EATS16 EATS16N Installation and user manual
Contents
1. E T N EATS16 EATS16N Installation and user manual Copyright O 2015 EATON All rights reserved Service and support Call your local service representative EATS16_EN SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the ATS The EATON ATS models that are covered in this manual are intended for installation in an environment within 0 C to 40 C 32 F to 104 F and free of conductive contaminant Certification standards e Safety IEC 62310 1 e EMC IEC 62310 2 e Performance IEC 62310 3 e CE Mark e Additional conformances IEC 60950 1 CISPR 22 Class B Important safety notes e Only qualified personnel can service this equipment e Follow the following precautions when working on this unit Remove watches rings or other metal objects Use tools with insulated handles e Examine the packing container Notify the carrier immediately if any damage is present e Do not disassemble the unit e Do not operate the unit near water or in an area with excessive humidity e Keep liquid and foreign objects from getting inside the unit e Do not operate the unit close to gas or fire e Verify whether the branch circuit breaker or fuse on service feed is correct e Verify line voltage requirements and the supplied line voltage prior to installation e This unitis supplied from multiple sources
2. by the manufacturer Reduced Air Flow Installation of the equipment in a rack should be such that the amount of air flow required for safe operation of the equipment is not compromised Mechanical Loading Mounting of the equipment in the rack should be such that a hazardous condition is not achieved due to uneven mechanical loading Circuit Overloading Consideration should be given to the connection of the equipment to the supply circuit and the effect that overloading of the circuits might have on overcurrent protection and supply wiring Appropriate consideration of equipment nameplate ratings should be used when addressing this concern Reliable Earthing Reliable grounding of rack mounted equipment should be maintained Particular attention should be given to supply connections other than direct connections to the branch circuit e g use of power strips Page 11 4 Power cables connection 4 1 Installation diagram ATS ATS Output to the sensitive equiment 4 2 Input Output connection EATS16 EATS16N Inputs connections Ouput connection to equipment from UPSs outputs 1 Connect input power cables to UPSs output and to ATS inputs S1 is the default priority source 2 Connect ATS output to the equipment Page 12 EATS16_EN 5 Communication 5 1 Communication ports EATS16N e RS232 communication port 1 Connect the RS232 2 communication cable to
3. disconnect all sources before servicing Electrical warnings Warning Page 2 e Check that power cords plugs and outlets are in good condition e RAL equipment Equipment intended for installation in Restricted Access Location e Intended to be connected to computer load e Notto be connected to inductive load or with gt 3 1 crest factor load EATS16_EN Contents 1 Introduction aiii aio rrrerrr Ts 4 2 PresentatiON sesiicicnid ici 4 2 Weights and AIMENSIONS escritas AR tal a elos 4 2 2 Rear panel layout EATS16 EATSI6N o oooooccnoocccococccononnncononncononnncnonnnnononononnnnnconnnnconnnno 4 23 Conrolpane ereenn cet raetentwateee E E seas ssunitceenccapivin eden E E E 4 24 CCD descriptions iiie ae ha a EAE E tem a EE r aaae 5 24 1 Power TOW esei e a e EE A Ea aE e A E ESEE deco ness 5 2A LIMUSA ltda 6 20 O on taeemacadeanchidedeeeuans owvaarteeades 6 2 6 A 8 3 Installation for ATS usada 9 3 1 Checking the accessory kit EATS16 EATS16N ooocinocccinoccccooccccoonncnononcnnonnnccnonnncnonnnno 9 32 o edo 10 3 3 Installation for rack mounting normal installation oooononnncnnnnonnonccnnnncconocccionncoos 10 3 4 Installation for rack mounting 2 post installation oooooononnnnnnnnnonnnnccnnnoccnonocccionncnos 10 39 Wallinstala O addon iasdds 10 3 5 INSTITUCION Sit a 11 A Power cables connection ssssssssssssssssnnnnnnssnnnnnsnnnnnnnnnnnnnnnnnnnnnnn 12 All Installation Da Misco A oa 1
4. the serial on the computer 2 Connect the other end of the communication cable 2 to the RS232 1 communication port on the ATS The ATS can now communicate with EATON power management software e Characteristics of the optocouplers communication port When a signal is activated the contact is closed between the common Pin 4 and the pin of the corresponding signal for n o contact and vice versa for n c contact Contact characteristics optocoupler e Voltage 48 V DC max e Current 25 mA max e Power 1 2 W Pin assignment Description Contact type Open State Close State Pin 1 Summary alarm signal n o Normal Alarm occurred Pin 2 RX Pin 3 TX Pin 4 Common Pin 5 GND Pin 6 Source 1 OK n c Source 1 is failure Source 1 is ok Pin 7 Source 2 OK n c Source 2 is failure Source 2 is ok Pin 8 Load on source 1 n c Source 1 not take load Source 1 takes load Pin 9 Load on source 2 n c Source 2 not take load Source 2 takes load n o normally opened n c normally closed EATS16_EN Page 13 5 Communication e Connectivity Cards EATS16N Connectivity cards allow the ATS to communicate in a variety of networking environments and with different types of devices The Network MS card has SNMP and HTTP capabilities as well as monitoring through a Web browser interface connects to Et
5. 2 4 2 Input Output connection EATS16 EATST6N issectae 12 5 COMMUNICATION scada a daniar aana iri diaii 13 5 1 Communication ports EATSIGN incoaci n nt a a EE 13 5 2 Eaton Intelligent Power Software SUITE oooooocnioccoconocccoooccnnononccooncnnnonnnnonnnnccnonnncnonnnos 14 6 Maintenance ooccccccccconccnccnncnnnnnncnononnnnnnrnnnnnnnnnnenrnnnnnnnrnrrnnrnnnnnnnrnnnnnn 15 sl Troubleshooting ina id 15 7 Specifica ti NS mm tica riada 16 EATS16_EN Page 3 1 Introduction The EATON Automatic Transfer Switch ATS is a high availability switch designed for providing redundant power for sensitive equipment It is powered by two independent power sources and automatically makes a rapid switch from one source to the other when the power supply used to power its connected load fails This ATS is designed to be efficient and reliable Users can know EATON ATS s power flow status parameters from the LCD interface Besides the EATS16N unit has a network interface for users to read and write parameters The network interface can be implemented via the Ethernet protocol through an RJ45 connector 2 Presentation 2 1 Weights and dimensions Rack installation Description Weights Dimensions H x W x D kg Ib mm inch EATS16 3 32 7 31 43 x 438 x 250 1 7 x 17 24 x 9 84 EATS16N 3 54 7 8 43 x 438 x 250 1 7 x 17 24 x 9 84 2 2 Rear panel layout EATS16 EATS16N i Input Source 1 IEC C20 in
6. Accessories for rack installation EATS16_EN Page 9 3 Installation for ATS 3 2 Storage e Please store the ATS in its original package and in a dry place Keep the storage temperature between 13 to 131 F 25 C and 55 C 3 3 Installation for rack mounting normal installation VIMLUURA 87 BURR Follow steps 1 to 3 for module mounting on the rails Accessories for rack installation e 1x Ear Left e 1x Ear Right e 4x M4 x 6 flat screw for ear e 4x M6 x 10 cage nut clip for rack4 e 4x M6 x 12 flat screw for rack e 4x M6 washer conical plate for rack 3 4 Installation for rack mounting 2 post installation RURAL ARRERR sy ex Y w 3 Follow steps 1 to 3 for module mounting on the rails Accessories for rack installation e 1x Ear Left e 1x Ear Right e 4x M4 x 6 flat screw for ear e 4x M6x 10 cage nut clip for rack4 e 4xM6 x 12 flat screw for rack e 4x M6 washer conical plate for rack Page 10 EATS16_EN 3 Installation for ATS 3 5 Wall installation 3 6 EATS16_EN Follow steps 1 to 2 for module mounting on the wall Instructions 1 Elevated Operating Ambient If installed in a closed or multi unit rack assembly the operating ambient temperature of the rack environment may be greater than room ambient Therefore consideration should be given to installing the equipment in an environment compatible with the maximum ambient temperature Tmax specified
7. act your service representative EEPROM fault note that the load is still powered Note the alarm message and the ATS serial number and then contact your service representative Page 15 7 Specifications Table 1 Model list Model Operating voltage Current rating Operating frequency EATS16 EATSI6N 200 208 220 230 240 Vac 14 16A 50 60 Hz Table 2 Weights and dimensions Model Dimensions H xW x D mm inch Weight kg Ib EATS16 43 x 438 x 250 1 7 x 17 24 x 9 84 3 32 7 31 EATS16N 43 x 438 x 250 1 7 x 17 24 x 9 84 3 54 7 8 Table 3 Electrical input connections Model Input connection EATS16 EATS16N IEC C20 inlet 2 x Input cables C19 C20 provided Table 4 Electrical output connections Model Output connection EATS16 EATS16N 1x C19 8 x C13 Table 5 Environmental and safety Operating temperature 0 C to 40 C 32 F to 104 F Storage temperature 25 C to 55 C 13 F to 131 F Relative humidity Storage 0 90 Operating 20 85 Operating altitude 2000m meters 6252 ft Audible noise 25 dBA max without buzzer Page 16 EATS16_EN
8. hernet network In addition an Environmental Monitoring Probe can be attached to obtain humidity temperature smoke alarm and security information o ETHERNET Setting Sensor A date Reset Oy Network MS card 5 2 Eaton Intelligent Power Software suite Eaton Software suite provides up to date graphics of ATS power and system data and power flow It also gives you a complete record of critical power events and it notifies you of important ATS or power information Page 14 EATS16_EN 6 1 EATS16_EN Troubleshooting 6 Maintenance Operation status Possible cause Action Overload Power requirement exceeds the ATS capacity greater than 105 of nominal Remove some of the equipment from the ATS The ATS continues to operate but may shutdown if the load increases The alarm resets when the condition becomes inactive A short circuit occurred Check device connection or integrity If error persists note the alarm message and the ATS serial number and then contact your service representative Internal relay fault note that the load is no powered Note the alarm message and the ATS serial number and then contact your service representative Source 1 or Source 2 power supply fault Internal power supply of one of the source is faulty the other source is powering the load Note the alarm message and the ATS serial number and then cont
9. let Input Source 2 IEC C20 inlet A ie Seo OTTI f E f y oo ML keco oe j Dn D SOC 2 O Output 1 x C19 16 A O e Output 8 x C13 10 A O OOO 2 3 Control panel The ATS has three buttons on the control panel and a LCD display It provides useful information about the ATS itself load status events measurements and settings Page 4 LCD panel Navigation Scroll down button Navigation Enter button Navigation Escape button OO OSO buttons pressed for 5s EATS16_EN Transfer Test Scroll down and Enter 2 Presentation 2 4 LCD description 2 0 WK Power flow ATS Settings Measures Infos Events 2 4 1 Power flow S1 is defined as the priority source true by default or S2 is defined as the priority source can be set S1 not powered or S2 not powered S1 powering the load or S2 powering the load S1 powered but not powering the load or S2 powered but not powering the load Transfer from S1 to S2 or Transfer from S2 to S1 Transfer from S1 to S2 for Test or Transfer from S2 to S1 for Test EATS16_EN Page 5 2 Presentation 2 4 2 Measures Output current default display Output voltage Input voltage S1 default display only when S1 voltage is out of tolerance Input frequency S1 default display only when S1 frequency is out of tolerance I
10. nput voltage S2 default display only when S2 voltage is out of tolerance Input frequency S2 default display only when S2 frequency is out of tolerance S1 and S2 phase shift available only when S1 and S2 are not synchronized 25 ATS settings Page 6 OUTPUT Sets voltage thresholds 200 V 208V 220 V 230 V default 240 V ALARM Silents alarm ON normal beep in warning or fault mode by default OFF silent SENSITIVITY mainly for LIA UPS Sets Std Normal Sensitivity by default Sensitivity mode for input mains detection Lo Low Sensitivity for compatibility with distorted a waveform P SOURCE Sets the priority source Sc 1 Priority on Source 1 by default Sc 2 Priority on Source 2 TRANSFER Std no additional break even if S1 and S2 are not synchronized by default Gap additional break during transfer if S1 and S2 are not synchronized EATS16_EN 2 Presentation Press Enter to reach settings menu gt To cancel the changes Y gt To select value Y EATS16_EN Page 7 2 Presentation 2 6 Warning For Fault refer to troubleshooting section 6 1 Page 8 Event Example of displays Rootcause Overload nO Load is over nominal rating Remove some of the equipment from the ATS The ATS continues to operate but may shutdown if the load increases The alarm resets when the condition becomes inactive Uns
11. ynchronized sources One source N and L are reversed S1 ansd S2 are fed by different phase L1 L2 L3 S1 and S2 frequency are different Source 1 or Source 2 power loss One of the source is missing The ATS power on the load with the source that is present Source 1 or Source 2 voltage out of tolerance One of the source voltage is out of tolerance The display shows the voltage measure of the faulty source Source 1 or Source 2 frequency out of tolerance One of the source frequency is out of tolerance The display shows the frequency measure of the faulty source Source 1 and Source 2 quality The sources are outside ranges so that it generates too many transfers within a short period of time The alarm resets when the condition becomes inactive EATS16_EN 3 Installation for ATS 3 1 Checking the accessory kit EATS16 EATS16N Verify that the following additional items are included with the ATS EATS16 User manual Quick start guide Safety manual printed 4 2 x Input cables C19 C20 2 x Input cable lockers 6 Plastic strips for output locking RS232 cable Accessories for rack installation EATS16N User manual Quick start guide Safety manual printed 2 x Input cables C19 C20 5 2 x Input cable lockers Plastic strips for output locking RS232 cable DB9 RJ45 serial cable for NMC card 9