Home
        PKV 50-XXX
         Contents
1.      The operational readiness and an error in the communication interface are dis   played by LEDs     Copyright   Hilscher Gesellschaft f  r Systemautomation mbH   De PK V50 2EN    General Device Description 7    3 1 Configuration of the Gateway with the SyCon System Configurator    The loading of new files on to the Gateway or the setting of the IP address of the  Gateway is carried out by means of the tools contained in SyCon     In order to be able to use the configuration tools in SyCon  it is necessary to lay  down a configuration with a PKV 50 Gateway in SyCon  Now the menu entry  PKV50 XXX  XXX here stands for the selected fieldbus system  appears in the  Tools menu point  This makes it possible to choose between a serial RS232 con   nection and a TCP IP connection     A crossed RS232 cable is necessary for operation at the serial interface and this  can be obtained from the Company Hilscher  CAB SRV      The configuration via TCP IP can also be carried out via a point to point con   nection with a crossed cable or  for example  via a Hub with commercial Ethernet    cables     The Gateway is supplied with a default IP address  see information sheet      PK  40 50 TCP IP Configuration Lx      File Configuration Info             M Connect with IP address    192 169 10 163 Connect   Cancel                henge lk addiess                            Please connect to device          Configuration dialog for the PKV 50 XXX Gateway via TCP IP    The procedure for the serial
2.    1 Output TXDE    2 Output TXDE    3 Input RXDE    6 Input RXDE                 Pin assignment of the Ethernet interface    The Ethernet interface is carried out by means of an 8 pin RJ45 socket for a  10 100BaseT connection     Copyright   Hilscher Gesellschaft f  r Systemautomation mbH   De PK V50 2EN    General Device Description 14    3 3 2 Fieldbus Interface  X6     The following tables describe the pin assignment for the individual fieldbus sy   stems available on the PKV 50 Gateway     3 3 2 1 PROFIBUS Interface for PKV 50 DPM                               Connnection Input  Signal Signal  9 pin D SUB Output designation  socket      PE Earth ground  1   PE PNO recommend not to use this  signal  6   VP Power supply  Input  RXD TXD A   Data line  Output  8 Input  RXD TXD B   Data line inverse  Output  Output CNTR A  Repeater control signal    DGND Data reference potential                   Pin assignment of the PKV50 DPM at the plug X6    3 3 2 2 CAN Bus Interface for PKV 50 COM  PKV 50 DNM       Connector Input  Signal Signal                            Connection 9   Connection 5 pin   Output   designation  pin D SUB plug COMBICON  for DeviceNet  a 5   PE Earth ground  9 5    V 24V external power    3     DGND Data reference potential  7 4 Input  CANH Data line high  Output  2 2 Input  CANL Data line low  Output  6 1   DGND Data reference potential    3   shield shield of bus cable                         Pin assignment of the PKV 50 COM and PKV 50 DNM at the plug X6 
3.    Copyright   Hilscher Gesellschaft f  r Systemautomation mbH   De PK V50 2EN    General Device Description 15    3 3 3 Diagnostic Interface  X3     The connection of a  Host  PC to the Gateway is also possible via the first serial  interface  X3   It corresponds to the RS232C standard according to CCITT or  DIN  However  only the required signals are available     The control signals are served or evaluated as follows   RTS is switched to high after the function readiness and not altered again     CTS must be connected by means of a wire bridge with Pins 4 and 8 of the D Sub  plug     The transfer between Host PC and Gateway is at 9 600 Baud and the following  data format  8 Data bits  1 Stop bit and even parity  The 3964R procedure is utili   zed as transfer protocol     The connection of the PC is carried out with a three wire cable which must not be  longer than 15 meters  The wiring of the cable is given below  For better interfe   rence suppression  the cable shielding also on the side of the Host PC should be  grounded over the plug housing                    KV  gt C AT  Protective earth  PE   zm i  through plug body   v d   N ra S  e   RAD  gt  f I 1    CRD   3         3     AD          l TXD            4   AME LEE o  opum          E   a  gt  a  E   lt  GND  6 h 6   JSR  gt e x Y  amp     4 DSR  8   CTS     ce CTS   9 pin DSub plug socket 9 pin DSub plug socket       Connecting cable between Gateway and Host PC    Copyright   Hilscher Gesellschaft f  r Systemautomat
4.  Web Server  HTML pages can be created on  a corresponding editor and then loaded on to the Gateway  Process data can be  linked via Java Applets  All that is still needed to access the data of the Gateway  via the Internet is a Web Browser such as for example  Microsoft Explorer or  Netscape Navigator     The configuration of the Gateways is carried out locally with our SyCon System  Configurator via the RS232C serial diagnostic interface or remotely via TCP IP     The PKV 50 fieldbus Gateway is now offered for the most important fieldbus  systems     Customer specific solutions can be implemented by us or by the customer  himself     Copyright   Hilscher Gesellschaft f  r Systemautomation mbH   De PK V50 2EN    Structure of the Gateway 5    2 Structure of the Gateway    Modern communication systems are structured in accordance with the ISO OSI  reference model  ISO IS 7498   This is based on a 7 layer structure  Here  every  layer makes the services of the next higher layer available but only uses the servi   ces of the next lower layer itself     The Gateway fulfills this structure                 Realtime OS    Tasks for Fieldbus  protocol                           Fieldbus  dependent    Physical    Fieldbus                  Ethernet             The Gateway in the ISO OSI reference model    Copyright   Hilscher Gesellschaft f  r Systemautomation mbH   De PK V50 2EN    General Device Description 6    3 General Device Description    The Gateway consists of a basic circuit b
5.  configuration or the TCP IP configuration is basical   ly the same  First an IP address must be entered into the field provided for it or  the serial interface with which the Gateway is connected must be selected  Then  the Connect switch must be activated  If a valid connection to the Gateway has  been established  then the menu entries and the switches for configuration of the  Gateway are released     In order to ensure communication via TCP IP  the TCP IP protocol on the PC    must be configured in such a way that a connection with the default IP address is  possible  see user manual for Windows NT      Copyright   Hilscher Gesellschaft f  r Systemautomation mbH   De PK V50 2EN    General Device Description 8    3 1 1 Loading Files into the Gateway    This function enables to load files into the User FLASH of the Gateway and to  carry out applications after downloading or after the start of the operating system     Before a new application or a new and already available DLL can be downloa   ded  any running older versions of the application or programs that use DLLs  must be ended  For this purpose  the corresponding running processes can be dis   played under the Configuration    View Running Tasks menu  If an entry has  been selected  then the Stop Process button can be activated and the selected  process is stopped     In order to transfer a new file  select the File    Copy to PKV menu or activate    the Copy to PKV button  Select the file to be loaded in the dialog 
6. EIS UE 4   2 Structure of the Gateway    naar 5  3  General Device Description 2    Hu  a eee ye d cid cate re rk eie puedes meee URN 6  3 1 Configuration of the Gateway with the SyCon System Configurator              sees 7  3 1 1 Loading Files into the Gateway               ssesessesese m e eme 8   3 1 2 Loading Files on to the Host PC    nase leere per hrs se e Rr Er NS 9   331 3  Deleting  Files M                                                    10  3 1 4 Setting the IP Address  22 5 ox er denne na 11   3 1 5 Starting Applications  u a IRA see ee 11   3 2 Connecting the Supply Voltage  X2     0    cence e e eme eee 12  3 3  Interf  ces usse Ib bh RID RI E Ebeoideiboibe eei b Lies ra 13  3 3 1 Ethernet Interface  X4  oo    ccc cece ee een een he hehe hern 13   3 3 2 Fieldbus  Interlace  XO  auch debe eese nre a daa Ur e eed 14  3 3 2 1 PROFIBUS Interface for PKV 50 DPM             sssssse ee 14   3 3 2 2 CAN Bus Interface for PKV 50 COM  PKV 50 DNM            sse 14   3 3 3 Diagnostic Interface  X3  0    ccc nnn eee eese 15   3 4 Status Displ  ys  iiic av ee bees ds MIA da Ter APER chided dh nena ete brin dh iei 16  3 5 Mechanical Dimensions    2 inchlch e ee bx RR DR RA PENAS sah ERU QUUM asain 17   A Appendix  2 2  een dehnen aaa 18  4 1 Technical Data nr    RR aan hassen CORE Rad 18    Copyright   Hilscher Gesellschaft f  r Systemautomation mbH   De PK V50 2EN    Introduction 4    1 Introduction    1 1 Scope of Performance    In automation technology it is becoming ob
7. a              ff  hilscher    COMPETENCE IN  COMMUNICATION    Device manual    PKV 50 XXX  Target System for Ethernet  Fieldbus Applications    Hilscher Gesellschaft f  r Systemautomation mbH  Rheinstra  e 15   D 65795 Hattersheim   Germany    Tel   49  6190  9907   0  Fax   49  6190  9907   50    Sales   49  6190  9907   0  Hotline and Support   49  6190  9907   99    Sales email  sales hilscher com  Hotline and Support email  hotline  hilscher com    Homepage  http   www hilscher com    List of revisions 2             Index Date Chapter Revision  1111 04 02 all created  2 26 07 02 all revised                                                    Although this appliance has been developed with great care and intensively tested  Hilscher Gesellschaft  f  r Systemautomation mbH cannot guarantee the suitability of this appliance for any purpose not confir   med by us in writing     Guarantee claims shall be limited to the right to require rectification  Liability for any damages which  may have arisen from the use of this appliance or its documentation shall be limited to cases of intent     We reserve the right to modify our products and their specifications at any time in as far as this contribu   tes to technical progress  The version of the manual supplied with the appliance applies     Copyright   Hilscher Gesellschaft f  r Systemautomation mbH   De PK V50 2EN    Table of Contents 3    Ici MEER BL ee 4  1 1 Scope of Performance  4 4 03 scitur riia enteni bre De ose i sen es 
8. ation menu has to  be selected  Now enter the name of the application into the field provided for this  purpose and press the OK button     Copyright   Hilscher Gesellschaft f  r Systemautomation mbH   De PK V50 2EN    General Device Description    3 2 Connecting the Supply Voltage  X2     The Gateway requires a supply voltage of 24 Volt  The maximum power con   sumption is given in section Technical Data  A three phase rectified supply or a  simple rectified switching with charge capacitor is sufficient  The supply voltage  must be led to ground  It is connected by means of a plug in screwed clamp  Use  is made of a 3 pin COMBICON plug from the PHOENIX company  MSTB    2 5 3 ST 5 08                           Connection Symbol Signal   1  24V   24V supply voltage   2 OV Reference potential   3 PE   Equipment grounding conductor       Connector pin assignment of the operating voltage connection X2    Copyright   Hilscher Gesellschaft f  r Systemautomation mbH   De PK V50 2EN       General Device Description 13    3 3 Interfaces  The PKV 50 Gateway possesses three independent interfaces     First interface  X3   The first interface can be operated as a diagnosis   configu   ration interface     Second interface  X6   The second interface is designed for operation at the  fieldbus     Third interface  X4   The third interface is used for connection to a  10 100BaseT network     3 3 1 Ethernet Interface  X4                       Connection      Input  Signal    Output designation
9. ded onto the Host PC     Copyright   Hilscher Gesellschaft f  r Systemautomation mbH   De PK V50 2EN    General Device Description 10    3 1 3 Deleting Files    In order to delete files  the menu point File    View Flash Dir can be selected af   ter building up the connection successfully  A list of files that are permanently  stored in the User FLASH memory is displayed now  Now previously selected  files can be deleted with the Delete button     Copyright   Hilscher Gesellschaft f  r Systemautomation mbH   De PK V50 2EN    Note  The Gateway must be  restarted to accept the ad   dress     General Device Description 11    3 1 4 Setting the IP Address    IP Address Setting Ea    IP   ddress  192 4 188  10 169       Dialog for setting the IP Address    It is possible to allocate a new IP address to the Gateway with the Configuration   gt  Setting IP address menu  For this purpose  a connection with the Gateway is  necessary as already mentioned     Now enter the desired valid IP address into the corresponding field  Press the Set  button and the new address is allocated to the Gateway     If the alteration of the IP was successful  it will be displayed  A request for restar   ting the Gateway will appear     Please note that the newly allocated IP address is only valid after a restart of the  Gateway     3 1 5 Starting Applications    Applications that have already been entered on to the Gateway can also be started  manually  For this purpose the Configuration  gt  Start Applic
10. ion mbH   De PK V50 2EN    General Device Description 16    3 4 Status Displays    There are eight LEDs are the PKV 50 Gateway acting as status displays                             Display Color  Condition Meaning  SYS  CON  ST1  The condition of these LEDs are application dependent and are  ST2 described in the corresponding manuals  With a device defect  a cycli    RDY Yellow  On Gateway ready  cal flashing of the RDY LED Flashs cyclically Bootstrap loader active  can also be caused by the Flashs irregularly Hardware or system error  continuous accessing of the Off Hardware defect  Watchdog monitoring  RUN Green  On Fieldbus communication running  Flashs irregularly  see   Parametrizing error  field bus   below    Off No fieldbus communication  ERR NET CH_A Fieldbus dependent  STA   MOD   CH B Fieldbus dependent                   The display on the LED is carried  out from left to right    After switching on  the Gateway carries out a self test  If this has been run  through successfully  then the yellow LED RDY is switched on  Otherwise the  LED begins to flash irregularly and the further processing of the program is abor   ted     If no fieldbus Firmware is loaded on the Gateway  then the Bootstraploader  shows this by a cyclical flashing of the RDY LED in a 1 second rhythm  During  the loading of the Firmware the blink rhythm increases to approximately 5 Hz     If the LED remains off  then there is a defect of the Gateway     If a fieldbus Protocol Task recognizes a para
11. metrizing error  the Task is displayed  by the RUN LED in accordance with the following figure     If there is no error and communication could be started  then the RUN LED is  switched on     If the communication operation is blocked  the the RUN LED remains off     start  1 sec     sign    start   sign    databits with separation sign   gt   lt                                                                                          RCS Task1 Task2 Task3 Task4 Task5 Task6 Task 7  with without without with without with with not  DBM  Error Error Error Error Error Error con   Error figured    Display of the tasks that have indicated a parametrizing error    Copyright   Hilscher Gesellschaft f  r Systemautomation mbH   De PK V50 2EN    General Device Description 17    3 5 Mechanical Dimensions    The Gateway is built into an aluminum profile housing  This permits direct instal   lation into the switching cupboard on a carrier rail  TS35 according to DIN EN    50022   The mechanical dimensions and the allocation of the pins are shown in  the following figures                 E  y  e       SS                                  FIELDBUS    Front view with pin arrangement on the Gateway          Side view of the Gateway for clipping on to a carrier rail    Copyright   Hilscher Gesellschaft f  r Systemautomation mbH   De PK V50 2EN    Appendix    4 Appendix    4 1 Technical Data    Processor  Memory structure  Ethernet interface    Fieldbus interface    Serial interface  Diagnostic in
12. oard with a power supply circuit with  DC DC transformers in which all the required auxiliary voltages are created  The  fieldbus communication interface is based on the basic circuit board  too     The Elan SC520 processor board is inserted into the basic circuit board  It con   tains a built in timer  interrupt  and DMA Controller and thus only requires few  external modules  The computing power is adequate for processing even large  quantities of data  Furthermore  the processor ensures efficient software develop   ment in a high level language  The firmware and the configuration data are stored  in a FLASH EPROM  This can be programmed within the switching and retains  its data even when the operating voltage is switched off     The proper function of the Gateway and its internal operating voltage is monito   red by a Watchdog circuit  In the case of error it triggers a Reset at the processor     The internal supply voltage is generated by means of a switched mode regulator   Its input voltage is filtered via a current transformed toroidal choke and filter ca   pacitors  A transient diode is available as spike and polarity reversal protection   In the case of malfunction  a semiconductor fuse switches the device down to a  low residual current until the malfunction is cleared  This means that the chan   ging of an internal sensitive fuse is dispensed with  Besides this  a charging ca   pacitor is available that blocks the voltage dips that occur in the switching of  fuses
13. terface    LED displays    Operating voltage  Power consumption  Operating temperature    Protection    18    586 133 MHz  16 MByte DRAM  16 MByte FLASH  potential free  10  100MBaud  10 100BaseT   RJ 45    potential free    RS485   12 MBaud PKV 50 DPM  ISO11898   1 MBaud PKV 50 COM  ISO11898   500 kBaud PKV 50 DNM    non isolated RS232C    Operation and communication readiness of the Gate   way  error on the serial interface or freely programma   ble by the user     18 30 V   max  250 mA at 24 V  0   C   50  C   IP20    Dimensions  L x W x H  105 x 44 x 105 mm    Installation    DIN rail EN 50022    Copyright   Hilscher Gesellschaft f  r Systemautomation mbH   De PK V50 2EN    
14. that appears  now     Copy to PKV x     Source  PC     n    Destination  PKV       indows s  E              osnsensssssssnessussssussssssnsene       Execute after download             Evecute etter PRV baat    Download                    Dialog for loading files on to the PKV 50 Gateway    The path and name can be entered directly into the Source  PC  text field or se   lect the path and file via the     button  The Destination  PKV  field cannot be  edited at present  All the files to be copied are read into the Windows directory of  the Gateway  According to requirements  now mark the buttons Save persistent   Execute after download and Execute after PKV boot  Now activate the Down   load button and the software is transferred to the Gateway     Copyright   Hilscher Gesellschaft f  r Systemautomation mbH   De PK V50 2EN    General Device Description 9    3 1 2 Loading Files on to the Host PC    It is also possible to load files from the Gateway on to the Host PC  For this pur   pose select the Copy to PC entry in the File menu     Copy To PC          Dialog for loading files from the PKV 50 Gateway to the Host PC    Now the path of the file that is to be loaded can be entered directly into the Sour   ce  PKV  field or the contents of the FLASH can be viewed via the     button and  a file can be selected     The target place and target name can be entered now in the Destination  PC   field or selected via the     button     After activating the Upload button  the file is loa
15. vious that Ethernet with the TCP IP  protocol from the classical conductor field is moving continuously forward into  the fieldbus region  Although attempts are being made to lead Ethernet up to the  individual I O modules  yet neither all the technical aspects been satisfactorily  solved nor can it be realized with a sufficient effort     This trend is further strengthened by the requirement for unbroken communicati   on from the office world up to the individual data point in the industrial installati   on  Remote maintenance via the Internet is the buzzword now     This is where our fieldbus Gateway PKV 50 comes into its own  It connects the  Internet  Ethernet world with the harsh industrial environment of established  fieldbus technology     It consists of a Master interface connection  which  by means of one of the stan   dardized fieldbus systems  exchanges data between the connected I O devices and  the internal process data memory  This data can be accessed for reading and wri   ting by means of TCP IP telegrams     The Microsoft Windows CE operating system is used on the Gateway  Here   further tasks  such as SoftPLCs  are simply added in order to incorporate extensi   ons of the functions  The development system is economical to build up and  many engineers are familiar with the development environment  All our inter   faces are open so that the experienced user can also bring his own applications in   to use on the Gateway     A further highlight is the integrated
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Gainward 4260183362425 NVIDIA GeForce GTX 570 1.25GB graphics card  MOTTI USER'S GUIDE version 3.2.1  MANUEL D`INSTALLATION ET D`UTILISATION    パワーコンディショナ取扱説明書  Manual Técnico DZ Condominium SP Jet Flex Z17 - Rev1.indd  NBDVR402G Manuel d`Utilisation (Français R06).cdr      USER'S MANUAL USER'S MANUAL    Copyright © All rights reserved. 