27006-QS001D-EN-P, InView Marquee Message Display Quick Start
Contents
1. M DHLPBootP Enable IP Address Subnet Mask Gateway Address Timeouts Connection Timeout 15000 ms Reply Timeout 15000 ms Inactivity Timeout 10 minutes lt Back Next gt Cancel 9 Enter the IP Address for your communication module and the required Subnet Mask and click Next TIP The node address of the controller and the IP address of the message display must be unique in the fourth entry for example 192 168 1 100 and 192 168 1 120 Leave the Gateway Address blank unless required for your application 10 In Tag Setup configure your tags as required by your application then click Next Tag Setup EtherNet IP Message Trigger Address N70 Variable Trigger Address Message Data Address N71 Variable Data Address N10 1 Message Array Se Rytes 16 Vanahle Array Size Rytest 16 lt Back Next gt Cancel Publication 2706 QS001D EN P January 2009 InView Marquee Message Display 15 11 In the dialog box that follows save your project then download it to the module InVview Metwork Communications Save to File Download to Module TIP The InView Message software CD contains demo applications for configuring the Tag Setup for various controller types and communication modules These can be found at Rockwell Automation InView Version 2 Demos Advanced SLC500 Rockwell Automation InView Version 2 Demos Advanced InView Download the File Serially If you want to download the file
2. By default when doing a download or cycling power the InView Message Display will always show the background message Any other messages that were also downloaded are stored in memory until that message number is triggered Download Individual Messages You can download and view a specific message in the file by right clicking the message and choosing Trigger Message InView Marquee Message Display 9 Follow these steps to download individual messages 1 Select your Message File i A 1 we ir Massaging Software tast VP l lax Fie Edil View Dipl escape Fie Meses Took Help ANAS mala Displays Message Files Gay Me Project ES Divs By Marne By lype By File Fea 2 Right click the message you want to trigger and choose Trigger Message 3 Select the display you want to download to and click Download Once it completes the download your InView Message Display now displays the message you just triggered select Displays for Download Message File Hame Messagehe Desciphor Select All Displays Clear All Displays Displays of ype 2706 PR Desaipliuri Drover tad Consis Ino COMI 9500 None 8 1 Add Publication 2706 QS001D EN P January 2009 10 InView Marquee Message Display Configure an EtherNet IP reas these steps to configure an EtherNet IP communication Communication Module What You Need This list indicates what you need to complete this task
3. Message File Details Edit Display Category Priority Pause Rename Display Low 2 Delete Display Low 2 Duplicate Display Associate Display Download Display By Name By File Ready 2 In the Edit Display dialog box click the Communication tab and choose Ethernet TCP IP as your Download Protocol 3 In the TCP IP settings click Configure Communications Edit Display Identification Communications Message File Setial eddies 1 Heailbeal Disabled r Download Protocot C Serial Ethemet TCPAP C Industrial Network Comms TCP IP settings Advanced Configure Communications Senal port settings COM port COM1 y Baud rate 9600 y Parity None y Stop bits 1 v Industrial Hotworks Communications Protocol None Advanced Configure Communications e InView Marquee Message Display 21 4 In the Ethernet TCP IP Communications dialog box type the IP Address of the 2706 PENET1 module the MAC Address of the communication module and the Subnet Mask Ethernet TCP IP Communications IP Address ex 192 168 0 100 0 0 0 0 Port 3001 Assign IP Address MAC Address ex 00 80 a3 61 63 dd 00 80 Setup Advanced Settings Galerray Addiess ex 192 168 0 1 Subnet Mask ex 255 255 255 0 255 255 255 0 Setup 5 Click Setup to make the changes in the communication module and click OK to finish IMPORTANT
4. There are two Setup buttons You need to set the IP and MAC as Stated in step 4 Click the first Setup button and then restart the 2706 PENET1 module After it cycles power click the next Setup button TIP Leave the Gateway Address blank unless required for your application Ready to Assign IP Address Ready to assign the new P Address Please luin the sign on now of di aliesdy on luin the power all hen on Success TIP Your computer needs to be on the same subnet as the communication module to set the communication Publication 2706 QS001D EN P January 2009 22 InView Marquee Message Display Troubleshooting Additional Resources Publication 2706 QS001D EN P January 2009 This table shows possible errors and the suggested solutions Error COM1 unresponsive The Download File dialog box opens Solution Make sure that RSLinx software is not active on COM1 Check to see If the communication module has power Make sure that you are using the correct COM port TIP For more troubleshooting information refer to InView Communication Module User Manual publication 2706 UM017 These documents contain additional information concerning related Rockwell Automation products Resource InView Marquee Message Display User Manual publication 2706 UMO16 InView Installation Instructions publication 2706 INO06 Communication Module Installation Instructions publication 2706 IN015 InView Commu
5. by using the serial port in the Download File dialog box accept the default Transfer Type and click OK Download File Application Name Inle Network Communications Cancel DF Point to Point Internal COM bil Setup H elp Transfer Type The Application Download dialog box opens This dialog box shows your download progress If there are any errors they will be displayed here Refer to the troubleshooting guide at the end of this document for a list of possible causes of errors Once the download is complete the module will restart The EtherNet Communication Module can now be connected to the message display and is ready to communicate with the message display and the controller Publication 2706 QS001D EN P January 2009 16 InView Marquee Message Display Download the File by Using Your EtherNet Driver TIP Verify that RSLinx software is enabled when downloading to the communication module Follow these steps to download a file by using an EtherNet driver 1 On the Download File dialog box from the Transfer Type pull down menu choose RSLinx Network and click Setup The RSLinx configuration dialog box opens Download File Applicabur Nane Irivievy Nelyeurk Cunuiurmcdtiur es Bee Transfer Type RSLinx Network Setup Help EEEE DF1 Point to Point Intemal COM2 RSLinx Network 1 Remote 1 0 Pass Through Memory Card F Autobrowse a Not Browsing El Workstation USMKEW
6. e Catalog numbers 2706 P22R 2706 P4x 2706 P7x 2706 P9x e Catalog numbers 2706 PENETP 2706 PENETM 2706 PENETK InView Ethernet modules TIP Use a 2706 PENETP module for a 2706 P22R display a 2706 PENETM module for a 2 06 P4x display and a 2706 PENETK module for a 2706 P7x or 2706 P9x display e Ethernet cable user supplied e RS 232 serial cable supplied with Ethernet module e RSLinx software e InView User Manual publication 2706 UMO16 e InView Installation Instructions publication 2706 IN006 e Communication Module Installation Instructions publication 2706 INO15 e Communication Module User Manual publication 2706 UMO17 Equipment Setup Follow these instructions to configure the communication module for a 2706 P22R display e Connect a Class 2 24V DC power supply e Connect the RS 232 catalog number 2711 NC13 cable to a personal computer Network Communication 0 2711 NC13 Cable PY supplied Power Publication 2706 QS001D EN P January 2009 InView Marquee Message Display 11 Follow these instructions to setup the communication module for a 2706 P4x 2706 P7x or 2706 P9x display e Connect the power cord e Disconnect the DB9 connector inside the communication module e Connect your RS 232 catalog number 2711 NC13 o
7. 06 IN006 e Communication Module Installation Instructions publication 2706 INO15 e Communication Module User Manual publication 2706 UMO17 Publication 2706 QS001D EN P January 2009 InView Marquee Message Display 19 TIP TCP IP is not available for catalog number 2706 P22R An external 2706 PENET1 module is not required for catalog number 2706 P9x Record the MAC address in catalog number 2706 PENET1 before installing a display or communication module The MAC address can be found on the label near the 2706 PENET1 module Equipment Setup Follow these instructions to connect the 2706 PENET1 communication module for downloading e Connect the power to the unit and RS 232 cable as shown TIP Verify RSLinx software is not using the serial port e Connect the Ethernet cable to the communication module Publication 2706 QS001D EN P January 2009 20 nView Marquee Message Display Publication 2706 QS001D EN P January 2009 Configure Communication Follow these steps to configure communication From an existing project start at the main page of the InView Messaging software 1 Right click the display you wish to modify and choose Edit Display vw InView Messaging Software New Project IVP File Edit View Display Message File Message Tools Help Message Files New Project Message File Display Type Partition Size g Display MessageFile 2706 P22R ES Display 1 Messagef ile 2706 7220 oum i Cut
8. 640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 2706 QS001D EN P January 2009 PN 38176 Supersedes Publication 2706 0S001C EN P August 2003 Copyright 2009 Rockwell Automation Inc All rights reserved Printed in the U S A
9. IJHENDRIOZ Network Name Ge LINX Gateways Ethernet 5 Linx Gatewa 2 In the Configure Drivers dialog box from the Available Driver Type pull down menu choose Ethernet devices and click Add New Another dialog box opens prompting you to give the new driver a name 3 Name the driver and click OK Another dialog box opens 4 Enter the address of your communication module your computer EtherNet card and click Apply then OK The default IP address of the communication module is 192 168 1 1 Publication 2706 QS001D EN P January 2009 InView Marquee Message Display 17 These two nodes now appear on RSLinx software Configure driver New_Driver Host Name 192 168 1 100 192 168 1 120 5 Minimize RSLinx software and go back to the InView Messaging software 6 Select the Node that corresponds to your communication module and click OK Download File gt Apphoalon Name Inview Network Cornmunications r Iranta Type RSI ro Network Setup Select Destinator R Autobrowse fresi EAE Browsing node 192 168 1 30 found E Workstation USMKESISCHNELZ Online Name He Linx Gateways Ethernet EEE 192 163 1 122 InView EtherMet IP 2706 PENETX gt Le AB_DFI 1 OH 465 Es AB_ETH 1 Ethernet i 192 160 1 122 Inview E 192 166 1 30 Compute s AB_KT 1 Data Highway Plus The Application Download dialog box opens This dialog box shows your download progress If th
10. Pub 0100225 02 A Quick Start InView Marquee Message Display Catalog Number 2706 00000000000000000 10000000000000000000000000000000000 00000000 QQ OR aaa 900000000000 00000000 00000000000 CNEA IAA N awa J00000000000 VOOOOOOOODOC OC O0OO0OOOOOOO 0OO0O0O0OOOODODO JOOOO IO O OOQOO0O00C 0000000 JOOOOOO0O o DOOC gt C YC NOL OOOOO ION MA ANA ANY DOOC JENS yA yt dd gt 26 0O0O0OD OOOOOODOODOO 90000000000 OOOOO0OOOOOO OO C 00000084 000000000 OA ONS YC Ax SS m y c CC VU z N dj Y O 00000000000000 r DUDA UY WU WU 0990900900 A A A A L GM MY NA N oy ond N TYY PJ DIY Y Shan A OA A OLU N OO O Sa O a O N y Ta N a a ENEN AEN Y JO N i y ODO O DVD ESOO JJOO AAA O gt SN NV ORO DO N A J JY JY OOO OOS JO N an da YOOOO CG sin SPECTRUM O N T R O L S About This Publication Configure the InView Display for Serial Download Quick Start InView Marquee Message Display Catalog Number 2706 Topic Page About This Publication 1 Configure the InView Display for Serial 1 Download Configure an EtherNet IP Communication 10 Module Configure a TCP IP Communication Module 18 Troubleshooting 22 Additional Resources 22 This publication provides steps for configuring an InView display to display messages Follow these
11. e display 1 On the main screen from the Message File menu choose Download Message File Eee Message Filo Details Categay Poly Pause Header Mekap Low a Rockwell Automation Low z Her Hira A dialog box appears that shows all of the displays in the project that are of the same type as the display you selected You can download to multiple displays at the same time by selecting the displays that you want to download in this dialog box You need to use the RS485 protocol to download to multiple displays 2 After you have selected the displays that you want to download to click Download Select Displays for Download Message hle Hams Hessayelde Description Select All Displays Clear Al Displays Displays of type U6 PZ2R Description Download Comms Into 2041 3800 Mone 8 1 Addr A new dialog box opens showing the download progress If there is a communication error it is displayed here During download the progress is indicated in the status field Publication 2706 QS001D EN P January 2009 8 InView Marquee Message Display Publication 2706 QS001D EN P January 2009 Refer to Troubleshooting on page 22 for a list of possible causes of errors Message File MessageFile Display Name Curirreclur Sulal Aldiess Display Senal 3 Once the download completes click Exit Verify that your InView Display shows the default background message of Rockwell Automation
12. ere are any errors they are displayed here Refer to Troubleshooting on page 22 for a list of possible causes of errors Publication 2706 QS001D EN P January 2009 18 InView Marquee Message Display Once the download is complete the module restarts The EtherNet Communication module can now be connected to the message display and is ready to communicate with the message display and the controller TIP The module may take up to 30 seconds to fully reboot Application Download Progress PFTSERY DLL 3 66 17 Program File Transfer Server 2 RS Linx 2 43 22 0 Library 32 2 43 22 0 Wed Sep 29 11 47 55 2004 Copyright 1993 2003 Allen Bradley Company LLC Help All rights reserved Download Tasks A Identifying operator terminal Verifying application file for download Preparing for File Transfer Checking operator terminal for compatibility Erasing operator terminal flash memory Transfening application file to operator terminal Progress 3533 bytes of 3633 transterred Configure a TCP IP Follow these steps to configure a TCP IP communication module Communication Module What You Need This list indicates what you need to complete this task e Catalog number 2706 P4x 2706 P7x 2706 P9x e Ethernet cable user supplied e Catalog number 2706 PENET1 e RS 232 serial cable supplied with Ethernet module e InView User Manual publication 2706 UMO16 e InView Installation Instructions publication 27
13. how this dialog next tme you start the Inview Messaging Software InView Marquee Message Display 3 4 In the Project Name field type an appropriate name for your project and click OK You can also write an optional description of the project if you choose Create new InView Project Project File C Documents and Sethings recanllo h y Documents New Project IVP ee Piugect Nane Mew Project Project Descopbore 5 In the Add Display dialog box type a display name and then choose your InView display type Add Display Identification Step 1 of 3 Display name D isplay Display type Number required 2706 P22R 1H Dimensions width 120 Height 7 olors Red Fonts 5 High 7 High 7 Fancy 6 Click Next to continue TIP You can add up to 100 displays to your project in the Add Display dialog box by changing the Number Required Displays can also be added individually from the main screen by right clicking the project folder on the top left side Publication 2706 QS001D EN P January 2009 4 InView Marquee Message Display Publication 2706 QS001D EN P January 2009 Add Display Communications Step 2 of 3 Configure Serial Communication Follow these steps to configure serial communication 1 In the Add Display dialog box click Serial for the Download Once you have selected it the Serial port settings heading becomes bold Unless otherwise required for your applica
14. ion that s contained in this manual You can also contact a special Customer Support number for initial help in getting your product up and running United States 1 440 646 3434 Monday Friday 8 a m 5 p m EST Outside United States Please contact your local Rockwell Automation representative for any technical support issues New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures United States Contact your distributor You must provide a Customer Support case number see phone number above to obtain one to your distributor in order to complete the return process Outside United States Please contact your local Rockwell Automation representative for the return procedure Allen Bradley Rockwell Automation InView RSLinx and TechConnect are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation Vorstlaan Boulevard du Souverain 36 1170 Brussels Belgium Tel 32 2 663 0600 Fax 32 2 663 0
15. next available ID number T Message Edilor MessageFile Sel File Edit View Format Tools Help Category Priority Low Pause 2 Seconds Mode Hold Line Control Alllines HS Hre a slr 38 89 Category Prioty Pause For Help press Fl hisgs 444 i Size 11 of 450 TIP For a full description of all of the icons on the Message Editor see Help topic Working with Messages subtopic Message Attributes The message is created with the defaults of the previous message Publication 2706 QS001D EN P January 2009 6 InView Marquee Message Display 3 Create a sample message a Click the new message row T Message Edilor MessageFile File Edit View Format Tools Help Category Priority Love Pause 2 Seconds Mode Hold Line Control Alnes coo Jeje rn Res foma 89m gt jal Categor Proy Pause For Help press Fl Msgs 444 1 Size 11 of 450 b Click the message editing field c Type New Message T Message Edilor MessageFile BEES File Edit View Format Tools Help Category Priority Love Pause 2Seconds Mode Categor Prionity Pause Message Low 2 Rockwell Automation Low 2 How Message For Help press Fl hisgs 444 1 Size 22 of 450 Publication 2706 QS001D EN P January 2009 InView Marquee Message Display 7 Download to the InView Display Follow these steps to download a message to th
16. nication Module User Manual publication 2706 UM017 Description Provides a more detailed description of how to use your InView display Provides details on installing and wiring InView displays Provides details on installing and wiring the InView communication module Provides information about using the InView communication module You can view or download publications at http literature rockwellautomation com To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative InView Marquee Message Display 23 Notes Publication 2706 QS001D EN P January 2009 Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products At http support rockwellautomation com you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect support programs For more information contact your local distributor or Rockwell Automation representative or visit_http support rockwellautomation com Installation Assistance If you experience a problem within the first 24 hours of installation please review the informat
17. r equivalent cable to a personal computer and the communication module Network Communication Cable Provided with Module To Personal Computer catalog number 2711 NC13 or equivalent Disconnect communication module internal DB9 connector connect your cable Publication 2706 QS001D EN P January 2009 12 InView Marquee Message Display Publication 2706 QS001D EN P January 2009 Configure Communication Follow these steps to configure the communication From an existing project start at the main page of the InView Messaging software 1 Right click the display you wish to modify and choose Edit Display vw InView Messaging Software New Project IVP Aca File Edit View Display Message File Message Tools Help Displays Message Files New Project Message File Display Type Partition Size Display MessageFile 2706 P22R 200 Display 1 Messagel ile 2706722 200 Sk r Cut Message File Details Edit Display Category Priority Pause Rename Display Low 2 Delete Display Low 2 Duplicate Display Associate Display Download Display By Name By File Ready 2 In the Edit Display dialog box click the Communications tab and choose Industrial Network Comms as your Download P
18. rotocol 3 At the bottom of the dialog box in the Industrial Network Communications settings click Configure Communications Edit Display Identification Communications Message File Setial eddiess 1 Heailbeal Disabled m Download Protocot C Serial C Ethemet TCP IP Industrial Network Comms TCPAP settings Address oooo Advanced Configure Canmuninatinns Senal port settings COM port comi y Baud rate 9600 Parity None v Data bits s o Stop bits 1 x Protocol O ee A oe ot C Industrial Network Commuricaturss nications D InView Marquee Message Display 13 4 In the InView Network Communications dialog box choose EtherNet IP as your communication protocol and click Next InView Network Communications select the communications protocol to use InView Serial Baud Hate ControlNct baad 9600 baal ControlNet DeviceNet DH DH485 EtherNet IP 5 From the Node Type pull down menu choose your node for example SLC 5 05 6 In the Node Address field type the controller s node address Communications Setup EtherNet IP InterScan Delay 100 ms Network Node Node Type SLC 5 05 v Node Path 4 Back Next gt Cancel 7 Click Next Publication 2706 QS001D EN P January 2009 14 InView Marquee Message Display 8 In the EtherNet IP Configuration dialog box uncheck both DHCP BootP Enable and DNS Enable EtherNet IP Configuration
19. steps to configure the display for serial download What You Need You need these items to complete this task e Catalog number 2706 P22R 2706 P4x 2706 P7x or 2706 P9x e Catalog number 2706 PCABLE1 Series A e Catalog number 2706 PSW1 InView Message software e 24V DC Class 2 SELV Power Supply for catalog number 2706 P22R only e InView User Manual publication 2706 UMO16 e InView Installation Instructions publication 2706 IN006 e Communication Module Installation Instructions publication 2706 INO15 e Communication Module User Manual publication 2706 UMO17 Rockwell ALLEN BRADLEY e ROCKWELL SOFTWARE Automation 2 InView Marquee Message Display Publication 2706 QS001D EN P January 2009 Equipment Setup Connect a power cord or power supply and catalog number 2706 PCABLE1 series A to the InView display and to COM1 of the computer TIP Verify RSLinx software is not using the serial port Configure the Display Follow these steps to configure the display 1 Install the InView Messaging software Refer to the installation instructions included on the CD 2 Launch the InView Software from Start gt Programs gt Rockwell Automation gt InView Software gt InView Messaging Software 3 After opening the software click Create New InView Project and click OK InView Startup What eile yns like to div fe Create a new InView project C Open an existing Iniviews project Project Files E lf S
20. tion accept the default Serial port settings 3 After you have finished setting up the Serial port settings click Serial address 1 Heartbeat Disabled Y j Pratacnat C Ethemet TCP IP Industrial Network Comms TCP IP settings Address 0 0 0 0 Advanced Configure Communications COM port COM1 Baud rate 9600 Party None v Data bits 8 Stop bits 1 Industrial Network Communications Protocol Nane Advanced Configure Communications Cancel lt lt Back Next gt gt Create Messages Next you will be directed to the message editor where you can create your messages The background message is the message that first appears when you power up the InView display The default background message is Rockwell Automation Follow these steps to create messages 1 You can modify the background message by clicking the row that contains the ID B and then clicking the message editing InView Marquee Message Display 5 The background message is always displayed on your InView Message Display when you cycle power and no messages are being triggered Message Editor MessagoFile Seg Category Priority Low Pause 2 decurs E a Line Control Allis Goto le 7 High Rockwell Automation lt Far Help press F1 Mage 444 1 Sire M nf 450 2 To create a new message click the down arrow icon until a new row is added to the message list with the
Download Pdf Manuals
Related Search
Related Contents
User Manual Systems Association canadienne des infirmières et infirmiers et Samsung 940BW PLUS Užívateľská príručka Le sursaut ou le chaos : Thibault de Montbrial décrypte le terrorisme iStarUSA WN2210 Controller User Manual nº 1907/2006 (REACH) Fecha / Actualizada el 6 de Agosto de 2010 MANUAL BIO-1 Es Document App Builder CET W/32 User guide Copyright © All rights reserved.