1756-TD003 - Rockwell Automation
Contents
1. 3 There are 128 connections are available for standard use An additional 3 connections are reserved for redundant control Rockwell Automation Publication 1756 TD003H EN E January 2015 17 1756 ControlLogix Communication Modules Specifications Table 14 Environmental Specifications 1756 ControlNet XT Module Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 CN2RXT C 25 70 C 13 158 F Temperature surrounding air max 70 C 158 F Temperature storage IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 2g 10 500 Hz Shock operating IEC 60068 2 27 Test Ea Unpackaged Shock 30g Shock nonoperating IEC 60068 2 27 Test Ea Unpackaged Shock 1756 CN2RXT C 30 g 1756 CN2RXT B 50 g Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 50 Pulse 100 AM 900 MHz 10V m
2. Cat No Firmware RSLogix 5000 RSLinxSoftware Packet Rate Capacity packets Support for Integrated Motion Revision Software Version Version second Extended on the EtherNet IP Uo HMI MSG Environment Network Axes 1756 EN2TXT 2X 15 02 00 or later 2 51 or later 10 000 2000 Yes N A 3 6 or later 18 02 00 or later 25 000 Up to 8 axes supported 1756 EN2TR 2X 17 01 02 or later 2 55 or later 10 000 2000 No N A 3 6 or later 18 02 00 or later 2 56 or later 25 000 Up to 8 axes supported 1756 EN2TRXT 5 028 or later 20 01 00 or later 2 56 or later 25 0004 2000 Yes N A 1756 EN2TSC 5 028 or later 20 01 00 or later 2 56 or later 25 000 930 with encryption No N A 1800 without encryption 1756 EN3TR 3 6 or later 18 02 00 or later 2 56 or later 25 0007 2000 No Up to 255 axes supported Table 4 Technical Specifications 1756 EtherNet IP Modules 1 This version is required to use CIP Sync technology Integrated Motion on the EtherNet IP Network or Exact Match keying 2 1 0 numbers are maximums they assume no HMI MSG HMI MSG numbers are maximums they assume no 1 0 Packet rates vary depending on packet size For more details see roubleshoot EtherNet IP Application Technique publication ENET AT003 and the EDS file for a specific catalog number 3 Module operates in a broad temperature spectrum 20 70 C 4 158 F and meets ANSI ISA S71 04 1985 Class G1 G2 and G3 as well as cULus Cl
3. Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 5096 Pulse 100 AM 900 MHz 10V m with 200 Hz 5096 Pulse 100 AM 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC61000 4 4 3 kV at 5 kHz on DeviceNet ports Surge transient immunity IEC 61000 4 5 2 kV line earth CM on DeviceNet ports Conducted RF immunity IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz 22 Rockwell Automation Publication 1756 TD003H EN E January 2015 1756 ControlLogix Communication Modules Specifications Table 18 Certifications 1756 DNB DeviceNet Module Certification 1756 DNB E C UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File E65584 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CSA CSA Certified Process Control Equipment See CSA File LR54689C CSA Certified Process Control Equipment for Class Division 2 Group A B C D Hazardous Locations See CSA File LR69960C CE European Union 2004 108 IEC EMC Directive compliant with the following e EN61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions e EN61131 2 Programmable Controllers Clause 8 Zone A amp B RCM Australian Radiocommunications Act co
4. Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 5096 Pulse 10096 AM at 900 MHz 1V m with 1 kHz sine wave 80 AM from 2000 2700 MHz Rockwell Automation Publication 1756 TD003H EN E January 2015 33 1756 ControlLogix Communication Modules Specifications Table 30 Certifications 1756 SYNCH Module Certification 1756 SYNCH UL UL Listed Industrial Control Equipment See UL file 65584 CSA CSA Certified Process Control Equipment See CSA File LR54689C CSA Certified Process Control Equipment for Class Division 2 Group A B C D Hazardous Locations See CSA file LR69960C CE European Union 2004 108 EC EMC Directive compliant with the following EN61131 2 Programmable Controllers Clause 8 Zone A amp B e EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions RCM Australian Radiocommunications Act compliant with EN 61000 6 4 Industrial Emissions FM FM Approved Equipment for use in Class Division 2 Group A B C D Hazardous Locations KC Korean Registration of Broadcasting and Communications Equipment compliant wi
5. 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 29 10 500 Hz Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 30g 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC61000 4 2 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 5096 Pulse 100 AM 900 MHz 10V m with 200 Hz 5096 Pulse 100 AM 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 3 kV at 5 kHz on ControlNet ports Surge transient immunity IEC 61000 4 5 2 kV line earth CM on ControlNet ports Conducted RF immunity IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Rockwell Automation Publication 1756 TD003H EN E January 2015 15 1756 ControlLogix Communication Modules Specifications Table 12 Certifications 1756 ControlNet Modules Certification 1756 CN2R B 1756 CNB E 1756 CNBR E 1756 CN2 C 1756 CN2R C 1756 CN2RK C C UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File 65584 UL Listed for Class I Division 2 Group A B C D Hazardous Locations certified for U S an
6. Conducted RF immunity IEC 61000 4 6 Table 21 Certifications 1756 DH and Remote 1 0 Modules Certification 1756 DHRIO E 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz 1756 RIO B C UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File E6558 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 4 CSA CSA Certified Process Control Equipment See CSA File LR54689C CSA Certified Process Control Equipment for Class I Division 2 Group A B C D Hazardous Locations See CSA File LR69960C CE European Union 2004 108 IEC EMC Directive compliant with the following e EN 61326 1 Meas Control Lab Industrial Requirements e EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions e EN 61131 2 Programmable Controllers Clause 8 Zone A amp B RCM Australian Radiocommunications Act compliant with EN 61000 6 4 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with the following EN 60079 15 Potentially Explosive Atmospheres Protection n e EN60079 0 General Requirements Il 3 G Ex nA IIC T4 Gc X KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 1 When product is marked See the Product Certification link at http www ab com for Declarations of Conformity C
7. 13 1756 CN2R B 1756 CN2R C 1756 CN2RK 1756 CNB 1756 CNBR ControlNet bridge 64 connections recommend using only 40 48 Logix 13 connections for 1 0 1756 CN2RXT ControlLogix XT ControlNet bridge 128 Logix connections 7 DeviceNet 1756 DNB E DeviceNet bridge 21 Data Highway Plus 1756 DHRIO Data Highway Plus Remote 1 0 module 25 1756 DHRIOXT ControlLogix XT Data Highway Plus Remote 1 0 module 27 Remote 1 0 1756 DHRIO Data Highway Plus Remote 1 0 module 25 1756 RIO B Remote 1 0 module 25 1756 DHRIOXT ControlLogix XT Data Highway Plus Remote 1 0 module 27 DH 485 module 1756 DH485 DH 485 module 30 SynchLink 1756 SYNCH SynchLink fiber optic communication link 32 1 128 connections are available for standard use An additional three connections are reserved for redundant control Rockwell Automation Publication 1756 TD003H EN E January 2015 1756 ControlLogix Communication Modules Specifications Communication Connections A ControlLogix system uses connections to establish communication links between devices The types of connections include the following Controller to local I O modules or local communication modules Controller to remote I O or remote communication modules Controller to remote I O rack optimized modules Produced and consumed tags Messages Controller access with the Studio 5000 environment Controller access with RSLinx software for HMI or other applications You indirectly determine the numbe
8. ports Surge transient immunity IEC 61000 4 5 2 kV line earth CM on Ethernet ports 2 kV line earth CM on Ethernet ports 2 kV line earth CM on Ethernet ports Conducted RF immunity IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz 1 Applies only to these modules series 1756 EN2T D 1756 EN2TSC A 1756 EN2TR C 1756 EN3TR B Table 6 Certifications 1756 EtherNet IP Modules Certification 1756 EN2T D 1756 EN2F C 1756 EN2TSC B 1756 EN2TR C 1756 ENBT A 1756 EWEB B 1756 EN3TR B c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File 65584 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CSA CSA Certified Process Control Equipment See CSA CSA Certified Process CSA Certified Process File LR54689C Control Equipment See Control Equipment See CSA Certified Process Control Equipment for Class CSA File LR54689C CSA File LR54689C Division 2 Group A B C D Hazardous Locations See CSA Certified Process CSA Certified Process CSA File LR69960C Control Equipment for Control Equipment for Class Division 2 Group Class I Division 2 Group A B C D Hazardous A B C D Hazardous Locations See CSA File Locations See CSA File LR69960C LR69960C CE European Union 2004 108 IEC EMC Directive compliant with EN
9. 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B RCM Australian Radiocommunications Act compliant with EN 61000 6 4 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with the following EN 60079 15 Potentially Explosive Atmospheres Protection n EN 60079 0 General Requirements I 3 G Ex nA IIC T4 Gc X DEMKO13ATEX1325026X 1756 EN2T C only FM All modules except 1756 EN2TSC FM Approved Equipment for use in Class Division 2 Group A B C D Hazardous Locations IECEX IECEx System compliant with IEC 60079 15 Potentially Explosive Atmospheres Protection n IEC 60079 0 General Requirements I 3 G Ex nA IIC T4 Gc IECEx UL 14 0008X 8 Rockwell Automation Publication 1756 TD003H EN E January 2015 Table 6 Certifications 1756 EtherNet IP Modules 1756 ControlLogix Communication Modules Specifications Certification 1756 EN2T D 1756 EN2F C 1756 EN2TSC B 1756 EN2TR C 1756 ENBT A 1756 EWEB B 1756 EN3TR B KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 EAC Russian Customs Union TR CU 020 2011 EMC Technical Regulation compliant with Russian Customs Union TR CU 004 2011 LV Technical Regulation compliant with EtherNet IP ODVA conformance tested to EtherNet IP specificati
10. NAP cable 1786 CP Wiring category 1 on ControlNet ports 1 on ControlNet ports 3 on USB ports 3 on NAP ports North American temperature code T4A IEC temperature code T4 Enclosure type rating None open style 1 The USB port is intended for temporary local programming purposes only and not intended for permanent connection Do not use the USB port in hazardous locations 2 Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 3 128 connections are available for standard use An additional three connections are reserved for redundant control 14 Rockwell Automation Publication 1756 TD003H EN E January 2015 Table 11 Environmental Specifications 1756 ControlNet Modules Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 ControlLogix Communication Modules Specifications 1756 CN2 C 1756 CN2R C 1756 CN2RK C 0 60 C 32 140 F 1756 CNB E 1756 CNBR E Temperature surrounding air max 60 C 140 F Temperature storage IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C
11. from the use or application of this equipment The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Documentation Feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature Rockwell Automation Rockwell Software Allen Bradley ControlLogix ControlLogix XT Data Highway Plus DH KwikLink Logix5000 PLC 5 PanelView SLC Stratix 8300 Stratix 5700 Stratix 8000 Stratix 6000 Stratix 2000 RSLinx RSLogix NetLinx Studio 5000 and SynchLink are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies Rockwell Otomasyon Ticaret A Kar Plaza Is Merkezi E Blok Kat 6 34752 erenk y stanbul Tel 90 216 5698400 www rockwellautomation com Power
12. ft 1761 NET AIC Advanced Interface Converter AIC connects each channel on the 1756 DH485 20 4 28 8V DC power source required module to the DH 485 network Typical 120 mA 24V DC current draw 9300 RADKIT Remote access dial in kit 56 Kbps modem connection to devices on a DH network SynchLink Communication The SynchLink module provides time synchronization and data broadcasting capabilities for distributed motion and coordinated drive control The 1756 SYNCH SynchLink module connects a ControlLogix chassis to a SynchLink including the following Preconfigured modem Communication module e DIN rail mounting hardware Associated cables fiber optic communication link The module does the following e Coordinates Coordinated System Time across multiple ControlLogix chassis e Moves a limited amount of data from one chassis to another at a high speed e Lets one controller consume motion axes data from a controller in another chassis Table 28 Technical Specifications 1756 SYNCH Module Attribute 1756 SYNCH SynchLink data rate 5 Mbps Operating wavelength 650 nm red Type of communication Synchronous Frame period 50 us Frame parameters 3 Flags 3 bytes Control field 1 byte Data field 24 bytes CRC field 2 bytes Current draw 5 1V DC 1200 mA Current draw 24V DC 3mA Power dissipation 6 2W Thermal dissipation 21 2 BTU hr Slot width 1 Module location C
13. intended for temporary local programming purposes only and not intended for permanent connection Do not use the USB port in hazardous locations 2 Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 3 Applies only to these modules series 1756 EN2T D 1756 EN2TSC A 1756 EN2TR C 1756 EN3TR B Table 5 Environmental Specifications 1756 EtherNet IP Modules Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat 1756 EN2F B 0 60 C 32 140 F IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 EN2T D 1756 EN2TR C 1756 EN2TSC A 1756 EN3TR B 1756 ENBT A 1756 EWEB B Temperature surrounding air max 60 C 140 F Temperature storage IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity 5 95 noncondensing IEC 60068 2 30 Test Db Unpackaged damp heat Vibration 2g 10 500 Hz IEC 60068 2 6 Test Fc Operating Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 30g 30 g 30 g 50g IEC 60068 2 27 Test Ea Unpackaged Shock
14. with 200 Hz 50 Pulse 100 AM 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 3 kV at 5 kHz on ControlNet ports Surge transient immunity IEC 61000 4 5 2 kV line earth CM on ControlNet port Conducted RF immunity IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz 18 Rockwell Automation Publication 1756 TD003H EN E January 2015 1756 ControlLogix Communication Modules Specifications Table 15 Certifications 1756 ControlNet XT Module Certification 1756 CN2RXT C C UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File E65584 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CE European Union 2004 108 IEC EMC Directive compliant with the following e EN61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN61000 6 4 Industrial Emissions e EN61131 2 Programmable Controllers Clause 8 Zone A amp B RCM Australian Radiocommunications Act compliant with EN 61000 6 4 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with the following EN 60079 15 Potentially Explosive Atmospheres Protection n EN 60079 0 General Requirements Il 3 G Ex nA IIC T4 Gc X KC Korean Registration of Broadcasting and Communications Equipment compliant with Art
15. 00 Hz 5096 Pulse 10096 AM 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC61000 4 4 3 kV at 5 kHz on Ethernet ports Surge transient immunity IEC 61000 4 5 2 kV line earth CM on Ethernet ports Conducted RF immunity IEC 61000 4 6 1 Applies only to these modules series 1756 EN2TXT D 1756 EN2TRXT C Table 9 Certifications 1756 EtherNet IP XT Module 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Certification 1756 EN2TXT D 1756 EN2TRXT C c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File 65584 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CE European Union 2004 108 IEC EMC Directive compliant with the following e EN61326 1 Meas Control Lab Industrial Requirements e EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B RCM Australian Radiocommunications Act compliant with EN 61000 6 4 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with the following EN 60079 15 Potentially Explosive Atmospheres Protection n e EN 60079 0 General Requirements Il 3 G Ex nA IIC T4 Gc X KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 EtherNet IP ODV
16. 1 Provides information on system architecture configuring secure communication and diagnostics DeviceNet Network Configuration User Manual publication DNET UM004 Provides information on system architecture configuring communication and diagnostics ControlLogix DH 485 Communication Module User Manual publication 1756 UM532 Provides information on system architecture configuring communication and diagnostics ControlLogix Data Highway Plus Remote 1 0 Communication Interface Module User Manual publication 1756 UM514 Provides information about programming messaging applying and connecting the module ControlLogix SynchLink Module User Manual publication 1756 UM521 Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Provides information about topologies configurations planning and installing a Synchlink module Provides general guidelines for installing a Rockwell Automation industrial system Product Certifications website http www ab com Provides declarations of conformity certificates and other certification details You can view or download publications at http www rockwellautomation com literature To order paper copies of technical documentation contact your local Allen Bradley distributor or Rockwell Automation sales representative Summary of Changes This manual contains new and updated information Changes throughout this revision are marked by cha
17. 1756 CN2RXT C Configuration Redundant ControlNet communication rate 5 Mbps Logix communication connections 128 Connections supported max 1319 Number of nodes max 99 Current draw 5 1V DC 1300 mA Current draw 24V DC 3mA Voltage and current ratings 5 1V DC 1 3A Power dissipation 6 6W 22 5 BTU Hr Thermal dissipation 22 9 BTU hr Isolation voltage 30V continuous Basic Insulation Type ControlNet A B to Backplane ControlNet A to ControlNet B USB to ControlNet A B and USB to Backplane Type tested at 500V AC for 60 s Weight approx 0 293 kg 0 64 Ib Slot width 1 Module location Chassis based any slot Chassis 1756 MLXT 1756 A5XT 1756 A7XT 1756 A7LXT Power supply standard 1756 PAXT 1756 PBXT Power supply redundant None ControlNet port 2 ControlNet BNC ControlNet cable 1786 RG6 quad shield RG6 coaxial cable USB port USB 1 1 full speed 12 Mbps Wiring category 1 on ControlNet ports 3 on USB port North American temperature code T4A IEC temperature code T4 Enclosure type rating None open style 1 The USB port is intended for temporary local programming purposes only and not intended for permanent connection Do not use the USB port in hazardous locations 2 Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1
18. 1756 EN2TSC bridge Use an Internet browser to remotely access tags in a ControlLogix controller Communicate with other EtherNet IP or generic Ethernet devices messaging only no 1 0 control Bridge EtherNet IP links to route messages to devices on other networks Rockwell Automation Publication 1756 TD003H EN E January 2015 1756 EWEB web server 1756 ControlLogix Communication Modules Specifications EtherNet IP Network Specifications Table 1 ControlLogix EtherNet IP Connections Specifications Cat No Connections CIP Unconnected T Messages backplane TCP apt Ethernet 1756 ENBT 64 128 64 64 1756 EN2F 128 256 128 128 1756 EN2T 128 256 128 128 1756 EN2TXT 128 256 128 128 1756 EN2TR 128 256 128 128 1756 EN2TRXT 128 256 128 128 1756 EN2TSC 128 256 128 128 1756 EN3TR 128 256 128 128 1756 EWEB 64 128 128 128 1 CP connections can be used for all explicit or all implicit applications For example a 1756 ENBT module has a total of 128 CIP connections that can be used for any combination of connections Table 2 ControlLogix EtherNet IP Data Specifications Number of Multicast Unicast Available in password required i tegoon Tags Max RSLogix 5000 Software 1756 ENBT 32 Version 16 03 00 or later No Yes Revision 3 3 1756 EN2F 32 Version 16 03 00 or later Yes Yes Revision 1 x 1756 E
19. 756 A13 1756 A17 Power supply standard 1756 PA72 1756 PA75 1756 PB72 1756 PB75 1756 PC75 1756 PH75 Power supply redundant 1756 PA75R 1756 PB75R 1756 PSCA2 Ethernet port 1 Ethernet fiber 1 Ethernet RJ45 Category 5 2 Ethernet RJ45 Category 5 1 Ethernet RJ45 Category 5 Ethernet cable Multimode fiber LC 802 3 compliant shielded 802 3 compliant shielded 802 3 compliant shielded 802 3 compliant shielded connector or unshielded twisted pair orunshielded twisted pair or unshielded twisted pair or unshielded twisted pair 6 Rockwell Automation Publication 1756 TD003H EN E January 2015 Table 4 Technical Specifications 1756 EtherNet IP Modules 1756 ControlLogix Communication Modules Specifications Attribute 1756 EN2F C 1756 EN2T D 1756 EN2TR C 1756 ENBT A 1756 EWEB B 1756 EN2TSC A 1756 EN3TR B USB port USB 1 1 full speed 12 USB 1 1 full speed 12 USB 1 1 full speed 12 Mbps Mbps Mbps Wiring category 3 on USB ports 2 on Ethernet ports 2 on Ethernet ports 2 on Ethernet ports 2 on Ethernet ports 3 on USB ports 3 on USB ports North American T4A temperature code IEC temperature code T4 Enclosure type rating None open style Transmitter launch power 19 dBm into 62 5 125 um at Beginning of Life BOL fiber N A 0 275 min 22 5 dBm into 50 125 um Allow 1 dB at End of Life EOL fiber N A 0 20 1 The USB port is
20. 86 TPYS Y tap straight Cables 1786 CP Programming cable to ControlNet RJ45 port 1786 RG6 ControlNet network shield high flex cable 1756 RG6F ControlNet network quad shield high flex coax cable Other 1786 TNCLXT4 ControlNet IP67 termination resistor 1786 XT ControlNet termination resistor Repeaters 1786 RPA ControlNet modular repeater adapter 1786 RPCD ControlNet coaxial hub repeater 1786 RPFRL ControlNet fiber ring repeater long distance 1786 RPFRXL ControlNet fiber ring repeater extra long distance 1786 RPFS ControlNet fiber repeater short distance 1786 RPFM ControlNet fiber repeater medium distance For more information see ControlNet Media System Components List publication AG PA002 20 Rockwell Automation Publication 1756 TD003H EN E January 2015 1756 ControlLogix Communication Modules Specifications DeviceNet Network The DeviceNet network is open providing connections between simple industrial devices such as sensors and actuators and higher level devices such as controllers and computers The DeviceNet network uses the Common Industrial Protocol CIP to control configure and collect data for industrial devices Table 16 Technical Specifications 1756 DNB DeviceNet Module Attribute 1756 DNB E DeviceNet communication rate 125 Kbps 500 m max 250 Kbps 250 m max 500 Kbps 100 m max Number of nodes max 64 Current draw 5 1V DC 400 mA Current draw 24V DC 0 mA DeviceNet curr
21. A conformance tested to EtherNet IP specifications 10 Rockwell Automation Publication 1756 TD003H EN E January 2015 1756 ControlLogix Communication Modules Specifications 1 When product is marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details ENET Module Diagrams Figure 1 1756 EN2T EtherNeUIP LIII co E LA i Allen Bradley g EtherNet IP Figure 2 1756 EN2TR 1756 EN3TR Allen Bradley EtherNet IP Rockwell Automation Publication 1756 TD003H EN E January 2015 11 1756 ControlLogix Communication Modules Specifications B Figure 3 1756 EN2F EtherNeUIP llen Bradley Alle p EtherNet IP 32520 M Accessories Ethernet Network Cat No Description Specifications 1585J M8PBJM x Ethernet RJ45 patchcord 8 conductor teal riser PVC cable flex rated cable also available X 2 2m 5 5 m or 10 10 m 1585J M8CC H RJ45 insulation displacement connecto
22. Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation NV Pegasus Park De Kleetlaan 12a 1831 Diegem Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 1756 TD003H EN E January 2015 Supersedes Publication 1756 TD003G EN E July 2014 Copyright 2015 Rockwell Automation Inc All rights reserved Printed in the U S A
23. DH 485 network You can have two controllers per one 1761 NET AIC converter but you need a different cable for each controller Connect one controller to port 1 9 pin connector and one controller to port 2 mini DIN connector Use this cable 1747 CP3 1761 CBL ACOO To connect to this port Port 1 DB 9 RS 232 DTE connection Port 2 1761 CBL APOO 1761 CBL PM02 mini DIN 8 RS 232 connection Table 25 Technical Specifications 1756 DH485 Module Attribute 1756 DH485 Communication rate 19 2 Kbps 9600 Kbps Current draw 5 1V DC 850 mA Current draw 24V DC 1 7mA Power dissipation 45W Thermal dissipation 15 4 BTU hr Isolation voltage 50V continuous basic insulation type DH485 A B to backplane and DH485 A to DH485 B Type tested at 750V DC for 60 s Slot width 1 Module location Chassis Power supply standard 1756 PA72 C 1756 PA75 B 1756 PB72 C 1756 PB75 B 1756 PC75 B 1756 PH75 B Power supply redundant 1756 PA75R 1756 PB75R 1756 PSCA2 Ports 2 DH 485 9 pin D shell Wiring category 2 on DH485 ports North American temperature code T5 Enclosure type rating None open style 1 Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 30 Rockwell Automation Publication 1756 TD003H EN E January 2015 Tabl
24. EC 60068 2 14 Test Nb Operating Thermal Shock 1756 DHRIO E 0 60 C 32 140 F 1756 RIO B Temperature surrounding air max 60 C 140 F Temperature storage 40 85 C 40 185 F IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Rockwell Automation Publication 1756 TD003H EN E January 2015 25 1756 ControlLogix Communication Modules Specifications Table 20 Environmental Specifications 1756 DH and Remote 1 0 Modules Continued Attribute 1756 DHRIO E 1756 RIO B Vibration 2g 10 500 Hz IEC 60068 2 6 Test Fc Operating Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 5096 Pulse 100 AM 900 MHz 10V m with 200 Hz 5096 Pulse 100 AM 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC61000 4 4 2kV at 5 kHz 2 kV at 5 kHz Surge transient immunity IEC 61000 4 5 2 kV line earth CM
25. Emission Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8 kV air discharges Rockwell Automation Publication 1756 TD003H EN E January 2015 1756 ControlLogix Communication Modules Specifications Table 5 Environmental Specifications 1756 EtherNet IP Modules Continued Attribute Radiated RF immunity IEC 61000 4 3 1756 EN2F B 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 5096 Pulse 100 AM 900 MHz 10V m with 200 Hz 5096 Pulse 100 AM 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz 1756 EN2T D 1756 EN2TSC A 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 5096 Pulse 100 AM 900 MHz 10V m with 200 Hz 5096 Pulse 100 AM 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz 1756 EN2TR C 1756 EN3TR B 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 5096 Pulse 100 AM 900 MHz 10V m with 200 Hz 5096 Pulse 10096 AM 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz 1756 ENBT A 1756 EWEB B 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 5096 Pulse 10096 AM 900 MHz 10V m with 200 Hz 5096 Pulse 100 AM 1890 MHz 1V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 3 kV at 5 kHz on Ethernet ports 3 kV at 5 kHz on Ethernet ports 2 kV at 5 kHz on Ethernet
26. N2T 32 Version 16 03 00 or later Yes Yes Revision 1 x 1756 EN2TXT 32 Version 16 03 00 or later Yes Yes Revision 1 x 1756 EN2TR 32 Version 17 01 02 or later Yes Yes Revision 1 x 1756 EN2TRXT 32 Version 20 01 00 or later Yes Yes Revision 1 x 1756 EN2TSC 32 Version 20 01 00 or later Yes Yes Revision 1 x 1756 EN3TR 32 Version 18 02 00 or later No Yes Revision 3 x 1756 EWEB N A N A Yes Yes Revision 2 2 1 Each controller can send a maximum of 32 produced tags to one single consuming controller If these same tags are sent to multiple consumers the maximum number is 31 Table 3 ControlLogix EtherNet IP Packet Rates Specifications Cat No Firmware RSLogix 5000 RSLinxSoftware Packet Rate Capacity packets Support for Integrated Motion Revision Software Version Version second Extended on the EtherNet IP UO TIHM MSG Environment Network Axes 1756 ENBT Any 8 02 00 or later 2 30 or later 5000 900 No N A 1756 EN2F 2X 15 02 00 or later 2 51 or later 10 000 2000 No N A 3 6 or later 18 02 00 or later 25 000 Up to 4 axes supported Up to 8 axes supported 1756 EN2T 2 x or earlier 15 02 00 or later 2 51 or later 10 000 2000 No N A 3 6 or later 18 02 00 or later 25 0009 Up to 8 axes supported Rockwell Automation Publication 1756 TD003H EN E January 2015 5 1756 ControlLogix Communication Modules Specifications Table 3 ControlLogix EtherNet IP Packet Rates Specifications
27. Technical Data Allen Bradley 1756 ControlLogix Communication Modules Specifications Standard ControlLogix Catalog Numbers 1756 EN2F 1756 EN2T 1756 EN2TR 1756 EN3TR 1756 EN2TSC 1756 ENBT 1756 EWEB 1756 CN2 1756 CN2R 1756 CNB 1756 CNBR 1756 CN2RK 1756 DNB 1756 DHRIO 1756 RIO 1756 DH485 1756 SYNCH ControlLogix XT Catalog Numbers 1756 EN2TXT 1756 EN2TRXT 1756 CN2RXT 1756 DHRIOXT Topic Page Additional Resources 2 Summary of Changes 2 Available Communication Modules 3 EtherNet IP Network 4 Stratix Switches 12 ControlNet Network 13 DeviceNet Network 21 DH and Remote 1 0 Networks 24 DH 485 Network 30 SynchLink Communication 32 LISTEN Ns Rockwell Allen Bradley Rockwell Software Automation 1756 ControlLogix Communication Modules Specifications l Additional Resources These documents contain additional information concerning related products from Rockwell Automation Resource EtherNet IP Modules Installation Instructions publication ENET IN002 Description Provides information on installing EtherNet IP modules EtherNet IP Secure Communication User Manual publication ENET UM003 Provides information on system architecture configuring secure communication and diagnostics ControlNet Modules Installation Instructions publication CNET IN005 Provides instructions for installing ControlNet modules ControlLogix System User Manual publication 1756 UM00
28. ass 1 Div 2 C Tick CE ATEX Zone 2 and SIL 2 requirements for increased protection against salts corrosives moisture condensation humidity and fungal growth 4 This value assumes the use of a 1756 L7x ControlLogix controller For a 1756 L6x ControlLogix controller see ControlLogix Controllers User Manual publication 1756 UM001 Attribute 1756 EN2F C 1756 EN2T D 1756 EN2TR C 1756 ENBT A 1756 EWEB B 1756 EN2TSC A 1756 EN3TR B EtherNet IP 10 100 Mbps communication rate Current draw 5 1V DC 12A 1A 1A 700 mA 700 mA Current draw 24V DC 3mA 3mA 3mA Voltage and current ratings 5 1 V DC 1 2A Power dissipation 62W 5 1W 5 1W 3 7W 37W Thermal dissipation 21 28 BTU hr 17 4 BTU hr 17 4 BTU hr 12 6 BTU hr 12 6 BTU hr Isolation voltage 30V continuous Basic 30V continuous Basic 30V continuous Basic 30V continuous basic 30V continuous basic Insulation Type USB to Insulation Type Ethernetto Insulation Type Ethernetto insulation type Ethernet insulation type Ethernet Backplane Backplane USB to Backplane USB to network to backplane network to backplane Type tested at980V AC Backplane and USB to Backplane and USB to Type tested 707V DC for Type tested 707V DC for for 60s Ethernet Ethernet 60 s 60 s Type tested at 980V AC for Type tested at 980V AC for 605 60s Slot width 1 Module location Chassis based any slot Chassis 1756 A4 1756 A7 1756 A10 1
29. d Canada See UL File E194810 CSA CSA Certified Process Control Equipment See CSA File LR54689C NA CSA Certified Process Control Equipment for Class Division 2 Group A B C D Hazardous Locations See CSA File LR69960C CE European Union 2004 108 IEC EMC Directive compliant with the following e EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B RCM Australian Radiocommunications Act compliant with EN 61000 6 4 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with the following EN 60079 15 Potentially Explosive Atmospheres Protection n EN 60079 0 General Requirements I3GExnAIICT4 GcX KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 FM FM Approved Equipment for use in Class Division 2 Group A B C D Hazardous Locations cl ControlNet International conformance tested to ControlNet specifications 1 When product is marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details 16 Rockwell Automation Publication 1756 TD003H EN E January 2015 1756 ControlLogix Communication Modules Specifications Table 13 Technical Specifications 1756 ControlNet XT Module Attribute
30. ductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Refer to the DeviceNet Media Design and Planning Guide publication DNET UM072 for information specific to your DeviceNet network Rockwell Automation Publication 1756 TD003H EN E January 2015 21 1756 ControlLogix Communication Modules Specifications Table 17 Environmental Specifications 1756 DNB DeviceNet Module Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 DNB E 0 60 C 32 140 F Temperature surrounding air max 60 C 140 F Temperature storage IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 29 10 500 Hz Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8kV air discharges
31. e 26 Environmental Specifications 1756 DH485 Module Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 DH485 0 60 C 32 140 F 1756 ControlLogix Communication Modules Specifications Temperature surrounding air max 60 C 140 F Temperature storage IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 29 10 500 Hz Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 4 kV contact discharges IEC 61000 4 2 8kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 5096 Pulse 10096 AM 900 MHz 1V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC61000 4 4 2 kV at 5 kHz on communication ports Surge transient immunity IEC 61000 4 5 1 kV line earth CM on communication ports Conducted RF immunity IEC 61000 4 6 Tab
32. ent draw 24V DC 60 mA DeviceNet voltage range 11 25V DC CL 2 SELV Power dissipation 35W Thermal dissipation 11 9 BTU hr Isolation voltage 50V continuous basic insulation type DeviceNet network to backplane Type tested at 853V AC for 60s No isolation between USB and backplane Slot width 1 Module location Chassis based any slot Chassis 1756 A4 1756 A7 1756 A10 1756 A13 1756 A17 Power supply standard 1756 PA72 C 1756 PA75 B 1756 PB72 C 1756 PB75 B 1756 PC75 B 1756 PH75 B Power supply redundant 1756 PA75R 1756 PB75R 1756 PSCA2 DeviceNet power To comply with the CE low voltage directive LVD the DeviceNet network must be powered from a source compliant with the safety extra low voltage SELV or protected extra low voltage PELV To comply with UL restrictions the DeviceNet network must be powered from a source compliant with Class 2 or limited voltage current DeviceNet port 1 DeviceNet open style 5 or 10 pin linear plug DeviceNet connector torque 0 56 0 79 Nem 5 7 Ib in USB port USB 2 0 full speed 12 Mbps Wiring category 1 On DeviceNet ports 3 On USB ports North American temperature code T4A IEC temperature code T4 Enclosure type rating None open style 1 The USB port is intended for temporary local programming purposes only and not intended for permanent connection Do not use the USB port in hazardous locations 2 Use this con
33. er to controller interlocking always take precedence over program uploads and downloads and messaging If your application requires Select one of these interfaces 128 ControlNet connections per communication module 1756 CN2 B 1756 CN2 C 1756 CN2R B 1756 CN2R C 1756 CN2RK C 1756 CN2RXT B 1756 CN2RXT C Control in environments where temperatures range from 1756 CN2RXT C 25 70 C 13 158 F 40 48 ControlNet connections per communication module 1756 CNB 1756 CNBR Connect to Other Devices via a ControlNet Network The Studio 5000 environment supports a generic ControlNet module that allows connections to ControlNet nodes for which there is no specific support currently available in the programming software A module configured as a generic ControlNet module communicates with the controller in the form of input output status and configuration tags For example use the generic module configuration to set up communication between a ControlLogix controller and a 1203 CN1 ControlNet communication module Then use the CIP generic MSG instruction type to send and receive messages from the 1203 CN1 module Table 10 Technical Specifications 1756 ControlNet Modules Attribute 1756 CN2 C 1756 CNBR E Configuration Standard Redundant Standard Redundant ControlNet communication rate 5 Mbps Logix communication connections 128 40 48 Connections supported max 1319 64 Numbe
34. ermal dissipation 15 4 BTU hr 8 5 BTU hr Isolation voltage 30V continuous basic insulation type DHRIO A B to backplane 50V continuous basic insulation type RIO and DHRIO A programming port to DHRIO B communication lines to backplane No isolation between DHRIO A and Programming port Type tested at 500V ACfor 60 s Type tested at 877V DC for 60 s Slot width 1 Module location Chassis based any slot Chassis 1756 M 1756 A7 1756 A10 1756 A13 1756 17 Power supply standard 1756 PA72 C 1756 PA75 B 1756 PB72 C 1756 PB75 B 1756 PC75 B 1756 PH75 B Power supply redundant 1756 PA75R 1756 PB75R 1756 PSCA2 Ports 2 individually selectable for DH or remote 1 0 1 for remote 1 0 Screw terminal torque 0 5 0 6 Nem 5 7 bein Wire size 0 519 mm2 20 AWG Belden 9463 copper twinaxial Wiring category 2 on DHRIO ports 2 on RIO ports 3 on local programming port North American temperature code T4A IEC temperature code T4 Enclosure type rating None open style 1 Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Table 20 Environmental Specifications 1756 DH and Remote 1 0 Modules Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat I
35. ertificates and other certification details 26 Rockwell Automation Publication 1756 TD003H EN E January 2015 1756 ControlLogix Communication Modules Specifications Table 22 Technical Specifications 1756 DH and Remote 1 0 XT Module Attribute Communication rate 1756 DHRIOXT E 57 6 Kbps 115 2 Kbps 230 4 Kbps DH communication connections 32 DH messages per DH module Remote 1 0 communication connections Remote 1 0 scanner only 32 logical rack connections per remote 1 0 channel 16 block transfer connections per remote 1 0 channel Connections supported max 32 Current draw 5 1V DC 850 mA Current draw 24V DC 1 7mA Power dissipation 45W Thermal dissipation 15 4 BTU hr Isolation voltage 30V continuous basic insulation type DHRIO A B to backplane and DHRIO A programming port to DHRIO B No Isolation between DHRIO A and Programming port Type tested at 853V AC for 60 s Slot width 1 Module location Chassis based any slot Chassis 1756 A4LXT 1756 A5XT 1756 A7XT 1756 A7LXT Power supply standard 1756 PBXT Power supply redundant None Ports 2 individually selectable for DH or remote 1 0 Screw terminal torque 0 5 0 6 Nem 5 7 bein Wire size 0 519 mm2 20 AWG Belden 9463 copper twinaxial Wiring category 2 on DHRIO ports 3 on local programming port North American temperature code T4A IEC temperature code T4 Enclosure t
36. for predetermined cable lengths Round media Round trunk cable is available in bulk spools or as pre molded cordsets or patchcords in varying lengths A wide variety of rugged durable DeviceNet components is available for use in round trunk systems Stainless steel versions of round cable system components are also available Thick trunk round media systems use thick cable for maximum DeviceNet trunk line length e Round media thin trunk systems use thin cable to reduce maximum trunk line distances with a more compact and cost effective installation for some applications Thin cable outer jacket material is TPE for additional chemical resistance For more information on selecting DeviceNet media see the NetLinx Selection Guide publication NETS SG001 Rockwell Automation Publication 1756 TD003H EN E January 2015 23 1756 ControlLogix Communication Modules Specifications DH and Remote 1 0 Networks The Data Highway Plus network supports messaging between devices The remote I O link connects to remote I O chassis and other intelligent devices The 1756 DHRIO module supports messaging between devices on DH networks The remote I O functionality enables the module to act as a scanner for transferring digital and block transfer data to and from remote I O devices The 1756 RIO module can act as a scanner or adapter on a remote I O network In addition to digital and block transfer data the 1756 RIO module transfers analog a
37. hassis based any slot Chassis 1756 A4 1756 A7 1756 A10 1756 A13 1756 A17 Power supply standard 1756 PA72 C 1756 PA75 B 1756 PB72 C 1756 PB75 B 1756 PC75 B 1756 PH75 B Power supply redundant 1756 PA1756 PA75R 1756 PB75R 1756 PSCA2 32 Rockwell Automation Publication 1756 TD003H EN E January 2015 1756 ControlLogix Communication Modules Specifications Table 28 Technical Specifications 1756 SYNCH Module Continued Attribute 1756 SYNCH Ports 2 fiber optic Cable fiber type 200 230 micron HCS Hard Clad Silica Cable fiber termination type Versalink V System Cable length 1 300 m 3 28 984 2 ft North American Temp Code T4A Endosure type rating None open style Table 29 Environmental Specifications 1756 SYNCH Module Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock Temperature surrounding air max 1756 SYNCH 0 60 C 32 140 F 60 C 140 F Temperature storage IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 29 10 500 Hz
38. icle 58 2 of Radio Waves Act Clause 3 Cl ControlNet International conformance tested to ControlNet specifications 1 When product is marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details CNET Module Diagrams Figure 4 1756 CN2 IET L Ay ay E vis mil 32516 M Rockwell Automation Publication 1756 TD003H EN E January 2015 19 1756 ControlLogix Communication Modules Specifications B Figure5 1756 CN2R Accessories ControlNet Network TB I L3 EE P Allen Bradley o6 9 im 32517 M Cat No Description Taps 1786 TCT2BD1 T tap straight IP67 rated 1786 TPR T tap right angle 1786 TPS T tap straight 1786 TPYR Y tap right angle 17
39. le 27 Certifications 1756 DH485 Module 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Certification 1756 DH485 c UL us UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CE European Union 2004 108 IEC EMC Directive compliant with the following e EN61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B RCM Australian Radiocommunications Act compliant with EN 61000 6 4 Industrial Emissions KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 1 When product is marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details Rockwell Automation Publication 1756 TD003H EN E January 2015 31 1756 ControlLogix Communication Modules Specifications Accessories DH 485 Network Cat No 1747 CP3 Description 9 pin D shell straight 9 pin D shell right angle Specifications 3 m 9 8 ft 1761 CBL ACOO 9 pin D shell right angle 9 pin D shell right angle 45 cm 17 7 in 1761 CBL APO0 9 pin D shell right angle 8 pin mini DIN 45 cm 17 7 in 1761 CBL PM02 9 pin D shell straight 8 pin mini DIN 2m 6 5
40. mpliant with EN 61000 6 4 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with the following EN 60079 15 Potentially Explosive Atmospheres Protection n EN60079 0 General Requirements Il 3 G Ex nA IIC T4 Gc X FM FM Approved Equipment for use in Class Division 2 Group A B C D Hazardous Locations KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 DeviceNet ODVA conformance tested to DeviceNet specifications 1 When product is marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details Accessories DeviceNet Network Cat No Description KwikLink Lite flat media KwikLink Lite flat media is a newer ODVA approved solution for wiring DeviceNet networks Drop lines for connecting nodes are added by using the KwikLink Lite two piece connectors This cable system supports the intermixing of DeviceNet cable types thin round with flat All ofthe KwikLink Lite connectors provide insulation displacement technology with reduced assembly time KwikLink flat media The KwikLink flat media system provides a modular cabling method with its flat four wire cable and Insulation Displacement Connectors IDCs The KwikLink system allows nodes to be added to the network without severing the trunkline Cutting or stripping of the trunkline is eliminated as is the need
41. nd specialty data without message instructions Example Configuration DH Network PLC 5 1784 U2DHP Studio 5000 environment _ PanelView Plus ControlLogix 1756 DHRIO SLC 5 04 Example Configuration Remote 1 0 Network 1756 DHRIO as a Remote 1 0 Scanner SET a i ER 1794 V 0 A 17911 0 PanelView Plus 1756 RIO as a PLC 5 Remote 1 0 Adapter EHE densi 8 a al a ai Bi 24 Rockwell Automation Publication 1756 TD003H EN E January 2015 Table 19 Technical Specifications 1756 DH and Remote 1 0 Modules Attribute Communication rate 1756 DHRIO E 57 6 Kbps 115 2 Kbps 230 4 Kbps 1756 ControlLogix Communication Modules Specifications 1756 RIO B Remote 1 0 communication Remote 1 0 scanner only 32 logical rack connections per remote 1 0 channel 16 block transfer connections per remote 1 0 channel Remote 1 0 scanner or adapter 32 physical racks 0 76 any combination of rack size and block transfers Connections supported max 3 10 scheduled 1 0 Current draw 5 1V DC 850 mA 450 mA Current draw 24V DC 17mA 5mA Power dissipation 45W 25W Th
42. nge bars as shown to the right of this paragraph New and Updated Information This table contains the changes made in this revision Topic Added ControlLogix EtherNet IP Connections Specifications Page ControlLogix EtherNet IP Data Specifications ControlLogix EtherNet IP Packet Rates Specifications Removed the 1756 EN2F B Model and Added 1756 EN2F C module Added ENET Module Diagrams 11 Added CNET Module Diagrams 19 2 Rockwell Automation Publication 1756 TD003H EN E January 2015 1756 ControlLogix Communication Modules Specifications Available Communication Modules Network Cat No Description Page EtherNet IP 1756 EN2F EtherNet IP bridge fiber 256 Logix connections 6 1756 EN2T EtherNet IP bridge copper 256 Logix connections 6 1756 EN2TSC EtherNet IP secure communication module 6 1756 EN2TR EtherNet IP bridge embedded switch copper 6 Supports as many as 8 axis of motion 1756 EN3TR EtherNet IP bridge embedded switch copper 6 Supports as many as 128 axis of motion 1756 ENBT EtherNet IP bridge copper 128 Logix connections 6 1756 EWEB Ethernet web server 128 Logix connections Class 3 messaging only 6 1756 EN2TXT ControlLogix XT EtherNet IP bridge copper 256 Logix connections 6 1756 EN2TRXT ControlLogix XT EtherNet IP bridge module with embedded switch 6 ControlNet 1756 CN2 B 1756 CN2 C ControlNet bridge 128 Logix connections
43. oadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 1 When product is marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details Accessories DH and Remote 1 0 Networks Cat No Description Specifications 1770 CD Cable to connect communication module to DH network Belden 9463 twinaxial 9300 RADKIT Remote access dial in kit 56 Kbps modem connection to devices on a DH network including the following Preconfigured modem Communication module e DIN rail mounting hardware e Associated cables Rockwell Automation Publication 1756 TD003H EN E January 2015 29 1756 ControlLogix Communication Modules Specifications DH 485 Network On the DH 485 network the controller can send and receive messages to and from other controllers on the network The DH 485 connection does support remote programming and monitoring via the Studio 5000 environment Excessive traffic over a DH 485 connection can adversely affect overall performance and can lead to timeouts and loss in the Studio 5000 environment configuration performance IMPORTANT Use Logix5000 controllers on DH 485 networks only when you want to add controllers to an existing DH 485 network For new applications with Logix5000 controllers we recommend open architecture networks You need a 1761 NET AIC converter for each controller on the
44. ons 1 When product is marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details Table 7 Technical Specifications 1756 EtherNet IP XT Modules Attribute 1756 EN2TXT D 1756 EN2TRXT C EtherNet IP communication rate 10 100 Mbps Logix communication connections 256 TCP IP communication connections 128 Current draw 5 1V DC 1A Power dissipation 5 1W 17 4BTU Hr Thermal dissipation 17 4 BTU hr Isolation voltage 30V continuous Basic Insulation Type Ethernet to Backplane USB to Backplane and USB to Ethernet Slot width Module location Chassis based any slot Chassis 1756 A4LXT 1756 A5XT 1756 A7XT 1756 A7LXT Power supply standard 1756 PAXT 1756 PBXT Power supply redundant None Ethernet port 2 Ethernet RJ45 Category 5 Ethernet cable 802 3 compliant shielded or unshielded twisted pair USB port USB 1 1 full speed 12 Mbps Wiring category 8 2 on Ethernet ports 3 on USB ports North American temperature code T4A IEC temperature code T4 Enclosure type rating None open style 1 2 3 publication 1770 4 1 Applies only to these modules series 1756 EN2TXT D 1756 EN2TRXT C The USB port is intended for temporary local programming purposes only and not intended for permanent connection Do not use the USB port in hazardous locations Use this conductor catego
45. r IDC 0 128 0 325 mm 26 22 AWG Cat 6 IDC no tool required 1585J M8CC C RJ45 crimp connector with boot qty 50 pieces 0 128 0 205 mm 26 24 AWG Cat 5e requires crimp tool for assembly 1585A JCRIMP Crimp tool 9300 RADES Remote access dial in kit 56 Kbps modem connection to devices on an Ethernet network Stratix Switches To effectively manage real time control and information flow throughout the manufacturing and IT enterprise Rockwell Automation offers a full portfolio of industrial Ethernet switches and media including a line of Stratix switches integrated with Cisco technology The Stratix line of switches includes modular managed fixed managed and unmanaged switches For detailed specifications for Stratix switches see Stratix Ethernet Switch Specifications Technical Data publication 1783 T D001 12 Rockwell Automation Publication 1756 TD003H EN E January 2015 1756 ControlLogix Communication Modules Specifications ControlNet Network The ControlNet network is an open control network for real time high throughput applications The ControlNet network uses the Common Industrial Protocol CIP to combine the functionality of an I O network E anda peer to peer network providing high speed performance for both functions The ControlNet network gives you deterministic repeatable transfers of all mission critical control data in addition to supporting transfers of non time critical data I O updates and controll
46. r of connections the controller uses by configuring the controller to communicate with other devices in the system The limit of connections may ultimately reside in the communication module you use for the connection If a message path routes through a communication module the connection related to the message also counts towards the connection limit of that communication module EtherNet IP Network The Ethernet Industrial EtherNet IP network protocol is an open industrial networking standard that If you need to Control 1 0 modules and drives Act as an adapter for 1 0 on remote EtherNet IP links Communicate with other EtherNet IP devices messages and HMI Bridge EtherNet IP links to route messages to devices on other networks supports both real time I O messaging and message exchange The EtherNet IP network uses off the shelf Ethernet communication chips and physical media Select this interface 1756 EN2F bridge 1756 EN2T bridge 1756 ENBT bridge Support device level ring DLR and linear topologies 1756 EN2TR redundant bridge 1756 EN3TR redundant bridge Provide control in environments where temperatures range from 25 70 C 13 158 F 1756 EN2TXT bridge Support device level ring DLR and linear topologies Provide control in environments where temperatures range from 25 70 C 13 158 F 1756 EN2TRXT redundant bridge Secure access to a control system from within the plant network
47. r of nodes max 99 Current draw 5 1V DC 1100 mA 1300 mA 970 mA Current draw 24V DC 3mA 17 mA Power dissipation 5 6W 67W 5 1W Thermal dissipation 19 1 BTU Hr 22 9 BTU hr 17 4 BTU hr Rockwell Automation Publication 1756 TD003H EN E January 2015 13 1756 ControlLogix Communication Modules Specifications Table 10 Technical Specifications 1756 ControlNet Modules Continued Attribute 1756 CN2 C 1756 CN2R C 1756 CN2RK C 1756 CNB E 1756 CNBR E Isolation voltage Standard 30V continuous basic insulation type ControlNet network to backplane Redundant 30V continuous basic insulation type ControlNet A B to backplane and ControlNet A to ControlNet B USB to backplane and USB to ControlNet No isolation between NAP or USB and backplane Type tested at 500V AC for 60 s Weight approx 0 26 kg 0 57 Ib 0 293 kg 0 64 Ib 0 26 kg 0 57 Ib 0 293 kg 0 64 Ib Slot width 1 Module location Chassis based any slot Chassis 1756 M 1756 A7 1756 A10 1756 A13 1756 A17 Power supply standard 1756 PA72 C 1756 PA75 B 1756 PB72 C 1756 PB75 B 1756 PC75 B 1756 PH75 B Power supply redundant 1756 PA75R 1756 PB75R 1756 PSCA2 ControlNet port 1 ControlNet BNC 2 ControlNet BNC 1 ControlNet BNC 2 ControlNet BNC ControlNet cable 1786 RG6 quad shield RG6 coaxial cable USB port USB 1 1 full speed 12 Mbps NAP port 1 NAP RJ45 1 NAP RJ45
48. rom 80 2000 MHz 10V m with 200 Hz 5096 Pulse 100 AM 900 MHz 10V m with 200 Hz 5096 Pulse 100 AM 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 2 kV at 5 kHz on DHRIO ports Surge transient immunity IEC 61000 4 5 2 kV line earth CM on DHRIO ports Conducted RF immunity IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz 28 Rockwell Automation Publication 1756 TD003H EN E January 2015 1756 ControlLogix Communication Modules Specifications Table 24 Certifications 1756 DH and Remote 1 0 XT Module Certification 1756 DHRIOXT c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File 65584 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CE European Union 2004 108 IEC EMC Directive compliant with the following e EN 61326 1 Meas Control Lab Industrial Requirements e EN61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions e EN61131 2 Programmable Controllers Clause 8 Zone A amp B RCM Australian Radiocommunications Act compliant with EN 61000 6 4 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with the following EN 60079 15 Potentially Explosive Atmospheres Protection n EN 60079 0 General Requirements Il 3 G Ex nA IIC T4 Gc X KC Korean Registration of Br
49. ry information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines Rockwell Automation Publication 1756 TD003H EN E January 2015 1756 ControlLogix Communication Modules Specifications Table 8 Environmental Specifications 1756 EtherNet IP XT Module Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 EN2TXT D 1756 EN2TRXT C 25 70 C 13 158 F Temperature surrounding air max 70 C 158 F Temperature storage IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged damp heat 5 95 noncondensing Vibration 29 10 500 Hz IEC 60068 2 6 Test Fc Operating Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8k V air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 50 Pulse 100 AM 900 MHz 10V m with 2
50. th Article 58 2 of Radio Waves Act Clause 3 1 When product is marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details Accessories SynchLink Network Description 1403 CFxxx Rockwell Automation fiber optic cable assembly HCP M0200T VO1RK Lucent Technologies 200 um simplex cable 34 Rockwell Automation Publication 1756 TD003H EN E January 2015 1756 ControlLogix Communication Modules Specifications Notes Rockwell Automation Publication 1756 TD003H EN E January 2015 35 Important User Information Read this document and the documents listed in the additional resources section about installation configuration and operation of this equipment before you install configure operate or maintain this product Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes laws and standards Activities including installation adjustments putting into service use assembly disassembly and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice If this equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting
51. ype rating None open style 1 Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Rockwell Automation Publication 1756 TD003H EN E January 2015 27 1756 ControlLogix Communication Modules Specifications Table 23 Environmental Specifications 1756 DH and Remote 1 0 XT Module Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 DHRIOXT 25 70 C 13 158 F Temperature surrounding air max 70 C 158 F Temperature storage IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 2g 10 500Hz Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM f
Download Pdf Manuals
Related Search
Related Contents
Traitement Purifiant Habitacle Parfum « AIR FRAIS » ou « FLEUR User's Guide for the amsmath Package (Version 2.0) American 取扱説明書 - 株式会社フキ COBALT Migration Utility Farm & Ranch FR1245-2 Instructions / Assembly RéGIONS - Association François Aupetit ダウンロードはこちら Central Pneumatic Air Compressor 93785 Air Compressor User Manual Sony LCS-TWAB Copyright © All rights reserved.