MND Modbus Network Display Manual
Contents
1. APG Providing tailored solutions for measurement applications 18 Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com Rev A1 5 14 MND WRITE allows the MND operating in Master mode to write a value to a specific holding register of a specific sensor When Write is selected the MND will guide you through the following steps Sensor Address set the address number of the target sensor Register Number set the register number you wish to change Register Type set the type of register being written 16 bit or 32 bit Register Value set the value you want to write to the selected register Write Yes No select Yes to write the new register value and complete the procedure or No to cancel the write and return to the Communications menu Write function example changing the Empty Distance value register 40407 to 2150 in sensor address number 5 Sensor Address 05 Register Number 407 Register Type U16 unsigned 16 bit Register Value 02150 Write Yes No select Yes by pressing Enter AdDRCHG Address Change allows the user to quickly change a sensor s address when the MND is operating as the Master device Simply enter the current address of sensor you wish to change NOU then enter the new address you wish to write to the sensor NEU Automation Products Group Inc APG APG Providing tailored solutions for measurement applications TUM Tel 1 888 525 7300 Fax 1 435 7
2. The Mode options include On Off 30 Sec 1 min 2 min 4 min 8min and 16 min To adjust the backlight intensity select brightness BRT NES in the menu and use the up down arrow buttons to increase decrease the brightness APG Automation Products Group Inc APG Providing tailored solutions for measurement applications 20 Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com Rev A1 5 14 MND e INPUT Analog Input optional Feature Used to adjust how the MND reads the analog input signal SAM RT determines how often the MND reads the analog input signal AVERGE determines how many readings of the analog signal will be averaged together to become the displayed reading A higher average setting will result in smoother readings but will also cause slower response to rapid changes The following is a list of parameters required to read an analog input COMM menu Set C TYPE to RINPUT OUTPUT menu Set AL SET to the value associated with a 4mA input signal Set RH SET to the value associated with a 20mA input signal Adjust AL CAL and AH CAL as necessary INPUT menu Adjust SAM RT as necessary Adjust AVERAGE as necessary parameters normally do not require adjustment Automation Products Group Inc APG APG Providing tailored solutions for measurement applications pisi Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com 21 MND Rev A1
3. 20 Analog Input Set p NR Tm 21 Using the APG Modbus Software essssessssessssssesererrssrrrrrsseeereerrsssrrresseesrreeese 22 25 Communications Setup Examples sssssessssssssssssseesrrrssssreressttttrerreserresessttreenesesees 26 Resetung to Factory Defaults sssri siiis eni ania senar apena E anaE abra dai a 27 SPE CHMCAIO NG MENS 28 Sensor Register Lists crrsciearcec e eunti rm RE KE UH RU MUERE 29 30 APG Automation Products Group Inc APG Providing tailored solutions for measurement applications 2 Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com Rev A1 5 14 MND e Warranty and Warranty Restrictions APG warrants its products to be free from defects of material and workmanship and will without charge replace or repair any equipment found defective upon inspection at its factory provided the equipment has been returned transportation prepaid within 24 months from date of shipment from factory THE FOREGOING WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES NOT EXPRESSLY SET FORTH HEREIN WHETHER EXPRESSED OR IMPLIED BY OPERATION OF LAW OR OTHERWISE INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE No representation or warranty express or implied made by any sales representative distributor or other agent or representative of APG which is not specifically set forth herein shall be binding upon APG APG shall not be lia
4. 9600 None 1 Master 1 1 303 4 U32 unsigned 32 bit 000 5 seconds Sen 1 Sen 11 00000 disabled Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com 27 MND Rev A1 5 14 Specifications Environmental Housing IP67 Storage Temp 40 to 160 F 40 to 71 C Operating Temp 0 to 160 F 18 to 71 C Electrical Batteries 9 V Lithium or 3 6 V Lithium no outputs External Power 9 28 Vdc Physical Case Material injection molded material EMI X PDX W 88341 4 20 mA Output Input Voltage Requirements 9 Vdc min no load to 28 Vdc max Signal Variance 0 16 mA at set points Output Input 2 wire loop powered Resolution 14 bit Protection reversed polarity 0 5 VDC Output Input Voltage Requirements 9 to 28 VDC Signal Variance 0 05 VDC at set points Type non isolated 3 wire Resolution 1 4 bit Protection reversed polarity Trip Point Solid State Relay Outputs Maximum Switched Voltage 120 V AC DC Maximum Switched Current 120 mA APG Automation Products Group Inc APG Providing tailored solutions for measurement applications 28 Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com Rev A1 5 14 Input Registers 0x04 Register Type 30300 U16 30302 S16 30303 30304 Holding Registers 0x03 Register 40400 40401 40402 40403 40404 40405 40406 40407 40408 40409 40410 40411 40412 40413 40414 40415 4
5. Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com Rev A1 5 14 MND Saving a Settings Configuration To save the current settings configuration click on File then select Save Mode Values Choose the file name and location where you wish to save the file then click Save APG_MODBUS Display Load Mode Values Save Mode Values Exit Max Cal Recalling a Saved Settings Configuration To upload a previously saved settings configuration to the MND click on File then se lect Load Mode Values Choose a file you wish to upload then click Open This will load the parameter values into the software Click the Send All button at the bottom of the window to write the parameters to the MND APG_MUDBUS Display APG_MODBUS Display e Sensor 1 Load Mode Values Sensors input Registers Add Finden ade finden m Save Mode Values EE eene El oec nte 1 287 m Resting mmm A01 Cosssssication 0 3Snif L Ses MASTER SETUP Exit ps Reading imm MQ Bas Rao 0 3408 9600 15200 28408 ATRL A Temparaseo C Pasity O2jasas evan odd Calculated Stop Bits 0 441 stop 2 steph Calculated Scan Rate densi 13999 Signal Snagh Function Code 345 16 Bamesy Voltage y 299 10 608 Tie t on Tig 2 Scroll Readings 0 140 disabled 1 emabbed Register Type 07 Decimal Place o4 Vetere Units os Cuntenn Unit Name AZ Bamery Fell Level Oo enata Battery Emp
6. apgsensors com sales apgsensors com 17 MND Rev A1 5 14 NUR SEN Number of Sensors sets the number of sensors to be monitored When using the MND to display readings from multiple sensors the sensor addresses must begin at 1 and increment sequentially see note above REGNUM Register Number sets the register number to be displayed The readings of APG sensors are stored in register 30303 NOTE the register number is entered using only the last 3 digits of the full register number For example register 30303 would be entered as 303 or register 40401 would be entered as 401 FUNCTN Function sets the function code for the register to be displayed 3 holding resister 4 input register Sensor readings are stored in input registers while sensor parameter values are stored in holding registers REGTYP Register Type sets the bit type of the register to be displayed Options are signed 8 bit low byte S8L signed 16 bit S16 signed 8 bit high byte S8H unsigned 16 bit U16 unsigned 8 bit low byte U8L signed 32 bit S32 unsigned 8 bit high byte U8H unsigned 32 bit U32 NOTE the readings of APG s sensors are stored as an unsigned 32 bit value Refer to the sensor s user manual for a list of register numbers and their corresponding register types SCANRT Scan Rate determines how often the MND polls the sensor s in seconds when operating in Master mode APG Automation Products Group Inc
7. the reading associated with the low analog value either 4mA or OV Used for analog output or analog input AH SET Analog High Set point sets the reading associated with the high analog value either 20mA or 5V Used for analog output or analog input AL CAL Analog Low Calibration adjusts the low end of the analog output either 4mA or OV Increasing decreasing the value will cause an increase decrease at the low end of the analog output AH CAL Analog High Calibration adjusts the high end of the analog output i e either 20mA or 5V Increasing decreasing the value will cause an increase decrease at the high end of the analog output T ITYPE amp TO TYPE Trip 1 amp 2 Type determines the basic functional logic of the solid state relay outputs as described in the Trip Type descriptions on pages 14 16 NOTE the MND s solid state relays are rated for a maximum switched load of 120 mA T IREAd amp TEREAG Trip 1 amp 2 Reading defines the display reading that corresponds to a change in the state of the associated relay output as determined by the Trip Type selected Ti WIN amp Te WIN Trip 1 amp 2 Window defines the secondary value beginning from the Trip Reading for Exclusive Inclusive and Hysteresis Near amp Far Trip Types refer to descriptions below For example if the Trip Reading is set to 250 and the secondary trip value is desired at a reading of 350 then the Trip Window should be set to 100 250
8. to 100000 mm O to 100000 mm O to 100000 mm APG Providing tailored solutions for measurement applications Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com Rev A1 5 14 MND Notes Automation Products Group Inc APG APG Providing tailored solutions for measurement applications PEN Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com 31 PRODUCTS GROUP INC APG Providing tailored solutions for measurement applications Automation Products Group Inc Tel 1 888 525 7300 1 435 753 7300 Fax 1 435 753 7490 e mail sales apgsensors com www apgsensors com Automation Products Group Inc 1025 W 1700 N Logan UT 84321 To order additional copies of this manual ask for APG part number PN9000000 Rev A 6 09
9. until the reading is once again greater than the Trip Reading Trip Window refer to chart on next page NI IN c3 Holds the output closed whenever the display is powered c3 F Disables the output continued on pages 15 16 Automation Products Group Inc APG APG Providing tailored solutions for measurement applications m Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com 13 MND Rev A1 5 14 Trip Type Descriptions continued INCLUSIVE Sh ao OFF ON open closed HYSTERESIS FAR e closed ZERO READING TRIP READING TRIP WINDOW ee d ons j close open NEAR i ON OF ON closed open closed EXCLUSIVE ON ON closed OFF closed open HYSTERESIS NEAR OFF open ies j bis d open close FAR O ke l OFF ON OFF open closed open APG Automation Products Group Inc APG Providing tailored solutions for measurement applications 14 Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com Rev A1 5 14 MND Trip Type Descriptions continued LOERST LOE RST forces the output to follow the state of the corresponding output of an LOE or RST sensor acting as the master device For example whenever output T1 of the LOE RST activates deactiv
10. with one of APG s Modbus sensors MNU MP or MPT series to create a simple yet complete monitoring system Whenever relay 1 T1 is active the battery voltage will be applied to the switched power source output which should be connected to the voltage input of the sensor By setting relay 1 to On and then setting up a short Auto Off timer refer to Advanced settings the user can simply push the power button on the MND to wake the system and poll the sensor to get the reading The Auto Off will automatically power down the system to save battery life APG recommends an Auto Off setting of 15 20 second in order to maximize battery life WARNING the switched power output sources voltage directly from the battery and caution must be taken not to let the output come in contact with any of the other output lines DC common or the communication lines APG Automation Products Group Inc APG Providing tailored solutions for measurement applications 16 Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com Rev A1 5 14 MND e COMM Communications bAUd R Baud Rate 2400 9600 19200 38400 PARITY even odd none STOPDT Stop Bit 1 2 NOTE all APG Modbus based sensors communicate using 9600 baud no parity and 1 stop bit C TYPE Communications Type MASTER sets the MND to operate as the master device SNIFER Sniffer sets the MND to passively monitor communications between a mast
11. 0416 40417 40418 40419 40420 40421 40435 40436 40437 40438 40439 40440 40441 40442 40443 40444 40445 U32 Type U16 U16 U16 U16 U16 U16 U16 U16 U16 U16 U16 U16 U16 U16 U16 U16 U16 S16 U16 U32 U32 U32 U32 U32 Automation Products Group Inc APG Providing tailored solutions for measurement applications MND MNU Series Ultrasonic Returned Data Raw Distance Level Reading in mm Temperature Reading in C signed Calculated Reading in selected units no decimal Description Value Range Device Address 1 to 255 Units 1to3 Application Type 0 10 Volume Units 0to6 Decimal Place 0to3 0 to 10364 mm O to 10364 mm 0 to 10364 mm Max Distance Full Distance Empty Distance Sensitivity 0 to 100 Pulses 0 to 20 Blanking O to 10364 mm Gain Control 0to4 Averaging O to 100 Filter Window 0 to 10364 mm Out of Range Samples Oto 255 Sample Rate 50 to 1000 msec Multiplier 1 to 1999 Offset 10364 mm reserved Temperature Compensation 0 off 1 0n reserved Parameter 1 Data Parameter 2 Data Parameter 3 Data Parameter 4 Data Parameter 5 Data 0 to 100000 mm 0 to 100000 mm 0 to 100000 mm 0 to 100000 mm 0 to 100000 mm APG Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com 29 MND Input Registers 0x04 Register Type 30300 U16 30301 U16 30302 S16 30303 30304 U32 30305 30306 U32 Holding Registers 0x03 Register 40400 40401 40402
12. 100 350 APG Automation Products Group Inc APG Providing tailored solutions for measurement applications 12 Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com Rev A1 5 14 MND Trip Type Descriptions Refer to the chart on the next page for an illustration of Near Far Exclusive Inclusive and Hysteresis Near amp Far trip types NERR The output will activate whenever the reading is less than the Trip Reading setting refer to chart on next page EXCLSV Exclusive The output will activate whenever the reading is less than the Trip Reading OR greater than the Trip Reading Trip Window refer to chart on next page H NERR Hysteresis Near The output will activate until the reading is greater than the Trip Reading Trip Window at which point the output will deactivate and remain in that state until the reading is less than the Trip Reading refer to chart on next page FAR The output will activate whenever the reading is greater than the Trip Reading refer to chart on next page INCUSV Inclusive The output will activate whenever the reading is greater than the Trip Reading and less than the Trip Reading Trip Window refer to chart on next page H FAR Hysteresis Far The output will activate when the reading increases beyond the Trip Reading Trip Window and will remain active until the reading falls below the Trip Reading The output will remain deactivated
13. 40403 40404 40405 40406 40407 40408 40409 40410 40411 40412 40413 40414 40415 40416 40417 40418 40420 40421 40422 40423 40424 40425 40426 40435 40436 40437 40438 40439 40440 40441 40442 40443 40444 40445 APG 30 Type U16 U16 U16 U16 U16 U16 U16 U16 U16 U16 U16 U16 U16 U16 U16 U16 S16 S16 U16 U32 U32 U32 U32 U32 U32 U32 U32 MP Series Magnetostrictive Returned Data Rev A1 5 14 Raw Top Float Reading in mm unsigned Raw Bottom Float Reading in mm unsigned Temperature Reading in C signed Calculated Top Float Reading in selected Units Calculated Bottom Float Reading in selected Units Description Device Address Units Application Type Volume Units Decimal Place Max Distance Full Distance Empty Distance Sensitivity Pulses Blanking reserved Averaging Filter Window Out of Range Samples Sample Rate Multiplier Offset reserved RTD Offset OC Float Window Top Float Offset Bottom Float Offset Gain Offset reserved Parameter 1 Data Parameter 2 Data Parameter 3 Data Parameter 4 Data Parameter 5 Data Automation Products Group Inc Value Range 1 to 255 1to3 0 10 Oto6 0 to 3 O to 10364 mm O to 10364 mm O to 10364 mm O to 100 O to 20 O to 10364 mm O to 100 O to 10364 mm Oto 255 50 to 1000 msec 1 to 1999 10364 mm 100 to 100 O to 1000 mm 10364 mm 10364 mm Oto 255 0 to 100000 mm O to 100000 mm O
14. 5 14 Programming the MND using APG Modbus Software The MND s Setup communications type see C TYPE on page 17 allows the MND to be programmed using software instead of the buttons on the display The software used to program the MND is the same software used to program any of APG s line of Modbus sensors MNU MP PT series Interfacing with the software also allows the user to save MND configurations to a PC or to write a previously saved configuration back to the MND see page 24 Use the following steps to establish communications and program the MND via the APG Modbus software Step 1 Use the buttons on the MND to enter the Communications menu and change the Communications Type C TYPE to SETUP Step 2 While still in the MND Communications menu take note of the Sensor Address SENAGR setting This setting will become the MND s address when communicating to the software Step 3 Install and run the APG Modbus software Step 4 Click on Configure in the top menu then select Communication to bring up the Communication Configuration window APG MODBUS Disriay e Configure 7 Tools Help l Input Registers Descnpue Max Calculate Value Calculated2 Signal Strength Add Chart ESTE Meters a a hr continued on next page APG Automation Products Group Inc APG Providing tailored solutions for measurement applications 22 Tel 1 888 525 7300 Fax 1 43
15. 5 753 7490 www apgsensors com sales apgsensors com Rev A1 5 14 MND Step 5 Check the USB Communication Step 6 Ensure Sensor box when using an RST 6001 RS 485 to matches the Sensor Address USB converter setting in the MND or Select the Com Port assigned to the RS 485 to RS 232 converter being used tep 7 Select MND Decription 1 Sensor 1 Update Comm Pt SE lt I lt i SEE I tep 8 Once all the changes have been made click Save Config then click Close Step 9 Click on Sensor 1 to enter the programming window for the MND continued on next page Automation Products Group Inc APG APG Providing tailored solutions for measurement applications rr Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com 23 MND Rev A1 5 14 tep 10 When the programming window opens the register values should automati cally populate if not click the Receive All button at the bottom of the window To change a single parameter simply click on the value you wish to change enter the desired value then click the adjacent Send button to write the new value to the MND APG MOUBUS Deptay Adi Furcten Akt funden Medel Typo t DH device ness m Reading imm 401 Coasmmm cation 301 Readieg nuni 402 Baed Rate 302 Temperature C A03 Pasity m Calculamd Step Bits 305 Calculated Scan Rate ess 307 Signal Shen
16. 53 7490 www apgsensors com sales apgsensors com 19 MND Rev A1 5 14 e SENLAb Sensor Labels Allows the user to assign a custom label for each sensor being displayed up to 10 sensors an LOE RST master The sensor label will appear on the lower display line which will alternate between the Sensor Label and the selected Unit of measure NOTE Setting a Mode Access Password refer to Access Modes on page 7 If a label is assigned for Sensor 10 the label becomes the password to access the Mode setting If the label for sensor 10 is set to the default of 10AAAA then no password will be required to access the Mode setting e PCTFUL Percent Full Allows sensor readings to be displayed as a percentage of full based on a user defined 10096 value To enable the Percent Full feature select PC TFLL in the main menu Select the sensor number you want to display as a percentage of full and enter the value associated with 10096 096 empty is assumed to be O Setting the value to 00000 default will disable the Percent Full feature NOTE the label PCTFUL will be automatically be displayed as the units of measure for all sensors running in Percent Full mode NOTE when controlling one of the MND s outputs with a sensor setup to display in Percent Full mode the settings controlling the output need to be entered based on the underlying readings and not the displayed percentage value e bLIDHT Back Light optional Feature
17. A re White Green Fswitched Source Red TL See 4 20 mA no connection on internal battery powered option refer to Switched Power Source description on page 16 for more information 5 Conductor Cable V Red V com RS 485 A White RS 485B Green 0 5 Vdc 420mA 8 Conductor Cable 2 SS Relays 0 5 Vdc 2 SS Vk Red Red com RS 485A RS4855 5S Relay 1 SS Relay 1 Blue SSRelay2 Blue shared common SS Relay osv c orange APG Automation Products Group Inc APG Providing tailored solutions for measurement applications 4 Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com Rev A1 5 14 MND 5 Pin Micro Connector g 20 Ow rmn ite 3 Blue 3 5 4 O O 4 Black 5 Grey No Outputs Switched PowerSource 420m o5Vdc ve mibow Pnitown in 1 brown Pin 3 blue Pin3 blue Switchsoure Pini brown o oswe TO Pith xm 1 DW39w no connection for internal battery powered option refer to page X for more information 8 Pin Micro Connector Pin 1 White Pin 2 Brown Pin 3 2 Green Pin 4 Yellow Pin 5 Grey Pin 6 Pink Pin 7 Blue Pin 8 Red SS Relay 1 SS Relay 1 Pin 5 grey SS Relay 2 shared common S5 Relay 2 Automation Products Group Inc APG APG Providing tailored solutions f
18. AL RH CAL T ITYPE T IREAd T 1 WIN TeTYPE TeRERd A Te un EXIT RUTO 4 AdVSET dEC PL MASK SHIFT MLTPLR bAR D bRR 108 GVR Ld bAT EN bRTFUL nos EXIT A DISPLAYED VALUE 3930 Main Menu GALLON MAXMIN ENTR TEMP C TEMP F 2 REAd EXIT comm pbAUd R PRRITY TOPbT C TYPE SENAGR NUMSEN REGNUM FUNCTN REGTYP SCANRT WRITE RdREHG EXIT SENLAb p SEN n SEN SEN SEN SEN SEN SEN SEN SEN SEN ID torst EXIT PCTFUL gt SEN a SEN 2 SEN 3 SEN 4 SEN 5 5 3 B 9 nua urew OO 4 gv ume wi ony SEN SEN SEN SEN SEN 10 NS tEeesr EXIT bLIGHT r MOJE bRTNES EXIT INPUT gt SAM RT i AVERGE EXIT Main Menu Automation Products Group Inc APG Providing tailored solutions for measurement applications Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com Rev A1 5 14 Rev A1 5 14 MND e UNITS Units of Measure Label Allows the user to select the unit of measure label that will appear on the lower display line Options CU FT Cubic Feet LITERS Liters MCU FT Million Cubic Feet CU IN Cubic Inches GALLON Gallons bARREL Barrels CU M Cubic Meters PCTFUL Percent Full CUSTOM Custom Units NOTE the units of measure selected will be applied to all sensor readings and cannot be set individually for each sensors NOTE the units label will automati
19. PRODUCTS GROUP INC Operator s Manual MND Modbus Network Display DOC 9003708 Rev A1 5 14 Automation Products Group Inc APG Providing tailored solutions for measurement applications Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com E mail sales apgsensors com MND Rev A1 5 14 Table of Contents hari f NY 3 ire ge RET TER 4 5 B U Au1 ALI eme ENSE 6 Access ModE hc PEINE RE 7 Menu Flow Chatt EN E EE 8 Units of WCE SUING ssop konnen REEE VA EEN EEES EEDEN 9 Enter B tton FUMCHON ncsaccnssenne tac deeevseuvverpateewareiourkewnnnpas EEE 9 Advanced Seti Lied na dass utis near fe pee ra ee d eint rene ee ae 10 11 Auto ur NIMM EMT TU 11 punit 11 Digit NSLS c M c 11 Digit SWI cece T 11 PRU ee Dm 11 Beeld Gra trc TP 11 ONE OGG ee MINE E 11 Battery Indicator MN ren E O R OEE 11 Edi c E E E e Ea a pens 12 15 Analog Seting ade face reece a sect E TOS 12 Solid State Relay Settings iocsoscebx qi to rete pela tutu dato ou c epe ERR ER NINOS Gd uE 12 15 Switched Source POWOT 2 5 m cc botte Po Rap Expo Ur Re Cx eux rd do wx E REB Epp ARR Eikai 16 COMMUNICATIONS Settings esrin cnet at EE po RUEPUM Une ve p IUE pls uvis iUe 17 19 S cgi Rooms eee 20 Percent Full Mde cis 20 Bist Fe ICIS DE enerne sne Eo a NEE EEE EE EN
20. ates then output T1 of the MND will activate deactivate as well TIME R Timed Interval sets the output to activate on a timed interval The Interval Time INTMIN sets the time between activations in minutes and the On Time GN SEC determines how long the output remains active at each interval in seconds NOTE when using the Timed Interval in conjunction with the Auto Off feature the MND will wake power on at each Interval and will remain powered on for the duration of the relay On Time regardless of the Auto Off setting INTERVAL TIME in minutes ON TIME in seconds Relay OFF open Relay ON closed 1 H TEMP Heater Temperature The LCD heater is controlled using Trip Relay 1 Set the heater on temperature using the Trip 1 Reading T IREAD parameter in C The Trip 1 Window T UIN parameter is used to set the off temperature defined by the number of degrees above the on temperature For Example to activate the heater at 30 C and deactivate the heater above 10 C T ITYPE set to H TEMP T IRERO set to 0030 T i UIN setto 00020 Optional Feature Automation Products Group Inc APG APG Providing tailored solutions for measurement applications Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com 15 MND Rev A1 5 14 Switched Power Source This option is designed to allow an internal battery powered MND to share the battery power
21. ble for any incidental or consequential damages losses or expenses directly or indirectly arising from the sale handling improper application or use of the goods or from any other cause relating thereto and APG s liability hereunder in any case is expressly limited to the repair or replacement at APG s option of goods Warranty is specifically at the factory Any on site service will be provided at the sole expense of the Purchaser at standard field service rates All associated equipment must be protected by properly rated electronic electrical protection devices APG shall not be liable for any damage due to improper engineering or installation by the purchaser or third parties Proper installation operation and maintenance of the product becomes the responsibility of the user upon receipt of the product Returns and allowances must be authorized by APG in advance APG will assign a Return Material Authorization RMA number which must appear on all related papers and the outside of the shipping carton All returns are subject to the final review by APG Returns are subject to restocking charges as determined by APG s Credit Return Policy Automation Products Group Inc APG APG Providing tailored solutions for measurement applications zia Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com 3 MND Rev A1 5 14 Display Wiring 4 Conductor Cable No Outputs Switched Voltage Source 4 20 m
22. cally display PCTFUL percent full for any reading being displayed in Percent Full mode see page 21 for more information e ENTR Enter Button Function Selects the function of the ENTER button when in standard operating mode Enter Button Function 2RD IF enD IC o RERd TEMP F Automation Products Group Inc APG APG Providing tailored solutions for measurement applications Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com cycles between 2 readings amp temperature in F cycles between 2 readings amp temperature in C cycles between 2 readings cycles between the reading and the temperature in F cycles between the reading and the temperature in C cycles between the present reading and the highest and lowest readings 2nd reading is applicable to MP dual float sensors only MND Rev A1 5 14 e RHaVSET Advanced Settings UTO Auto Off The Auto Off feature will automatically power off the MND whenever no buttons are pressed within the specified time frame The minimum Auto Off time is 15 seconds To disable the Auto Off feature set the value to 65535 default NOTE the Auto Off cannot be set to less than the relay On Time setting when using the Timed Relay option see Outputs dEC PL Decimal Place defines where the decimal point will be displayed within the reading NOTE most APG sensors have the ability to set the number of decimal places of the readi
23. er device and one or more sensors The master device must be actively polling the sensor s in order for the MND to update the reading s LRSNIF LOE RST Sniffer functions the same as Sniffer mode with addition of monitoring the readings from an LOE series or RST 5000 series Ethernet based sensor acting as the master device SETUP sets the MND to act operate as a slave device in order to be programmed using the APG Modbus software NOTE the Sensor Address parameter see below is used to set the MND s own sensor address when in operating in Setup mode AINPUT displayed reading is based on the analog input signal and related settings Optional feature Refer to INPUT menu section for more information SENAGR Sensor Address sets the address number of the sensor to be displayed when only one sensor is being monitored The Sensor Address is also used to set the MND s own address when operating in Setup mode NOTE in order to monitor readings from multiple sensors the assigned sensor address numbers must begin at 1 and increment sequentially For example if 5 sensors are to be monitored the sensor addresses must be set to 1 thru 5 NOTE when displaying the readings from multiple sensors the Sensor Address setting determines which sensor is controlling the output s of the MND Automation Products Group Inc APG APG Providing tailored solutions for measurement applications Tel 1 888 525 7300 Fax 1 435 753 7490 www
24. g Functse Code 30 Bamery Voltage Reqistes Address 08 Tip 1 Wumbe of Samsois 1m Tile 2 Scroll Readings 0 19 disabled 1 sable Registe Type o7 Decimal Piace n4 Vobewer Unite os Corstens Unit Rame Az05 Bamery Felt Level Oto 99 qr Battery Empty Level Oto 999 ft Battery Enable 0 2 Mo battintermat ASTLOE Display Mack 0 3 498 0 00 40H Decimal Si 04 40 1 99 996 10001 Mena Leck om Stertup Logo Custom Flag 0 465595 Trip 1 type os Trip 2 type nA nA Step 11 To change multiple parameters individually click on the values you wish to change enter the desired values then click the Send AII button at the bottom of the window to write all the values to the MND After clicking Send or Send All a green window indicates good communication and the value was successfully written to the MND A yellow window indicates the value was not written due to either a communication ailure or the value exceeds the allowable limits for that parameter 405 Scan Rate iei 19999 Send Read 405 Scan Rate jmd 19995 A Funcmes Code LAAN 4 Send Read A0 Func amp se Code 344 8 AU Register Address 209 te 040 2 Bead AU Regsan Address 299 te 600 A08 ember of Seasons on 1 Send Bead 408 Member of Sensen on 109 Sere Readings 108 dnabled 1 enabled Send Read 40 Scre Readings 108 sables 1 enablodi APG Automation Products Group Inc APG Providing tailored solutions for measurement applications 24
25. ngs being sent to the MND Refer to the sensor manual for more information MASK Digit Mask allows the user to mask the value of the least significant digit s up to 3 places so that masked digit s will always display O and will not increment SHIFT Digit Shift allows the user to shift the reading to the right by dividing the reading by 10 100 or 1000 fL TPLR Multiplier allows the user to apply a conversion multiplier to the sensor readings For example a multiplier setting of 2 0 will double the reading received from the sensor NOTE most APG sensors have the capability to apply a conversion multiplier to the reading before the value it is sent to the MND bAR D Bar Graph 096 amp bRR i00 Bar Graph 100 define the readings associated with 096 and 10096 on the display bar graph Bars will appear disappear in 1096 increments of the total span NOTE the bar graph limits will be applied to all sensor readings when multiple sensor are being displayed and cannot be set individually for each sensor Advance Settings continued on next page APG Automation Products Group Inc APG Providing tailored solutions for measurement applications 10 Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com Rev A1 5 14 MND OVR Ld Overload allows the user to set an overload warning if the reading increases beyond the specified value NOTE when displaying the readings from multiple sen
26. or measurement applications UR Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com 5 MND Rev A1 5 14 Using the MND Output Status Indicator Scalable Bar Graph Battery Meter Increase Button Enter Button Decrease Power Button Increase Button Function in Operating Mode cycles through sensor readings when setup to display multiple sensors readings Function within Setup Menu press to cycle upward through menu options or to increase mode setting values Decrease Power Button Function in Operating Mode press and hold for 1 second to power on or off the MND Function within Setup Menu press to cycle downward through menu options or decrease mode setting values Enter Button Function in Operating Mode cycles between the current maximum and minimum readings Function within Setup Menu press to enter into the selected menu or to accept a setting option within a menu APG Automation Products Group Inc I APG Providing tailored solutions for measurement applications 6 Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com Rev A1 5 14 MND Access Modes The MND has several operating modes which will limit or lock access to the setup menus Refer to the mode descriptions at the bottom of the page for more information To access the operating mode setting follow the steps below Step 1 Step 2 001 002 003 004 005 Simul
27. r Address n a sensors addresses are assumed to begin at 1 Register Number 303 Function 4 Register Type U32 unsigned 32 bit APG Automation Products Group Inc APG Providing tailored solutions for measurement applications 26 Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com Rev A1 5 14 MND Resetting the MND to factory defaults Simultaneously press and hold the Decrease Power button and Enter button for approximately 5 seconds This will bring up the 3 digit operating mode number Change the mode number to 125 and press the enter button This will reset all parameter values to the following factory defaults Parameter Units Auto Off Decimal Place Digit Mask Digit Shift Multiplier Bar Graph 0 Bar Graph 100 Over Load Battery Gauge Enable Battery Full Battery Low Analog Low Reading Analog High Reading Analog Low Calibration Analog High Calibration T1 Type T1 Reading T1 Window T2 Type T2 Reading T2 Window Baud Rate Parity Stop Bits C Type Sensor Address Number of Sensors Register Number Function Register Type Scan Rate Sensor Labels Percent Full Automation Products Group Inc APG APG Providing tailored solutions for measurement applications Value Gallons 65535 disabled 0 Off 0 1 000 0 10000 99999 max display value No Battery 13 5V 11 0V 0 99999 0 16383 Off 1000 500 Off 1000 500
28. sors the Overload setting will be applied to the readings of all the sensors and cannot be set for each sensor individually By default the Overload is set to 99999 so that the overload warning will only be displayed when a sensor reading is greater than 5 digit limit of the display bAT EN Battery Enabled allows the user to select either No Battery Internal Battery or RST Battery options The Internal Battery option is used to monitor the voltage of a battery powered MND The RST Battery option is used to monitor the supply voltage of an RST 5000 module acting as the master device NOTE the Internal battery indicator is limited to battery voltages less than 15 Vdc bATFUL Battery Full Voltage sets the voltage associated with a full battery indication bRHTLOU Battery Low Voltage sets the voltage associated with a low battery indication Automation Products Group Inc APG APG Providing tailored solutions for measurement applications TUM Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com 11 MND Rev A1 5 14 e OUTPUT Outputs The MND is offered with optional outputs such as solid state relays or 4 20 mA or 0 5 Vdc analog signals Not all output menu options are applicable to all MND configurations NOTE when displaying the readings from multiple sensors the Sensor Address setting determines which sensor is controlling the output s of the MND AL SET Analog Low Set point sets
29. taneously press and hold the Decrease button and the Enter button for approximately 5 seconds to bring up the 3 digit mode access number Use the Increase Decrease buttons to change the value of he flashing digit and Enter button to accept the value and advance to the next digit The mode options are as follows Description Full Access All menu options are accessible including those that may not be applicable to all MND configurations Locks access to all setup menus The Increase Button will scroll through sensor readings when the MND is configured for multiple sensors The Decrease Power Button will turn on off the display The Enter button will scroll between the maximum minimum and the current reading Hides the Output menu All other setup menus are accessible Hides the analog options in the Output menu only the relay options are accessible Hides the relay options in the Output menu only the analog options are accessible All menus are hidden and all buttons are lock except the Decrease Power button which will power on off the MND Also see Setting Mode Access Password under Sensor Label section of page 20 APG Providing tailored solutions for measurement applications suns E Automation Products Group Inc APG Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com 7 MND Menu Flow Chart APG 8 anes nr _ Many AL SET OUTPUT AH SET AL C
30. ty Level Oto rhet Bamery Enable 0 2 Mo batt IntormaASTLOE Disptay Mack OF 0H 0 00 00 Decimal Shit 04 40 1 99 0060 10001 Mesa Leck om Startup Logo 0 10 Custom Flag 045535 Trip 1 type oe Trip 2 type 0 WA wa J 3 1 o o 5 4 LE 3 1 amp o L Eu E Automation Products Group Inc APG APG Providing tailored solutions for measurement applications A Tel 1 888 525 7300 Fax 1 435 753 7490 www apgsensors com sales apgsensors com 25 MND Rev A1 5 14 Communications Setup Examples For APG sensors the sensor readings are stored in register 303 which is an unsigned 32 bit register MND master displaying readings from a single sensor address 1 C Type Master Number of Sensors 1 Sensor Address 1 Register Number 303 Function 4 Register Type U32 unsigned 32 bit MND master displaying multiple sensor readings addresses 1 6 C Type Master Number of Sensors 6 Sensor Address n a sensors addresses must begin at 1 Register Number 303 Function 4 Register Type U32 unsigned 32 bit MIND in Sniffer mode displaying readings from a single sensor address 3 C Type Sniffer Number of Sensors 1 Sensor Address 3 Register Number 303 Function 4 Register Type U32 unsigned 32 bit MIND displaying the readings from 2 sensors an LOE ultrasonic C Type LOE RST Sniffer LRSNIF Number of Sensors 2 the LOE sensor is assumed and not included in the count Senso
Download Pdf Manuals
Related Search
Related Contents
Indesit FV 10 K.B IX GB Oven User Manual USER`S MANUAL VERY WIDE BEDS XXL DIVISYS AND XXL Dahle 41314 paper shredder Mode d emploi Liste des pièces de rechange aerosol ambientador ph 06 - Sea-Doo.net Supermicro A+ Server 1040C-T, Beige 取付・取扱説明書 - ミツバサンコーワ Bedienungsanleitung Sabine SL820 SM820 - TRIUS Samsung Samsung GALAXY Copyright © All rights reserved.