Alarm Driven Data Log Entries Organizing Data Log Files ttt tte diia i i tr eti n a esae aiaiai Storage Considerations E Maintenance Lg entere enm eite sd ticae entestibess apatite sects CHAPTER 6 WAVEFORM CAPTURE 1 eeeeeeeenn nne e nana nina aaa a annes Ra Rasa sa sU PR Ra asas sss assa assa sra assa asa sma 41 4 Cycle Wavetorm Capture ees n Eva p eo e HAPUS e c PH FUHR EMEN EEES 41 Manual Waveform Capture ieeceinideiseieentette niii ti riri betae tete ee Ie Pede Fa ran in in Ta doe ra ee aaa sE iassa 41 Automatic Waveform Capture essei nier tbteten karisina sete rhe eb de tarn iaa ebore da rae satura tese tegis 41 Waveform Strage siiis iosi 43 Extended Event Capture c ccscccscsscscissscsscssitsisciescsssctseccantecdceastctesdusinsdbetedbsnteteastieesssdiedandtodississietisstesiasisenssnseatevted 44 Manual Event CapEbute sto de ceci rir tee eet ete e aede c EE
90. Setpt Alarm Period was Last Entered 784 789 Present Set Date Time 790 795 Date Time of Calibration STATUS INPUTS Appendix B Abbreviated Register Listing Units Sec Min Hour Day Month Yr Sec Min Hour Day Month Yr Sec Min Hour Day Month Yr Sec Min Hour Day Month Yr Sec Min Hour Day Month Yr Sec Min Hour Day Month Yr Sec Min Hour Day Month Yr Sec Min Hour Day Month Yr Day Month Yr Sec Min Hour Sec Min Hour Day Month Yr Sec Min Hour Day Month Yr Sec Min Hour Day Month Yr Sec Min Hour Day Month Yr Sec Min Hour Day Month Yr Range Same as Regs 700 705 Same as Regs 700 705 Same as Regs 700 705 Same as Regs 700 705 Same as Regs 700 705 Same as Regs 700 705 Same as Regs 700 705 Same as Regs 700 705 Regs 700 705 Same as Same as Regs 700 705 Same as Regs 700 705 Same as Regs 700 705 Same as Regs 700 705 Same as Regs 700 705 2400 Input Status None 2401 Input Conditional Energy Control None 2402 2403 Input 1 Label None 2404 2405 Input 1 Count Counts 2406 Input 1 On Timer Seconds 2407 2408 Input 2 Label None 2409 2410 Input 2 Count Counts 2411 Input 2 On Timer Seconds 0000 to OOFF Hex 0000 to OOFF Hex Alpha Numeric 4 Chars 0 to 99 999 999 0 to 32 767 Alpha Numeric
91. UTION instruction can result in damage to equipment Note Provides additional information to clarify or simplify a procedure PLEASE NOTE Electrical equipment should be serviced only by qualified electrical maintenance personnel and this document should not be viewed as sufficient for those who are not otherwise qualified to operate service or maintain the equipment discussed Although reasonable care has been taken to provide accurate and authoritative information in this document no responsibility is assumed by Square D for any consequences arising out of the use of this material FCC NOTICE This equipment complies with the requirements in Part 15 of FCC rules for a Class A computing device Operation of this equipment in a residential area may cause unacceptable interference to radio and TV reception requiring the operator to take whatever steps are necessary to correct the interference TECHNICAL SUPPORT For technical support contact the Power Management Operation Technical Support Center Hours are 7 30 A M to 4 30 P M Central Time Monday through Friday Phone 615 287 3400 Fax 615 287 3404 BBS 615 287 3414 Email PMOSUPRT SquareD com POWERLOGIC SY MAX SY NET SY LINK POWER ZONE VISI VAC ISO FLEX and are Registered Trademarks of Square D Company SYSTEM MANAGER and CIRCUIT TRACKER are Trademarks of Square D Company Windows Windows NT and Windows 95 are Registered Trademarks of Microsoft Corpor
92. V 240V 3020 IOM 11 1 status IN 1 KYZ pulse OUT 11 VA 15 VA 3020 IOM 18 8 status IN 1 KYZ pulse OUT 11 VA 15 VA 3020 IOM 44 4 status IN 1 KYZ pulse OUT 3 Form C relay OUT 14 VA 20 VA 3020 IOM 4411 01 4 status IN 1 KYZ pulse OUT 3 Form C relay OUT 1 Analog IN 1 Analog OUT 0 1 mA 20 VA 25 VA 3020 IOM 4411 20 4 status IN 1 KYZ pulse OUT 3 Form C relay OUT 1 Analog IN 1 Analog OUT 4 20 mA 20 VA 25 VA 3020 IOM 4444 01 4 status IN 1 KYZ pulse OUT 3 Form C relay OUT 4 Analog IN 4 Analog OUT 0 1 mA 21 VA 27 V 3020 IOM 4444 20 4 status IN 1 KYZ pulse OUT 3 Form C relay OUT 4 Analog IN 4 Analog OUT 4 20 mA 21 VA 27 V wire See Analog Inputs in this chapter for more information Analog Inputs are 0 5 Vdc Each analog input can be independently configured to accept a 4 20 mA input by connecting an external jumper 1999 Square D Company All Rights Reserved Bulletin No 3020IM9806 February 1999 STATUS INPUTS 18 The circuit monitor s I O modules offer 1 4 or 8 status inputs see table 3 1 on the previous page Status inputs can be used to detect breaker status count pulses count motor starts and so on The following are important points about the circuit monitor s status inputs 1999 Square D Company All Rights Reserved The circuit monitor maintains a counter of the total transitions for each status input Status input S2 is a high speed stat
93. alues are reset 66 1999 Square D Company All Rights Reserved Setting Scale Factors cont To change scale factors do the following 1 Determine the required scale factors Chapter 9 Advanced Topics There are 5 scale groups The desired scale factor for each group must be determined The following is a listing of the available scale factors for each of the 5 user defined scale groups The factory default for each scale group is 0 If you need either an extended range or more resolution you can select any of the available scale factors to suit your need Scale Group A Phase Current Scale Factor Amps 0 327 67A 0 3276 7 A 0 32767 A Scale Group B Neutral Current Amps 0 327 67A 0 3276 7 A 0 32767 A 0 327 67 kA Scale Group C Ground Current Amps 0 327 67A 0 3276 7 A 0 32767 A 0 327 67 kA Scale Group D Voltage L L L N Voltage 0 3276 7 V 0 32767 V 0 327 67 kV 0 3276 7 kV Scale Group E Power kW kVAR kVA Power 0 32 767 kW kVAR kVA 0 327 67 kW KVAR kVA 0 3276 7 kW kVAR kVA 0 32767 kW kVAR kVA 0 327 67 MW MVAR MVA 0 3276 7 MW MVAR MVA 0 32767 MW MVAR MVA 2 Using POWERLOGIC application software read the existing scale factors from registers 2020 2024 and write them down Register 2020 Scale Group A Register 2021 Scale Group B Register 2022 Scale Group C Register 2023 Scale Group D Register 2024 Scale Group E 3 Make note of the changes requi
94. and TETTE Generic Demand Voltage Demand Eneroy Readings crs en EE a A A RM UE AGE Power Analysis Values CHAPTER 3 INPUT OUTPUT CAPABILITIES Input Output Modes sasssa a i RUE e tet d nues A EI Ee ber eo EE R Status Mputa M Demand Synch Pulse Input iccccc cscscscsecsiccsccscescectecssetensetsteaseihdvseseestbenssvseutonastesvtsteesecustestesieciecuarseetseasenestecirentes Analog Inputs ere ERU un edited tette i ra sie die es bel tuti tesa amiss Analog Input Example isse diese tinieciietestteite dini ie deris oiean ie E aniier aaaeaii Eanan 21 Relay Output Operating Modes cese iecte ciis es ticket bett seras be eb ded eb es Febre aatri isiin 22 Mechanical Relay OUtptuts ione e ioc entren DH HERO HEUS nete 24 Setpoint Controlled Relay Functions enirn nitent nitetntnbente nt nse tede ta tubo edet tanks bester tache tbe eo cina 25 Sold State KYZ Pulse O tpUut inii diam anta dA bte n dee tete ntn 26 2 W we Pulse InlBatot ica ori i dir pr Ee ERI EOHH URN CICER RE UBER RAS LER GE de e T 26 3 Wire Pulse InitiatOE ear d xit re r Boh et riv e dede e ied 27 Calculating the Watthour Per Pulse Value issiima rit hei de beet tinens 28 Purlhraeinii M 29 Analog Output Example treten ttr tetti tri e eR Niisiis tl etae nia 30 1999 Square D Company All Rights Reserved i Bulletin No 3020IM9806 February 1999 CHAPTER 4 ALARM FUNCTION
95. ar Factor 7 lagging Range of Power 8 leading Factor Values SQUARE D COMPANY Note Assumes a positive power flow Figure 2 1 Power factor min max example Quadrant 2 WATTS NEGATIVE VARS NEGATIVE 1 WATTS POSITIVE VARS NEGATIVE P F LAGGING P F LEADING lt Reverse Power Flow Normal Power Flow gt WATTS NEGATIVE VARS POSTIVE P F LAGGING Quadrant 3 WATTS POSITIVE VARS POSTIVE P F LEADING Quadrant 4 REACTIVE POWER REAL POWER REACTIVE POWER Quadrant Quadrant 2 1 WATTS NEGATIVE WATTS POSITIVE VARS POSITIVE VARS POSITIVE P F LEADING P F LAGGING Reverse Power Flow Normal Power Flow gt REAL POWER WATTS NEGATIVE VARS NEGATIVE WATTS POSITIVE VARS NEGATIVE P F LAGGING P F LEADING Quadrant Quadrant 3 4 Figure 2 2 Default VAR sign convention 1999 Square D Company All Rights Reserved Figure 2 3 Alternate VAR sign convention 11 Bulletin No 3020IM9806 February 1999 DEMAND READINGS Demand Power Calculation Methods 12 The circuit monitor provides a variety of demand readings including coincident readings and predicted demands Table 2 2 lists the available demand readings and their reportable ranges Table 2 2 Demand Readings Demand Reading Reportable Range Demand
96. are as storage locations for e Units for example KWH kVARH or kVAH Weight factor a weight factor for each pulse For example you might define that each pulse is equal to 10 0 kW Scale Code a scale factor to indicate what power of 10 to apply to the weight factor The pulse demand interval can be chosen to synchronize all channels with the power demand interval block only the incremental energy interval a status input transition or by external communications Figure 9 5 page 79 shows how you might apply the pulse demand metering feature In the example channels 1 2 have been assigned to count pulses from inputs S1 and S2 respectively Channel 10 has been assigned inputs S1 and S2 Therefore channel 10 will totalize the pulses from S1 and S2 Refer to Appendix B Abbreviated Register Listing for information on registers 2898 2999 78 1999 Square D Company All Rights Reserved Chapter 9 Advanced Topics Channel 1 Units KWH Present Demand Pulse Count Weight Factor Last Completed Interval Pulse Count 10 KWH per pulse Peak Demand Pulse Count Date Time of Peak lt q Input S1 Channel 2 Units KWH Present Demand Pulse Count Weight Factor Last Completed Interval Pulse Count 10 KWH per pulse Peak Demand Pulse Count Date Time of Peak lt q Input S2 e e e e Channel 10 Units KWH Present Demand Pulse Count Weight Factor Last Completed Interval Pulse Count 10 KWH per
97. ase A alarm view the Phase A Current Observe the location of the decimal point in the displayed value and determine if either the Kilo or Mega light is turned on This reading can be used to determine the scaling required for alarm setpoints The location of the decimal point in the displayed quantity indicates the resolution that is available on this metering quantity There can be up to 3 digits to the right of the decimal point indicating whether the quantity is stored in a register as thousandths hundredths tenths or units The Kilo or Mega LED indicates the engineering units Kilowatts or Megawatts that are applied to the quantity The alarm setpoint value must use the same resolution as shown in the display 1999 Square D Company All Rights Reserved 117 Bulletin No 3020IM9806 February 1999 ALARM CONDITIONS AND ALARM NUMBERS For example consider a power factor alarm If the 3 phase average power factor is 1 000 meaning that the power factor is stored in thousandths enter the alarm setpoints as integer values in thousandths Therefore to define a power factor setpoint of 0 85 lagging enter 850 the sign indi cates lag For another example consider a Phase A B Undervoltage alarm If the V ap reading is displayed as 138 00 with the Kilo LED turned on then enter the setpoints in hundredths of kilovolts Therefore to define a setpoint of 125 000 volts enter 12 500 hundredths o
98. ata e Sag swell alarm priority e Pickup setpoint in amps or volts e Pickup delay in cycles e Dropout setpoint in amps or volts e Dropout delay in cycles e Data and waveform logging instructions Relay output actions Note Relays which are specified to be operated by high speed status input events should not be operated by standard events or high speed sag swell events Unpredictable relay operation will result Requires circuit monitor firmware version 15 002 or higher 1999 Square D Company All Rights Reserved 55 Bulletin No 3020IM9806 February 1999 MULTIPLE WAVEFORM RETRIEVAL SMS 3000 SMS 1500 or PMX 1500 SMS 770 SMS 700 EXP 550 or EXP 500 POWERLOGIC application software can be used to retrieve multiple waveform information for later analysis When a set of multiple continuous 12 cycle waveform captures are triggered they are stored in the circuit monitor as individual 12 cycle recordings Using SMS 3000 SMS 1500 or PMX 1500 software you can retrieve a continuous 12 60 cycle extended event capture figure 7 5 L POWERLOGIC System Manager New Workspace Imported Waveform We PIEI EI Eile Edit View Setup Control Display Reports Tools Window Help lj x aj Oly sj xj zo E oi Bal SompingMode MANUAL r5 oe Nen Phase B N Voltage T l Tm Mun Wee Phase A C a L TT 4574 e C Current Ready ONLINE Square D Plan EDIT
99. ation Other names are trademarks or service marks of their respective companies 1999 Square D Company All Rights Reserved Please fill out detach and mail the postage paid card below Fill out only one registration card even if you have purchased multiple POWERLOGIC devices Registration Card Register your POWERLOGIC OR POWERLINK product today and get Free expert technical phone support just call 615 287 3400 Notice of product upgrades and new product releases Notice of special product offers and price discounts Name Dept Title Company Mailing Address City State Country Zip Postal Code Email Address Telephone Fax Product Purchased Through Distributor Please tell us how many of each of the following products you have Circuit Monitors Q 1 5 Q 6 20 L 21 50 Q 51 100 Q 100 Power Meters Q 1 5 Q 6 20 Q 21 50 Q 51 100 Q 100 Are you interested in receiving information on POWERLOGIC Application Software Q Yes Q No 1999 Square D Company All Rights Reserved BUSINESS REPLY MAIL FIRST CLASS MAIL PERMIT NO 635 PALATINE IL POSTAGE WILL BE PAID BY ADDRESSEE SQUARE D COMPANY 295 TECH PARK DR STE 100 LA VERGNE TN 37086 9908 NO POSTAGE NECESSARY IF MAILED IN THE UNITED STATES Contents CONTENTS CHAPTER 1 INTRODUCTION ice cesses ccssececd sic cckceececcecetcecccds ceed lancedseccsausdoedesceuconcaves suaausesssesccescecesssvecunccuddstsauce 1 What
100. ays for Circuit Monitor Internal Control Overriding an Output Relay Releasing an Overridden Relay For the circuit monitor to automatically control relays based on alarm conditions or as a pulse initiator output you must configure the relays for circuit monitor internal control To configure relays for circuit monitor internal control do the following 1 Write a bitmap see below to the command parameter register specifying the relays to be setup for internal control Reg Value Description 7701 Bitmap Bitmap corresponding to relays to be placed under internal control Bit 1 corresponds to KYZ Bit 2 corresponds to Relay 1 Bit 3 corresponds to relay 2 Bit 4 corresponds to relay 3 2 Write a command code 3311 to the circuit monitor s command interface register 7700 7700 3311 Command code to configure relay for internal control It is possible to override a circuit monitor output relay set up for circuit monitor internal control Once overridden the specified relays will respond to manual control To override relays do the following 1 Write a bitmap see below to the command parameter register specifying the relays to be overridden Reg Value Description 7701 Bitmap Bitmap corresponding to relays to be placed under override control Bit 1 corresponds to KYZ Bit 2 corresponds to Relay 1 Bit 3 corresponds to relay 2 Bit 4 corresponds to relay 3 2 Write a command code 3341 to the ci
101. can perform harmonic magnitude and angle calculations for each metered input The harmonic magnitude can be formatted as either a percentage of the fundamental or as a percentage of the rms values The harmonic magnitude and angles are stored in a set of registers 4002 4447 The circuit monitor updates the values in these registers over a 10 metering update cycle period During the time that the circuit monitor is refreshing harmonic data the circuit monitor posts a value of 0 in register 2037 When the whole set of harmonic registers is updated with new data the circuit monitor posts a value of 1 in register 2037 The circuit monitor can be configured to hold the values in these registers for up to 60 metering update cycles once the data processing is complete There are three operating modes for harmonic data processing disabled voltage only and voltage and current Because of the extra processing time necessary to perform these calculations the factory default operating mode is disabled Write to the following registers to configure the harmonic data processing Reg No Value Description 2033 1 60 Number of metering update cycles between harmonic data updates 2034 0 1 Harmonic magnitude formatting 0 of fundamental default 1 of rms 2035 0 1 2 Harmonic processing 0 disabled 1 voltage harmonics only enabled 2 voltage and current harmonics enabled Register 2037 indicates whether harmonic data processing is complete 2037
102. cates that the reading is invalid by displaying N A or asterisks When the input voltage is above five volts the maximum input voltage the circuit monitor reports the upper limit 1999 Square D Company All Rights Reserved Analog Input Example Chapter 3 Input Output Capabilities Figure 3 2 shows an analog input example In this example the analog input has been configured as follows Upper Limit 500 Lower Limit 100 Offset Voltage 1 Volt Units PSI The table below shows circuit monitor readings at various input voltages Input Voltage Circuit Monitor Reading 5V 32 768 invalid 1V 100 PSI 2V 200 PSI 25V 250 PSI 5V 500 PSI 55V 500 PSI Circuit Monitor Reading Upper sp0 pei _ n Limit 500 PSI Lower Limit 100 PSI Input 1V 5V Voltage f Offset Maximum Input voltage Voltage Not User Definable Figure 3 2 Analog input example 1999 Square D Company All Rights Reserved 21 Bulletin No 3020IM9806 February 1999 RELAY OUTPUT OPERATING MODES 22 Before we describe the 10 available relay operating modes it is important to understand the difference between a relay configured for remote external control and a relay configured for circuit monitor internal control Each mechanical relay output must be configured for one of the following 1 Remote external control the relay is controlled either from a PC usi
103. cifies Command Interface as the source Bit 6 indicates which mechanism controls cond energy 0 indicates status inputs default 1 indicates command I F Bit 7 indicates status of conditional energy accumulation 0 indicates Cond Energy Accum is off default 1 indicates Cond Energy Accum is on Bit 8 is unused Bit 9 indicates status of Unit 1 response to enquire 0 indicates response is enabled default 1 indicates response is disabled Bit 10 indicates whether front comm port is enabled 0 indicates front comm port is enabled default 1 indicates front comm port is disabled Bit 11 indicates whether front panel setup is enabled 0 indicates front panel setup is enabled default 1 indicates front panel setup is disabled Bit 12 indicates status of log and wfc files master enable 0 indicates files are enabled default 1 indicates files are disabled All other bits are unused Reg No Name 2083 Present Day of the Week 2085 Square D Product I D Number equal to 460 for CMA Model A 2088 On board non volatile memory 2091 Prior PLOS Rev Sub Level 2092 Prior PLOS Revision Level 2093 PLOS Rev Sublevel 2094 Firmware Revision Level 2123 CT Phase Shift Correction 1 Amp 2124 CT Phase Shift Correction 5 Amps Reg No Name GENERIC DEMAND 2200 Generic Demand Reset Selection 2201 Generic Demand interval 2202 2204 Date Time of last generic demand maximum minimum reset 2205 2224 Selected registers of quantities to perform generic de
104. condition occurs The 12 to 60 cycles of captured data do not correspond with the sample data taken at the beginning of the update cycle The captured data is taken from later in the metering update cycle therefore the 12 to 60 cycles of captured data may not contain the same data that triggered the standard setpoint but rather the data immediately following For automatic recording of disturbances such as sags and swells see Chapter 7 The circuit monitor must be set up for automatic setpoint controlled waveform capture using POWERLOGIC application software To set up the circuit monitor you must do three things 1 Select an alarm condition See Appendix D for a listing of alarm conditions 2 Define the setpoints 3 Select the check box for automatic waveform capture Repeat these steps for the desired alarm conditions For specific instructions on selecting alarm conditions defining setpoints and specifying an alarm condition for automatic waveform capture refer to the POWERLOGIC application software instruction bulletin 46 1999 Square D Company All Rights Reserved Extended Event Capture Storage Chapter 6 Waveform Capture Circuit monitor model 2250 stores 12 cycle event captures differently than models 2350 and higher store 12 to 60 cycle event captures The lists below describe how each model stores extended event captures CM 2250 Stores only one captured 12 cycle event Each new event captu
105. d drives programmable controllers PCs and data communication networks are all susceptible to transient power problems After the electrical system is interrupted or shut down determin ing the cause may be difficult 1999 Square D Company All Rights Reserved 49 Bulletin No 3020IM9806 February 1999 DESCRIPTION CONT There are several types of voltage disturbances each may have different origins and require a separate solution For example a momentary interrup tion occurs when a protective device interrupts the circuit feeding the customer s facility Swells and overvoltages are also a concern as they can accelerate equipment failure or cause motors to overheat Perhaps the biggest power quality problem facing industrial and commercial facilities is the momentary voltage sag caused by faults on remote circuits A voltage sag is a brief 1 2 cycle to 1 minute decrease in rms voltage magnitude A sag is typically caused by a remote fault somewhere on the power system often initiated by a lightning strike In figure 7 1 the fault not only causes an interruption to plant D but also results in voltage sags to plants A B and C Thus system voltage sags are much more numerous than interruptions since a wider part of the distribution system is affected And if reclosers are operating they may cause repeated sags The waveform in figure 7 2 shows the magnitude of a voltage sag which persists until the remote fault is cl
106. d file Resize Clear All refer to the appropriate POWERLOGIC application software instruction bulletin Allocation Capture Memory Resize Clear All After Setup of Multiple Waveform Capture is Complete Table 7 2 Multiple 12 Cycle Waveform Capture No of Back to Back No of Continuous Required Value 12 Cycle Waveform Cycles Recorded in Real gister 7298 Captures per Trigger per Trigger 1 12 1 20 24 2 30 36 3 40 48 4 50 60 5 PowerLogic System Manager sal File Edit SetUp Control Display Reports Macro Window Help Online CM2450 def rank C SMS V221 Sampling Manual e ev sexi Davicac 2450 eL ie On Board Data Storage 2450 Event Log Data Logs Events 100 Log Number Quantities Fil Frequency 12 Cycle Waveform See fo Temperature FIFO C Fill Hold Current A Waveform Capture Logs Offset Time 0 Sycle Captures 1 Interval 0 FIFO Min CHr e An ee RMS 12 Cycle Captures Records fo e eons B FIFO C Fill Hold Current Unbalance C Aocated Memory 76 Download Settings Unselect All Upload Settings Log Template Resize Clear All More Done View File Statistics Template Event Lag Ready eee Figure 7 4 POWERLOGIC System Manager SMS 770 O
107. d to analyze energy and power usage against present or future utility rates The informa tion is especially useful for doing what ifs with time of use rate structures When using the incremental energy feature keep the following points in mind Peak demands help minimize the size of the data log in cases of sliding or rolling demand Shorter incremental energy periods make it easier to reconstruct a load profile analysis Since the incremental energy registers are synchronized to the circuit monitor clock it is possible to log this data from multiple circuits and perform accurate totalization Incremental energy accumulation begins at the specified start date and offset time Once the start date has arrived a new incremental energy period begins at the specified offset time Incremental energy calculations continue around the clock at the specified interval However a new incremental energy calculation will begin each new day at the offset time regardless of where it is in the present interval For example Offset time 8 00 a m Interval 14 hours The first incremental energy calculation will be from 8 00 a m to 10 00 p m 14 hours The next interval will be from 10 00 p m to 8 00 a m the next day even though that interval will only be 10 hours This is because 8 00 a m is 74 1999 Square D Company All Rights Reserved CHANGING THE DEMAND CALCULATION METHOD Changing to the Block Rolling Method
108. e is large enough to hold 60 entries so that you could look back over the last hour s voltage readings Data Log 2 Voltage current and power logged hourly for a historical record over a longer period Data Log 3 Energy logged once daily File is large enough to hold 31 entries so that you could look back over the last month and see daily energy use Data Log 4 Report by exception file File contains data log entries that are forced by the occurrence of an alarm condition See Alarm Driven Data Log Entries above Note The same data log file can support both scheduled and alarm driven entries Data log file 1 is pre configured at the factory with a sample data log which records several parameters hourly This sample data log can be reconfigured to meet your specific needs 38 1999 Square D Company All Rights Reserved Storage Considerations Chapter 5 Logging The following are important storage considerations Circuit monitor model CM 2150 or higher is required for on board data logging For circuit monitor models CM 2150 and CM 2250 the total storage capacity must be allocated between the event log and up to 14 data logs For circuit monitor model 2350 and higher the total data storage capacity must be allocated between an event log a 4 cycle waveform capture log an extended event capture log and up to 14 data logs Circuit monitor standard models CM 2150 CM 2250 CM 2350 and CM 2450 store up to 51
109. eared Utility Circuit Breakers With Reclosers Plant A Utilit Transforme T Plant B Plant C Plant D T Fault Phase B N Voltage 174 87 174 Figure 7 1 A fault near plant D that is cleared by the utility circuit breaker can still affect plants A B and C resulting in a voltage sag 50 Figure 7 2 Voltage sag caused by a remote fault and lasting 5 cycles The disturbance monitoring capabilities of the CM 2350 CM 2450 and CM 2452 can be used to Identify number of sags swells interruptions for evaluation Compare actual sensitivity of equipment to published standards Compare equipment sensitivity of different brands contactor dropout drive sensitivity etc Distinguish between equipment failures and power system related problems 1999 Square D Company All Rights Reserved Chapter 7 Disturbance Monitoring Diagnose mysterious events such as equipment failure contactor dropout computer glitches etc Determine the source user or utility of sags swells Develop solutions to voltage sensitivity based problems using actual data Accurately distinguish between sags and interruptions with accurate time date of occurrence Use waveform to determine exact disturbance characteristics to compare with equipment sensitivity Provide accurate data in equipment specification ride through etc Discuss protection practices with s
110. ed in 2 wire or 3 wire pulse initiator applica tions Each of these applications is described below Most energy management system digital inputs use only two of the three wires provided with a KYZ pulse initiator This is referred to as a 2 wire pulse initiator application Figure 3 3 shows a pulse train from a 2 wire pulse initiator application Refer to this figure when reading the following points e Ina 2 wire application the pulse train looks like alternating open and closed states of a Form A contact Most2 wire KYZ pulse applications use a Form C contact but tie into only one side of the Form C contact The pulse is defined as the transition from OFF to ON of one side of the Form C relay In figure 3 3 the transitions are marked as 1 and 2 Each transition represents the time when the relay flip flops from KZ to KY At points 1 and 2 the receiver should count a pulse e na2 wire application the circuit monitor can deliver up to 5 pulses per second 26 1999 Square D Company All Rights Reserved 3 Wire Pulse Initiator Chapter 3 Input Output Capabilities Some pulse initiator applications require all three wires provided with a KYZ pulse initiator This is referred to as a 3 wire pulse initiator application Figure 3 4 shows a pulse train for a 3 wire pulse initiator application Refer to this figure when reading the following points e 3 wire KYZ pulses are defined as transitions between KY and KZ
111. eg No 4303 4304 4305 4306 4307 4308 4309 4310 4311 4312 4313 4314 4315 4316 4317 4318 4319 Phase C Current 4320 4321 4322 4323 4324 4325 4326 4327 4328 4329 4330 4331 4332 4333 4334 4335 4336 4337 4338 4339 4340 4341 4342 4343 4344 4345 4346 4347 4348 4349 4350 4351 4352 4353 4354 4355 4356 4357 Description H23 angle with reference to H23 Va angle H24 magnitude as a percent of H1 magnitude H24 angle with reference to H24 Va angle H25 magnitude as a percent of H1 magnitude H25 angle with reference to H25 Va angle H26 magnitude as a percent of H1 magnitude H26 angle with reference to H26 Va angle H27 magnitude as a percent of H1 magnitude H27 angle with reference to H27 Va angle H28 magnitude as a percent of H1 magnitude H28 angle with reference to H28 Va angle H29 magnitude as a percent of H1 magnitude H29 angle with reference to H29 Va angle H30 magnitude as a percent of H1 magnitude H30 angle with reference to H30 Va angle H31 magnitude as a percent of H1 magnitude H31 angle with reference to H31 Va angle Reserved H1 magnitude as a percent of H1 magnitude H1 angle with reference to H1 Va angle H2 magnitude as a percent of H1 magnitude H2 angle with reference to H2 Va angle H3 magnitude as a percent of H1 magnitude H3 angle with reference to H3 Va angle H4 magnitude as a percent of H1 magnitude H4 angle with reference to H4 Va angle H5 magnitude as a percent of H1 magnitude H5 a
112. egister Listing Range The date and time in registers 1800 1802 are stored as follows Other dates and times through register 1877 are stored in an identical manner Register 1800 Month byte 1 1 12 Day byte 2 1 31 Register 1801 Year byte 1 0 199 Hour byte 2 0 23 Register 1802 Minutes byte 0 59 Seconds byte 0 59 The year is zero based on the year 1900 in anticipation of the 21st century e g 1989 would be represented as 89 and 2009 would be represented as 109 1800 1802 1803 1805 1806 1808 1809 1811 1812 1814 1815 1817 1818 1820 1821 1823 1824 1826 1827 1829 1830 1832 1833 1835 1836 1838 1839 1841 1842 1844 1845 1847 1848 1850 Last Restart Date Time Date Time Demand of Peak Current Phase A Date Time Demand of Peak Current Phase B Date Time Demand of Peak Current Phase C Date Time of Peak Demand Average Real Power Date Time of Last Reset of Peak Demand Current Date Time of last Min Max Clear of Instantaneous Values Date Time of Last Write to Circuit Tracker Setpoint Register Date Time When Peak Power Demand Was Last Reset Date Time When Accumulated Energy Was Last Cleared Date Time When Control Power Failed Last Date Time When Level 1 Energy Mgmt Setpt Alarm Period Was Last Entered Date Time When Level 2 Energy Mgmt Setpt Alarm Period Was Last Entered Date Time When Level 3 Energy Mgmt Setpt Alarm Per
113. el 6 The definitions for registers 2960 2969 are the same as for 2900 2909 except that they apply to channel 7 The definitions for registers 2970 2979 are the same as for 2900 2909 except that they apply to channel 8 The definitions for registers 2980 2989 are the same as for 2900 2909 except that they apply to channel 9 The definitions for registers 2990 2999 are the same as for 2900 2909 except that they apply to channel 10 CIRCUIT MONITOR UTILITY REGISTERS 6800 6999 Utility Registers None 0 to 32 767 104 These read write registers can be used by the application programmer as required They are saved in non volatile memory when the circuit monitor loses control power 1999 Square D Company All Rights Reserved Reg No Description 5611 5612 5613 5614 5615 5616 5617 5618 5619 5620 5621 5622 5623 5624 5780 5781 5782 5783 5784 5785 5786 5787 5788 5789 5790 5791 5792 5793 5794 5795 5796 5797 5798 5799 5800 5801 5802 5803 5804 5805 5806 5807 5808 5809 5810 5811 5812 5813 5814 5815 5816 5817 5818 5819 5820 Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No
114. elect the Clear option For detailed instructions see Clearing the Priority 1 Log in Chapter 4 of the Circuit Monitor Installation and Operation Bulletin Phase Reversal 36 1999 Square D Company All Rights Reserved Pickup and dropout setpoints and delays do not apply to phase reversal The phase reversal alarm occurs when the phase voltage waveform rotation differs from the default phase rotation The circuit monitor assumes that an ABC phase rotation is normal If a CBA phase rotation is normal the user must change the circuit monitor s phase rotation from ABC default to CBA See Chapter 9 Advanced Topics When the phase reversal alarm occurs the circuit monitor operates any specified relays Relays configured for normal mode operation remain closed until the phase reversal alarm clears To release any relays that are in latched mode enter the circuit monitor s Alarm mode and select the Clear option For detailed instructions see Clearing the Priority 1 Log in Chapter 4 of the Circuit Monitor Installation and Operation Bulletin CHAPTER 5 LOGGING CHAPTER CONTENTS EVENT LOGGING Event Log Storage Chapter 5 Logging Ind cadboui p EER 37 Event Log StOfagesacuadundaotenimet eis NRI UTR AER SERENO I ed 37 org 38 Alarm Driven Data Log Entries esce retener rrr errem 38 Organizing Data Log Files datio teet EE 38 Storage Considerations eani FER HERE ERR E LEES EE E Eas 39 Mai
115. ements Ke 0 2 kWH pulse Summary e 3 wire basis 0 2 kWH pulse will provide approximately 2 pulses per second at full scale e 2 wire basis 0 1 kWH pulse will provide approximately 2 pulses per second at full scale To convert to the KWH pulse required on a 2 wire basis divide Ke by 2 This is necessary since the circuit monitor Form C relay generates two pulses KY and KZ for every pulse that is counted on a 2 wire basis 28 1999 Square D Company All Rights Reserved Chapter 3 Input Output Capabilities ANALOG OUTPUTS The circuit monitor supports analog outputs through the use of optional input output modules I O modules IOM 4411 20 and IOM 4444 20 offer one and four 0 20 mA analog outputs respectively I O modules IOM 4411 01 and IOM 4444 01 offer one and four 0 1 mA analog outputs respectively Table 3 1 on page 17 lists the available input output modules This section describes the circuit monitor s analog output capabilities For technical specifications and instructions on installing the modules refer to page 6 of the Circuit Monitor Installation and Operation Bulletin To setup analog outputs application software is required Using POWERLOGIC application software the user must define the following values for each analog output e Analog Output Label A four character label used to identify the output Output Range The range of the output current 4 20 mA for the IOM 4411 20 and
116. emory must be allocated among an event log 1 to 14 data logs a waveform capture log and an extended event capture log Specifics for each model are described below CM 2050 Provides no nonvolatile logging memory CM 2150 CM 2250 Available nonvolatile logging memory must be allo cated among an event log and 1 to 14 data logs CM 2350 CM 2450 CM 2452 Available nonvolatile logging memory must be allocated among an event log 1 to 14 data logs a waveform capture log and an extended event capture log When using POWERLOGIC application software to set up a circuit monitor the choices you make for the items listed below directly affect the amount of memory used The number of data log files 1 to 14 The quantities logged in each entry 1 to 97 for each data log file The maximum number of entries in each data log file The maximum number of events in the event log file The maximum number of waveform captures in the waveform capture file The maximum number of extended event captures in the extended event capture file 1999 Square D Company All Rights Reserved 69 Bulletin No 3020IM9806 February 1999 Total Circuit Monitor Non Volatile Memory The number you can enter for each of the above items depends on the amount of the memory that is still available The amount of memory still available depends on the numbers you ve already assigned to the other items Figure 9 1 below shows how the memory
117. en the percentage ratio of the smallest current to the largest current is equal to or below the pickup setpoint for the specified pickup delay in seconds When the phase loss current alarm occurs the circuit monitor operates any specified relays Relays configured for normal mode operation remain closed until the phase loss current alarm clears The phase loss current alarm clears when the ratio of the smallest current to the largest current remains above the dropout setpoint for the specified dropout delay in seconds To release any relays that are in latched mode enter the circuit monitor s Alarm mode and select the Clear option For detailed instructions see Clearing the Priority 1 Log in Chapter 4 of the Circuit Monitor Installation and Operation Bulletin Phase Loss Voltage Pickup and dropout setpoints are entered in volts The phase loss voltage alarm occurs when any voltage value but not all voltage values is equal to or below the pickup setpoint for the specified pickup delay in seconds When the phase loss voltage alarm occurs the circuit monitor operates any specified relays Relays configured for normal mode operation remain closed until the phase loss voltage alarm clears The alarm clears when one of the follow ing is true all of the phases remain above the dropout setpoint for the specified dropout delay in seconds OR all of the phases drop below the phase loss pickup setpoint
118. er 4 Alarm Functions for more information The circuit monitor can be set up to auto matically capture and save four cycles of waveform data associated with an alarm condition 1999 Square D Company All Rights Reserved 41 Bulletin No 3020IM9806 February 1999 Setting Up the Circuit Monitor The circuit monitor must be set up for automatic waveform capture using POWERLOGIC application software To set up the circuit monitor for automatic waveform capture perform the following steps 1 Select an alarm condition See Appendix D for a listing of alarm conditions 2 Define the setpoints This may not be necessary if the selected alarm is a status input change for example 3 Select the automatic waveform capture option Repeat these steps for the desired alarm conditions For specific instructions on selecting alarm conditions and specifying them for automatic waveform capture refer to the POWERLOGIC application software instruction manual How it Works At the beginning of every update cycle the circuit monitor acquires four cycles of sample data for metering calculations figure 6 1 During the update cycle the circuit monitor performs metering calculations and checks for alarm conditions If the circuit monitor sees an alarm condition it performs any actions assigned to the alarm condition These actions can include automatic waveform capture forced
119. er s demand interval window The circuit monitor does this by watching status input S1 for a pulse from the other demand meter When it sees a pulse it starts a new demand interval and calculates the demand for the preceding interval The circuit monitor then uses the same time interval as the other meter for each demand calculation Figure 3 1 illustrates this point When in this mode the circuit monitor will not start or stop a demand interval without a pulse The maximum allowable time between pulses is 60 minutes If 61 minutes pass before a synch pulse is received the circuit monitor throws out the demand calculations and begins a new calculation when the next pulse is received Once in synch with the billing meter the circuit monitor can be used to verify peak demand charges Important facts about the circuit monitor s demand synch feature are listed below The demand synch feature can be activated from the circuit monitor s front panel To activate the feature enter a demand interval of zero See Setting the Demand Interval in Chapter 4 of the Circuit Monitor Installa tion and Operation Bulletin for instructions When the circuit monitor s demand interval is set to zero the circuit monitor automatically looks to input S1 for the demand synch pulse The synch pulse output on the other demand meter must be wired to circuit monitor input S1 Refer to the appropriate I O Module instruction bulletin for wiring instructions
120. ernal Synch Pulse method can be set up from the circuit monitor faceplate See Setting the Demand Interval in Chapter 4 of the Circuit Monitor Installation and Operation Bulletin for setup instructions Other demand calculation methods can be set up over the communications link A brief description of each demand method follows 1999 Square D Company All Rights Reserved Demand Power Calculation Methods cont Predicted Demand Peak Demand Chapter 2 Metering Capabilities Thermal Demand The thermal demand method calculates the demand based on a thermal response and updates its demand calculation every 15 seconds on a sliding window basis The user can select the demand interval from 5 to 60 minutes in 5 minute increments See Setting the Demand Interval in Chapter 4 of the Circuit Monitor Installation and Operation Bulletin for instructions Block Interval Demand The block interval demand mode supports a standard block interval and an optional subinterval calculation for compatibility with electric utility elec tronic demand registers In the standard block interval mode the user can select a demand interval from 5 to 60 minutes in 5 minute increments See Setting the Demand Interval in Chapter 4 of the Circuit Monitor Installation and Operation Bulletin for instructions The demand calculation is performed at the end of each interval The present demand value displayed by the circuit monitor is the value for the la
121. erving utility and request changes to shorten duration of potential sags reduce interruption time delays on protective devices Justify purchase of power conditioning equipment Work with utility to provide alternate stiffer services alternate design practices Table 7 1 below shows the capability of the CM 2350 CM 2450 and CM 2452 to measure power system electromagnetic phenomena as defined in IEEE Recommended Practice for Monitoring Electric Power Quality Table 7 1 Circuit Monitor Electromagnetic Phenomena Measurement Capability Category Capability Transients Impulsive N A Oscillatory N A Short Duration Variations Instantaneous Momentary Temporary Long Duration Variations Voltage Imbalance Waveform Distortion eh RS Voltage Fluctuations Power Frequency Variations v Circuit monitor not intended to detect phenomena in this category Through the 31st harmonic 1999 Square D Company All Rights Reserved 51 Bulletin No 3020IM9806 February 1999 OPERATION MULTIPLE WAVEFORM SETUP SMS 3000 SMS 1500 or PMX 1500 The circuit monitor calculates rms magnitudes based on 16 data points per cycle every 1 2 cycle This ensures that even single cycle duration rms variations are not missed When the circuit monitor detects a sag or swell it can perform the following actions The event log can be updated with a sag swell pickup event date time stamp with 1 milli
122. ervoltage alarm clears The overvoltage alarm clears when the phase voltage remains below the dropout setpoint for the specified dropout delay period To release any relays that are in latched mode enter the circuit monitor s Alarm mode and select the Clear option For detailed instructions see Clearing the Priority 1 Log in Chapter 4 of the Circuit Monitor Installation and Operation Bulletin Unbalance Current Pickup and dropout setpoints are entered in tenths of percent based on the percentage difference between each phase current with respect to the aver age of all phase currents For example enter an unbalance of 16 0 as 160 The unbalance current alarm occurs when the phase current deviates from the average of the phase currents by the percentage pickup setpoint for the specified pickup delay in seconds When the unbalance current alarm occurs the circuit monitor operates any specified relays Relays configured for normal mode operation remain closed until the unbalance current alarm clears The unbalance current alarm clears when the percentage difference between the phase current and the average of all phases remains below the dropout setpoint for the specified dropout delay period To release any relays that are in latched mode enter the circuit monitor s Alarm mode and select the Clear option For detailed instructions see Clearing the Priority 1 Log in Chapter 4 of the Circuit Monitor Installation and Operation
123. es in 100ths In 10ths of degrees Range 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 10000 0 10000 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 109 Bulletin No 3020IM9806 February 1999 Reg No Description 4218 H13 magnitude as a percent of H11 magnitude 4219 H13 angle with reference to H13 Va angle 4220 H14 magnitude as a percent of H1 magnitude 4221 H14 angle with reference to H14 Va angle 4222 H15 magnitude as a percent of H1 magnitude 4223 H15 angle with reference to H15 Va angle 4224 H16 magnitude as a percent of H1 magnitude 4225 H16 angle with reference to H16 Va angle 4226 H17 magnitude as a percent of H1 magnitude 4227 H17 angle with reference to H17 Va angle 4228 H18 magnitude as a percent of H1 magnitude 4229 H18 angle with reference to H18 Va angle 4230 H19 magnitude as a percent of H1 magnitude 4231 H19 angle with reference to H19 Va angle 4232 H20 magnitude as a percent of H1 magnitude 4233 H20 angle with reference to H20 Va angle 4234 H21 magnitude as a percent of H1 magnitude 4235 H21 angle with reference to H21 Va angle 4236 H22 magnitude as a percent of H1 magnitude 4237 H22 angle with reference to H22 Va angle 42
124. escribes using a circuit monitor to make an extended event capture with 64 points per cycle resolution simultaneously on all channels when triggered by an external device such as an undervoltage relay This chapter describes how to continuously monitor for disturbances on the current and voltage inputs of circuit monitor models 2350 2450 and 2452 Models 2350 2450 and 2452 can perform continuous monitoring of rms magnitudes of any of the metered channels of current and voltage These calculations can be used to detect sags or swells on these channels Momentary voltage disturbances are becoming an increasing concern for industrial plants hospitals data centers and other commercial facilities Modern equipment used in many facilities tends to be more sensitive to voltage sags and swells as well as momentary interruptions POWERLOGIC Circuit Monitors can help facility engineers diagnose equipment problems resulting from voltage sags or swells identify areas of vulnerability and take corrective action The interruption of an industrial process due to an abnormal voltage condi tion can result in substantial costs to the operation which manifest them selves in many ways labor costs for cleanup and restart lost productivity damaged product or reduced product quality delivery delays and user dissatisfaction The entire process can depend on the sensitivity of a single piece of equip ment Relays contactors adjustable spee
125. eseesebess 9 Min Max Values tereti certe te Ree Aves 10 Demand Redding Ss scatet ep a dece m eit reir eed 12 Demand Power Calculation Methods eene 12 Predicted Dernmatid uni c er irte riri er i Cir Pul vv osani Lures 13 Peak Demand ettet eei en a ee ue e 13 Generic Demand sinon ne RETE DEREN 14 Energy Readings srren narra noT e E TEE Et 14 Power Analysis Values edet e aer e ferr teer abeo 15 The circuit monitor measures currents and voltages and reports rms values for all three phases and neutral ground current In addition the circuit monitor calculates power factor real power reactive power and more Table 2 1 lists the real time readings and their reportable ranges Table 2 1 Real Time Readings Real Time Reading Reportable Range Current Per Phase 0 to 32 767 A Neutral 0 to 32 767 A Ground 0 to 32 767 A 3 Phase Average 0 to 32 767 A Apparent rms 0 to 32 767 A Current Unbalance 0 to 100 Voltage Line to Line Per Phase Line to Neutral Per Phase 3 Phase Average Voltage Unbalance Real Power 3 Phase Total Per Phase Reactive Power 3 Phase Total Per Phase Apparent Power 3 Phase Total Per Phase Power Factor True 0 to 3 276 700 V 0 to 3 276 700 V 0 to 3 276 700 V 0 to 100 0 to 3 276 70 MW 0 to 3 276 70 MW 0 to 3 276 70 MVAr 0 to 3 276 70 MVAr 0 to 3 276 70 MVA 0 to 3 276 70 MVA 3 Phase Total 0 010 to 1 000 to 0 010 Per Phase
126. f H1 magnitude 4301 H22 angle with reference to H22 Va angle 4302 H23 magnitude as a percent of H1 magnitude 110 1999 Square D Company All Rights Reserved Units in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths Range 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 10000 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 R
127. f degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees Range 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 10000 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 111 Bulletin No 3020IM9806 February 1999 Reg No 4358 4359 4360 4361 4362 4363 4364 4365 4366 4367 4368 4369 4370 4371 4372 4373 4374 4375 4376 4377 4378 4379 4380 4381 4382 4383 Neutral Current 4384 4385 4386 4387 4388 4389 4390 4391 4392 4393 4394 4395 4396 4397 4398 4399 4400 4401 4402 4403 4404 4405 4406 4407 4408 4409 4410 4411 44
128. f kV To arrive at this value first convert 125 000 volts to 125 00 kilovolts then multiply by 100 This section lists the circuit monitor s predefined alarm conditions For each alarm condition the following information is provided Alarm No A code number used to refer to individual alarms Alarm Description A brief description of the alarm condition Test Register The register number that contains the value where applicable that is used as the basis for a compari son to alarm pickup and dropout settings Units The units that apply to the pickup and dropout settings Scale Group The Scale Group that applies to the test register s metering value A F For a description of Scale Groups see Setting Scale Factors for Extended Metering Ranges in Chapter 9 Alarm Type A reference to a definition providing details on the operation and configuration of the alarm For a description of alarm types refer to Alarm Type Definitions page 121 Alarm No Alarm Description Test Register Units Scale Group Alarm Type 01 Over Current Phase A 1003 Amps A A 02 Over Current Phase B 1004 Amps A A 03 Over Current Phase C 1005 Amps A A 04 Over Current Neutral 1006 Amps B A 05 Over Current Ground 1007 Amps C A 06 Under Current Phase A 1003 Amps A B 07 Under Current Phase B 1004 Amps A B 08 Under Current Phase C 1005 Amps A B 09 Current Unbalance Phase A 1010 Tenths 96 A 10 Current Unbalance Phase B 1011 Tenths A 11 Current Unbalance
129. f the states of the Outputs A 1 On a 0 Off Bit 1 represents the KYZ Output bits 2 4 represent relays R1 R3 respectively Register 235 is ghosted as Read Only and does not provide control Bit Map indicating active Relay Control states The lower byte indicates the status of internal external control A 1 Relay Control is under internal control and a O Relay Control is under external control The upper byte indicates the status of override control A 1 Relay Control is in override and a O Relay Control is not in override For each byte Bit 1 represents the KYZ pulse output and bits 2 4 represent relays R1 R3 respectively Label for KYZ output KYZ Output Mode Register 0 Normal 1 Latched 2 Timed 3 Absolute kWH pulse 4 Absolute kVArH pulse 5 kVAH pulse 6 kWH in pulse 7 kVarH in pulse 8 kWH out pulse 9 kVArH out pulse This register specifies the time the KYZ output is to remain closed for timed mode Reg No Name 2506 2507 2508 2509 2510 2511 2512 2513 2514 2515 2516 2517 2518 2519 2520 2521 KYZ Output kWH kVArH or kVAH Pulse Register Relay R1 Label Relay R1 Mode Reg Relay R1 Parameter Register Relay R1 kWH kVArH or kVAH Pulse Register Relay R2 Label Relay R2 Mode Reg Relay R2 Parameter Register Relay R2 kWH kVArH or kVAH Pulse Register Relay R3 Label Relay R3 Mode Reg Relay R3 Parameter Register Relay R3
130. ge of 1 5 volts across the resistor Refer to the appropriate I O module instruction bulletin for instructions on connecting the jumper wire To setup analog inputs application software is required Using POWERLOGIC application software the user must define the following values for each analog input e Units A six character label used to identify the units of the monitored analog value for example PSI e Input Type 0 5 V or 4 20 mA Tells the circuit monitor whether to use the default calibration constants or the alternate calibration constants for the internal 250 ohm resistor e Upper Limit The value the circuit monitor reports when the input voltage is equal to 5 volts the maximum input voltage Lower Limit The value the circuit monitor reports when the input voltage is equal to the offset voltage defined below Offset Voltage The lowest input voltage in hundredths of a volt that represents a valid reading When the input voltage is equal to this value the circuit monitor reports the lower limit defined above e Precision The precision of the measured analog value for example tenths of degrees Celsius This value represents what power of 10 to apply to the upper and lower limits The following are important facts regarding the circuit monitor s analog input capabilities When the input voltage is below the offset voltage the circuit monitor reports 32 768 POWERLOGIC application software indi
131. her the input is wired to a 0 5 V source or a 4 20 mA source using the internal 250 ohm resistor 0 0 5 1 4 20 The lowest input voltage in hundredths of a volt that represents a valid reading When the input voltage is equal to this value the circuit monitor reports the lower limit defined in register 2706 The value the circuit monitor reports when the input voltage is equal to the offset voltage defined in register 2705 The value the circuit monitor reports when the input voltage is equal to 5 volts the maximum input voltage 1999 Square D Company All Rights Reserved 103 Bulletin No 3020IM9806 February 1999 Reg No Name Units Range STATUS INPUT PULSE DEMAND METERING Description Note Registers 2898 2999 apply to circuit monitor models CM 2150 and higher only 2898 2899 2900 2901 2903 2904 2905 2906 2907 2909 2910 2919 2920 2929 2930 2939 2940 2949 2950 2959 2960 2969 2970 2979 2980 2989 2990 2999 Pulse Demand Interval Mode None No of Pulse Demand Intervals None Channel 1 Status Input Pulse None Demand Bit Map Utility Registers None Present Interval Pulse Count Counts Channel 1 Last Interval Pulse Count Counts Channel 1 Peak Interval Pulse Count Counts Channel 1 Date Time of Peak Interval Month Day Yr Pulse Count Channel 1 Hr Min Sec 0 to 3 0 to 32 767 0 to FF 32 767 to 32 767 0 to 32 767
132. his mode only the kVARH flowing out of the load is considered 1999 Square D Company All Rights Reserved 23 Bulletin No 3020IM9806 February 1999 MECHANICAL RELAY OUTPUTS Input Output module IOM 44 provides three Form C 10 A mechanical relays that can be used to open or close circuit breakers annunciate alarms and more Table 3 1 on page 17 lists the available Input Output modules optional Circuit monitor mechanical output relays can be configured to operate in one of 10 operating modes Normal Latched electrically held Timed e Absolute kWH pulse e Absolute kVArH pulse kVAH pulse e kWH in pulse kVARH in pulse kWH out pulse kVAr out pulse See the previous section for a description of the modes The last seven modes in the above list are for pulse initiator applications Keep in mind that all circuit monitor Input Output modules provide one solid state KYZ pulse output rated at 96 mA The solid state KYZ output provides the long life billions of operations required for pulse initiator applications The mechanical relay outputs have limited lives 10 million operations under no load 100 000 under load For maximum life use the solid state KYZ pulse output for pulse initiation except when a rating higher than 96 mA is required See Solid State KYZ Pulse Output in this chapter for a description of the solid state KYZ pulse output 24 1999 Square D Company All Rights Reserved
133. imum Current Phase C 1406 Maximum Current Neutral 14 1407 Maximum Current Ground I5 1408 Maximum Current 3 Phase Average 1409 Maximum Current Apparent rms 1410 Maximum Current Unbalance Phase A 1411 Maximum Current Unbalance Phase B 1412 Maximum Current Unbalance Phase C 1413 Maximum Current Unbalance Worst 1414 Maximum Voltage Phase A to B 1415 Maximum Voltage Phase B to C 1416 Maximum Voltage Phase C to A 1417 Maximum Volt L L 3 Phase Average 1418 Maximum Voltage Phase A to Neutral 1419 Maximum Voltage Phase B to Neutral 1420 Maximum Voltage Phase C to Neutral 1421 Maximum Volt L N 3 Phase Average 1422 Maximum Volt Unbalance Phase A B 1423 Maximum Volt Unbalance Phase B C 1424 Maximum Volt Unbal Phase C A 1425 Maximum Volt Unbal L L Worst 1426 Maximum Volt Unbal Phase A 1427 Maximum Volt Unbal Phase B 1428 Maximum Volt Unbal Phase C 1429 Maximum Volt L N Unbal Worst 1431 Maximum True Power Factor A 1432 Maximum True Power Factor B 1433 Maximum True Power Factor C 1434 Maximum True Power Factor 3 Phase Total 1435 Maximum Displ Power Factor Phase A 1436 Maximum Displ Power Factor Phase B 1437 Maximum Displ Power Factor Phase C 1438 Maximum Displ Power Factor 3 Phase Total 1439 Maximum Real Power Phase A 1440 Maximum Real Power Phase B 1441 Maximum Real Power Phase C 1442 Maximum Real Power 3 Total 1443 Maximum Reactive Power Phase A 1444 Maximum Reactive Power Phase B 1445 Maximum Reactive Po
134. ing all over under and phase unbal ance alarm conditions require that you define setpoints Other alarm conditions such as status input transitions and phase reversals do not require setpoints For those alarm conditions that require setpoints you must define the following information Pickup Setpoint e Pickup Delay in seconds Dropout Setpoint e Dropout Delay in seconds For instructions on setting up alarm relay functions from the circuit monitor front panel see Setting Up Alarm Relay Functions in Chapter 4 of the Circuit Monitor Installation and Operation Bulletin To understand how the circuit monitor handles setpoint driven alarms see figure 4 2 Figure 4 1 shows what the actual event log entries for figure 4 2 might look like as displayed by POWERLOGIC application software Note The software does not actually display the codes in parentheses EV1 EV2 Max1 Max2 These are references to the codes in figure 4 2 1999 Square D Company All Rights Reserved 31 Bulletin No 3020IM9806 February 1999 Max1 On Board Event Log cm2350 Datefim Event Value Condition Forced Log Entry EV1 21 08 23 95 06 49 22 000 AM Over Current B Pickup LWFC 4 i M22 08 23 95 06 49 22 000 AM Over Current C T Pickup LWFC 4 E EV2 23 08 23 95 06 49 26 000 AM Over Current C 48 Dropout 24 08 23 95 06 49 37 000 AM Over Current B 61 Dropout z el z Max2 Figure 4 1
135. iod Was Last Entered Present Set Date Time Date Time of Calibration Date Time of Peak K Factor Demand A Product 1999 Square D Company All Rights Reserved Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec See Above Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 Same as Regs 1800 1802 91 Bulletin No 3020IM9806 February 1999 Reg No Description Units Range 1851 1853 Date Time of Peak K Factor Demand B Product Month Day Yr Same as Hr Min Sec Regs 1800 1802 1854 1856 Date Time of Pea
136. ion on scale factors The per phase undervoltage alarm occurs when the per phase voltage is equal to or below the pickup setpoint long enough to satisfy the specified pickup delay in seconds When the undervoltage alarm occurs the circuit monitor operates any specified relays Relays configured for normal mode operation remain closed until the under voltage alarm clears The undervoltage alarm clears when the phase voltage remains above the dropout setpoint for the specified dropout delay period 1999 Square D Company All Rights Reserved 33 Bulletin No 3020IM9806 February 1999 Setpoint Controlled Relay Functions cont To release any relays that are in latched mode enter the circuit monitor s Alarm mode and select the clear option For detailed instructions see Clearing the Priority 1 Log in Chapter 4 of the Circuit Monitor Installation and Operation Bulletin Overvoltage Pickup and dropout setpoints are entered in volts Very large values may require scale factors Refer to Setting Scale Factors for Extended Meter ing Ranges in Chapter 9 for more information on scale factors The per phase overvoltage alarm occurs when the per phase voltage is equal to or above the pickup setpoint long enough to satisfy the specified pickup delay in seconds When the overvoltage alarm occurs the circuit monitor operates any specified relays Relays configured for normal mode operation remain closed until the ov
137. is a listing of command codes that can be written to the command interface register 7700 and to the command interface parameter registers 7701 7709 Code Parameter s 1110 None 1310 Sec Min Hr Day Mo Yr 2110 Scale Factors A E 2120 CT ratio correction factors A B C N 2130 PT ratio correction factors A B C 2310 Unit Address 2320 Baud Rate 2325 None 2326 None 2330 None 2331 None 2340 None 2341 None 2350 None 2351 None 2360 None 2361 None 2370 None 2371 None 3310 Bit Map Relay Designation 3311 Bit Map Relay Designation 3320 Bit Map Relay Designation 3321 Bit Map Relay Designation 3340 Bit Map Output Designation 3341 Bit Map Output Designation 62 1999 Square D Company All Rights Reserved Description Resets the circuit monitor Command code to set date and time Change scale factors A E and reset min max registers file Then reset unit Change CT ratio correction factors Change PT ratio correction factors Change unit s address to the address specified and reset unit Change unit s baud rate to the baud rate specified and reset unit Set communication to even parity default Set communication to no parity Enable unit 01 s response to the SY MAX enquire transmission default Disable unit 01 s response to the SY MAX enquire transmission Set control of conditional energy to status inputs default Set control of conditional energy to command Interface Enable front
138. is the Circuit Monitor i223 e ce eee es ee Se Reg 1 Expa ded Memory deis r E A A E A H 3 Reguirements Tor USIng annsna i a Quedan d E E R E 4 Identifying the Series and Firmware Revisions ccsssesssseseseesesseseesessseseenessseseeessssseseessssseseensssseseeneases 4 Model NUimbe tsi RR 4 Upgrading Existing Circuit Momnitors c cccicsccciscacccsscississcssscsnsessectensetsceesetiesisesssdsenieatensotterisenssntustunasesienseate 5 Memory Options Summary s p isis retta teta tceboe decet et tube ie eee babe enne datas eras eodera aeneae Eataa 5 Safety Precautions enoar tcd PEE ERE menie na ttem ect n dete e es ietit rede 6 Usine Thus BUEH esen HOHER EG HER EUER UE Hte IER DE ei eto eei erte dtt 6 Nootational Conventions 5i itecto a tete bc Ur rette e p e ettet iria 6 Topics Not Covered EIere s mener apre REED A i 7 Related Doc tmeftits aec EERE OEE i bt p n EO e NIKE Ieri ris rp tinet e cerei us 7 Fax OncDenmand 5 rte ierat ets beet eee phe e desees i re bes ben RR 7 Installation and Operation Bulletin ertet mtn necerais 8 CHAPTER 2 METERING CAPABILITIES 1 e eese eeeceeeeee nennt ne nnn nna nn nnns aaa a nass a snas asas nnmnnn ennaa 9 Real Time Reading e 9 huc AVE Ve CI ee Demand Readings T Demand Power Calculation Methods Predicted Demand sieo e ie ERU SG es Peak Dem
139. it 7 should read 1 when the status input is on indicating that conditional energy accumulation is on To clear all conditional energy registers 1629 1648 E Write command code 6220 to register 7700 1999 Square D Company All Rights Reserved 73 Bulletin No 3020IM9806 February 1999 INCREMENTAL ENERGY Using Incremental Energy The circuit monitor s incremental energy feature allows you to define a start time and time interval for incremental energy accumulation At the end of each incremental energy period the following information is available WHIN during the last completed interval reg 1649 1651 e VARH IN during the last completed interval reg 1652 1654 WH OUT during the last completed interval reg 1655 1657 VARH OUT during the last completed interval reg 1658 1660 e VAH during the last completed interval reg 1661 1663 Date time of the last completed interval reg 1869 1871 Peak kW demand during the last completed interval reg 1749 Date Time of Peak kW during the last interval reg 1878 1880 e Peak kVAR demand during the last completed interval reg 1750 Date Time of Peak kVAR during the last interval reg 1881 1883 Peak kVA demand during the last completed interval reg 1751 e Date Time of Peak kVA during the last interval reg 1884 1886 The incremental energy data listed above can be logged by the circuit monitor This logged data provides all the information neede
140. itor returns a high negative value for example 31 794 This happens because bit 16 1 for example the binary equivalent of 31 794 is 1000001111001110 To get a value in the range 0 to 1000 you need to mask bit 16 You do this by adding 32 768 to the value An example will help clarify Assume that you read a power factor value of 31 794 Convert this to a power factor in the range 0 to 1 000 as follows 31 794 32 768 974 974 1000 974 lagging power factor The circuit monitor offers two VAR sign conventions Figure 9 3 shows the default sign convention Figure 9 4 shows the alternate sign convention The procedures below tell how to change the sign convention using the command interface For a description of the command interface and a complete listing of command codes see The Command Interface in this chapter To change to the alternate sign convention complete the following steps 1 Write command code 4311 to register 7700 2 Write command code 1110 to register 7700 This resets the circuit monitor causing it to use the new convention To return to the default sign convention complete the following steps 1 Write command code 4310 to register 7700 2 Write command code 1110 to register 7700 This resets the circuit monitor causing it to return to the default sign convention Quadrant 2 WATTS NEGATIVE VARS NEGATIVE P F LEADING lt Reverse Power Flow WATTS
141. k K Factor Demand C Product Month Day Yr Same as Hr Min Sec Regs 1800 1802 1857 1859 Date Time of Peak Reactive Demand Power Month Day Yr Same as Hr Min Sec Regs 1800 1802 1860 1862 Date Time of Peak Apparent Demand Power Month Day Yr Same as Hr Min Sec Regs 1800 1802 1863 1865 Incremental Energy Start Time of Day Month Day Yr Same as Hr Min Sec Regs 1800 1802 1866 1868 Date Time when Conditional Energy Last Cleared Month Day Yr Same as Hr Min Sec Regs 1800 1802 1869 1871 Incremental Energy Last Update Date Time Month Day Yr Same as Hr Min Sec Regs 1800 1802 1872 1874 Date Time of Peak 3 Phase Avg Current Demand Month Day Yr Same as Hr Min Sec Regs 1800 1802 1875 1877 Date Time of Peak Neutral Current Demand Month Day Yr Same as Hr Min Sec Regs 1800 1802 Reg No Description Units Range 1878 1880 Date Time of Peak Real Power Demand Last Incremental Energy Period Month Day Yr Same as Hr Min Sec Regs 1800 1802 1881 1883 Date Time of Peak Reactive Power Demand Last Incremental Energy Period Month Day Yr Same as Hr Min Sec Regs 1800 1802 1884 1886 Date Time of Peak Apparent Power Demand Last Incremental Energy Period Month Day Yr Same as Hr Min Sec Regs 1800 1802 1887 1892 Reserved Month Day Yr Same as Hr Min Sec Regs 1800 1802 1893 1898 Present Date Time 6 register format Sec Min Hr Same as DATE TIME Expanded 6 registers
142. l Ground In 10 000ths 5 000 20 000 2013 PT Ratio Correction Factors Phase A In 10 000ths 5 000 20 000 2014 PT Ratio Correction Factors Phase B In 10 000ths 5 000 20 000 2015 PT Ratio Correction Factors Phase C In 10 000ths 5 000 20 000 2016 Nominal System Frequency Reg No Name Units Range Description 2020 Scale Group A None 2 to 1 Scale Group A Ammeter Per Phase Ammeter Per 2 scale by 0 01 Phase 1 scale by 0 10 O scale by 1 00 default 1 scale by 10 0 2021 Scale Group B None 2 to 1 Scale Group B Ammeter Neutral Ammeter Neutral 96 2 scale by 0 01 1 scale by 0 10 O scale by 1 00 default 1 scale by 10 0 1999 Square D Company All Rights Reserved Reg No Name Units 2022 Scale Group C None Ammeter Ground 2023 Scale Group D None Voltmeter 2024 Scale Group E None kwattmeter kVarmeter kVa 2025 Scale Group F None Frequency 2027 Energy Resolution None on Front Panel Reg No Name 2028 Command Password 2029 Display Setup Password 2031 Reset Access Password 2032 Limited Access Disable Bit Mask 2038 Sag Swell Suspend Bit map Range 2to 1 1to2 3 to 3 1to2 10 13 20 23 Units Range Appendix B Abbreviated Register Listing Description Scale Group C Ammeter Ground 2 scale by 0 01 1 scale by 0 10 O scale by 1 00 default 1 scale by 10 0 Scale Group D Voltmeter 1 scale by 0 10 O scale by 1 00 default 1 scale by 10 0 2 scale by
143. larm will dropout Pickup and Dropout setpoints can be positive or negative delays are in seconds The Voltage and Current Swell alarms will occur whenever the continuous RMS calculation is above the pickup setpoint and remains above the pickup setpoint for the specified number of cycles When the continuous RMS calculations fall below the dropout setpoint and remain below the setpoint for the specified number of cycles the alarm will drop out Pickup and Dropout setpoints are positive delays are in cycles The Voltage and Current Sag alarms will occur whenever the continuous RMS calculation is below the pickup setpoint and remains below the pickup setpoint for the specified number of cycles When the continuous RMS calculations rise above the dropout setpoint and remain above the setpoint for the specified number of cycles the alarm will drop out Pickup and Dropout setpoints are positive delays are in cycles The suspended sag swell alarm will occur whenever an excessive amount of current or voltage sag swell alarms occur typically due to erroneous alarm setpoints If more than six of any one type of sag or swell alarm occurs within 500 ms the disturbance monitoring detection in the circuit monitor will be suspended for approximately 8 seconds The disturbance detection will then resume If the disturbance detection is immediately suspended a second time the user will have to clear register 2038 and re enable the sag swell alarms 1
144. lass x 0 2 Accuracy Class x x x x Alarm Relay Functions x x x x On board Data Logging x x x x Downloadable Firmware x x x x Date Time for Each Min Max x x x x Waveform Capture x x x Extended Event Capture x x x Extended Memory up to 1 1 Meg x x x x Sag Swell Detection x x Programmable for Custom Applications x Standard memory CM 21 New Series G4 50 CM 2250 CM 2350 and CM 2450 100K CM 2452 356K or higher circuit monitor models CM 2150 and higher now are factory equipped with 100 kilobytes 100K of nonvolatile memory Earlier Series G3 models CM 2150 and CM 2250 shipped with 11K of memory models CM 2350 and CM 2450 with 100K of memory 1999 Square D Company All Rights Reserved Bulletin No 3020IM9806 February 1999 EXPANDED MEMORY cont Requirements for Using Expanded Memory Identifying the Series and Firmware Revisions Model Numbers For applications where additional memory is required you can order a circuit monitor with an optional 512K or 1024K memory expansion card resulting in 612K or 1124K respectively total nonvolatile memory 100K base memory plus the expansion card memory Memory upgrade kits are also available for most earlier circuit monitors See Upgrading Existing Circuit Monitors page 5 System Manager software version 3 02 with Service Update 1 3 02a with Service Update 1 or 3 1 or higher is required to take advantage of expan sion
145. ll data log files must be smaller than 182 272 Note The log file worksheet will provide a close approximation of the required memory allocation The memory allocation worksheet results may differ slightly from actual memory allocation requirements Applies to circuit monitor series G4 or later 1999 Square D All Rights Reserved 115 Bulletin No 3020IM9806 February 1999 Data log 1 Calculate the Size of the Event Log File Data log 2 1 Multiply the maximum number of events by 8 Data log 3 Data log 4 Calculate the Sizes of the Data Log Files Data log5 Repeat steps 2 7 for each data log file Data log 6 2 Multiply the number of cumulative energy readings by 4 2 o o M us 3 Multiply the number of incremental energy readings by 3 S RENE Data log 9 4 Enter the number of non energy meter readings 4 Data log 10 5 Add lines 2 3 and 4 5 Data log 11 6 Add3to the value on line 5 For date time of each entry 6 Data log 12 5 7 Multiply line 6 by the maximum number of records in the data Datalogi3 log file Enter the result in the data log box to the left Data tog 14 Repeat steps 2 7 for each data log file TOTAL 9 9 Total all data log files and enter the result here 9 Calculate the Size of the Waveform Capture Log File 10 For CM 2350s and higher only multiply the maximum number of waveform captures by 2 560 For CM 2150s and CM 2250s enter zero he
146. lues can be reset by using POWERLOGIC application software The minimum and maximum values can be reset by resetting the peak current demand values or through the command interface using command 5112 see Command Interface in Chapter 9 Com mand 5112 will reset only the generic demand minimums and maximums The circuit monitor is pre configured to perform a demand calculation on voltage using the generic demand capability Generic demand registers 2230 2253 automatically contain the values of the present voltage demand values along with the corresponding minimums and maximums The date and time for the minimum and peak voltage demands are located in registers 1900 1941 These quantities can be viewed using POWERLOGIC application software The circuit monitor provides energy values for KWH and kVARH which can be displayed on the circuit monitor or read over the communications link Table 2 3 Energy Readings Energy Reading 3 Phase Reportable Range D Reportable Front Panel Front Panel Display Accumulated Energy Real Signed Absolute 0 to 9 999 999 999 999 999 WHR 000 000 kWH to 000 000 kWH to 000 000 MWh Reactive Out Apparent Accumulated Energy Incremental Real In Real Out Reactive In Reactive Out Apparent 0 to 9 999 999 999 999 999 VARH 0 to 9 999 999 999 999 999 VAH 0 to 999 999 999 999 WHR 0 to 999 999 999 999 WHR 0 to 999 999 999 999 VARH 0 to 999 999 999 999 VARH 0 to
147. m 12 to 60 cycles of data from the buffer into the memory allocated for extended event captures You can specify from 2 to 10 pre event cycles This allows extended captures from 2 pre event and from 10 to 58 post event cycles to 10 pre event and from 2 to 50 post event cycles For specific instructions on setting the number of pre event and post event cycles refer to the POWERLOGIC application software instruction bulletin 1999 Square D Company All Rights Reserved 45 Bulletin No 3020IM9806 February 1999 Automatic Extended Capture Initiated by a Standard Setpoint Setting Up the Circuit Monitor Trigger Point l PowerLogic System Manager 2450 Thu Aug 24 11 08 08 1995 File Edit SetUp Display Reports Macro Window K 2 gt K 10 Post Event Cycles gt Pre Event Cycles Figure 6 3 12 cycle event capture example initiated from a high speed input S2 Figure 6 3 shows a 12 cycle event capture In this example the circuit moni tor was monitoring a constant load when a motor load started causing a current inrush The circuit monitor was set up to capture 2 pre event and 10 post event cycles The circuit monitor can detect over 100 alarm conditions such as metering setpoint exceeded and status input changes see Chapter 4 Alarm Functions The circuit monitor can be set up to save from 12 to 60 cycles of waveform data associated with the update cycle during which an alarm
148. mand calculations 2225 2229 Reserved None Bytes None None None None Degrees in 100ths Degrees in 100ths Minutes Mo Day Yr Hr Min Sec None Appendix B Abbreviated Register Listing Range 0to 6 0 to 3000 0 to 1131 0 to 9999 01 00 to 99 99 0 to 9999 01 00 to 99 99 1000 to 1000 1000 to 1000 Range 5 60 Same as Regs 1800 1802 Regs 1001 1199 2000 2999 3000 3999 4000 5199 1999 Square D Company All Rights Reserved Description Present Day of the Week 0 Sunday 1 Monday 2 Tuesday 3 Wednesday 4 Thursday 5 Friday 6 Saturday Square D Product I D Number equal to 460 for 2050 461 for 2150 462 for 2250 463 for 2350 464 for 2450 465 for 2452 Amount of on board non volatile memory present Prior PLOS revision sublevel before last firmware download Zero if not appli cable Prior PLOS revision level before last firmware download Zero if not appli cable PLOS revision sublevel used for diagnostic purposes only Firmware Revision Level in decimal The first two digits after the equal sign represent the revision of the reset boot code The last two digits represent the revision of the downloadable PLOS code CT phase shift compensation at 1 Amp CT phase shift compensation at 5 Amps Description Generic Demand Reset Selection 0 CMD 5110 amp 5112 1 CMD 5112 only Interval for generic demand calculati
149. mand value 18 2284 2286 The definitions for registers 2284 2286 are the same as for 2230 2232 except that they apply to generic demand value 19 2287 2289 The definitions for registers 2287 2289 are the same as for 2230 2232 except that they apply to generic demand value 20 Reg No Description Units Range DATE TIME GENERIC DEMAND PEAKS AND MINIMUMS FOR FIRST 10 VALUES 1900 1902 Date Time of Peak Demand Value 1 Month Day Yr Same as Hr Min Sec Regs 1800 1802 1903 1905 Date Time of Minimum Demand Value 1 Month Day Yr Same as Hr Min Sec Regs 1800 1802 1906 1908 Date Time of Peak Demand Value 2 Month Day Yr Same as Hr Min Sec Regs 1800 1802 1909 1911 Date Time of Minimum Demand Value 2 Month Day Yr Same as Hr Min Sec Regs 1800 1802 1912 1914 Date Time of Peak Demand Value 3 Month Day Yr Same as Hr Min Sec Regs 1800 1802 1915 1917 Date Time of Minimum Demand Value 3 Month Day Yr Same as Hr Min Sec Regs 1800 1802 100 1999 Square D Company All Rights Reserved Reg No Description 1918 1920 1921 1923 1924 1926 1927 1929 1930 1932 1933 1935 1936 1938 1939 1941 1942 1944 1945 1947 1948 1950 1951 1953 1954 1956 1957 1959 Reg No Date Time of Peak Demand Value 4 Date Time of Minimum Demand Value 4 Date Time of Peak Demand Value 5 Date Time of Minimum Demand Value 5 Date Time of Peak Demand Value 6 Date Time of Minimum Dema
150. might be allocated in a CM 2350 In this figure the user has set up a waveform capture log an extended event capture log an event log and three data logs two small logs and one larger log Of the total available nonvolatile memory about 25 is still available If the user decided to add a fourth data log file the file could be no larger than the space still available 25 of the circuit monitor s total storage capacity If the fourth file had to be larger than the space still available the user would have to reduce the size of one of the other files to free up the needed space POWERLOGIC System Manager Software indicates the memory allocation statistics in the On Board Data Storage dialog box shown in figure 7 3 page 58 and figure 7 4 page 54 The display uses color coding to show the space devoted to each type of log file along with the space still available For instructions on setting up log files using POWERLOGIC software refer to the instruction bulletin included with the software o If you want to add a new log file but the file is too large for the available space you must either reduce the size of data log 4 OR reduce the size of one or more of the existing files Figure 9 1 Memory allocation example CM 2350 70 1999 Square D Company All Rights Reserved Memory Example HOW POWER FACTOR IS STORED Chapter 9 Advanced Topics Table 9 1 shows how a user might configure the available mem
151. n sess 8 Note This edition of the circuit monitor instruction bulletin describes features available in series G4 or later and firmware version 17 009 or higher Series 2000 circuit monitors with older series numbers or firmware versions will not include all features described in this instruction bulletin If you have Series 2000 circuit monitors that do not have the latest firmware version and you want to upgrade their firmware contact your local Square D representative for information on purchasing the Class 3020 Type CM 2000U Circuit Monitor Firmware Upgrade Kit The POWERLOGIC Circuit Monitor is a multifunction digital instrumentation data acquisition and control device It can replace a variety of meters relays transducers and other components The circuit monitor is equipped with RS 485 communications for integration into any power monitoring and control system However POWERLOGIC System Manager application software written specifically for power monitoring and control best supports the circuit monitor s advanced features The circuit monitor is a true rms meter capable of exceptionally accurate measurement of highly nonlinear loads A sophisticated sampling technique enables accurate true rms measurement through the 31st harmonic Over 50 metered values plus extensive minimum and maximum data can be viewed from the six digit LED display Table 1 1 on page 3 provides a summary of circuit monitor instrumenta
152. nboard Data Storage setup dialog box Requires circuit monitor firmware version 15 002 or higher 54 1999 Square D Company All Rights Reserved SAG SWELL ALARMS Chapter 7 Disturbance Monitoring Table 7 3 CM 2350 and CM 2450 12 Cycle Waveform Capture Memory Allocation No of Back to Back ey a cia Legal Entries for 12 Cycle Max No of Triggered Captures Per Trigger Waveform Capture Memory Allocation Events Stored 1 Multiples of 1 1 2 3 8 8 20 Multiples of 2 2 4 6 8 4 30 Multiples of 3 3 6 2 40 Multiples of 4 4 8 2 50 Multiple of 5 5 1 Table 7 4 CM 2452 12 Cycle Waveform Capture Memory Allocation Ia Cya ee Legal Entries for 12 Cycle Max No of Triggered Captures Per Trigger Waveform Capture Memory Allocation Events Stored 1 Multiples of 1 1 2 3 29 29 20 Multiples of 2 2 4 6 28 14 30 Multiples of 3 3 6 9 27 40 Multiples of 4 4 8 12 28 7 50 Multiples of 5 5 10 15 20 25 5 As explained in chapter 6 the event capture has a user programmable number of pre event cycles ranging from 2 to 10 cycles This allows you to tailor the event capture for more or less pre event data On event captures consisting of multiple 12 cycle recordings the pre event cycles apply only to the first 12 cycle waveform of the series POWERLOGIC application software can be used to set up each of the sag swell alarms For each alarm the user programs the following d
153. nd Value 6 Date Time of Peak Demand Value 7 Date Time of Minimum Demand Value 7 Date Time of Peak Demand Value 8 Date Time of Minimum Demand Value 8 Date Time of Peak Demand Value 9 Date Time of Minimum Demand Value 9 Date Time of Peak Demand Value 10 Date Time of Minimum Demand Value 10 Name Units MAGNITUDE AND DURATION OF LAST SAG SWELL EVENT Appendix B Abbreviated Register Listing Units Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Month Day Yr Hr Min Sec Range Note Registers 2300 2341 apply to circuit monitor models CM 2350 and higher only 2300 2301 2302 2303 2304 2305 2306 2307 2308 2309 2310 2311 2312 2313 2314 2315 2316 2317 2318 2319 2320 Last Voltage A Swell Extreme Value Last Voltage A Swell Event Duration Last Voltage B Swell Extreme Value Last Voltage B Swell Event Duration Last Voltage C Swell Extreme Value Last Voltage C Swell Event Duration Last Current A Swell Extreme Value Last Current A Swell Event Duration
154. nded metering ranges 66 Setting the date and time using the command interf 69 Setting up relays for CM internal control 65 Setting up relays for remote external control 64 Setup alarm 117 Software instruction bulletins 7 Status input pulse demand metering 78 Status input control 73 V VAR sign convention alternate 11 default 11 72 optional 72 VAR sign convention changing the 72 Voltage demand 14 Voltage sag swell 50 Ww Waveform capture 41 47 4 cycle automatic 41 manual 41 CM 2452 memory allocation 12 cycle 55 extended event automatic high speed trigger 44 automatic standard setpoint 46 manual 44 storage 47 high speed trigger 44 multiple setup using SMS 3000 SMS 1500 or PMX 1500 52 using SMS 770 SMS 700 EXP 550 or EXP 500 54 setting up circuit monitor for 42 storage 43 Waveform storage 43 1999 Square D Company All Rights Reserved Index 129 Square D Company 295 Tech Park Dr Suite 100 LaVergne TN 37086 USA Printed in USA Order No 30201M9806 Replaces 30201M9301R10 97 dated January 1998 FP 4M 3 98
155. ng POWERLOGIC application software a programmable controller or in the case of a CM 2450 or CM 2452 a custom program executing in the meter 2 Circuit monitor internal control the relay is controlled by the circuit monitor models CM 2150 and above in response to a set point con trolled alarm condition or as a pulse initiator output Once you ve set up a relay for circuit monitor control option 2 above you can no longer operate the relay remotely You can though temporarily override the relay using POWERLOGIC application software The first three operating modes normal latched and timed function differently when the relay is remotely controlled versus circuit monitor con trolled The descriptions below point out the differences in remote versus circuit monitor control Modes 4 through 10 all pulse initiation modes are circuit monitor control modes remote control does not apply to these modes 1 Normal Remotely Controlled The user must energize the relay by issuing a com mand from a remote PC or programmable controller The relay remains energized until a command to de energize is issued from a remote PC or programmable controller or until the circuit monitor loses control power Circuit Monitor Controlled When an alarm condition assigned to the relay occurs the relay is energized The relay is not de energized until all alarm conditions assigned to the relay have dropped out or until the circuit monitor lose
156. ngle with reference to H5 Va angle H6 magnitude as a percent of H1 magnitude H6 angle with reference to H6 Va angle H7 magnitude as a percent of H1 magnitude H7 angle with reference to H7 Va angle H8 magnitude as a percent of H1 magnitude H8 angle with reference to H8 Va angle H9 magnitude as a percent of H1 magnitude H9 angle with reference to H9 Va angle H10 magnitude as a percent of H1 magnitude H10 angle with reference to H10 Va angle H11 magnitude as a percent of H1 magnitude H11 angle with reference to H11 Va angle H12 magnitude as a percent of H1 magnitude H12 angle with reference to H12 Va angle H13 magnitude as a percent of H1 magnitude H13 angle with reference to H13 Va angle H14 magnitude as a percent of H1 magnitude H14 angle with reference to H14 Va angle H15 magnitude as a percent of H1 magnitude H15 angle with reference to H15 Va angle H16 magnitude as a percent of H1 magnitude H16 angle with reference to H16 Va angle H17 magnitude as a percent of H1 magnitude H17 angle with reference to H17 Va angle H18 magnitude as a percent of H1 magnitude H18 angle with reference to H18 Va angle 1999 Square D Company All Rights Reserved Appendix B Abbreviated Register Listing Units In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths o
157. nitors The harmonic magnitudes can be formatted as either a percentage of the fundamental default or a percentage of the rms value Refer to Chapter 9 A dvanced Topics for information on how to configure the harmonic calculations Table 2 4 Power Analysis Values Value Reportable Range THD Voltage Current 3 phase per phase neutral 0 to 3 276 7 thd Voltage Current 3 phase per phase neutral 0 to 3 276 7 K Factor per phase 0 0 to 100 0 K Factor Demand per phase 0 0 to 100 0 Crest Factor per phase 0 0 to 100 0 Displacement P F per phase 3 phase 0 010 to 1 000 to 0 010 Fundamental Voltages per phase Magnitude 0 to 3 276 700 V Angle 0 0 to 359 9 Fundamental Currents per phase Magnitude 0 to 32 767 A Angle 0 0 to 359 9 Fundamental Real Power per phase 3 phase 0 to 327 670 kW Fundamental Reactive Power per phase D 0 to 327 670 kVAR Harmonic Power per phase 3 phase 0 to 327 670 kW Phase Rotation ABC or CBA Unbalance current and voltage 0 0 to 100 Individual Harmonic Magnitudes 0 to 327 67 Individual Harmonic Angles 0 0 to 360 0 Via communications only 16 1999 Square D Company All Rights Reserved Chapter 3 Input Output Capabilities CHAPTER 3 INPUT OUTPUT CAPABILITIES CHAPTER CONTENTS INPUT OUTPUT MODULES Input Output Modules rrt eren e hereto en rto e e tinere Re 17 statis Inputs ieri ERR HERE
158. nitude H20 angle with reference to H20 Va angle H21 magnitude as a percent of H1 magnitude H21 angle with reference to H21 Va angle H22 magnitude as a percent of H1 magnitude H22 angle with reference to H22 Va angle H23 magnitude as a percent of H1 magnitude H23 angle with reference to H23 Va angle H24 magnitude as a percent of H1 magnitude H24 angle with reference to H24 Va angle H25 magnitude as a percent of H1 magnitude H25 angle with reference to H25 Va angle H26 magnitude as a percent of H1 magnitude H26 angle with reference to H26 Va angle H27 magnitude as a percent of H1 magnitude H27 angle with reference to H27 Va angle H28 magnitude as a percent of H1 magnitude H28 angle with reference to H28 Va angle H29 magnitude as a percent of H1 magnitude H29 angle with reference to H29 Va angle H30 magnitude as a percent of H1 magnitude H30 angle with reference to H30 Va angle H31 magnitude as a percent of H1 magnitude H31 angle with reference to H31 Va angle Reserved H1 magnitude as a percent of H1 magnitude H1 angle with reference to H1 Va angle H2 magnitude as a percent of H1 magnitude H2 angle with reference to H2 Va angle H3 magnitude as a percent of H1 magnitude H3 angle with reference to H3 Va angle H4 magnitude as a percent of H1 magnitude H4 angle with reference to H4 Va angle H5 magnitude as a percent of H1 magnitude H5 angle with reference to H5 Va angle H6 magnitude as a percent of H1 magnitude H6 angle with reference to H
159. nitude as a percent of H1 magnitude H6 angle with reference to H6 Va angle H7 magnitude as a percent of H1 magnitude H7 angle with reference to H7 Va angle H8 magnitude as a percent of H1 magnitude H8 angle with reference to H8 Va angle H9 magnitude as a percent of H1 magnitude H9 angle with reference to H9 Va angle H10 magnitude as a percent of H1 magnitude H10 angle with reference to H10 Va angle H11 magnitude as a percent of H1 magnitude H11 angle with reference to H11 Va angle H12 magnitude as a percent of H1 magnitude H12 angle with reference to H12 Va angle H13 magnitude as a percent of H1 magnitude H13 angle with reference to H13 Va angle H14 magnitude as a percent of H1 magnitude H14 angle with reference to H14 Va angle H15 magnitude as a percent of H1 magnitude H15 angle with reference to H15 Va angle H16 magnitude as a percent of H1 magnitude H16 angle with reference to H16 Va angle H17 magnitude as a percent of H1 magnitude 108 1999 Square D Company All Rights Reserved Units in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100th
160. nt Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 Appendix B Abbreviated Register Listing Reg No Description 5876 5877 5878 5879 5880 5881 5882 5883 5884 5885 5886 5887 5888 5889 5890 5891 5892 5893 5894 5895 5896 5897 5898 5899 Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter No Event Counter
161. ntenance Log sss nnne entente nennen nennen nennen 40 The circuit monitor provides an event log file to record the occurrence of important events The circuit monitor can be configured to log the occur rence of any alarm condition as an event The event log can be configured as first in first out FIFO or fill and hold Using POWERLOGIC application software the event log can be uploaded for viewing and saved to disk and the circuit monitor s event log memory can be cleared Circuit monitor models 2150 and higher provide nonvolatile memory for event log storage The size of the event log the maximum number of events is user definable When determining the maximum number of events take the circuit monitor s total storage capacity into consideration For circuit monitor models 2150 and 2250 the total storage capacity must be allocated between the event log and up to 14 data logs For circuit monitor models 2350 2450 and 2452 the total data storage capacity must be allocated between an event log a 4 cycle waveform capture log an extended event capture log and up to 14 data logs See Memory Allocation in Chapter 9 for additional memory considerations 1999 Square D Company All Rights Reserved 37 Bulletin No 3020IM9806 February 1999 DATA LOGGING Alarm Driven Data Log Entries Organizing Data Log Files Circuit monitor models CM 2150 and higher are equipped with nonvolatile memory for storing meter reading
162. odes For a listing of circuit monitor registers see Appendix B For a listing of command codes see The Com mand Interface in this chapter To set control of conditional energy to the command interface m Write command code 2341 to register 7700 To verify proper setup read register 2081 Bit 6 should read 1 indicating command interface control Bit 7 should read 0 indicating that condition energy accumulation is off To start conditional energy accumulation m Write command code 6321 to register 7700 While conditional energy is accumulating bit 7 of register 2081 should read 1 indicating that conditional energy accumulation is on To stop conditional energy accumulation m Write command code 6320 to register 7700 To clear all conditional energy registers 1629 1648 1 Write command code 6220 to register 7700 To configure conditional energy for status input control 1 Write command code 2340 to register 7700 2 Specify the status input that will drive conditional energy accumulation by writing a bitmap to register 7701 Set the appropriate bit to 1 to indicate the desired input input S1 bit 1 S2 bit 2 S3 bit 3 S4 bit 4 3 Write command code 3390 to register 7700 To verify proper setup read register 2081 Bit 6 should read 0 indicating that conditional energy accumulation is under status input control Bit 7 should read 0 when the status input is off indicating that conditional energy accumulation is off B
163. oduct 1717 K Factor Demand Phase C Coincident Peak Product 1718 Current Demand Phase C Coincident Peak Product POWER DEMAND Amps Scale Factor A Amps Scale Factor A Amps Scale Factor A Amps Scale Factor A Amps Scale Factor A In 10ths In 10ths In 10ths Amps Scale Factor A Amps Scale Factor A Amps Scale Factor A Amps Scale Factor A Amps Scale Factor A In 10ths Amps Scale Factor A In 10ths Amps Scale Factor A In 10ths Amps Scale Factor A Range 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 10 000 0 to 10 000 0 to 10 000 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 10 000 0 to 32 767 0 to 10 000 0 to 32 767 0 to 10 000 0 to 32 767 Reactive Demand may be calculated using either the fundamental only default or total harmonics user selectable 1730 Average Power Factor Over Interval 1731 Present Real Power Demand 3 Phase Total 1732 Present Reactive Power Demand 3 Phase Total 1733 Present Apparent Power Demand 3 Phase Total 1734 Peak Real Power Demand 3 Phase Total 1735 Average Power Factor for Peak Real 1736 Reactive Power Demand for Peak Real 1737 Apparent Power Demand for Peak Real 1738 Peak Reactive Power Demand 3 Phase Total 1739 Average Reactive Power Factor for Peak Reactive 1740 Real Power Demand for Peak Reactive 1741 Apparent Power Demand for Peak Reactive 1742 Peak Apparent Power Demand 3 Phase Total 1743 Average Apparent Power Factor for Peak Apparent 1
164. of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths Range 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 10000 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 Reg No 4413 4414 4415 4416 4417 4418 4419 4420 4421 4422 4423 4424 4425 4426 4427 4428 4429 4430 4431 4432 4433 4434 4435 4436 4437 4438 4439 4440 4441 4442 4443 4444 4445 4446 4447 Description H14 angle with reference to H14 Va angle H15 magnitude as a percent of H1 magnitude H15 angle with reference to H15 Va angle H16 magnitude as a percent of H1 magnitude H16 angle with reference to H16 Va angle H17 magnitude as a percent of H1 magnitude H17 angle with reference to H17 Va angle H18 magnitude as a percent of H1 magnitude H18 angle with reference to H18 Va angle H19 magnitude as a percent of H1 magnitude H19 angle with reference to H19 Va angle H20 magnitude as a percent of H1 magnitude H20 angle with reference to H20 Va angle H21 magnitude a
165. on 101 Bulletin No 3020IM9806 February 1999 Reg No Name 2321 2322 2323 2324 2325 2326 2327 2328 2329 2330 2331 2332 2333 2334 2335 2336 2337 2338 2339 2340 2341 Reg No Last Voltage A Sag Extreme Value Last Voltage A Sag Event Duration Last Voltage B Sag Extreme Value Last Voltage B Sag Event Duration Last Voltage C Sag Extreme Value Last Voltage C Sag Event Duration Last Current A Sag Extreme Value Last Current A Sag Event Duration Last Current B Sag Extreme Value Last Current B Sag Event Duration Last Current C Sag Extreme Value Last Current C Sag Event Duration Last Current N Sag Extreme Value Last Current N Sag Event Duration Name Units ANALOG OUTPUT CONFIGURATION REGISTERS 2600 2601 2602 2603 2604 2605 Analog Output 1 None Label Analog Output 1 None Enable Analog Output 1 None Register Number Analog Output 1 None Lower Limit Analog Output 1 None Upper Limit Units Volts Scale Factor D Cycles Volts Scale Factor D Cycles Volts Scale Factor D Cycles Amps Scale Factor A Cycles Amps Scale Factor A Cycles Amps Scale Factor A Cycles Amps Scale Factor B Cycles Range Alphanumeric 4 chars Oori Any valid reg 32767 to Upper Limit Lower Limit to 32 767 The description for registers 2608 2613 is the same as 2600 2605 2608 2609 2610 2611 2612 2613 Analog Output 2 Label Analog Output 2 Enable Analog Output 2 Register Number
166. on thermal demand default 5 Date Time of last generic demand maximum minimum reset Generic demand calculation performed on value stored in these registers Regs 2205 2212 are defaulted to voltage registers 1014 1021 99 Bulletin No 3020IM9806 February 1999 Reg No Name Units Range Description 2202 2204 Generic Demand Value 1 None 0 to 32 767 Present demand value for generic present demand demand value 1 2331 Generic Demand Value 1 None 0 to 32 767 Peak demand value for generic Peak Demand demand value 1 2332 Generic Demand Value 1 None 0 to 32 767 Minimum demand value for generic Minimum Demand demand value 1 2233 2235 The definitions for registers 2233 2235 are the same as for 2230 2232 except that they apply to generic demand value 2 2236 2238 The definitions for registers 2236 2238 are the same as for 2230 2232 except that they apply to generic demand value 3 2239 2241 The definitions for registers 2239 2241 are the same as for 2230 2232 except that they apply to generic demand value 4 2242 2244 The definitions for registers 2242 2244 are the same as for 2230 2232 except that they apply to generic demand value 5 2245 2247 The definitions for registers 2245 2247 are the same as for 2230 2232 except that they apply to generic demand value 6 2248 2250 The definitions for registers 2248 2250 are the same as for 2230 2232 except that they apply to generic demand value 7
167. on Bulletin Software Order No SMS 3000 System Administrator s Guide client server 3080IM9602 SMS 3000 User s Manual client server 30801M9601 System Manager Standalone SMS 1500 PMX 1500 SMS 121 30801M9702 SMS 770 700 30801M9305 EXP 550 500 30801M9501 PSW 101 30801M9302 Several optional add on modules are available for use with the circuit monitor Each module is shipped with an instruction bulletin detailing installation and use of the product Available add on modules for the circuit monitor are listed below Instruction Bulletin Title Reference No e POWERLOGIC Control Power Module CPM 48 30901M9305 e POWERLOGIC Ride Through Module 30901M9701 I O Modules IOM 11 44 18 30201M9304 e O Modules IOM 441 1 4444 30201M9401 e Voltage Power Module 30901M9302 Optical Communications Interface OCI 2000 30901M9303 Ethernet Communications Module ECM 2000 ECM RM 30201B9818 In addition the software and add on module instruction bulletins listed in this chapter are available through D Fax the Square D fax on demand system Phone 1 800 557 4556 and request a POWERLOGIC Power Monitoring index Then call back and order the document s you want by specifying the Fax Document Number s from the index The document s will be faxed to your fax machine This service is accessible seven days a week 24 hours a day Reference numbers listed are the original document numbers If a document has been revised the listed number
168. onding to relays to be placed under manual control Bit 1 corresponds to KYZ Bit 2 corresponds to Relay 1 Bit 3 corresponds to relay 2 Bit 4 corresponds to relay 3 2 Write a command code 3310 to the circuit monitor s command interface register 7700 7700 3310 Command code to configure relay for remote external control Energizing a Relay To energize a relay do the following 1 Write a bitmap see below to the command parameter register specifying the relays to be energized Reg Value Description 7701 Bitmap bitmap corresponding to relays to be energized Bit 1 corresponds to KYZ Bit 2 corresponds to Relay 1 Bit 3 corresponds to relay 2 Bit 4 corresponds to relay 3 2 Write a command code 3321 to the circuit monitor s command interface register 7700 7700 3321 Command code to energize relay De Energizing a Relay To de energize a relay do the following 1 Write a bitmap see below to the command parameter register specifying the relays to be de energized Reg Value Description 7701 Bitmap bitmap corresponding to relays to be de ener gized Bit 1 corresponds to KYZ Bit 2 corresponds to Relay 1 Bit 3 corresponds to relay 2 Bit 4 corresponds to relay 3 2 Write a command code 3320 to the circuit monitor s command interface register 7700 7700 3320 Command code to de energize relay 64 1999 Square D Company All Rights Reserved Chapter 9 Advanced Topics Setting Up Rel
169. ons standard Front panel RS 232 optical communications port standard Modular field installable analog and digital I O 1 ms time stamping of status inputs for sequence of events recording I O modules support programmable KYZ pulse output Setpoint controlled alarm relay functions On board event and data logging Waveform and event captures user selectable for 4 12 36 48 or 60 cycles 64 and 128 point cycle waveform captures High speed triggered event capture Programming language for application specific solutions Downloadable firmware System connections 3 phase 3 wire Delta 3 phase 4 wire Wye Metered or calculated neutral Other metering connections Optional voltage power module for direct connection to 480Y 277V Optional control power module for connecting to 18 60 Vdc control power Wide operating temperature range standard 25 to 70 C UL Listed CSA certified and CE marked MV 90 billing compatible Pre configured data log and alarms EXPANDED MEMORY Chapter 1 Introduction Table 1 1 Summary of Circuit Monitor Instrumentation Real Time Readings Energy Readings Current per phase N G 30 Voltage L L L N Real Power per phase 3 Reactive Power per phase 32 Apparent Power per phase 3 Power Factor per phase 39 Frequency Temperature internal ambient THD current and voltage K Factor per phase Accumulated Energy Real Accumulated
170. ory for various circuit monitor models In this example the circuit monitors have been set up with one data log that stores the following data hourly 3 phase average amps volts L L L N PF kW kVAR frequency 3 phase demand for amps kW kVA kWH and kVARH The circuit monitors store waveform captures and extended event captures as follows The CM 2250 can store only one waveform capture and one 12 cycle event capture It stores these in volatile memory therefore they do not reduce the amount of nonvolatile memory available for event and data logs The CM 2350 can store multiple waveform captures and extended event captures It stores these in nonvolatile memory therefore they do affect the amount of nonvolatile memory available for event and data logs For specific instructions on calculating log file sizes see Appendix C Calculating Log File Sizes Table 9 1 Memory Configuration Example Typical Standard Memory Configuration CM 2050 CM 2150 CM 2250 CM 2350 2450 CM 24529 Event Log N A 500 Events 500 Events 500 Events 1500 Events 1 Data Log N A 40 Days 40 Days 40 Days 120 Days Waveform Captures N A N A 1 39 99 Event Captures N A N A 1 39 139 This table illustrates a typical memory configuration for a standard circuit monitor with one data log storing the following data hourly 30 avg amps volts L L L N PF kW KVAR freq 30 demand for amps kW kVA
171. ower loss The number of waveforms that can be stored is based on the amount of memory that has been allocated to waveform capture See Memory Allocation in Chapter 9 1999 Square D Company All Rights Reserved 43 Bulletin No 3020IM9806 February 1999 EXTENDED EVENT CAPTURE Circuit monitor models CM 2250 and higher are equipped with a feature Manual Event Capture Automatic Event Capture High Speed Trigger called extended event capture By connecting the circuit monitor to an external device such as an undervoltage relay the circuit monitor can capture and provide valuable information on short duration events such as voltage sags and swells For a CM 2250 each event capture includes 12 cycles of sample data from each voltage and current input For a CM 2350 and higher an extended event capture can include 12 24 36 48 or 60 cycles of sample data An adjustable trigger delay lets the user adjust the number of pre event cycles In a CM 2250 there are three ways to initiate a 12 cycle event capture Manually from a remote personal computer using POWERLOGIC application software e Automatically using an external device to trigger the circuit monitor Automatically by the circuit monitor when an alarm condition such as Alarm 55 Over value THD voltage Phase A B occurs These methods are described below Note Models CM 2350 and higher can also trigger on high speed events allowing it to perform di
172. panel comm port default Disable front panel comm port Enable front panel setup default Disable front panel setup Set normal phase rotation to ABC default Set normal phase rotation to CBA Place specified relays under external control default Place specified relays under internal control De energize designated relays per specified bit map Energize designated relays per specified bit map Release specified relays from override control Place specified relays under override control Reset Req d N A N N Code 3390 4110 4310 4311 4910 4911 5110 5112 5120 5310 5311 5320 5321 5910 5920 6210 6220 6310 6311 6320 6321 6330 6331 6910 7510 Parameter s Bit Map Input Designation None None None None None None None None None None None None None None None None None None None None None None None Bit Map 1999 Square D Company All Rights Reserved Chapter 9 Advanced Topics Description Set control of conditional energy to indicated status inputs Reset Min Max Set VAr sign convention to CM1 convention default Set VAr sign convention to alternate convention Trigger 4 cycle waveform capture Trigger 12 cycle waveform capture Reset Peak Demand Currents K Factors Generic Demand Reset Peak and MinimumGeneric Demand quantities Reset Peak Demand Powers and associated average Power Factors Set power demand method to thermal default Set power demand method
173. ple conditions e g Time of Day and Input Status Note Apply the circuit monitor appropriately as a programmable power monitoring device not as a primary protective device Purchasers of circuit monitor models CM 2450 or CM 2452 can receive a program developer s kit at no additional charge The developer s kit includes an instruction bulletin program compiler and sample programs enabling you to create your own CM 2450 programs Contact your local Square D representative or PMO Technical Support to order the developer s kit 1999 Square D Company All Rights Reserved Chapter 9 Advanced Topics CHAPTER 9 ADVANCED TOPICS CHAPTER CONTENTS THE COMMAND INTERFACE The Command Intertace aee trennen eterne i eia Pigeon Command Codes senis p duni diee ite i Eier be PI nie Operating Relays Using the Command Interface sess Setting Up Relays for Remote External Control Energizing a Relay teer sis eee iier ir erede et rea baie ert ieg De Energizing a Relay ete eed e tended tenete e ets Setting Up Relays for Circuit Monitor Internal Control Overriding am Output Relay eteontebem eee iet Releasing an Overridden Relay sie eret tenter etd Setting Scale Factors For Extended Metering Ranges ssus Setting The Date and Time Using the Command Interface Memory AJIOCABOD siamet tea drei onem abt em tad muse tels Memory E
174. r kVAH per pulse for relay R2 when in those modes Label for relay R3 Relay R3 Mode Register 02 Normal 1 Latched 2 Timed 3 Absolute kWH pulse 4 Absolute kVArH pulse 5 kVAH pulse 6 kWH in pulse 7 kVarH in pulse 8 kWH out pulse 9 kVArH out pulse This register specifies the time relay R3 is to remain closed for timed mode This register specifies the KWH kVArH or kVAH per pulse for relay R3 when in those modes 1999 Square D Company All Rights Reserved 95 Bulletin No 3020IM9806 February 1999 Reg No Description Units Range CIRCUIT MONITOR CONFIGURATION VALUES 2001 System Connection None 30 3 wire mode 40 4 wire with calculated neutral 41 4 wire with metered neutral 42 4 wire 2 1 2 element with calculated neutral 43 4 wire 2 1 2 element with metered neutral 2002 CT Ratio 3 Phase Primary Ratio Term None 1 to 32 767 2003 CT Ratio 3 Phase Secondary Ratio Term None 1to5 2004 CT Ratio Neutral Primary Ratio Term None 1 to 32 767 2005 CT Ratio Neutral Secondary Ratio Term None 1to5 2006 PT Ratio 3 Phase Primary Ratio Term None 1 to 32 767 2007 PT Ratio 3 Phase Primary Scale Factor None 0t02 2008 PT Ratio 3 Phase Secondary Ratio Term None 1 to 600 2009 CT Ratio Correction Factors Phase A In 10 000ths 5 000 20 000 2010 CT Ratio Correction Factors Phase B In 10 000ths 5 000 20 000 2011 CT Ratio Correction Factors Phase C In 10 000ths 5 000 20 000 2012 CT Ratio Correction Factors Neutra
175. r of 0 01 for 50 60 Hz 1 multiplier of 0 10 for 400 Hz 5 Write a command code 2110 to the circuit monitor s command interface register 7700 68 1999 Square D Company All Rights Reserved SETTING THE DATE AND TIME USING THE COMMAND INTERFACE MEMORY ALLOCATION Chapter 9 Advanced Topics The command interface can be used to set the date and time To set the date and time do the following 1 Write values to a series of command parameter registers one for each time parameter SEC MO DA HR MN YR Reg No Value Description 7701 7706 Sec min hr Secs corresponds to Register 7701 day mo yr Mins corresponds to Register 7702 Hours corresponds to Register 7703 Day corresponds to Register 7704 Month corresponds to Register 7705 Year corresponds to Register 7706 2 Write a command code 1310 to the circuit monitor s command interface register 7700 Reg No Value Description 7700 1310 Command code to set date and time This section describes memory allocation for nonvolatile logging memory only It does not apply to nonvolatile memory used to store critical values such as setup parameters min max values and energy and demand values In all circuit monitor models these critical values are stored in a separate nonvolatile memory area Circuit monitors are available with different amounts of nonvolatile logging memory Depending on the circuit monitor model the available nonvolatile logging m
176. r than 32767 or is a non integer it is expressed as an integer in the range of 32767 associated with a multiplier in the range of 10 3 to 103 For more information on scale factors see Setting Scale Factors for Extended Metering Ranges in Chapter 9 When POWERLOGIC application software is used to set up alarms it automatically handles the scaling of pickup and dropout setpoints When alarm setup is performed from the circuit monitor s front panel the user must determine how the corresponding metering value is scaled and take the scale factor into account when entering alarm pickup and dropout settings Pickup and dropout settings must be integer values in the range of 32 767 to 32 767 For example to set up an under voltage alarm for a 138 kV nominal system the user must decide upon a setpoint value and then convert it into an integer between 32 767 and 432 767 If the under voltage setpoint were 125 000 V this would typically be converted to 12500 x 10 and entered as a setpoint of 12500 This section is for users who do not have POWERLOGIC software and must set up alarms from the circuit monitor front panel It tells how to properly scale alarm setpoints The circuit monitor is equipped with a 6 digit LED display and a two LED s to indicate Kilo or Mega units when applicable When determining the proper scaling of an alarm setpoint first view the corresponding metering value For example for an Over Current Ph
177. rcuit monitor s command interface register 7700 7700 3341 Command Code to place relay under override control To return an overridden relay to circuit monitor internal control you must release the override To release the override do the following 1 Write a bitmap see below to the command parameter register specify ing the relays to be released from override Reg Value Description 7701 Bitmap Bitmap corresponding to relays to be released from override control Bit 1 corresponds to KYZ Bit 2 corresponds to Relay 1 Bit 3 corresponds to relay 2 Bit 4 corresponds to relay 3 2 Write a command code 3340 to the circuit monitor s command interface register 7700 7700 3340 Command Code to release overridden relays 1999 Square D Company All Rights Reserved 65 Bulletin No 3020IM9806 February 1999 SETTING SCALE FACTORS FOR EXTENDED METERING RANGES The circuit monitor stores instantaneous metering data in single registers Each register has a maximum range of 32 767 In order to meter extended ranges current voltage and power readings can accommodate multipliers other than one Multipliers can be changed from the default value of 1 to other values such as 10 100 or 1000 These scale factors are automatically selected for the user when setting up the circuit monitor either from the front panel or using POWERLOGIC application software The circuit monitor stores these multipliers as scale factors
178. re 10 Calculate the Size of the Extended Event Capture Log File 11 For CM 2350s and higher only for every 12 cycles multiply by 6 400 Example for 60 cycles 5 x 6 400 32 000 For CM 2150s and CM 2250s enter zero here 11 Total All Log Files 12 Add lines 1 9 10 and 11 For standard CM 2150s CM 2250s CM 2350s and CM 2450s the total cannot exceed 51 200 For CM 2452s the total cannot exceed 182 272 For models with the 512k option the total cannot exceed 313 344 For models with the 1024k option the total cannot exceed 575 488 12 The CM 2150 does not provide waveform capture The CM 2250 can store one 4 cycle waveform capture and one 12 cycle event capture but these are stored in separate memory locations and do not affect the amount of memory available for event and data logging 116 1999 Square D All Rights Reserved Appendix D Alarm Setup Information APPENDIX D ALARM SETUP INFORMATION SCALING ALARM SETPOINTS The circuit monitor is designed to handle a wide range of metering require ments To handle very large and very small metering values the circuit monitor uses scale factors to act as multipliers These scale factors range from 001 up to 1000 and are expressed at powers of 10 for example 0 001 10 3 These scale factors are necessary because the circuit monitor stores data in registers which are limited to integer to values between 32767 and 32767 When a value is either large
179. re either manual or automatic replaces the last captured data Stores the captured data in volatile memory the data is lost on power loss The captured data does not affect event log and data log storage space The captured waveform is stored separately CM 2350 and higher Stores multiple captured 12 to 60 cycle events Stores the captured data in nonvolatile memory the data is retained on power loss The number of extended event captures that can be stored is based on the amount of memory that has been allocated to extended event capture See Memory Allocation in Chapter 9 1999 Square D Company All Rights Reserved 47 Chapter 7 Disturbance Monitoring CHAPTER 7 DISTURBANCE MONITORING CHAPTER CONTENTS INTRODUCTION DESCRIPTION Tint OAUCH OM ANN 49 rego 49 cio H 52 Multiple Wavetormi5et p ertet tetti revise tti ope edens 52 SMS 3000 SMS 1500 or PMX 1500 sisie ssiri esst eaii 52 SMS 770 SMS 700 EXP 550 or EXP 500 cccscssescsssseesestesstesescesesesesesnanenens 54 Sag Swelll Alarms 5 nme rr ai rr irte ire ceci ii Peers 55 Multiple Waveform Retrieval eere rentre tenere threaten 56 SMS 3000 SMS 1500 or PMX 1500 reseso EE 56 SMS 770 SMS 700 EXP 550 or EXP 500 ccscssesesssseesesteseteseececesesesesnenenens 56 High Speed Event Log Entries eren eri ep eee orien 57 Chapter 6 Waveform Capture d
180. red to the scale groups 1999 Square D Company All Rights Reserved 2 1 0 default 2 1 0 default 1 2 1 0 default 1 1 0 default 1 0 default 1 2 3 67 Bulletin No 3020IM9806 February 1999 4 Write the appropriate values see below to a series of command parameter registers one for each scale group Reg No Value Description 7701 7705 Scale Factors Scale Group A write to reg 7701 Scale Group B write to reg 7702 Scale Group C write to reg 7703 Scale Group D write to reg 7704 Scale Group E write to reg 7705 Scale Group A Ammeter Per Phase 2 multiplier of 0 01 1 multiplier of 0 10 O multiplier of 1 00 default 1 multiplier of 10 0 Scale Group B Ammeter Neutral 2 multiplier of 0 01 1 multiplier of 0 10 O multiplier of 1 00 default 1 multiplier of 10 0 Scale Group C Ammeter Ground 2 multiplier of 0 01 1 multiplier of 0 10 O multiplier of 1 00 default 1 multiplier of 10 0 Scale Group D Voltmeter 1 multiplier of 0 10 O multiplier of 1 00 default 1 multiplier of 10 0 2 multiplier of 100 Scale Group E kWattmeter kVarmeter kVA 3 multiplier of 0 001 2 multiplier of 0 01 1 multiplier of 0 10 O multiplier of 1 00 default 1 multiplier of 10 0 2 multiplier of 100 3 multiplier of 1000 4 multiplier of 10 000 5 multiplier of 100 000 Scale Group F Frequency Determined by CM 2 multiplie
181. rent Phase B 1052 51 Over Value THD Current Phase C 1053 52 Over Value THD Voltage Phase A N 1055 53 Over Value THD Voltage Phase B N 1056 54 Over Value THD Voltage Phase C N 1057 55 Over Value THD Voltage Phase A B 1058 56 Over Value THD Voltage Phase B C 1059 57 Over Value THD Voltage Phase C A 1060 58 Over K Factor Phase A 1071 59 Over K Factor Phase B 1072 60 Over K Factor Phase C 1073 61 Over Predicted kVA Demand 1748 62 Over Predicted KW Demand 1746 63 Over Predicted KVAR Demand 1747 64 Over kVA Demand Level 1 1733 65 Over kVA Demand Level 2 1733 66 Over kVA Demand Level 3 1733 67 Over kW Demand Level 1 1731 1999 Square D Company All Rights Reserved Appendix D Alarm Setup Information Units Scale Group Alarm Type Volts Volts Volts Volts Volts Volts Volts Volts Volts Tenths 96 Tenths 96 Tenths 96 Tenths 96 Tenths 96 Tenths 96 Volts kVA KW KW kVAR kVAR Amps Amps Amps Amps Hundredths of Hertz Hundredths of Hertz Thousandths Thousandths Thousandths Thousandths Tenths 96 Tenths 96 Tenths 96 Tenths 96 Tenths 96 Tenths 96 Tenths 96 Tenths 96 Tenths 96 Tenths 96 Tenths 96 Tenths 96 kVA kW kVAR kVA kVA kVA kW is UU UUUuUucUc T nTmrm2250 7 mr m i i rnc TIT T TI ITI TI ITI ITI cmmomimuo222502525 5 25 5 0U5755 5 5 5UUUUUU 5 QDADDAQQDFTPrPrPrPrrrPrrrrTrS S 119 Bulletin No 3020IM9806 February 1999 Alarm No Alarm Descrip
182. replaced by the CM 2450 512k which has more memory at a lower price than the CM 2452 However existing CM 2452 circuit monitors can be upgraded as detailed on the following page Table 1 4 Circuit Monitor Model Numbers Standard Models Models with 512k Option Models with 1024k Option 3020 CM 2050 N A N A 3020 CM 2150 3020 CM 2150 512k 3020 CM 2150 1024k 3020 CM 2250 3020 CM 2250 512k 3020 CM 2250 1024k 3020 CM 2350 3020 CM 2350 512k 3020 CM 2350 1024k 3020 CM 2450 3020 CM 2450 512k 3020 CM 2450 1024k 1999 Square D Company All Rights Reserved Chapter 1 Introduction Upgrading Existing Memory upgrade kits are available for field installation by a qualified Circuit Monitors electrician No special tools are required A DANGER HAZARD OF ELECTRIC SHOCK BURN OR EXPLOSION Only qualified electrical workers should install a memory upgrade kit in a circuit monitor Perform the upgrade only after reading the installation instructions shipped with the upgrade kit Before remov ing the cover of the circuit monitor to install the memory board Disconnect all voltage inputs to the circuit monitor Short the CT secondaries De energize the control power inputs Failure to observe this precaution will result in death or serious injury For Series C3 and earlier circuit monitors the memory upgrade kit can be installed only in circuit monitor models CM 2350 and CM 2450 Note Model CM
183. rite registers only Use the SELECT METER Value buttons to increase or decrease the displayed register number until it reaches the register you d like to write Press the PHASE Enter button The circuit monitor alternately displays the register number and the register contents as a decimal value Use the SELECT METER Value buttons to increase or decrease the displayed decimal value until it reaches the value you d like to write If you ve accidentally selected a read only register the circuit monitor will not allow you to change the value Press the MODE button The circuit monitor displays No To abort the register write press the PHASE Enter button To write the value press the up arrow SELECT METER Value button to change from No to Yes Then press the PHASE Enter button The display flashes indicating that the value has been written then returns to the register number To write another register repeat steps 9 14 above To leave the Diagnostics mode press the MODE button while the circuit monitor displays rEg No Note You can use the diagnostics mode to execute commands using the circuit monitor s command interface First write the desired values to the command parameter registers Then write the code to execute the command See The Command Interface in Chapter 9 for a description of the command interface 1999 Square D Company All Rights Reserved 126 INDEX A
184. rograms are developed using an ASCII text editor such as DOS Edit and saved as SRC files A circuit monitor programming language compiler is then used to process the text file looking for syntax errors or illegal com mands Any errors that are found are listed in a report detailing the errors After program errors are corrected the compiler generates a HEX file which can be downloaded into the circuit monitor using the downloadable firmware utility program Programs that are downloaded into the circuit monitor are secure they cannot be uploaded If changes to a program are desired the new program can be modified from the original program text file re compiled and written over the previous program as a new application 1999 Square D Company All Rights Reserved 59 Bulletin No 3020IM9806 February 1999 APPLICATION EXAMPLES DEVELOPER S KIT 60 Examples of applications where the CM 2450 can be very valuable are as follows metering of specialized utility rate structures e data reduction using smart data logging e automatic monthly logging of kWH and Peak Demand synchronization of Demand Intervals to Time of Day statistical profile analysis of metered quantities e CBEMA power quality analysis calculations for IEEE 519 verification metering of combined utilities gas water steam electric non critical control output decisions such as Load Control or Power Factor Correction based on multi
185. s in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees Range 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 113 Appendix C Calculating Log File Sizes APPENDIX C CALCULATING LOG FILE SIZES This appendix tells how to calculate the approximate size of log files To see if the log files you ve set up will fit in the available logging memory calcu late the size of each event log data log waveform capture log and extended event capture log using the worksheet on the following page Then sum all log files to find the total space required The total space required must be smaller than the numbers listed below e CM 2150 and CM 2250 standard 512k 1024k Sum of event log file and all data log files for standard 512k and 1024k must be smaller than 51 200 313 344 and 575 488 respectively e CM 2350 and CM 2450 standard 512k 1024k Sum of event log file waveform capture log file extended event capture and all data log files for standard 512k and 1024k must be smaller than 51 200 313 344 and 575 488 respectively e CM 2452 Sum of event log file waveform capture log file extended event capture and a
186. s In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths Range 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 10000 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 Reg No 4163 4164 4165 4166 4167 4168 4169 4170 4171 4172 4173 4174 4175 4176 4177 4178 4179 4180 4181 4182 4183 4184 4185 4186 4187 4188 4189 4190 4191 Phase B Current 4192 4193 4194 4195 4196 4197 4198 4199 4200 4201 4202 4203 4204 4205 4206 4207 4208 4209 4210 4211 4212 4213 4214 4215 4216 4217 Description H17 angle with reference to H17 Va angle H18 magnitude as a percent of H1 magnitude H18 angle with reference to H18 Va angle H19 magnitude as a percent of H1 magnitude H19 angle with reference to H19 Va angle H20 magnitude as a percent of H1 mag
187. s with 64 points per cycle resolution To set up the extended waveform capture using SMS 3000 SMS 1500 or PMX 1500 follow these steps 1 In the Onboard Data Storage screen figure 7 3 select the number of cycles for extended capture from the pull down menu 2 Allocate the amount of memory to be used for extended waveform capture by specifying the number of extended waveform captures to be stored 52 1999 Square D Company All Rights Reserved Chapter 7 Disturbance Monitoring Device Setup Asheville Number of Cycles in Extended Event Capture pu mig mAagoo ooascorm Log Log Log Log Log Log Log Log Log Log Log Extended Capture Memory Allocation See View Log Quantities E Figure 7 3 POWERLOGIC System Manager SMS 3000 Onboard Data Storage dialog box 1999 Square D Company All Rights Reserved 53 Bulletin No 3020IM9806 February 1999 SMS 770 SMS 700 EXP 550 or EXP 500 To configure the number of back to back 12 cycle recordings triggered by a single event write a 1 2 3 4 or 5 to register 7298 see table 7 2 below You must then allocate the onboard memory as shown in tables 7 3 and 7 4 to support multiple back to back 12 cycle waveform captures Allocate onboard memory using the Onboard Data Storage setup screen figure 7 4 Once the memory is properly allocated you must perform a file Resize Clear All For information on register writes an
188. s a percent of H1 magnitude H21 angle with reference to H21 Va angle H22 magnitude as a percent of H1 magnitude H22 angle with reference to H22 Va angle H23 magnitude as a percent of H1 magnitude H23 angle with reference to H23 Va angle H24 magnitude as a percent of H1 magnitude H24 angle with reference to H24 Va angle H25 magnitude as a percent of H1 magnitude H25 angle with reference to H25 Va angle H26 magnitude as a percent of H1 magnitude H26 angle with reference to H26 Va angle H27 magnitude as a percent of H1 magnitude H27 angle with reference to H27 Va angle H28 magnitude as a percent of H1 magnitude H28 angle with reference to H28 Va angle H29 magnitude as a percent of H1 magnitude H29 angle with reference to H29 Va angle H30 magnitude as a percent of H1 magnitude H30 angle with reference to H30 Va angle H311 magnitude as a percent of H1 magnitude H311 angle with reference to H31 Va angle 1999 Square D Company All Rights Reserved Appendix B Abbreviated Register Listing Units In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degree
189. s a percent of H1 magnitude H5 angle with reference to H5 Va angle H6 magnitude as a percent of H1 magnitude H6 angle with reference to H6 Va angle H7 magnitude as a percent of H1 magnitude H7 angle with reference to H7 Va angle H8 magnitude as a percent of H1 magnitude H8 angle with reference to H8 Va angle H9 magnitude as a percent of H1 magnitude H9 angle with reference to H9 Va angle H10 magnitude as a percent of H1 magnitude H10 angle with reference to H10 Va angle H11 magnitude as a percent of H1 magnitude H11 angle with reference to H11 Va angle H12 magnitude as a percent of H1 magnitude H12 angle with reference to H12 Va angle H13 magnitude as a percent of H1 magnitude H13 angle with reference to H13 Va angle H14 magnitude as a percent of H1 magnitude 112 1999 Square D Company All Rights Reserved Units in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths
190. s at regular intervals The user can configure up to 14 independent data log files The following items can be configured for each data log file Logging Interval 1 minute to 24 hours Offset Time First In First Out FIFO or Fill amp Hold Values to be logged up to 100 including date time of each log entry Each data log file can be cleared independently of the others using POWERLOGIC application software For instructions on setting up and clearing data log files refer to the POWERLOGIC application software instruction bulletin The circuit monitor can detect over 100 alarm conditions including over under conditions status input changes phase unbalance conditions and more See Chapter 4 Alarm Functions for more information Each alarm condition can be assigned one or more tasks including forced data log entries into any or all data log files For example assume that you ve defined 14 data log files Using POWERLOGIC software you could select an alarm condition such as Overcurrent Phase A and set up the circuit monitor to force data log entries into any of the 14 log files each time the alarm condition occurs There are many ways to organize data log files One possible way is to organize log files according to the logging interval You might also define a log file for entries forced by alarm conditions For example you could set up four data log files as follows Data Log 1 Voltage logged every minute Fil
191. s control power 2 Latched Remotely Controlled The user must energize the relay by issuing a com mand from a remote PC or programmable controller The relay remains energized until a command to de energize is issued from a remote PC or programmable controller or until the circuit monitor loses control power Circuit Monitor Controlled When an alarm condition assigned to the relay occurs the relay is energized The relay remains energized even after all alarm conditions assigned to the relay have dropped out until a command to de energize is issued from a remote PC or programmable controller until the P1 alarm log is cleared from the front panel or until the circuit monitor loses control power 1999 Square D Company All Rights Reserved Chapter 3 Input Output Capabilities 3 Timed Remotely Controlled The user must energize the relay by issuing a command from a remote PC or programmable controller The relay remains energized until the timer expires or until the circuit monitor loses control power If a new command to energize the relay is issued before the timer expires the timer restarts Circuit Monitor Controlled When an alarm condition assigned to the relay occurs the relay is energized The relay remains energized for the duration of the timer When the timer expires if the alarm has dropped out the relay will de energize and remain de energized However if the alarm is still active when the relay timer
192. se input 19 Demand synch pulse input setting upa 76 Developer s kit 60 Disturbance monitoring 49 high speed event log entries 57 sag swell alarms 55 voltage sag swell 50 E Energizing a relay 64 Energy readings 14 Event log high speed entries 57 storage 37 Extended event capture 44 Extended metering ranges setting scale factors fo 66 F Fax On Demand 7 Front panel reading and writing from the 125 G Genericdemand 14 1999 Square D Company All Rights Reserved 127 Bulletin No 3020IM9806 February 1999 H Harmonic calculations setting up individual 77 High speed event log entries 57 How power factor is stored 71 Incremental energy 74 using 74 Input modules Interface command 61 Introduction 1 17 L Log file sizes calculating 115 Logging 37 40 data 38 event 37 maintenance 40 M Maintenance log 40 Memory allocation 69 Memory configuration example 71 Metering capabilities 9 Min max power factor conventions 10 values 10 Min max values 10 Monitoring disturbance 49 Multiple waveform retrieval using SMS 3000 SMS 1500 or PMX 1500 56 using SMS 770 SMS 700 EXP 550 or EXP 500 56 0 Operating relays using command interface 64 Output modules 17 Overriding an ouput relay 65 P Peak demand 13 Pinouts communications pinouts 81 Power analysis values 15 16 Power factor how it is stored 71 Power factor min max conventions Predicted demand 13 Programming language 59
193. second resolution and an rms magnitude corresponding to the most extreme value of the sag or swell during the event pickup delay Anevent capture consisting of up to five back to back 12 cycle recordings can be made for a maximum of 60 continuous cycles of data The event capture has a resolution of 64 data points per cycle on all metered cur rents and voltages e A forced data log entry can be made in up to 14 independent data logs e Any optional output relays can be operated upon detection of the event Atthe end of the disturbance these items are stored in the Event Log a dropout time stamp with 1 millisecond resolution and a second rms magnitude corresponding to the most extreme value of the sag or swell The front panel can indicate by a flashing Alarm LED that a sag or swell event has occurred A list of up to 10 of the prior alarm codes can be viewed in the P1 Log from the circuit monitor s front panel In addition to these features the CM 2350 CM 2450 and CM 2452 include expanded non volatile memory for logging Using POWERLOGIC applica tion software the user can choose how to allocate the nonvolatile memory among the 14 data logs the event log multiple 4 cycle waveform captures and multiple extended event captures You can configure the CM 2350 CM 2450 and CM 2452 to record up to five back to back 12 cycle waveform captures This allows you to record 60 cycles of continuous data on all current and voltage input
194. st completed demand interval Block Interval Demand with Sub Interval Option When using the block interval method a demand subinterval can be defined The user must select both a block interval and a subinterval length The block interval must be divisible by an integer number of subintervals A common selection would be a 15 minute block interval with three 5 minute subintervals The block interval demand is recalculated at the end of every subinterval If the user programs a subinterval of 0 the demand calculation updates every 15 seconds on a sliding window basis External Pulse Synchronized Demand The circuit monitor can be configured to accept through status input 51 a demand synch pulse from another meter The circuit monitor then uses the same time interval as the other meter for each demand calculation See Demand Synch Pulse Input in Chapter 3 for additional details The circuit monitor calculates predicted demand for kW kVAr and kVA The predicted demand is equal to the average power over a one minute interval The predicted demand is updated every 15 seconds The circuit monitor maintains in nonvolatile memory a running maximum called peak demand for each average demand current and average demand power value It also stores the date and time of each peak demand In addition to the peak demand the circuit monitor stores the coinciding average demand 3 phase power factor The average 3 phase power factor is
195. sturbance monitoring of voltage and current waveforms See Chapter 7 for a description of the CM 2350 s disturbance monitoring capability Using POWERLOGIC application software you can initiate a manual exten ded event capture from a remote personal computer Manual event captures which can be used for steady state analysis can be stored in two ways 12 60 cycles of data captured at 64 samples cycle for all voltages and currents simultaneously 12 cycles only in a CM 2250 e 6 30 cycles of data captured at 128 samples per cycle for selected voltages and currents CM 2350 and higher models only To initiate a manual capture select a circuit monitor equipped with extended event capture choose the desired method and issue the acquire command The circuit monitor captures the data and the software retrieves and dis plays it POWERLOGIC software lets you view all captured voltage and current waveforms up to 60 cycles simultaneously or zoom in on a single waveform For instructions on performing manual extended event capture using POWERLOGIC software refer to the application software instruction manual By connecting the circuit monitor to an external device such as an undervoltage relay the circuit monitor can capture and provide valuable information on short duration events such as voltage sags The circuit monitor must be equipped with an optional I O module 44 1999 Square D Company All Rights Reserved Setting
196. t a eene Changing the Demand Calculation Method ttr terni tinere ctim ttai berba tirer o ee 75 Changing to the Block Rolling Method tette triti iiini 75 Setting Upa Demand Synch Pulse Input etit i eee iE te ME pesetas eese e Dk 75 Controlling the Demand Interval Over the Communications Link sss 76 Setting Up Individual Harmonic Calculations ettet ertet qe PEL t Pe ener E 77 Status Input Pulse Demand Metering Pulse Counting Example eame e ERR e US RE Eee Came eir LDedees APPENDICES Appendix A Commiunication Cable Pinouts o tede tpe rene er e ri prie R E e Appendix B Abbreviated Register Listing 5 eri et ice igei Appendix C Calculating Log Fil Sizes ete et nir E eee ED e E eua erhalte Appendix D Alarm Setup Information rettet teretes rt nne tree ic eres Appendix E Reading and Writing Registers from the Front Panel FIGURES 1 1 Circuit monitor series firmware revision sticker croses a aian a 4 2 1 Power factor mm max example eiat ae eite PE lente teer tie nae io PERS 11 22 Default VAR sign COD VventiOn ndr be ise Pee a iaae Ai ehe chi ete 11 2 3 Alternate VAR sign convention ca eerte o e die reip eet A aeir 11 3 1 Demand synch pulse timing esie tete tritt erhebt ta ets eate tbc rete redeo tiende esaet spa 19 32 Analoginputexample ciini recnetiie tiene edeeti nte tlie trib iisas te te hee arbe ele detta sedia 21 3 3 2 wire pulse train
197. t the beginning of the document or the table of con tents at the beginning of a specific chapter Notational Conventions This document uses the following notational conventions Procedures Each procedure begins with an italicized statement of the task followed by a numbered list of steps Procedures require you to take action Bullets Bulleted lists such as this one provide information but not procedural steps They do not require you to take action e Cross References Cross references to other sections in the document appear in boldface Example see Analog Inputs in Chapter 3 6 1999 Square D Company All Rights Reserved Topics Not Covered Here Computer Operating System Windows NT Windows NT Windows NT Windows 95 Windows 3 1 Windows 3 1 DOS RELATED DOCUMENTS Fax On Demand Chapter 1 Introduction This bulletin does not describe the installation and operation of the circuit monitor For these instructions see the Circuit Monitor Installation and Opera tion Bulletin No 3020IM9807 Some of the circuit monitor s advanced features such as on board data log and event log files must be set up over the communications link using POWERLOGIC application software This bulletin describes these advanced features but it does not tell how to set them up For instructions on setting up these advanced features refer to the appropriate application software instruction bulletin listed below Instructi
198. ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees Range 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 10000 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 107 Bulletin No 3020IM9806 February 1999 Reg No 4108 4109 4110 A111 4112 4113 4114 4115 4116 4117 4118 4119 4120 4121 4122 4123 4124 4125 4126 4127 Phase B Voltage 4128 4129 4130 4131
199. tion The circuit monitor is available in several models to meet a broad range of power monitoring and control applications Table 1 2 on page 3 lists the circuit monitor models Table 1 3 compares the features available by model Circuit monitor capabilities can be expanded using add on modules that mount on the back of the circuit monitor A voltage power module and several input output modules are available See Input Output Capabilities in Chapter 3 for a description of the available I O modules 1999 Square D Company All Rights Reserved 1 Bulletin No 3020IM9806 February 1999 What is the Circuit Monitor cont Using POWERLOGIC application software users can upgrade circuit monitor firmware through either the RS 485 or front panel optical communi cations ports This feature can be used to keep all circuit monitors up to date with the latest system enhancements Some of the circuit monitor s many features include 1999 Square D Company All Rights Reserved True rms metering 31st harmonic Accepts standard CT and PT inputs Certified ANSI C12 16 revenue accuracy High accuracy 0 2 current and voltage Over 50 displayed meter values Min Max displays for metered data Power quality readings THD K factor crest factor Real time harmonic magnitudes and angles Current and voltage sag swell detection and recording On board clock calendar Easy front panel setup password protected RS 485 communicati
200. tion Test Register Units Scale Group Alarm Type 68 Over KW Demand Level 2 1731 kW E G 69 Over KW Demand Level 3 1731 kW E G 70 Over kVAR Demand 1732 kVAR E G 71 Over Lagging 3 phase Avg Power Factor 1730 Thousandths H 72 Under 3 Phase Total Real Power 1042 kW E 73 Over Reverse 3 Phase Power 1042 kW E J 74 Phase Reversal 1117 K 75 Status Input 1 Transition from Off to On R 76 Status Input 2 Transition from Off to On E 77 Status Input 3 Transition from Off to On L 78 Status Input 4 Transition from Off to On L 79 Status Input 5 Transition from Off to On L 80 Status Input 6 Transition from Off to On L 81 Status Input 7 Transition from Off to On L 82 Status Input 8 Transition from Off to On L 83 Status Input 1 Transition from On to Off M 84 Status Input 2 Transition from On to Off M 85 Status Input 3 Transition from On to Off M 86 Status Input 4 Transition from On to Off M 87 Status Input 5 Transition from On to Off M 88 Status Input 6 Transition from On to Off M 89 Status Input 7 Transition from On to Off M 90 Status Input 8 Transition from On to Off M 91 98 Reserved 99 End of Incremental Energy Interval N 100 Power Up Reset O 101 End of Demand Interval N 102 End of Update Cycle N 103 Over Analog Input Channel 1 1191 Integer Value P 104 Over Analog Input Channel 2 1192 Integer Value P 105 Over Analog Input Channel 3 1193 Integer Value Pp 106 Over Analog Input Channel 4 1194 Integer Value P 107 Under Analog Input Channel 1 1191 Integer Value Q
201. to block rolling Set external demand synch source to input 1 Set external demand synch source to the command interface Start new demand interval Set new Status Input Pulse Demand Interval Clear all accumulated energies Clear all conditional energies Set energy accumulation method to absolute Set energy accumulation method to signed Disable conditional energy accumulation Enable conditional energy accumulation Set reactive energy and demand method to include only the fundamental component Set reactive energy and demand method to include the both fundamental and harmonic components Start new incremental energy interval Trigger Data Log Entry Reset Req d N lt x lt Z z Zz X lt 63 Bulletin No 3020IM9806 February 1999 OPERATING RELAYS USING By writing commands to the command interface you can control circuit THE COMMAND INTERFACE monitor relay outputs This section tells how to operate the relay outputs See Appendix B registers 2500 2521 for information on relay output configuration Setting Up Relays for To set up the circuit monitor for remote external relay operation you must Remote External Control configure the circuit monitor for remote relay control To configure the circuit monitor for remote relay control 1 Write a bitmap see below to the command parameter register specifying the relays to be setup for remote control Reg Value Description 7701 Bitmap Bitmap corresp
202. ude H23 Va angle defined as 0 0 for H23 reference H24 magnitude as a percent of H1 magnitude H24 Va angle defined as 0 0 for H24 reference H25 magnitude as a percent of H1 magnitude H25 Va angle defined as 0 0 for H25 reference H26 magnitude as a percent of H1 magnitude 106 1999 Square D Company All Rights Reserved in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths tenths of degree in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths In 10ths of degrees in 100ths Range 10000 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0 0 to 32767 0
203. ude H6 angle with reference to H6 Va angle H7 magnitude as a percent of H1 magnitude H7 angle with reference to H7 Va angle H8 magnitude as a percent of H1 magnitude H8 angle with reference to H8 Va angle H9 magnitude as a percent of H1 magnitude H9 angle with reference to H9 Va angle H10 magnitude as a percent of H1 magnitude H10 angle with reference to H10 Va angle H11 magnitude as a percent of H1 magnitude H11 angle with reference to H11 Va angle H12 magnitude as a percent of H1 magnitude H12 angle with reference to H12 Va angle H13 magnitude as a percent of H1 magnitude H13 angle with reference to H13 Va angle H14 magnitude as a percent of H1 magnitude H14 angle with reference to H14 Va angle H15 magnitude as a percent of H1 magnitude H15 angle with reference to H15 Va angle H16 magnitude as a percent of H1 magnitude H16 angle with reference to H16 Va angle H17 magnitude as a percent of H1 magnitude H17 angle with reference to H17 Va angle H18 magnitude as a percent of H1 magnitude H18 angle with reference to H18 Va angle H19 magnitude as a percent of H1 magnitude H19 angle with reference to H19 Va angle H20 magnitude as a percent of H1 magnitude H20 angle with reference to H20 Va angle H21 magnitude as a percent of H1 magnitude H21 angle with reference to H21 Va angle 1999 Square D Company All Rights Reserved Appendix B Abbreviated Register Listing Units In 10ths of degrees in 100ths In 10ths of degrees in 100
204. us input Input S2 can be tied to an external relay used to trigger the circuit monitor s 12 cycle event capture feature see Extended Event Capture in Chapter 6 Note The IOM 11 module does not have an input S2 Status input transitions can be logged as events in the circuit monitor s on board event log Status input transition events are date and time stamped For the IOM 11 IOM 18 and IOM 44 the date and time are accurate to within one second For the IOM 4411 and IOM 4444 all status input transition events are time stamped with resolution to the millisecond for sequence of events recording Status input S1 can be configured to accept a demand synch pulse from a utility demand meter see Demand Synch Pulse Input on the next page Status inputs can be configured to control conditional energy see Conditional Energy in Chapter 9 for more information Status inputs can be used to count KYZ pulses for demand and energy calculation By mapping multiple inputs to the same counter register the circuit monitor can totalize pulses from multiple inputs see Status Input Pulse Demand Metering in Chapter 9 for more information Chapter 3 Input Output Capabilities DEMAND SYNCH PULSE INPUT The circuit monitor can be configured to accept through status input Sl a demand synch pulse from another demand meter By accepting the demand synch pulses the circuit monitor can make its demand interval window match the other met
205. utton until diAg is displayed 3 Press the PHASE Enter button to select the Diagnostics mode The circuit monitor displays the password prompt P 4 Enter the master password To enter the password use the SELECT METER Value buttons to increase or decrease the displayed value until it reaches the password value Then press the PHASE Enter button The circuit monitor display alternates between rEg No an abbrevia tion for register number and 1000 the lowest available register number 5 Usethe SELECT METER Value buttons to increase or decrease the displayed register number until it reaches the desired number 6 Press the PHASE Enter button The circuit monitor reads the register then alternately displays the register number in the format r xxxx and the register contents as a decimal value If you are viewing a metered value such as voltage the circuit monitor updates the displayed value as the register contents change Note that scale factors are not taken into account automatically when viewing register contents 1999 Square D Company All Rights Reserved 125 Bulletin No 3020IM9806 February 1999 10 11 12 13 14 15 16 To read another register press the MODE button then repeat steps 5 and 6 above To write to a register continue with step 9 below Note Some circuit monitor registers are read write some are read only You can write to read w
206. wer Phase C 1446 Maximum Reactive Power 3 Phase Total 1447 Maximum Apparent Power Phase A 1448 Maximum Apparent Power Phase B 1449 Maximum Apparent Power Phase C 1450 Maximum Apparent Power 3 Phase Total 1451 Maximum THD Phase A Current 1452 Maximum THD Phase B Current 88 1999 Square D Company All Rights Reserved In 1000ths of a second Hertz Scale Factor F Degrees Cent in 100ths Amps Scale Factor A Amps Scale Factor A Amps Scale Factor A Amps Scale Factor B Amps Scale Factor C Amps Scale Factor A Amps Scale Factor A Percent in 10ths Percent in 10ths Percent in 10ths Percent in 10ths Volts Scale Factor D Volts Scale Factor D Volts Scale Factor D Volts Scale Factor D Volts Scale Factor D Volts Scale Factor D Volts Scale Factor D Volts Scale Factor D Percent in 10ths Percent in 10ths Percent in 10ths Percent in 10ths Percent in 10ths Percent in 10ths Percent in 10ths Percent in 10ths in 1000ths In 1000ths In 1000ths In 1000ths In 1000ths In 1000ths In 1000ths Percent kW Scale Factor E kW Scale Factor E kW Scale Factor E kW Scale Factor E kVAr Scale Factor E kVAr Scale Factor E kVAr Scale Factor E kVAr Scale Factor E kVA Scale Factor E kVA Scale Factor E kVA Scale Factor E kVA Scale Factor E 96 in 10ths 96 in 10ths Range 0 to 10 000 2300 to 6700 50 60 3500 to 4500 400 10 000 to 10 000 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to 32 767 0 to
207. xample erepto aeter tere toin ente Ha eese RiEs How Power Factor is Stored essercene oe E E EE Changing the VAR Sign Convention eise prises iter ieri tinte Conditional EM Ory accaaneeonm bem tenista iere nnd nde Bri ete iei eg Command Interface Control esses Status Input Control efie reri baee vere eek Pea tete deoa Incremental Energy i mette reet destud ee apetito etn Using Incremental Energy ie cmo eiie peres eed ens Changing the Demand Calculation Method sss Changing to the Block Rolling Method sss Setting Up a Demand Synch Pulse Input 7 eee Controlling the Demand Interval Over the Communications Link Setting Up Individual Harmonic Calculations sss Status Input Pulse Demand Metering sse Pulse Counting Example neant rerit eerte The circuit monitor provides a command interface that can be used to perform various operations such as manual relay operation To use the command interface do the following 1 Write related parameters to the command parameter registers 7701 7709 Some commands require no parameters For these com mands write the command code only to register 7700 2 Wirite a command code to the circuit monitor s command interface register 7700 1999 Square D Company All Rights Reserved 61 Bulletin No 3020IM9806 February 1999 Command Codes The following

Download Pdf Manuals

image

Related Search

Related Contents

  2.1.13 BETEC 305 H  GSM Digital Telephony Card User Manual  Bedienungsanleitung ACD30P ACD31P (pdf, 2,04MB, deutsch)  Losmandy Digital Setting Circles  conservare queste istruzioni  Vers un modèle de "Dictionnaire combinatoire et explicatif des  Parameter input - Cervenka Consulting    952551  

Copyright © All rights reserved.
Failed to retrieve file