ioLogik E2240 Series User`s Manual

image

Contents

1. CI Overview a Basic Settings O Enable the accessible IP list Disable will not allow all IP s connection request 0 Network Settings No Active IP Address Netmask ao I O Settings k o NS System Management CO ccessible IP Settings O A SNMP Agent 3 O CO Network Connection 4 O a o Lem 5 o 9 Change Password 6 o dJ Load Factory Default Save Restart j LI 8 O 9 O 10 O You may add a specific address or range of addresses by using a combination of IP address and netmask as follows To allow access to a specific IP address Enter the IP address in the corresponding field enter 255 255 255 255 for the netmask To allow access to hosts on a specific subnet For both the IP address and netmask use 0 for the last digit e g 192 168 1 0 and 255 255 255 0 To allow unrestricted access Deselect the Enable the accessible IP list option Refer to the following table for additional configuration examples Allowed Hosts IP address Netmask Any host Disable 192 168 1 120 192 168 1 120 255 255 255 255 4 5 ioLogik E2240 User s Manual Using the Web Console Allowed Hosts IP address Netmask 192 168 1 1 to 192 168 1 254 192 168 1 0 255 255 255 0 192 168 0 1 to 192 168 255 254 192 168 0 0 255 255 0 0 192 168 1 1 to 192 168 1 126 192 168 1 0 255 255 255 128 192 168 1 129 to 192 168 1 254 192 168 1 128 255 255 255 128 SNMP Agent On the SNMP Agent page you may enable SN
2. 2 8 Host 192 168 127 3 Gp ioLogik AB 192 168 127 254 E2240 Enable Logic IF THEN HIT aro l io Rawle 81T 140 0 y o Rawie x 2 alo l io Rawi x 27 40 0 ilo Rawy 3T falo l io Rawtc x 31 40 0 y 0 Rawfe v Relation between conditions JAND 28 IB eme Equivalent Logic Statement J OK X Cancel E2240 I O syne rate 26 sec f Ready 115200 None The configuration window is where the rule is defined There are two types of rules that can be defined Logic rules and peer to peer I O rules Logic rules are used for AI event based triggers whereas peer to peer I O rules are used for mapping I O channels between two ioLogik E2240 servers The Equivalent Logic Statement at the bottom shows a real time text based summary of the rule that you are defining It can be a useful way to make sure that the rule is designed as you intended A ATTENTION When configuring input or output control or response values you must select the unit of measurement before entering a value If you select a unit of measurement after entering a value the value will not be retained Also when an I O channel is being used in a Click amp Go Logic rule the channel s range and units may not be modified Defining Logic Rules IF conditions Under the IF column you may set up to 3 sensor conditions that must be satisfied for the actions under the THEN column to take place Use the pull downs to specify the condi
3. Address 0x0015 0x0016 0x0017 0x0018 0x0019 Ox001A 0x001B Modbus TCP Address Mappings Data Type CHI AI PowerOn Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value CH2 AI PowerOn Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value CH3 AI PowerOn Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value CH4 Al PowerOn Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value CH5 AI PowerOn Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value CH6 AI PowerOn Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value CH7 AI PowerOn Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value ioLogik E2240 User s Manual Address 0x001C 0x001D 0x001E 0x001F 0x0020 0x0021 0x0022 Modbus TCP Address Mappings Data Type CHO AI Safe Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value CH1 AI Safe Range 00 150 mV
4. 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value CH2 Al Safe Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value CH3 AI Safe Range 00 150 mV 01 500 mV 02 5V 03 10V 0 20 mA 4 20 mA 04 05 Others return Illegal Data Value CH4 AI Safe Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value CH5 AI Safe Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value CH6 AI Safe Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value ioLogik E2240 User s Manual Modbus TCP Address Mappings Data Type 0x0023 1 word CH7 AI Safe Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value Function 8 Data Field Reguest Data Field Response 0x0001 OxFF00 Echo Request Data 0x0001 OxSSAA Echo Request Data Reset with Factory default B 7 C Used Network Port Numbers E2210 E2240 Network Port Usage Port Type Usage 80 TCP WebServer_ _ 68 up BOOTPC 68 up DHCP 69 UDP Export import file Active Message Default SNMP MIB Il RFC1213 MIB Il Supported SNMP Va
5. 5V 10V ioLogik E2240 User s Manual Using ioAdmin ioLogik E2240 Network I O Server Configuration Configuration File 10Admin allows the entire Date 2006 12 7 Time 09 38 28 AM configuration of the ioLogik E2240 to be saved as a file The O file is viewable as text and can MOD TYPE E2240 Active Ethernet I O Server 8AI 2A0 MOD LOC serve three purposes MOD_NAME 2 I O Configurations e asarecord or backup of configuration Ett o AI01 5 4 20mA e asa template for the AI02 3 10V AI03 3 10V configuration of other servers aro4 3 4 10v AI05 3 10V e asaquick reference guide for aroe 3 10v 107 3 10 you to configure Modbus A E drivers in a SCADA system A000 1 4 20mA A000 PWN 4095 RAW A000 SAFE 4095 RAW A001 1 4 20mA A001 PWN 0 RAW A001 SAFE O RAW The file includes the following 3 Modbus address table information CHANNEL I O TYPE MODBUS REFERENCE MODBUS ADDRESS Dec Hex 1 file title date and time AIOO Input 30001 0000 0x0000 AI01 Input 30002 0001 0x0001 2 model information AIO2 Input 30003 0002 0x0002 AI03 Input 30004 0003 0x0003 3 Modbus address AI04 Input 30005 0004 0x0004 ioAdmin Main Screen Main Screen Overview This is ioAdmin s main screen The main window defaults to the I O Configuration tab which displays a graphic of the ioLogik E2240 and the status of every I O channel below it The other t
6. 0 20 mA and 4 20 mA AI Channel 0 Settings Input Range 10 4 10 0 2 0rn 5 e 2OmA AO Channels On the AO Channels page you may configure each AO analog output channel by clicking on the channel The available options are 0 10V and 4 20 mA You may use the Power On field to specify the channel s initial value when the ioLogik E2240 is powered on and the Safe Status field to specify channel s value when the ioLogik E2240 enters Safe Status Note that Safe Status 1s 4 4 ioLogik E2240 User s Manual Using the Web Console controlled by the Host Connection Watchdog which is disabled by default If the Host Connection Watchdog is disabled the ioLogik E2240 will never enter Safe Status and your Safe Status settings will have no effect AO Channel 0 Settings Output Range Output Value 1 Current Range 4 20ma z 2 Power On Setting i 3 Safe Status Setting Hosa Submit Close System Management Accessible IP Settings On the Accessible IP Settings page you may control network access to the 10Logik E2240 by allowing only specified IP addresses When the accessible IP list is enabled a host s IP address must be listed in order to have access to the ioLogik E2240 Total Solution for Industrial Device Networking Al Main Menu E2240 s Accessible IP Settings
7. Data Value 0x000C 1 word CHO AI Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value 0x000D 1 word CHI AI Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value ioLogik E2240 User s Manual Address 0x000E Ox000F Ox0010 0x0011 0x0012 0x0013 0x0014 Modbus TCP Address Mappings Data Type CH2 Al Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value CH3 Al Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value CH4 Al Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value CH5 AI Range 00 150 mV 01 500 mV 02 5V 03 10V 0 20 mA 4 20 mA 04 05 Others return Illegal Data Value CH6 AI Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value CH7 Al Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value CHO AI PowerOn Range 00 150 mV 01 500 mV 02 5V 03 10V 04 0 20 mA 05 4 20 mA Others return Illegal Data Value ioLogik E2240 User s Manual
8. Ethernet MAC Address 00 90 e8 0d 0e 90 RS 485 Setting 115200 n 8 1 CJ Change Password Load Factory Default Save Restart s di EA a s ss se Navigation Panel The left panel is the navigation panel and contains an expandable menu tree for navigating among the various settings and categories When you click on a menu item in the navigation panel the main window will display the corresponding options for that item Configuration changes can then be made in the main window For example if you click on Basic Settings in the navigation panel the main window will show a page of basic settings that you can configure You must click on the Submit button after making configuration changes The Submit button will be located at the bottom of every page that has configurable settings If you navigate to another page without clicking the Submit button your changes will not be retained Submitted changes will not take effect until they are saved and the ioLogik E2240 is restarted You may save and restart the server in one step by clicking on the Save Restart button after you submit a change If you need to make several changes before restarting you may save your changes without restarting by selecting Save Restart in the navigation panel If you restart the ioLogik E2240 without saving your configuration the ioLogik E2240 will discard all submitted changes ioLogik E2240 User s Manual Using the Web Console Basic Set
9. Monitor POPUP PREP RPEP ERE R ERE EE EERE ERE k REESE EEE S Ma DEG BES FES pda pla vka via dti is i ittittisiittjjiH sITTTTTTTTTTTTTTTTTTTTTTTTTTTTTTT 20 000 mA 10 G40 LA O OA4 SE Coris Range Settings Input Range T Apply to all channels E2240 I O sync rate 23 sec 3 7 ioLogik E2240 User s Manual Using ioAdmin Configuring Analog Output Channels The ioLogik E2240 is equipped with 2 AO analog output channels that can be set individually to 0 10V 4 20 mA You may also set all channels at once using the Apply to all channels checkbox 1 Range Settings Output Range 4 20 mA v 2 Power On Settings Output Value 4095 0 4095 3 Safe Status Settings Output Value 4095 0 4095 T Apply to all channels Power On Settings Use this field to set the initial value for the AO channel when the ioLogik E2240 is powered on The Power On Settings field uses raw data values If you do not know how to translate the raw data values into real values use the Test function for assistance Safe Status Settings Use this field to specify how the AO channel responds to a break in network communication When the network connection is lost for the amount of time specified in the Host Connection Watchdog the ioLogik E2240 enters Safe Status and the AO channel s Safe Status settings will go into effect Note that the Host Connection Watchdog is disabled by defaul
10. Settings tab Enter your own e mail address in the From Address field Under Mail Server Settings you must configure the IP address of the SMTP server with your username and password Since the ioLogik E2240 supports DNS you may enter the domain name of the SMTP server 5 8 ioLogik E2240 User s Manual Click amp Go Logic Mail Content Settings Mail Subject amp Mail Content lt p Keyword Lookup Mail Address Settings Name Mail Address De Available receiver s list Receiver s list Name e Mail Address Name e Mail Address From Address Mail Server Settings SMTP Server Address IP Login Name Login Password X Cancel Defining Peer to Peer I O Rules A basic use of analog input and output is to connect a sensor to a dial The sensor is the analog input with status determined by temperature or other measurement and the dial is the analog output with status controlled by the sensor The peer to peer I O function allows this operation to be mapped over Ethernet from an analog input on one ioLogik E2240 to the analog output on another ioLogik E2240 This allows a sensor in one location to monitor or have direct control of a hardware dial in another room building or even city Peer to peer I O can be used for simple one to one mapping but also supports one to many and many to many mapping A single analog input channel can be mapped to up to fi
11. User s Manual Introduction With LCD Module unit mm 9 TAR in pu 000000 a O co O NG pi 000000000000000000000000 maga 1 ioLogik E2240 User s Manual Introduction Hardware Reference Panel Guide 24 VDC power input accepts 12 to 48 VDC RS 485 cascading interface Power Ready Serial LEDs Optional LCM Rose RS 485 baudrate dial RJ45 Ethernet EEE TB1 TB2 System bus 009999 V V FG D D SG s e 5 sm or se MOXA ioLogik E2240 Ethernet I O Server 1 T louti I O module latch ATAT i 3 LJ 0009000000000 TB3 VO status LEDs BRE gt Release button for Removable terminal block for I O points cascaded O module 3 81 mm max 14 AWG NOTE The reset button restarts the server and resets all settings to factory defaults Use a pointed object such as a straightened paper clip to hold the reset button down for 5 sec The RDY LED will turn red as you are holding the reset button down The factory defaults will be loaded once the RDY LED turns green again You may then release the reset button LED Indicators Ethernet Connected to a 10 Mbps Ethernet connection Ethernet Connected to a 100 Mbps Ethernet connection flashing Transmitting or receiving data pred Power is on off Power is off a System error ystem A eee TITO TUT flashing Serial port is receiving transmitting E I O AI x8 pins OFF s
12. amount of time specified in the timeout the Host Connection Watchdog will switch the 1oLogik E2240 to Safe Status and the AO channels will reset to their Safe Status settings By default the Watchdog is disabled To enable the Watchdog make sure Enable Host Connection Watchdog is checked set the Timeout value then click the Update button AH A e Host Connection Monitor Enable Host Connection Watchdog Timeout value a sec Update Refresh MAA vm a After the Watchdog is enabled the ioLogik E2240 will enter safe status if the network connection is lost Once the connection has been restored you will need to return to the Watchdog Tab in order to exit safe status There will be a message saying Host Connection Lost indicating that the server is in safe status Click Clear Alarm to exit safe status and return to normal operation Click amp Go Logic Tab The Click amp Go Logic tab is where administrators set up the 10Logik E2240 s active I O messaging program Instead of the server reacting passively to a host s repeated polling requests for I O data the 10Logik E2240 server proactively sends I O information to the host when an I O channel satisfies conditions that you specify Click amp Go Logic was developed by MOXA to provide a powerful and 3 11 ioLogik E2240 User s Manual Using ioAdmin easy to use tool for defining the conditions under which I O information will be sent over the network Pleas
13. to a host computer rather than remotely over the network 2 Configure the host PC s IP address to 192 168 127 xxx xxx from 001 to 253 In Windows you will need to do this through the Control Panel ioLogik E2240 Default IP Address Default Netmask Default Gateway 192 168 127 254 255 255 255 0 None 3 Use 10Admin or the web console to detect the ioLogik E2240 Once the ioLogik E2240 has been detected modify the settings as needed for your network environment then restart the server Setting the RS 485 Baudrate The RS 485 port on the 1oLogik E2240 is reserved to chain another RS 485 I O server The RS 485 port can run Modbus RTU or I O command sets The baudrate is set by a physical dial on the back of the ioLogik R2110 The default settings are baudrate 115200 parity check N data bits 8 and stop bit 1 Baudrate for RS 485 Dial setting and corresponding baudrate parameters are N 8 1 0 115200 1 57600 2 38400 3 19200 4 9600 5 4800 6 2400 7 1200 Remember to restart the ioLogik E2240 after making any changes to the RS 485 baudrate Adding More I O Channels A cost effective way to add more I O channels to your ioLogik E2000 I O server is to attach the appropriate 10Logik R2000 I O server The two servers can be snapped together using the RS 485 2 2 ioLogik E2240 User s Manual Initial Setup system bus connector as shown in the following figure Additional analog I O channels are obtained by at
14. 0Logik E2240 1f you need to reset the ioLogik E2240 due to a forgotten password or for other reasons Load Factory Default This function will reset all of the ioLogik E2240 s settings to the factory default values All previous settings including the console password will be lost Save Restart If you change the configuration do not forget to reboot the system 4 7 5 Click amp Go Logic Click 8K Go Logic was developed by MOXA to provide an easy way to program your ioLogik E2240 for active I O messaging In the chapter we will show you how Click amp Go Logic works and how to use it to develop your active I O messaging program The following topics are covered in this chapter Q Overview Q Features Q Click amp Go Logic Basics gt Working with Rules Q Defining Logic Rules gt IF conditions gt THEN actions Q Defining Peer to Peer I O Rules gt Configuring Input for Peer to Peer I O gt Configuring Output for Peer to Peer I O Q Working with Click amp Go Rulesets gt Activating the Ruleset gt Ruleset Management Bar gt Ruleset Import Export ioLogik E2240 User s Manual Click amp Go Logic Overview The ioLogik E2240 s Active Ethernet I O system eliminates the need for host computers to continually poll I O devices for status Instead the server itself is able to monitors the status of each I O device and take the appropriate action when the I O status satisfies a user defined condition For example the ioLog
15. 2 168 127 254 BY E2240 TO syne rate 2 sec Ready 115200 None 8 1 0 00 03 08 EF 09 17 22 Server Info Tab Server information such as firmware version is displayed in the Server Info tab 9 1 0 Configuration BE Server Info Server Settings EX Message Monitor Read Vendor ID Read Unit ID for MODBUS RTU Read Vendor Name Read Product Name Read Firmware Revision Read Firmware Release Date Read Number of TCP connection 0x0100 Read Ethemet Interface Speed 10 100 00 90 E8 0D DE 90 Read MAC Address US Read LCM Detection Read LCM Firmware Revision Read LCM Firmware Release Date Read i System Elapsed Time in sec Read ADC version Read write IP Address Read Write Subnet Mask Read Write Gateway Read Write Modbus TCP Alive Check Timeout Read Wiite System Local Time Read Write System Time Zone Read wrte Time Server Address Read write DNS Server Address Read wite _DNS2 Server Address ioLogik E2240 User s Manual Using ioAdmin server Settings Tab General The Server Settings tab is where you log in as an administrator This is required in order to gain access to the 10Logik E2240 configuration options If no administrator password has been set up simply click on Login and leave the Password for entry field blank Please refer to
16. 60 Hz Zero drift Span drift Load resistor Power Requirements Power input Power consumption Field power Mechanical Specifications Wiring Environmental Operating temperature Storage temperature Shock None 8 l None 1200 to 115200 bps Modbus RTU Yes 8 16 bit 150 mV 500 mV 5 V 10 V 0 to 20 mA 4 to 20 mA 16 bit integer 0 1 FSR 25 C 0 3 FSR 10 60 C 10 samples sec voltage 6 samples sec current 900 kQ 102 Q 3K VDC 2 12 bit 0 to LOV 4 to 20 mA 16 bit integer 0 1 FSR 25 C 0 3 FSR 10 60 C 95 dB min 9 wV C 25 ppm C current load lt 250 2 voltage load gt 1 MQ 24 VDC nominal 12 to 48 VDC 282 mA 24 VDC typical 24 VDC nominal up to 36 VDC I O cable max 14 AWG 10 to 60 C 14 to 140 F 5 to 95 RH 40 to 85 C 4 to 185 F 5 to 95 RH 1EC60068 2 27 1 4 ioLogik E2240 User s Manual Introduction Freefall IEC60068 2 32 Vibration IEC60068 2 6 Agency Approvals EMI FCC Part 15 CISPR EN55022 Class A EMS IEC61000 4 2 ESD level 2 3 IEC61000 4 3 RS level 2 IEC61000 4 4 EFT level 2 IEC61000 4 5 Surge level 3 IEC61000 4 6 CS level 2 IEC61000 4 8 PM level 1 IEC61000 4 11 Dip Safety UL 508 Warranty 2 years Physical Dimensions Without LCD Module unit mm 45 39 10 7 000000000000000000000000 6 46 51 A 93 02 4651 9 5 ioLogik E2240
17. I O Click amp Go s intuitive graphical interface lets administrators uses simple IF THEN statements as rules to determine how the Active Ethernet I O server responds to different I O conditions For example the Active Ethernet I O server could be programmed to adjust an attached voltage dial as well as send an e mail or SNMP trap when an attached temperature sensor reaches a certain value Click amp Go makes it easy to define a set of these rules which will become the basis for your Active Ethernet I O system 1 2 ioLogik E2240 User s Manual Introduction Optional Liquid Crystal Display Module LCM As a MOXA Easy View product the ioLogik E2240 supports an optional hot pluggable Liquid Crystal Display Module LCM for field management and configuration The module can display network and I O settings such as analog input value and range The ioLogik E2240 s IP address and netmask may also be configured using the module and one module can be used to maintain and configure all your Easy View devices Product Features Click amp Go logic builder for easy configuration of your Active Ethernet I O system High speed active I O messaging 8 channels of mV V mA analog input A hwith wire off detection at 4 to 20 mA 2 channels of analog output AO for voltage or current actuator control 10 100 Mbps Ethernet with Modbus TCP protocol connecting up 10 hosts Bundled Windows utility and quick programming library for VB VC BCB Supports R
18. Introduction The ioLogik E2240 is a stand alone Active Ethernet I O server that can connect sensors for automation applications over Ethernet and IP based networks The following topics are covered in this chapter U Overview gt Traditional Remote I O gt Active Ethernet I O gt Click amp Go gt Optional Liquid Crystal Display Module LCM Product Features Packing List Product Specifications Physical Dimensions DODODUO Hardware Reference gt Panel Guide gt LED Indicators ioLogik E2240 User s Manual Introduction Overview i 9 i na mak wal Win sa F o T Yi trom SE dil MO 53 LL COO yee 2 00 Om MAAL A E Gg m a ze OM EN ny ES Y CI Loz 4p cr ga shown with and without optional LCM The ioLogik E2240 is part of the E2000 series of 1oLogik Active Ethernet I O servers which are designed for intelligent pro active status reporting of attached sensors transmitters transducers and valves over a network The 1oLogik E2240 also supports an optional hot pluggable Liquid Crystal Display Module LCM as shown above to view and configure device settings Traditional Remote I O Ethernet remote I O solutions have been on the market for a long time Traditional solutions are passive in the sense that I O servers wait passively to be polled by a host computer The response time in this type of setup however tends to be on the order of seconds The passive remot
19. J Main Menu E2240 Overview i Basic Settings LCM Module Information Hi LCM Module H i mi tacsa Settings LCM Module attached ao I O Settings Firmware Yersion 1 0 0 0 eo System Management Firmware Release Date 03 01 2006 fa Load Factory Default E Save Restart 4 6 ioLogik E2240 User s Manual Using the Web Console Change Password Total Solution for Industrial Device Networking J Main Menu E2240 1 Overview Basic Settings Network Settings a 1 0 Settings HI System Management New password CJ LCM Retype password Change Password Password Old password Hl Load Factory Default O Save Restart For all changes to the ioLogik E2240 s password protection settings you will first need to enter the old password Leave this blank if you are setting up password protection for the first time To set up a new password or change the existing password enter your desired password under both New password and Confirm password To remove password protection leave the New password and Confirm password fields blank A ATTENTION If you forget the password the ONLY way to configure the ioLogik E2240 is by using the reset button to load the factory defaults Before you set a password for the first time it is a good idea to export the configuration to a file when you have finished setting up your ioLogik E2240 Your configuration can then be easily imported back into the 1
20. M Toggle HEX 10 DestIP 0000 X ce ioLogik E2240 User s Manual Click amp Go Logic SNMP trap Select SNMP trap along with a trap number between 1 and 20 You may need to consult with your network administrator to determine how trap numbers will be used and defined in your network Click the memo icon to specify up to 10 IP addresses to receive the SNMP trap You can also bind the status of up to three I O channels within each trap THEN 1 v SNMPtrap Bo 2 v Messaging y a 317 Emi z a Binding Yariables pre Y Manager list global Manager IP Manager IP PO Manager IP PO Manager IP fT O Manager IP Manager IP FP OS Manager IP Ho Manager IP EU Manager IP HU Manager IP O A O ENS i o E mail Select E mail to send a user defined email to the specified addresses Click the memo icon to enter the desired message and the intended recipients Dynamic fields such as time date IP address and I O status may be inserted in your message by clicking on the Keyword Lookup button To add a recipient you must first add the recipient s e mail address to the Available receivers list You may then use the finger icons to move e mail addresses to and from the Receivers list To edit an e mail address click on the memo icon Note that the Available Receivers list will already contain a list of names if you provided the DNS server information in the Network
21. MP and set the read and write community strings The 10Logik E2240 provides SNMP v2 Simple Network Management Protocol to allow monitoring of network and I O devices with SNMP Network Management software It is useful in building automation and telecom applications gt Total Solution for Industrial Device Networking Al Main Menu E2240 T Overview Ga Basic Settings ea Network Settings SNMP Agent Configurations HH 1 0 Settings SNMP Enable O Disable Bey System Managements Read Community Name public CO Accessible IP Settings Write Community Name public a SNMP Agent Contact i a Network Connection Location im LCM m Change Password CI Load Factory Default Save Restart Network Connection LCM On the Network Connection page you may view the TCP connections from other hosts This may assist you in the management of your devices Total Solution for Industrial Device Networking SI Main Menu E2240 a Overview T Basic Settings ao Network Settings ae 1 O Settings aa System Management a Accessible IP Settings A SNMP Agent Network Connection Total connection s ng Host Address 192 168 127 1 Connect Type HTTP ia Change Password 2 Load Factory Default Y SavejRestart If you have installed the optional LCM you may view the status and firmware details on the LCM page Total Solution for Industrial Device Networking S
22. S 485 modules for expandable I O Support for SCADA software such as Wonderware InTouch and GE Intellution 1F1x32 SNMP for system management and I O status Remote management over the network including firmware updates Supports use of TFTP server to import configuration Configurable power on and safe status AO modes Optional hot pluggable LCM for status display and configuration NIST traceable calibration Packing List The 1oLogik E2240 is shipped with the following items Standard Accessories e ioLogik E2240 Active Ethernet I O Server e Document amp Software CD Optional Accessories e LDP1602 ioLogik Liquid Crystal Display Module LCM NOTE Notify your sales representative if any of the above items are missing or damaged ioLogik E2240 User s Manual Introduction Product Specifications LAN Ethernet Protection Protocols Serial Interface Serial line protection 10 100 Mbps RJ45 1 5 KV magnetic isolation Modbus TCP TCP IP UDP DHCP Bootp SNMP MIB for I O and Network HTTP RS 485 2 wire Data Data GND 15 KV ESD for all signals Serial Communication Parameters Parity Data bits Stop bits Flow control Speed Protocol Built in RTC Analog Input Inputs Resolution Input range Data format Accuracy Sampling rate all channels Input impedance Built in resistor for current input Optical isolation Analog Output Outputs Resolution Output range Data format Accuracy CMR 50
23. Same as local hode fo chet Bytes sent 5401 Im 3 15 4 Using the Web Console You may use the ioLogik E2240 s built in web console to configure many options The following topics are covered E U a LUUL Introduction to the Web Console Basic Settings Network Settings gt General Settings gt Ethernet Configuration gt RS 485 Settings T O Settings gt AI Channels gt AO Channels System Management gt Accessible IP Settings gt SNMP Agent gt Network Connection LCM Change Password Load Factory Default Save Restart ioLogik E2240 User s Manual Using the Web Console Introduction to the Web Console The ioLogik E2240 web console is a browser based configuration utility When the 1oLogik E2240 is connected to your network you may enter the server s IP address in your web browser to access the web console Note that although most configuration options are available in the web console some settings are only available through ioAdmin Furthermore the web console can be disabled under Web Access Settings in ioAdmin If you are unable to access the web console check the Web Access Settings in ioAdmin Total Solution for Industrial Device Networking PN RS Welcome to ioLogik Series JA Basic PELIN Active Remote I O Server 19 Network Settings Model Name E2240 Ca 1 0 Settings Serial Number 9 0 System Management Firmware Version 1 1 0 0 E LCM Ethernet IP Address 192 168 127 254
24. Settings The ioLogik E2240 is configured with the following factory defaults Default IP address Default Netmask Default Gateway Communication watchdog Modbus TCP alive check Timeout AI Input Range AO Output Range AO Safe Status Password Module Name Module Location SNMP Community Contact Location 192 168 127 254 255 255 255 0 0 0 0 0 Disable 60 secs 10 to 10V 0 to 10V Off 0V NONE NONE NONE Enable Public NONE NONE F Pinouts and Cable Wiring Ethernet Port Pinouts Serial Port Pinouts E2240 RS 485 Network Adapter Pin Assignment Vr V FG Dr D SG Pin Assignment of Terminal Blocks Ethernet Power RS 485 TB1 TB2 1 Te 2 Tx 3 Res i ERSS RES 6 Rx V V FG D D SG I O left to right mil Vin0 Vind4 Vin5 mnl CO CA AC CA 7 CT A 5 m Signal Vin6 Vin6 Vin7 Vin7 Vout0 Vout0 lout0 lout0 Vouti Voutl lout1 lout1 DOGOOODODOOOGOOOOOOCOODOGOOO ioLogik E2240 Series User s Manual Pinouts and Cable Wiring I O Device Wiring Analog Input Analog Input Analog Output Voltage Current 0 10V 4 20MA 150mV pa 500mV E 5V 10V AO Schematic AIN Schematic voltage mode Al Al IIN Schematic current mode Al 125 ohm Al F 2 G Restriction of Hazardous Substance Material Declaration Electronic information products may contain hazardous materials such as lead m
25. abs in the main window take you to server and network settings and further functions are available when you log on as an administrator Note that configuration options are not available until you log on as an administrator Fie busem Sgt Help rE Host 921681271 ZE iologik BE Mira ars L zan 1 0 Configuration p Server Info e Server Settings ES Message Monitor 999900 2 SRGRRRRRRRRRRRRR RRR kk RRR RRR REESE We We FG De D SG Osi gm tere ray te MOXA ioLogik SD OD ID OD GOD ADD 1359291210105 11415554 PTI Ny AAA AAA AAA RAR AAA RARA RAMA 000000000000000000000000 Al 01 0 237 Y 0 234 Y 0 246 Y A0 01 Al 02 10 0 237 V 0 217 Y 0 242 Y Al 03 10 0 237 V 0 236 V 0 239 V Al 04 10 0 237 V 0 231 Y 0 245 V Al 05 7 10Y 0 237 V 0 234 Y 0 245 V Al 06 10 0 237 V 0 229 Y 0 244 Y Al 07 2 10Y 0 237 Y 0 236 V 0 245 Y 6 E2240 10 syne rak 11508 None LA GO BF abe ioLogik E2240 User s Manual Using ioAdmin ioAdmin Main Screen Title Menu bar Quick link Navigation panel Main window Sync rate status 7 Status bar Wiring Guide 10Admin provides a wiring guide to the ioLogik E2240 You may access the wiring guide by right clicking the graphic of th
26. ake several minutes K Port Settings ii Exit Found adapter s D 10 server s were found Model IP Address Port MAC Address Unit ID Description ioLogik E2240 User s Manual Initial Setup If ioAdmin is unable to find the 10Logik E2240 there may be a problem with your network settings Please verify that your host and the ioLogik E2240 are on the same network segment ATTENTION 10Admin does not support dual LAN architecture If your PC is using dual LAN architecture please deactivate the LAN that is not being used by the ioLogik E2240 when using 10Admin 3 Monitor I O status Once the ioLogik E2240 is found by 10Admin you may view the status of all VO devices on 10Admin s main screen ll File System Sort Help R g 2 8 Host 192 168 127 1 ioLogi HB 192 168 127 254 4 1 0 Configuration EE Server Info KA Server Settings Message Monitor 11990900 Mia 10 0 237 V 0 234 Y 10 0 237 V 0 217 Y 10 0 237 V 0 236 V 10 0 237 V 0 231 Y 10 0 237 V 0 234 V 10 0 237 V D 229W 10 0 237 V 0 236 V E2240 1 0 sync rate 2 sec Ready 115200 None 8 1 0 00 03 08 ES 09 17 22 You may now use 10Admin to setup or configure your the ioLogik E2240 3 Using ioAdmin This chapter goes over the functions available in ioAdmin the ioLogik E2240 s main configuration and management utility The f
27. and as an output module simultaneously within one rule This may be done only by using at least two rules one rule to configure input module operation and another rule to define output module operation Configuring Output for Peer to Peer I O Configuring the peer to peer I O output module will use up one Click amp Go rule for each output channel that mirrors a remote input channel In the Click amp Go tab open a new rule s configuration window and enable peer to peer I O Select Output channel and provide the AO channel that will mirror the remote input channel the IP address of the input module 1 e the remote ioLogik E2240 and the AI channel that will be mirrored m da ora For example AO 0 on the output module can be configured to mirror AI 0 on the input module If AL 0 on the input module changes to 5 mA AO 0 on the output module will also change to 5 mA Make sure that the remote 10Logik E2240 has been configured to mirror its input channels to this 10Logik E2240 s IP address Also any channels used for peer to peer I O must operate in 4 20mA on both the input and output modules Channels that are not operating in 4 20mA will not be available for peer to peer I O f Enable peer to peer 1 0 r annels m CI Output channel 0 0 mirror from remote P 192 168 127 254 channel Al 0 ki Once both the input and output sides have been configured you may begin peer to peer I O operation by activating the rulesets on bo
28. annel Select AO 0 or AO 1 in order to have that channel be automatically set to a specific value You may enter the value in RAW or V mA 5 6 ioLogik E2240 User s Manual Click amp Go Logic Active Message Select Active Message for active I O messaging over TCP or UDP Click the memo icon to configure the message and parameters Note that TCP and UDP cannot be used at the same time within a ruleset all rules must use the same protocol After clicking the memo icon you may enter your desired message in the Message Content window If necessary Dynamic fields such as time date IP address and I O status may be inserted in your message by clicking on the Keyword Lookup button Up to 10 IP destinations for the message can be specified in the Message Receiver list The default Message Port is 9000 and this can be modified as necessary to work with your firewall By default messages are sent in ASCII although 10Admin can display the message in HEX in Message Monitor Message Content Settings PIG Message Content This is ASCI code format which sent at lt TIME a Firmware Update l i Watchdog s Click Go Logic GP Message Monitor UDP TCP QP Keyword Lookup Send as HEX seperated by 47 max chars 200 Hr z z k i This is ASCII code format which sent at 18 03 52 Message Receiver list global Messaging protocol global 1 Dest IP 192 168 127 3 UDP
29. b Access settings for the ioLogik E2240 Y 10 Configuration Server Info Server Settings sla Network KO Firmware Update ek Watchdog on Click amp Go Logic E Message Monitor Number of Modbus TCP connection s 2 IP Settings IP Configuration Static v IP Address fi 92 168 127 254 Subnet Mask 255 255 255 0 Gateway 0 0 0 0 MAC 00 90 E8 0D 0E 90 fe Accessible IP Modbus TCP Alive Check Timeout jv Enable Modbus TCP idle connection timeout interval DNS Settings DNS 1 0 0 0 0 DNS 2 0 0 0 0 E2240 I O sync rate 2fsec Serial Settings Unit ID 1 Baud Rate 115200 Data Bits 8 Stop Bits 1 Parity None Timout ms 2500 f SNMP Settings Y Enable SNMP Read Community pubic Write Community public Contact fo Location fo Web Access Settings V Ena CE Refresh ioLogik E2240 User s Manual Using ioAdmin IP Settings You can set up a static or dynamic IP address for the 1oLogik E2240 as well as the subnet mask and gateway address The Accessible IP screen can be used to control network access to the 1oLogik E2240 and attached sensors Network requests that originate from sources that are not listed in the accessible IP list will be unable to use Modbus TCP or ioAdmin to access the ioLogik E2240 Modbus TCP Alive Check Timeout Settings The Modbus TCP Alive Check Timeout is designed to avoid TCP connection failure When the host is down the 1oLogik E2240 w
30. ccccccnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnononinnnnnnss 3 7 Server Settings Tab Administrator Na GG kninang bh ahat 3 9 Ne nor eo o ora ER A AO en 3 9 Dim ae DOA NA PA 3 10 WV AUC OO MAD ee EE E ado 3 11 Hidro nn 3 11 perver Contex MENU dana nA na a E 3 13 Using the Web Console sisi idad 4 1 Introduction tothe Web Console dd 4 2 Basto Seno as 4 3 NA OE AA ee eee he 4 3 Central CGI So oa ideas acreage eit ee 4 3 Chapter 5 Appendix A Appendix B Appendix C Appendix D Appendix E Appendix F Ethernet CONN eu TA OM aaah hd estates one ren nada eee 4 3 overs ee O PE O O 4 4 KO DONOS a io OR TEE obe AE see ee 4 4 PMG TANT E E a E E E te ita teat a vale Saas eli Ma ej 4 4 AA 4 4 SY tom Manacor 4 5 ACCESS DLE AUP SE ULI OS A A neke ee ek o en 4 5 SNMP ATON iene emer eta cate ny a rt eee a earner a A A 4 6 NGO CONA CCH OM an ei ole gos olje ei oe le meni tral lid ob delilne net aa 4 6 RO 4 6 Chance Pas O haa AA ai ta 4 7 koda Factory Deraul O 4 7 Save NE ei A AE AP A EEA O saunas EMA mannose NE ARENA A RE AP ARA MN 4 7 CICKS GO LOGIC iii io AA oe cad 5 2 OVO AA 3 3 KAG AA ANON ANING NAAN AA ANA AA ANA 5 3 Click SO LOBI O GAAN BANA 5 4 NAA Rules nadando 5 4 Denning GA ALA AA AA 5 5 AN AA AA NM 5 5 PIB INC ACUIONS NAN GANA NN GANANG 5 6 Defining Peer to Peer JO Rules A nn DADAAN 5 9 Contouring Input for Peer to Peer MO aaa Nadaan 5 10 Configuring Output for Peer to Peer I O ccccccnnccncnnnnnnnonnnnnnnnnnnnnnn
31. ction for the specified amount of time By default the Watchdog is disabled When the Watchdog is enabled and a timeout occurs the 10Logik E2240 will enter Safe Status You may use 10Admin to configure how each AO channel responds in that channel s Safe Status settings To enable the Watchdog check off Enable connection watchdog set the timeout value and restart the server With Watchdog enabled the ioLogik E2240 will enter Safe Status after there is disruption in communication that exceeds the time specified Ethernet Configuration On the Ethernet Configuration page you may set up a static or dynamic IP address for the ioLogik E2240 as well as the subnet mask and gateway address Total Solution for Industrial Device Networking A Main Menu E2240 _ Overview T Basic Settings aa Network Settings Ethernet Configurations Ethernet Parameters l m General Settings AO Static v T Ethernet Contiqurationg TP Address EE Ee CO RS 485 Settings Subnet Mask 255 255 255 0 sa I O Settings Gateway 0 0 0 0 ea system Management CO Lem NU Change Password Load Factory Default J Save Restart ioLogik E2240 User s Manual Using the Web Console RS 485 Settings On the RS 485 Settings page you may view the serial communication parameters but no configuration changes are allowed The baudrate may only be configured by the physical dial on the back of the ioLogik E2240 This is a reserved f
32. e 10Logik E2240 in the I O Configuration tab Select Wiring Guide in the submenu to open a help file showing the wiring information and electrical characteristics of the ioLogik E2240 di System Overview Ethernet pin assignment El E 2 3 RX 6 RX AAA UU UCU CUCU UU CRU URRUUUR URES EGU REG Ethernet RS 485 Cascade Port Communication Settings 0 115200ps N81 z z ps loLogik Er 1 57600bps N81 aan ae o 2 38400bps N81 nem lt E 3 19200bps N81 TELE 4 9600bps NS LI 1 5 4800bps N81 DOB00000000000000000000 6 2400bps N81 7 1200bps N81 Wiring Example Analog Input Analog Input Analog Output Voltage Current 0 10V 4 20mA 150mV 500mV 4 20MA ES 5V ka f LSJ 10V A v You may also access the On line Wiring Guide through the Help menu on the menu bar lt MOXA ioAdmin File System Sot Hep 22 S E Host 192 168 127 1 Mc ai ioLogik Wiring Guide for ioLogik4000 SAB 192 1 9 1 0 Configuration g Server Info Server Settings GS Message Monitor jpoooooj Xx AA Ann nn AA AA A AA AA KANA ga Fem BOY Seni Iv ioLogik E2240 User s Manual Using ioAdmin O Configuration Tab General The I O Configuration tab shows the status of every I O channel This is the default tab when you first open 10Admin MOXA ioAdmin File System Sort Help jes a JE Host 192 168 127 1 ESR ioLogik AB 19
33. e I O structure 1s simply inadequate for Data Acquisition and Control DAC systems that require an efficient real time I O solution with a response time on the order of hundredths of seconds Active Ethernet I O MOXA s Active Ethernet I O line was developed specifically to address the limitations of the traditional passive approach Rather than requiring the host computer to poll the I O device server over the network for the status of each I O device an Active Ethernet I O server intelligently sends the host computer status information only under specified conditions This is a report by exception approach which greatly reduces the load on CPU and network resources Network packets are far fewer in number and far smaller in size since I O information is only sent when necessary and only information from the specified I O device is sent Based on field tests of an ioLogik E2000 series server used in an RFID system 50 ms is the typical response time over a 100 Mbps Ethernet network MOXA s active I O messaging system uses TCP or UDP for I O messaging and supports sending messages to up to ten host computers simultaneously In addition to providing intelligent status reporting Active Ethernet I O servers are backwards compatible with all of the functions and capabilities of traditional passive remote I O servers Click amp Go MOXA developed the Click amp Go logic control interface for easy configuration and deployment of Active Ethernet
34. e Update Tab The ioLogik E2240 supports remote firmware updates through the Firmware Update tab Enter the path to the firmware file or click on the icon to browse for the file Click on Update to update the firmware The wizard will lead you through the process until the server is restarted 9 140 Configuration Server Info Server Settings as Network 229 Firmware Update GG Watchdog an Click amp Go Lagic ee Message Monitor Firmware File Path AA Warning 1 The firmware download may take around 4 5 minutes 2 Disconnecting power or network cable during the time would lead to firmware corruption Es Step 2 3 ANG kf G8 9 8 O RK YE O a Total progress 3 10 ioLogik E2240 User s Manual Using ioAdmin A WARNING Do not interrupt the firmware update process An interruption in the process may result in your device becoming unrecoverable After the firmware is updated the 10Logik will restart and you will have to log in again to access administrator functions The firmware on any attached I O expansion module such as an ioLogik R2000 server must be updated over the RS 485 bus Firmware on cascaded modules cannot be updated over Ethernet Watchdog Tab The Watchdog tab is where you configure the Host Connection Watchdog which is used with the Safe Status settings to define each AO channel s response to a lost network connection When the 10Logik E2240 loses its network connection for the
35. e refer to Chapter 5 Click amp Go Logic for more detailed information A A ARA Logic Name gt Changes made in the Click amp Go Logic tab are not effective until the 10Logik E2240 is restarted Note that when Click amp Go Logic is being used the range and units of I O channel being used in Click amp Go Logic may not be modified 3 12 ioLogik E2240 User s Manual Using ioAdmin Server Context Menu The Server context menu is accessed by right clicking on the server model name in the navigation panel MOXA ioAdmin File System Sort ng Host 192 168 127 1 SA ioLogik SB 192 168 127 254 Mm TE 2240 Connect onfiguration p Server Info Server Settings ge Network 65 Firmware Update Watchdog 8 Click amp Go Logic amp Messi Disconnect Delete 1 0 Server 000000 gamma iiliiiliili Add Serial 1 0 Server o s Restart System Rest to Default Export System Config Import System Config risa da 11551115555 TI TI 000000000000000000000000 A0 00 E2240 I O sync rate 2 sec Ready IE Connect Select this command to have ioAdmin attempt a re connection over the network to the selected 10Logik server Disconnect Select this command to have 10 Admin drop the network connection with the selected 10Logik server Delete I O Server Select this command to have ioAdmin remove the selected server Add Serial I O Server Select this command t
36. ead always 0 Write 1 reset AI Max value 0 return Illegal Data Value 00013 0x000C Ibit Reset CH4 AI Max Value Read always 0 Write 1 reset AI Max value 0 return Illegal Data Value 00014 0x000D 1 bit Reset CH5 AI Max Value Read always 0 Write 1 reset AI Max value 0 return Illegal Data Value 00015 0x000E Ibit Reset CH6 AI Max Value Read always 0 Write 1 reset AI Max value 0 return Illegal Data Value 0x000F Reset CH7 AI Max Value Read always 0 Write 1 reset AI Max value 0 return Illegal Data Value bit l bit bit l bit 3xxxx Read Only Registers Support Function 4 ioLogik E2240 User s Manual Modbus TCP Address Mappings Data Type 30020 0x0013 CH3 Read AI Max Value 30021 0x0014 CH4 Read AI Max Value 30022 0x0015 CH5 Read AI Max Value 30023 0x0016 CH6 Read AI Max Value 30024 0x0017 CH7 Read AI Max Value 4xxxx Read Write Registers Support Function 3 6 16 0x0006 1 word CHO AO Range 0 0 10 VDC 1 4 20 mA Others return Illegal Data Value 0x0007 1 word CH1 AO Range 0 0 10 VDC 1 4 20 mA Others return Illegal Data Value 0x0008 1 word CHO AO PowerOn Range 0 0 10 VDC 1 4 20 mA Others return Illegal Data Value 0x0009 1 word CH1 AO PowerOn Range 0 0 10 VDC 1 4 20 mA Others return Illegal Data Value Ox000A 1 word CHO AO Safe Range 0 0 10 VDC 1 4 20 mA Others return Illegal Data Value 0x000B 1 word CH1 AO Safe Range 0 0 10 VDC 1 4 20 mA Others return Illegal
37. ercury cadmium Cr 6 multi bromines biphenyl and multi bromines diphenyl oxide In order to minimize the impact to human and environmental health care must be taken when using disposing of and disassembling an electronic information product The following table lists the hazardous substances and elements that are contained in this electronic information product Product ioLogik E2240 Toxic and Hazardous Substances and Elements Hexavalent Polybrominated Polybrominated Product Lead Mercury Cadmium Chromium Biphenyls Diphenyl Ethers Component Pb Hg Cd PBB PBDE PCB AIO x o o o o 0o ADG X O O O O O PCB u x o o o o o X Component contains the substance O Component does not contain the substance Service Information This appendix shows you how to contact MOXA for information about the ioLogik E2240 and other products and how to report problems In this appendix we cover the following topics O MOXA Internet Services Q Problem Report Form O Product Return Procedure ioLogik E2240 User s Manual Service Information MOXA Internet Services Customer satisfaction 1s our top priority To ensure that customers receive the full benefit of our products MOXA Internet Services has been set up to provide technical support driver updates product information and user s manual updates The following services are provided Technical Support E mail Address support MOXA com Website
38. for Product Information http www MOXA com ioLogik E2240 User s Manual Service Information Problem Report Form MOXA ioLogik E2240 Active Ethernet I O Server KON YYA MOXA Product 10Logik E2240 Serial Number Problem Description Please describe the symptoms of the problem as clearly as possible including any error messages you see A clearly written description of the problem will allow us to reproduce the symptoms and expedite the repair of your product ioLogik E2240 User s Manual Service Information Product Return Procedure For product repair exchange or refund the customer must complete each of the following Provide evidence of original purchase Obtain a Product Return Agreement PRA from the sales representative or dealer Fill out the Problem Report Form PRF with as much detail as possible to minimize repair time Carefully pack the product in an anti static package and send it pre paid to the dealer The PRA should be visible on the outside of the package and should include a description of the problem along with the return address and telephone number
39. for TCP UDP messaging Up to 5 simultaneous IP destinations for peer to peer I O Choice of email TCP UDP or SNMP Trap for active I O messaging Customizable message content with dynamic fields for time date IP address and more Configurable interval for time triggered events 9 3 ioLogik E2240 User s Manual Click amp Go Logic Click amp Go Logic Basics To use Click amp Go Logic open ioAdmin and log on as an administrator on the Server Settings tab Once you are logged on go to the Click amp Go Logic tab It should appear as below Click amp Go Logic Tab 1 Logic Name In this field you may assign a name for the set of rules 2 Rules List In this area each rule s conditions actions and status are displayed 3 Ruleset Management Bar In this area you manage the ruleset Working with Rules Rules are the building blocks of your Active Ethernet I O system With rules you define the exact trigger conditions for transmission of I O information as well as the content and destination of that information AO operation can also be automated through AI trigger conditions or mapped directly to a remote AI channel on another ioLogik E2240 In the main screen you will see a list of the rules in the current ruleset Double click on a rule to open that rule s configuration window or double click on an empty rule to start a new rule ioLogik E2240 User s Manual Click amp Go Logic MOXA ioAdmin File System Sort Help 2 a
40. gt 2 Destip 0000 win BR Copy T Toggle HEX 3 Dest IP 0 0 0 0 tej Firmware Update i Watchdog B Click amp Go Logic Message Monitor 4 Dest iP 0 0 0 0 Message Port TCP UDP UDP TCP 5 Dest IP 0 0 0 0 9000 546869732069732041 5343494920636F 646520666F 726D61 74207768696368207 3656E 742061742031383 A 4303634323422 6 Dest IP 0 0 0 0 3 7 Dest lRe 0 0 0 0 ooo BR Cop Toggle HEX 8 Dest IP 0 0 0 0 bs 99 9 Dest IP 0 0 0 0 10 Dest IP 0 0 0 0 amp X con Messages may also be entered in HEX by selecting the Send as HEX checkbox When sending a message in HEX each HEX value must be entered using the decimal equivalent delimited by commas Note that certain numbers are control characters that will not show up in the Message Monitor Please refer to the following example lt Message Content Settings Message Content 01 02 08 31 32 49 50 51 52 Firmware Update 3 Watchdog a Click amp Go Logic GF Message Monitor jv Send as HEX seperated by 33 max chars 200 SS cad DP rcP Message Receiver list global Messaging protocol global 1734 se sh Gaga baba ER Copy T Toggle HEX 4 Dest IP TS Message Port TCP UDP O Firmware ie l BY Watchdog a Click amp Go Logic e Message Monitor 5 Dest IP 0000 OO 500 Mm rce 6 Det IP 0000 0102031F 2031323334 8 DestIP 0000 z 9 DestiP 0000
41. ik E2240 could be configured to send a TCP UDP message only when the temperature sensor attached to AI 0 exceeds a certain level This structure results in a much improved response time and a much reduced load on the host computer s CPU and on network bandwidth Click amp Go Logic was developed by MOXA to easily and intuitively configure when and how I O information is transmitted over the network Using simple If Then statements you may set the conditions that need to be satisfied on one side and the resulting actions on the other side Up to three conditions and three actions can be combined in any one rule and you may define up to 16 rules SNMP traps and TCP UDP messages may be configured for transmission to up to 10 computers simultaneously Click amp Go can also be used to map an input channel on one 10Logik E2240 to an output channel on another ioLogik E2240 for direct peer to peer communication Up to five different IP addresses can be entered as the output destination This function is called peer to peer I O and provides a very flexible and easy way to extend I O signals It can be used for example to replace or extend the wiring of PLC or DCS systems over Ethernet Features Click amp Go Logic s key features are as follows Easy local logic control using intuitive IF THEN style construction Up to 16 user defined rules Up to 3 I O based conditions and 3 AO or network actions per rule Up to 10 simultaneous IP destinations
42. ill continue to wait for a response from the host This will cause the TCP port to be indefinitely occupied by the host When the Modbus TCP idle connection timeout interval is enabled the 10Logik E2240 will close the TCP connection automatically if there is no TCP activity for the specified time DNS Settings Use this field to specify up the IP addresses of up to 2 DNS servers These two DNS servers may be used to find available e mail addresses when configuring e mail messages in Click amp Go Serial Settings You may view the reserved RS 485 communication parameters here and you may set the timeout value for breaks in RS 485 communication Note that the other serial communication parameters cannot be modified If you wish to adjust the baudrate you will need to use the physical dial on the back panel of the 1oLogik E2240 SNMP Settings The ioLogik E2240 provides SNMP v2 Simple Network Management Protocol to allow monitoring of network and I O devices with SNMP Network Management software It is useful in building automation and telecom applications Use these fields to enable SNMP and set the read and write community strings Web Access Settings This field enables and disables the 10Logik E2240 s web console The web console allows the configuration of many settings using a web browser that is directed to the server s IP address If the web console is not enabled in this field you will not be able to access the web console Firmwar
43. ings E2240 Modbus Mapping 0xxxx Read Write Coils Support Function 1 5 15 00001 0x0000 1 bit Reset CHO AI Min Value Read always 0 Write 1 reset AI Min value 0 return Illegal Data Value 00002 0x0001 Ibit Reset CH1 AI Min Value Read always 0 Write 1 reset AI Min value 0 return Illegal Data Value 00003 0x0002 l bit Reset CH2 AI Min Value Read always 0 Write 1 reset AI Min value 0 return Illegal Data Value 00004 0x0003 Ibit Reset CH3 AI Min Value Read always 0 Write 1 reset AI Min value 0 return Illegal Data Value 00005 0x0004 1 bit Reset CH4 AI Min Value Read always 0 Write 1 reset AI Min value 0 return Illegal Data Value 00006 0x0005 1 bit Reset CH5 AI Min Value Read always 0 Write 1 reset AI Min value 0 return Illegal Data Value 0x0006 Ibit Reset CH6 AI Min Value Read always 0 Write 1 reset AI Min value 0 return Illegal Data Value 00008 0x0007 1 bit Reset CH7 AI Min Value Read always 0 Write 1 reset AI Min value 0 return Illegal Data Value 00009 0x0008 1 bit Reset CHO AI Max Value Read always 0 Write 1 reset AI Max value 0 return Illegal Data Value 00010 0x0009 Ibit Reset CH1 AI Max Value Read always 0 Write 1 reset AI Max value 0 return Illegal Data Value 00011 0x000A 1 bit Reset CH2 AI Max Value Read always 0 Write 1 reset AI Max value 0 return Illegal Data Value ioLogik E2240 User s Manual Modbus TCP Address Mappings Data Type Reset CH3 AI Max Value R
44. ioLogik E2240 User s Manual Second Edition January 2007 www moxa com product Moxa Technologies Co Ltd Tel 886 2 8919 1230 Fax 886 2 8919 1231 Web www moxa com Moxa Technical Support Worldwide support moxa com tw The Americas support moxa com loLogik E2240 User s Manual The software described in this manual is furnished under a license agreement and may be used only in accordance with the terms of that agreement Copyright Notice Copyright 2007 Moxa Technologies Co Ltd All rights reserved Reproduction without permission is prohibited Trademarks MOXA is a registered trademark of the MOXA Group All other trademarks or registered marks in this manual belong to their respective manufacturers Disclaimer Information in this document is subject to change without notice and does not represent a commitment on the part of MOXA MOXA provides this document as is without warranty of any kind either expressed or implied including but not limited to its particular purpose MOXA reserves the right to make improvements and or changes to this manual or to the products and or the programs described in this manual at any time Information provided in this manual is intended to be accurate and reliable However MOXA assumes no responsibility for its use or for any infringements on the rights of third parties that may result from its use This manual might include unintentional technical or typog
45. nd exported As you make changes to a ruleset you may export the system configuration in order to save that ruleset 9 12 A Liquid Crystal Display Module LCM As an Easy View device the ioLogik E2240 supports an optional detachable Liquid Crystal Display Module LCM for easier field maintenance The LCM is hot pluggable and can be used to configure the network settings or display other settings When plugged in the module displays the 10Logik E2240 home page and pressing any button takes you into the settings and configuration LCM Controls The up and down buttons navigate between the current options The right and left buttons enter and exit the submenus The center button is used when modifying settings or restarting the server An e in the upper right hand corner of the display indicates that the parameter can be modified Press the center button on the LCM to modify that parameter s settings LCM Options Display Explanation Actions This is the default home page showing the IP address Press the down button to view the submenus lt ioLogik E2240 gt Enter this submenu to display information about the specific server you are viewing e serial number SLOLOGLIK E2240 gt name server location E2240 f w ver lem f w ver model name ioLogik E2240 User s Manual Liguid Crystal Display Module LCM Display Explanation Actions Enter this submenu to display information and setting
46. ned from within ioAdmin for your convenience The easily accessible wiring guide can save administrators much time while planning or troubleshooting File System Sort Help R s e Host 192 168 127 1 SA i SA ioLogi n AB 192 168 127 254 aag 2240 po b 9 1 0 Configuration le Server Info Server Settings EF Message Moni RR GARA A TAKA AKA AKA AKA DAGANG a om EZ MOXA ioLogik GRR RNI tiiiiiiiiiiiiiilitiiii loo 100000000000000000 ooo GI 7 10V 0 237 V E E AOL 00 0 104 0 000 v AI 01 10Y 0 237 V 0 234V 0 246 Y A0 01 0 10V 0 000 Y rar 02 Mani 0 237 V 0 217V 0 242 Y AI 03 EVO 0 237 V 0 236V 0 239 V IAI 04 10Y 0 237 Y 0231 Y 0 245 Y AI 05 10 0 237 V 0 234V 0 245 Y METAS 10Y 0 237 V 0 223 0 244 Y rat 07 ZOV 0 237 V 0 236V 0 245 Y E2240 10 sync rate 2 sec Ready 115200 None 8 1 0 00 03 08 E 09 17 22 System Overview 000000 MOXA RS 485 Cascade Port Communication Settings 0 115200ps N81 1 57600bps N81 2 38400bps N81 3 19200bps N81 4 9600bps N81 5 4800bps N81 PWR RDY Serial v vy ioLogik E2240 Ethernet VO Server EEA NM x gt Go OD CD PIG PIA RA A ddi ii iiiiiiiijiiitjjij 000000000000000000000000O 6 2400bps N81 7 1200bps N81 Wiring Example Analog Input Voltage Analog Output 4 20mA Analog Input Current 0 10V 150mV 500mV
47. nnnnnnnnnnnnnnanannno 5 11 Wotkine with Click amp Go Rulesets aa 5 12 Activating the Rules 5 12 Ruleset Mipagement Bar ita ooo NAA NAG GN 3 12 RES IMPOL EXPO A MAA NIN NAAT A a 5 12 Liquid Crystal Display Module LCOM ooccoccccccccoccconcccconconccnonaronanonanos A 1 Modbus TCP Address Mappings nena B 1 Oxxxx Read Write Coils Support Function 1 5 15 B 1 1xxxx Read Only Coils Support Function 2 cccccsccscsesceeseeeeeeesesecsecseseesesseseesensesees B 2 3xxxx Read Only Registers Support Function 4 B 2 4xxxx Read Write Registers Support Function 3 6 16 ccccccccccnccnccnnccccccnccininininanos B 3 A A B 7 Used Network Port NumMberS ooomocccconncccoonccconnncnconanononnnnnnonnnrnonanencannnnnos C 2 SNMP MIB Eo e do dd D 1 Factory Default SQUUING Saan RA AE E 2 Pinouts and Cable Wiring nana F 1 Bihermei POTU PINOS ut NON R F Serial LO AA AA F Pin Assignment of Terminal Blocks A GAN F KO D vice Wiri it F 2 IS A ano a NAJ seus A LANA ANAN F 2 AIN Schematic yoltase anode caos F 2 JIN Schematic current MOE ui F 2 Appendix G Restriction of Hazardous Substance Material Declaration G 1 Appendix H Service Information nana H 1 MOXA ka NA H 2 Technical Support E mail Address H 2 Website for Product Information H 2 Problemi Report OA tdi ei Geakavedasseaasadion H 3 Product Return Pr o ae ake at H 4 1
48. o add a server by using its Unit ID Restart System Select this command to restart your ioLogik E2240 from a remote site Reset to Default Select this command to reset all settings including console password to factory default values 3 13 ioLogik E2240 User s Manual Using ioAdmin Export System Config Select this command to export the configuration of the 1oLogik E2240 to a text file It is strongly recommended you use this method to back up your configuration after you have finished configuring the 10Logik E2240 for your application Below is an excerpt from a sample configuration file ioLogik E2240 Network I O Server Configuration Date 2006 12 7 Time 09 38 28 AM MOD TYPE E2240 Active Ethernet I O Server BAI 2A0 MOD LOC MOD NAME 2 I O Configurations AI00 5 4 20mA AI01 5 4 20mA AI02 3 10V ATO3 3 10V AI04 3 10V ATO5 3 10V AIO06 3 10V AI07 3 10V A000 1 4 20mA AO00 PWN 4095 RAW A000 SAFE 4095 RAW AO01 1 4 20mA A001 PWN 0 RAW AO01 SAFE 0 RAW 3 Modbus address table CHANNEL I O TYPE MODBUS REFERENCE MODBUS ADDRESS Dec Hex A100 Input 30001 0000 0x0000 AI01 Input 30002 0001 0x0001 AI02 Input 30003 0002 0x0002 AI03 Input 30004 0003 0x0003 AI04 Input 30005 0004 0x0004 AI05 Input 30006 0005 0x0005 AI06 Input 30007 0006 0x0006 AI07 Input 30008 0007 Ox0007 AO00 Output 40001 0000 0x0000 A001 Ou
49. ollowing topics are covered O Introduction to ioAdmin O Features of ioAdmin U E ioAdmin Main Screen VVVVV WV Main Screen Overview Wiring Guide I O Configuration Tab General Server Info Tab Server Settings Tab General Message Monitor Tab ioAdmin Administrator Functions V V V V VOV I O Configuration Tab Administrator Server Settings Tab Administrator Network Tab Firmware Update Tab Watchdog Tab Click amp Go Logic Tab Server Context Menu ioLogik E2240 User s Manual Using ioAdmin Introduction to ioAdmin All ioLogik remote I O Servers may be managed and configured over the Ethernet by 10A dmin a Windows 2000 XP utility provided with your ioLogik E2240 10Admin s graphical user interface gives you easy access to all status information and settings The ioLogik E2240 also supports configuration by web console and by optional LCM but full configuration and management is only available through 10A dmin 10Admin also includes Click amp Go logic control for the configuration of your Active Ethernet I O system 10Admin consists of following software ioAdmin with Click amp Go Logic ioLogik 2000 Wiring Guide Features of ioAdmin Remote Management Over the Ethernet network 10Admin allows users to find and configure multiple 10Logik servers monitor and configure attached I O devices test I O devices reset the server On line Wiring Guide An on line wiring guide can be ope
50. raphical errors Changes are made periodically to the information herein to correct such errors and these changes are incorporated into new editions of the manual Chapter 1 Chapter 2 Chapter 3 Chapter 4 Table of Contents ij AA e 1 1 OVER anar 1 2 Tiadi ona Remote TO OO E RO E o E E EE OE 1 2 Active Etienne VVO AA 1 2 CHEKA a aaa Re pana naaa re a ee ae rn ee a ee eee a 1 2 Optional Liquid Crystal Display Module LCM oocccccccccnnnncnnnnnnnnnnnnnnnnnnnnonnnoninininininoss 1 3 Produc AA EI E O RR 1 3 Pack MEE a a E nj ee eee 1 3 PROCUCT specications 2 ia ai ee is ad 1 4 Physical DIMENS ONS eer anisori Am AA a AA ANA AA AA Ama an NAN 1 5 Without LED Module UNAN ls eles 1 5 WELCO Module UA 110 1 lc 1 6 Hardware Retenes 1 7 Pan Guide nacio 1 7 LEDS til an e il tad 1 7 ata AN Unas 2 1 Hardware Tasta lat is 2 2 Cona euno MI a ds 2 2 Grounding the 10 051k E2240 ta 2 2 Connecting to the NEO o 2 2 Setting the RS 485 Baudrate un a 2 2 Addime More VO Cha e de e dl O tt 2 2 DSO Ware TOSAMA MO tds 2 3 USING TOA GIN wisi sine NN aid 3 1 jatroduc On OU O NAMI A A NI RI nemi 3 2 Features Ob RAMI nea ne A AA eb 3 2 a Y inje oja A OEEO EN EOR OE TE EEA NENA 3 3 Mam CLON NT 3 3 a e PU PO AN AA ao aaa 3 4 KO Contieuration Lab Ena As 3 5 Server AA PO 3 5 Derversettines Tab Genta a eo na aa 3 6 Message Montor Taba AA NA AA UNG AA a 3 6 10Admin Administrator Functions AA 3 7 I O Configuration Tab Administrator ooccccc
51. riables The ioLogik E2240 has built in SNMP Simple Network Management Protocol agent software that supports RFC1317 RS 232 like groups and RFC 1213 MIB IL I O status MIB System MIB SysDescr SysUpTime SysName Interfaces MIB mu imo font CU YU IP MB ipForwarding IpAdEntBcastAddr ipDefault TTL ipAdEntReasmMaxSize ipInreceives ipRouteDest 1pInHdrErrors ipRoutelfIndex 1pInAddrErrors ipRouteMetric 1 ipForwDatagrams ipRouteMetric2 ipInUnknownProtos ipRouteMetric3 ipInDiscards ipRouteMetric4 ipInDelivers ipRouteNextHop IpRoutingDiscards ipOutRequests ipRouteType mi tl ipOutDiscards ipRouteProto i ioLogik E2240 User s Manual SNMP Agents with MIB Il maa TY UU a ifSpeed 1fInUcastPkts IfOutN UcastPkts UDP MIB UdpInDatagrams UdpInErrors UdpLocalAddress MN UdpNoPorts UdpOutDatagrams UdpLocalPort A Address Translation MIB AtIfIndex AtPhys Address AtNetAddress pc tepRtoAlgorithm tepOutSegs ioLogik E2240 User s Manual SNMP Agents with MIB Il snmpInPkts snmpOutPkts snmpInBadVersions snmpInBadCommunityNames snmpInBadCommunity Uses snmpInASNParseErrs snmpInTooBigs snmpInNoSuchNames snmpInBadValues snmpInReadOnlys snmpInGenErrs fonpowoobis O Z Ea MOXA IO MIB total ChannelNumber firmware Version AI00 Index AI00 Type AI00 Range AT00 Min AI01 Type AI01 Range AI01 Min AI02 Index AI02 Type AI02 Range AT02 Min A106 Type AI06 Range Factory Default
52. rt Do not use the reset button as that will load all factory defaults and erase your ruleset from memory 8 After the ioLogik E2240 has restarted the ruleset must be activated for Active Ethernet I O operation First you will need to log in as an administrator again in ioAdmin s Server Setting tab Once you have logged in go to the Click amp Go Logic tab and click Run in the Ruleset Management bar This will activate the ruleset and the ioLogik E2240 will begin working as an Active Ethernet I O server When the ruleset has been activated it will remain active even when the 1ioLogik E2240 is disconnected from the host computer or from the network If the ioLogik E2240 is turned off Active Ethernet I O operation will resume when it is turned back on This allows you to use the ioLogik E2240 for PC independent automation Ruleset Management Bar Clear The Clear command erases the ruleset in both ioAdmin and the 1oLogik E2240 Retrieve The Retrieve command copies the ruleset from the 1oLogik E2240 into 10A dmin Download The Download command copies the ruleset from ioAdmin onto the ioLogik E2240 Run The Run command starts the active I O messaging system using the ruleset that the 10Logik E2240 booted up with e Stop The Stop command stops the active I O messaging system Ruleset Import Export Although rulesets alone cannot be imported and exported the entire system configuration including the current ruleset may be imported a
53. s for the network e Ethernet link MAC address lt ioLogik E2240 gt IP mode network IP address netmask gateway DNS server 1 DNS server 2 Enter this submenu to display information about the ruleset lt ioLogik E2240 gt being used by the active I O system click go e name e status lt ioLogik E2240 gt Enter this submenu to display the RS 485 cascade port settings serial port Enter this submenu to access I O channel status Here are examples of settings that you might see lt ioLogik E2240 gt ai 00 0 20mA 1 89mA i o setting e ai 01 10V 0 23V Press up or down to navigate through the different I O channels without having to go back to the previous menu SLOLOGIK 1224405 Enter this submenu to see if the web console is enabled or console disabled Select this option to enter an IP address to ping If you get a timeout error it indicates that the E2240 cannot reach that IP address Otherwise the display will show the response time lt ioLogik E2240 gt ping Enter this submenu to display the restart now submenu Enter the restart now submenu to display the restart option Press the center button to modify this option then select enable to save changes and reboot the I O server The disable option has no effect lt ioLogik E2240 gt save restart A WARNING Any configuration changes that are made through the LCM will not take effect until the 10Logik E2240 is restarted Modbus TCP Address Mapp
54. st time the password will be blank and you may simply click on Login Additional functions will available after logging in including the following new tabs as Network Gea Firmware Update aE watchdog ag Click amp Go Lagic When making configuration changes you will need to click on Update or on Apply to save the changes Some changes will require a restart of the 1oLogik E2240 in order to take effect and you will be given the option to restart the computer if necessary ATTENTION You MUST log in to access any administrator function including Network Communication Watchdog Timer and Firmware Update tabs If you forget the password you may hold down the Reset button to clear the password and load factory defaults This will result in the loss of all configuration settings and your Click amp Go Logic active I O messaging program O Configuration Tab Administrator When logged on as an administrator you may double click on a channel in the I O Configuration tab to configure that channel s settings Configuring Analog Input Channels The ioLogik E2240 1s equipped with 8 AI analog input channels that can be set individually to 150 mV 500 mV 5V 10V 0 20 mA and 4 20 mA You may also set all channels at once using the Apply to all channels checkbox Q 1 0 Configuration las Server Info Server Settings Fa Network 65 Firmware Update PH Watchdog SR Click amp Go Logic E Message
55. t If the Host Connection Watchdog 1s disabled the ioLogik E2240 will never enter Safe Status and the Safe Status settings will have no effect Test I O You can test the AO channel in the Test tab 8 Contig Test Select 40 Channel iao 00 x 40 Output Test g 10 5 pu 1 1 1 1 1 i 3 0 000 Y 5 001 Y RAW 2048 0 oOo Note that the slider shows both the raw data value and the engineering value V mA You may use this as a guide when entering values for the Power On and Safe Status settings 3 8 ioLogik E2240 User s Manual Using ioAdmin server Settings Tab Administrator You may set up a password server name location date time zone and time server in the Server Settings tab Password for entry S 10 Configuration Server Info e Server Settings ES Network 59 Firmware Update Watchdog an Click amp Go Logic E Message Monitor d Logout E Login imac Settings Change Password 8 char max Reconfirm Password e Update Server Name 18 char max Y Update Server Location 18 char max YU pasel Time Settings Local Date 2000 sjh 2 23 Time lt m o is Ki Time Zone GMT 08 00 Pacific Time US Ce y Time Server A f Update Network Tab Refresh The Network tab is where you configure IP settings Modbus TCP Alive Check Timeout settings DNS settings Serial settings SNMP settings and We
56. taching the 1oLogik R2140 and additional digital channels are obtained using the ioLogik Sar E p ma ee agp at dn i ol ee MM z si Wee Pa GTA TA AAA A Software Installation 10Admin is a Windows utility provided for the configuration and management of the ioLogik E2240 and attached I O devices It may be used from anywhere on the network to monitor and configure the 10Logik E2240 You may also configure some of the settings through the web console or optional LCM l Install from CD ROM Insert the Software CD into the host computer Run SETUP EXE which is located in the root directory The installation program will guide you through the installation process and install the ioAdmin utility along with the MXIO DLL library Connect host and server Configure the host IP address and connect the host to the ioLogik E2240 with an Ethernet cable Open ioAdmin After installation is finished run ioAdmin from Start gt Program Files gt ioLogik gt Utility gt ioAdmin Search the network for the server On the menu bar select System gt Auto Scan Remote VO Server A dialog window will pop up Click Start Search to begin searching for the 10Logik E2240 MOXA ioAdmin E Host 192 168 4 113 SA ioLogik di Module Connection UnitiD Description Status Auto Searching for ioLogik I O Server s Select auto search type V Ethernet 1 0 server Y Start Search RS 232 485 1 0 server This will t
57. tatus current modes 4 20mA only This chapter describes how to install the 1oLogik E2240 The following topics are covered U Hardware Installation gt Connecting the Power gt Grounding the ioLogik E2240 gt Connecting to the Network gt Setting the RS 485 Baudrate U Software Installation 2 Initial Setup ioLogik E2240 User s Manual Initial Setup Hardware Installation Connecting the Power Connect the 12 to 48 VDC power line to the 1oLogik E2240 s terminal block TB1 If power is properly supplied the Power LED will glow a solid red color until the system is ready A ATTENTION Disconnect the power before installing and wiring Disconnect the power cord before installing and or wiring your ioLogik E2240 Do not exceed the maximum current for the wiring Determine the maximum possible current for each power wire and common wire Observe all electrical codes dictating the maximum current allowable for each wire size If the current exceeds the maximum rating the wiring could overheat causing serious damage to your equipment Grounding the ioLogik E2240 The ioLogik E2240 is equipped with two grounding points one on the back wall mounting plate and the other on the DIN rail attachment Connecting to the Network 1 Connect the ioLogik E2240 to the host PC with an Ethernet cable For initial setup of the 10Logik E2240 it is recommended that the 10Logik E2240 be configured using a direct connection
58. th ioLogik E2240 servers and making sure they both have valid connections to the network If the 10Logik E2240 will be serving simultaneously as an input module and as an output module you will need to use at least two rules one rule to configure input module operation and one rule to for each output module channel 9 11 ioLogik E2240 User s Manual Click amp Go Logic Working with Click amp Go Rulesets Activating the Ruleset A Click amp Go Logic ruleset consists of all the rules that are defined for the I O server The Click amp Go Logic tab lists all the rules in the current ruleset which acts as the brain of your active I O system The rules in a ruleset work together to determine what I O information is sent who it 1s sent to how it is sent and under what I O conditions it 1s sent This simple but powerful tool is significantly more efficient with network and CPU resources than traditional blanket polling methods In order to operate as an Active Ethernet I O server rather than a passive remote I O server the 10Logik E2240 will need to perform three steps after all rules in the ruleset have been defined 6 The ruleset must first be downloaded from 10A dmin onto the ioLogik E2240 You may do so by clicking on Download in the Ruleset Management bar 7 After the ruleset has been downloaded you must restart the 10Logik E2240 You may do this by right clicking on the server name in the navigation panel in ioAdmin and selecting Resta
59. the ioAdmin Administrator Functions section later on in this chapter for more detail 140 Configuration Server Info Server Settings E7 Message Monitor Password for entry Login F Management Settings Time Settings nm pos zle s Abad po ct A pS oo po 4 V Upine Retest Message Monitor Tab The Message Monitor tab will display any TCP UDP I O messages received from the ioLogik E2240 When you install the ioLogik E2240 for the first time the active I O messaging ruleset will not have been defined yet so there will be no messages in the Message Monitor Tab Please refer to Chapter 5 Click amp Go Logic for information on how to program the 10Logik E2240 s active I O messaging system Once the active I O messaging system has been configured and activated TCP UDP messages sent from the 1ioLogik E2240 will be viewable in the Message Monitor tab 1 0 Configuration Server Info Server Settings GF Message Monitor UDP rcP EX Copy DB Clear Toggle HEX 3 6 ioLogik E2240 User s Manual Using ioAdmin Messages can be displayed in ASCII or in HEX To display messages in HEX make sure that Toggle HEX is checked IoAdmin Administrator Functions For full access to all configuration options log in as an administrator in the Server Settings tab This is required whenever you start up ioAdmin or boot up restart the 10Logik E2240 When you install the 10Logik E2240 for the fir
60. tings On the Basic Settings page you may set the 10Logik E2240 s system time or provide the IP address of a time server for time synchronization gt Total Solution for Industrial Device Networking SI Main Menu E2240 i Overview PAANAN AA Basic Settings i Time Settings EU Network Settings r i Time zone 24 hour GMT 08 00 Taipei v ea 1 O Settings HA System Management ae ed 2000 01 j 15 02 03 36 1 modify a LCM System Elapsed Time 0 4 33 fa Change Password SEEK Load Factory Default Web console Enable O Disable O Save Restart Network Settings General Settings On the General Settings page you may assign a server name and location to assist you in differentiating between different I O servers You may also enable the Host Communication Watchdog and define the timeout value Total Solution for Industrial Device Networking Sl Main Menu E2240 fa Overview i Basic Settings aa Network Settings General Settings I O Server Settings Ga generalisa ici Ca Ethernet Configurations Server Location CJ RS 485 Settings DNS Server 1 0 0 0 0 A 10 Settings DNS Server 2 0 0 0 0 ea SEME seen C Enable communication watchdog 0 sec LCM CJ Change Password a Load Factory Default E Save Restart The Host Connection Watchdog activates Safe Status when the ioLogik E2240 loses its network conne
61. tions and units of measurement are e g Al 0 mV The available operators are lt gt lt gt Under Relation between condition select AND to specify that all conditions must satisfied for the action to take place select OR to specify that any one of the conditions may be satisfied for the action to take place A Time Trigger rule can be used to verify operation at regular intervals For example you can set a 3600 second interval so that a status TCP message is sent every hour Note When using Time 5 5 ioLogik E2240 User s Manual Click amp Go Logic Trigger with pulse output make sure that trigger interval is at least one second greater than the output pulse cycle THEN actions Under the THEN column you may set up to 3 actions that will be performed if the conditions under the IF column are satisfied The available actions are AO setting SNMP trap Active Message by TCP UDP and E mail Additional parameters may be configured for SNMP trap Active Message and E mail actions by clicking the memo icon ay v Enable fe Enable Logic IF THEN BIT a0 x ilo Rawie x mp a0 0 y 0 RAW Ic ep a1 0 y zilo RAW ec z 2 aoo 0 RAW Ic y HIT a o zilo RAW ec HIT A0 0 0 Rawe y Relation between conditions 14ND be na 3 soo z ooo so y Equivalent Logic Statement Jf OK X Cancel THEN 1 JZ SNMP Trap Si 82 14 Active Message SB 43M aoo D TRAE y AO Ch
62. tput 40002 0001 0x0001 4 Timer Settings TIME ZONE 49 GMT 08 00 Taipei TIME SERVER 5 Network Settings NET CONFIG 0 Static NET_IP 192 168 127 254 NET MASK 259 255 255 0 NET GATEWAY 0 0 0 0 NET MAC 00 90 E8 0D 0E DD IDLE TIMEOUT 60 sec BAUD 115200 bps DNS 1 0405020 DNS 2 00050 WEB 1 sec SNMP 1 Enabled SNMP_READ public SNMP_RW SNMP_CONTACT SNMP LOC CONNECTION WATCHDOG 0 Disabled 6 Click amp Go Settings STATUS 0 3 14 ioLogik E2240 User s Manual Using ioAdmin Import System Config A Select this command to reload a configuration that was exported to a text file You will need to restart the 1oLogik E2240 in order for the new configuration to take effect This command may be used to restore a configuration after loading the factory defaults or to duplicate a configuration to multiple 1oLogik E2240 s ATTENTION You can import the configuration file from a TFTP server For example you can run TFTP Client software open the configuration file and enter the remote server s IP Note that both ASCII and Octet mode are supported When the download process is complete the I O server will reboot Win TFTF Client Pro x ah L ES Upload Download Abort Settings About Help Remote server Local file name gz BE J ve C testhik 2240 tet S 132 168 19 24 Timeout 2 z s Remote file name Bork JES ik2240 tel Block size E 2 bytes
63. unction gt Total Solution for Industrial Device Networking SI Main Menu E2240 sd Overview ml Basic Settings aa Network Settings RS 485 Settings Serial Parameters EG Unit ID 0x01 a General Settings Baud Rate 15200 ra Ethernet Configurations Data Bits 8 O gys Settings Stop Bits 1 ag 1 O Settings Parity None af System Management icm a Change Password i Load Factory Default CJ Save Restart I O Settings Al Channels On the AI Channels page you may view the status and range of each AI analog input channel Under Min and Max you may view the minimum and maximum values that have been detected for each sensor since the 1oLogik E2240 was powered on Total Solution for Industrial Device Networking J Main Menu E2240 CJ Overview Basic Settings AI Channel Settings ii AI Channel Range Value Min Max poe Network Settings ar 00 10Y 0 23v 0 23v 0 23v IT 1 0 Settings A1 01 10Y 0 234 0 23Y 0 234 Cd Al Channels AI 02 10Y 0 234 0 234 0 234 Ca A0 Channels AI 03 10Y 0 234 0 234 0 234 loreto iris mark AI 04 10Y 0 234 0 234 0 234 E A1 05 10Y 0 234 0 234 0 234 NO Lom AI 06 10Y 0 23Y 0 23v 0 23v O Change Password AI 07 10Y 0 23 0 23y 0 23Y fo Load Factory Default o Save Restart You may also configure each channel s analog input mode and range by clicking on the channel The available options are 150 mV 500 mV 5V 10V
64. ve remote analog output channels Exiting Ethernet PREME et a PS Output up to 8 inputs up to 2 outputs Input Module ioLogik E2240 User s Manual Click amp Go Logic Input Module a Output st Module Peer to peer I O is configured in two steps On the input module a rule is defined to send I O data to one or more destination IP addresses On the output module a rule is defined for a specific output channel to mirror a specific channel on the input module Configuring Input for Peer to Peer I O Configuring the peer to peer I O input will use up one Click amp Go rule on the ioLogik E2240 providing the input channels In the Click amp Go tab open a new rule s configuration window and enable peer to peer I O Select Input channels to mirror to then click remote IP and enter up to five IP addresses as destinations Each IP address should belong to an 1oLogik E2240 server that will provide output channels for the peer to peer I O You may repeat this process with additional peer to peer I O rules if you wish to mirror input channels to more than five destinations If all 16 rules are used for peer to peer I O a total of 80 destination IP addresses can be entered 5 10 ioLogik E2240 User s Manual Click amp Go Logic 1 Dest IP 0 0 0 0 KA Dest IP 0 0 0 0 Dest IF 0 0 0 0 Dest IP 0 0 0 0 Dest IF 0 0 0 0 X cons Note that you cannot configure the 1oLogik E2240 as an input module