Home
        Data sheet DB EN IL MOD BK DI8 DO4-PAC
         Contents
1.    8    IL MOD BK DI8 DO4 PAC    Notes on using the terminal in potentially explosive areas       WARNING  Explosion hazard    Before startup  ensure that the following points  and instructions have been observed     Approval according to EC directive 94 9      II 3G Ex nA IIC T4 X    Installation notes    1   2     This Inline terminal can be installed in zone 2     The Inline terminal must only be installed  operated   and maintained by qualified personnel     Please follow the installation instructions given in the  IL SYS INST UM E user manual and the package slip     When installing and operating the device  the  applicable safety directives  including national safety  directives   accident prevention regulations  as well as  general technical regulations  must be observed     Please refer to the corresponding documentation  user  manual  data sheet  package slip  and the certificates   EC type examination and other approvals  if  applicable  for safety related data     It is not permitted to access the circuits inside the Inline  terminal  Do not repair the Inline terminal by yourself but  replace it with a terminal of the same type  Repairs may  only be carried out by the manufacturer    IP20  EN 60529  protection of the device is provided for  a clean and dry environment    Do not subject the Inline terminal to mechanical strain  and or thermal loads  which exceed the limits specified  in the product documentation    The Inline terminal has not been designed for use i
2.   Factory   plug and play mode configuration    P amp P   Position 3  P amp P ON  default   Position 4  P amp P OFF    Position 0  1200   Position 1  2400   Position 2  4800   Position 3  9600   Position 4  19200  default   Position 5  38400   Position 6  57600   Position 7  115200    Position 0  7 bits   Position 1  8 bits  default   Position 0  None   Position 1  Even  default   Position 2  Odd    Position 14  stop bits  Position 0  1 bit  default   Position 1  2 bits   Position 15  watchdog    Position 0  ON  default   Position 1  OFF    Position 11  baud rate     Position 12  data bits     Position 13  parity     By default upon delivery as well as after a  reset to factory configuration  the parameters  labeled  default  in the table are set        In the event of a power on reset  voltage reset   only the set  operating parameter is read in and stored  To set several  parameters  this procedure must be repeated for each  individual parameter     While reading in a parameter  the watchdog LED flashes  quickly  2 Hz   If the parameter has been accepted  the  watchdog LED flashes slowly  0 5 Hz   If the parameter is  invalid  the watchdog LED flashes very quickly  5 Hz      Example  The following is to be set   Plug and play OFF   and  ASCII      e Set  Plug and play OFF  first    e Execute a voltage reset    e After the parameter has been accepted  set  ASCII    e Execute a voltage reset again     PHOENIX CONTACT 12    IL MOD BK DI8 DO4 PAC    10 3 Parameterizing the IL M
3.   Firmware services and error messages  user manual     Hardware and firmware manual for the FL IL 24 BK FL IL 24 BK PAC  Ethernet Inline bus terminal  user manual    7258 en_03    Type  SUBCON PLUS MODBUS IL BK  IL BKDIO PLSET    Type  CLIPFIX 35 5    E AL NS 35    IL CP    ZB 6    see CLIPLINE catalog  ZB 12     see CLIPLINE catalog    NS 35 7 5 PERF  NS 35 7 5 UNPERF    Type   AH IL BK IO LIST   IL SYS INST UME  AH EN IL EX ZONE 2    IBS SYS PCP G4 UME  IBS SYS FW G4 UME  FL IL 24 BK PAC UME    IL MOD BK DI8 DO4 PAC    Order No  Pcs  Pkt   2878696 1  Order No  Pcs  Pkt   Order No  Pcs  Pkt   2310808 1  2778599 1  Order No  Pcs  Pkt   3022276 50  1201662 10  2878696 100  0801733 1  0801681 1  Order No  Pcs  Pkt   9015358 1  2698737 1  7217 1  2745169 1  2745185 1  9014205 1   PHOENIX CONTACT    3    3 Technical data    General data   Housing dimensions  width x height x depth   Weight   Ambient temperatures  operation    Ambient temperature  storage    Humidity  operation storage transport    Air pressure  operation storage transport   Degree of protection   Protection class   Response time  aligned I Os     Connection data  Designation   Connection method   Conductor cross section  Conductor cross section  AWG     Interface  Inline local bus  Connection method  Transmission speed    Interface  Modbus  Connection method    Number of positions  Transmission speed    System data of the bus coupler  Number of supported devices   Number of connectable local bus devices  Number 
4.  2 A flowing through potential jumper U  is not  exceeded     PHOENIX CONTACT 11    9 Startup    Default upon delivery default settings    By default upon delivery  the following functions and  features are available     Configuration of the RS 485 interface      Transmission mode RTU     Baud rate 19200 bps    Data bits 8     Parity Even     Stop bits 1   Modbus telegram watchdog 10000 ms   connection monitoring    Plug and play mode Enabled    Fault response mode Reset fault mode    10 Hardware configuration    10 1 Address setting    The address is set using two rotary encoding switches  The  left switch is used to set the position in tens and the right  switch is used to set the position in units  Addresses can be  set between 1 and 99  The figure shows the address setting   74         Figure 6 ADDRESS rotary encoding switches    A valid address is applied on power up  It cannot be  modified during operation   10 2 Parameterization via rotary encoding switches    In addition to the address  various operating parameters can  also be set via these rotary encoding switches  The  operating parameters are only read in following a power on    7258_en_03    IL MOD BK DI8 DO4 PAC    reset   Parameter setting  mode is assumed when the  address switch for tens is set to a position that is not  assigned to an address  i e   2 10     Tens switch  x10  Units switch  x1     Position 10 Position 0  RTU  default     Transmission mode  Position 1  ASCII   factory configuration  Position 2
5.  ETH BK                                     MODBUS RTU ASCII             ADDRESS  o o  14 2 say   HWE  OE   XS N  10 16 a   8 98    x10 x1                                                                                                       Oo          Ol             Ol                                                                                                                                                                                     JE  o0 o0 og                            Ol                     18888888  I A a02                Modbus register location of process data    DATA IN       Address 0000 mra    Address 0001 C rra  Address 0002 r a   aoned Address 0192   Al Byte oriented Address 0193 C o a  Address 0194   Address 0195 tema    lt      DI _ Bit oriented    Address 0196  Address 0197       DATA OUT    Address 0384   ee Address 0385   DO Bitoriented address 0386  Byte oriented Address 0576   a   Address 0577  Address 0578   Address 0579   Address 0580   Address 0581   Address 0582       7275C015    Figure 10 Example for the location of process data in static tables    7258 en_03 PHOENIX CONTACT 23    IL MOD BK DI8 DO4 PAC    Dynamic table   For dynamic tables  there is no fixed assignment of the register areas  Depending on the structure of the Inline station  the  following general order of the process data applies        DATA IN  bit oriented        DATA IN  byte oriented         DATA OUT  bit oriented        DATA OUT  byte oriented     Modbus register tab
6.  can be acknowledged by setting  bit 1 in the command word  If the Net Fail has been  acknowledged successfully  bit 1 is reset to  zero     If a peripheral fault occurred  it can be acknowledged by  setting bit 2 in the command word  If the peripheral fault has  been acknowledged successfully  bit 2 is reset to 0      15  14  13  12 11   10  9 8 7 6 5 4 3 2  4 0    Reserved bits  Clear peripheral fault        Clear Net Fail    Plug and play    61560030    Figure 12 Command word    7258_en_03    Status register  status word    7996     Only the two least significant bits have a function  If bit 0     0   this means that an error  e g   a bus error  has occurred   If bit O    1   no error has occurred  Bit 1 indicates whether a  Net Fail occurred  bit 1   1  or not    bit 1   0     This results in the following values for the status word        0  An error occurred  e g   bus error        1  No error occurred       2  A Net Fail occurred    15  14  13 12 11  10  9  8  7 6  5  4 3  2  1 0        Figure 13 Status word    PHOENIX CONTACT 26    Local bus diagnostic status register  7997     Each bit in the local bus diagnostic status register is  assigned a state of the local bus master on the bus coupler   The states in the error bits  USER  PF  BUS  CTRL  are  described in greater detail using the diagnostic parameter  register  Whenever one of the error bits described above is  set  the diagnostic parameter register is rewritten   Otherwise  the diagnostic parameter register ha
7.  please visit www phoenixcontact net download        7258 en_03    IL MOD BK DI8 DO4 PAC    Criterion B   6 kV contact discharge  8 kV air discharge  Criterion A   Field strength  10 V m  Criterion A   All interfaces  1 kV  Criterion B   All interfaces  2 kV  Criterion B    DC supply lines   0 5 kV 1 kV  symmetrical asymmetrical   Fieldbus cable shielding 1 kV    Criterion A  Test voltage 10 V    Class A    PHOENIX CONTACT 6    IL MOD BK DI8 DO4 PAC    4 Basic circuit diagram    Modbus  interface    7258C004       Figure 1 Basic circuit diagram for the bus coupler    The gray areas in the basic circuit diagram represent the electrically  isolated areas     Protocol chip A  Modbus interface  B  Logic    Key   acy Optocoupler C  I O  m  m    Microprocessor    Power supply unit with electrical  isolation   RS 485 interface driver   with electrical isolation    PNP transistor    Al    7258_en_03 PHOENIX CONTACT T    IL MOD BK DI8 DO4 PAC    5 Local diagnostic and status indicators    MODBUS  PWR             Figure 2 Indicators on the bus coupler    LED   Golor   Weaning       Stato  Description ofthe LED states  UL ogic 24 V bus coupler supply 7 5 V communications power present  OFF      OFF       24 V bus coupler supply 7 5 V communications power not present    US   Green Uscom  ni 24 V segment circuit supply present  OFF 24 V segment circuit supply not present  Gaal Sen  See  Men pee  a0 sip tpg    TR   Yellow TRaffic Data exchange at the RTU ASCIl interface  OFF No data exchan
8. 0  high   Register address  low  Register address  low     00 igh     Register value  high  Register value  low     Register value  high   Register value  low        7258 en_03 PHOENIX CONTACT 20    IL MOD BK DI8 DO4 PAC    Function code fc15    Request PDU    1 byte  Start address 2 bytes O000ney     FFFFrex  Number of outputs 2 bytes 0001 hex     07BOhex    Byte counter byte  Outpt vale Nxtbye  SS       Number of outputs  8  if the remainder is  gt  0  N   N 1       Response PDU    Start address 0000pex     FFFF nex  Number of outputs 2 bytes 0001 hex     07BOhex       Error    1 byte  Exception code 1 byte 01 or 02 or 03 or 04    Example for a request to write a series of 10 outputs  starting with output 20  The   data contains two bytes  The binary values are assigned to the outputs as follows     E o e oe       Output  27   26   25   24  23  22  21  20             2 28  The first transmitted byte  CDhex  addresses outputs 27 to 30  whereby the LSB in this setting  addresses output 20     The next transmitted byte  O1hex  addresses outputs 29 and 28  whereby the LSB in this setting  addresses output 28  In the last data byte  unused bits should be filled with zeros     Start address  igh   00 _ Startaddress  righ    o  Number of outputs  high    00   Number of outputs  igh    00          7258_en_03 PHOENIX CONTACT 21    Function code fc16    Request    1 byte  Start address 2 bytes O000hey     FFFFrex    Number of registers 2 bytes   0001he      0078hex  Byte counter 1 by
9. IL MOD BK DI8 DO4 PAC    Inline bus coupler for Modbus with eight digital    inputs and four digital outputs    AUTOMATION    Data sheet  7258 _en_03    1 Description    The bus coupler is the link between the Modbus RTU ASCII  system and the Inline installation system     Up to 61 Inline terminals can be connected in any position to  an existing Modbus RTU ASCII system using the bus  coupler  The bus coupler and the Inline terminals form one  station with a maximum of 63 local bus devices  Here  the  inputs and outputs of the bus coupler together form the first  and second local bus devices     Up to eight PCP devices can be operated on the bus  coupler              PHOENIX CONTACT   09 2009    Features    Modbus RTU ASCII    Modbus connection via 9 pos  D SUB female  connector    Interface physics RS 485 for Modbus  Electrical isolation of Modbus interface and logic    Data transmission speed of 1 2 kbps to 115 2 kbps   configurable     Rotary encoding switches for setting the Modbus  address and for configuration    Supported Modbus addresses 1 to 99  Up to 8 PCP devices can be connected  Eight digital inputs   Four digital outputs   Diagnostic and status LEDs    Automatic baud rate detection on the local bus   500 kbps or 2 Mbps     WARNING  Explosion hazard when used in potentially explosive areas       When using the terminal in potentially explosive areas  observe the corresponding notes on page 11     Make sure you always use the latest documentation   It can be downl
10. ION FOSISLONS aseene tee mipaterner a e earn Cree E osc eee 9   6 3 Terminal point assignment of input ANd output CONNECHOSS              ccccceeeceecceeeeeceaeeeeeeseeeeeseaeeeeseaaeeeeesaanaeeees 10  CONNECTION EXAMP Eai mein aa ere ari er ar keen eee np eens eh Me ec ee eens cee ee ee 10  Notes on using the terminal in potentially explosive areas             ccccceeccecceeeceeeeeeseeeeeeaeeeeeeeeeneeees 11   BS eM UNIO  AE E EIE E E EE E E EES assed A E ET ees EE EEE 12   LO  Haraware COMnMQUEANOM rearen i E atcan verter  12  10 1  Address seting e nsiecsenne sne n e e a a a a a gyveaaedabelaueeeedtel 12   10 2 Parameterization via rotary encoding SWILCNES             cece tee e eee ee eee eee e seers eae eee sada eeesaneeeeaas 12   10 3 Parameterizing the IL MOD BK DI8 DO4 PAC via Modbus registers                ccccceeeeeeeeeeeeeeeeeeeeeeeeaaeeeeeeeeenaas 13   10 4 Modbus telegram watchdog  CONNECTION MONILOLING             cccececeeeeeeee eee eeeeeeeeeeeeaeeeeeeeeeaaaaeeeeeeeaaeeeeeeeeaaaaaees 14   10 55 Pigandplay ModE si225 seach vecladesat ein casciude ia desea datteteceteetlanaleautidvaa Ieee a A sare 14   TE NDODUS D OOC Ol sasaaa enc atca beauden A E E datas 15  12  MOaDUSTUNCIONS cesme n E ace Oat ataaes 16  13 Examples for Modbus FUNCTIONS                 cece ceecceeececceece cece ceceeecaeeceeecaeecaeecaeeseeeseesseeeauesauesauesseeess 17  TA MOODUSTA DIE aE a tad breadisenie E aacenianis ieee E A 23  WAS  PrOcCeS Sda Teine ee E E E separa nice iane tess 23   
11. OD BK DI8 DO4 PAC via Modbus registers    In addition to the described setting options using rotary  encoding switches  the configuration can be modified via  the Modbus registers     2100  16 bit word  Transmission mode 0  RTU  default   1  ASCII    2101  16 bit word  Baud rate 0  1200  1  2400  2  4800  3  9600  4  19200  default   5  38400  6  57600  7  115200    2102  16 bit word  Data bits 0  7 bits  1  8 bits  default     2103  16 bit word  Parity 0  None  1  Even  default   2  Odd    2104  16 bit word  Stop bits 0  1 bit  default   1  2 bits    1280  16 bit word  Watchdog 0  Watchdog deactivated  200 ms to 65000 ms  1 ms steps   10000 ms  default     2002  16 bit word  Fault response mode 0  Standard fault mode  1  Reset fault mode  default    2006  16 bit word  Command register 1  Enable plug and play mode  default   0  Disable plug and play mode    The new parameters are applied following a positive  response  This response is transmitted again with the  old   parameters  The next request is then made with the new  parameters        Default values  19200 baud  8 data bits  even parity  1 stop  bit  10000 ms watchdog    Following a power up  the last valid parameter record  applies     a   When the baud rate changes  the RTU framing  also changes by default  i e   times t 1 5 and t 3 5  are adjusted   t 1 5   Maximum permissible gap between the  bytes of a Modbus telegram    t 3 5   Minimum pause between two Modbus  telegrams    Detailed information can be found at   
12. TAZ     Special registar S ea a a a a ae ae 25   T3 DesciptionorspecialrsgiStelS secs a E 25    7258_en_03 PHOENIX CONTACT 2    2 Ordering data    Product  Description    Inline bus coupler for Modbus RTU ASCIl with eight digital inputs and four  digital outputs  complete with accessories  end plate  Inline connector  and    labeling fields     Accessories  Additional system components  Description    Type  IL MOD BK DI8 DO4 PAC    Type    FO interface converters for fiber optic data conversion and transmission  see INTERFACE catalog     Power supply units for supplying the bus coupler  see INTERFACE catalog     Accessories  Connectors    Description  SUBCON connector    Connector set for Inline bus coupler with aligned I Os  as replacement item     Accessories  Other  Description    Quick mounting end clamp for securing the module Inline station on the DIN  rail for a horizontal mounting position  to the right and left of the module Inline    station    End clamp for securing the module the Inline station on the DIN rail for a    vertical mounting position  above and below the module Inline station  Keying profile  Zack marker strip to label the terminals    DIN EN 50022 DIN rail  2 meters    Documentation    Description   I O terminals at bus couplers  application note   Automation terminals of the Inline product range  user manual     Inline terminals for use in zone 2 potentially explosive areas   application note     Peripherals Communication Protocol  PCP   user manual 
13. aracters  CR  LF     The transmitted characters comprise the ASCII code and transmission    consist of 1 byte each  The frame start     and end  CR  LF  are specified using  The advantage the ASCII transmission mode offers over the special characters  Gaps between the bytes of a frame are  RTU transmission mode is non time critical data not important     12 Modbus functions    The Modbus protocol functions determine whether data is to  be written or read and what type of data is involved     The following Modbus functions are supported     Write multiple coils Write multiple digital outputs  Write multiple registers Write multiple output registers    For additional information about Modbus  functions  please refer to the  FL IL 24 BK PAC UM E user manual        7258 en_03 PHOENIX CONTACT 16    13 Examples for Modbus functions    Function code fc1    Request    1 byte  Start address 0000pex       FFFF nex       Number of outputs 1     2000  7D0hex     Response    byte  Number of bytes T byie  Output status     N    Number of outputs  8  if the remainder is  gt  0  N   N 1       Error    Tye   Function code   Spa  Exception code 01 or 02 or 03 or 04    Example for a request to read digital outputs 20     38 38    IL MOD BK DI8 DO4 PAC    Start address  high  Number of bytes   low        Start address  low Output status 27     20  Number of outputs  high    00  Output status 35     28  Number of outputs  low  Output status 38     36    Function code fc2    Request    Start addre
14. e pin DGND  reference potential to 5 V    assignment  please refer to the figure and the table  6e VCC    Reserved    cable A    o  Reseved SSOS S S    aa RxD TxD N  receive transmit data           6 2 Mains termination resistors    The use of this SUBCON connector ensures that the cable  termination meets the Modbus RTU ASCIlI specification     SNaddoW       7258B002    Figure 3 Pin assignment of the 9 pos  D SUB female  connector    Pin    Reserved    Reserved    3 RxD TxD P  receive transmit data      cable B       7258 _en_03 PHOENIX CONTACT 9    6 3 Terminal point assignment of input and output                                                                         connectors  O1 11 12  AC eee re a ardu Sl at  pE V pof  12 66L 22 12 0   22 3 2 J6 4 2  PI Po PI  1 3 5512 3 1385 23 338 5  4 3  PY Po Dc  WISH 24 1 4 55L 24 34th 44  Po Pe Po  1 2 3 4  Figure 4 Terminal point assignment    Terminal point assignment of the power connector  1     ponte ee cite  e  points points   ground  FE  ground  FE   Terminal point assignment of the output connector  2   ponte me cite Se  points points    4    Terminal point assignment of the input connector  3     Terminal Terminal  a points             Terminal point assignment of the input connector  4     Terminal Terminal  points points       7258 en_03    IL MOD BK DI8 DO4 PAC    7 Connection example    PWR DO4 DI4 DI4  1 2 3 4    a           UJU   z     TTF i    Modbus    7258A005    Figure 5 Connection example    PHOENIX CONTACT 10 
15. er of input registers       Error    moye  Exception code 01 or 02 or 03 or 04    Example for a request to read input register 9  Request              Field name  Function  01         Start address  high  Number of bytes   Start address  low  Input register 9  high    Number of input registers  hi Input register 9  low   h    Number of input registers  hi       gh   gh        Function code fc5    Request    Function code 1 byte  Output address 2 bytes 0000hex     FFFFhex  Output value 0000hex     FFOOhex    Response    Function code 1 byte  Output address 2 bytes 0000hex     FFFFhex       Output value 2 bytes 0000hex     FFOOhex    Error    1 byte  Exception code 01 or 02 or 03 or 04    7258_en_03    Response    IL MOD BK DI8 DO4 PAC         PHOENIX CONTACT 19    IL MOD BK DI8 DO4 PAC    Example for a request to write output 173 ON    Request  Field name    Function  Output address  high    00  Output address  high   Output address  low  Output address  low   igh          5  C  Output value  high  Output value  high  Output value  low  Output value  low         Request    Function code 1 byte  Register address 2 bytes   0000hex     FFFFhex  Register value 2 bytes   0000pex     FFFFhex    Function code fc6    Response    Function code 1 byte  Register address 2 bytes   O000he      FFFFrex       Register value 2bytes   0000be      FFFFnex    Error    Exception code 1 byte 01 or 02 or 03 or 04    Example for a request to write register 2 to 0003hex    Register address  high    0
16. ge at the RTU ASCIl interface    CO COnfiguration The active station configuration differs from the saved configuration  The active station configuration matches the saved configuration     WD WatchDog ON Time between two Modbus telegrams exceeded during active connection  monitoring  Modbus telegram watchdog     Flashing   On power on reset   at 2 Hz Reading in new parameters  Flashing  On power on reset   at0 5 Hz  Parameters transferred successfully  Flashing   On power on reset   at 5 Hz Parameters not transferred  FF    No error                      7258 _en_03 PHOENIX CONTACT 8    IL MOD BK DI8 DO4 PAC    LED   Color   Meaning   State  Description of the LED states    Green   Diagnostics Data transmission active within the station  at 0 5 Hz  b p    had Error   ON __  Short circuit overload of local outputs    No short circuit overload of local outputs  Yellow   Output 1 Outputs are active  Outputs are not active    Yellow   Input 1 to Inputs are active  input 8 Inputs are not active    Error message sent to the higher level control system           Sensor supply not present  peripheral fault       Short circuit overload at an output  peripheral fault     See also  Local bus diagnostic status register  7997   on  page 27     6 Connecting Modbus  power supply  actuators  and sensors    6 1   Connecting Modbus CNTR P  control signal for repeater     Connect Modbus to the bus coupler using a 9 pos  D SUB direction control   connector  see  Ordering data  on page 3   For th
17. le Internal IL MOD BK tables Function codes that can be used  8000   8192  16 bit word  Dynamic process data table fc2 to fc16    Assignment of the process data in dynamic tables    XxX  a  IL     Lu  2  Q                  PH  NIX  CONTACT   IL MOD BK DI8 DO4 PAC  Order No   2878696                                       MODBUS RTU ASCII          ADDRESS  o 0  14a  EES  E GE   106 OKA  8 98    x10 x1                                                                                                                                                                                                                                                                                             Modbus register location of process data  DATA IN    Address 8000 C merra    P Address 8001  rrr  a  DI Bit oriented Address 8002            ori Address 8003       Al Byte oriented 2       Address 8004   Address 8005   Address 8006   Address 8007 D a A    Channell2 status    POX XXX   PK XX XXX XX     Address 8008  Channel status         DATA OUT    Address 8009 C T xxx    Address 8010 L330    _DO Bitoriented address 8011  AO _ Byte oriented Address 8012  Address 8013   Address 8014   Address 8015   Address 8016   Address 8017   Address 8018    Figure 11 Example for the location of process data in dynamic tables       72750014    7258 en_03 PHOENIX CONTACT 24    14 2 Special registers    Modbus register table    IL MOD BK DI8 DO4 PAC    Internal IL MOD BK tables    1280  16 bit word  Read write Modbus 
18. ly  started up if the configuration of the connected  bus matches the saved configuration     If plug and play mode is enabled  the writing of  process data is rejected by an exception  Read  access to the process data is possible        PHOENIX CONTACT 14    11 Modbus protocol    Additional  PDU         ADU  7258A018  Figure 7 Modbus protocol  Key   PDU Protocol data unit  ADU Application data unit  protocol frame     The Modbus application protocol is created by the client that  initiates a Modbus transmission     The function code field of the protocol  1 byte  informs the  server of which action it is to perform     The data fields of messages  which are sent from a client to  a server  contain additional information that the server uses  in order to perform the action specified by the function code  field  This includes  e g   digital addresses and register  addresses  the number of units to be managed  and the  number of actual data bytes         Client Server    Initiate Request         Perform the Action  Initiate the Response         Receive the Response    7258A016    Figure 8 Modbus transmission  without errors   Key    Client Control system   Server Modbus devices    If no error occurs in a correctly received Modbus protocol for  the requested Modbus function  the data field for aresponse  from a server to a client contains the requested data     When the server responds to the client  it uses the function  code field to indicate either a normal  error free  respo
19. mited to 3 mA  maximum  1 2 ms  typical   100 m    4  2 and 3 wire technology  24 V DC    lt 1V   0 5A   2A    12W   12W   12 VA  1 2 H    0 5 Hz  1 2 H   maximum  1 2 ms  typical   Auto restart   Output may be damaged    Protected against reverse voltages    IL MOD BK DI8 DO4 PAC    Protected against reverse voltages  permissible current 2 A  maximum    The output follows the supply voltage without delay      30 0 V  approximately    10 WA  When not loaded  a voltage can be measured even at an output that is    not set      Suppressor diode parallel to supply voltage    Diode for protection against polarity reversal    Free running circuit    Error messages to the higher level control or computer system    Short circuit overload of the digital outputs  Sensor supply not present    Mechanical tests  Vibration resistance according to IEC 60068 2 6  Shock test according to IEC 60068 2 27    7258 en_03    Yes  Yes    5g    Operation  25g  11 ms period  half sine shock pulse    PHOENIX CONTACT    5    Conformance with EMC directive 2004 108 EC    Noise immunity test according to EN 61000 6 2  Electrostatic discharge  ESD  EN 61000 4 2     IEC 61000 4 2  Electromagnetic fields EN 61000 4 3   IEC 61000 4 3  Fast transients  burst  EN 61000 4 4    IEC 61000 4 4    Surge voltage EN 61000 4 5     IEC 61000 4 5  Conducted interference EN 61000 4 6   IEC 61000 4 6  Noise emission test according to EN 61000 6 4  Noise emission of housing EN 55011    Approvals    For the latest approvals 
20. n  potentially dust explosive atmospheres     7258 en_03    Installation in zone 2    1     Observe the specified conditions for use in potentially  explosive areas     When installing the terminal  use an appropriate and  approved housing with a minimum protection of IP54   Please observe the EN 60079 14 requirements  e g   a  steel housing with a wall thickness of 3 mm     In potentially explosive areas  only snap the Inline  terminal onto the rail and connect the cables when the  power is switched off     In zone 2  only connect devices to the supply and signal  circuits that are suitable for operation in potentially  explosive areas of zone 2 and the conditions at the  installation location     Restrictions limit values    1     Only Inline terminals that are approved for use in  potentially explosive areas may be snapped next  to this Inline terminal  Before using an Inline terminal  in a zone 2 potentially explosive area  first check that  the terminal has been approved for installation in this  area  For a list of terminals that are approved for the  potentially explosive areas of zone 2  please refer to the  AH EN IL EX ZONE 2 application note     Please make sure that the maximum permissible  current of 4 A flowing through potential jumpers Um  and Us  total current  is not exceeded when using the  Inline terminals in potentially explosive areas     The supply of Up and Us at the bus coupler must not  exceed 4 A    Also ensure that the maximum permissible current  of
21. n registers are  supported     PHOENIX CONTACT 27    PCP registers    Communi   cation  reference    7258 en_03    Communi   cation  register    Configura   tion register    6021    6022  6023  6024   6029    6031 ndex    6032 Subindex  6033 Invoke ID  6034   6039   Reserved    6041    Index   Subindex  Invoke ID       Reserved    ndex       6042 Subindex  6043 Invoke ID  6044   6049   Reserved    6051       Subindex  Invoke ID  Reserved  Co  Index   Subindex  Invoke ID  Reserved  ME  6071      ndex    6071 Index    54   6059    9  6072 Subindex  6073 Invoke ID  60724   6079   Reserved  6081 Index  84   6089  4   6099    6082 Subindex  6083 Invoke ID    60 Reserved    6091 Index    6092 Subindex  6093 Invoke ID  Reserved       IL MOD BK DI8 DO4 PAC    Example     In order to read object 5FEO    of an IB IL RS 232 with  communication reference 4  first set the configuration  registers  6041   6043  to the desired values with the FC 16  command  e g   6041 index  5FEOhex  6042 subindex  Oney   6043 invoke ID  Ope    The fc3 command can then be used  to read 29 words via communication register 6040     A Modbus function is only ever used for read write access to  a PCP index  For example  the f  3 command cannot be  used to read 20 words from registers 6020 to 6039     The communication register contains a different value range  due to the selected values of the register and the terminal  used  Therefore  the IB IL RS 232 terminal  for example   has three different PCP objects  
22. nds  on the set fault response mode  By default upon delivery     the fault response mode is set to reset fault mode  For reset  fault mode  the following applies         Set digital outputs to zero      Freeze analog outputs      Watchdog LED ON    7258 en_03    Special feature when disabling the watchdog via write  access to register 1280     Settings modified by write access  disable watchdog   modify monitoring time  are only applied following a power  up reset  Watchdog activation via register 1280 is applied  immediately during operation     PHOENIX CONTACT 25    Fault response mode   2002     IL MOD BK DI8 DO4 PAC    Faultresponsemode  Value  Function  Standard fault mode   0  All outputs are set to  0      Reset fault mode  default  I The digital outputs are set to  0  and the analog outputs are held at the last  value        Hold last state mode   2   All outputs are held at their last value     Net Fail reason   2004     This register can be used to read the reason after the   Net Fail signal has been triggered  For the   IL MOD BK DI8 DO4 PAC there can only be one reason   the connection monitoring watchdog has failed  In Net Fail  Reason register 2004  the value 000D    appears     Command register  Command word    2006     Activation deactivation of plug and play mode is performed    in the least significant bit of the command word  Bit 0    0        gt  plug and play mode deactivated  bit 0    1    gt    plug and play mode activated    If a Net Fail occurred  it
23. nse or  to indicate an error  this is also known as an exception  response   For a normal response  the server returns the  original function code to the request     7258 en_03    IL MOD BK DI8 DO4 PAC        Client Server    Initiate Request       Error Detected in the Action  Initiate an Error    7258A017       Receive the Response       Figure 9 Modbus transmission  exception response   Key    Client Control system   Server Modbus devices    For an exception response  the server returns a code that  corresponds to the original function code of the request  PDU  whereby the MSB is set to logic 1     There are two different transmission modes  RTU and  ASCII  Both differ in terms of the type and form of  information represented in a telegram  In a Modbus  network  each device must have the same transmission  mode     Modbus RTU    Modbus RTU telegrams consist of the following parts     Station CRC  address       0 252 bytes    Modbus RTU telegrams are separated by breaks known as  end of frame times  The time is at least 3 5 times the time of  a sent character  It cannot be adjusted     The advantage the RTU transmission mode offers over the  ASCIl transmission mode is a higher data throughput with  the same baud rate     PHOENIX CONTACT 15    IL MOD BK DI8 DO4 PAC    Modbus ASCII    Modbus ASCII telegrams consist of the following parts     Stan Station address  Function   Daa   Rc   mD       1 character     2 characters 2 characters 0   2 x 252 2 characters 2 characters  ch
24. oaded at www phoenixcontact net download        DO dD O 0 cD ED o dD o oE  hiona       INSPIRING INNOVATIONS    IL MOD BK DI8 DO4 PAC    The intelligent wiring method used by Inline terminals operating voltages for the bus coupler and the connected  enables the station to be created quickly and easily  since  Inline terminals   e g   time consuming wiring of the terminal power supply is    The end plate is supplied with the bus coupler  Place this  not required     plate at the end of the Inline station  The end plate has no  In the simplest case  it is only necessary for the power electrical function  It protects the station from ESD pulses  supply units integrated in the bus coupler to be supplied with and the user from dangerous contact voltage    24 V DC on the input side  They then generate the required    Table of contents    T   WIGS CHOU O Iactattce aes thce he neet neetenstoones Ea E T 1  2    OPOS ING sCla tatnsacace laste tanteca abana ia setsnte E AS 3  S    IOC IAM CAN CALA ninna aa Gat meas aeeigc es ace ena a anee et enuuauiarenetot ee eaptae 4  A  NS aSIG CIFCUI QIAG aN si a a a a lena radinawemneiedousiae  7  5  LOGal GlagnOsiG and  Status Indicators wel cineioictiuiastadietnseniasitabanetieiedeealecasasabdeiatemeveeentiane baton  8  6 Connecting Modbus  power supply  actuators  ANd SENSOIMS            ccccccceecceeeeceeeeeeeeceeeseueeeeesaees 9  6 1 COMME CHING MODUS niiret aac anita ie cos dura Save N Gace ant Ie c qaauead adnate A 9   602   Mais TOMIMIMA T
25. of devices with parameter channel  PCP     Supply voltage for Ugx Us Um  Recommended cable lengths   Continuation   Nominal value   Permissible range  according to EN 61131 2     IL MOD BK DI8 DO4 PAC    80 mm x 119 8 mm x 71 5 mm   320 g  with connectors     25  C      60  C    45  C      85  C   10      95   according to DIN EN 61131 2    70 kPa to 106 kPa  up to 3000 m above sea level     IP20  Class Ill according to EN 61131 2  IEC 61131 2  4 ms  typical    Inline I O connector   Spring cage connection   0 08 mm      1 5 mm   solid or stranded   28   16 AWG  28     16    Inline data jumpers  500 kbps  2 Mbps  automatic detection  no combined system     9 pos  D SUB female connector  electrically isolated supply  shielding directly  connected to functional earth ground     9  1 2 kbps to 115 2 kbps  configurable     63  maximum  per station   61  maximum  on board I Os are two devices   8  maximum    30 m  maximum  do not route cable through outdoor areas  Through potential routing   24V DC   19 2 V to 30 V  ripple included     NOTE  Electronics may be damaged when overloaded    Provide external fuses for the 24 V areas UL  US  and UM  The power supply unit must be able to supply four times the nominal current of the    external fuse  to ensure that it trips in the event of an error     Communications power U   7 5 V  and the analog supply U ana  24 V  are generated from the bus coupler supply Upx        Power consumption   Current consumption from U   7 5 V   Current cons
26. s the value  0000hex      Bit  Constant  Meaning    0  USER_BIT  Application program eror  peripheral fault  4    DETECT BIT   Error localization    LOOK FOR FAIL      RUN_ BIT Exchanging data cycles  6  ACTIVE_BIT  Local bus master ACTIVE    7  READY_BIT  Local bus master READY  selftest  completed    Local bus diagnostic parameter register 1  7998     For detected local bus errors  the local bus diagnostic  parameter register contains the error location   Error location  e g   device number 0 3    Device number of a device  e g    0 3  for bus segment O   device 3    Segment number Position in the segment    7275a007    Figure 14 Contents of the local bus diagnostic parameter    register  example     Local bus diagnostic parameter register 2  7999     Local bus diagnostic parameter register 2 contains  additional information about the error codes     For additional information about local bus    diagnostics  please refer to the  IBS SYS FW G4 UM E user manual        7258 en_03       IL MOD BK DI8 DO4 PAC    PCP registers  6020   6093     The PCP registers are divided into two classes     1  Communication registers for exchanging data with the  desired PCP device    2  Configuration registers for selecting the invoke ID   index  and subindex of the PCP device    For additional information about PCP    communication  please refer to the  IBS SYS PCP G4 UM E user manual        The terminal supports eight PCP devices  therefore eight  communication registers and 24 configuratio
27. ss 2 bytes   0000h  x     FFFFhex  Number of outputs 1     2000  7D0 hex     Response    Tovo  Number of bytes T byie          Output status SES SS     N    Number of inputs  8  if the remainder is  gt  0  N   N 1    Error      Error code   byte   82hex      Modbus Application Protocol Specification V1 1a    Exception code 01 or 02 or 03 or 04    7258 en_03    PHOENIX CONTACT 17    IL MOD BK DI8 DO4 PAC    Example for a request to read digital inputs 197     218     Start adcress thon   00  Number ofbytes   Number ofinputs  high    00 _  inputstatus 95 28    Function code fc3       Request    O3hox  Start address 2 bytes   0000pex     FFFFhex  Number of registers 2 bytes 1    125  7Dhex     Response    Number of bytes Tbyie          Register values waoe SSS     N   Number of registers    Error    Exception code 1 byte 01 or 02 or 03 or 04    Example for a request to read registers 108     110    Startadress ton   00 _ Numberofbyies            Star address  ow    6B  Register value  igh   108   Register number  high    00  Register value  ow   108         Register number ow    03  Register value  high   109    00  Register value  low   108    00   o    Register value  high   110   Register value  low   110                       7258_en_03 PHOENIX CONTACT 18    Function code fc4    Request    1 byte    Start address 0000hex     FFFF nex  Number of input registers 0001 hex     007 Dhex    Response    1 byte       Number of bytes T byie  input registers Nx2bye  SSS S     N   Numb
28. tary encoding  switches  on page 12   The switch position is mapped to the  command register  Modbus register 2006   see page 26    By default upon delivery  P amp P mode is activated  The P amp P  mode status  active or inactive  is stored retentively on the  bus coupler  In P amp P mode  the connected Inline terminals  are detected and their function checked  If this physical  configuration is ready for operation  it is stored retentively on  the bus coupler as a reference configuration     P amp P mode must be deactivated again so that the reference  configuration is not overwritten the next time the bus coupler  is started  At the same time  the deactivation of P amp P mode  also acknowledges the reference configuration and enables  process data exchange     When P amp P mode is deactivated  the reference configuration    is Compared to the physical configuration  If they are the  same  the bus coupler can be set to the  RUN  state     Plug and play mode    If the reference configuration and the physical configuration  differ  the CO LED lights up and process data exchange is  no longer possible for safety reasons     In order to operate the bus you have the following two   options    1  Restore the original configuration so that the reference  configuration and the physical configuration are the  same again   2  Activate P amp P mode so that the active physical  configuration is accepted as the reference  configuration     If plug and play mode is disabled  the bus is on
29. te  Register value NF x2 bytes     N   Number of registers       Response    Start address 2 bytes O000ney     FFFFnex       Number of registers 2 bytes  1    123  Z8hex     Error    byte  Exception code 1 byte 01 or 02 or 03 or 04    Example for a request to write two registers  starting with 2 to  000Ahex and 0102hex    Response  Field name  Function  Start aaress thon   00  Start address  high   Start address  low    Number of registers  high    00   Number of registers  high  Number of registers  low   o                         Register value  high     Register value  low     Register value  high     Register value    cm   AN   A    low     7258_en_03    IL MOD BK DI8 DO4 PAC    PHOENIX CONTACT 22    IL MOD BK DI8 DO4 PAC    14 Modbus tables    14 1 Process data    The Modbus register tables provide information about the location of process data in the control system  Generally  the bit   oriented process data appears first in the registers followed by the byte oriented process data     Static table    Modbus register table Digital Modbus Digital Modbus Internal IL MOD BK   Function codes  inputs table outputs table tables that can be used    0   191  16 bit word  0   3071  bits           Digital inputs    192 385  Te bitword                      Analog inputs  384   575  16 bit word      0   3071  bits  Digital outputs fc1  fc5  fc15  576   767  16 bit word      Analog outputs fc3  fc6  fc16    Assignment of the process data in static tables       MOD BK  DO4 ETH BK  DI8
30. telegram watchdog  connection monitoring      1400   1463  16 bit word     2002  16 bit word Read write  2004  16 bit word  2006  16 bit word    2100  16 bit word    2101  16 bit word    2102  16 bit word Data bits  7  8  default   1   8 bits   see table on page 13              2103  16 bit word  Write        default   10000 ms     Read Up to 1400  Number of local bus devices  Above 1401  ID code of the relevant device   Read write   Fault response mode  default   reset fault mode     Net Fail reason  Read write Command register  command word     Write Transmission mode  RTU  ASCII  default   0   RTU mode   see table on page 13    Baud rate  1200     115200   Default   4   19200   see table on page 13    Parity  None  even  odd  default   1   even parity    see table on page 13    2104  16 bit word Stop bits  1  2  default   0   1 stop bit   see table on page 13    6020   6093  16 bit word  Write PCP    mooo       14 3 Description of special registers    Modbus telegram watchdog  connection monitoring     1280     Valid values for the register are 0  200 ms to 65000 ms     The watchdog monitors Modbus telegrams and is triggered  each time a Modbus telegram is received correctly  It can be  enabled and disabled via the rotary encoding switches  see   Parameterization via rotary encoding switches  on   page 12  The time can be setvia register 1280  0   disabled   200 ms to 65000 ms     Actions after triggering the watchdog    The action taken when the watchdog is triggered depe
31. two objects are one word  long  but the third is 29 words long  The three configuration  registers can be read written with a single Modbus  command  An attempt to access a reserved register  generates an exception response     PHOENIX CONTACT GmbH  amp  Co  KG    32823 Blomberg    Germany    Phone   49  0  5235 3 00 28  PHOENIX CONTACT    P O Box 4100    Harrisburg    PA 17111 0100    USA    Phone   717 944 1300  www phoenixcontact com    
32. umption from Us  24 V   Current consumption from Uj   24 V   Current consumption from Uana  24 V   Power dissipation    7258 en_03    0 07 mA  typical 0 8 A  maximum  8 A  maximum   8 A  maximum   0 5 A  maximum   1 7 W  typical    PHOENIX CONTACT 4    Digital inputs   Number   Connection method for sensors   Input design   Definition of switching thresholds  Maximum low level voltage  Minimum high level voltage   Common potentials   Nominal input voltage UIN   Permissible range   Nominal input current for Uin   Current flow   Response time   Permissible cable length to the sensor    Digital outputs   Number   Connection method for actuators   Nominal output voltage Ugyut   Differential voltage at lhom   Nominal current lhom per channel   Total current   Nominal load   Ohmic   Lamp   Inductive   Switching frequency with nominal inductive load  Response time   Overload response   Response with inductive overload   Reverse voltage protection against short pulses  Resistance to permanently applied reverse voltages  Response upon power down   Limitation of the voltage induced on circuit interruption  Maximum output current when switched off    Protection   Supply   Surge voltage  polarity reversal   Digital inputs   Polarity reversal   Digital outputs   Short circuit protection  overload protection    8  2 and 3 wire technology  According to EN 61131 2 Type 1    Uimax  lt  5 V   Uumin  gt  15 V   Sensor supply Us  ground  24 V DC    30 V  lt  Uj  lt   30 V DC   3 mA  typical   Li
33. www modbus org           7258 en_03 PHOENIX CONTACT 13    10 4 Modbus telegram watchdog     connection monitoring     The watchdog monitors Modbus telegrams and is triggered  each time a Modbus telegram is received correctly  It can be  enabled and disabled via the rotary encoding switches  see     Parameterization via rotary encoding switches  on   page 12  The time can be set via register 1280  0   disabled   200 ms to 65000 ms      Actions after triggering the watchdog    The action taken when the watchdog is triggered depends  on the set fault response mode  By default upon delivery   the fault response mode is set to reset fault mode  For reset  fault mode  the following applies         Set digital outputs to zero       Freeze analog outputs       Watchdog LED ON   Special feature when disabling the watchdog via write  access to register 1280         Settings modified by write access  disable watchdog   modify monitoring time  are only applied following a  power up reset     Watchdog activation via register 1280 is applied  immediately during operation     The Modbus telegram watchdog does not  operate during plug and play mode     7258 en_03    IL MOD BK DI8 DO4 PAC    10 5    The IL MOD BK DI8 DO4 PAC supports plug and play  mode  P amp P   This mode enables Inline terminals connected  in the field to be started up using the bus coupler without a  higher level computer     P amp P mode can be enabled and disabled with the ADDRESS  switches  see  Parameterization via ro
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Samsung LA40N71B راهنمای محصول  Cahier de texte et progression TS spé 2014-2015  RAEMesh Reader 900MHz User's Guide  取扱説明書 - 三菱電機  Sencor SFD 1305BK fruit dryer  Drücken Sie      Copyright © All rights reserved. 
   Failed to retrieve file