Home
        PACSystems RX7i Redundancy Memory Xchange Module, GFK
         Contents
1.  other  This must be a two node ring  no other    RMX016    reflective memory nodes are allowed to be part of this fiber optic network  roue  GE Fanuc strongly recommends two redundancy links  for a total of four RMX modules  be    i  configured and installed  Optionally  systems can be configured for a single redundancy link  for    a total of two RMX modules      When the RMX is being used as link in a redundancy system  it cannot be used as a general   purpose Memory Xchange module  For details on the operation of a PACSystems CPU  redundancy system  refer to the PACSystems Hot Standby CPU Redundancy User   s Manual   GFK 2308     A PACSystems RX7i main rack supports a maximum of four Memory Xchange modules in any  combination of RMX016 and CMX016 modules  A maximum of two RMX modules can be  configured as redundancy communication links     OWN DATA    Features   PACSystems RX7i single slot form factor    16 Mbytes reflective memory with parity     Software configuration of all node parameters  no jumper or switch settings required     High speed easy to use 2 12 Gbaud fiber optic network    No RX7i CPU processing required to operate the network    Network compatible with VMIC 5565 family of reflective memory devices    Connection with multimode fiber up to 300m  984 25ft    Dynamic packet sizes of 4 to 64 bytes  controlled by the Memory Xchange module     Maximum network transfer rate of 43 Mbyte s  4 byte packets  to 174 Mbyte s  64 byte  packets     Programmable VMEbus 
2. PACSystems    RXTi  IC698RMX016 DC    GFK 2324B Redundancy Memory Xchange Module  June 7  2005    The Redundancy Memory Xchange  RMX  module operates as a node on a reflective memory  network or as a dedicated link between CPUs in a redundant RX7i system  When the RMX is  not being used as a link in a redundancy system  it is functionally identical to the IC698CMX016  module  Each node in the network can be any reflective memory device that is compatible with  the 5565 family  Whenever data is written to one node  all nodes on the network are  automatically updated with the new data     When used as a node on a reflective memory network  the RMX module provides deterministic  sharing of data among PLCs and other computing devices on a high speed fiber optic network   A reflective memory network can contain up to 256 nodes     Each node in the reflective memory network is connected in a daisy chained loop using fiber o  optic cables  The transmitter of the first node is tied to the receiver of the second  The   transmitter of the second node is tied to the receiver of the third node  and so on  until the loop Ta  is completed at the receiver of the first node  ane    When used in a CPU redundancy system  the RMX modules provide a path for transferring data  between the two redundancy CPUs in the redundant system  A complete communications path  consists of one RMX in the primary unit  one RMX in the secondary unit  and two high speed  fiber optic cables connecting them to each
3. Redundancy Memory Xchange Module             GFK 2324B  Ordering Information  Description Catalog Number  Redundancy Memory Xchange Module for RX7i IC698RMX016  IC698CMX016    Control Memory Xchange Module for RX7i       Fiber Optic Cables    VMICBL 000 F5 0XX   where 0XX is used to distinguish  different lengths                         RX7i VME 700MHz CPU with Redundancy IC698CRE020  Lithium Battery pack IC698ACC701  Rack Fan Assembly  120VAC IC697ACC721  Rack Fan Assembly  240VAC IC697ACC724  Rack Fan Assembly  24VDC IC697ACC744  RX7i PLC Power Supply  85 to 264 VAC at 47 to 63 Hz Input  100 watt output IC698PSA100  RX7i PLC Power Supply  85 to 264 VAC at 47 to 63 Hz Input  350 watt output IC698PSA350  IC200CBL001     Optional  RS 232 cable  also Station Manager cable for Ethernet interface          FOR CLASS    DIVISION 2     BEFORE REPLACING OR WIRING MODULES     HAZARDOUS LOCATIONS ONLY        The following information is for products bearing the UL marking for Hazardous Locations   HM WARNING   EXPLOSION HAZARD   SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY    E WARNING   EXPLOSION HAZARD  WHEN IN HAZARDOUS LOCATIONS  TURN OFF POWER    E WARNING   EXPLOSION HAZARD   DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS  BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS    E EQUIPMENT LABELED WITH REFERENCE TO CLASS I  GROUPS A  B  C   amp  D  DIV  2 HAZARDOUS  LOCATIONS IS SUITABLE FOR USE IN CLASS I  DIVISION 2  GROUPS A  B  C  DOR NON              
4. als at the beginning of a transaction  Under most conditions  not  latching these signals had no effect on the system  However  certain sequences of data  patterns can cause momentary transactions on the address and AM lines  This could  lead to the Memory Xchange module disconnecting signals from the VME bus that it  should be driving monitoring  leading to data corruption on either a read from the board  or a write to the board           Network Bandwidth    The maximum bandwidth of the reflective memory network is 174Mbytes s  The application must avoid a  situation where the transmit FIFO becomes full  You can accomplish this by not having multiple nodes  transmit a large amount of data at the same time    The RX FIFO Almost Full status  bit 09  of the LISR  Region 2  offset 10h  can be monitored to determine if  the network is becoming saturated    For an example of network load balancing  refer to    Optimizing Network Bandwidth    in the PACSystems RX7i  Memory Xchange Modules User   s Manual  GFK 2300        Redundancy Memory Xchange Module 3                            GFK 2324B  Secondary Uit Primary Unit    c R G    a 2  c IRIRI  G       P  iM  B 2   e Mim  B  tack 0     5 e    u k x   c  a  Required fan assembly  not shown     30 31  High speed fiber optic link   E High speed fiber optic link   Genius Bus    Remote Drop       Legend    CPU   RX7i CPU  RMX  Redundancy Memory Xchange Module  GBC  Genius Bus Controller              Wmzz paw        Supports up to 30 48
5. interrupt output     Four general purpose network interrupts with 32 bits of data each    Network error detection    Up to 256 nodes per network         Redundant transfer mode operation  This optional mode reduces the chance of a data  packet being dropped from the network        Configurable network memory offset allows you to assign nodes on a network to groups  according to the 16MB segment in the network address space that they use       Not available when operating as a redundancy link ina CPU redundancy system     2 Redundancy Memory Xchange Module  GFK 2324B    Release Information  Release History       Release Hardware Version Firmware Version       DC D C       CB                      C B  BA B A  AA  Initial Release  A A       Updates    IC698RMX016 Modules with versions  BA and earlier must be returned to the manufacturing facility for  replacement     Customers can upgrade IC698RMX016 CB version modules to version  DC by ordering and installing  upgrade kit 44A753080 G01     All Conformal Coated boards  IC698RMX016CA xx and IC698CMX016CA xx  must be returned for  replacement     Problems Resolved in this Release  DC        Subject Description          Corrupted Data In earlier versions  certain sequences of data patterns  when written to or read from the  module would result in corrupted data    This problem is resolved with version    DC    Problem Details    In earlier versions  the Memory Xchange module did not latch the VME address lines  and VME AM code sign
6. m 100ft fiber optic cable     Sample PACSystems RX7i CPU Redundancy System    User Features  The front panel of the RMX module has eight LED indicators  a toggle switch that can be used to manually  request a role switch  and an optical transceiver     Role Switch   The Role switch is a spring loaded two position switch that rests in the OFF state  When the RMX module is  being used as a redundancy link  this switch allows you to manually switch control from the active controller to  the backup controller  To initiate the switching of roles  lift the switch to the ON position for at least 1 second   The role switch state is de bounced and filtered to prevent accidental activation    When the RMX module is used as a node in a general purpose reflective memory network  i e  not used as a  redundancy link   the Role switch has no effect on module operation     Optical Transceiver   The optical transceiver has two    LC    type fiber optic ports  The port labeled    TX    is the transmitter and the port  labeled    RX    is the receiver    Memory Xchange modules are networked together using either simplex  single fiber  or duplex  dual fiber   multimode fiber optic cables  The specific cable construction depends on your operating environment  For  details on fiber optic cables  refer to the PACSystems RX7i Memory Xchange Modules User   s Manual  GFK     2300     4 Redundancy Memory Xchange Module             GFK 2324B  LEDs  All front panel LED indicators are green  The default s
7. tate of all LED indicators after reset is OFF   LED Label Description  OK ON indicates the module is functioning properly   LINK OK When not used as a redundancy link  ON indicates the module is configured     When used as a redundancy link  ON indicates the link is functioning properly    LOCAL READY ON indicates the local unit is ready    LOCAL ACTIVE ON indicates the local unit is active    REMOTE READY   ON indicates the remote unit is ready    REMOTE ACTIVE   ON indicates the remote unit is active    OWN DATA ON indicates the module has received its own data packet from the network at least once   SIGNAL DETECT   ON indicates the receiver is detecting a fiber optic signal                                  Installation   Make sure you have the items listed below before you begin    m APACSystems RX7i CPU with release 2 00 or higher firmware  m APACSystems Rx7i CPU rack with power supply     m Programming software  Machine Edition     Logic Developer PLC  version 4 5 or later  and a PC   compatible computer      m Cables  For details  see    Fiber optic Cables and Connectors    in the PACSystems RX7i Memory Xchange  Modules User   s Manual  GFK 2300     Note  RX7isystems that include one or more Memory Xchange modules must be installed in a metal  enclosure with conduit or equivalent to meet radiated emission standards  For details  refer to the  PACSystems RX7i Installation Manual  GFK 2223     Installing the RMX Module in an RX7i Rack    Do not insert or remove modules wi
8. th power applied  This could cause the CPU to stop  damage the  module  or result in personal injury     Memory modules must only be installed in the main  Rack 0  RX7i rack     Note  Itis recommended that the RMX modules be installed in slots 3 and 4 of the main rack  This gives  VME interrupt request priority to the RMX modules  Although this configuration is recommended  it is  not required that the RMX modules be located in slots 3 and 4     1  Make sure rack power is off   Slide the module into the slot for which it was configured in the system     3  Press the board firmly in place  but do not force the board  Tighten the screws on the top and bottom of  the faceplate     Connect the cables to the TX and RX connectors     5  Route the fiber optic cable from TX to the RX connector of the next node in the ring  Connect the cable  from that board   s TX to the RX connector of the next node  Repeat this step until the last node in the ring  routes its TX to the RX of the first node     6  Turn on power to the RX7i rack     Redundancy Memory Xchange Module 5  GFK 2324B    Configuration  The RMX module initially powers up in an unconfigured state with its optical transmitter disabled  The module  cannot operate on a network until the RX7i CPU has sent a hardware configuration to the module     For general purpose reflective memory operation  you can configure the following parameters in the hardware  configuration  Node ID  Redundant Transfer Mode  Rogue Master  Network Memor
9. y Offset  and Interrupt  enable   If Redundant Link operation is selected  these parameters are set by the CPU and are not  configurable      When the RMX is used as a general purpose reflective memory module  additional functions beyond the  basic read and write operations  including enabling interrupts  reading interrupt status  enabling parity  and  reading parity errors  can be performed by user logic  For details on accessing these advanced functions   refer to the PACSystems RX7i Memory Xchange Modules User   s Manual  GFK 2300     Related Publications   PACSystems RX7i CPU Reference Manual  GFK 2222   PACSystems RX7i Installation Manual  GFK 2223   PACSystems RX7i Memory Xchange Modules User   s Manual  GFK 2300  PACSystems RX7i CPU Redundancy User   s Manual  GFK 2308   Proficy    Machine Edition Logic Developer PLC Getting Started  GFK 1918             Specifications   Physical size PCB  6 299    W x 9 187    H  Packet size Dynamic  automatically controlled by Memory Xchange module  User memory 16MB SDRAM       Operating voltage  5VDC  from power supply   Current requirements   1 8A    Connectors m Fiber optic LC type  conforms to IEC 61754 20  Zirconium ceramic ferrule   Insertion loss  0 35 dB  maximum    Return loss   30dB   Temperature Range   20  C to  85  C                           For environmental specifications and compliance to standards  for example  FCC or  European Union Directives   refer to the PACSystems RX7i Installation Manual  GFK   2223        6 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Manual De Instrucciones y Términos de Garantía  Requerimientos de información sistema de información de recursos  KOHLER K-T309-4M-BV Installation Guide  Form A6188 - Well Control User Program  Cooper Lighting Metalux MC Series User's Manual  HBD-D268AV  PC0009_05 PS1 Technical Manual, Rev 05    バイタルセンサS-DV    Copyright © All rights reserved. 