MOD9200D MODBUS Transceiver User Manual

image

Contents

1. User s Manual MOD9200D MODBUS Transceiver MOD9200 MODBUS Gateway Programming Software License Agreement for Automation Components Inc Software IMPORTANT READ THESE TERMS CAREFULLY BEFORE INSTALLING THIS SOFTWARE THESE TERMS AND CONDITIONS ESTABLISH A CONTRACT BETWEEN YOU INDIVIDUALLY IF YOU ARE AGREEING TO IT IN YOUR OWN CAPACITY OR IF YOU ARE AUTHORIZED TO AGREE ON BEHALF OF YOUR COMPANY OR ANOTHER ORGANIZATION BETWEEN THE ENTITIY FOR WHOSE BENEFIT YOU ACT YOU AND ACI BY INSTALLING THIS SOFTWARE PACKAGE YOU ACKNOWLEDGE THAT YOU HAVE READ THIS LICENSE AGREEMENT THAT YOU UNDERSTAND IT AND THAT YOU AGREE TO BE BOUND BY ITS TERMS IF YOU DO NOT AGREE TO THE TERMS AND CONDITIONS OF THIS LICENSE AGREEMENT OR IF YOU DO NOT UNDERSTAND THEM PROMPTLY RETURN THE UNOPENED PACKAGE AND ALL ACCOMPANYING ITEMS TO ACI FOR A FULL REFUND 1 Grant of License for Registered Users ACI grants you a non exclusive non transferable license to use the software program with which this license is distributed the Product including any documentation files accompanying the Product Documentation on any single computer You may use the Product on a second computer so long as only one 1 is used at a time 2 Backup Copy You may make one backup copy of the Product You may use it only to reinstall the Product 3 Ownership You have no ownership rights in the Product Rather you have a license to use the Product as long as this License Agree
2. 2 3 4 e The active transmission channels or output number are factory set as follows Device Digital Analog RD2402 1 to 2 for relay 1 NA Wireless relay and relay 2 output module RD2432 1 to 4 for relay 1 1 to 4 for analog Wireless digital amp to relay 4 output to 4 analog output module g Analog Output Holding Register Configuration e Select the Analog Output Holding Register table by clicking the RegisterBank tab f S Editor CURRENTLY EDITING File Settings Points Row RegisterEntry Register Bank ADDRESS GROUP NAME Input Registers 0 Garage Digital Qutput Coil Registers Analog Output Holding Registers AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 18 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software e First we will assign the REG ADDRESS by clicking in the cell Before entering register addresses ensure the RegisterEntry AutoSet is turned off as shown e Enter the Register address in the REG ADDRESS window The valid range is O to 49 REG ADDRESS GROUP NAME POINT MAME TRANSMITTER ID TRANS CHAN Again use the mouse to move to the next column Enter a GROUP NAME if desired for the data set by typing the group name in the cell Enter the name in the cell by using the mouse to click on the next c
3. Gateway Programming Software File Transfer EJ C trstconfigiT rs Suite ini File Name TCP IP 192 168 0 1 IP Address TCPAP ie Comm Status Disconnected Connect Disconnect E Fie Status e Click on Connect and the status of the connection will be displayed in the Comm Status window When the Gateway is connected click on Send File to the send the config file to the Gateway m Activating The Config File e Once the config file has been sent to the Gateway it will become active immediately If you have changed the IP Address in the config file you will lose your connection and have to reconnect using the IP Address and Subnet Mask that was sent in the new config file AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 30 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software File Transfer C Mtrs config Trs Suite ini File Name TCP IP 192 168 0 1 IP Address TCFP7IP T Comm Status Connect Disconnect E Fie Status OO mde Cee e To confirm that the appropriate configuration file is saved on the Gateway reopen the File Transfer Dialog and click on Get File to retrieve a copy of the active configuration file from the Gateway The Editor will automatically save this file in the folder trs config with the file name of _config ini e Click on File gt Open Con
4. Spectrum Mesh Network Radio technology When used with other wireless sensors the system can transmit remote sensor readings status alarm indications and control signals to a centralized networked monitoring station or controller without the need for extensive wiring The MOD9200 is compatible with any control system or Programmable Logic Controller PLC panel that utilizes the TCP IP or RS485 RS232 RTU ASCI MODBUS communication protocols a MOD9200 Gateway System e MOD9200 MODBUS Network Receiver e Receives input from up to 50 remote wireless sensor modules and or wireless output modules RD2402 amp RD2432 per Transceiver e Signal repeater router RR2552 can be used to extend the wireless sensor transmission distance if needed e Ethernet Network Connection or RS485 RS232 Connection e MOD9200 Configuration Software Sensor Wireless Remote Digital Analog Input Modules amp Energy Totalizer Wireless Immersion amp Remote Sensors Wireless Outside Air Temperature amp Humidity AUTOMATION COMPONENTS INC 2305 Pleasant View Road Middleton Wisconsin 53562 www workaci com 888 967 5224 Wireless Wall Temp amp Humidity MODBUS Network Z Wireless Digital Relay Outputs voo aih MODBUS Transceivers i i Wireless Digital amp Analog Outputs Repeater Increases Transmission Distance if needed Sub System Overview Version 0 2 10000676 Page 4 of 38 MOD9200 MODBUS Gateway Progr
5. View Road 10000676 Middleton Wisconsin 53562 Page 25 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software e The number of Data Bits needs to be the same as in the Master configuration Serial Comm Port Properties Masinun Speed a600 Modbus Transport Connection Freferences RTU 0 ASCII Data Bits 8 Parity Jiz Shop Bits 1 ae p ance e Parity is used for simple error checking Select the proper Parity even odd or none by clicking on the selection arrow and selecting either even odd or none If none is selected 2 stop bits are required e Parity needs to be the same as in the Master configuration Serial Comm Port Properties Maximum Speed S600 Modbus Transport i E Connection Preferences ATU Data Bits Parity fe ASCII Stop Bits OK Cancel e The appropriate number of Stop Bits depends on the Parity selected If even or odd parity is selected 1 stop bit is used If a Parity of none is selected 2 stop bits are used Select the Stop Bits by clicking on the selection arrow and selecting either 1 or 2 Stop Bits need to be the same as in the Master configuration AUTOMATION COMPONENTS INC 2305 Pleasant View Road Middleton Wisconsin 53562 Page 26 of 38 www workaci com 888 967 5224 Version 0 2 10000676 MOD9200 MODBUS Gateway Programming Softwa
6. 0 Gateway e To send the new configuration file to the MOD9200 Gateway click on File gt File Transfer and a dialog box will appear ES Editor File Settings Row New Gateway File Open Gateway File Save Save As File Transfer Exit B File Transfer File Name TCP IP 192 168 0 1 IP Address TCPAP amp Comm Status Disconnected Connect Disconnect File Status Cancel AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 28 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software e Click on Select File and a window will open Move to the trs config directory and select the appropriate file from the list Trs Suite inv Select File Ax Look in config j c Ez SSensorvull ini ty ST rs Suite ini My Recent Documents B Desktop My Documents My ple t en Why Network Fil Tre Suite in z a le name rS SUE Files of type Config files trs config ini Cancel Click on Open to automatically enter the selected file path as the File Name Enter the current IP Address of the Gateway Note This can be different than the IP Address entered into the configuration file AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 29 of 38 www workaci com 888 967 5224 MOD9200 MODBUS
7. 6 XX File Settings Points Row RegisterEntry Register Bank e To open anew configuration table Click on File gt New Gateway File A blank configuration table will open File Settings Points Row RegisterEntry Register Bank 4 REG FUNCTION REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN DATA FORMAT e The default startup is the Input Register configuration table and System Setup page e By clicking the RegisterBank tab you can go to the Digital Output Coil register configuration table or Analog Output Holding Register configuration table AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 10 of 38 www workaci com 888 967 5224 e Input Register Configuration MOD9200 MODBUS Gateway Programming Software e Fach row of the configuration table is a unique data register having 8 special attributes REG FUNCTION REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN DATA FORMAT LOG AUTOMATION COMPONENTS INC 2305 Pleasant View Road Middleton Wisconsin 53562 www workaci com 888 967 5224 Identifies the function of the register Analog or Digital Discrete Note If selecting the Digital Discrete function be sure to set the appropriate Digital Capture Time Page 15 Assigns the address of the data register 0 to 99 Automatically assigns the address of the error register 400 to 499 1 e data register addres
8. AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 32 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software e Input Output Configuration Map Analog and Digital Inputs Programmer Software Input Register 00 to 99 to MODBUS Input Register 30001 to 30100 Digital Relay Outputs Programmer Software Digital Output Coil Register OO to 49 to MODBUS Coil Register 01 to 50 Analog Outputs Programmer Software Analog Output Holding Register 00 to 49 to MODBUS Holding Register 40001 to 40050 e The Input Registers The MODBUS Input Register 30001 to 30100 are used to receiver all sensor inputs All wireless sensor information analog and discrete input will be displayed as numeric values All digital status alarms will be received and stored by MOD9200 as 1 or 0 1 input contact closed amp O input contact open The Digital Capture Time can be set to hold momentary contact closures long enough to be picked up by the system The Digital Capture Time can be set up to 240 minutes 4 hours in applications where an extended period of time is needed such as unoccupied period by pass All analog data will be received and stored as integer values For data types THERM 20k RTD Ik RTD 1k Ext and HUMIDITY the least significant digit of the integer value is the decimal number 1 e 8000 will mean 800 0 For
9. Each transmitter is factory configured with a unique ID refer to the sensor product data sheet for the location of the transmitter ID AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 13 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software e Assign the appropriate sensor transmission channel to the data register by clicking in the cell to open a drop down menu Click on the appropriate transmission channel 01 to 04 to select NAME TRANSMITTER ID TRANS CHAN TRANS TIMEOUT e The active transmission channels are factory configured as follows Device Analog CH 01 Analog CH 02 Digital CH 01 WT2630A Space Temp Therm 20K WT2630B Space Temp SetPoint Override Discrete Therm 20K Analog See page 15 to set the Digital Capture Time WT2630C Space Temp Override Discrete Therm 20K See page 15 to set the Digital Capture Time WH2630A Humidity WH2630B Space Temp Humidity Therm 20K OA2630A Outdoor Temp Outdoor Therm 20K Humidity OST2630A Outdoor Temp Therm 20K DT2630A Duct Temperature Therm 20K DT2650A Ave Temperature Therm 20K DH2630A Duct Humidity DH2630B Duct Temperature Duct Humidity Therm 20K FT2630A Fluid Temperature Therm 20K RT2630A B C See Device Label for Analog 4 and Digital 4 Configuration RT2620A See Device Label for Digit
10. ODBUS Client Server Model and utilizes the MODBUS messaging services over TCP IP or RS485 RS232 to communicate toa MODBUS Client e For implementation information please refer to the Modbus Standard Library at www modbus org Both the MODBUS Application Protocol Specification and the MODBUS Messaging On TCP IP Implementation Guide are available for download there b MOD9200D MODBUS Transceiver Application Parameters e When interfacing 3 party monitoring software or controllers to the MOD9200 Gateway be sure to set the appropriate MOD9200 Gateway Unit Identifier see page 18 and for TCP IP connect to the MOD9200 Gateway Port 0502 If either the Serial RTU mode or Serial ASCII mode are used connect through the appropriate COM serial port e TCP IP APPLICATION NOTE When using the MOD9200D in TCP IP mode the MODBUS Master polling interval should be set to occur within 2 minutes 59 seconds or less If no polling activity occurs within 3 minutes the MOD9200D will automatically close the network connection and the MODBUS Master will have to close and re open the connection to re establish communications The MODBUS Master should not attempt to re open the network connection for at least 3 1 2 minutes after the network connection has been closed Only 1 TCP IP connection is allowed at a time e The MOD9200 MODBUS Gateway receives data from up to fifty 50 wireless sensors and updates its data registers on a real time basis
11. R LOSS OF BUSINESS LOSS OF PROFITS BUSINESS INTERRUPTION OR LOSS OF BUSINESS INFORMATION ARISING OUT OF THE USE OF OR INABILITY TO USE THE PROGRAM OR FOR ANY CLAIM BY ANY OTHER PARTY EVEN IF ACI HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES ACI S AGGREGATE LIABILITY WITH RESPECT TO ITS OBLIGATIONS UNDER THIS AGREEMENT OR OTHERWISE WITH RESPECT TO THE PRODUCT AND DOCUMENTATION OR OTHERWISE SHALL NOT EXCEED THE AMOUNT OF THE LICENSE FEE PAID BY YOU FOR THE PRODUCT AND DOCUMENTATION BECAUSE SOME STATES COUNTRIES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES THE ABOVE LIMITATION MAY NOT APPLY TO YOU 8 Export Restrictions THIS LICENSE AGREEMENT IS EXPRESSLY MADE SUBJECT TO ANY LAWS REGULATIONS ORDERS OR OTHER RESTRICTIONS ON THE EXPORT FROM THE UNITED STATES OF AMERICA OF THE PRODUCT OR INFORMATION ABOUT SUCH PRODUCT WHICH MAY BE IMPOSED FROM TIME TO TIME BY THE GOVERNMENT OF THE UNITED STATES OF AMERICA YOU SHALL NOT EXPORT THE PRODUCT DOCUMENTATION OR INFORMATION ABOUT THE PRODUCT AND DOCUMENTATION WITHOUT CONSENT OF ACI AND COMPLIANCE WITH SUCH LAWS REGULATIONS ORDERS OR OTHER RESTRICTIONS 9 Termination This License Agreement is effective until it is terminated You may terminate this License Agreement at any time by destroying or returning to ACI all copies of the Product and Documentation in your possession or under your control ACI may terminate this License Agreement for any rea
12. REG ADDRESS GROUP NAME POINT MAME TRANSMITTER ID TRANS CHAN 0 Garage e Enter a POINT NAME if desired for the data point by typing the name in the cell Enter the name in the cell by using the mouse to click on the next column Note DO NOT use commas or semicolons in the Point Name Points Row RegisterEntry Register Bank REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN 0 Garage Exhaust Far e Assign a sensor transmitter to the data register by clicking in the TRANSMITTER ID cell to open a drop down menu This is the device ID of the remote output devices RD2402 amp RD2432 Use the scroll bar to scroll to the correct address or automatically scroll to the address by typing the hexadecimal address in the cell To select the address click on the appropriate ID in the drop down menu REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN 0 Garage Exhaust Fan i AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 17 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software e Assign the appropriate digital or relay output TRANS CHAN to the data register by clicking in the cell to open a drop down menu Click on the appropriate transmission channel 01 to 04 to select File Settings Points Row RegisterEntry Register Bank REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN 0 Garage Exhaust Fan 3456 a i
13. RRANTS THAT THE PRODUCT WILL OPERATE SUBSTANTIALLY IN ACCORDANCE WITH THE THEN CURRENT DOCUMENTATION SHOULD THE PRODUCT NOT SO OPERATE YOUR EXCLUSIVE REMEDY AND ACI S SOLE OBLIGATION UNDER THIS WARRANTY SHALL BE AT ACI S SOLE DISCRETION CORRECTION OF THE DEFECT OR REFUND OF LICENSE FEES PAID BY YOU FOR THE PERIOD DURING WHICH THE DEFECT WAS NOT CORRECTED AND MATERIALLY AFFECTED THE OPERATION OF THE PRODUCT ANY USE BY YOU OF THE PRODUCT IS AT YOUR OWN RISK THIS LIMITED WARRANTY IS THE ONLY WARRANTY PROVIDED BY ACI REGARDING THE PRODUCT EXCEPT FOR THE LIMITED WARRANTY ABOVE THE PRODUCT IS PROVIDED AS IS TO THE MAXIMUM EXTENT PERMITTED BY LAW ACI DISCLAIMS ALL OTHER WARRANTIES OF ANY KIND EITHER EXPRESSED OR IMPLIED INCLUDING WITHOUT LIMITATION IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ACI DOES NOT WARRANT THAT THE FUNCTIONS CONTAINED IN THE PRODUCT WILL MEET ANY REQUIREMENTS OR NEEDS YOU MAY HAVE OR THAT THE PRODUCT WILL OPERATE ERROR FREE OR IN AN UNINTER RUPTED FASHION OR THAT ANY DEFECTS OR ERRORS IN THE PRODUCT WILL BE CORRECTED OR THAT THE PRODUCT IS COMPATIBLE WITH ANY PARTICULAR PLATFORM SOME JURISDICTIONS DO NOT ALLOW THE WAIVER OR EXCLUSION OF IMPLIED WARRANTIES SO THEY MAY NOT APPLY TO YOU 7 Limitation of Liability IN NO EVENT WILL ACI BE LIABLE TO YOU OR ANY THIRD PARTY FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES INCLUDING WITHOUT LIMITATION INDIRECT SPECIAL PUNITIVE OR EXEMPLARY DAMAGES FO
14. TION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 23 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software k Configuring The Gateway For RS485 RS232 RTU ASCIT MODBUS Protocol e When using the MODBUS Serial Line communications protocol the Gateway needs to be assigned a unique Identifier Slave Address to differentiate it from other serial devices on the network To enter the Gateway Unit ID Slave Address into the Configuration File click on the Menu Comm gt Unit Identifier _sunset_lane_bl File Comm Row ANALOG INPUTS e Click on the drop down menu arrow and select the Gateway Unit ID from the drop down menu and click OK The default Unit ID is 1 REG ADDRESS GROUP MAME POINT NAME PS 0 Ath Floor Conf Arn rs 1 Bth Floor Cont Am B PS 2 Bth Floor Conf Am C BR Miel E F OF Cancel Oo J 07 O71 Fs Lo M Bee e Click on Menu Comm gt Serial Transport to activate the Serial Comm Port dialog box my Editor CURRENTLY EDITING INPUT REGISTE Unt kientiher 5 GROUP NAME POINT NAME TRANSMITTER ID v Serial Transport TCP IP Transport Network ID Miscellaneous AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 24 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software e Use the Serial Comm Port co
15. UTS 5 Warehouse East 1 THERM 20k AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 15 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software f Digital Output Coil Register Configuration e Select the Digital Output Coil Register table by clicking the RegisterBank tab Editor Settings Points Row _RegisterEntry Register Bank Input Registers Digital Qutput Coil Registers Analog Output Holding Registers e First we will assign the REG ADDRESS by clicking in the cell Before entering register addresses ensure the RegisterEntry AutoSet is turned off as shown e Enter the Register address in the REG ADDRESS window The valid range is O to 49 File Settings Points Row RegisterEntry Register Bank REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN 0 AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 16 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software e Again use the mouse to move to the next column Enter a GROUP NAME if desired for the data set by typing the group name in the cell Enter the name in the cell by using the mouse to click on the next column Note DO NOT use commas or semicolons in the Group Name File Settings Points Row RegisterEntry Register Bank
16. al 4 Configuration RT2602B Digital 2 Inputs SST2630A Temperature Therm 20K SST5630AE Temperature RTD 1K AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 14 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software e Select the appropriate DATA FORMAT value by clicking in the cell to open a drop down menu ATO 1k Ext ANALOG DIGITAL HUMIDITY MOISTURE e To create a new data register row click on Row gt Append Continue to do this for each row data register that needs to be configured e The completed configuration example for an office building is as follows File Settings Points Row REG FUNCTION REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN DATA FORMAT LOG ANALOG_INPUTS 0 Sth Floor Conf Rm A 38E 1 THERM 20k ENERGY_COOU e The columns may be resized by placing the cursor over one side of the column When the cursor changes to two arrows hold down the left mouse button and drag the side of the column to resize it BB Editor _config ini CU File Settings Points Row RegisterEntry Register Bank REG ADDRESS GROUP NAME TRANSMITTER ID TRANS CHAN DATA FORMAT D First Floor YP Office 1 THERM 20k 1 First Floor YP Office 2 HUMIDITY ANALOG_INPUTS 2 First Floor general Office 1 THERM 20k ANALOG_INPUTS 3 Warehouse North 1 THERM 20k ANSLOG_INPUTS 4 Warehouse West 1 THERM 20k ANALOG_INP
17. ally reset itself and initialize the new configuration file 4 If the Gateway is configured to use the MODBUS Serial transport protocols RTU or ASCII the Gateway needs to be connected to the appropriate serial communication connections AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 37 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software For more information please contact ACI 2305 Pleasant View Rd Middleton WI 53562 Telephone 1 608 831 2585 Wwww workaci com AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 38 of 38 www workaci com 888 967 5224
18. amming Software Il MODBUS Transceiver Installation amp Network Setup a Transceiver Installation e Choose a location close to the computer network hub or RS485 loop e Mount the gateway on the wall using four 8 screws e 24 VAC Input Connect 24VAC 60 Hz and earth ground to the input terminals using 18 AWG wire as shown in the product data sheet e TCP IP If using TCP IP use RJ45 Category 5 Ethernet cable to connect the Gateway J2 to the network hub or computer See Figure 1 e RS232 If using RS232 RTU ASCI use the MOD9200 RS232 cable sold separately to connect the Gateway J1 to the serial port on the computer See Figure 1 TCP IP Connection J2 Connection J2 HLU Default IP Jumper SPI NER zat RS485 Terminals 24 VAC Input Figure 1 e RS485 If using RS485 RTU ASCII use 18 gauge shielded twisted pair wire to connect the Gateway Terminals A amp B to the MODBUS master When running the RS485 loop into a breaker panel use wire with appropriate insulation for the voltage present See Figure 1 AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 5 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software e Multiple RS485 Devices If more than one RS485 device is used the devices should be daisy chained or straight line connected by connecting all the A wires to the A terminals a
19. cell to automatically scroll to the appropriate value To select the timeout interval click on the appropriate value in the drop down menu e Digital Scaling On check box Should be UNCHECKED Check only when configuring the MOD9200BNT BACnet receiver or the MOD9200LON LonWorks Receiver AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 22 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software e Units Select the appropriate default temperature scale F C e Register Value When Sensor Lost The user has the options to select whether the sensor value should remain unchanged or set to 19999 when the communication link is lost with the sensor after the transmitter timeout period j Configuring The Gateway For TCP IP MODBUS e Click on the menu Comm gt TCP IP to select the TCP IP configuration menu EE Editor CURRENTLY EDITING INPUT REGISTERS ac File Points Row RegisterEntry Register Bank Unit Identifier GROUP NAME POINT NAME TRANSMITTERID TRANS CHAN DATA FORMAT LOG y Serial Transport TCP IP Transport Network ID al Miscellaneous e Type in the appropriate IP address and click OK The TCP IP transport protocol is automatically setup fi 92 16801 IP Address 255 255 255 0 Subnet Router Setup Webserver Only fi 97 1680 254 Router IP Address Forwarded Port OF Cancel AUTOMA
20. ddleton Wisconsin 53562 Page 2 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software Table of Contents L FNEPOUUCIION sxccotscstrtie en ENR 4 a MOD9200 Gateway System ssesesececssesesecesessoseseseossosesesescoseseseoo 4 IL MODBUS Transceiver Installation amp Network Setup sssssesscssees 5 a Transceiver Installation ssi isss da0scideacindensweacestegansrsaseiiwtennivastnieessne 5 D INCU WOEK SCD oee EEE 6 c Setting A New IP Address o cvsdossssononssdesssesvaven dunscaneouswvenerseeracseeuseess 6 d Manually Resetting The Factory Default IP Address cccceees 8 Ui Configuration SoftWare wvisccccstavicderesarescsverestnwncenbesdadaadsedeeseeteensembensvies 9 a Configuration Software Description sssesecessesesecesseseseseesesesessoeoe 9 Ds System Reguiremenis s cq50cesncrescweesecucessieesseeseesscuesseeuenesseeeseeenneusces 9 c Configuration Software Installation essesesecessesesecosccsesesecoesseseoeoe 9 d Creating A MODBUS Configuration File ccccccccsssccccccccccecces 10 e Input Register Configuration esessesessesecoesoesesoessesoesesoesoesesoeseoo 11 f Digital Output Coil Register Configuration sesessesecseseesecssesesssoee 16 g Analog Output Holding Register Configuration cccccssssseeees 18 h Setting the Mesh Network ID for the repeater router devices 21 i IVMISCENANEOUS Menu sxcc
21. fig File and select the _config ini file Click on Open to open the file in the Editor Confirm that the file is the same as the original configuration file File Settings Points Row REG FUNCTION REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN DATA FORMAT LOG ANALOG_INPUTS 0 3rd Floor Sensors Temp 33BC 33BC 1 THERM 20k ENERGY_COOL ANALOG_INPUTS 1 3rd Floor Sensors RH 33BC 33BC 2 HUMIDITY HUMIDITY ANALOG_INPUTS 2 3rd Floor Sensors Temp 33BD 33BD 1 THERM 20k ENERGY_COOL ANALOG_INPUTS 3 3rd Floor Sensors AH 338D 33BD 2 HUMIDITY HUMIDITY ANALOG_INPUTS 4 3rd Floor Sensors Temp 33BE 33BE 1 THERM 20k ENERGY_COOL ANALOG_INPUTS 5 3rd Floor Sensors RH 33BE 33BE 2 HUMIDITY HUMIDITY ANASLOG_INPUTS 6 3rd Floor Sensors Temp 33BF 33BF 1 THERM 20k ENERGY_COOL e NOTE The _config ini file is a dynamic file If multiple MOD9200 Gateways are being administered from the same PC the _config ini file will be a copy of the configuration file from the last Gateway administered AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 31 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software IV Data Acquisition a MODBUS Standard e MODBUS is an application layer messaging protocol for client server communication between devices connected on different types of buses or networks e The MOD9200 functions asa MODBUS Server in the M
22. g File turn off the power to the Gateway and move the jumper back to Norm Turn the power back on and the Config File will become active The Gateway will have the IP Address that was set in the Config File e TCP IP APPLICATION NOTE When using the MOD9200D in TCP IP mode the MODBUS Master polling interval should be set to occur within 2 minutes 59 seconds or less If no polling activity occurs within 3 minutes the MOD9200D will automatically close the network connection and the MODBUS Master will have to close and re open the connection to re establish communications The MODBUS Master should not attempt to re open the network connection for at least 3 1 2 minutes after the network connection has been closed Only 1 TCP IP connection is allowed at a time AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 8 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software III Configuration Software a Configuration Software Description e The MODBUS data registers of the Gateway need to be configured prior to use The configuration program SETUP exe can be found on the disk or CD ROM on the back cover of this manual will configure the data register as follows Assign the Input Register function Analog or Discrete Assign wireless Digital Output Coil Register function Assign wireless Analog Output Holding Register f
23. gister 40101 to 40150 will be automatically assigned by the MOD9200BNT These 50 registers objects will display the status of the analog output commanded via the previous Register 40001 thru 40050 After the remote unit executed the command issued by the MOD9200 it will send a feedback status of the analog output value to the MOD9200 e The Alarm Registers The MODBUS Register 30401 to 30500 are the alarm registers for all the input and output data points Input Register 30001 to 30100 Coil Register 101 to 150 and Holding Register 40101 to 40150 Each point utilizes 6 binary bits of information representing the alarm conditions of the Input Register Digital Output Coil Register and Analog Output Holding Register AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 34 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software Holding Register Input register Bit 5 amp 6 Bit 1 amp 2 aan 000000 Coil Register Bit 3 amp 4 The Present Value of each register displays a decimal value representing the alarm status of all 3 point types Each point type returns an individual alarm value in decimal format All 3 point types decimal values are added together to represent the status of the 3 alarm status The decimal values of different point types are The Input Register alarms Normal Low Battery Ala
24. isconsin 53562 Page 20 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software e The active transmission channels or output number are factory set as follows Device Digital Analog RD2402 1 to 2 for relay 1 NA Wireless relay and relay 2 output module RD2432 1 to 4 for relay 1 1 to 4 for analog Wireless digital amp to relay 4 output to 4 analog output module h Setting the Mesh Network ID for the repeater router devices Unit Identifier POINT NAME TRANSMITTER ID TRANS CHAN J seater dL Sec TCP IP Transport Network ID e The mesh network ID of the MOD9200 Gateway can be set to specific network from to 64 The MOD9200 functions as a network coordinator Any repeater router that has the same network ID will be able to communicate and channel sensor information to the MOD9200 i Miscellaneous Menu e The transmitter timeout interval default temperature degrees C F and Digital Input Capture Time are set globally for all sensors using the Miscellaneous Dialog Screen e Click on Settings gt Miscellaneous Unit Identifier _ POINT NAME TRANSMITTER ID TRANS CHAN _ Serial Transport SHES TCP IP Transport Network ID Miscellaneous AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 21 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Prog
25. led with the next sequential number from 0 to 99 B Editor File Settings Points Row Editor Fil Settings Points Row REG FUNCTION ANALOG INPUTS e Again use the mouse to move to the next column Enter a GROUP NAME for the data set by typing the group name in the cell Enter the name in the cell by using the mouse to click on the next column Note DO NOT use delimiters lt gt in the Group Name i MODBUS Configuration Tool File Comm Row REG FUNCTION REG ADDRESS ANALOG INPUT GROUP HAME POINT g Sth Floor AUTOMATION COMPONENTS INC 2305 Pleasant View Road Middleton Wisconsin 53562 Page 12 of 38 www workaci com 888 967 5224 Version 0 2 10000676 MOD9200 MODBUS Gateway Programming Software e Enter a POINT NAME for the data point by typing the name in the cell Enter the name in the cell by using the mouse to click on the next column Note DO NOT use delimiters in the Point Name w MODBUS Configuration Tool File Comm How REG FUNCTION REG ADDRESS GROUP NAME POINT NAME TRE ANALOG _INPUT Sth Floor Cont Air e Assign a sensor transmitter to the data register by clicking in the TRANSMITTER ID cell to open a drop down menu Use the scroll bar to scroll to the correct address or automatically scroll to the address by typing the hexadecimal address in the cell To select the address click on the appropriate ID in the drop down menu
26. ment remains in full force and effect Ownership of the Product Documentation and all intellectual property rights therein shall remain at all times with ACI Any use of the Product by any other person business corporation government organization or any other entity is strictly forbidden and is a violation of this License Agreement You may not make more copies of the Product than specified in this agreement or allowed by applicable law despite this limitation publish the Product for others to copy or rent lease or lend the Product 4 Copyright The Product and Documentation contain material that is protected by United States Copyright Law as well as other intellectual property law and international treaty provisions All rights not granted to you herein are expressly reserved by ACI You may not remove any proprietary notice of ACI from any copy of the Product or Documentation 5 Restrictions You may not publish display disclose rent lease modify loan distribute or create derivative works based on the Product or any part thereof You may not reverse engineer decompile translate adapt or disassemble the Product nor shall you attempt to create the source code from the object code for the Product You may not transmit the Product over any network or between any devices although you may use the Product to make such transmissions of other materials You may access the Product from only one computer at a time 6 Limited Warranty ACI WA
27. n 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 6 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software e Click on Settings gt TCP IP Transport Unit Identifier nail GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN DATA FORMAT LOG Serial Transport TCP IP Transport Miscellaneous e Enter the new IP Address and Subnet Mask and click OK The new IP Address will take affect when the Config File is downloaded to the Gateway f 932 168 0 1 IP Address 255 255 255 0 Subnet Router Setup Webserver Only fi 92 168 0 254 Router IP Address Forwarded Port OF Cancel e Router Setup Webserver Do not Use AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 7 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software d Manually Resetting The Factory Default IP Address e The Gateway can manually be reset to the default IP Address by moving the jumper J6 from Norm to Init e Turn off the power to the Gateway and move the jumper from Norm to Init Turn on power and the Gateway can be communicated with using the Factory Default IP Address 192 168 0 1 Subnet Mask 255 255 255 0 The Config File is no longer active while the jumper is in the Init position A new Config File can be downloaded to the Gateway if desired e To reactivate the Confi
28. nd the B wires to the B terminals Do not use spur lines or a star configuration e RS485 Terminating Resistor If the MOD9200 is at the end of a RS485 loop a terminating resistor should be installed to match the electrical impedance characteristic of the twisted pair loop and prevent signal echoes from corrupting the data b Network Setup e Note Even if you are planning to use the RS485 RTU ASCIH MODBUS protocol option a network connection or crossover cable is required during the initial setup of the gateway for transporting the Gateway Configuration File via FTP e Connect the MOD9200 Gateway to a 10 100Base T Ethernet network or use a crossover cable to connect directly to the PC Note Only 1 TCP IP connection is allowed at a time either a MODBUS Polling Master or the Programmer Configuration Tool DO NOT try to use both at the same time e Apply 24 VAC 60 Hz power to the MOD9200 Gateway c Setting A New IP Address e The MOD9200 is shipped from the factory with an IP address of 192 168 0 1 and a subnet mask of 255 255 255 0 Note To initially connect to the Gateway the networked PC must have a static IP address in the form of 192 168 0 X where X is gt 1 with a subnet mask of 255 255 255 0 e The IP Address is changed by changing the IP Address in the Gateway Config File Open either an existing config file or a new config file using the Programmer Software AUTOMATION COMPONENTS INC Versio
29. nfiguration dialog box to select the appropriate internal communication parameters Connect Speed Connect Preferences and Transport Mode for the Transceiver Ss Serial Comm Port Properties Maximum Speed 38400 vl Modbus Transport Connection Preferences RTU Data Bits g Parity NONE Stop Bits 11 7 i ance e There are two different serial transmission modes defined in MODBUS the RTU mode and the ASCII mode They define the bit contents of the message fields transmitted serially on the line and determine how information is packed into the message fields and decoded e The MOD9200 transmission mode and serial port parameters need to be exactly the same as those configured for the Master e Select the Maximum Speed In the Serial Comm Port configuration window click on the drop down selection arrow and select the Maximum Speed for communication speeds range from 9600 bps to 38400 bps e Communications speed needs to be the same as in the Master configuration Serial Comm Port Properties Maximum Speed Modbus Transport Connection A t ATU f ASCII Data Bits Parity Stop Bits 1 ae ance e Select the number of Data Bits click on the selection arrow and select either 7 or 8 bits The RTU transport mode requires 8 bits Standard ASCII transport mode requires 7 bits and Extended ASCII requires 8 bits AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant
30. olumn Note DO NOT use commas or semicolons in the Group Name REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN 0 Office West AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 19 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software e Enter a POINT NAME if desired for the data point by typing the name in the cell Enter the name in the cell by using the mouse to click on the next column Note DO NOT use commas or semicolons in the Point Name File Settings Points Row RegisterEntry Register Bank REG ADDRESS GROUP HAME POINT HAME TRANSMITTER ID TRANS CHAN 0 Office West SunShade e Assign a sensor transmitter to the data register by clicking in the TRANSMITTER ID cell to open a drop down menu This is the device ID of the remote output devices RD2432 Use the scroll bar to scroll to the correct address or automatically scroll to the address by typing the hexadecimal address in the cell To select the address click on the appropriate ID in the drop down menu REG ADDRESS GROUP NAME POINT HAME TRANS CHAK O Office Wrest Sunshade e Assign the appropriate digital or relay output TRANS CHAN to the data register by clicking in the cell to open a drop down menu Click on the appropriate transmission channel 01 to 04 to select AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton W
31. ramming Software e Set the transmitter transmission timeout interval requires a minimum of 30 min by clicking in the Transmitter Timeout cell to open a drop down menu Use the scroll bar to scroll down to the appropriate value 1 to 60 min or type the value in the cell to automatically scroll to the appropriate value This will be used to generate an error message if the transmitter fails to transmit in the specified time interval Transmitter Timeout min Digital Capture Time 240 Seconds C Minutes Digital Scaling Units v Digital Scaling On Degrees F Degrees C Register Value When Sensor Lost C Retain Last Value o K Set to 19999 e To select the timeout interval click on the appropriate value in the drop down menu e The Digital Input Capture Time can be set to hold a momentary contact closure such as the override button on the WT2630B C for a period of time Default is O min amp recommended value is 1 min so the controller has time to recognize the contact closure e The Digital Capture Time can be set up to 240 minutes 4 hours in applications where an extended period of time is needed such as unoccupied period by pass e Set the Digital Capture Time interval seconds or minutes by clicking on Seconds or Minutes Click in the Digital Capture Time cell to open a drop down menu Use the scroll bar to scroll down to the appropriate value 0 to 240 or type the value in the
32. re Serial Comm Port Properties Maximum Speed 3600 Modbus Transport i Connection Preferences ATU Data Bits lg Parity Even Stop Bits i r z ance t ASCII e Select the appropriate Modbus Transport Mode RTU or ASCII and click OK to save the serial communication parameters to the Configuration File The transport mode selected needs to be the same as in the Master configuration e To Save the configuration file click on File gt Save Itis recommended that the configuration ini file be saved in the trs config folder already setup 1 e C trs config Save Register Configuration Save in SensorVulL ini 78s Suite ini My Recent Documents Desktop My Documents gf My Computer e File name Sunset Lane ini rg My Network Save as type cotrs contig ini Cancel Places AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 27 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software l Sending The Configuration File To The MOD9200 e Note Even if you are planning to use the RS485 RTU ASCIT MODBUS protocol option a network connection or crossover cable is required during the initial setup of the gateway for transporting the Gateway Configuration File via FTP e Always Save the configuration file to the folder trs config before sending it to the MOD920
33. rm Bit 1 set a 2 Lost Communication Alarm Bit 2 set The Digital Output Coil Register alarms 0 Normal 8 Lost Communication Alarm Bit 4 set The Analog Output Holding Register alarms 0 Normal 32 Lost Communication Alarm Bit 6 set Alarm Status Examples Example 1 Input Register 30108 returns a value of 33 representing Input Register 30008 Low Battery Alarm Coil Register 08 Normal amp Holding Register 40008 Lost Communication Example 2 Input Register 30108 returns a value of 40 representing Input Register 30008 Normal Coil Register 08 Lost Communication amp Holding Register 40008 Lost Communication Example 3 Input Register 30128 returns a value of 42 representing Input Register 30028 Lost Communication Coil Register 28 Lost Communication amp Holding Register 40028 Lost Communication AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 35 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software Example 4 Input Register 30128 returns a value of 9 representing Input Register 30028 Low Battery Alarm Coil Register 28 Lost Communication amp Holding Register 40028 Normal AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 36 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gate
34. s 400 Assigns a group name to the data register Multiple data registers can have the same group name This is useful for monitoring and data logging programs Assigns a unique name to the data register to help identify the location of the sensor transmitter Multiple point names can have the same group name Assigns a wireless sensor transmitter address to the data register Each wireless sensor is factory configured with a unique hexadecimal address Assigns a wireless sensor transmitter data channel to the data register A wireless sensor transmitter may have up to four 4 analog channels and 4 digital status alarm channels Assigns the data type to the register temperature RTD or Thermistor 20K analog voltage totalizer or humidity This register is left blank if the REG FUNCTION is Digital Discrete Obsolete Function Version 0 2 10000676 Page 11 of 38 MOD9200 MODBUS Gateway Programming Software e First we will assign the REG FUNCTION by clicking in the REG FUNCTION cell to open a drop down menu Select the appropriate function File Settings Points Row RegisterEntry Register Bank REG FUNCTION REG ADDRESS GROUP NAME POINT NAME TRANSMITTER ID TRANS CHAN DATA FORMAT ANALOG_INPUTS ma 6 SENSOR_CNTRL 7 SENSOR _CNTRL e Use the mouse to move to the next column to assign the REG ADDRESS by clicking in the cell When the RegisterEntry AutoSet is turned on REG ADDRESS is automatically fil
35. son including but not limited to if ACI finds that you have violated any of the terms of this License Agreement Upon notification of termination you agree to destroy or return to ACI all copies of the Product and Documentation and to certify in writing that all known copies including backup copies have been destroyed All provisions relating to confidentiality proprietary rights and non disclosure shall survive the termination of this Product License Agreement Additionally it is understood that termination of this Agreement will not affect a refund of any license fees paid or owed to ACI 10 General This License Agreement shall be construed interpreted and governed by the laws of the State of Wisconsin without regard to conflicts of law provisions thereof The exclusive forum for any disputes arising out of or relating to this License Agreement shall be an appropriate federal or state court sitting in the State of Wisconsin USA This License Agreement shall constitute the entire Agreement between the parties hereto Any waiver or modification of this License Agreement shall only be effective if it is in writing and signed by both parties hereto If any part of this License Agreement is found invalid or unenforceable by a court of competent jurisdiction the remainder of this License Agreement shall be interpreted so as to reasonably effect the intention of the parties AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Mi
36. the data type ANALOG there is no decimal and data is displayed in counts 0 to 4095 For example the setpoint pot of the WT2630B is setup as an ANALOG data type with ranges from 0 Cool to 4095 Warm For the data type TOTALIZER there is no decimal and data is displayed in counts 24 bits When the count reaches 16 777 215 24 bits the count value rolls over to O and begins again AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 33 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software e The Digital Output Coil Registers The MODBUS Coil Register 01 to 50 are used for command remote wireless digital outputs relays module 1 e RD2402D amp the RD2432D devices Values to be entered or sent is l1 on and O off The MODBUS Coil Register 101 to 150 will be automatically assigned by the MOD9200 These 50 registers will display the status of the relays commanded via the previous Register 01 thru 50 After the remote unit executed the command issued by the MOD9200 It will send a feedback status of the relays to the MOD9200 e The Analog Output Holding Registers The MODBUS Holding Register 40001 to 40050 are used to command remote wireless analog outputs O 10VDC or 0 5 VDC module such as the RD2432D devices Value to be entered or sent is from 0 to 4095 counts representing the full output range The MODBUS Holding Re
37. ucecevisnvensdsceeeecucort nese s Traio CEE a EEES 21 j Configuring The Gateway For TCP IP MODBUS cccccccceseeees 23 k Configuring The Gateway For RS485 RS232 RTU ASCII MODBUS 24 l Sending The Configuration File To The MOD9200 ceescssreees 28 m Activating The Configuration File ccccccccccsscccccccccccsscccccscccess 30 A MAA VCO UISILION E onset secawsncssee eskauss estou rsaawenesseesce 32 a MODBUS sland ard aces icsenscandassacesecadnessaiinteasuasnnbecececnaeisvsccantanns 32 b MOD9200D MODBUS Transceiver Application Parameters 32 The Input ROCIS CES co scncdrscces ca waceeos usri tridos r nT arian E E 33 e The Digital Output Coil Registers esesessssesesessesesesesseseseseoee 34 e The Analog Output Holding Registers cccsscccccccccccccceecs 34 e PRG Alar RCC S Oy oreista nean E ence saevoucsesessust cneneavasacvouseen 34 Ve Quick Setup Instructions s cec cccecratneotesavienauer tes iea a 37 a Installing The MOD9200 MODBUS Gateway ccccccccccccccccees 37 b Installing The MOD9200 Configuration Software cccccccccscceeees 37 AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 0000676 Middleton Wisconsin 53562 Page 3 of 38 www workaci com 888 967 5224 I Introduction MOD9200 MODBUS Gateway MOD9200 MODBUS Gateway Programming Software The MOD9200 MODBUS network receiver utilizes reliable Spread
38. unction Assign the register address Assign the Wireless Sensor ID and transmission channel Assign the data type e The MOD9200 Transceiver can have up to 100 addresses O to 99 data registers configured to be either Analog or Discrete 50 digital outputs and 50 analog outputs e Error registers are directly mapped to the data registers 400 addresses 400 to 499 For example errors for data register 55 will be in error register 455 b System Requirements e PC Notebook or desktop with Windows 98 XP Vista or Windows 7 e Ethernet connection e 10 MB of hard drive memory available c Configuration Software Installation e If other applications are running close them before inserting the ConfigTool CD into the CD ROM Drive The Programmer setup program should automatically start running Follow the on screen instructions to complete the installation e If the Programmer setup program does not start automatically click on Start gt Run gt Browse and click on the Programmer CD ROM Double click on setup exe Follow the on screen instructions to complete the installation AUTOMATION COMPONENTS INC Version 0 2 2305 Pleasant View Road 10000676 Middleton Wisconsin 53562 Page 9 of 38 www workaci com 888 967 5224 MOD9200 MODBUS Gateway Programming Software d Creating A MODBUS Configuration File e To create anew MOD9200 configuration file open the Programmer by clicking on Start gt Programs gt Trs Programmer
39. way Programming Software V Quick Setup Instructions a Installing The MOD9200 MODBUS Gateway 1 Locate the Gateway close to a computer 10 100 Base T network hub or RS485 RS232 connection 2 Connect the Gateway to the TCP IP network using RJ45 Category 5 Ethernet cable or a crossover cable see Fig page 4 3 Apply 24 VAC 60 Hz power to the input terminals of the Gateway The Gateway current draw is less than 0 1 Amp 4 The Gateway is shipped with an IP address of 192 168 0 1 and a subnet mask of 255 255 255 0 see page 8 for instructions on changing the IP address Note To initially connect to the Gateway the networked PC must have a static IP address with a subnet mask of 255 255 255 0 5 The Gateway is ready to be configured b Installing The MOD9200 Configuration Software 1 Insert the Programmer 6 00 X disk or CD into the CD ROM Drive the setup program should start automatically If the setup program does not start automatically click on Start gt Run gt Browse and select the CD ROM Drive with the ConfigTool disk Double click on setup exe Follow the on screen instructions to complete the installation 2 To open the program click on Start gt Programs gt ConfigTool To create a new configuration file see the instructions To send an existing configuration file to the MOD9200 Gateway see the instructions on previous pages 3 After sending a configuration file the Gateway will automatic