Home
        User Manual
         Contents
1.                                                       2 L    oo 6 0 0 06 oa ga o  9 06 6 9 9 oe 99 o                Figure 3 15 Parallel board    2  Place the ready switch on the front panel of the module to the an position  i e   in  unready state     3  Insert one power module in the installation position and push it into the cabinet    4  Secure the module to the cabinet through the fixing holes on both sides of the front  panel of the module     5  Place the ready switch to the db position  Le  in ready state      Remove a Power Module    Before removing any Power Module  make sure the remaining Power Modules can  support the critical loads        1  Turn the ready switch to the av position    2  The Power Module LED indicator is off to indicate the Power Module discharged and  shut down completely    3  Use a screwdriver to remove the four screws from fixing holes    4  Two people pull out together and remove the Power Module from its slot     3 5 4 STS Module  For detail n please refer to chapter 5     Seidel  KOUP ME   Ea ml ICT    Banana  HAB LUW    000  EEN  REES  SC  WOO  nse  CO  SUL    ABG  OW  FIN  miu  CIL  MYO  AL  NES  a   Ar       Figure 7 16  STS module    16    3 5 5 Remove the STS Module  Z  Warning      Only qualified service personnel can perform the following procedures      The STS Module has been pre installed in the factory  Only remove the STS Module  when maintenance or replacement is necessary      When the UPS is in Bypass Mode and its critical l
2.     SYSTEM ON   Standby Mode   INPUT G  e MENU       CONTROL Bypass O    MEASUREMENT    setup INVERTER         INFORMATION    EVENTS    Ji    JL ENTER Home      b      OOO         BATTERY OH       Figure 4 5 Menu screen    4 2 4 Control Screen  Use UP and DOWN buttons to choose CONTROL option  and press ENTER button to enter into the    submenu  as shown in Figure 4 6 and 4 7    000    E  se  mg                Figure 4 6 Control menu                     Yes or No    23    INPUT G    BYPASS    Bypass       INVERTER    INVERTER       BATTERY O BATTERY O    ALARM O    o       Figure 4 7 Control screen    Use LEFT and RIGHT buttons to choose YES or NO  Choose YES and press ENTER button to confirm  command or choose NO to cancel command  as shown in Figure 4 8     SYSTEM ON  Standby Mode       e System Turn On    Do you want to turn on  BYPASS O    INVERTER       BATTERY OH    ALARM     30     09309 2     t JL ENTER Home  I        Figure 4 3 Yes or No screen    4 2 5 Measurement Screen  Use UP and DOWN buttons to choose MEASUREMENT option  Choose module ID number to    measure Input  Output  Bypass  Load  and Battery of every module  as shown in Figure 4 9  4 10  and Table 4 4     Figure 4 9 Measurement menu    24       e MEASUREMENT    j BYPASS         Output  INVERTER         Bypass    road BATTERY O      Battery    ALARM O  LA  JE    t JL ENTER How      b    00000    e 5       Figure 4 10 Measurement screen    Table 4 4    Input phase voltage  L1  L2  L3   Units 0 1V    Frequen
3.    26    Table 4 5 All setting items in setup Menu    Mode Mode Mode Mode  mH  IB     L   EN  La    UPS operation       Setting item    Turn On  Change Turn On  Bypass Voltage   Bypass    Auto Restart  Cold Start    Battery Mode  System snow  Uem Restore    Redundancy    Nominal Battery  Voltage  Battery Capacity    in Ah  Maximum     lt    lt    lt    lt    lt       lt     Y    m    Y    Y      lt      lt              lt       lt     Battery  Test Mode       Fault  Mode    Converter  Mode       ECO  Mode     Charging Current                              Battery  Low Shutdown  Setting  Periodic Battery  MERC epee  Battery Test  mM BE IP trt    Stop by Time PY   Y      Stop by Battery  GEESS   Stop by Patchy  am TT                  Battery   Battery Age Alert   Alert   Y      am ne    Y means that this setting item can be set in this operation mode        4 2 6 1 Setup General Screen   Use UP and DOWN buttons to choose between different sub menus  and press ENTER button to  enter into the GENERAL setting screen  as shown in Figure 4 14  General setting can be set in any  operating mode and Setup General setting list is shown in table 4 6        Figure 4 14 Setup General screen    Use LEFT and RIGHT buttons to choose YES or NO  Choose YES and press ENTER button to    28    confirm the setting change or choose NO to cancel the setting  as shown in Figure 4 15     SYSTEM ON  Standby Mode         Language  ect Language  English Bypass     INVERTER        x  BATTERY Q    ALARM Q  E
4.    For standard model in 30U 120KVA cabinet    me sa   mm     fuum tataran  force  Ib in     3 6 2 DC input maximum current and power cable configuration           For standard model in 30U 80KVA cabinet    Power cable  mm      in     For standard model in 30U 120KVA cabinet       Di ni cas   50   95   n0   203   253   mm     force  Ibin        2    2    2    2    nm  force  Ib in        19    4  Control Panel and Display Description    4 1 Introduction  This control panel and display description is located on the front door of the UPS  It is the USER    control and monitoring of all measured parameters  UPS and battery status and alarms  The control  panel and display description is divided into four functional areas   1  LCD display   2  LED  indications   3  Control keys   4  Audio Alarm  as shown in Figure 4 1      1  BYPASS     INVERTER     2     BATTERY       t ENTER HOME       Figure 4 1 Control panel parts     1  LCD display  Graphic display and all measured parameters    2  LED indications  Refer to table 4 1    3  Control keys  Refer to table 4 2     20    Table 4 1  LED indications    of    on  INVERTER   Green Dn    Inverters not operating   Load on Battery   Flashin Low batter  BATTERY   Yellow noo  Off Battery converter is normal and battery  is charging   UPS fault     Flashing   UPS alarm        Table 4 2  Function key table    Control Key Description    Return to previous screen or cursor displacement  When  Esc screen is in Main screen  it will enter setting
5.  C Lower limit   10   20   30 default   20     delay time to accept steady bypass voltage  10s     Frequency Range Hz rt 1Hz      2Hz      4Hz  default  4Hz     1  Factory setting is 400V  380V or 415V is selectable by commissioning engineer        53    
6.  ID  04  INVERTER     2  Fault  Inverter Voltage High  Alarm On Time  2013 10 21 01 02 03 BATTERY O  Module ID  04  Datal  2500 Data2  2500    SAEN    ENTER HOME       Figure 4 30 History Events screen    4 2 8 3 Reset All Events   It   s required to enter 4 digit password to enter Reset All Events screen as shown in Figure 4 31   Then  use LEFT and RIGHT buttons to choose YES or NO  Choose YES and press ENTER button  to reset all events or choose NO to cancel this action as shown in Figure 4 32     38    SYSTEM ON  Standby Mode       e Enter Password    Enter Password  0 0 0 0 BYPASS OH  INVERTER     BATTERY       ALARM       ENTER HOME  b    SYSTEM ON  e          Reset All Events    BYPASS     INVERTER     BATTERY       ALARM O    ENTER HOME W        Figure 4 32 Reset All Events screen    4 3 Alarm List  In Table 4 11  it provides the complete list of UPS alarm messages     Table 4 11    Representation in display LCD Explanation  Fault  Bus Over Voltage DC bus voltage is too high  Fault  Bus Under Voltage DC bus voltage is too low    Fault  Bus Voltage Unbalance DC bus voltage is not balanced  Fault  Bus Short DC bus is short    l The rectifiers could not start due to low  Fault  Bus Soft Start Time Out  n    DC bus voltage within specified duration       39    Fault  Inverter Soft Start Time Out ae x    voltage within specified duration    R phase inverter Output Negative Power  Fault  Inverter R Negative Power  over range  l S phase inverter Output Negative Power  Fault  
7.  Signal  12C communication SDA Signal    Power GND       5 6 Bypass back feed Control Port    This function is reserved    5V        Eh   12V         Figure 5 7 Bypass back feed Control Port    Table 5 6 Description of Bypass back feed Control Port       5 7 Battery breaker Control Port  This function is reserved     45     5V     12V       ees        eg N  cO cO  x X    CNTL    Figure 5 8 Battery breaker Control Port    Table 5 7 Description of Battery breaker Control Port       5 8 Other Communication Interface    The RS232 port and USB Port can use in UPS commissioning and service or monitor the Ups  information by Monitoring Software      This UPS has facility of internally fitted SNMP Card options     46    6 Service    This chapter introduces the UPS service  including the service procedures of the power module   STS  amp  control module and the replacement of air filter     6 1 Replacement Procedures Of Power Module  STS  amp  Control Module  6 1 1 Notes    1  Only the customer service engineers shall service the power modules and bypass module    2  Remove the power modules and bypass module from top to bottom  so as to prevent cabinet  toppling due to high centre of gravity    3  To ensure safety  before servicing the power modules and bypass module  be sure to use a  multimeter to verify that the DC bus capacitor voltage is lower than 60Vdc  and that the  voltages between the earth and the components you are going to work on are under  dangerous voltage values  that
8.  is  lower than 60Vdc or 42 4Vac peak value    4  The static transfer switch module is NOT hot pluggable  It should be replaced only  when the UPS is in maintenance bypass mode or completely powered off    5  The power modules and bypass module should be serviced five minutes and installed in the  cabinet again 10 minutes after they are removed     6 1 2 Power Module Replacement Procedures  Confirm UPS is in normal mode and bypass function source is available     1  Enter to  menu   gt  control  gt  Turn To Bypass  gt  YES on the operator control and display  panel for manually turn off the inverters  Then  the UPS transfers to bypass mode     2  Turn ready switch to d WM position on replaceable power module     3  Two minutes later  remove the fixing screws on both sides of the front panel of the module  and pull the module out from the cabinet     Note  The module will be blocked by a metal safe locker on the left side of the module when the  module is pulled out halfway from the cabinet  At this point  you must press the metal safe  locker before you continue to pulling the module out    4  After servicing the module  confirm that the DIP switch of the module is set correctly and the         ready switch is in unready state d W  5  Push the module into the cabinet and tighten the screws on both sides  If it s more than one  power module to re install  please wait 10 second duration before installing another module     6  Wait for two seconds before turning ready switch of 
9.  maximum capacity indicated         7 6 Electrical Characteristics  Inverter Output     Table 7 6 Inverter output  to critical load     Rated power  kVA  20   120    Rated AC voltage  Vac   380 400 415  three phase four wire  with neutral  reference to the bypass neutral     50 60 Auto Selectable    Overload   105  110  for 60min  110  125  for 10min  126  150  for 1min   gt 150  for 200ms    Neutral current capability 170   Steady state voltage stability  1  balanced load    2  100  unbalanced load   Total harmonic voltage  lt 1  linear load    lt 4  non linear 10303     Synchronization window         1Hz      2Hz      4Hz  default  4Hz   Note   1  Factory setting is 400V  380 or 415V is selectable by commissioning engineer        52    7 7 Electrical Characteristics  Bypass Mains Input     Table 7 7 Bypass mains input    ac 380 400 415  Three phase four wire  sharing neutral with  the rectifier input and providing neutral reference to the  output     Rated current A 30U for 80KW     158  380V   151  400V   145  415V  30U for 120KW     236  380V   226  400V   217  415V  Overload Din  105  110  for 60min  110  125  for 10min  126  150  for 1min   gt 150  for 200ms    Upstream protection  N A Circuit breaker  rated up to 100  of nominal output  bypass line current    Current rating of neutral  1 7 x In   cable    Frequency Hz 50 60 Auto Selectable    ransfer time  between ms  bypass and inverter  Synchronous transfer   lt 20ms     Va Upper limit   10   15 or  20  default   15 
10.  menu by  pressing ESC key     Key for menu page navigation  or digit modification    Key for menu page navigation  or digit modification    Confirmation of commands  or cursor displacement   Home Return to Main screen     Power On Off   Turn on UPS or Turn off UPS   hold 2 Sec         4  Audible Alarm  Table 4 3  Audio Type  Buzzer sounds two seconds   Battery mode   Buzzer sounds every 2 seconds     Low battery   Buzzer sounds every half seconds     UPS alarm Buzzer sounds every 1 second     UPS fault Buzzer continuously sounding        21    4 2 Screen Description  4 2 1 Start Screen  Upon UPS start  the UPS executes self test  The initial screen displays and remains approximately    5 seconds as shown in Figure 4 2        BYPASS       INVERTER     BATTERY       ALARM       ENTER HOME  D       Figure 4 2 Initial screen    4 2 2 Main Screen  After initialization  the main screen will display as Figure 4 3  Main screen is divided into five parts      1  UPS Mode  Current Operation Mode     2  UPS Flow Chart  Current flow chart and measurement data    3  Menu  Press ESC button to enter Menu screen     4  UPS model name with power rating     5  Date and Time       svsmmon SS SYSTEM ON        Standby Mode 20KVA  INPUT         BYPASS       INVERTER       BATTERY Q    ALARM          Figure 4 3 Main screen    22    4 2 3 Menu Screen  Use UP and DOWN buttons to choose between different menus  and Press ENTER to enter into    the sub screen  as shown in Figure 4 4 and 4 5           
11.  room temperature build up  Air  filters are necessary if the UPS is operated in a dusty environment     Note  The UPS is suitable for mounting on concrete or other non combustible surface only     e The UPS is air cooled with the aid of internal fans  Cold air enters the UPS through the  ventilation grilles at the front of the cabinet and hot air is released through the grilles at the  back  Do not cover the ventilation openings    e Do not allow unauthorized personnel to enter the installation area  Assign specific personnel to  keep the UPS key     11    For safety concerns  we suggest that you shall   1  Surroundings of the installation area with CO2 or dry powder fire extinguishers   2  Install the UPS in an area where the walls  floors and ceilings were constructed by fireproof  materials   It is recommended that you parallel the external battery cabinets to the UPS  The following  clearances are suggested   1  Keep a clearance of 100cm from the top of the UPS for maintenance  wiring and ventilation   2  Keep a clearance of 100cm from the back of the UPS and the external battery cabinets for  ventilation   3  Keep a clearance of a 150cm from the front of the UPS and the external battery cabinets for  maintenance and ventilation     3 4 3 Transportation   N Warning    The UPS is fixed on the pallet with four balance supports  When removing them     pay attention to the movement of the casters to avoid accidents    The cabinet can be pushed forward or backward only  Pushi
12.  to connecting or disconnecting terminal   Determine if the battery is inadvertently grounded  If it is  remove the source of the  ground  Contact with any part of a grounded battery can result in electrical shock  The  likelihood of such shock is reduced if such grounds are removed during installation and  maintenance    When replacing batteries  use the same number of sealed  lead acid batteries    Do not dispose of battery in a fire  The battery may explode    Do not open or mutilate the battery  Release electrolyte is harmful to the skin and eyes  and  may be toxic     Oy EE    R 5 Recycling the used battery    Do not dispose of the battery in a fire  Battery may explode  Proper disposal of battery is  required  Refer to your local codes for disposal requirements    Do not open or mutilate the battery  Released electrolyte is harmful to the skin and eyes  It  may be toxic    Do not discard the UPS or the UPS batteries in the trash  This product contains sealed  lead   acid batteries and must be disposed of properly  For more information  contact your local  recycling reuse or hazardous waste center    Do not discard waste electrical or electronic equipment  WEEE  in the trash  For proper  disposal  contact your local recycling reuse or hazardous waste center     2 Operation  amp  structure            A               ES    e    Figure 2 1  Wiring diagram for dual inputs    Maintenance             Figure 2 2  Wiring diagram for single input    3  Installation    3 1 Mechani
13. Installation and Wiring   3 4 1 Before Installation   Due to different installation environments  please read this user manual thoroughly before  installation and wiring  Only authorized engineers or service personnel can perform installation  and maintenance  If you want to install the UPS by yourself  installation must be under the  supervision of authorized engineers or service personnel    If you use a forklift or other equipment to move the UPS  please make sure its load bearing is  sufficient     Down Right    Key for menu page navigation or digit modification       3 4 2 Installation Environment     The UPS is designed for indoor use only  Do not install or place it in an outdoor area    e Make sure that transportation routes  e g  corridor  door gate  elevator  etc  and installation  area can accommodate and bear the weight of the UPS  the external battery cabinet and  handling equipment      Ensure that the installation area is big enough for maintenance and ventilation      Keep the installation area s temperature around 30  C and humidity within 90   The highest  operating altitude is 2000 meters above sea level    e The UPS is intended for indoor installation and should be located in an environment with clean  air and with adequate ventilation to keep the ambient temperature within the specified  operating range  The UPS is air cooled with the aid of internal fans  Cold air enters the UPS  through      If necessary  install a system of room extractor fans to avoid
14. Inverter S Negative Power  over range  l T phase inverter Output Negative Power  Fault  Inverter T Negative Power  over range    Make sure adequate space is allowed for  Fault  Over Temperature l   l  air vents and the fan is working  Fault  Relay Fault    The load devices are demanding more    Warning  Over Load Fail power than the UPS can supply  Line       mode will transfer to Bypass mode     Warning  Communicate CAN Fail CAN communication error    In Line mode  the load devices are  Warning  Over Load demanding more power than the UPS       can supply     40    Communicate Trigger signal fault  Battery Life expiration  Warning  Battery Voltage Low    41    5  Interface and Communication    As shown in figure 5 1  the Static Transfer Switch  STS  Module includes dry contact Port   X1 X8   and communication port  RS232 Port  USB port  SNMP Card Port  on the front panel     SNMP Card Port           D  L  D  D  2  L    Anji janam rara Ejaan jai Ja   3872 L JL TIDIO CHORAL CH B ES  TAN OM DND   Y T  aL L HE aa       E  en    255   i fol   Be ee ios aon es L 2  Rs232 Port USB Port   Figure 5 1 Dry contact ports and communication ports    Dry Contact    No   BCB Port  Battery Circuit Breaker       reserved function  Maintenance Bypass Switch State Port       Battery Cabinet Temperature Detection Port      reserved function   Bypass back feed Control Port     reserved  function   Battery breaker Control Port     reserved  function       Internal Output Switch State Port     rese
15. S  masts    Leveling Foot       Figure 3 8  Leveling foot and caster    12    3 4 4 Unpacking    After shipping the product to the user first check the packaging to determine intact  and then    open the package  check the equipment in good condition  If damaged  please immediately  notify the carrier     3 4 4 1 System Packaging    1  Use a forklift to move the product to installed area  Refer to Figure 3 9   2  Please follow the order in Figure 3 10 to remove carton and foams     1       Figure 3 9 Figure 3 10    3  Put a ramp in the front of the cabinet and insert small wood into groove  Then  remove  two side panels  Refer to Figure 3 11        Bottom  side panel  10x12x700mm Bottom  small wood side panel    Ramp    Figure 3 11    13    4  Remove 4 fixing cabinet plates and loosen leveling feet by rotating in counterclockwise   Then  move the cabinet from the pallet   5  To fix the cabinet in position  simply rotate leveling feet in clockwise                       Screws         z Screw nut    Leveling foot           SS    Leveling foot    Figure 3 12 Figure 3 13    3 4 5 Positioning    Leveling feet are provided at the bottom of the UPS cabinet to prevent the UPS from moving once    it has been placed to its final position  For optimal design life  the installed place must be   e easy connection   enough space to easily work on the UPS   sufficient air exchange to dispel heat produced by UPS   protection against atmospheric agents   protection against excessive humidity 
16. TES K3    ENTER HOME    000000    Esc       Figure 4 15 SETUP YES or NO screen    Table 4 6    Setting Item Sub Item Explanation  Model Name Naa Set UPS Name xxxxxxxxxx     Provides 3 optional LCD languages  Language  English  Traditional Chinese and Simplified  Chinese      TIME Set current date and time mm   dd  MesTme Time ER      Yyyy      ane M   min   sec     System Installed Date   Set system installed date  yyyy   mm   dd     System Last Maintain   Set system latest maintenance date  yyyy    Date mm   dd     Battery Installed Date   Set battery installed date  yyyy   mm   dd     Battery Last Maintain   Set battery latest maintenance date  yyyy    Date mm   dd     Change Password   Set New Password     Set COM PortO Baud Rate 2400  4800   9600    Baud Rate  Set COM Port1 Baud Rate 2400  4800   9600    Audible Alarm     J Set Audible Alarm  Disable  or  Enable     Factory Reset           M      Restore to factory default setting  EEPROM Reset        SetEEPROM default    Set EPO  Normal Close Active  or  Normal  EPO Function l  Open Active       Save Setting   Save EEPROM    Turn On Password Se Set Turn On Password    Disable    or    29       Nan Tene       Change Turn On  9 Set New Turn On Password   Password    4 2 6 2 Setup System Screen  Use UP and DOWN buttons to browse different menus and press ENTER button to enter into the  SYSTEM setting screen  as shown in Figure 4 16  System setting can be set only when UPS is  operated in certain mode  Please check setting i
17. and high heat sources   protection against dust   compliance with the current fire prevention requirements    For VRLA  Valve Regulated Lead Acid  batteries the operating environment    temperature is kept between 20  C and 25  C  VRLA batteries are at maximum    efficiency in this temperature range    3 5 Modules    The hot swappable Power Modules allow quick maintenance and expansion  A latch located on the  front of each module fixes and locks the module in its assigned slot  Each Power Module has an    LED indicator to show its operation status     3 5 1 Power Module       Figure 3 14  Power module    14    The Power Module   s LED indicator shows its operation status  Please refer to the following table       No    LED indicator  FAULT Steady red LED indicates that the system is abnormal     2 FAULT Flashing red LED indicates that the system is in  parallel abnormal     host UPS   slave UPS     3 5 2 Install a Power Module  Follow below procedures to install the power module   1  Usethe DIP switch on the front panel of each Power module to set the module address   The setting range is from 1 to 3  The module address should be exclusive  The setting  method is shown in Table 3 1     Module address MODULE DIP SWITCH Parallel board    OC g SW1 and SW2 DIP  3 POWER   Parallel board is  located at the back of  A Er CH UPS cabinet  The  4 POWER mm appearance is shown  in figure 3 15     Table 3 1 DIP switch setting method                   15    3 5 3          0 Tj    t  0    
18. cal Characteristics  Intermediate DC Circuit            oo  oma 52   7 6 Electrical Characteristics  Inverter Output     NNN NNN 52    7 7 Electrical Characteristics  Bypass Mains Input     53    1  Safety    1 1 Important Safety Instructions   This UPS contains LETHAL VOLTAGES  All repairs and service must be performed by  AUTHORIZED SERVICE PERSONNEL ONLY  There are NO USER SERVICEABLE PARTS inside the  UPS     WARNING      The UPS designed for commercial and industrial purpose  it is forbidden to apply for any life  sustainment and support      The UPS system contains its own energy source  The output terminals may carry live  voltage even when UPS is disconnected from an AC source      To reduce the risk of fire or electrical shock  UPS installation has to be in a temperature and  humidity controlled  indoor environment  Ambient temperature must not exceed 40  C  The  system is not intended for outdoor use      Ensure all power is disconnected before performing installation or service      Service and maintenance should be performed by qualified service personnel only     Before working on this circuit    Isolate Uninterruptible Power System  UPS     Then check for Hazardous Voltage between all terminals including  the protective earth     AN Risk of Voltage Backfeed    The isolation device must be able to carry the UPS input current        1 2 EMC  WARNING   This is a product for commercial and industrial application in the second environment      installation restrictio
19. cy  Hz  Input Frequency  L1  L2  L3   Units 0 1Hz    out  Bypass phase voltage  L1  L2  L3   Units 0 1V    Bypass Bypass Frequency  L1  L2  L3   Units 0 1Hz   Bypass Power Factor  L1  L2  L3     1000  The percentage of the UPS rating load  Units 1      Positive Voltage   V  S Battery Positive Voltage  Units 0 1V   Negative Voltage  M S Battery Negative Voltage  Units 0 1V   Positive Current  Battery Positive Current  Units 0 1A   Battery A   Negative Current    S Battery Negative Current  Units O 1A     Remain Time  Sec    Battery run time remaining  Units 1sec       The percentage of the capacity of the battery   OS Units 1     Test Result Battery test result  25       EE Charging Status Battery charging status    4 2 6 Setup Screen  Use UP and DOWN buttons to choose SETUP options  It s required to enter password to access    General  SYSTEM and BATTERY sub menus  as shown in Figure 4 11  4 12 and 4 13     PRE ALARM    Figure 4 11 Setup menu    Its required to enter 4 digit password to enter SETUP menu  If incorrect password is entered  the  LCD screen will ask for retry     SYSTEM ON  Standby Mode       e Enter Password    Enter Password  0 0 0 0 BYPASS OH  INVERTER     BATTERY OH    ALARM O    t  lt  gt  ees How  I     O O O O O O    Esc 4a  gt     SYSTEM ON  Standby Mode       INPUT    SETUP           GENERAL Bypass       system     sartery INVERTER       PRE ALARM BATTERY O    ALARM       t  lt  gt  eme Home      D    000000    Esc de  gt        Figure 4 13 Setup screen 
20. ease refer to the  following sections     3 2 1 Input and Output Breakers   Open front and back door  The Input Breaker  Bypass Breaker and Output Breaker are located on  the front of the UPS  The input  output wiring terminal block are at the back of the UPS  See Figure  3 4        D g lt  TEL PS d        B  eg    KM     I         Main input Bypass Output  Breaker Breaker Breaker          Figure 3 4  Front View Output  Bypass  and Main Input Breakers    3 2 2 Wiring Terminal Block  Open the UPS s back doors and you will see the wiring terminal block  For connection instructions   please refer to Figure 3 5     Neutral terminals   Neutral terminals   Neutral terminals   terminal     cabinet Positive      Negative        and Neutral  N  terminals        H EE i   EKLE    19501     uie Ie           XXE    C                                M P                   n l         LLELE  AM IL ELLELAX    Bao 0          0   SL         ds iiis    C lT    Be da BE  dod R d dRea ibi  ld 0 R AKR E  n d a    Figure 3 5  Rear View  amp  Wiring Terminal Block    3 2 3 Modules  The STS  amp  Control module and Power Module allow quick maintenance  replacement and  expansion  The module latches secure the modules in place     e STS  amp  Control Module  It includes control  power  communication circuits  an internal Static  Transfer Switch and a fuse     e Power Module  Each power module capacity is 20kVA  20kW  It includes a power factor  correction rectifier  a battery charger  an inverter and co
21. ed warning text in the Main Screen as shown in Figure 4     26  Besides  you also can enter the EVENTS Menu to check the latest event lists and history  events as shown in Figure 4 27 and 4 28     36       Bypass       INVERTER OH    BATTERY O           SYSTEM ON  Standby Mode  INPUT    e EVENTS    j Current Events BYPASS OH    History Events           Reset All Events INVERTER O    BATTERY          saj O    ENTER Home W     O O O         Figure 4 28 Events screen    4 2 8 1 Current Events   When event occurs  it displays Module ID and alarm code in Current Events screen  It can save  up to 50 events in current events  Only 4 events can list in one page  Therefore  if it exceeds more  than four  you have to press UP or DOWN button to read other event as shown in Figure 4 29     37    SYSTEM ON  Standby Mode       INPUT G    e Current Events  1  Warning  Charge Fail  Module ID  or BYPASS     2  Warning  Epo Active  Module ID  00 INVERTER     3  Fault  Battery Fault  Module ID  02 BATTERY O  4  Warning  Fan Lock  Module ID  01           L     Aen    ENTER HOME       Figure 4 29 Current Events screen    4 2 8 2 History Events   It saved detailed information in history events  When warning occurs  it will display alarm code   alarm time and Module ID  When fault event occurs  it will display alarm code  alarm time  Module  ID and data 1 2  Refer to Figure 4 30 for display screen       History Events    1  Warning  Charge Fail BYPASS O  Alarm On Time  2013 10 21 01 02 03    Module
22. ign       Ww    0 A  C x    T      E  O eo  ET Kg      d  n  Q D  c Si  O v  y 2  co  Oo c  Q    2  gt     T  C c  O    D    C    7      D  E S    4   D    a   CC            Table Of Contents    Ee 1  1 1 Important Safety InstructiOnS            on 1  IA En na 1  1 3 Installatiori infor 1 le  ea 1  L4 Manten ele EE 2  Lo Remyeling Me 46609 Be age Naa 2   ZOPA He ek e deo Eos pap MD MEME EI UM D MEME 3   3 Hu Ce UE re oN BEE 4  31   Mechanism and  EXteriOnr cussssciisoomaveduneet n Pasta vo bones Urs Eege 4   3 1 1 Mechanical Data    5  CX HORMEL TA T ET 5  3 2 Internal OT ie ONS eae 7  3 2 1  Input and Output TE 7  3 242  WM  ring Termilial BlOGK km ama DUE ERR 8  22an POGUICS PN 9  3 3 Control Panel GUIDEerTace EG 10  Sa  9 25 STs Telre lt 1 Ten orte rovc da vat eb vHa d hse tl dud abah 10  ee  ECD DIK aa a 10  Dio  IEHDCHOD Key 11  3  Installadon and  WN  lt  kiai 11  3 4 1 Before TASCA AE On naa aa Fama qi dais aman Bian anandi 11  3 4 2  Installation Environment aa a ok Dass Naa naa P ana 11  E neien E N 12  See  UNPACKING EE 13  EE Ge eleis DE Itin eI EM I M IM DIM DIA A aes 14  3 9 MOGUIES TTE TO 14  SEN Power MOGU t UU TM 14  3 5 2  Install a e Oe TE EE 15  3 5 3 Remove a Power Module    sss sss sss sese eee 16  35A  STS Ge el   orem e ana 16  355 Remove KE FS Mode ia aa ai in Da ia 17  9920  Battery ln Ee UE eTel aa anal 18  3 6 Beie ele aa an anna NI UI I MNT 18  3 6 1 AC input and output maximum current and power cable configuration             19  3 6 2 DC input ma
23. n  mode  See Setup Pre Alarm setting list in table 4 9        SYSTEM ON  Standby Mode    PRE ALARM  Bypass     INVERTER OH  BATTERY       ALARM       ENTER HOME  b    060800       Figure 4 19 Setup Pre Alarm screen    34    Table 4 9    Setting Item Sub Item Explanation    Set line voltage range  upper limit   5    Line Voltage Range  10    15    20   and lower limit     5    10    15    20        Ic  line frequency range  upper limit  Line Frequency eranc Renge    e  2Hz   3Hz   4Hz  and lower    limit   1Hz   2Hz   3Hz   4Hz     Set UPS Overload percentage  Load  40 100    Load Unbalance Set UPS output load unbalance  percentage  20 100      4 2 7 Information Screen  In this Screen you can check the UPS configuration of the unit  and INFORMATION divided into    Identification  System and Battery  as shown in Figure 4 21  4 22  4 23  4 24 and 4 25            SYSTEM ON  Standby Mode         INFORMATION    Bypass     INVERTER     BATTERY       ALARM             ENTER HOME    06090060       Figure 4 23 Information Identification screen    35          Bypass O  INVERTER      to Re 5 INVERTER       BATTERY O   Cold Start  BATTERY O         English  ALARM      EN ALARM        lt  gt  enter wow      D       Bypass O  INVERTER O  BATTERY       ALARM       ENTER Home    D             Bypass    Bypass       INVERTER    INVERTER       BATTERY    BATTERY       ALARM O ALARM O    Q        Figure 4 25 Information Battery screen    4 2 8 Events Screen  When event occurs  you will see flash
24. ng it sideward is not  allowed  When pushing the cabinet  take care   not to overturn it as the gravity center is high          If you need to move the UPS over a long distance  please use appropriate equipment like a  forklift  Do not use the UPS casters to move the over a long distance      After the UPS has been removed from the pallet to ground  we suggest that at least three  people move the UPS to the installation area  One person use hands to hold a lateral side of  the UPS  one person hold the other lateral side of the UPS with hands  and one person use  hands to push the UPS either from the front side or from the backside to move the unit to the  installation area and avoid tipping the UPS      The casters are designed to move on level ground  Do not move the UPS on an uneven surface   This might cause damage to the casters or tip the UPS which could damage the unit      Ensure that the UPS weight is within the designated surface weight loading of any handling   equipment      At the bottom of the UPS  there are four casters to help you to move the UPS to a designated  area  Before you move the UPS  please turn the four leveling feet counterclockwise to raise  them off the ground  This protects the leveling feet from damage when moving the UPS   Please use sufficient manpower at least six people  and equipment  e g  forklift  to carefully  move the UPS from its pallet to ground  Please pay attention to the movement of the casters  to avoid accidents           1 Wi  D
25. ns or additional measures may be needed to prevent disturbances     1 3 Installation information    WARNING    e Installation must be performed by qualified personnel only      The cabinets must be installed on a level floor suitable for computer or electronic  equipment      The UPS cabinet is heavy  If unloading instructions are not closely followed  cabinet may  cause serious injury    e Do not tilt the cabinets more than 10       Ground conductor is properly installed    e Installation and Wiring must be performed in accordance with the local electrical laws and  regulations    e The disconnection device should break line and neutral conductors  four poles for three  phases     1 4 Maintenance    UPS is designed to supply power even when disconnected from the utility power  After  disconnect the utility and DC power  authorized service personnel should attempt internal  access to the UPS    Only qualified service personnel should perform the battery installation    Do not disconnect the batteries while the UPS is in Battery mode    Disconnect the charging source prior to connecting or disconnecting terminals    Batteries can present a risk of electrical shock or burn from high short circuit current    The following PRECAUTIONS should be observed   Remove watches  rings  or other metal objects    Use tools with insulated handles    Wear rubber gloves and boots    Do not lay tools or metal parts on top of batteries or battery cabinets    Disconnect the charging source prior
26. ntrol circuits     Switch unit    STs  amp control module    Power Module    zs    Ca    KN    da    l i          e   d              ul       W  E    E           Figure 3 6  Front View with Modules    3 3 Control Panel  amp  interface   The front access Graphic Display  amp  Control interface brings all measured parameter  UPS  amp   Battery current states and Alarms  Through the interface  users can easily monitor status and  configure settings  For detailed information  please refer to the charter 4     LCD Display LED Indicators    INVERTER CH    BATTERY CH       Function keys    Figure 3 7  Control Panel  3 3 1 LED indications    On Input source is normal   INPUT Green   Flashing   Input source is abnormal     No input source  On    Load on Bypass     BYPASS Green iai Input source is abnormal    Off    Bypass not operating     LEES on inverters   INVERTER   Green         not operating       Load on Battery     BATTERY   Yellow E Low battery   Off    Battery converter is normal and battery is charging     omo us fault   ALARM     UPS alarm   Normal     3 3 2 LCD Display  Graphic display and all measured parameters        10    3 3 3 Function Keys    Esc Return to previous screen or cursor displacement  When screen is in  Main screen  it will enter setting menu by pressing ESC key    Up Left  Key for menu page navigation or digit modification     Enter Confirmation of commands  or cursor displacement  Home Return to Main screen    Power  Turn on UPS or Turn off UPS     3 4 
27. oads are connected  removing the    STS Module without turning off the Bypass Breaker could generate high voltage   which may melt its connectors      If the UPS is in Bypass Mode  cutting off the bypass AC source will terminate power  supply to the critical loads      The STS Module is heavy   gt 30 kg   At least two people are required for handling        Please follow the steps below to remove the STS Module    1  Turn OFF the Bypass Breaker    2  Use a Screwdriver to remove the four screws from the two sides of the STS Module   3  Two people together pull out and remove the STS Module     NOTE  Reverse the steps above to insert the STS module     17    3 5 6 Battery Installation  Please follow below chart to connect wires to external battery cabinet         di              External battery cabinet    External  Battery  Input Output  Breaker           External batteryscabinet    After battery is completely installed  be sure to set up nominal battery voltage  battery capacity  and maximum charging current in LCD setting  Otherwise  if battery setting is different from real  installation  the UPS will keep warning  Please refer to section 4 2 6 3 and Table 5 17 for the  details     3 6 Power Cable    Please follow the local wiring regulations  Follow environmental conditions and  refer to IEC60950 1        18    3 6 1 AC input and output maximum current and power cable configuration     For standard model in 30U 80KVA cabinet    Power cable  mm     66   16   40   53    in  
28. re for UPS       50    7 3 Mechanical Characteristics    Table 7 3 Mechanical characteristics    30U    Model       30U 80 300 120  Rated power  kVA    Unt       80       120    Dimensions  W x D x H 600 x 1100 x 1475    Protection degree  IEC  60529  IP20  front door and back door  is open or closed     7 4 Electrical Characteristics  Input Rectifier        Table 7 4 Rectifier AC input  mains     Rated power  kVA  20KVA 120KVA    Rated AC input voltage Vac 380 400 415  3 phase and  sharing neutral with the bypass  input   derated below 70      Power factor KW kVA  0 99  0 98   full load  half  load     Harmonic current distortion   THDI96 FL       51    7 5 Electrical Characteristics  Intermediate DC Circuit     Table 7 5 Battery  Intermediate DC circuit    Model    Rated power  kVA     30U 120  120    30U 80    Number of lead acid 216  6cells x 36 12V battery block   cells 240  6cells x 40 12V battery block   192  6cells x 32 12V battery block   Constant current and constant voltage charge mode   compensation    Ripple voltage   V float     lt 1  Ripple current Yo C10    lt 5    Boost voltage 2 35V cell  Constant current and constant voltage charge mode    EOD voltage V cell 1 67V cell    Battery charge Limit current and constant voltage charge mode  V cell Floating Voltage 2 3V cell  Boost charging 2 35V cell  noui Earn 6   per power module  adjustable   power max current    Note   1  At low input voltage the UPS recharge capability increases with load decrease  up to  the
29. rrent    INVERTER    INVERTER         BATTERY LOW SHUTDOWN SETTING BATTERY O BATTERY O      BATTERY TEST    ALARM     LA  E    t  lt  gt  ees Home      D    000000    Esc E Ee    ALARM       t   gt  ees How  I     000000    Esc E C         Figure 4 18 Setup Battery Screen    33    Table 4 8    Setting Item Sub Item Explanation  Nominal Battery EN Set battery nominal voltage 16x12V   Voltage 18x12V  20x12V   Battery Capacity in Ah       Set battery capacity   0 999   Maximum Charging Set battery maximum charging current  Current  1 128A    Battery Low Set battery low voltage   Voltage  10 5 11 5V x battery Number   BATTERY Battery Low  LOW SHUTDOWN Set battery low capacity  20 50    SETTING   Battery Shutdown Sg EH         for system   Voltage snutdown in battery mode    10 0 11V  x  battery Number     Periodic Battery Set periodic battery test  Disable   Test or  Enable   Battery Test  Set battery test interval  7 99 Days   Set testing time for battery test  BATTERY TEST Stop by Time  10 1000sec     Stop by Battery Set stop battery voltage in battery test   Voltage  11 12V  x  battery Number    Stop by Battery Set battery capacity to stop battery    Capacity testing   20 50     Battery Age Alert Set battery age for replacement   alai geen  Months   12 60Months     4 2 6 4 Pre Alarm Screen   Use UP and DOWN buttons to switch different sub menus  Press ENTER button to enter into the  Pre Alarm setting screen  as shown in Figure 4 19  Pre Alarm setting can be set in any operatio
30. rved  X5  function     reserved function    5 1 Remote EPO Input Port  The UPS has an Emergency Power off  EPO  Function that can be operated by a remote contact  provide by user  Users can set the logic  N C or N O  of this EPO Function through LCD panel     X1 is the remote EPO input port  The port is shown in Figure 5 2 and described in Table 5 1     T      12V    te    CN  e  X    e  x  Figure 5 2 Remote EPO input port    Table 5 1 Description of remote EPO port    EPO Logic Setting      X1 1  amp  X1 2 EPO activated when Opened X1 1  amp  X1 2  NO      X1 18 amp X1 2   EPO activated when Shorted X1 1  amp  X1 2    If EPO Logic setting is Normal Closed  N C   EPO is triggered when pins 1 and 2 of X1 are  opened  Otherwise  EPO Logic setting is Normal Opened  N O   EPO is triggered when pins 1 and  2 of X1 are opened        Note    1  EPO action shuts down the rectifiers  inverters and static transfer switch  But it does not  internally disconnect the input power supply    2  The default setting of the EPO function logic is Normal Opened  N O      5 2 BCB Port  This function is reserved     Ld Lei   12 D D 1120    a    ei OO m s  x X XX  Figure 5 3 BCB port    Table 5 2 Description of BCB port    BCB CONNECTED Pin1    BCB CONNECTED Pin 2  BCB STATUS Pin 3  BCB STATUS Pin 4       5 3 Maintenance Bypass Switch State Port  X4 is the maintenance bypass switch and External maintenance bypass switch state port  The  port is shown in Figure 5 4 and described in Table 5 3   This f
31. sing Battery Start Button  Refer to  cold start operation for the details     Battery Mode M Set system shutdown delay time in  Delay Time battery mode  0 9990sec     GREEN M Set system shutdown time  0 2 99min     SEN BEER ae Set system restore time  0 9999min   Redundancy a Set total power and redundancy    31       Cold Start Operation  Step 1  Press    Cold Start    button as shown in below chart     Cold Start Button       Step 2  After pressing Cold Start Button  UPS will enter Standby mode  Refer to below chart for  LCD display     INPUT    BYPASS     INVERTER          B i k  95      UN BATTERY O       Step 3  Before UPS enters shutdown mode  please press    Power On Off    button for 2 second  immediately as shown in below chart     INVERTER       BATTERY Q           ENTER   Home    b  50060      arora       32    Step 4  Then  UPS will enter Battery Mode as shown below chart  Cold start procedure is  complete        Bypass       INVERTER      BATTERY         4 2 6 3 Setup Battery Screen  Use UP and DOWN buttons to switch different sub menus  Press ENTER button to enter into the    BATTERY setting screen  as shown in Figure 4 18  Battery setting can be set only when UPS is  operated in standby mode  If it   s not in standby mode  the warning screen will appear as shown  in Figure 4 17  See Battery System setting list in table 4 8     SYSTEM ON  Standby Mode            BATTERY    BATTERY Age Alert BYPASS 0    Bypass         Battery Capacity in Ah    Maximum Charging Cu
32. sm and Exterior  In the front of the UPS  there are control interface  LCD Panel  and door lock  Inside the cabinet   there are an STS Module and 1 6 Power Module slots     All wiring terminal blocks are allocated in the back of system  The side panels are lockable  The  casters at the bottom of the UPS cabinet can be used to move over short distances  There are  four leveling feet to fix and stabilize the UPS cabinet on the ground     Side Panel    Control Panel    Door Lock    LevelingFeet    Casters       Figure 3 1  UPS Exterior    3 1 1 Mechanical Data    Dimensions    UPS cabinet Width Depth Height  20 120Kw 30U  1100mm 1475mm    TOP VIEW 30U FRONT VIEW    en          1475 mm                      Figure 3 2  Dimensions    3 1 2 Other Views  e Front View  Unlock and open the front door to see STS Module  Switch unit and Power Module     Rear View  Unlock and open the rear door to see input output terminals        E       ind  Ld    p          schte o  T  Uto offe dort    EES         EI a       xL                      Figure 3 3  Rear View Front View  1  Switch unit  2  Bypass module  3  Power module    Configurations   There are two models for Standard Series     Standard Series                   E a      Heig ht   Switch Unit  Lil   E e           Max  Power  Module       3 2 Internal Mechanisms   After opening the front door  you can see the Switch unit  Bypass module and Power module  After  opening the back door  you can see the input  output wiring terminal block  Pl
33. t         AY  p  4   gt  AN  L                    f           Ar          L  Air Filter       The air filter replacement procedures are as follows    1  Open the front door of the UPS to reveal the air filters on the back of the door   2  Remove a fixing bar on either side of the air filter    3  Remove the air filter  and insert a clean one     4  Replace the fixing bar     7 Specifications    The chapter provides the UPS specifications     7 1 Conformity And Standards    The UPS has been designed to conform to the European and international standards listed in  Table 7 1     Table 7 1 European and international standards    General and safety requirements for UPS  for UPS  requirements of UPS    Notes     ESD IEC EN 61000 4 2 Level 3  IEC EN 61000 4 3 Level 3  EFT IEC EN 61000 4 4 Level 3  IEC EN 61000 4 5 Level 3  IEC EN 61000 4 6 Level 3  Power Frequency Magnetic field IEC EN 61000 4 8 Level 3  Low Frequency Signals IEC EN 61000 2 2 Level 10V  Conduction IEC EN62040 2 Category C3  Radiation IEC EN62040 2 Category C3       7 2 Environmental Characteristics    Table 7 2 Environmental characteristics  Specifications  Noise within 1 m dB    Max75               o  m    Altitude   1000  derate power by 1  per 100m between  1000m and 2000m  Relative humidity 0   95  non condensing    Operating temperature     C     Output capacity will be derated when  temperature is over 30  C  It will be derated to  90  at 35  C and 80  at 40  C     Storage and transport oC  15   60  temperatu
34. tem availability table 4 5 for the details  If it s not  set up under specific mode  the warning screen will appear  Refer to figure 4 17 and Setup System  setting list is shown in table 4 7     Bypass O      Auto  Bypass     INVERTER    etary Shade D   Thee INVERTER     BATTERY O BESSE BATTERY O    ALARM      ALARM       D e O          900000    SYSTEM ON  Standby Mode    e SYSTEM    Redundancy BYPASS O  INVERTER O  BATTERY O    ALARM O    ENTER HOME    066666       Figure 4 16 Setup System screen    30       e Warning    Warning  BYPASS O    This mode cannot be SETUP  INVERTER O  BATTERY O    ALARM O    ENTER HOME  b       Figure 4 17 Warning screen    Table 4 7    Setting Item Sub Item Explanation    Set output voltage  220Vac  230Vac     Set bypass voltage range  upper limit   dii Voltage    410   41596   20   and lower limit     9 10    20    30      BYPASS SETTING   D  Bypass Frequency Set bypass Frequency range  upper limit  Ranae   1Hz   2Hz   4Hz  and lower limit     S 1Hz   2Hz   4Hz   Converter Mode M Set converter mode  Disable  or  Enable     ECO Mode IR Set ECO mode  Disable  or  Enable   Bypass Mode PEN Set bypass mode  Disable  or  Enable     Set auto restart  Disable  or  Enable    After  Enable  is set up  once UPS  Auto Restart shutdown occurs due to low battery and  then utility restores  the UPS will return  to line mode   Set cold start  Disable  or  Enable    After  Enable  is set  the UPS can be  Cold Start turned on without utility connection by  pres
35. the module to db position  it will be  added into the system automatically and begin to work few seconds later     7  Press manual control  gt  system turn on  gt YES on the operator control and display panel for  two seconds to manually turn on the inverter mode     6 1 3 STS  amp  Control Module Service Procedures  The static transfer switch module is NOT hot pluggable   Confirm the UPS is in normal mode and bypass function is available     47      Press menu  gt  control  gt  Turn To Bypass YES on the operator control and display panel for  manually turn off the inverters  and the UPS transfers to bypass mode       Turn on main switch and off maintenance bypass switch       Two minutes later  remove the fixing screws on both sides of the front panel of the module  and pull the module out from the cabinet       After servicing the module  push the module into the cabinet and tighten the screws on both  sides       Turn on maintenance bypass switch and off main switch       Wait for two seconds  Press menu control  gt  system turn on  gt YES on the operator control  and display panel for two seconds to manually turn on the inverter mode     48    6 2 Replacement Procedures Of Air Filter    As shown below figure  the UPS provides four air filters on the back of the front door  Each filter  is fixed by a fixing bar on both sides       Air Filter            Fixing bar              T  4 4  e     4  E A  Pt L   D D a     BA    KEE A    A    ar  B IA   Leg  AN         Fixing bar  
36. unction is reserved     43    Ld Lei   12 D  F vUN    E iri  e 0 m    E    amp  e  x X x X    Figure 5 4 Maintenance Bypass Switch State port    Table 5 3 Description of Maintenance Bypass Switch State port  Maintain Bypass Pin1 Maintenance bypass switch state    Maintain Bypass Pin 2 Maintenance bypass switch state  Ext  Maintain Bypass Pin 3 Ext Maintenance bypass switch state  Ext  Maintain Bypass Pin 4 Ext  Maintenance bypass switch state       5 4 Internal Output Switch State Port  X5 is the internal output switch state port  The port is shown in Figure 5 5 and described in  Table 5 4   This function is reserved    uc       N    i     Figure 5 5 Internal Output Switch State Port    Table 5 4 Description of Internal Output Switch State Port  Internal Output Pini Internal Output switch state  Reserved        Internal Output Pin 2 Internal Output switch state  Reserved     5 5 Battery Cabinet Temperature Detection Port   The UPS has battery cabinet temperature detection function  UPS can through the external  battery cabinet temperature detection board to receive battery cabinet temperature   Communication between the Ups and Battery temperature detection board was by I2C  communication protocol  X6 is the battery cabinet temperature detection port  The port is shown  in Figure 5 6 and described in Table 5 5     44       Figure 5 6 Battery Cabinet Temperature Detection Port    Table 5 5 Description of Battery Cabinet Temperature Detection Port    Name  12C communication SCL
37. ximum current and power cable configuration                               19   4  Control Panel and Display Description NENNEN 20  a Hae s s s  V SEIS RENT REM 20    2 oc een Re la Le EE ER   AA el gl sll aa 22  SANAT Ree  TT E US NA NE 22  22 94 Menu Seken 23  42A Control SCIeer uae vum Mun putes DEVE E ME EL ona EC 23  22 9 Measurement en NEE 24    eZ JOSS CLL SCI Ce ECCE E DIN INIT 26    22 7 Informalloh SCEE EE 35    e EHA EE Bo UV NEQU NV EMA UE 36   e GE EE un EE 20   5  wie Te and e ei in le Uer ale EE 42  Sel Ren ole EP o e el E e EE 42   SL DC PON tuse RE en DNE MEUS AA 43   5 3 Maintenance Bypass Switch State Port sss esse cesse eenn 43   5 4 Internal Output SWIECD State POM  EE 44   5 5 Battery Cabinet Temperature Detection POFt         oWoo o co  oo  44   5 6 Bypass back feed Control Port    uk NENNEN RANNER 45   5 7 Battery breaker Centro ae Rai 45   5 8 Other Communication Interface    nan 46   Giz SN Bi ae nak 47  6 1 Replacement Procedures Of Power Module  STS  amp  Control Module                                47  SM MEE eI T LU UT 47   6 1 2 Power Module Replacement Drocedures uk 47   6 1 3 STS  amp  Control Module Service Procedures                           eene 47   6 2 Replacement Procedures Of Air Filter    oo  oo oo 49   J    Opera ni 50  7  Conrormity And  Standard Ss  aa 50   7 2 Environmental Characteristics            oo    oo  mo    mo    50   Ao Mechanical lee asiron a aka 51   7 4 Electrical Characteristics  Input Rechter     uk 51   7 5 Electri
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
WX220J 取扱説明書 文字の入力について    Superior GHC/GRD-5500 User's Manual      COE-SOFT_IFU_4Language (Revision 06-2015)_2  Pro 550 - Garmin    ALTINA A800 User`s Manual      Copyright © All rights reserved. 
   Failed to retrieve file