Home
K-BUS R Binary Inputs, 4 fold User manual
Contents
1. 58 6 9 Communication object Counter 59 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold 6 10 Communication object Multiple operation 61 6 11 Communication object Shutter control 62 1 General The Binary input fulfils the individual demands in functional buildings as well as in residential buildings In the same way system planners are provided with varied application possibilities with regard to the implementation of functions The binary input can install to be system with EIB KNX bus and other device and the functions are both simple to operation and intuitive Users can program it according to the requirement to implement the function systematically This manual provides detailed technical information about the binary input for users as well as assembly and programming details and explains how to use the binary input by the application examples 1 1 Product and functional overview The binary input is a modular installation device for fast installation in the distribution board on 35 mm mounting rails to DIN EN 60 715 The electrical connection is implemented using screw ter
2. NOTE OP operation 1f 1 fold object 2f 2 fold object 3f 3 fold object 3f_T 3 fold object value toggle Operation OP OP OP OP OP eee Time gt ls lt ls lt ls lt ls jeee Object 1f 1f T 2f 3f 3f_T eee Object value 1 0 0 0 ee ere NOTE OP operation 1f 1 fold object 2f 2 fold object 3f 3 fold object 1f_T 1 fold object value toggle 3f_T 3 fold objet value toggle If the parameter Value on every operation set NO It will send the last object value after Max time Be set in following parameter elapsed Parameter Value send object Tele Operation fold This parameter sets which object value is to be sent The settings ON OFF and Toggle are possible With Toggle the current object value is inverted Options On Off Toggle Parameter Value on every operation send The parameter sets whether the respective object value is updated and sent with each operation 47 E a N www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold Options Yes No If Yes is selected the object value is updated and sent with each operation With 3 fold operation as an example the object output 1 fold after Ist operation output 2 fold after the 2nd operation and output 3 fold after the 3rd operation are sent If No is selec
3. 36 5 5 2 6 Counter 39 5 5 2 7 Push button with multiple operation 45 5 5 2 8 Shutter Control 49 6 Description of communication object 52 6 1 Communication object Manual Automatic 52 6 2 Communication object Jointly adjustable Dimming 53 6 3 Communication object Jointly adjustable Shutter 54 6 4 Communication object Switch 54 6 5 Communication object Switch Dimming 55 6 6 Communication object Value force output 56 6 7 Communication object Scene control 57 6 8 Communication object Switch sequence
4. 150ms Min operation The Min operation can be set in fig 5 8 Parameter Enable differential counter The parameter set whether enable the differential counter Options Yes No If this parameter is set to yes the parameter window fig 5 14 3 is displayed Parameter Pulse detection on The parameter set how the input pulse is generated Options Closing contact rising edge Opening contact falling edge Both rising and falling If Closing contact rising edge is selected the input pulse is only generated with a closing contact rising edge If Opening contact falling edge is selected the input pulse is only generated with a opening contact falling edge If Both rising and falling is selected the input pulse is generated with a opening contact falling edge and a closing contact rising edge Parameter Mode of counter The mode of counting of the counter is set with this parameter Options Normal 1 Manual set If Normal 1 is selected the counter value is incremented by one with generated a input pulse If Manual set is selected the following two parameters appear Parameter Divider number of input pulse for one counter step 1 10000 The parameter is visible if the option manual set has been selected with the parameter mode of counter It is used to set the number of input pulses required to generate a counter pulse for the main and differ
5. C T 1 007 DPT_Step This communication object is used to send a stop shutter moving command Telegram value 0 stop moving 1 stop moving Table 6 3 Communication object table Jointly adjustable Shutter 6 4 Communication object Switch Ho Group Adard Function object name Type Priority c r w r ju 01 01 001 Binary Input 1M10xxC03B Binary Input Ed 0 CH A Disable Disable A 1 Bit Low v v o4 1 CH A Switch Switch A 1 Bit Low v vv a 2 CH A switch long Switch long A 1Bit Low v v Fig 6 4 Communication object Switch No Function Object name Data type flags DPT 54 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold 0 CH X Disable Disable X lbit C W 1 003 DPT_Enable When enable the channel function this communication object will be active to disable enable the channel function Telegram value O disable the channel function 1 enable the channel function All objects of the function are ineffectiveness when the channel function is disabled The channel function default to enable after bus voltage recovery The object disable is the same for all operation modes of the channel 1 CH X Switch Switch X lbit C W T 1 001 DPT_Switch In accordance with the parameter setting this communication object can be
6. 60 BSS Sn IEE S SSE www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold 6 10 Communication object Multiple operation The communication object Multiple Operation will be shown in Fig 6 10 If the input is operated several times within a defined period a defined object value can be modified by the number of operations Ho Group Adare Function object name Type Priority G R w t u 01 01 001 Binary Input 1M10xxC03B Binary Input md 0 CH A Disable Disable A 1 Bit Low v v C 1 CH A 1 fold Output 1 fold A 1Bt Low v v B 2 CH A 2 fold Output 2 fold A 1 Bit Low v v m 3 CH A 3 fold Output 3 fold A 1 Bit Low v v o 4 CH A 4 fold Output 4 fold A 1 Bit Low v v Fig 6 10 Communication object Multiple operation No Function Object name Data type flags DPT 1 4 CH X 1 fold 1 4 Output 1 fold X 1 4 1Bit C T 1 001 DPT_Switch The number of the communication object maximum 4 is set with the parameter Max number of operations Num of objects If the input is operated several times within a defined period the objects will send the relevant telegram value on the bus which the telegram value is set with the parameter value send object Tele Operation fold The objects will be described in the multiple operation parameter chapter
7. GVS K BUS KNX EIB Binary Inputs 4fold type to 0 The limit value 2 is preset which depend on the data width of main counter selected and the input field of limit value 2 can be freely edited Parameter Send counter value on change This parameter is used to select if a change of the counter state is to be sent for the main counter Options Yes No Parameter Send counter value cyclically This parameter is used to determine if the counter values are to be sent cyclically on the bus for the main counter The interval time between two telegrams that are sent cyclically to be set with the parameter Cyclically send counter value Base x Factor Options Yes No W 1 1 3 Binary Input 2304 4fold General Setting Differential Counter A Manual Automatic Setting Enable Disable manual operation p n Channel LED Data width of counter 16 bit 32768 32767 Preset Channel A D Counter limit value 1 0 Channel A 32768 32767 Main Counter A Counter limit value 2 1000 Differential Counter A 32768 32767 Channel B Shanna Mehean Like main counter set Channel D When counter crossing limit value Continue circular counting Send counter value on change no Send counter value cyclically no Fig 5 14 3 Parameter window Differential Counter X Parameter Date width of counter The data width of the differential counter is selected with this parameter The co
8. enable option is selected the manual operation button is enabled The first time the manual operation button is actuated closing of the external contact is simulated nothing happens when the button is released The second time the manual operation button is actuated opening of the external contact is simulated nothing happens when the button is released If the disable option is selected the manual operation button is disabled and the manual operation buttons do not have a function On disabled channels the respective channel LED will not react if the respective manual operation button is pressed For safety relevant systems such as for fault signals the button functions are inhibited using the disable option 12 SS SSS ES N www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold 5 4 Parameter window Channel LED Parameter window Channel LED can be shown in fig 5 4 It used to set channel LED indicate as a normal or inverted function for binary input in manual or automatic mode W 1 1 3 Binary Input 2304 4fold General Setting Channel LED Manual Automatic Setting Enable Disable manual operation Channel LED LED indicate of Channel A Normal Preset Channel 4 D Channel A LED indicate of Channel B Normal Channel B Channel C LED indicate of Channel C Normal Channel D LED indicate of Cha
9. 5 CH X Long fold Output Long fold X 1Bit C T 1 001 DPT_Switch It is visible if parameter Additional object for long operation selected yes Once detected a long operation the object will send telegram value on the bus the telegram is set with the parameter value send object Tele Long operation Table 10 Communication object table Multiple operation 61 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold 6 11 Communication object Shutter control The communication object Shutter Control will be shown in Fig 6 11 Ho Group Addr Function Object name Type Priority C R WIT U 01 01 001 Binary Input 1M10xxC038 Binary Input Ed 0 CH A Disable Disable A 1 Bit Low v v 1 CH A shutter UP DOWN Output shutter UPDOAN A 1 Bit Low v v m 2 CH A Stopjamella adj Output Stopjamella adj amp 1 Bit Low v v Ed 3 CH A Upper limit position Upper limit position amp 1 Bit Low v v Ed 4 CH A Lower limit position Lower limit position amp 1 Bit Low v v Fig 6 11 Communication object Shutter Control No Function Object name Data type flags DPT CH X shutter UP DOWN Output shutter UP DOWN X 1Bit C T 1 008 DPT_UpDown This communication object sends a shutter motion command up or down to the bus Telegram value 0 move up 1 mo
10. KNX EIB Binary Inputs 4fold Design Modular installation device Modular installation device ProM Dimensions 90x36x64mm HxWxD Installation On 35mm mounting rails Weight 0 1KG Housing color Plastic housing grey Approvals EIB KNX certificate CE mark In accordance with the EMC guideline and low voltage guideline 3 Circuit and dimension diagram 3 1Circuit diagram 4 Mi a KNX BUS 1 Programming button 4 Manual automatic LED 2 Programming LED 5 Manual automatic button 3 Bus connection terminal 6 Connection terminals 5 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold 7 Channel LED 8 Manual operation button 3 2Dimension diagram ie Oe VY I f OO0000 O 0O Q D O G Q O S 90 0 4 Project design and programming 4 1Overview of the functions ae Max number of Max number of group Max number of Application program ae i ae communication objects address associations Binary Inputs 4 fold 34 105 105 The following operating modes are available for each channel Switch function fault signal input The function is used for switching the lighting or scanning conventional contacts such as dimmer and switch actuator Distinction between long and short operation and cyclical sending of 6 www video star com cn 8620 393389
11. and Reaction on long operation falling edge If there is no distinction between short and long operation the parameter is used to define the data type that is sent when the contact is actuated with short or long operation If distinction it 30 T A E E E www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold defines the data type that is sent when the contact is actuated with rising edge or falling edge Parameter set as shown in Fig 5 11 3 Options No reaction lbit value 0 1 4 byte value 0 4294967295 Parameter Output value Parameter set as shown in fig 5 11 3 Here defines the value which is sent with the operation The value range depends on the data type set for the parameter Reaction on operation rising edge or Reaction on long operation falling edge Parameter Debounce time This parameter is used to set the debounce time Debouncing prevents unwanted multiple operation of the input e g due to bouncing of the contact Options 10ms 20ms 150ms Min operation The Min operation can be set in fig 5 8 It can only be set when there is no distinction between a short and a long operation 5 5 2 4 Scene control Parameter window Scene control X will be shown in Fig 5 12 it will be visible when the function of the channel Scene control is selected This function enables the
12. 2 CH X Dimming Dimming X 4bit C T 3 007 DPT_Control Dimming This communication object inputs by a long operation and sends the command to dim up or dim down It can make the dimming device on the bus to carry out relative dimming It will send a stop command to stop dimming when the long operation is end The object inputs with a long operation if the option dimming and switching is selected with the parameter dimming functionality There is no distinction between short long operations if the option is only dimming Table 6 5 Communication object table Switch Dimming 6 6 Communication object Value force output There are many data types and communication objects it will not list in Fig 6 6 The communication objects of different data types have the same operation that are transmit the object value which the range of transmit object value are different It is possible to distinguish a long short operation or not the two objects enable when distinguished Ho Group Addrd Function object name l Type Priority lc R w T lu 01 01 001 Binary Input 1M10xxC03B Binary Input a 0 CH A Disable Disable A 1Bt Low v vy E 1 CH A Value 1bit sr Output 1bit shortirising A 1 Bit Low v v E 2 CH A Yalue 1bit If Output 1bit long falling A 1 Bit Low v v Fig 6 6 Communication object Value Forced output No Function Object name Data typ
13. 2304 4fold General Setting Preset Channel A D Manual Automatic Setting Enable Disable manual operation i n Channel LED Function Select A B Seperately adjustable Preset Channel 4 D Channel A Function Select C D Seperately adjustable Channel B Channel C Channel D Cancel Default Fig 5 5 1 Parameter window Preset Channel A D separately adjustable working mode 14 RE ee Sz www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold W 1 1 3 Binary Input 230E 4fold General Setting Preset Channel A D Manual Automatic Setting Enable Disable manual operation 5 F ae Channel LED Function Select A B Jointly adjustable Dimming Shutter Preset Channel A D Function 4 B Dimming with two inputs with stop telegram Channel assignment 4 B Off darker On brighter Connect contact type 4 B normally closed Debounce Time 4 B 1 Oms Function Select C D Jointly adjustable Dimming Shutter Function C D Shutter with two inputs with stop telegram Channel assignment C D MOVE Up Z MOVE Down with stop Connect contact type C D normally closed Debounce Time C D 10ms Fig 5 5 2 Parameter window Preset Channel A D Jointly adjustable working mode 5 5 1 Jointly adjustable working mode for binary input In the
14. Base x Factor Base options 100ms 1s 1h Factor options 2 255 Parameter Number of objects for short long object operation The parameter is visible if the option yes has been selected with the parameter distinction between long and short operation It is able to set one or two communication objects for short long operation When one communication object is set long and short operations share a communication object When two communication objects are set long and short operations use a communication object separately Options lobject 24 I a a mT www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold 2objects 5 5 2 2 Switch Dimming operation mode Parameter window Switch Dimming can be shown in Fig 5 10 It is visible when Function of the channel Switch Dimming is selected It is possible that switch and dimming the lighting via a button operation Wi 1 1 3 Binary Input 230M 4fold General Setting Channel A Manual Automatic Setting Enable Disable manual operation Channel LED Function of the charnel v Preset Channel A D Channel A Connect contact type normally open Channel B ote Channel C Dimming functionality Dimming and switching Channel D Reaction on short operation ON Reaction on long operation Dim BRIGHTER DARKER with start BRIGHTEF Long operation after 1s Debo
15. E send read out the telegram The object values Output group A E can be modified via the bus for the duration of the long operation If the object Store scene X receives the value 0 on the bus the current object value can t be modified or the long operation has finished the object Store scene X sends the value 0 on the bus and the current object values also can t be modified Provided that a 1 has not been received at the object Store scene X a long operation 34 p a SSS E www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold is interpreted in the same way as a short operation i e recall scenes Parameter Long operation after This parameter is visible when the parameter Store scene is On long operation or On long operation and object value 1 it is defines the period T here after which an operation is interpreted as long Options 0 38 0 5s 10s Parameter Debounce time This parameter is used to set the debounce time Debouncing prevents unwanted multiple operation of the input e g due to bouncing of the contact Options 10ms 20ms 150ms Parameter Control of actuator group A F by This parameter is able to set various data types for each of 6 actuator groups A F The actuator gro
16. If a decrementing counter is defined with the parameter factor one counter step changes counter value by 10000 10000 namely negative counting the initial value is for the high limit value The device counts from the high limit to low limit When the count value is less than low limit value it will overflow Then the new count value the count value the low limit value the high limit value 1 and the device will start continually counting from the new count value If an incrementing counter is defined with the parameter factor one counter step changes counter value by 10000 10000 namely positive counting the initial value is for the low limit value The device counts from the low limit to high limit When the count value is greater than the high limit it will overflow Then the new count value the count value the high limit value the low limit value 1 and the device will start continually counting from the new count value The application program automatically compares the counter limit value1 and limit 41 T T E I SE A www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold value 2 looks for the high limit value from both set limits and commences to count up or down to suit the counting direction About the high low limit value parameters are described below The mode of counter is the same for the main and differential
17. If the Off darker On brighter option is selected represent input signal for off darker when contact of channel X is closed input signal for stop darker when contact of channel X is open However channel Y is opposite Input signal for on brighter when contact of channel Y is closed input signal for stop bright when contact of channel Y is open In the function assignment of channel X Y other options are similar with the above option The on off formation is sent to the bus via the object switch X Y the darker brighter formation is sent to the bus via the object dimming X Y Here setting the function assignment of channel X Y in the jointly function for shutter Option MOVE Down MOVE Up with stop MOVE Up MOVE Down with stop If the MOVE Down MOVE Up with stop option is selected the shutter move down when contact of channel X is closed the shutter move up when contact of channel Y is closed When the contact of channel X Y is open the shutter stops moving down up Another option is similar with the above option The shutter moves up down via the object Shutter move up down X Y To stop shutter moving via the object shutter stop X Y 16 I A E I M www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold Parameter Connect contact type X Y The parameter defines whether the input contact is
18. Multiple operation Enable the function if the input is operated several times within a defined period a defined object value can be modified by the number of operations In this manner for example different light scenes are possible by multiple pushes of a button 45 a a E ee www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold W 1 1 3 Binary Input 230E 4fold General Setting Channel A Manual Automatic Setting Enable Disable manual operation Functi n Son Channel LED unction of the channel Multiple operation Preset Channel A D Channel Connect contact type normally open Channel B Max number of operations Channel C Num of objects Channel D 2 fold operation Value send ON object tele operation fold L Value on every operation send Max time between two operation Additional object for long operation Long operation after Value send object Tele long operation L TOGGLE Debounce time 50ms Fig 15 Parameter window Multiple operation X Parameter Connect contact type This parameter is used to set whether the input contact is a normally closed or normally open contact Options Normally open Normally closed The parameters that are described in this chapter are based on normally open connect type as example the normally closed connect
19. The implement direction of the parameter Switch upwards is O00 001 011 111 the implement direction of the parameter Switch downwards is 111 011 001 000 After the bus voltage recovery the current value is 000 if the parameter Switch downwards is selected the effect will be invisible when operation then it is possible to operation after switch up a few levels by the object level increment decrement X Parameter Sequence is This parameter indicate the manage process of switching sequence Parameter Debounce time Min Time This parameter is used to set the debounce time Debouncing prevents unwanted multiple operation of the input e g due to bouncing of the contact Options 10ms 20ms 150ms Min operation The Min operation can be set in fig 5 8 38 ES Sa ee a ay oe en ne SSSR www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold 5 5 2 6 Counter Parameter window Counter X can be shown in Fig 5 14 It is visible when the input is operated with the function counter Using the Counter function the device is able to count the number of pulse edges at the input A differential counter is therefore available if required in addition to the standard counter Both counters are triggered by counting pulses but otherwise operate independently of each other The data wi
20. a normally closed or normally open contact when actuated for channels x y Options Normally closed Normally open The parameters that are described in this chapter are based on normally open connect type as example the normally close connect type is just opposite Parameter Debounce Time X Y This parameter is used to set the debounce time for channel X Y Debouncing prevents unwanted multiple operation of the input e g due to bouncing of the contact Options 10ms 20ms 150ms 5 5 2 Separately adjustable working mode for binary input In the separately adjustable working mode for binary input each channel can be set separately and parameters and objects which are assigned to each channel are the same Using channel A as an example described Parameter window Channel X The parameter window channel X can be shown in fig 5 6 The channel operating mode is set with this parameter Option No function Switch Switch Dimming Value Forced output Scene Control Switching sequence Counter Multiple operation Shutter control Each operating mode is assigned to the corresponding parameters and objects the follow chapters in detail 17 SSS ND ae a www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold W 1 1 3 Binary Input 2305 4fold General Setting Channel A Manual Automatic Setting Enable Disable manu
21. automatic LED is on In the automatic mode the manual automatic LED is off The devices are in automatic mode after connection to the bus and the respective manual operation buttons do not have a function 9 e a a a ae a a a S T G gt T NE SUN www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold W 1 1 3 Binary Input 2300H 4fold General Setting Manual Automatic Setting Manual Automatic Setting Enable Disable manual operation A Channel LED Manual Automatic button Enable Disable by object Preset Channel A D w i d a A TEPEE Ri Channel A anual to automatic metho utomatically and by push button Channel B Manual to automatic after 100 Channel C 10 60000 1s Channel D Report on Man Auto Status change Yes Fig 5 2 Parameter window Manual Automatic Setting Parameter Manual Automatic button The parameter defines if the switchover between the manual operation and automatic operation operating states is disabled or enabled using the manual automatic button on the binary input Options Enable Disable by object Enable If the enable disable by object is selected the En Dis Man Auto communication object appears The object receiving telegram value 0 disable the manual automatic button and then the manual automatic mode cannot be switched If the object receiving te
22. be sent to the bus Options Yes No If the yes option is selected the Report Man Auto Status communication object appears The object sends telegram value 1 the current status for manual operation the object sends telegram value 0 the current status for automatic operation When operation status changed the object sends the current status telegram on the bus immediately 5 3 Parameter window Enable Disable manual operation Parameter window Enable Disable manual operation can be shown in fig 5 3 It is used to set whether the respective manual operation buttons do have a function in the manual mode 11 a OS a SSE __ www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold W 1 1 3 Binary Input 230E 4fold General Setting Enable Disable manual operation Manual Automatic Setting Enable Disable manual operation Channel LED Channel Manual Button Enable Preset Channel 4 D Channel A Channel B Manual Button Enable Channel B Channel C Channel C Manual Button Enable Channel D Channel D Manual Button Enable Fig 5 3 Parameter window Enable Disable manual operation Parameter Channel A D Manual button This parameter enables or disables the operation of the manual operation button It is set separately for each channel Option Enable Disable If the
23. counter It is important to ensure that both limit values are set to different values If identical end limit values are entered the behaviour of the counter cannot be defined When disable the counter function both input scanning and object in out are disabled Any input status change will be ignored W 1 1 3 Binary Input 2300 4fold General Setting Main Counter A Manual Automatic Setting Enable Disable manual operation Channel LED Data width of counter 16 bit 32768 32767 Preset Channel A D Channel Counter limit value 2 Differential Counter A 32768 32767 Channel B Channel C Send counter value on change no Channel D Counter limit value 1 o 0 Send counter value cyclically no Cancel Default Fig 5 14 2 Parameter window Main Counter X Parameter Data width of counter The data width of the main counter is selected with this parameter The counting range and the data type of the object Mcounter Counter value X depend on this parameter setting Options 8bit 0 255 16bit 32768 32767 16bit 0 65535 32bit 2147470000 2147470000 Parameter Counter limit value 1 2 The parameter is used to set the counter limit value The limit value 1 is preset for every data 42 SRT EN ENTE E _ _ _ SSE www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465
24. dimming command to dim up or dim down It can make the dimming device on the bus to carry out relative dimming It will send a stop command to stop dimming when the 53 E www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold operation is end 2 Switch X Y Switch X Y Ibit C T 1 001 DPT_Switch This communication object is used to send switch command Telegram value 0 OFF 1 ON Table 6 2 Communication object table Jointly adjustable Dimming 6 3 Communication object Jointly adjustable Shutter The communication object Jointly adjustable Shutter can be shown in Fig 6 3 Ho Group Addrd Function Object name Type Priority C R W T U 01 01 001 Binary Input 1M10xxC03B Binary Input Ed 0 CH AJB Disable Disable A B 1 Bit Low v v C l 1 Shutter move up down 4 8 Shutter move up down A B 1 Bit Low v v 2 Shutter stop A B Shutter stop 4 8 1 Bit Low v v Fig 6 3 Communication object Jointly adjustable Shutter No Function Object name Data type flags DPT 1 Shutter move up down Shutter move up down X Y 1bit C T 1 008 X Y DPT_UpDown This communication object is used to send a shutter moving command up or down to the bus Telegram value 0 move up 1 move down 2 Shutter stop X Y Shutter stop X Y 1bit
25. exceeded MCounter Limit exceeded amp 1 Bit Low v v Ed 7 CH A Request counter value Request counter value 1Bit Low v v Fig 6 9 Communication object Counter No Function Object name Data type flags DPT 1 CH X Counter MCounter lbyte 0 255 CT 5 010 DPT_Value_1_Ucount value Counter value X 2byte 32768 32767 8 001 DPT_Value_2_Count 2byte 0 65535 7 001 DPT_Value_2_Ucount 59 S www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold 4byte 2147470000 13 001 DPT_Value_4_Count 2147470000 This communication object is used to transmit the current counting value of the main counter The counting range depends on data type which is defined with the parameter Date width of counter 2 CH X DCounter DCounter lbyte 0 255 C T 5 010 DPT_Value_1_Ucount value Counter value X 2byte 32768 32767 8 001 DPT_Value_2_Count 2byte 0 65535 7 001 DPT_Value_2_Ucount Abyte 2147470000 13 001 DPT_Value_4 Count 2147470000 It is visible if enable the parameter Enable differential counter This communication object is used to transmit the current counting value of the differential counter The counting range depends on data type which is defined with the parameter Date width of counter CH X DCounter DCounter Limit 1bit CT 1 002 DPT_Bool 3 Limit e
26. jointly adjustable working mode for binary input each jointly adjustable can be set separately and parameters and objects which are assigned to each jointly adjustable are the same Using channel A B jointly adjustable as an example described the parameters can be shown in fig 5 5 2 Parameter Function Select X Y This parameter set work ways of channel X Y Options Separately adjustable Jointly adjustable dimming shutter If the Jointly adjustable dimming shutter option is selected channel X Y for jointly adjustable work mode in the follow parameters appear Parameter Function X Y The parameter set the functions of channel X Y in the jointly adjustable which is used to set 15 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold dimming or shutter Option Dimming with two inputs with stop telegram Shutter with two inputs with stop telegram The jointly adjustable function of channel X Y can realize the dimming or the shutter via two objects In automatic operation mode channels input for 9 265V In manual operation mode channels input by manual operation buttons Parameter Channel assignment X Y The parameter set the function assignment of channel X Y in the jointly function for dimming Option Off darker on brighter On brighter off darker Toggle darker Toggle brighter Toggle darker Toggle brighter
27. on short operation The parameter is visible if the option dimming and switch has been selected with the parameter dimming functionality It is used to set if the value of object Switch X is ON OFF TOGGLE or if no action should be occur with short operation Options No action Off On Toggle Parameter Reaction on long operation The parameter is visible if the option dimming and switch has been selected with the parameter dimming functionality It is used to set if the object dimming X sends a brighter or darker telegram with long operation When the operation is over the object will send a stop dimming telegram Options Dimming BRIGHTER Dimming DARKER Dim BRIGHTER DARKER with start BRIGHTER Dim BRIGHTER DARKER with start DARKER If the option Dim BRIGHTER DARKER with start DARKER is selected the dim command which is the opposite to the last dim command is set and the first action is dimming darker with long operation Other options are similar with the option Parameter Long operation after The parameter is visible if the option dimming and switch has been selected with the parameter dimming functionality Here defines the period T after which an operation is 26 a www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold interpreted as long Options 0 3s 0 5s 10s Parameter Reactio
28. states of several actuator groups to be recalled and stored 31 ag ae SS ig www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB W 1 1 3 Binary Input 230W 4fold General Setting Manual Automatic Setting Enable Disable manual operation Channel LED Preset Channel 4 D Channel Scene Page 1 Scene Page 2 Channel B Channel C Channel D Function of the channel Connect contact type Store Scene long operation after Debounce time Binary Inputs 4fold Channel A Scene control bs normally open On long operation O5s Fig 5 12 1 Parameter window Scene control X W 1 1 3 Binary Input 230E 4fold General Setting Manual Automatic Setting Enable Disable manual operation Channel LED Preset Channel 4 D Channel A Scene Page 2 Channel B Channel C Channel D www video star com cn 8620 39338986 Control of actuator group by Preset value actuator group 4 ON OFF Store group by object Control of actuator group B by Preset value actuator group B ON OFF Store group B by object Control of actuator group C by Preset value actuator group C ON OFF Store group C by object Scene A Page 1 Info 1 bit value ON OFF ON no 1 bit value ON OFF ON no 1 bit value ON OFF ON maketing video
29. type as example the normally closed connect type is just opposite Parameter Operation functionality type This parameter sets the shutter operating functionality type which overview is provided in the following tables 1 push button short stepping long moving Short operation Alternate implement Stop Adjust upward or Stop Adjust downward operation alternate send the value of the object 0 and 1 Long operation Alternate implement Move up or Move down operation alternate send the value of the object 0 and 1 1 push button short moving long stepping Short operation Alternate implement Move up or Move down operation alternate send the value of the object 0 and 1 Long operation Alternate implement Stop Adjust upward or Stop Adjust downward operation alternate send the value of the object 0 and 1 1 push button operation moving On operation When operation send the command in sequence bas gt Move up gt Stop Adjust upward gt Move down gt Stop Adjust downward gt 1 switch operation moving Start of operation Alternate implement Move up or Move down operation contact closed alternate send the value of the object 0 and 1 End of operation Stop Adjust contact open 2 push button standard Short operation Stop Adjus
30. used to set the debounce time Debouncing prevents unwanted multiple operation of the input e g due to bouncing of the contact Options 10ms 20ms 150ms 5 5 2 8 Shutter Control Parameter window Shutter control X can be shown in fig 5 16 It is visible when the input is operated with the function shutter control The function enables the operation of blinds and shutters with buttons or switches W 1 1 3 Binary Input 2305 4fold General Setting E Channel A Manual Automatic Setting Enable Disable manual operation E pe z Channel LED unction of the channel Shutter Control v Preset Channel 4 D Channel A Connect contact type normally closed Channel B aay Channel C Operation functionality type 1 push button short stepping long moving Ch 1D Deea _ Short move UP DOWN Note about fuctionality Long Lamella I Long operation after O5s Debounce time Cancel Default Fig 5 15 Parameter window Shutter control X Parameter Connect contact type This parameter is used to set whether the input contact is a normally closed or normally open contact Options Normally open Normally closed 49 Ree EE eee ee ee eee eee ee eee eee aa www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold The parameters that are described in this chapter are based on normally open connect
31. 3 communication objects level 1 Jevel 2 and level 3 The first operation modified the value of level 1 the second operation modified the value of level 2 the third operation modified the value of level 3 the fourth from modified the value of level 3 the switch sequence is 000 001 011 111 011 The data send on the bus is the value of the communication object that after modified which is the alterative data The communication object level increment decrement X is used to increase or decrease the switch level 1 means increase level and 0 means decrease The follow table describes in detail A 3 Level sequence as an example the type is sequentially on off one push button Switching sequence Value of the communication objects Input operation number Binary code Level 3 Level 2 Level 1 0 000 Off Off Off 1 001 Off Off On 2 current operation 011 Off On On 3 111 On On On 4 011 Off On On In the above table the current operation is 2 the next time will be to operation 3 Butif the object level increment decrement X receive 1 Increase a Level the next time will jump one time forward and the next time will be to operation 4 also if the object level increment decrement X receive 0 decrement a level the next time will jump one time backward and the next time will be to position 2 no change I
32. 86 maketing video star com cn Tel Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold the contact state are possible Switch dimming function For switching dimming the lighting via a one push button or two push buttons function Start stop dimming and stepwise dimming as well as dimming via a single push button is possible Value force output It is possible to send different values or data types e g temperature values time or scene after a short long operation The activation deactivation of the priority control of actuators is also possible No distinction between long and short operation sending different values or data types on rising falling edge Scene control The function is used for recalling and storing the states of several actuator groups The actuator groups can be controlled via max 6 individual objects Switching sequence The function is used for the operation of several actuator groups in preset sequences e g the latching relay It is also used for operation of several loads in a fixed switching sequence Counter This is used for counting input pulses Different data types can be set for the counter It is also able to set the counting rate and whether to sending the current counting values cyclically to the bus When enable the differential counter the differential counter can reset the count value and report in count overflow Count can be stopped in overflow Thereby it is convenien
33. K BUS Binary Inputs 4 fold User manual Ver 1 CTBI 04 00 1 KNX EIB Intelligent Installation Systems ___36 0 a 64 0 a __ E o o O e gt i oh www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold Contents 1 General 3 1 1 Product and functional overview 3 2 Technical data 4 3 Circuit and dimension diagram 5 3 1Circuit diagram 5 3 2Dimension diagram 6 4 Project design and programming 6 4 1Overview of the functions 6 5 Parameter setting description in the ETS 8 5 1
34. Parameter window General Setting 8 5 2 Parameter window Manual Automatic Setting 9 5 3 Parameter window Enable Disable manual operation 11 5 4 Parameter window Channel LED 13 5 5 Parameter window Preset Channel A D 14 5 5 1 Jointly adjustable working mode for binary input 15 5 5 2 Separately adjustable working mode for binary input 17 5 5 2 1 Switch operating mode 18 5 5 2 2 Switch Dimming operation mode 25 5 5 2 3 Value Forced output 28 5 5 2 4 Scene control 31 5 5 2 5 Switching sequence
35. _2_Ucount 2byte Float 9 001 DPT_Value_Temp 3byte time of day 10 001 DPT_TimeOfDay 4byte 2147483648 13 001 DPT_Value_4 Count 2147483647 4byte 0 4294967295 12 001 DPT_Value_4_Ucount This communication object is used to transmit the input value It is only transmit the object value in long operation if distinguish a long and short operation It will transmit the object value in falling edge if no distinction between long and short operation The object value range depend on the data type The data type is set in the parameter Reaction on long operation falling edge Table 6 6 Communication object table Value Forced output 6 7 Communication object Scene control The communication object Scene control will be shown in Fig 6 4 The actuator groups can be controlled via max 6 individual objects which provided 3 data types 57 gt gt E gt E Ei _ E E gt _ gt _ gt _ gt E E EEEEEEEEEE_ E _ Ej gt LL T T G www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold Ho Group Addrd Function Object name Type Priority c r w t u 01 01 001 Binary Input 1M10xxC03B Binary Input BY o CHA Disable Disable A 1 Bit Low v v Ed 1 CH A Store scene Store scene A 1 Bit Low v vv mA 2 CH A 1bit Group A Output 1bit Group A A 1Bit Low v vvY E
36. al operation Channel LED Function of the channel No Function Preset Channel 4 D No Function Channel A Channel B Channel C Channel D Shutter Control Fig 5 6 Parameter window Channel X 5 5 2 1 Switch operating mode Parameter window Switch operating mode can be shown in fig 5 4 and fig 5 9 No distinguish between long and short operation in Fig 5 7 It is opposite in Fig 5 9 18 RN a N www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold W 1 1 3 Binary Input 2300 4fold General Setting Channel A Manual Automatic Setting Enable Disable manual operation Channel LED Function of the channel Preset Channel A D Distinction between long and Channel A short operation Channel B Channel C Cyclic send Tele Tele switch Channel D Reaction on closing the contact OFF Rising edge Reaction on opening the contact Falling edge no action Interval of Tele cyclic send Base 1s Factor 1 255 10 Send object value after voltage N recovery if YES not equal TOGGLE es Debounce time Min Time Fig 5 7 Parameter window Switch No distinction long short operation Parameter Distinction between long and short operation This parameter defines whether the input distinguishes between a short and long operation If yes is selected th
37. an Auto Status Ibit C T 1 011 DPT_State The object is used to send the status report after man auto operation status changed Telegram value O the current status for automatic operation 1 the current status for manual operation Table 6 1 Communication object table Manual Automatic 6 2 Communication object Jointly adjustable Dimming The communication object Jointly adjustable dimming can be shown in Fig 6 2 Ho Group Addre Function Object name Type Priority C R W T U 01 01 001 Binary Input 1M10xxC03B Binary Input of o CH A Disable Disable A B 1Bit Low v v B 1 Dimming iB Dimming IB 4Bt Low v v H 2 Switch AB Switch AB 1 Bit Low v va Fig 6 2 Communication object Jointly adjustable Dimming No Function Object name Data type flags DPT 0 CHX Y disable CHX Y disable Ibit C W 1 003 DPT_Enable When enable the jointly adjustable function this communication object will be active to disable enable the channel jointly function Telegram value O disable the function 1 enable the function All objects of the function are ineffectiveness when the function is disabled The function default to enable after bus voltage recovery The object disable is the same for all jointly operation modes of the channel 1 Dimming X Y Dimming X Y 4bit C T 3 007 DPT_Control Dimming This communication object is used to send
38. arameter Brightness change on every sent The parameter is visible if the option step dimming has been selected with the parameter dimming mode It is used to set the change brightness in percent which is cyclically sent with every dim telegram Options 100 27 a I a a T a www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold Parameter Interval of Tele Cyclic send The parameter is visible if the option step dimming has been selected with the parameter dimming mode It is used to set the interval time between two telegrams that are sent cyclically during a long operation Options 0 3s 0 5s 5 5 2 3 Value Forced output Parameter window Value Forced output can be shown in Fig 5 11 It is visible when Function of the channel Value Forced output is selected W 1 1 3 Binary Input 230 4fold General Setting Channel A Manual Automatic Setting Enable Disable manual operation Channel LED Function of the channel Value Forced output v Preset Channel A D Distinction between long and yi m Channel short operation a Channel A Force out Value Channel B Connect contact type normally open Channel C Long operation after Channel D base us Factor 2 255 10 Debounce time Cancel Default l Fig 5 11 1 Parameter window Value Force output X Distinction long short oper
39. ation 28 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold W 1 1 3 Binary Input 2305 4fold General Setting Channel A Manual Automatic Setting Enable Disable manual operation 5 Channel LED Function of the channel Value Forced output Preset Channel A D Distinction between long and Channel A short operation x Channel amp Force out Value Send object value after Channel B voltage recovery Channel C Channel D Debounce time Min Time No v Fig 5 11 2 Parameter window Value Force output X No distinction long short operation W 1 1 3 Binary Input 230E 4fold General Setting Channel A Force out Value Manual Automatic Setting Enable Disable manual operation i rae m Channel LED Reaction on operation rising edge 1 bit value 0 1 Preset Channel 4 D Channel Output value 0 1 0 Channel Force out Value Channel B Reaction on long operation falling edge 1 bit value 0 1 Channel C Channel D Output value 0 1 0 Cancel Default Info l www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold Fig 5 11 3 Parameter window Force out Value X Parameter Distinction between long and short operation This parameter defines whether the input disting
40. d 3 CH A 1bit Group B Output 1bit Group B A 1 Bit Low v vvYv G4 4 CH A hit Group C Output 1bit Group C A 1Bt Low v vvv Ed 5 CH A 1bit Group D Output 1bit Group D amp 1 Bit Low v vvYv ad 6 CH A 1bit Group E Output 1bit Group E amp 1Bit Low v vveY ad 7 CH A 1bit Group F Output 1bit Group F A 1Bit Low v y yyxy Fig 6 7 Communication object Scene control No Function Object name Data type flags DPT 1 CH X Store scene Store scene X 1Bit C W T 1 002 DPT_Bool The communication object is used to store scene if as soon as a long operation is detected and the object has the value 1 or only the object receives the value 1 storing is activated If the object receives or sends the value 0 storing is ended The storage manners of scene are described in the parameter setting chapter 2 7 CH X Ilbit l1byte 2byte Output 1bit ON OFF C W T 1 001 DPT_Switch Group A F 1bit lbyte 2byte 1byte 0 100 U 5 001 DPT_Scaling Group A F X 1byte 0 255 5 010 DPT_Value_1_Ucount 2byte Float 9 001 DPT_Value_Temp The communication object is used to control the actuator group it can control by a 1 bit 8 bit data or 16 bit data set by parameter When saving the scene the object output 1bit 8bit group A E will be read and which can be modified and storage on the bus After the bus voltage recovery the value of the object resume to the default value and the new sto
41. dth which has been selected for both counters can be set to same or different The function of differential counter is similar with the main counter The different is that the differential counter can reset the counter value count from the initial value and stop counting after overflow via the bus The parameters of main counter can be set in fig 5 14 1 and fig 5 14 2 The parameters of differential counter can be set in fig 5 14 1 and fig 5 14 3 The parameters set as follows E 1 1 3 Binary Input 2300 4fold General Setting Channel A Manual Automatic Setting Enable Disable manual operation Channel LED Function of the channel Preset Channel 4 D Channel Debounce time Min Time Main Counter A i Differential Counter A Enable Differential Counter Channel B Channel C Pulse detection on Closing contact rising edge Channel D Mode of counter Normal 1 Send object value after voltage recover No Cyclically send conter value Base Factor 1 255 Cancel Default Fig 5 14 1 Parameter window Counter X Parameter Debounce time Min Time 39 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold This parameter is used to set the debounce time Debouncing prevents unwanted multiple operation of the input e g due to bouncing of the contact Options 10ms 20ms
42. e contact rising edge opening the contact falling edge If one of the two parameters has the value toggle no values are sent in general on the bus after bus voltage recovery If No reaction or Stop cyclic transmission is selected there is no values are sent on the bus either Parameter Debounce time This parameter is used to set the debounce time Debouncing prevents unwanted multiple operation of the input e g due to bouncing of the contact Options 10ms 20ms 150ms Min operation The minimum operation time can only be set when there is no distinction between a short and a long operation This option is different from others the Minimum time of the contact operation is not only means the effective time when contact close but also the contact open The parameter window can be shown in Fig 5 8 21 a aT ag er ee www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold W 1 1 3 Binary Input 230H 4fold General Setting A MiniTime Manual Automatic Setting Enable Disable manual operation D ET Channel LED Minimum operation time base Preset Channel A D Minimum operation time Factor Channel 4 1 255 Channel B Channel C Channel D Fig 5 8 Parameter window X Mini Time Parameter Minimum operation time BasexFactor The minimum time of the contact operation is BasexFac
43. e flags DPT 1bit 0 1 1 001 DPT_Switch 1 CH X Value sr Output C T lbyte 128 127 6 010 DPT_Value_1_Count short rising X lbyte 0 255 5 010 DPT_Value_1_Ucount lbyte recall scene 17 001 DPT_SceneControl lbyte store scene 18 001 DPT_SceneControl 56 me EN www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold 2byte 32768 32767 2byte 0 65535 8 001 DPT_Value_2 Count 7 001 DPT_Value_2_Ucount 2byte Float 9 001 DPT_Value_Temp 3byte time of day 10 001 DPT_TimeOfDay Abyte 2147483648 13 001 DPT_Value_4 Count 2147483647 4byte 0 4294967295 12 001 DPT_Value_4_Ucount This communication object is used to transmit the input value It is only transmit the object value in short operation if distinguish a long and short operation It will transmit the object value in rising edge if no distinction between long and short operation The object value range depend on the data type The data type is set in the parameter Reaction on operation rising edge 2 CH X Value lf Output long falling X 1bit 0 1 Ibyte 128 127 1byte 0 255 1byte recall scene lbyte store scene 2byte 32768 32767 2byte 0 65535 C T 1 001 DPT_Switch 6 010 DPT_Value_1_Count 5 010 DPT_Value_1_Ucount 17 001 DPT_SceneControl 18 001 DPT_SceneControl 8 001 DPT_Value_2_Count 7 001 DPT_Value
44. ential counter For example the counter states are incremented by 1 after 5 input 40 ae Eye EEE www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold pulses Options 1 10000 Parameter Factor one counter step changes counter value by 10000 10000 The parameter is visible if the option manual set has been selected with the parameter mode of counter It is used to set the level of change on the counter state with each counter pulse for the main and differential counter Options 10000 10000 Negative entry e g 5 defines a decrementing counter e g 100 0 Positive entry e g 10 defines an incrementing counter e g 0 100 Parameter Send object values after voltage recover The parameter set whether the device sends the object value Mcounter counter value X on the bus after bus voltage recover If the differential counter has been enabled it also sends the object value Dcounter counter value X on the bus Options Yes No The main and differential counters are reset to the starting value in the bus voltage failure Parameter Cyclically send counter value Base x Factor The parameter is used to set the interval time between two telegrams that are sent cyclically Transmission cycle time Base xFactor Base options 100ms 1s 1min 1h Factor options 1 255 Note Counting rules the mode of counter
45. ere is a delay after opening closing the contact to determine whether there is a short or long operation Only then is a possible reaction triggered The following diagram illustrates the function Without distinction With distinction between short long between short long oo Input signal Possible reaction Possible reaction to the input signal to the input signal Option yes 19 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold No Note The long operation in the below chapters are the same with here T is the period after which a push button action is recognised as a long operation Parameter Cyclical send Tele Tele Switch This parameter is visible if there is no distinction between a short and long operation It is able to set whether to send the current value of object Switch X cyclically on the bus Options No Always If switch off If switch on If the parameter value always is selected the object sends cyclically on the bus regardless of its value is O or 1 If the parameter value if switch off or if switch on is set only the corresponding object value is sent cyclically Parameter Reaction on closing the contact rising edge Reaction on opening the contact falling edge This parameter is visible if there is no distinction between a short and long o
46. he switching sequence parameter chapter 6 CH X Level Level lbit C W 1 001 DPT_Switch increment decrement increment decrement X The communication object level increment decrement X is used to increase decrease the level of the switch It will increase one level when receiving 1 and decrease a level when receiving 0 The object is derailed description in the switching sequence parameter chapter Table 8 Communication object table Switching sequence 6 9 Communication object Counter The communication object Counter will be shown in Fig 6 9 Including main counter and differential counter communication object both these communication objects will start count when the input pulse is generated with an operation The data width which has been selected for both counters can be set to same or different But the counting is independent of each other Ho Group Addr Function Object name Type Priority C R WI T U 01 01 001 Binary Input 1M10xxC03B Binary Input Ed 0 CH A Disable Disable A 1 Bit Low vy v Ed 1 CH A Counter value MCounter Counter value 4 2Byte Low v vv Ed 2 CH A DCounter value DCounter Counter value amp 2 Byte Low v vv B 3 CH A DCounter Limit exceeded DCounter Limit exceeded amp 1 Bit Low vy v 4 CH A DCounter Reset value DCounter Reset value A 1 Bit Low v v md 5 CH A DCounter Stop DCounter Stop A 15t Low v vv B 6 CH A MCounter Limit
47. in a defined sequence W 1 1 3 Binary Input 2305 4fold General Setting Channel A Manual Automatic Setting Enable Disable manual operation a e e r ap Channel LED unction of the channel Switching sequence Preset Channel A D Channel amp Connect contact type normally open Channel B Channel C No of objects 3level Channel D Type of swiching sequence Sequentially on offseveral push buttons Function on operation Switch upwards Sequence is neen 000 001 011 111 lt NOTE Information Debounce time Min Time 50ms Cancel Default Fig 5 13 Parameter window Switching sequence X Parameter Connect contact type This parameter is used to set whether the input contact is a normally closed or normally open contact Options Normally open Normally closed The parameters that are described in this chapter are based on normally open connect type as example the normally closed connect type is just opposite Parameter No of objects 36 EEN N www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold The parameter set the number of communication objects has the same meaning the number of levels max 5 The communication objects level 1 to level 5 are enabled accordingly Options 2level 3level 4level Slevel For example parameter 3level means there are
48. legram value 1 enable the manual automatic button and then the manual automatic mode can be switched If the enable is selected the manual automatic button has been enabled Parameter Manual to automatic method This parameter defines how long the binary input remains in the manual operation state after the manual automatic button has been pressed Options 10 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold By push button Automatically and by push button If the by push button option is selected the binary input will remain in manual operation until the manual automatic button is pressed again If the automatically and by push button option is selected the binary input will remain in manual operation until the manual automatic button is pressed again or the parameterized Manual to automatic after 10 60000 1s has timed out Parameter Manual to automatic after 10 60000 1s The parameter appears when automatically and by push button is selected in the parameter manual to automatic method It is used for setting the time for automatic reset from the manual operation to automatic operation state after the last push of a button Option 10 60000s Parameter Report on Man Auto status change The parameter defines whether report on man auto status change and the current status can
49. minals The connection to the bus is implemented using the supplied bus connection terminal The binary input is connected to the input directly instead of an extra voltage supply It is able to use the Engineering Tool Software ETS ETS2 v1 3 or later with a VD2 VD3 file to allocate the physical address and set the parameters but a VD3 file imported is required for EST3 software The devices feature one manual operation button and one LED per channel The inputs can be operated manually with this button and the LED indicates contact connection state In the case of manual operation there is no additional voltage input The binary inputs serve as interfaces for operation of EIB KNX systems via conventional buttons switches or for coupling of binary signals signal contacts such as input 24V 230V The binary input has many functions that can be used in a wide variety of application areas The following list provides an overview gt Switch and dimming function also 1 button operation gt Control of blinds and shutters also 1 button operation gt Sending of values e g temperature values time etc gt Control and storing of light scenes 3 ELE SELL S SS SSS Se www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold gt Operation of various loads by multiple push button actions gt Operation of several loads in a fixed switching seque
50. mmunicate with the bus The communication object and the object in each channel are the same using channel A as the example to introduce the function of each communication object in the following 6 1 Communication object Manual Automatic Note C in Flag column in the below table means that the object has a normal link to the bus W means the object value can be modified via the bus R means the value of the object can be read via the bus T means that a telegram is transmitted when the object value has been modified U means that value response telegrams are interpreted as a write command the value of the object is updated 52 a a aT a a DT www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold Ho Group Addr Function Object name Type Priority C R WI T U J 01 01 001 Binary Input 1M10xxCO3B Binary Input Ed 32 En Dis Man Auto En Dis Man Auto 1 Bit Low v va C 33 Report Man Auto Status Report Man Auto Status 1 Bit Low vy v Fig 6 1 Communication object Manual Automatic No Function Object name Data type flags DPT 32 En Dis Man Auto En Dis Man Auto 1bit C W 1 003 DPT_Enable The object is used to disable and enable the manual automatic button Telegram value O disable the manual automatic button 1 enable the manual automatic button 33 Report Man Auto Status Report M
51. ms to decrease the burthen on the bus It is possible to set how many telegrams can be sent within an adjustment period Options Yes No 8 Ea R www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold When yes is selected in this parameter the Period and Max Number Tele Within a period parameters appear Parameter Period The limit time of sending telegrams is set with the parameter Options 300ms 500ms When device completes initialization in bus voltage recovery start the observation period and start count the sent telegrams As soon as the Max Number of transmitted telegrams has been reached no further telegrams are sent on the bus until the end of the observation period With the start of a new observation period the telegram counter is reset to zero and the sending of telegrams is permitted again Parameter Max Number Tele Within a period This parameter sets the number of telegrams which can be sent within an observation period Options 5 2 Parameter window Manual Automatic Setting Parameter window Manual Automatic Setting can be shown in fig 5 2 It is possible to switch between manual operation and automatic operation by pressing the manual automatic button about 2s When the manual automatic operations are switched successfully the manual automatic LED will flash for three times In the manual mode the manual
52. n on operation The parameter is visible if the option dimming and switch has been selected with the parameter dimming functionality There is no distinction between short and long operation Therefore the object dimming X will send a brighter or darker telegram after an operation trigger When the operation is over the object will send a stop dimming telegram Options Dimming BRIGHTER Dimming DARKER Dim BRIGHTER DARKER with start BRIGHTER Dim BRIGHTER DARKER with start DARKER Parameter Debounce time This parameter is used to set the debounce time Debouncing prevents unwanted multiple operation of the input e g due to bouncing of the contact Options 10ms 20ms 150ms Min operation The Min operation can be set in fig 5 8 if the option only dimming and switch has been selected with the parameter dimming functionality Parameter Dimming mode The parameter sets whether the dimming mode is start stop dimming or steps dimming Options Start stop dimming Steps dimming If the option start stop dimming is selected it will start the dimming mode with a bright or darker telegram and end the dimming mode with a stop dimming telegram at the end of operation The dimming telegram need not be cyclically sent in start stop dimming mode If the option step dimming is selected the dimming telegram is sent cyclically during a long operation The stop telegram ends the dimming process at the end of operation P
53. n this function It only send the changed bit This code value compare to the operation 1 value for example from operation 2 to operation 3 The Most Significant Bit is changed the object according to Level 3 will send value 1 Although the number of levels is different their processes are similar in the case of the same switch sequence type 37 eee a l O E www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold Parameter Type of switching sequence The switching sequence can be selected here Each sequence has other object values for each switching level Options Sequentially on off one push button Sequentially on off several push buttons All combinations Take 3level as the example to explain the difference between them send the changed data on the bus data 0 OFF 1 ON Type of switching sequence Example Sequentially on off one push button 000 001 011 111 011 001 Sequentially on off several push buttons 000 001 011 111or 111 011 001 000 All combinations 000 001 011 010 110 111 101 100 Gray code Parameter Function on operation The parameter is only visible in the switching sequence Sequentially on off several push buttons It can be set whether an operation of the push button switches up or down a level Options Switch upwards Switch downwards
54. nce gt Standard counting and differential counting gt Channel disable enable function Each input can take over any of the functions described above Buttons on the front of the device can be used to simulate the input state The status of the inputs are displayed by LEDS 2 Technical data Power supply Bus voltage Current consumption bus Power consumption bus Input Number Permitted voltage range U Input current I Signal level for 0 signal Signal level for 1 signal Connections EIB KNX Inputs Cable cross section Tightening torque Permitted cable length Operating and display Programming LED and button 21 30V DC via the EIB bus lt 12mA lt 360mW Orisa 265V AC DC Max 2mA Oc ised 3V AC DC SSE 265V AC DC Via bus connection terminal Using screw terminals Multi core 0 2 2 5mm Single core 0 2 4 0mm Max 0 6 Nm lt 100M cross section for 1 5mm For assignment of the physical address elements Channel LED 1LED per channel for display of the input state Manual operation button 1 button per channel for changing the input Manual Automatic LED State 1LED for display of the manual automatic mode states Manual Automatic button 1 button for switchover of manual and automatic mode Temperature rang Operation ED ACen alee Storage 25 C 55 C Transport 25 C 70 C 4 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS
55. nnel D Normal Fig 5 4 Parameter window Channel LED Parameter Channel A X LED This parameter is used to represent the LED display as a normal or inverted function It is set separately for each channel Option Normal Inverted If the Normal option is selected represent the LED display as a normal function then contact is closed signal is present LED is on Contact is open no signal LED is off If the inverted option is selected represent the LED display as a inverted function then contact is closed signal is present LED is off Contact is open no signal LED is on 13 a N www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold 5 5 Parameter window Preset Channel A D Parameter window Preset Channel A D can be shown in fig 5 5 Channel function of Binary input can select two ways of working If the separately adjustable working way is selected each channel can be set separately If the jointly adjustable working way is selected two channels can be set to work jointly such as channel A and channel B jointly channel C and channel D jointly Each jointly adjustable can be set separately which is used to set dimming and shutter functions It is able to switch and dimming together with one button operation input and it is also able to move and stop shutter with one button operation E 1 1 3 Binary Input
56. ong operation It is visible if the shutter control type is 2 push button standard This parameter defines the operation with long operation Options Move up Move down Parameter Reaction on operation It is visible if the shutter operation functionally type is 2 push button moving shutter 2 switch operation moving shutter and 2 push button stepping It is defines the action when operation Different operation functionally type makes different operate action The former two operations functionally type is move up and down the last operation functionally type is stop lamella reaction Options Move up Move down 51 a ET www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold Options Stop lamella up Stop lamella down Parameter Long operation after This parameter is visible if long operation activate it is defines the period T here after which an operation is interpreted as long Options 0 38 0 5s 10s Parameter Denounce time This parameter is used to set the debounce time Debouncing prevents unwanted multiple operation of the input e g due to bouncing of the contact Options Options 10ms 20ms 150ms 6 Description of communication object The communication object is the medium to communicate other device on the bus namely only the communication object can co
57. only possible with a decrementing counter or exceeds the high limit value only possible with an incrementing counter the object Dcounter stop X will send telegram 0 on the bus and the counter stops counting until the counter value is reset or the object Dcounter stop X receiving telegram 1 If the object Dcounter stop X receiving telegram 1 the counter continues circular counting from the new count value If the counter value is reset it will count from the initial value of the parameter The new count value is described in the above chapters Parameter Send counter value on change 44 ESSS __ E gt E___ a ye ee er Sa www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold This parameter is used to select if a change of the counter state is to be sent for the differential counter Options Yes No Parameter Send counter value cyclically This parameter is used to determine if the counter values are to be sent cyclically on the bus for the differential counter The interval time between two telegrams that are sent cyclically to be set with the parameter Cyclically send counter value Base x Factor Options Yes No 5 5 2 7 Push button with multiple operation Parameter window Multiple operation X can be shown in Fig 5 15 It is visible when the input is operated with the function
58. peration There is set the reaction on closing rising edge or opening falling edge the contact Options No action Off On Toggle Stop cyclic send If Toggle is selected the current operation is inverted in next operation For example if the current operation is On the next operation will become off If Stop cyclic transmission is selected it will stop the cyclical sending telegram till there is a new object value to be sent If No action is selected it will not implement any operation Parameter Interval of Tele cyclic send Base x Factor This parameter is used to set the interval time between two telegrams that are sent cyclically it is visible if cyclical sending has been set Transmission cycle time Basex Factor Base options 0 5s Is 1h 20 P SSS ae gag www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold Factor options TN 3255 Parameter Send object value after voltage recovery if yes not equal toggle It can be set whether to send the value of the object Tele Switch X on the bus after bus voltage recovery this parameter is visible if there is no distinction between a short and long operation Options Yes No If Yes is selected a value is however only sent on the bus if the value toggle has not been set in either of the two parameters Reaction on closing th
59. rage value will be lost Table 6 7 Communication object table Scene control 6 8 Communication object Switch sequence The communication object Switching sequence will be shown in Fig 6 8 It can modify the object value with an operation step by step An object corresponds to one switch level Ho Group Addre Function Object name Type Priority C R WI T U mamm Binary Input 1M10xxC03B Binary Input m 0 CH A Disable Disable A 1Bit Low v v 4 CH A level Output level 1 A 1Bt Low v v 2 CH A level 2 Output level 2 A 15t Low v v 3 CH A level 3 Output level 3 A 1 Bit Low v vy 4 CH A level 4 Output level 4 4 1 Bit Low v v C 5 CH A level 5 Output level 5 4 1 Bit Low v v m 6 CH A Leve increament decrement Leve increament decrement A 1 Bit Low v v Fig 6 8 Communication object Switching sequence 58 MEN www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold No Function Object name Data type flags DPT 1 5 CH X level 1 1 5 Output level 1 1 5 X 1bit C T 1 001 DPT_Switch The number of the communication object maximum 5 which the levels of switch are set by parameter No of object The communication object sent on the bus is the object which one of binary code is modified which the bit of the binary code had been changed The objects are derailed description in t
60. se is Factor 2 255 10 Number of objects for short long object operation Tobject Debounce time 50ms www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold Fig 5 9 Parameter window Switch Distinction long short operation Parameter Connected contact type This parameter is visible if there is distinction between a short and long operation It is used to set whether the input contact is a normally closed or normally open contact Options Normally open Normally closed The parameters that are described in this chapter are based on normally open connect type as example the normally close connect type is just opposite Parameter Reaction on short operation or Reaction on long operation The parameter is visible if the option yes has been selected with the parameter distinction between long and short operation It is used to set if the object value is ON OFF TOGGLE or if no action should be occur The object value is updated as soon as it has been determined if a short or long operation has occurred Options No action Off On Toggle Parameter Long operation after basexFactor The parameter is visible if the option yes has been selected with the parameter distinction between long and short operation Here defines the period T after which an operation is interpreted as long TL
61. star com cn Info Tel Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold W 1 1 3 Binary Input 2305 4fold General Setting Scene A Page 2 Manual Automatic Setting Enable Disable manual operation Channel LED Preset Channel A D Preset value actuator group D ON Channel ON OFF Scene A Page 1 Store group D by obiect ro Channel B Channel C Control of actuator group E by 1 bit value ON OFF Channel D Control of actuator group D by 1 bit value ON OFF Preset value actuator group E ON ON OFF Store group E by object no Control of actuator group F by 1 bit value ON OFF Preset value actuator group F ON ON OFF Store group F by object Fig 5 12 2 Parameter window Scene X Page 1 2 X Parameter Connect contact type This parameter is used to set whether the input contact is a normally closed or normally open contact Options Normally open Normally closed The parameters that are described in this chapter are based on normally open connect type as example the normally close connect type is just opposite Parameter Store scene This parameter defines the manner in storing of the current scene Options No On long operation With object value 1 On long operation and object value 1 The manner of storing scene in the following table provides an overview Parameter value Behavior 33
62. switched by actuation of the ON OFF or TOGGLE input With TOGGLE the previous value e g 1 is switched directly to the value 0 Telegram value 0 OFF 1 ON 2 CH X Switch long lbit C T 1 001 DPT_Switch This communication object is only visible if the parameter Distinction between long and short operation yes and the parameter Number of objects for short long object operation 2 objects This additional communication object is assigned to the long operation Telegram value 0 OFF 1 ON Table 6 4 Communication object table Switch 6 5 Communication object Switch Dimming Ho Group Addr Function Object name Type Priority C R W T U 01 01 001 Binary Input 1M10xxC03B Binary Input a o CH A Disable Disable A 1Bt Low EY I 4 CH A Switch Switch A 1Bt Low v vv a 2 CH A Dimming Dimming amp 4Bt Low v v Fig 6 5 Communication object Switch Dimming No Function Object name Data type flags DPT 1 CH X Switch Switch X 1bit C W T 1 001 DPT_Switch 55 SS TEN aR www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold It is visible if parameter Dimming functionality selected Dimming and switching Operate with a short operation to input the object value to carry out the relevant action such as ON OFF TOGGLE Telegram value 0 OFF 1 ON
63. t to count the daily consumption Push button with multiple operation For triggering various functions depending on the frequency of the operation A long operation can also be detected and trigger a function Shutter control For movement lamella adjustment of a blind or a shutter via a one push button or two push buttons function Eight preset operating responses are possible in total Channel disable enable function 7 ES ___E_ gt gt _ E SSS Sy a o SSE www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold Each channel of a device can be disabled separately via a communication object 5 Parameter setting description in the ETS 5 1 Parameter window General Setting Parameter window General Setting can be shown in fig 5 1 The function is used for limiting the number of sending telegrams to the bus which can affect the complete device The device initialization takes about 5s W i 1 3 Binary Input 230E 4fold General Setting Manual Automatic Setting Enable Disable manual operation ae Channel LED Limit number of Tele Preset Channel 4 D R Channel A Period Channel B Channel C Channel D Max Number Tele within a period 1 255 Cancel Default f Fig 5 1 Parameter window General Setting Parameter Limit number of Tele It is used to limit the number of sending telegra
64. t upward or Stop Adjust downward set by parameter Long operation Move up or Move down set by parameter 2 push button moving shutter On operation When operation send the command in sequence Move up down set by parameter 2 push button stepping On operation Stop Adjust upward or Stop Adjust downward 50 _ EE www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold set by parameter keep pressing the button can send cyclic 2 switch operation moving shutter Start of operation Move up or Move down set by parameter End of operation Stop Adjust upward or Stop Adjust downward the sending value is identical to the value that the operation starting Parameter Tele STOP lamella adj Cyclical send It is visible if the shutter control type is 1 push button short moving long stepping and 2 push button stepping It is able to set the interval time of sending the object stop adjust adj cyclical Options 0 38 0 5s 10s Parameter Reaction on short operation It is visible if the shutter control type is 2 push button standard This parameter defines the operation with short operation Options Stop lamella up Stop lamella down Parameter Reaction on l
65. ted the last object value will be sent after Max time between two operation elapsed Parameter Max time between two operation This parameter sets the maximum allowed interval time between two operations If no further operations occur within this time a new fold will be generated from 1 fold with the next operation Options 0 3s 0 5s 10s Parameter Additional object for long operation The parameter sets whether additional communication object for long operation Options Yes No If the option yes is selected in this parameter the following two parameters appear Parameter Long operation after This parameter is visible if the parameter additional object for long operation is yes it is defines the period T here after which an operation is interpreted as long Options 0 3s 0 5s 10s Parameter Value send object Tele Long Operation This parameter is visible if the parameter additional object for long operation is yes It is used to set the value of object output long fold that is to be sent on the bus with longer operation of input The settings ON OFF and Toggle are possible With Toggle the current object value is inverted Options On Off 48 a a a 2 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold Toggle Parameter Denounce time This parameter is
66. tor Base options 100ms 1h Factor options 1 255 Note The parameter window Debounce time and the explanation of option Min operation are the same with here in the below chapters To prevent the debounce process If a pulse edge is detected at the input the input reacts to it immediately e g by sending a telegram The debounce time Tp starts simultaneously The signal at the input is not evaluated within the debounce period As shown below 22 Ea EN www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold Input signal Detected pulse edge To T T Once a pulse edge has been detected at the input further edges are ignored for the duration of the debounce time Tp The process of preventing debounce in the below chapters are the same with here Tp is the effective time of a pulse edge input namely the period after a input signal is recognised as a operation W 1 1 3 Binary Input 230E 4fold General S etting Channel A Manual Automatic Setting Enable Disable manual operation Channel LED Function of the channel Preset Channel A D Distinction between long and Yes Channel short operation TAS Channel B Channel C Connect contact type normally open Channel D Reaction on short operation OFF Reaction on long operation no action Long operation after Ba
67. type is just opposite Parameter Max number of operations Num of objects This parameter is used to set the max number of operations The number is equal to the Output X fold of communication objects Options Single operation 2 fold operation 3 fold operation 4 fold operation The following describes in detail 3 fold operation as an example the value send for toggle If the option 3 fold operation is selected there are three objects value appear and they are 46 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold not independent meanwhile they send value according to a certain sequence 1 fold gt 2 fold gt 3 fold In order to state clear the following parameter Value on every operation set YES if operation count reach Max number of operations in a certain time every operation time lt 1s the first time of reach Max number of operations 3 fold send the same value with 1 fold and 2 fold and the next time 3 fold will carry out toggle action In the certain time if you don t reach Max number of operations the next operation will generate a new fold from 1 fold and carry out toggle action The following two forms state process of operation Operation OP OP OP OP OP eee Time lt ls lt ls lt ls Klisa oll E aeea Object 1f 2f 3f 3f_T B3f_T een Object value 1 1 1 0 O ais
68. uishes between a short and long operation If yes is selected there is a delay after opening closing the contact to determine whether there is a short or long operation Only then is a possible reaction triggered Options Yes No Parameter Connect contact type This parameter is visible if there is distinction between a short and long operation It is used to set whether the input contact is a normally closed or normally open contact Options Normally open Normally closed The parameters that are described in this chapter are based on normally open connect type as example the normally close connect type is just opposite Parameter Long operation after Base x Factor 2 255 The parameter is visible if the option yes has been selected with the parameter distinction between long and short operation Here defines the period T after which an operation is interpreted as long TL Base x Factor Base options 100ms Is 1h Factor options 2 255 Parameter Send object value after voltage recovery This parameter is visible if there is no distinction between a short and long operation as shown in fig 5 11 2 It can be set whether to send the value of the object Output long falling short rising X on the bus after bus voltage recovery Options Yes No If Yes is selected the object value will be sent on the bus after bus voltage recovery Parameter Reaction on operation rising edge
69. unce time 50ms Dimming mode Steps dimming Brightness change on every sent 1 56 Interval of Tele cyclic send 1s Cancel Default Fig 5 10 Parameter window Switch Dimming X Parameter Connect contact type This parameter defines whether the input contact is a normally closed or normally open contact Options Normally open Normally closed The parameters that are described in this chapter are based on normally open connect type as example the normally close connect type is just opposite Parameter Dimming functionality This parameter is used to define whether the lighting can only be dimmed or whether it also 25 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold should be permitted switching In this case a long operation actuated dimming and a short operation actuates switching Options Dimming and switching Only dimming If Only dimming is selected there is no distinction between a short and long operation Therefore the dimming is carried out immediately after an operation action there is not required to determine whether the operation is long or short If Dimming and switching is selected it will distinguish the operation is a short or long operation In this case the lighting is dimmed via a long operation and switched via a short operation Parameter Reaction
70. unting range 43 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold and the data type of the object DCounter Counter value X depend on this parameter setting Options 8bit 0 255 16bit 32768 32767 16bit 0 65535 32bit 2147470000 2147470000 Parameter Counter limit value 1 2 The parameter is used to set the counter limit value1 2 The limit value 1 2 are preset which depend on the data width of differential counter selected and the input field of limit value 1 2 can be freely edited Parameter Mode of counter The parameter indicates the counting mode of differential counter is the same with the main counter Parameter When counter crossing limit value This parameter sets the reaction when a limit value is reached Options Continue circular counting Stop until reset If Continue circular counting is selected the counter continues circular counting If the actual value falls below the low limit value only possible with a decrementing counter or exceeds the high limit value only possible with an incrementing counter the new count value is set to the start count value and the pulse count is continued The new count value is described in the above chapters If Stop until reset is selected the counter stops counting and waits for a reset If the actual value falls below the low limit value
71. ups can be controlled via max 6 individual objects Data types of the object Output 1bit 1byte 2byte group A F depend on the data types which has been selected for the actuator groups Options lbit value ON OFF lbyte value scale 0 100 lbyte value 0 255 2byte value float Parameter Preset value actuator group A F The parameter is used to set the preset value for each actuator group A F The value range depends on the data type set for the parameter control of actuator group A F by Parameter Store group A F by object It is used to set whether the preset value is allowed to be modified via the bus Options Yes No If the option yes is selected the preset value can be modified via the object Output lbit lbyte 2byte group A F If the bus voltage recovery this value will be modified as preset value That is the stored value is not saved 35 p SSS Se a age RS TT www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold 5 5 2 5 Switching sequence Parameter window Switching sequence can be shown in Fig 5 13 It is visible if the function of the channel Switching sequence is selected The switching sequence function enables up to five switch objects to be modified in a defined sequence by actuation of just a single input Thus up to reach five actuators or actuator groups can be switched
72. ve down 2 CH X Stop lamella adj Output Stop lamella adj X 1Bit C T 1 007 DPT_Step This communication object sends a stop command or lamella adjustment Telegram value O stop adjust up 1 stop adjust down 3 CH X Upper limit Upper limit position X 1Bit CW 1 002 DPT_Bool position The object is used to upper limit shutter moving Telegram value 0 no limit moving up 1 limit moving up 4 CH X Lower limit Lower limit position X 1Bit C W 1 002 DPT_Bool position The object is used to lower limit shutter moving Telegram value 0 no limit moving down 1 limit moving down Table 11 Communication object table Shutter Control 62 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465
73. www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Binary Inputs 4fold On long operation As soon as a long operation is detected the object store scene X sends the value 1 on the bus and the objects Output group A F send read out telegram If the object store scene X have received a telegram 1 then the object value 1 will not send out again when long operation The objects Output group A F can be modified via the bus for the duration of the long operation Once the long operation has finished the object Store scene X sends the value 0 on the bus and the current object value can not be modified On the long operation If the object Store scene X receives the value 0 on the bus even the long operation has not finished the current object value also can t be modified If object value 1 If the object Store scene X receives the value 1 the object values Output group A F are read out via the bus Then the objects Output group A F can be modified via the bus On receipt of the object value 0 the current object values can t be modified On long operation and object value 1 If the object Store scene X receives the value 1 on the bus on the next long operation the objects Output group A
74. xceeded exceeded X When the differential count value exceeded the limit value the object will send telegram value 1 which report counting overflow CH X DCounter DCounter Reset 1bit C W 1 015 DPT_Reset 4 Reset value value X The communication object is used to reset the count value of differential counter When the object receives telegram value 1 the current count value will become count initial value limit value 5 CH X DCounter DCounter Stop 1bit C W T 1 002 DPT_Bool Stop X When the differential counter overflow the object sends telegram value 0 which report count stopping set in the parameter Meanwhile if the object receives telegram value 0 the differential counter can also stop counting If the object receives telegram value 1 it will continue counting 6 CH X MCounter MCounter Limit lbit C T 1 002 DPT_Bool Limit exceeded exceeded X When the main count value exceeded the limit value the object will send telegram value 1 which report counting overflow CH X Request Request Counter lbit C W 1 002 DPT_Bool 7 Counter value value A When the object receives telegram value 1 the objects MCounter Counter value X and DCounter Counter value X will send their current value on the bus Table 9 Communication object table Counter