        JSI-G2.5K PVGrid-Connected Inverter User Manual
         Contents
1.     Fig 2 shows the main circuit of JSI G2 5K  a transformerless grid connected  inverter  The DC DC boost stage increased the input DC voltage  the IGBT  full bridge converts the DC power to AC voltage and current  The AC power is  then fed to the grid after being processed by a filter     JSI G1 5K JSI G2 5K    DC  DC Full Brid       Fig 2 circuit diagram of JSI G2 5K    4 2 Features of JSI G2 5K    l     The following are the Technical features of JSI G2 5K     The fifth generation Intelligent Power Module from Mitsubishi improves    the system efficiency     2     MPPT auto optimizing technique makes the most of the PV generation    capacity     De    Simple parameters settings      Multi communication interface      High reliability due to complete protection functions     Wide DC input voltage range  up to 450V DC      NYDN       Multilingual LCD display     4 3 The Wiring Interface    RS485 GRID    Ground  RS485A    RS485B Grid N Grid L    Fig 3 The wiring interface of JSI G2 5K    Table4 1 Terminal descriptions    Description    RS485 A  pin 1  RS485 B  pin 3    DC   DC   input terminal    DC   DC   input terminal    Connected to the grid   Red wire connected to the GRID L  pin 1  Black wire connected to the GRID N  pin3    Yellow green wire connected to the ground       5 Operation Description    Sa    Operation Modes    This chapter illustrates the operation modes of the JSI G2 5K   Stand by mode    Standby mode is entered due to fault or insufficient input power  a
2.    JALP Q WER  JSI G2 5K PV Grid Connected Inverter       User Manual    JALPOWER Corporation  Ltd     Table of contents       yd OOS  Epl AnA ON ppccinnnncattcwnetyanattanseaueendogaunsbaneduidwus iene E 1  X oduUCio meaa a a S OS 2  2  Grd  Connected PV Inverter Su m unu NE awa apapuna a ahass 2   2 2 HOW tO Use MiS Manual uu u nasi u qa EEEO 2   Js WaAlely INSU IICIIONS eorn a EE TEE ue nai ARS 3  A General  Descriptions Ol  S1 G25K  siesena Ea 4  4 L Circuit  Descriptio eessen na E A EERE wadiaeeemaatens 4   AD  Features Ol JISE K noen n NE N 4   AD Vine  Winnie Inter xu a maa ukana ku skua aoe eee wees 5   5 COBOrOali6ONDODESCIIpDI IIS u nisen aa a eed ceva da ykappawpupakonssa hapik u maq ae 6  Sule OPEO MOIES uuu pa a a a 6   J2 COMMISSIONE L L u uu E E EOE 6   39 REdured Grid Condi ons srera A NN 7   6  Monitore qrd D Xisplagysuu uuuuy a aku u E LE 8  Gal     Basic  COMIMUNICAIONS sore u u uuu Xu ukpa st sassa amas 8   O PC AV tse ri csesncrs ees a E eeu a Os 9  RCDD p  esac cetse ecarceh ees unuta oe suspa  10   OTe NAS lla Onu kiya uui aasan aude nee pamiceaue 22  7 1 Checking for Shipping Damage                                               22   E2 Mechanical Mounting uuu E Qapaq bapak nai aie Steel 23  7 2 1 Safety Mounting Instructions                                               23   7 2 2 Device Dimensions and Wei  ht                                         24   Teano MOUNUNS JREGUIFEMICINS yincn cova u au pi kim ssuaa z nu kuquta yasa 25   ko Electrical CONN 
3.    The ambient temperature should remain from    20  C to 40  C    Itis important to have air freely circulating around the inverter  therefore keep  the area within 30 centimeters of the inverter free from obstacles    The inverter should be mounted in a well ventilated area     Avoid mounting the inverter in a dusty area    22    7 2 Mechanical Mounting  7 2 1 Safety Mounting Instructions    As with any electrical system  touching live components can be hazardous  to life and limb  This device contains DC voltage of up to 450V and the grid  voltage up to 260 V     WARNING     Only a qualified person can work on this equipment     This work is only permissible if the AC and DC power    supplies are safely disconnected from the JSI G2 5K     WARNING     Before any maintenance  always wait for approx 10  minutes so that the capacitors in the JSI G2 5K can    discharge  Only then may the cover be opened        23    7 2 2 Device Dimensions and Weight    The external dimensions and weight of the JSI G2 5K is in fig 10        11 3KG  Fig 10 Dimensions and weight of JSI G2 5K    NOTICE     The ambient temperature should be within  20  C and     40  C     Caution     Some parts of the JSI G2 5K can reach temperature of  over 80  C  Keep a suitable distance from flammable    materials     WARNING     Never install the JSI G2 5K in areas that contain    explosive atmospheres  battery rooms  fuel storage    rooms etc         24    7 2 3 Mounting Requirements      Mounting Place  The J
4.   hotline will be happy to assist you  Please keep the following data when    contacting    JINLPOWER    Address       Jalpower Corporation Ltd      USA  107 East Meda Ave  Glendora  CA9891741 USA  Tel   1 626 9h 34 2054  Email sales malpower corm    Taiwan  2E  No 4  Aly  1  Ln  225  Sec  1  Neihu Rd  Neihu Dist   Taipei City 114  Taiwan    ROC   Tel   886 2 265937 37    Email  Supportenjalpower com  China    Room 2504  No 18  Shun j Road  Shanghai  200083 Ching  Tel  8B 21 54259997    Ernail sales mlalpower corm    34    
5.  KEEEEE   l L ESC       E today 000 0KWH  P ac 0000W               ENTER P       2006 11 22 11 44  State             State cha  ged after     stop    operation    16     gt  Explanation   This command is helpful when users want to stop the operation of the    inverter  The state shown in the default display menu will change after stop    operation       The general parameters selecting menu    Select number by   ENTER  gt   Change value by   ESC             _  ENTER               ENTER  gt             L ESC          General parameters  selecting menu        gt  Explanation    Users must input the password before setting parameters  The default    password is 1111   This screen contains    Sys param     gt     Run param           Pro param   and           Com param           Sys param    contains basic running parameters of the Inverter      Run param    contains nothing        Pro param       contains the adjustable system protection parameters      Com param    contains basic communication parameters of the    inverter     17      The specific parameters selecting menu             ENTER  gt         ESC                ESC       Specific parameters  selecting menu     gt  Explanation   The adjustable parameters of    Sys param    Includes display  language Language  gt  display time Time   generated energy display  value Power adj and load default task load default  The firmware version  willonly be helpful for the maintenance personnel and useless to users       The display l
6. 1  nu  ur GODT 6 314       GOTJo 9013 nuow Avjdsip ou  E      Start up menu         Explanation    This screen displays the type of the inverter  Note that this screen will  only appear once after start  After about 7 seconds of this screen  the LCD  display will automatically change to the default display menu        The default display menu      ESC  Y       Default  display menu      Explanation   This menu includes 2 separate screens  The first screen includes          parameters of    E today    and    P ac       E today    indicates the daily output  energy generated by JSI G2 5K in the unit of KWH     P ac    indicates the real time  output power of JSI G2 5K in the unit of KW    The second screen includes parameters of date time and    state      Date Time display the current time and can be adjusted  The    State    shows    the inverter    s working state according to table 6 2     Table 6 2 State of the inverter    The inverter in normal  function  operation    Stand by The inverter in stand by state  The inverter stops working  Fault of LCD inverter communication channel      Note  To quickly access the system running parameters  press        JESC V  when in any state of the above 2 screens  as shown in the    figure below     12    Shortly press the    ESC V    key   quickly enter the real time parameters    display menu       Shortly  press the  ESC V key  to move to  next screens       Default    display menu Real time    parameters menu    The parameters displ
7. CCION 5s uyu u eee ea 5aySSaus ans 26  7 3 1 Electrical Connection Requiements                                   26   Taek  WAKES CONN CCUOMs idence dnoieaestdhcessead NA 2   7 4 Communication Installation esseere r n esa 29   Bo par aI CC LOS a a nuance amuses uate race    30   Ti Dede St P UMS AN VEEL uy yu A E 30   72522  Close  Ihe  IBvOr  GE spa aaa kiuqq a aayopuupaiahu qun A 30   S lechnical Dal uu uyu asia yayta khisuy AT ansa OAA 31  S21 pieeinicalSpeeiti aligpbSu uu y u S asuy awa a au nu rete 31   6 2  Mechanical Spec liCations  sera teas a 31   Bo CAME CS Yu u otis ata Speers ea sa Con re tae ars en ene 32   SR 6   9  5  I  C cuyas sn umma Ep nakay apina sa aasma ee a en 33  9 1  Exclusion OF Lia DUI serein pnan a EEEE ESE sateen 33    ED  COMAC US eun ae TE T E T AE E 34    1  Symbols Explanation    Please note the following explanation of the symbols used in this manual     WARNING     This indicates a condition that can cause fatal injury or    death     NOTICE     This indicates a condition that will help to achieve    optimal system operation     Caution     This indicates a condition that may cause minor or    moderate injury        2 Introduction    Thank you for buying the JSI G2 5K from the JALPOWER  We hope that  the device will meet with your satisfaction when you use it with your PV plant  system     2 1 Grid Connected PV inverter    A JSI G2 5K grid connected PV system is shown in Fig l  JSI G2 5K  transforms the direct current generated by the PV arr
8. Operation time H    CO2 total Reduced CO2 weight  2006 11 22 11 44 The current date time on          Fault record    menu       Fault occurred Fault type and Fault record    time parameter number            ENTER  gt     ESC  Y    Ay    ESC       I    Parameters display   amp  set menu     gt  Explanation    The    Fault record    menu displays the latest 20 fault records  which Includes   fault type see table 6 5    fault occurred time   fault parameter and fault   record number within 20        Note that the fault record number is created in the order of fault occurred  time  the latest fault record number is always 01  the oldest fault record    number is always 20 suppose there is at least 20 fault records   etc   Table6 5 Fault type with simple explanation    Vac low      The start and stop menu      ESC         ENTER  gt   i  i    Parameters display   ESC      amp  set menu        gt  Explanation  The    Start Stop    menu can control the start and stop state of the    inverter     15      Start process through LCD  iz      RSC       E today 000 0KWH  P ac OOOOW               2006 11 22 11 44  State                State changed after     start    operation     gt  Explanation    This command is needed to restart the system after a LCD stop  operation by user  The state shown in the default display menu will change  after start operation    The state of the inverter won t change if the inverter is already running  when perform this command       Stop process through LCD 
9. SI G2 5K has a relatively high weight of 11 3kg Please keep this in    mind when selecting the place where and how to mount the JSI G2 5K   NOTICE     The ambient temperature should be within 20  C and   40  C The JSI G2 5K should be installed in a place where it    is not exposed to direct sunlight     WARNING     Some parts of the JSI G2 5K can reach temperature over    80  C  Keep a suitable distance to flammable materials     WARNING     Never install the JSI G2 5K in areas that likely contain    explosive atmospheres  battery rooms  fuel storage rooms    etc       NOTICE   Since the AC and DC connections are wired to the breakers  and or junction box only  there 1s no need to open the inverter    enclosure during installation        25    7 3 Electrical Connection  7 3 1 Electrical Connection Requirements      Grid 230V AC   The JSI G2 5K is designed for 230V grid  single phase  The voltage should  be within 180V to 260V and the frequency should be the frequency should be  47 51 5 57 61 5Hz          PV array limit         ground  The inverter must be grounded in compliance with local safety codes    using appropriately sized protective conductors     Notice     Ic All electrical installations must comply with all local    and national electrical codes     WARNING  Make sure that the DC input voltage    never exceeds 450V Higher input voltages will damage    the JSI G2 5K        26    7 3 2 Wires connection  The complete wiring for a JSI G2 5K is shown schematically in th
10. TX  RX     RS485 232 Converter                JSI G2 5K PC RS232 Port    Fig 13 Communication network       Fig 14 RS485 RS232 converter    29    7 5 Start and close  7 5 1 Start the Inverter    To turn on the inverter  please follow the steps below    1  Switch on the DC side circuit breaker   2  Switch on the AC side breaker   3  The inverter willto check whether that voltage  impedance and frequency  parameters are within operating range    4  If the parameters check is correct  then the LCD will display the normal  working screen    5  Then the inverter willexport to the grid and the green Power LED    will continuously lit  provided there is enough PV power    7 5 2 Close the Inverter    1  If users want to shut down the inverter  please refer to stop command in  the LCD menu in chapter 6    2  If users want to shut down the inverter immediately  first switch off the AC  side breaker then switch off the DC side breaker  incorrect switch off order    may cause danger to the personnel and damage to the inverter     30      Technical Data    8 1 Electrical Specifications    E Input Data  Max  PV Power    Max  Number of Input Strings    Max  Input Current    MPP Voltage Range    Maximum DC Voltage    E Output Data    Nominal AC output power  AC Voltage Range   AC Frequency Range   Power Factor    Peak Efficiency    European Efficiency    Internal consumption during stand by    THD of Output Current       8 2 Mechanical Specifications    Dimensions W x H x D     Weight  Ingre
11. Y2  ENTER    Table6 1 LED descriptions    RUN LED JSI G2 5K is working  JSI G2 5K is not working    FAULT LED A fault has occurred  No fault has occurred       6 3 LCD Display    The display board is equipped with two line LCD  Users can get basic  information from the LCD display         GRID CONNECTED INVERTER    O O O  RUN FAULT ESC W ENTERA    Fig 8 LCD display and key board       E Key functions explanation   There are 2 keys In the LCD board  ESC  Y key and ENTER  P key    ESC  Y key  when you press the    ESC  WY    key less than 2 seconds  this key  performs the     W    function  which is used to move the arrow up and down in  the screen or increase decrease number   denoted by       ESC  Y       The    ESC V    key will perform    ESC    function if it is pressed longer than 2  seconds  which is used as Return finish function   denoted by         ESC  Y         ENTER        key  when you press the    ENTER        key less than 2 seconds   this key performs        function  which is used to move the arrow left or right  in the screen   denoted by     ENTER  P       The    ENTER          key will perform    ENTER    function if it is pressed longer  than 2 seconds  which is used to select menu item and confirm changes    denoted by     ENTER     gt         E Activation of the background illumination   The background illumination is activated by slightly press the any key    The background illumination is automatically deactivated after 1 minute to    Save power     90
12. anguage adjustment menu  Change number by   ESC V      4 ENTER  gt                    4 ESC          v ESC Y     ENTER   gt       4 ENTER  gt     Display language has  changed after setting     gt  Explanation  Users can set the LCD display language in this screen  there are 2    languages can be selected  CH represents Chinese  EN represents English       The display time adjustment menu    Select number by   ENTER  gt   Change number by   ESC                ESC           ESC        ENTER      Display time has changed    after setting id  ENTER   gt         gt  Explanation  The date format is year month date  the time format is  hour minute second  Note that the hour display is in 24 hours type       The firmware version menu  not open to users     4 4 ENLEK  P           ESC       The firmware version can  not be adjusted by users     gt  Explanation   This firmware version display screen is only provided to maintenance  personnel and cannot be adjusted by users     Note  the first two digits    20    of year  like 2006  cannot be changed and  the second    45   will not be displayed in the menu       The displayed generated energy adjustment menu    Select number by   ENTER  gt   Change value by   ESC          e        ESC            Adjustable range     ESC    Vy ENTER y      999 to  999      ENTER  gt           After   adjustment  Before   adiustment       E total             19     gt  Explanation   This generated power adjustment screen is useful in case the total  powe
13. ay  set menu       Parameters display  Default  amp  set menu    display menu      Explanation     This menu contains Running   information    Run inform     fault  record    Fault record     start stop control of the inverter    Start Stop      parameters setting    Set param     Users can press     ESC V   key to make the  arrow pointed to selected menu name      Note that users can always quit to the upper level menu by press       PESC Y    key     13       Current inform    menu        Run inform    menu    Real time  parameters menu                 ENTER  gt     ENTER   gt   A     ESC           ESC               General  Parameters men    History parameters  menu         Parameters display   amp  set menu         ESC           ENTER  gt     Explanation     The    Run inform    menu contains the    Total inform       data are explained in the table 6 3 and table 6 4     Table6 3 Electrical real time data  Current inform       bgrid     Output AC current A  V    W  Energy generated today KWH  Energy generated this month    The whole generated Energy       A   H  V _  W  KWH   K    14      ESC  Y      ESC       and    The    Total inform    includes history logged data  such as  totally generated energy    E total     monthly generated  energy    E month     total running hour    h total    and reduced CO2 weight        CO2 total     The    Current inform    includes real time system data  All the    Table6 4  Non electrical real time data  Total inform     Total hours of 
14. ay into stable alternating    current and output to the utility grid        PV Arra  _ Utility Grid    JSI G2 5K    Fig l Grid connected Inverter for PV power application    2 2 How to use this manual    The purpose of this manual is to provide users with detailed product  information and instructions for the use of the JSI G2 5K grid tied PV    inverter     3  Safety Instructions      Please read the instructions in this manual carefully before  installing and operating the JSI G2 5K       Always disconnect the inverter from the grid first       ALL CONNECTIONS SHOULD ONLY BEUNDERTAKEN BY  QUALIFIED PERSONNEL        Allelectrical installations shall be done in accordance with  local and national electrical codes       Please contact your authorized system installer if any  maintenance is required       Connection of the JSI G2 5K to the utility grid must be done  only after receiving prior approval from the utility company  and performed by qualified personnel       Completely disconnect the output from the PV array before  connecting to the JSI G2 5K or use other methods to prevent  electrical shock hazards  This is important because if the PV  array keeps connecting during the connection process may  produce dangerous voltages     WARNING     Make sure that the DC input voltage never exceeds    450V Higher input voltages will damage the JSI G2 5K    and willlead to the loss of any and all warranty rights        4 General Descriptions of JSI G2 5K    4 1 Circuit Description
15. e Fig 11     Breaker Rating     gt  260V 20A  JSI G2 5K terminals 2 poles AC  brekaer           L    Grid L  red wire         gt       s 1    rid N  black wire   B  gt     Ground   yellow green wire    Grid        Ground    Ne This 2 poles DC breaker  PV array rating  gt 450V 20A    Fig  11 Simplified electrical connection diagram         Ground wire     yellow green wire    lt        Single phase grid L   red wire     Single phase grid N   black wire     Fig  12 attached wires for JSI G2 5K    27    Caution     The wiring of the inverter   s AC and DC cables must only be    done with the DC and AC circuit breakers are in the off state        Please follow the Fig 11 to connect the wires     Connect the wires of the DC cable as follows      lt  JSI G2 5K    DC      wire to the PV array     A Jsr g2sg     DC       wire to the PV array         Note  there are 2 input ports of PV array  we recommend users at least    connect 2 channels with each channel maximum current no more than 10A and  total current no more than 20A      Connect the wires of the AC cable as follows     lt   JSI G2 5K   s    L    wire to the grid   P        lt   JSI G2 5K   s    N    wire to the grid   N        lt   JSI G2 5K    GND    wire to the ground     Caution     Make sure tall the wires are firmly tightened        28    7 4 Communication Installation    Fig 13 shows the communication installation of the JSI G2 5K with the    PC by RS485 serial communication port            RS485A  gt     RS485B s    
16. frequency must be 47 51 5Hz 57 61 5Hz  check table 5 1 for  the adjustable frequency range  Once the grid frequency exceeds this range    the JSI G2 5K is disconnected from the grid with 0 2s     Table5 1 protection parameters range    Simple explanation Adjustable range Default value  maximum AC voltage 240V 260V 250V  minimum AC voltage 180V 200V 180V    maximum AC frequency 50 5Hz 51 5Hz    Fgrid min minimum AC frequency 47 0Hz 49 5Hz  57 0Hz 59 5Hz       6 Monitoring and Display    6 1 Basic Communications    The inverter normally operates automatically  without user  interaction and any maintenance    To enable our customers to gain a thorough comprehension about  the operation of the inverter  we have provided various data collection  approaches to monitor system data    Data logger    Inverter       Data Logger       Fig 4 data logger collects data through RS485 bus  PC    Inverter           RS485 RS232    Fig 5 PC collects data through RS485 bus    Data logger  PC    Inverter    Daneel RS485 RS232 SS  Converter    Fig 6 data logger  amp pc collects data through RS485 bus       6 2 LED Indicators    The inverter operates automatically without the need for user interaction or  maintenance  There are two LEDs and two keys at the panel of the inverter  From    the leds we can get the basic work state of the JSI G2 5K         GRID CONNECTED INVERTER    O O O  RUN FAULT ESC W ENTER     Fig 7 LED amp KEY and LCD Display       Green LED  RUN  Red LED  FAULT  KEY1  ESC V    KE
17. iple inverters  The    baud rate  parameter decides the  baud rate between the inverter and upper machine  Four alternative values    can be selected  1200  2400  4800 and 9600 bps     21    7 Installation    This chapter gives installation instructions for JSI G2 5K     7 1 Checking for Shipping Damage    The JSI G2 5K inverters are thoroughly checked and tested rigorously  before they are shipped  Even though they are delivered in a rugged  heavy  cardboard box  the inverters can be damaged in shipping which typically is the  shipping company   s fault  So you should check the inverter before installation    Please inspect the inverter thoroughly after it is delivered  If any damage is  seen please immediately notify the shipping company  If there is any question  about potential shipping damage  contact JALPOWER Power Supply  A photo  of the damage may be helpful    Do not accept unit if visibly damaged or note visible damage when signing  shipping company receipt  Please report the damage immediately to the  shipping company  Do not remove the unit from packaging    7 2 Basic Installation Requirements   The IP level of JSI G2 5K is IP41  so it can only be installed indoors    A list of these requirements is shown below    Itis advised not to install the inverter in living quarters  since the inverter may  produce some operating noise   lt  40 dB     Avoid installing the inverter in a location subject to vibrations    The LED and display should always be legible for users 
18. r  displayed by LCD has difference with reading value from the external power  measuring device  like an electrical meter    The adjustable range is from  999  999 kWh     The load default menu      ENTER  gt  L ENLEK   gt         ENTER  gt        All the internal  logged data  Are cleared after     load default        gt  Explanation  Users can clear the logged data by using    Load fault     After inputting the    correct password  1111   and confirm this command    J    ENTER  P     After  the appearing of    Set Complete    screen  all the logged parameters are  cleared       Note that the load default operation is irreversible     20      The protection parameters adjustment menu    Select number by    ENTER   gt   Change value by    ESC            ENTER  gt         gt  Explanation  Users can set the maximum allowable grid voltage  gt the minimum allowable    grid voltage  the maximum allowable grid frequency  gt   and the minimum    allowable grid frequency  please check table 5 1     Select number by   ENTER  gt   Change value by   ESC     Address range  0 255  Baud rate value 1200 2400 4800 9600              y ENIEK  P         J ESC           ESC    Y y ENTER            ENTER  gt            gt  Explanation    2 communication parameters can be altered in this menu  the address  and the baud rate    The    Address    parameter is useful to separate the current inverter form  other inverters to avoid address violation when an upper machine is utilized  to monitoring mult
19. ss Class    Operating Temperature    2    150 380V  450V    2500W    180     260 V AC  47 51 5 57 61 5Hz   gt 0 99 at nominal power       288 x 460x 126 mm  11 3 kg   IP41  indoor       20C   40C   l       8 3 Features    RS485 Ethernet Optional  GPRS Optional     EMC EN61000 6 2  EN61000 6 4       32    9  Appendix    9 1 Exclusion of Liability    The content of these documents 1s periodically checked and revised  when  necessary  please call us or check our website www JALPOWER com for the  information  However discrepancies cannot be excluded  No guarantee is  made for the completeness of these documents  Please contact our company  or distributors to get the latest version    Guarantee or liability claims for damages of any kind are excluded if they are  caused by one or more of the following     Improper or inappropriate use of the product    Operating the product in an unintended environment    Operating the product when ignoring relevant safety regulations in the  deployment location    gnoring safety warnings and instructions contained in all documents relevant  to the product    Operating the product under incorrect safety or protection conditions   Altering the product or supplied software without authority    The product malfunctions due to operating attached or neighboring devices  beyond allowed limit values     In case of unforeseen calamity or force majeure     33    9 2 Contact Us    If you have any questions about or technical problems with the JSI G2 5K  our
20. t  stand by mode the inverter is ready to switch into Grid mode provided all the  specified conditions are met  otherwise the inverter will keeps at stand by  mode    Connecting to the grid    After all system tests have been performed and all connection  conditions are met  the inverter switches from stand by mode to  connecting mode    In this mode the inverter delivers power to the grid  This mode is the  normal operational mode    Fault   When faults occur  the inverter willswitch off the AC side relay and go  into fault or stop mode to protect the PV power system  when the fault is  solved  the inverter will wait for 300 seconds and test whether all the grid  connection conditions are met again  if everything Is satisfied  the    inverter will start to generate power     Commissioning    The inverter works as follows when connecting to the grid    The PV modules are activated and start producing power    The JSI G2 5K inverter starts charging the DC bus    If the DC input voltage exceeds 170 V  the inverter is ready for grid connection   The inverter checks that grid conditions are OK     The JSI G2 5K starts feeding power to the grid     5 3 Required Grid Conditions    E GRID Conditions necessary for JSI G2 5K operation     Grid voltage  The grid voltage must be within a range of 180V 260V  gt  check table 5 1  for the adjustable voltage range  Once the grid voltage exceeds this range the  JSI G2 5K is disconnected from the grid within 0 2s   e Grid frequency  The grid 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
AP-8122 Access Point Installation Guide  RUGGEDCOM ROS  Samsung SPF-72H Εγχειρίδιο χρήσης  EM4591 Répéteur universel Wi-Fi avec WPS    EDEN : INCIDENCE ET PRÉVALENCE DES AFFECTIONS  Comfort Plus M20 - HANSGROHE:www.hansgrohe.be  Avocent ECS17KMM8  aseptol® excellium  MANUAL LECTOR ZL100FP    Copyright © All rights reserved. 