Home
        Unitary Controller (UNT) - Johnson Controls
         Contents
1.                         Ziv        a ziv WOIV                  mmm     LM WOW LE LIV                 Diagram is for UNT110 111 and    Note  UNT110 111 is shown in illustration   UNT120 121     Figure 10  UNT110 111 and UNT120 121 Terminal Designations    26 UNT Controller   Unitary Controller  UNT     Table 7  UNT110 111 and UNT120 121 Terminal Identification                v ______                COMMON AOCM                      7        1 Binary Output 7  AO Common Analog Output 1                          Common              2 Binary Output 8  AO Common Analog Output 2       UNT Controller   Unitary Controller  UNT  27      ELEISON  CONTRELS                     LOW HIGH       NY          000 mee             ud C SWITCHING L hy     zone  O oTa Egs   lt   STAT  Za 598 122  ZBUS 598                          Gay               Gi      i            SS                                                                       1                     RTN      BOS RTN BOS BOT                                                                       UNT140                BO6 BO7 RTN BO8       A A A  15 24 24        All        Al2 AI3          14 AIS        AIS             yac BI2 BI3             jag BOTRTN BO2        RTN                                                                REF   2   2           CY         CSC YC           CS CS         CWCY BO      Triac Jumper Connector    an COM   2                  AIS         dO               2 B ic 14 NS                           RTN        Bg   
2.                      15 000 ohms       e NNN                      00    M100J 1  for Return 10 4  8 1 p    Air Damper    120 24 VAC    Power  Transformer  Z  y    T                        858    120 24 VAC    Power  M100J Transformer   _   4    for Exhaust  Air Damper                untm100e    Figure 18  R81EAA 2 UNT Controller Interface    UNT Controller   Unitary Controller  UNT  39    HE 6300 Humidity Perform the following steps to connect an HE 6300 Humidity Sensor to  Sensor the UNT  see Figure 19      1  Set the analog input DIP switches on the AS UNTxxx board to    10 volts   Switch 1   OFF  Switch 2   ON    2  Enter the range of the humidity sensor through HV AC PRO for  Windows  0 to 10 VDC is equal to 0 to 100  RH                                                                                            Analog Input  DIP Switch  Setting  sw2  SW1  S BINARY IN   A BINARY OUTPUTS         FERAI           PWT     unthe  HE   Ewe Huy         Sensor          Figure 19  Example of HE 6300 Humidity Sensor Connection    40 UNT Controller   Unitary Controller  UNT     Temperature  Sensors          CESON  CONTRELS                                                                         CBLPRO       9        or 25 pin          Adapter    2 amp   ez 2    Laptop         Zone           6       to 8 pin       HA        or    Zone  Terminal             CBLPRO           9 pin or25 pin          8 pin  Adapter       5               to         g 8 pin  Laptop PC Zone Bus  6 pin to 6 pin
3.                 z    NO                         AS RLY050 0   AS RLY002 0    unt2ahu    Note 1  Separate low voltage wiring on the left from line voltage wiring on the right    Note 2  Hand operation using the H O A switch requires common to the COILS  terminal and 24 VAC to the TRIAC terminal to energize the relay    Note 3  The Hand or Off position signals the binary input connected to those terminals   These switches can be hardwire  OR ed and connected to one BI  This  switch uses the HOA COM terminal  which is isolated from the relays    Note 4  Your application will determine exact connections to UNT     Figure 16  UNT110 111 Wired to RLY050 002 with Isolated BOs    36 UNT Controller   Unitary Controller  UNT     Wiring Sensors    and Actuators    You can obtain a Double Pole  Double Throw  DPDT  relay configuration  by connecting the BO signal to two terminals on the relay kit terminal  block  e g   B and C   If you require a phone jack at a remote relay kit  add       AS CBLCON O     For additional information  refer to the grounding and isolation  information in the Wiring Details section of this technical bulletin     Use 18 AWG twisted pair wire for all sensor and output wiring  Shielding  is not required  However  if you decide to use it  earth ground the shield at  the transformer  You may also use 24 AWG wire in some applications  but  maximum wire length will be reduced due to the increased resistance  To  minimize sensor error caused by field wiring  the total
4.            N               t Y                        NV        P P  ln  In     o  HHIH S HHH ONS    Wh   d    x          t c  COO RS te 3  HH R   m    m    Metal Barrier                                     Y2    iN                          UNT             Figure 39  UNT Directly Driving Loads    86 UNT Controller   Unitary Controller  UNT        7777                                                                                                                 i  22 AN       BH            Ls CN  e MN       D      NS       ie    9              p            n   n     2    3     4        2 M       RB    IR    t 3  S       Metal Barrier         Metal Barrier       gt        a        2 2  3 3 5  3 3 3       Load                                               I                 Ns      UNT             Figure 40  UNT with Pilot Relays    UNT Controller   Unitary Controller  UNT  87    Considerations The following information should be taken into consideration for specific  for Specific rooftop units     Rooftop Units 1  Lennox GCS16 Series Rooftop Units  For Lennox      16 series rooftop units  bypass the K25 blower fan  delay relay  TDR  by disconnecting the K25 coil power wire  Lennox  provides K25 blower control for use with electromechanical  thermostats  The reason for disconnecting this when a UNT provides  the blower control functions is that the K25 causes unnecessary  contactor cycling  This creates additional electrical noise  On some  Lennox models  it may also cause blowe
5.        Go to the Network Map on the Operator Workstation  OWS      Double click the system name to which the new UNT object is to be    Select Type N2 devices in the Item New dialog box     itemnew    Figure 2  Item New Dialog Box    Note  The Hardware System and Hardware Object text fields are not  used for this object type     UNT Controller   Unitary Controller  UNT  7    6  Highlight UNT in the Add N2 Device dialog box as shown in Figure 3     Hardware    Add N2 Device    OK       Device Type  AHU  060  DCM  DR9100  DX9100    IFC 2020  LCP                      n2dve    Figure 3  Add N2 Device Dialog Box    7  Click OK   8  Complete the attribute fields in the UNT Definition window   see Figure 4      UNT Definition           Edit View Action Go To Accessory                      Tower 1  Floor 1 Bookmark                               Hardware                            Comm Disabled             Hardware Flags   N2 Trunk Number Auto Dialout  N2 Device Address  Poll Priority                                                                      windobj  Figure 4  UNT Control Device Object Definition Window    Note  Fill in the blank UNT Definition attribute fields as required   Specify an N2 Device Address from 1 to 255  Default values in the  remaining attribute fields may be accepted or changed     8 UNT Controller   Unitary Controller  UNT     Defining a UNT    Control Device  in Companion  Software    Table 3 explains the blank attribute fields  The Operator Workstation  U
6.     IMPORTANT  When setting the N2 Address  do not use Address 0     Set the N2 address and test for N2 voltage  polarity  and isolation before  actually wiring the UNT for operation  The factory default address is 3     The switches located in the upper right corner of the UNT must be set to  the same number as the software assigned to the module  The Metasys  or  Companion  Facility Management System  FMS  uses this address for  polling and commanding  The numbers are in binary format and  horizontally arranged  with the least significant digit on the right     For example  if the controller address is 17  decimal   the binary  representation is 00010001  Switches    1    and    16    must be set to the    on     position  1   16   17   as shown in Figure 23           If you change the address while  the UNT is online  you must  cycle power for the network to  recognize the new address                J amp HNSON  CONTRELS     METASYS            123456             Address Switches             BINARY OUTPUTS    Figure 23  Setting the N2 Address DIP Switches    46 UNT Controller   Unitary Controller  UNT     N2 Wiring to the  Network Control  Module                NCU  TB1 on  Communication  Terminal Board                                                                                8 nee    Note  Since the UNT is a self terminating device  end of line termination  for the N2 Bus is not required  n2wire a    Figure 24  Connecting the UNT Controller to an NCM    Table 14  Term
7.    the Zone Terminal tab  Zone Terminal Technical Bulletin   LIT 6363014   for proper cabling between the ZT  ASC  and CBLCON     50 UNT Controller   Unitary Controller  UNT     Fan Coil  Applications    Application Examples       All of the following examples were created by answering configuration  questions using HVAC PRO for Windows to identify terminal locations of  the inputs and outputs  Refer to the HVAC PRO for Windows User s  Manual  FAN 637 5   the UNT Controller section  for detailed information  regarding controller configuration  The UNT110 111 series controller was    used in all examples     Table 18  Fan Coil Parameters and Configuration Selections  Configuration Selections  Common Heating Cooling Coil    HVAC PRO for Windows Parameters    Heating Type    Yes       Lighting Integration    Return Air                Discharge Air                                                                                               Figure 26  Fan Coil Mechanical Flow Diagram    UNT Controller   Unitary Controller  UNT  51    Transtormer g RM SP    120 24 VAC  TE1  120 VAC Power     24        RM T        ANALOG INPUTS BINARY OUTPUTS    ANALOG                                                                                       PIT 1011 41111     1111                     om     VA1                    2           canna                       R1   Lighting   Relay             fcwire    Figure 27  Fan Coil Wiring Example    Bill of Materials     Table 19  Fan Coil      of Mate
8.   N     f                      A                    BO6 BO7 RTN BO8       7 AL       e   lt  iL     gt  5 E uaa  m zz  UNT141   OR oc  N          A A A  15 24    Al                                             6 vpe      vac                            scrtrm2    Figure 11  UNT140 141 Terminal Designations    28 UNT Controller   Unitary Controller  UNT     Table 8  UNT140 141 Terminal Identification    as  Noui SSCS     ________                                        a4 Agua       _________                  Aekghu     m     Bmymui           Return  24 VAC or Common   or Analog Output Common  Common  Transformer Low Side    zBus      S O  Ne    Depends on triac switching jumper setting  If high  return is    Common      If low  return is    24 VAC                UNT Controller   Unitary Controller  UNT  29    Analog Inputs The six analog input terminals  their power supply  and their common  points occupy the lower left corner of the terminal strip  These inputs may  be of two types  resistive or voltage  The UNT processes and controls the  configured control strategy  It reads the analog inputs through the analog  input DIP switches located directly above the analog input terminals     Use these switches and HVAC PRO for Windows to select the type of  analog input  Use the T position for all temperature sensors and setpoint  potentiometers  Use the V position for all active voltage transmitters  For  humidity applications using 3 wire voltage transmitters  such as the  HE 6300 
9.   Note    that in this case you do not need a relay on every BO  unless isolating noise with relays  see the Important  preceding this one         e You must use a line filter between the binary output of the UNT and  the control input of the ignition device for direct spark ignition  systems  Many pilot ignition systems do not require this filtering   However  we recommend its use if you are not familiar with your  rooftop unit   s particular ignition device  Pilot ignition devices light  small pilot flames and generate small amounts of electrical noise   Direct ignition devices generate large amounts of noise by creating  hot sparks with enough energy to ignite main gas valve burners     e You must also filter any wires connected to the gas valves that you  route with other wires leaving the gas heating section  An individual  line filter can filter two wires  but it is acceptable to use only half of it  if you need to filter a single wire  Mount the filters on the metal wall  between the ignition chamber and the fan chamber  We recommend  the filters listed in Table 40     Table 40  Recommended Filters    ava 8174542  152439       Note  These filters        all rated 3A  120 250V  and are available from  Newark Electronics  These models are specified for derating with  an unbalanced load  No other models are authorized     e You must use a pilot relay to isolate the UNT binary output from any  gas valve containing a full wave bridge rectifier  The bridge rectifier  causes 
10.   features of the different hardware sets  Table 2 lists the differences by  model     UNT Controller   Unitary Controller  UNT  5    Table 1  Unitary Controller Hardware Characteristics  Similarities    Characteristic    6 Analog Inputs RTD temperature elements  1000 ohm nickel  platinum  or silicon   Adjustable 0 to 2k ohm setpoint potentiometers  0 to 10 VDC or 0 to 2 VDC transmitters    4 Binary Inputs  4  24 VAC input only  24 VAC provided    1  Momentary pushbutton from Zone Sensor for temporary occupancy mode  BI 5   BI 4 may be used as an accumulator input for frequencies less than 2 Hz     Zone Bus Removable screw terminal block  Light Emitting Diode  LED  Indication  8 pin phone jack   see Table 2  on controller   24 VAC Power in Removable screw terminal block   ISP TES    N2       Terminations   Removable screw terminal block       Table 2  Unitary Controller Hardware Characteristics   Differences    Characteristic   UNT110 1 UNT111 1 UNT120 1 UNT121 1 UNT140 1 UNT141 1       Operating 0 to 52  C 0 to 52  C  40 to 52  C  40 to 52  C 0 to 52  C 0 to 52  C  Temperature  32      125     3210125       40to 125      40to 125    32to 125 F     32 to 1253   Rating  Analog Outputs      to 10 VDC   10mA  Binary Outputs   24 VAC Triacs    0 5A or 0 8A if  total power is  limited  Low or High side  common  selectable  Zone Bus  see Additional Additional  Table 1  6 pin Phone 6 pin Phone  Jack Jack       Terminations i i i i Fixed Screw _   Fixed Screw  Connects Connects Conne
11.  400 mA     25 VA for UNT120 121  due to heater     Ambient Operating Conditions 0 to 52  C  32 to 125  F  and   40 to 52  C   40 to 125  F  for UNT12n 1    10 to 90  RH    Ambient Storage Conditions  40 to 70  C   40 to 158  F   10 to 90  RH    Dimensions 165 x 163 x 56 mm  6 5 x 6 4 x 2 2 in     H x Wx D  without enclosure  ENC     173 x 185 x 119 mm  6 8 x 7 3 x 4 7 in   with  enclosure    Shipping Weight 0 64 kg  1 4 Ib   800652                 32           64K ROM  8K EEPROM    Standards Compliance IEEE 472  IEEE 518  IEEE 587 Category A  FCC Part 15  Subpart J  Class A  UL 916  UL 864    Agency Listings UL Listed and CSA Certified as part of the  Metasys Network        UNT Controller   Unitary Controller  UNT  77    78 UNT Controller   Unitary Controller  UNT     Environmental    Information    Installation  Requirements    Appendix A  Precautions for  Rooftop Installations       Mount the UNT within the rooftop unit or some other enclosure to protect  it from rain  snow  etc  We recommend venting for small enclosures in  environments that regularly exceed 32  C  90  F   The installation site of  the UNT must meet the following environmental standards     e The atmosphere must be free of explosive gases  or corrosive  chemical or salt vapors     e The relative humidity  noncondensing  must be between 10 and 90      e        temperature for the UNT110 111 series controllers must be  between 0 and 52  C  32 and 125  F      e The temperature for the UNT120 121 series contr
12.  Damper    to 10 VDC  Actuator  Spring Return    72 UNT Controller   Unitary Controller  UNT     Accessories    Vendor Code    Numbers    Table 31  UNT Accessories  FASRLYOOO ______ Rey 2SPOT SA240VAG        AS RLY050 0 Relay Kit  2 SPDT  5A   240 VAC with enclosure  AS RLY100 1 Relay Kit  4 SPDT  5A   240 VAC with enclosure               0 Replacement N2 Bus and Five N2 Bus and  Power Terminal Block Five Power Terminal  Connectors Blocks  EN EWC10 0 Enclosure for UNT  optional  UPM Plastic  EN EWC15 0 Enclosure with 50 VA UPM with 50 VA  Transformer  TE 6001 961 Momentary Button Kit for N A  Temporary Occupancy or  Boost Modes  for TE 6100 11   12 only   MM CVT101 0 RS 232 RS 485 Converter for   N A  N2 Download Commissioning  with HVAC PRO for Windows  WS WINPRO 0 HVAC PRO for Windows N A  Software  WS WINPRO 6 HVAC PRO for Windows N A  Software Upgrade  Y65XX X Series Transformer 24 120 220 277 480 VAC  to 24 VAC    AS ZTU100 1 Zone Terminal    N A      Note  The AS ZTU100 1 supports both AS UNTxxx 0 and AS UNTxxx 1 models   The AS ZTU100 0 supports AS UNTxxx 0 models only        Tables 32 and 33 list preconfigured cables and cable components available  from     Southwest Wire  5950 Office Blvd  Albuquerque  NM 87109    Phone  1 800 334 2150  Fax   505  344 3400    UNT Controller   Unitary Controller  UNT  73    Use Table 32 to order preconfigured cables from Southwest Wire     Table 32  Preconfigured Cables  Southwest Wire    RJ45 Straight through 7 62 m  25 ft  CBL STAT2
13.  Metastat    Figure 20  Example of Temperature Sensor Connection    To make all necessary wiring terminations between the UNT and TE 6400  series Metastat     use phone cable that has preterminated 8 pin RJ 45  connectors  For cable ordering information  refer to Vendor Code Numbers  in the Ordering Information section of this technical bulletin     Connect one end of the cable to the Zone Bus connector on the controller  and the other end to the 8 pin connector on the back of the sensor as  shown in Figure 20     In addition to the 8 pin RJ 45 connection  the TE 6410 sensor also has a  6 pin  RJ 12 connection under its cover  This allows remote connection of  the CBLPRO or the Zone Terminal  used for system monitoring      For UNT140 141 series controllers  there is an additional 6 pin jack for  Zone Bus communication  You may permanently connect a Metastat to  the 8 pin jack of the controller and simultaneously connect a   laptop PC CBLPRO or Zone Terminal to the Zone Bus via the 6 pin jack     UNT Controller   Unitary Controller  UNT  41       Phone Jack Figure 21 illustrates the polarization of the 6 pin and 8 pin phone jacks on  Polarization the UNT or Metastat  Terminal 1 is to the extreme left as you face the jack  opening  tab notch down                           Figure 21  Phone Jack Polarization    The following table defines the pin usage for each jack     Table 13  Phone Jack Pin Identification    8 Pin Jack  UNT to Temperature 6 Pin Jack  UNT140 Controller to  Se
14.  Mount the UNT in a convenient location using the predrilled mounting  holes  The controller must be mounted vertically on a wall or panel where  it can be easily wired through the enclosure cover  This also applies to  remote location packages     UNT Controller   Unitary Controller  UNT  13    Do not use this knockout   Otherwise  controller will  be in the way of wiring                                      lt   fe     Ed Wwe     Top   Bottom       Side                                                                      untencl    UNT Enclosure  Cover     Figure 5  Installing the UNT Controller in ENC100 Enclosure Kit    Installing the UNT   To install the UNT in an ENC100 enclosure kit  see Figure 5   use the    in a ENC100 following procedure     Enclosure Kit         1  Use a flat blade screwdriver and pliers to remove the necessary wire    passage knockouts        2  Position the enclosure firmly against the mounting surface and mount  it with the appropriate screws     3  Secure the UNT    inside the enclosure kit     using the  three mounting tabs   on the sides of the controller board base     4  Attach the enclosure cover    after installing the wiring     14 UNT Controller   Unitary Controller  UNT     UNTxxx 101 The UNT can be directly mounted into an EWC10 enclosure  You may  also purchase the UNT110 111 or UNT140 141 premounted in an EWC10  enclosure with    24 VAC 50 VA transformer  When the UNT is  premounted in an EWCIO enclosure with a 50 VA transformer  th
15.  Zone Terminal  and  AS CBLCON  The bus interface sustains no damage in the presence of  fault voltages of 24 VAC or less     M100 actuators should be powered with separate transformers  therefore   only the Zone Bus and common wires need to be pulled     See Table 15 for Zone Bus specifications     48 UNT Controller   Unitary Controller  UNT     CBLPRO  Description    Table 15  Zone Bus Specifications    Recommended Cable Type 18 AWG with shield  Beldon 8760  or   24 AWG with no shield  unshielded telephone cord   Maximum Bus Length 150 m  500 ft  with 18 AWG cable or    30 m  100 ft  with 24 AWG cable    Range of Addresses 0 to 63    Voltages    Logic High Voltage 4 VDC minimum  approximately   Logic Low Voltage 1 VDC maximum  approximately     Data Transmission 1 Start Bit  low level   8 Data Bits  least significant bit first   1 Stop Bit  high level      Note  If a CBLPRO 1 and a Zone Terminal are used  the cable length must be limited  to 15 m  50 ft    The UNT110 111  UNT120 121  and UNT140 141 series controllers  contain an LED that blinks to indicate Zone Bus activity with or without  external connection  During power up  there is a brief delay while the  UNT undergoes a diagnostic reset  The LED will blink once  turn off for  approximately 10 seconds  and turn on again  When a PC communicates  with the UNT via CBLPRO  the blink rate may appear to change  that is  it  may appear to be more steady        Table 16  Zone Bus LED    poh                                The 
16.  and 125  F  with relative humidity  non condensing   maintained between 10 and 90 percent     e        UNT120 121 series controllers used with outdoor rooftop  applications  the temperature must be maintained between   40 and 52  C   40 and 125  F  with relative humidity maintained  between 10 and 90 percent  Some intermittent condensation is  tolerable  This operating temperature range is possible in the  UNT120 121 series controllers due to the heater  coated circuit board   and BZ 1000 7 size enclosure     The UNT is commonly packaged either in an enclosure provided by the  installation contractor  or in an AS ENC100 0 or EN EWC10 0 enclosure   The UNT140 141 101 and UNT110 111 101 come mounted in an EWC10  enclosure with a 50 VA transformer  The controller requires a flat  mounting surface area to match its dimensions     The UNT controller has the following dimensions   e 165 x 163 x 56 mm  6 5 x 64 x 2 2 in   H x W x D without enclosure    e 173 x 185 x 119 mm  6 8 x 7 3 x 4 7 in  Hx W x D with the  AS ENC100 0 enclosure    e 229x406x 191 mm  9 0 x 16 0 x 7 5 in   H x W x D with the  EWC10 or UNTxxx 101 version    Allow enough room to install the enclosure and conduit for wiring  terminations to the controller     12 UNT Controller   Unitary Controller  UNT     Enclosures for  Mounting a  UNT 120 121    Positioning    The UNT120 121 low temperature rated controller must be installed in an  enclosure as suggested below  unless it is mounted within the enclosed   low vol
17.  and REF  The N2  and N2   lines carry the data signals  The REF line provides a reference so that each  connected device is capable of electrically receiving and transmitting data  by creating a common voltage reference among all the devices connected  together by the N2 lines  Three lines are required     The configuration of the UNT can be uploaded  downloaded  and  commissioned over the N2 Bus using an Operator Workstation  OWS   with HVAC PRO for Windows and an NCM  or a PC with HVAC PRO  for Windows and an MM CVT101 0  This can also be accomplished with  Controller Access and Companion directly or remotely connected    Refer to the Controller Access Technical Bulletin  LIT 6364013  in the  HVAC PRO for Windows User   s Manual  FAN 637 5      UNT Controller   Unitary Controller  UNT  45    Installing the    N2 Bus    Setting the N2  Address    IMPORTANT  The N2  and N2  lines must be twisted pair lines   This allows most induced noise  common mode    noise  from external sources to affect both lines  equally  thereby canceling the noise        Notes  Do not run N2 Bus wiring in the same conduits as line voltage  wiring  30 VAC or above  or wiring that switches power to highly  inductive loads  such as contactors  coils  motors  or generators      For more N2 Bus overview information  refer to the Application  Specific Controllers Technical Manual  FAN 636 3   the  Introduction tab  the ASC and N2 Bus Networking and  Troubleshooting Guide Technical Bulletin  LIT 6363003  
18.  and cable components available  from     Anixter  4701 W  Schroeder Drive  Brown Deer  WI 53223    Phone   414  355 0222  1 800 447 8565  Fax   414  355 8601    Use Table 36 to order preconfigured cables from Anixter     Table 36  Preconfigured Cables  Anixter  Cable Length    RJ45 Straight through 7 62 m  25 ft  Q1093 307 25  Cable Assembly  Non plenum    Non keyed plugs 15 24 m  50 ft  Q1093 307 50    24 AWG 30 48 m  100 ft  Q1093 307 100  8 Conductor  Solid Wire    RJ45 Straight through 7 62 m  25 ft  Q0893 404 25  Cable Assembly Plenum    Non keyed plugs 15 24 m  50 ft  Q0893 404 50    24 AWG 30 48 m  100 ft  Q0893 404 100  8 Conductor  Solid Wire       UNT Controller   Unitary Controller  UNT  75    Use Table 37 to order cable components from Anixter for creating your  own cables     Table 37  Cable Components  Anixter    304 8 m  1000 ft  Roll of Non plenum CM 00424BAG 3  Rated    e 24AWG  e 8                     e Solid Wire    304 8 m  1000 ft  Roll of Plenum Rated CMP 00424SAS 3    e 24AWG  e 8 Conductor  e Solid Wire    8 Position Non keyed Plugs for Solid 074683 Stewart  Cable  bag of 25    Hand Tool with 8 Position Die Set for 060612   Solid 24 AWG Wire       76 UNT Controller   Unitary Controller  UNT     Specifications       Table 38  Specifications  AS UNT110 1   AS UNT1 11 1    AS UNT120 1   AS UNT121 1  AS UNT140 1   AS UNT141 1    Power Requirements   System 24 VAC  50 60 Hz at 40 VA  per typical  system     Power Draw UNT with sensors transmitters   10 VA 
19.  is  required if the NCM is to communicate with N2 devices  On the NCM200  and NCM300  the specific connection point for the Metasys Network is  the built in N2 Submodule  On the NCM100 and NCM101 401  install  this submodule into one of the submodule slots     When installed in a Metasys Network  the UNT receives commands from  the NCM or Companion on the N2 Bus  and transmits status reports in  return  The maximum electrical limit on the N2 Bus is 255 devices   However  the number of controllers on the N2 Bus is a database memory  issue at the NCU or Companion  Refer to the database generation  documents in either the Metasys Companion Technical Manual    FAN 628 1  or the Operator Workstation User   s Manual  FAN 634  to  determine practical limitations to the number of controllers on the N2 Bus     The N2 Bus connections are electrically isolated from other UNT110 111   UNT120 121  and UNT140 141 circuitry to 500V by optical and magnetic  coupling     For runs up to 1 520 m  5 000 ft   use stranded 18 AWG or heavier   twisted 3 conductor wire  electrically  lighter gauge wire works  but it is  fragile and prone to nicks and breaks   Avoid using solid wire when  possible  as it is prone to break when pulled  Runs longer than 5 000 feet  require use of a bus repeater  An N2 network may be extended to a  maximum length of 4 568 m  15 000 ft  using two repeaters     The N2 Bus is a daisy chain communications line  It consists of   three wires carrying three signals  N2   N2  
20.  is the internal shared node of each triac output    see Figure 13   When connecting this terminal  via the wire jumper  to  24 VAC for high side switching  each load must be connected between the  binary output terminal and any common terminal  When connecting this  terminal to common for low side switching  each load must be connected  between the binary output terminal and any 24 VAC terminal     UNT Controller   Unitary Controller  UNT  31    UNT140 141    Analog Outputs    Zone Bus    On the UNT140 141 series controller  terminals labeled RTN  Return  are  associated with the binary outputs  and a jumper block sets high side or  low side switching  Setting the jumper block to Low Side BO sets the  RTN terminals to 24 VAC  Setting the jumper block to High Side BO sets  the RTN terminals to common     The       101  UNT111  UNT121         UNT141 controllers have   two analog outputs  The load connects between the analog output and  analog output common terminals  Each output generates a proportional  voltage output of 0 to 10 VDC to common  The maximum load for each  output is 10 mA with a minimum 1000 ohm load resistance     The Zone Bus provides UNT connections for   100   series actuators   CBLPRO  for HVAC PRO for Windows commissioning   and the Zone  Terminal  ZT   The Zone Bus is available for connection at the Zone  Temperature Sensor  Zone Humidity Sensor  M100C series actuators   UNT Controller Board  and CBLPRO     32 UNT Controller   Unitary Controller  UNT     
21.  mode to  force the controller into Occupied  mode or insert a jumper across the  defined  occupied BI if the UNT is  already configured to Occupied  mode     Check the configuration to verify if  the fan was to cycle during  Occupied mode     Check air proving switch  Restart  by breaking and making unit power     See above     Remove actuator cover and check  for 24 VAC across T1 and T2   Insert jumper CW to COM  Actuator  should fully open outdoor dampers   Remove jumper     Check that wire from Zone Bus on  UNT is connected to bus terminal   on actuator  Check address of the  M100C actuator  it should be 22     Ensure Zone Sensor is properly  connected with an 8 pin plug to the  UNT     Simulate a load at the sensor using  HVAC PRO for Windows     Simulate a value at the OA sensor  using HVAC PRO for Windows  Commissioning     Wait until time delays have expired   approximately five minutes      Upgrade the ZTU100 0 to a  ZTU100 1  Refer to the Zone  Terminal Technical Bulletin in this  manual for more information     Set jumper so that triacs are  switching proper side of  transformer     Add a 1k ohm  2 watt resistor  across the relay coil        Troubleshooting    the N2 Bus       Troubleshoot the N2 Bus if the Companion system is not properly  communicating with the UNTs  Tables 26 and 27 cover many UNT or N2  communication problems and suggest which actions to take     Specific troubleshooting tests are also given in this section  Before trying  one of these tests  y
22.  resistance of all  resistive sensor wiring should be less than 3 0 ohms     A CAUTION  Do not run AL BI  AO  BO  ZBUS          Bus  wiring in the same conduit as line voltage wiring   30 VAC or above  or wiring that switches power to  highly inductive loads such as contactors  coils   motors  or generators     The insulator on the  15 VDC terminal prevents  inadvertent shorting to the adjacent 24 VAC  terminal  To prevent damage to the controller   remove and discard this insulator only when you  need to use that specific terminal        Table 11  Input and Output Load Impedances   main             mnt  Range Impedance Impedance    inputs o    Al Voltage 0 2V or 0 10 VDC 470k ohm    Al Temperature  1000 ohm Si  Ni  Pt  or   3540 ohm  Potentiometer 0 2k ohm Potentiometer    BI VAC 60 Hz 0 24 VAC  2 5V 470k ohm    AO Voltage 0 10 VDC   10 mA 1k 10M ohm  maximum    BO VAC Triac 24 VAC   50 800 mA   30 480 ohm    With total controller power draw limited as described previously        UNT Controller   Unitary Controller  UNT  37    Table 12  Sensor Wire Sizes and Maximum Lengths                        Sensor Type Length In Meters  Feet    Length In Meters  Feet     Al Voltage 152 4 m  500 ft  30 5 m  100 ft   BI Voltage Contact 152 4 m  500 ft  152 4 m  500 ft     152 4 m  500               If a CBLPRO 2 and a Zone Terminal are used  the cable length must be limited  to 15 m  50 ft         M100 R81CAA 2      850  CONTRELS   METASYS           A CAUTION  If the same transformer is 
23.  used for both the UNT  and M100 boards  ensure  that polarity is correct   1      COM connected to   1   to avoid shorting the  transformer                                                                       UNTxxx 1   Z CW EOM T    shown here                        24  ZBUS               Note  When you connect      M100C  CCW BUS T2 actuator to the Zone Bus  we      y recommend powering it with a        ND separate 24 VAC transformer        M100 Motor with  R81CAA 2 Board          HVAC PRO for Windows    J       indicates the needed address        Zone Bus  Address Switch  Set address to 22     012345678                         untm100c    Figure 17  M100C Motor Zone Bus Connection Using an R81CAA 2 Board    38 UNT Controller   Unitary Controller  UNT     When you connect an M100C actuator to the Zone Bus  we recommend  powering it with a separate 24 VAC transformer  However  you may use  the UNT   s transformer if it is sized to provide the required additional   20 VA and connected with the correct polarity  See Figure 17 for terminal  locations when wiring an M100C actuator                                                                                          M100 R81EAA 2  ANALOG INPUTS   BINARY IN   BINARY OUTPUTS  LLL El aye                11955555              Outdoor Air Damper Control R81EAA 2  tf     24 VAC  d 12024                  uos       Damper Command  Power J   common         7  Transformer   Minimum Position  m 4 aim   807 Override  O Mixed Air  Sensor 
24. 5 SW  Cable Assembly Plenum    Non keyed plugs 15 24 m  50 ft  CBL STAT50 SW    24 AWG 22 86 m  75 ft  CBL STAT75 SW    8 Conductor 30 48 m  100 ft  CBL STAT100 SW  Solid Wire    Use Table 33 to order cable components available from Southwest Wire  for creating your own cables        Table 33  Cable Components  Southwest Wire  304 8 m  1000 ft  Roll of Plenum Rated CMP 00424SAS 3      24 AWG  e 8 Conductor  e Solid Wire    RJ45 Modular Plugs  100710  Premium Economy Crimp Tool  104012  Twisted Pair Easy Strip  104020       Tables 34 and 35 list preconfigured cables and cable components available  from    Windy City Wire   832 S  Central Ave   Chicago  IL 60644    Phone  1 800 379 1191  Fax   773  379 1243    Use Table 34 to order preconfigured cables from Windy City Wire     Table 34  Preconfigured Cables  Windy City Wire    RJ45 Straight through 7 62 m  25 ft  CBL STAT25 WC  Cable Assembly Plenum    Non keyed plugs 15 24 m  50 ft  CBL STAT50 WC    24 AWG 22 86 m  75 ft  CBL STAT75 NC    8 Conductor 30 48 m  100 ft  CBL STAT100 WC  Solid Wire       74 UNT Controller   Unitary Controller  UNT     Use Table 35 to order cable components from Windy City Wire for  creating your own cables     Table 35  Cable Components  Windy City Wire    304 8 m  1000 ft  Roll of Plenum Rated CBL 24 8STAT WC  e 24AWG        8 Conductor    e Solid Wire    RJ45 Modular Plugs  100710  Premium Economy Crimp Tool  104012  Twisted Pair Easy Strip  104020       Tables 36 and 37 list preconfigured cables
25. 6NR20 4     Thomson VE17M00131K VE17M00251K VE17M00301K None  VD24M00131K VD24M00251K VD24M00301K      Indicates the preferred model if several are listed        UNT Controller   Unitary Controller  UNT  17    VO and The I O wiring and N2 Bus must be    clean     without electrical noise  Communications transients from nearby lighting  heavy equipment switching  or inductive  Wiring loads being driven     Tr  ansient Noise For the N2 Bus  the Transient Eliminator    model TE JC04C12  made by   Precautions Advanced Protection Technologies  APT  is recommended  Refer to the  Metasys Network Technical Manual  FAN 636   the N2 Communications  Bus Technical Bulletin  LIT 636018   for more information     18 UNT Controller   Unitary Controller  UNT     Wiring Details       This section details the special precautions and grounding procedures you  must observe when installing the UNT        Possible Equipment Damage or Electrical Shock   To avoid damaging equipment or suffering electrical  shock  ensure that all power supplies to the system  have been disconnected prior to wiring installation     The Complementary Metal Oxide Semiconductor   CMOS  circuits used in the controller are static  sensitive  Use static protection  anti static  mats  and or grounding straps when working on or near  internal circuitry        Power Source The power transformer used must comply with   and Loads e CSA 22 2 No  205  e          ICS 2  Part 2  230    The power to each UNT must be limited to 3 ampe
26. AS CBLPRO is an interface device used between    computer running  HVAC PRO for Windows and Application Specific Controllers  ASCs    It is used for database downloading  uploading  or commissioning via the  Zone Bus communication port     When used with a Zone Bus device  such as the UNT or ZT  the CBLPRO  is strictly an electrical interface between the serial RS 232 port of the  computer and the Zone Bus  CBLPRO operates on 24 VAC drawn from a  UNT over the wire used to make the Zone Bus connections  The data  transfer rate on both the RS 232 and the Zone Bus is 1200 baud     The connection to the RS 232 COM port of the computer is through a  DB9 or DB25 connector supplied with the               After connecting it   make sure the CBLPRO is more than 30 cm  1 ft  away from the computer  monitor and system unit     UNT Controller   Unitary Controller  UNT  49    IMPORTANT  In some cases  a computer monitor or PC will emit  electromagnetic noise that may disturb CBLPRO    communications  Therefore  do not position the  CBLPRO near the monitor or PC        Zone Bus communications to the application specific controllers or ZT  may also be monitored with an AS CBLCON 0  This device has red and  green LEDs whose purposes are described in Table 17     Table 17  CBLCON LED Description    On On Zone Bus wire shorted to common or  CBLCON 0 switch in download  position    Blinking Normal communications          Refer to the Application Specific Controllers Technical Manual   FAN 636 3
27. Application Specific Controllers Technical Manual 636 3  UNT Controller Section                SYS  Technical Bulletin ius    Issue Date    Unitary Controller  UNT        Introduction Page 5  e Description 5  e Standards Compliance 6  Configuring the Controller 7  e Using HVAC PRO for Windows Configuration Tool 7  e Defining a UNT Control Device Object  7  e Defining a UNT Control Device in Companion Software 9  Installation Procedures 11  e Design Considerations  11  e Tools Needed  11  e Environmental Information 12  e Mounting the Controller  12  e Power Line Wiring Transient Noise Precautions  16  e   O and Communications Wiring Transient Noise Precautions 18  Wiring Details 19  e Power Source and Loads  19  e Wiring Precautions 21  e Grounding and Isolation UNT110 111  120 121  140 141 22  e Grounding and Isolation UNT110 111  UNT120 121    and UNT140 141 with Separate Load Transformer  28       ndicates those sections where changes have occurred since the last printing        1998 Johnson Controls  Inc  1  Code No  LIT 6363081 www johnsoncontrols com    e Terminal Designations Page 25    e Analog Inputs  30  e Binary Inputs 31  e Binary Outputs  Triac Jumper Information   81  e Analog Outputs 32  e Zone Bus 32  e Wiring to Unit Mounted Controls  UNT 110 111 and UNT120 121  33  e Wiring to RLY050 002 Relays  85  e Wiring Sensors and Actuators 197   Networking the Controller 45  e N2 Bus Overview  45      Installing the     Bus  46  e Zone Bus Communications  48  Applicat
28. Note 1  Separate low voltage wiring on the left from line voltage wiring on the right   Note 2  Hand operation using the H O A switch requires common to the COILS   terminal and 24 VAC to the TRIAC terminal to energize the relay   Note 3  The Hand or Off position signals the binary input connected to those terminals    These switches can be hardwire  OR ed and connected to one BI  This   switch uses the HOA COM terminal  which is isolated from the relays   Note 4  Your application will determine exact connections to UNT     Figure 15  UNT110 111 Wired to RLY050 002    UNT Controller   Unitary Controller  UNT  35       Figure 15 shows a jumper between 24 VAC and the triac  If the jumper is  between the triac and common make the following changes     1  Disconnect TRIAC from HOA COM   2  Reverse the COILS and TRIAC wires from RLYOSO to the UNT     3  Runa separate wire from HOA COM to 24 VAC at the Binary In  terminal section     Figure 16 shows a UNT110 111 wired to an RLY050 002 with all BOs  isolated from earth ground        BINARY OUTPUTS       ANALOG INPUTS         3  3l              of o   lt    lt   lt    lt     BINARY IN      of      oe          BI 2               6     15 0         15VDC         vc    24 VAC     24 VAC                AI CM  24 VAC                                                 COM  B              Low     l gt  High  See  Voltage           Voltage Note 1      Note 3  7           j     JET  do     i M    NC       NO  COM    NC                           
29. Series  use the 15 VDC power supply terminals next to the  inputs for AI 6  Table 9 shows each configuration     Table 9  Analog Input Configurations    Voltage  V  0 to 2 VDC SW1 to Position V and SW2 to  Position 2V    Voltage  V  0 to 10 VDC SW1 to Position V and SW2 to  Position 10V   Resistance   1 000 ohm Nickel  Platinum  SW1 to Position T and SW2 to   Temperature  T  Silicon  2k ohm potentiometer Position 2V       Setting the The UNT has two sets of DIP switches  One set is for configuring the  Analog DIP analog input points  and the other set is for setting the controller address   Switches Use Table 10 to set analog input DIP switches  Instructions for setting the    N2 Address DIP switches are in the Networking the Controller section of  this technical bulletin                   CONTRELS     METASYS           ANALOG INPUTS   4 28  6    3 5    5  2   lt         COMMONS o  9                         m  a  B    g    24VAC mm       24VAC                TRACS mm     Z       GS eO e       Look             COMMON  m co              T 2V 10V    V       Analog Input Switches    Figure 12  Setting the Analog Input DIP Switches  30 UNT Controller   Unitary Controller  UNT     Binary Inputs    Binary Outputs     Triac Jumper  Information     UNT110 111 and  UNT120 121    The AI switches should be factory set with AI 1  2  and 3 as resistive  inputs  and AI 4  5  and 6 as 0 to 10 VDC inputs  You may reconfigure the  switches by using the following table  For example  if you conn
30. UNT Controller   Unitary Controller  UNT  91    Table 42  UNT100 101 Terminal Identification   Terminal  AICM Alt  AI CM   2                        4           5           6   15 VDC  15 VDC  BICM Bit  BICM BI2  BICM       BI CM Bl4  24 VAC POWER 24 VAC COMMON   ZBUS Common   24 VAG B0   2a VAG 802  24 VAG         24 VAC B04  24 VAC B05  24 VAC B06    24 VAC AOCM 24 Volts AC  BO 7 AO 1 Binary Output 7  AO Common Analog Output 1  24 VAC AOCM 24 Volts AC  BO 7 AO 2 Binary Output 7  AO Common Analog Output 2       92 UNT Controller   Unitary Controller  UNT     Grounding and    Isolation  UNT100 101    Transformer      11   120 24 e  S  24 24 5     2     Power               E             gt  9  Transformer      5   V PA     5  t  a z  as   6       z        wn  4             gt   Load   A       Contactor N  Isolation  Relay    Isolation                                                                                                       visoxfmr    UNT100   101    Figure 42  Transformer and Relay Isolation Wiring Diagram  for Series 100 101 UNT Controllers    All UNT100 101 connections must be isolated from earth ground to  protect the CBLPRO  laptop PC  or other system components from  damage  Due to OEM system designs and or electrical codes  the  UNT100 101 may become earth grounded unless you take isolation  measures        osos Potential equipment damage and improper  functioning  Do not earth ground the 24 VAC high  side of the UNT transformer or any of the UNT  BO   termin
31. Wiring to Unit A  Mounted CAUTION  Some local electrical codes require the secondary    Controls   common of stepdown transformers be connected to  UNT110 111 and earth ground  typically on units which are powered by  UNT120 121 greater than 150 VAC   You may have a maximum of    one single earth ground connection  which must be at  the transformer secondary common  whether one or  multiple controllers are powered by the same  transformer                 ____     LED    BINARY OUTPUTS       UNT Controller    d     M Shared Triac Node    Triac Switching     gt  11113 A      4          Wiring Connections    24        ZBUS   REF N2  N2    VAC    Jumper allows field selection of the supply leg to  be switched by the triacs  In this example  the  triacs terminal is jumpered to  24 VAC   so the  triacs switch the 24 VAC power  high side  leg                                                                   COM     L1 L2                           24         Unit Mounted Control Enclosure                                                                                             tepdown   24        4 Transformer       COMMON                               COMPRESS                                  Heat Comp   Relay                            See the Application Examples  section for more information   See CAUTION for           Wiring to Unit  Mounted Controls    UNT110 111 and  UNT 120 121 section     On unit mounted controls  OEMs typically minimize  wiring between digital controls an
32. a DC current to flow through the triac which can prevent it  from turning off  If you are unfamiliar with the gas valve in your  rooftop unit  a pilot relay is recommended     84 UNT Controller   Unitary Controller  UNT     Keep the length of the high voltage wire from the ignition control to  the spark bundled  and as short as possible  Bundle the spark wire to  itself if it is too long  Keep the ignition control and the UNT as far  apart as possible  Route the power wires to the ignition control along  the metal mounting surface     Ensure that you physically separate the wires on the line side of the   filter from those on the load side of the filter  Route noisy wiring so  that its path is as short as possible  and always avoid routing noisy   wires close to quiet wires  We recommend a 30 cm  1 ft  or greater  separation between parallel noisy and quiet wires         Never mount the UNT in the same compartment as the ignition  device     e If you must install noisy wiring near quiet wiring  have the wires  cross at right angles and as far apart as possible  Route both near  the metal mounting surface     Note  For specific information regarding noisy and quiet wiring  refer  to the Application Specific Controllers Technical Manual   FAN 636 3   the Introduction tab  the ASC and N2 Bus  Networking and Troubleshooting Guide Technical Bulletin   LIT 6363003      UNT Controller   Unitary Controller  UNT  85    Metal Barrier                                                     
33. als  If you do  the UNT N2 Bus    communications will cycle online and offline  You  will also damage all of the interface components that  are connected  including the CBLPRO  laptop PC   Companion PC  and MM CVT101        Depending on the primary voltage of the power transformer and the  prevailing electrical code  the 24 VAC secondary might be earth grounded   Earth ground on the 24 VAC side of the secondary destroys hardware by  creating a short circuit path through the CBLPRO and laptop PC serial  card during a download  Earth ground on either side of the secondary can  disrupt the isolation required for N2 communication integrity     UNT Controller   Unitary Controller  UNT  93    Power  Transformer  Isolation  UNT100 101    Load Isolation  UNT100 101    Binary Inputs    Binary Outputs    In some OEM systems  the contactor solenoid coils driven by the UNT  may also be earth grounded  This also disrupts the isolation required for  N2 communication integrity     Note  The Troubleshooting section of this technical bulletin contains a  detailed process that will reduce installation errors by ensuring  proper isolation     If the secondary of the power transformer is grounded  you must use a  separate 24 VAC to 24 VAC isolation transformer such as the Y65G13   see Figure 42      If UNT output loads  such as driven contactor or solenoid coils  are  grounded  you must use a separate isolation relay for each load   see Figure 42      The binary inputs on the UNT100 101 series c
34. ample in Figure 30  Johnson Controls recommends that packaged  rooftop applications have separate transformers for controller and loads   Sharing of transformers for controller and loads for packaged rooftop  wiring is not recommended     Table 22  Packaged Rooftop Parameters and Configuration  Selections    Zone                 Humidity  o                      _                                                                                                 Exhaust Air T Return Air  DA  Outdoor Air                    7                   dS ete  e _  i  TE                        TE   prmech    Figure 30  Packaged Rooftop Mechanical Flow Diagram    UNT Controller   Unitary Controller  UNT        55    120 VAC d    ANALOG 14     Power  Transformer       EX IN       EPRE                               jo  a   gt             Ir  9           lt    gt    x   a    24 VAC  24 VAC          120 24 VAC    120 VAC    24 VAC    24 VAC    120 24 VAC               R  Equipment 24 VAC  B  Equipment Ground  G  Indoor Blower  W1  Heat Stage 1  W2  Heat Stage 2  Y1  Cooling Stage 1  Y2  Cooling Stage 2    TE1  Room    Sensor    Triac  Jumper  Removed    BINARY           TRENER                                         5  IE                e                                        24VAC       COM  ZBUS                                                 W2 Yi    Unit Terminal Strip                                     priwire2      Phase correctly and size the transformer to include 20 VA for the M100C se
35. ary Controller  UNT  23    A separate load transformer may be necessary because of transformer VA  limitations  or may be desirable to completely isolate loads from the UNT  digital circuitry for better noise immunity     You may connect the UNT110  UNT120  or UNT140 power transformer  secondary directly to earth ground  If you elect to do so  the grounded side  must connect to the common input terminal of the controller     A CAUTION  Equipment damage hazard  You may have a  maximum of one single earth ground connection   which must be at the transformer secondary  common  whether one or multiple controllers are  powered by the same transformer     When grounding one side of the transformer  secondary  the grounded side must connect to the  common power input terminal     Connecting the grounded side of the transformer to  the 24 VAC power input terminal will damage a  CBLPRO 1  0  or laptop        You may connect the separate load power transformer secondary to earth  ground as long as doing so is compatible with the equipment being  controlled     24 UNT Controller   Unitary Controller  UNT     Terminal The UNT terminal designations that identify sensor  actuator  and power  Designations connection points are illustrated in Figures 10  11  and 41  Terminal  functions are listed in Tables 7  8  and 42     You may make connections to the UNT by connecting single wires to the  individual screw or spade terminals     Note  The N2 terminal connectors on the new              1 s
36. ary Output Triac Connections on Terminal Strip Versions  of the UNT140 141    34 UNT Controller   Unitary Controller  UNT     Wiring to  RLY050 002  Relays       Connect power to the relay module and the transformer through the  conduit knockouts in each box  Wire the module according to the  following diagrams  For a schematic diagram of the relay module  see the  Application Specific Controllers Technical Manual  FAN 636 3   the   AHU Controller tab  the AHU Controller Technical Bulletin   LIT 6363010   the AHU Tower Wiring Details section        Possible equipment damage or electrical shock     Disconnect power circuit before wiring relay kit        Figure 15 shows a UNT110 111 wired to an RLY050 002 with      BOs  isolated from earth ground                      BINARY OUTPUTS    rp up Opty                  YALE el el e       z           9158168   gt            s            5  A            ANALOG INPUTS  444444       Sj  gt       of    of Of o  ai  lt   lt   lt  lt                        COMMON BO8    COMMON BO 7                                         z  o   lt                                                                                      Low High  See  Voltage  lt   gt  Voltage Note 1     Note3               AT  C    gt                         i                   37 M B                                     COILS         KO           e  Rac            NC    HAND               OFF           HN   HOA BO Wo f  I    COM               AS RLY050 0   AS RLY002 0  unt1ahu   
37. cts Connects Terminal Terminal   Spade Lugs     Spade Lugs     Spade Lugs     Spade Lugs    Block Block  Available UNT110 101 UNT111 101 UNT140 101 UNT141 101  Premounted in  EWC10  with  24 VAC  50 VA  Transformer  Standards The UNT complies with the following standards   Compliance     FCC Part 15  Subpart B  Class A  e IEEE 472    e IEEE 587 Category A  e UL 916  UL 864  6 UNT Controller   Unitary Controller  UNT     Using   HVAC PRO for  Windows     Configuration  Tool    Defining a UNT    Control Device  Object    Configuring the Controller       All UNTxxx 1 models require HVAC PRO for Windows  HVAC PRO for  Windows also works with previously released UNT models  This software  tool configures  commissions  uploads  and downloads the UNT database   Refer to the HVAC PRO for Windows User   s Manual  FAN 637 5  for   more information on configuring the UNT     In a Metasys Network System  enter data into the Attribute menu to define  a UNT device object     1   2     On the Item menu  click New     UNT   Item New          ype      Accumulator      Analog data      Analog input      Analog output digital     Analog output setpoint  O Binary data      Binary input      Binary output      MS data      MS input       MS output   O Control system  O DL LR group  O LC group      PID loop      Fire Zone      12 devices         2 devices     82 devices     Card Reader             Hardware system name     Hardware object name     Copy of  System Object                             
38. d equipment interface  relays by using one leg of the stepdown transformer   as common     Figure 13  Binary Output Triac Connections on    Quick Connect     Versions of the UNT110 111 and UNT120 121    UNT Controller   Unitary Controller  UNT  33          Triac  Switching  Jumper       Internal Wiring Connections LOW HIGH    72114  E GG   CERERE Jumper allows  REF N2                field selection                                                                   VAC BUS       e              of the supply leg  to be switched  by the triacs     UNT Controller  Triac Switching                         In this example                        the triacs  BOs  will switch to  the 24 VAC power   high side  leg             OOOO OOO O OO    O    24    vac 814 jag BO  RTN                      BO4 805        BOG    24           Bl2                                                                                                                                                      B04  B02  B01  COM  24 VAC  L1 L2  Unit Mounted Control Enclosure  n d f  Stepdown   24 VAC    Transformer      T     COMMON    FAN                    COMPRESS  Fan Heat Comp   Relay Relay Relay                            wireunt2    See CAUTION for  Wiring to Unit  Mounted Controls    UNT110 111 and      On unit mounted controls  OEMs typically minimize  UNT120 121 section     wiring between digital controls and equipment interface  relays by using one leg of the stepdown transformer  as common     Figure 14  Bin
39. e 6 00 and  Controller Access  Because the communication rate is 9600 baud   performing this process over the N2 Bus saves a great deal of time when  loading the initial configuration files and parameters into the controller     UNT Controller   Unitary Controller  UNT  59    60 UNT Controller   Unitary Controller  UNT     Hardware  Installation  Inspection    Tools Needed    for  Troubleshooting    Installation  Checkout    Troubleshooting       Once the mechanical contractor starts receiving delivery of the UNTs with  factory mounted controls  we recommend that arrangements be made to  pull a sample of the shipment for bench testing  This can be done by  loading a job configuration before all the controllers are mounted in the  unit cabinets     Tools needed for typical troubleshooting include     e ASC and     Bus Networking and Troubleshooting Guide Technical  Bulletin  LIT 6363003     e Digital Multimeter  DMM       100k ohm resistor         optional  Double banana plug  see Figure 34  available from a local  electronics store or ITT Pomona Stock No  34F856 or 34F845    100k ohm 1 4 watt resistor for earth ground voltage tests   100k ohm  1 4 watt         Use double banana plug for all tests that require       100k ohm resistor placed in parallel with DMM        Steps   27557 1  Connect 100k ohm resistor under plug s prongs       2  Insert banana plug into DMM     a 3  Connect leads of DMM into banana plug   banana                 dh                      Figure 34  Doubl
40. e Banana Plug Used with 100k ohm Resistor    Review the mounted UNT and compare it with the appropriate  illustrations in the  nstallation Procedures section of this technical bulletin  to ensure proper installation  Also refer to the engineering drawings  supplied for the individual site     1  Ensure that the mounting screws holding the subassembly onto the  base frame are secure     Ensure that accessory equipment is connected and labeled correctly   Ensure that the controller terminal connections are secure     Ensure that the N2 connections are secure and labeled correctly          Sa    Ensure that the UNT switches are appropriately positioned   Refer to  the Wiring Details and Networking the Controller sections of this  technical document      6  Ensure that there are no unwanted earth ground connections to the  controller     UNT Controller   Unitary Controller  UNT  61    Although a single earth ground connection to the common terminal of  UNT110 111  UNT120 121  and UNT140 141 series controllers is  allowed  you may not intend to have one  The procedures described in the  following directions may be used when no earth ground connections to  the UNT are intended or to ensure that there is only one earth ground    connection   Isolation and This section will help you ensure proper isolation within your system   Grounding UNTS These procedures are not required  but are recommended to reduce  without an Earth installation errors  To ensure proper isolation  test the fol
41. e model  number will be UNTxxx 101 rather than UNTxxx 1  For instructions on  mounting the enclosure to a wall  see the Application Specific Controllers  Technical Manual  FAN 636 3   the Accessories tab  the Universal  Packaging Module Technical Bulletin  LIT 6363070                                 Low Voltage  172  Wiring Trough                      untpwer2    Figure 6  UNT Premounted in EWC10  with  50 VA Transformer  UNTxxx 101     Mounting a UNT To mount the UNT in the EWCIO  use the following procedure              1  Position the terminals of             toward the low voltage wiring    trough located on the left side of the enclosure  see Figure 6      2  Align the three mounting holes in the base of the controller with the  holes in the backbone of the enclosure  On the side with  four mounting holes  use the two outside holes for mounting in the  EWC     3  Secure the controller with three No  8 x 1 in  screws  For best results   use a plastite type thread  A thread forming or sheet metal type thread  may also be used     UNT Controller   Unitary Controller  UNT  15    Power Line  Wiring  Transient Noise  Precautions    Surge Levels    The standard UNT  when powered by any typical separate isolation  transformer or stepdown transformer  operates reliably in an electrical  environment defined as Location Category A by the IEEE 587 Standard   that is  when installed more than 30 feet from electrical distribution  panels or major bus and feeder systems in industrial p
42. ect a   10 VDC input to AI 4  set SW1 4 to Off and SW2 4 to On     Table 10  Analog Input DIP Switch Settings   Point Input  2 VDC Input  10 VDC Input    Switch       SW1   SW2   swi   SW2   swi   SW2         ____              or                   ov     uz   ow            or   or                           ow   or   om   or   or  on  ma   ow   or   om   o   or  on  ms   ow   or   om          or  on  Lue   ow   or   om   or          on       Four binary inputs on the controller are located in the center of the  terminal strip     The binary inputs on the UNT110 111  120 121  and 140 141 series  controllers are inactive when open or connected to UNT common  When a  binary device closes to complete a binary circuit  the binary input provides  the 24 VAC which  in turn  activates the input  Binary inputs have a  threshold between 5 VAC and 18 VAC  BI 4 may be used as an  accumulator input for frequencies less than 2 Hz     Binary outputs are triacs on the controller hardware  The controller has  either six or eight binary outputs  These outputs switch 24 VAC to the  output     For the UNT110 111  UNT120 121  and UNT140 141 series controllers   use the terminal labeled TRIACS when using a separate load transformer   Remove the high side low side triac jumper on the UNT110 111   UNT120 121  and UNT140 141 for this application  see Figure 8   For  important power and load specifications  see Table 5     The terminal labeled TRIACS on the UNT110 111 and UNT120 121  series controllers
43. ed by the  same transformer                                                                                         Grounding and  Isolation     UNT110 111        2024              MH    120 121                      ET ower           140 141 La Transformer    s       Nee 8 A    2                N i     15VDC OF  Q 8      x  al  To zay 7801         Load  7    BO2           lt        Triac               Contactor                    isoxfmr2  Triac Jumper to Note  UNT110 is shown in illustration   24 VAC only Diagram is for all UNT models     Figure 7  Transformer Wiring Diagram for UNT110 111   UNT120 121  and UNT140 141 Series Controllers    You may connect the UNT power transformer secondary directly to earth  ground  If you elect to do so  the grounded side must connect to the  common power input terminal of the controller     A CAUTION  You may have a maximum of one single earth ground  connection  which must be at the transformer  secondary common  whether one or multiple  controllers are powered by the same transformer     When grounding one side of the transformer  secondary  the grounded side must connect to the  common power input terminal     Connecting the grounded side of the transformer to  the 24 VAC power input terminal will damage a  CBLPRO 1  0  or laptop           22 UNT Controller   Unitary Controller  UNT     Power 24 VAC to 24 VAC isolation transformers for UNT110 111     Transformer UNT120 121  and UNT140 141 series controllers are not mandatory   Isolatio
44. ely  isolated circuit        Line SHE      Voltage  lt     gt  24VAC               7  100k mae  E  189K mn    1 4  oa       lt           transfmt    Figure 36  Testing the Transformer    Determine the polarity of the transformer s leads by using a DVM  referenced to earth ground without the 100k ohm resistor  see  Figure 36   Connect the transformer s secondary lead with the higher  voltage potential to the 24 VAC terminal on the UNT  Connect the  transformer s secondary lead with the lower potential to the 24 VAC  common terminal on the UNT     64 UNT Controller   Unitary Controller  UNT     Load Isolation    UNTs without an  Earth Ground  Connection    If the field wires are not yet connected  the Field Device Wiring  Isolation   UNTs without an Earth Ground Connection section was  skipped   disconnect one 24 VAC wire and terminate the field wires   Reconnect the 24 VAC wire     e Connect the leads of the DVM in parallel with the 100k ohm resistor  from the DC power supply   15 VDC  output terminal of the UNT to  earth ground  see Figure 37   This tests whether the field devices  the  UNT  and the transformer    assembly    are properly isolated     If you read 5 VDC VAC or greater indicates the circuit is  improperly isolated  Follow these steps to correct this     Note  Binary outputs are often the cause of ground loops  therefore  we  recommend that you test the binary outputs of the UNT before  testing other points     1     Remove all the field wires and N2 Bus wires f
45. eries  controllers are different from the UNTxxx 0 series  The REF   N2   and N2  terminations are arranged in different order  see  Figure 9                           UNTxxx 0 UNTxxx 1    compare    Figure 9  N2 Terminal Connector Comparison    UNT Controller   Unitary Controller  UNT  25                                                                                                                     T        2 218                m    LIg                5     E  0207 WOOV         lt      a  2 07 WOOV  ome                  gr              o  908           Bm            808            5          gu NONNO            m               NOWINOO  Ho       NOWNOO 02 98                          so 5        groa nomos        yA p 908              S           5         608 sov  Osoa               lt             gt      2504  TR        2508            208 OVArE  8         ofa 5           ey a          m 09  2                        CN  bo    2   CJ 334           gt         pote EN  _  r3 snaz  Z 8   8     woo    o                           snaz  I OVArZ  t A        WOO  ER Ecm   OVATE 718 OWA       54        2           EE             obi 3 88 vig                    2               S Sia      2              T  amp  0 m      OVA                                                                           OQAS           91   WOlV         5         WO IV    o   2  E   lt          lt         lt        21    ANALOG INPUTS       lt         o   lt   ANALOG INPUTS                WO IV             
46. hm   the circuit may be properly isolated   It will not be  isolated if there are earth grounds that exist at higher voltages     A value of infinite ohms indicates a completely isolated circuit at  approximately zero volts  Connect this wire to the appropriate UNT  terminal and check the next wire     Field Device    IN OUT    IN OUT COM          or LED Test Circuit  Preferred Method    ow     0                   10      470                        5 1 4 watt SX TP    isocirct    Figure 35  Testing for an Isolated Circuit    UNT Controller   Unitary Controller  UNT  63    Power  Transformer  Isolation     UNTs without an  Earth Ground  Connection    This section will assist you in determining if the supply transformer is  properly isolated     Before connecting the transformer to the UNT  connect the input  power to the primary leads of the 24 VAC transformer     Measure the voltage of each secondary transformer lead to earth  ground with the DVM in parallel with a 100k ohm 1 4 watt resistor   see Figure 36  if using a double banana plug  insert the plug into the  DVM      If you read 5 VAC VDC or greater  the transformer is earth  grounded  You need an isolation transformer in order to isolate the  connections from earth ground and protect system components   Wire a separate 24 VAC to 24 V AC isolation transformer  such as  the Y65G13  to the UNT     If you read less than 5 VAC VDC  the circuit is properly isolated   Usually a value less than 0 10 VAC VDC indicates a complet
47. igh Volume  Transducer 0 5 to 19 psig  relay    HE 6300 Series Wall Mount Humidity 12 30 VDC Supply  Transmitter   HE 6310 Series Duct Mount Humidity 18 30 VDC Supply  Transmitter    HE 6400 Series Metastat Various  Humidity Temperature  Transmitter  Wall Mount          6100 11   12 Series Zone Temperature Sensor Nickel  1000 ohm with  Phone Jack    TE 6300 Series Temperature Sensor Nickel  Platinum  Silicon    TE 6400 Series Metastat Zone Temperature   Resistance  Sensor Series       Table 30  UNT Dampers and Valve Actuators    VA 715x Series Valve Actuator Incremental or 0 to 10 VDC  Proportional   VA 7200 Series Valve Actuator Incremental or 0 to 10 VDC  Proportional    VA 8020 Series Valve Actuator Assemblies 1 2 in  24 VAC Triac Incremental  VA 8022 Series Valve Actuator Assemblies 1 2 in  0 to 10 VDC    VA 8050 Series Valve Actuator Assemblies 1 2 in   24 VAC Triac Incremental  3 4 in   1 in   and 1 1 2 in     VA 8051 Series Valve Actuator Assemblies 1 2 in   24 VAC Triac Incremental   3 4 in   1 in   and 1 1 2 in  with Feedback    VA 8052 Series Valve Actuator Assemblies 1 2 in   0to 10 VDC  3 4 in   1 in   and 1 1 2 in     EDA 2040 Series 24 VAC Triac Incremental  M100C Series Zone Bus Addressable  M100E Series 24 VAC Triac   M100G Series 0 to 10           M9000 500 Series Valve Linkage Assembly for 0 5  through 2 in  Globe  M9100 and M9200 Direct Mount style Valve Bodies  Actuators    Direct Mount Proportional Damper    to 10 VDC  Actuator   Direct Mount Proportional
48. il current  as well as from the spark  or contact arc itself  Electromagnetic fields are also present around wires  carrying power to the ignition control  These are    noisy    wires     For more information  refer to the Power Line Wiring Transient Noise  Precautions section of this technical bulletin     UNT Controller   Unitary Controller  UNT  81    Nuisance Rooftop units experiencing nuisance resets require an application upgrade   Resets in Use HVAC PRO for Windows  Version 6 05 or greater  and the following    Rooftop Units procedure     1  2  3  4   5  6  7    Run HVAC PRO for Windows  6 05 or greater    Go to the Upload menu    Select Upgrade Controllers    Select Multiple Controllers    Highlight the rooftop controllers experiencing the nuisance resets   Select OK     Save each configuration when prompted     Note  Factory downloaded applications in all UNT controllers have been    upgraded effective December 15  1997  however  even on the new  units  if controller applications are modified  the modifications  must be performed using HVAC PRO for Windows  Version 6 05  or greater     Rooftop units with 460 VAC or greater primary voltage require  additional changes under the following conditions     If the controller Date Code is less than 9618  perform the following  procedure     a  Loosen the 24 VAC and COM screws of the input power  connector     b  Insert the terminals of a Harris V47ZA7 Transient Voltage  Suppressor into the 24 VAC and COM slots of the input p
49. inal Locations    TB1 Terminal Function       Number   UNT Connection _______    Chassis Ground   6        N2 Bus  N2        UNT Controller   Unitary Controller  UNT  47    N2 Wiring to A hardware connection between the N2 Communications Bus and the   Companion Companion PC Panel LTD is required to communicate with N2 devices   An MM CVT101 0 Communications Converter is required to network to  the PC Companion  See Figure 25 for terminal locations  Refer to the  Metasys Companion Technical Manual  FAN 628 1  for information  specific to the MM CVT101 or Companion Panel LTD     Companion PC Version      BHNSON  CONTRELS     METASYS     RS232 to N2 Bus  Converter   N2 Bus Terminal                                                                             9VDC    9 V COM  MM CVT101 0               NL To      1     N Next         P f      N2                N2 RE Device                   Figure 25  Connecting the UNT Controller to Companion    Note  For more information on installing the N2 Bus  refer to the  Application Specific Controllers Technical Manual  FAN 636 3    the Introduction tab  the ASC and N2 Bus Networking and  Troubleshooting Guide Technical Bulletin  LIT 6363003      Zone Bus   Communications   Zone Bus The Zone Bus is a 2 wire communications bus that allows a computer to  Description communicate with the UNT  to download the UNT   s database  and to    communicate with the Zone Terminals and M100 actuators  A third wire  is used for 24 VAC power to the CBLPRO 
50. ion Examples 51   e Fan Coil Applications 51  e Unit Vent Applications  53  e Packaged Rooftop Applications  55  e Heat Pump Applications 57  Downloading Commissioning 59  e Commissioning Procedures 59      Via Zone Bus 59  e Via N2 Bus 59      Indicates those sections where changes have occurred since the last printing     2 UNT Controller   Unitary Controller  UNT     Troubleshooting Page    Hardware Installation Inspection   Tools Needed for Troubleshooting   Installation Checkout   Troubleshooting the UNT Controller with HVAC PRO for Windows  Troubleshooting the N2 Bus   Zone Bus Troubleshooting   HVAC PRO for Windows    Ordering Information    Johnson Controls Code Numbers  Vendor Code Numbers    Specifications    Appendix A  Precautions for Rooftop Installations    Environmental Information   Installation Requirements   Electrical Noise in Rooftop Units  Nuisance Resets in Rooftop Units  Considerations for Gas Ignition  Considerations for Specific Rooftop Units    Appendix B  UNT100 101    What s Different About      UNT 100 101  UNT100 101 Terminal Designations  Grounding and Isolation UNT100 101  Binary Inputs   Binary Outputs      Indicates those sections where changes have occurred since the last printing     UNT Controller   Unitary Controller  UNT     61    61  61   61   67  69  70    71    71   73    77  79    79   79   81   82   84   88    91    91  91  93   94  94    3    4 UNT Controller   Unitary Controller  UNT     Description    Introduction       The Unita
51. l on the York relay board to the A2 terminal     88 UNT Controller   Unitary Controller  UNT     Table 41  York Rooftop Unit Serial Number Date Conversion    Second Digit   Month   Third Digit       UNT Controller   Unitary Controller  UNT  89    90 UNT Controller   Unitary Controller  UNT     What   s Different    About the  UNT100 101    UNT100 101    Terminal  Designations    Appendix B  UNT100 101       This section contains information specific to the discontinued  UNT100 101  To troubleshoot the UNT100 101  refer to the  Troubleshooting section of this technical bulletin     The following list contains features of the UNT100 101 which differ from  the other UNT types     pd 3  3 il 3 9        sz               a 4  4    No earth ground connections are allowed when wiring a  UNT100 101 series controller     The N2 bus is not isolated  The secondary of the 24 VAC transformer  cannot be grounded     The BIs can accept dry contacts only  not 24 VAC  They can also  accept 100 Hz as accumulator input     The BO is not jumper selectable  The triac switches to the common  side of 24 VAC only                                      AS UNT101 0                TO ZONE STAT    BINARY OUTPUTS  43 8 a  44       8 3 3 3       ANALOG INPU              BINARY              44414 COMMON        232                            15VDC   15v DC    LA  EL       AICM  24VAC                                                        B  lt    lt  2    Figure 41  UNT100 Terminal Designations    untrm100    
52. lants     IEEE 587 Location Category A power line surge noise level is specified at  6       500 A  Normal Mode Ringwave      The UNT exceeds the Category A specification by meeting these surge  levels as well     TEEE 587 style Common Mode Pulse 3 kV            587 style Normal Mode Pulse 1 5                472 style Common Mode Ringwave 1 5                472 style Normal Mode Ringwave 500 V    When the controller is installed within 9 m  30 ft  of electrical distribution  panels or major bus and feeder systems in industrial plants  you must take  further precautions to prevent unwanted binary output cycling  resetting   or other possible controller malfunctions  This electrical environment is  defined as Location Category B by the IEEE 587 Standard     You can use the following method to prevent electrical noise from  adversely affecting the controller     e Connect an MOV  Metal Oxide Varistor  across the UNT supply  transformer primary  The MOV must be rated appropriately for the  line voltage  Use the list in Table 4 to select the correct MOV sold  through your electronics parts distributor     The UNT meets the following power line surge noise standards when you  correctly apply the MOV as described     TEEE 587 Common Mode Pulse 1 5       Normal Mode Pulse 6kV  Normal Mode Ringwave 6kV            472 Common Mode Ringwave 1 5       Normal Mode Ringwave 500 V    Note  The 50 VA split bobbin transformer in the EWC15 or  101 model  UNT provides additional surge noise immu
53. lowing   Ground  Connection e field device wiring for proper isolation    e transformer for isolation and correct polarity termination        connected field devices  transformer  and UNT for proper isolation    62 UNT Controller   Unitary Controller  UNT     Field Device  Wiring Isolation    UNTs without an  Earth Ground  Connection    This section assists you in measuring field wiring which will be  terminated to the UNT  If you are confident that the field wiring has no  earth grounds  you may go to the following section  Power Transformer  Isolation   UNTs without an Earth Ground Connection  A field device that  is earth grounded may become apparent when you test the entire  controller     Before you terminate the field wires to the UNT  measure the  resistance of each wire to earth ground using an LED test circuit   preferred          DVM  For the LED test circuit  assemble the test  circuit illustrated in Figure 35  Then  connect the circuit from each  input to earth ground and then from each output to ground  For the  DVM test  connect the DVM from each input to earth ground and  then from each output to ground  see Figure 35      If the LED turns On  or you read a value less than 1 Megohm at any  input or output   the circuit is improperly isolated  Replace or repair  the wiring or the field device  or  for a binary output  add an isolation  relay  Repeat the test until the LED does not turn on     If the LED does not turn On  or you read a value greater than   1 Mego
54. lowing adequate room for installation and maintenance accessibility   Also take into consideration any existing power sources or communication  lines  The UNT must be secured to a solid wall and not to any vibrating  surface     IMPORTANT  Do not mount the UNT near high voltage or    electrically noisy devices  Refer to Appendix A   Precautions for Rooftop Installations        For a typical installation  you need the following    e HVAC PRO for Windows software  current release  e IBM   PC compatible laptop computer   e  Microsoft amp  Windows    3 xx      95     e AS CBLPRO 2  for Zone Bus downloading  uploading  and  commissioning  or MM CVT101 0  for N2 downloading  uploading   and commissioning     e two screwdrivers  1 8 in  and 1 4 in  flat blade   e drill  e  optional  AS ZTU100 1  Zone Terminal unit     Note  The AS ZTU100 1 supports both AS UNTxxx 0 and  AS UNTXxxx 1 models  The AS ZTU 100 0 supports  AS UNTXxxx 0 models only     UNT Controller   Unitary Controller  UNT  11    Environmental    Information    Mounting the    Controller    Physical  Dimensions    The installation site of the UNT must meet the following environmental  standards     e The atmosphere must be free of explosive vapors and escaping gases     e        atmosphere must be free of exposure to corrosive chemical or salt  vapors that might damage electrical equipment     e        UNT100 101  UNT110 111  and UNT140 141 series  controllers  the temperature must be maintained between  0 and 52  C  32
55. n  Load Isolation UNT110 111  UNT120 121  and UNT140 141 series controllers do not    require an isolation relay  However  you must connect the jumper wire  from the triac terminal to 24 VAC if the contact or coil loads are grounded   via the single earth ground connection at the transformer secondary  common  see Figure 7   In this case  all loads are configured for    high side  switching     see Figure 13   For the UNT140 141  you must move the  jumper block to the appropriate position rather than use a jumper wire           Grounding and                                                                                  P   Optional    120 24    Isolation 2   Earth Ground    UNT110 111  UNT S   v         12     Power e        UNT120 121  Transformer v UNT COMMON Only     and UNT140 141 M   zd  with Separate  Load      Transformer M    11     120 24        L  L2 Bowel       Transformer    a      3  To  Load    Contactor                      isoxfmr  Shared Triac Node Note  UNT110 is shown in illustration    Discard small wire jumper   Diagram is for all UNT models     Figure 8  Transformer Wiring Diagram for UNT110 111   UNT120 121  and UNT140 141 Series Controllers with a  Separate Load Transformer    A CAUTION  Equipment damage hazard  When separate  transformers are used  it is very important to remove    the jumper that otherwise connects the triacs terminal  to 24 VAC  high side  or common  low side   This  prevents possible controller damage        UNT Controller   Unit
56. n open air environment must be limited to a  maximum of 75 VA           Tables 5 and 6 will assist you in determining the total 24 VAC power  draw of your system     Table 5  UNT Power and Load Specifications    UNT with Sensors Transmitters 10 VA  400 mA   25 VA for UNT120 121  due to heater     BO Load  Relay  Contactor  Solenoid  Incremental Actuator     Refer to specific product  Maximum allowable load for any individual binary   documentation   output  triac  is 19 VA    800 mA at 24 VAC      Minimum required load for each binary output   triac  used is 1 2 VA  50 mA at 24 VAC      Relay loads less than 50 mA may cause triac relay  chattering  If necessary  use a 1k ohm  2 watt    resistor across the relay coil     Triac BOs cannot drive loads which use DC  currents  such as a device which has a full wave  rectifier  Triacs can drive only AC resistive or  inductive loads  i e   AC relays  contactors  and  actuator motors  If the driving of a DC device is  required  a pilot relay must be used to isolate the  triac     AO Load See Table 6   Actuator    Maximum allowable load for each AO is 10 mA    10 VDC with a minimum load resistance of  1 000 ohms     Zone Terminal or CBLPRO 1 2 VA  50 mA       Actuator VA requirements found in Table 6      With total controller power limited as described previously        20 UNT Controller   Unitary Controller  UNT     Wiring  Precautions    Table 6  Actuator VA Requirements    VA Requirements      Actuator                   Spring Ret
57. nity     For more information  refer to Appendix A  Precautions for Rooftop  Installations in this technical bulletin     16 UNT Controller   Unitary Controller  UNT     Table 4  MOV Selection Table  Power Transformer Primary Voltage    S  120 VAC 208 to 240 VAC 277 VAC 347 VAC    Minimum 130 to 135 VRMS 250 to 280 VRMS 300 to 320 VRMS 385 VRMS  Continuous Only 250V types listed   Voltage Rating   Minimum Energy pu Joules 55 Joules 80 Joules per   Joules  Rating    Minimum Peak 4 000 NN 4 000 Amperes 4 000 Amperes 4 000       Current    8 x 20 micro   second pulse     V130LA10A V250LA20A None None  V130LA20A  V250LA40A   V130LA20B  V250LA40B    V130K14 V250K14 V300K14 V385K14  LEN NN NEN NN NI  0632170 131    15    D6321Z0V251RA90   D6321Z2OV301RA105    D6521ZOV131RA20    D6521Z0V251RA130    D6521ZOV301RA150   D692172OV131RA09   D6921Z0V251RA72 0692170 301    80   VSAC20DK201U  VSAC20DK391U  VSAC20DK471U  VSAC20DK621U   TNR15G211KM TNR15G391KM TNR15G471K    TNR23G201KM  TNR23G391JM  TNR23G471K   TNR23G211KM  TNR23G391KM     Oneida    CKE    OZ130LA10A OZ250LA20A 07211471 None  OZ130LA20A  OZ250LA40A   OZ130LA20B  OZ250LA40B   07211221  0216NR14 3  0216NR20 4     Panasonic ERZ C14DK201U ERZ C14DK391U ERZ C14DK471U ERZ C14DK621U                      ps  23225955135   202250552516   232250550016  22250553816    S14K130 S14K250 S14K300 S14K385  pem eem       0216NR14 3 0390NR14 3 0620NR14 3 0620NR14 3  0216NR20 4  0390NR20 4  0620NR20 4  0620NR20 4     0216NR20DB  0416NR14 3  041
58. nsor  CBLPRO or ZT and CBLPRO or ZT to  eae     Sensor     Al 2 Warmer Cooler  24 VAC  or Cooling Setpoint   3 Al 1 Temperature 3 24 VAC ZnBs  Sensor Common  Al 1 Sensor 4 Not Used  Ene            Al 2 3 Common       24 VAC   ZnBs Not Used  Common    Notes  When using the Metastat  do not move the hardware point  assignments in HVAC PRO for Windows     For information on cables  refer to the Vendor Code Numbers  section in this technical bulletin     42 UNT Controller   Unitary Controller  UNT     Sharing a Sensor     You may use one sensor as a master input to multiple         instead of  mounting and wiring separate Zone Sensors for each controller  This  application is especially beneficial when you have a mechanical system  that uses more than one terminal unit to serve the same area  for example   a classroom with two unit ventilators  or an open office space with  multiple water source heat pumps     Figure 22 shows the wiring and analog input switch settings for   two controllers using one Zone Sensor  When sharing a sensor  both  controllers must be set to the same temperature sensor type  the default is  resistive nickel  on the HVAC PRO for Windows Analog Input Modify  screen  To ensure the noise immunity of the UNTS  pull the N2 Bus wiring  with the sensor wiring between controllers that share the same sensor     Set the HVAC PRO for Windows software for both controllers for the temperature sensor used           Set for Set for  2 VDC and 2 VDC and  Voltage Tempera
59. ollers must be  between  40 and 52  C   40 and 125  F      Use the UNT120 121 series controllers in extremely cold environments or  where some condensation is possible  The UNT120 121 series controllers  have built in heaters and conformally coated circuit assemblies  You must  mount the UNT120 121 series controller within a relatively small  enclosure  such as a BZ 1000 7  or within the confined area of the rooftop  unit   s wiring cabinet for optimal heater efficiency     Instructions for installing a UNT in a rooftop unit are detailed in this  section     1  Mount the UNT inside the rooftop unit or some other enclosure to  protect it from outside elements  such as rain  snow  etc     2  Install a separate transformer  not the rooftop unit s power  transformer  to provide 24 VAC power to the UNT  You may use a  line voltage to 24 VAC transformer or a 24 VAC to 24 VAC isolation  transformer  We recommend using one of the following transformer  types    Note  Unless the UNT has a separate transformer  the UNT is prone  to resetting due to electrical noise within the rooftop unit     UNT Controller   Unitary Controller  UNT  79    Table 39  Recommended Transformers    Transformer Type   Power   Description          Johnson Controls AS XFR050 0 120 VAC to 24 VAC   insulated windings  high  noise immunity  resettable  breaker        3  Drive rooftop unit loads via pilot relays  see Figure 40  if any of  the following conditions exists     e The rooftop unit contains any contacto
60. one Bus  clear  then try again     UNT Controller   Unitary Controller  UNT  69    Notes  For more N2 Bus troubleshooting information  refer to the  Application Specific Controllers Technical Manual  FAN 636 3    the Introduction tab  the ASC and N2 Bus Networking and  Troubleshooting Guide Technical Bulletin  LIT 6363003      For NCM troubleshooting information  refer to your NCM  technical bulletin     Zone Bus There are some errors that may occur while using the HVAC PRO for  Troubleshooting  Windows commissioning tool with the UNTs over the Zone Bus  The  HVAC PRO for cause of the error is often a loose or improper connection between the  Windows CBLPRO  AS CBLPRO   laptop PC  and the controller  A defective COM    port on the laptop  or a defective controller could also be at fault     Note  It takes ten seconds for a UNT to reset and resume communication  after being downloaded     An effective troubleshooting technique is to use a CBLCON and observe  its LEDs  which will indicate the problem  see Table 17 for a description  of LEDs and their meanings   You may also try exchanging the  component that you believe is defective with a working component of the  same type     A noisy wire adjacent to the Zone Bus can also cause communication  errors  Noise can be periodically induced into the Zone Bus  thereby  causing sporadic communication failures between the laptop and the UNT   Most often  noisy lines cause intermittent disruption  not total loss of  communication     F
61. ontrollers are inactive when  open or    5 VDC logical high is supplied  They are active when a contact  closure to UNT common or a logical low is applied  BI 4 may be used as  an accumulator input for frequencies less than 100 Hz     Each UNT100 series controller   s binary outputs must be connected  between the BO terminal and 24 VAC terminal since it is low side  switching     94 UNT Controller   Unitary Controller  UNT     Notes    UNT Controller   Unitary Controller  UNT  95    JeHNSON  CONTROLS    Controls Group   507 E  Michigan Street  P O  Box 423  Milwaukee  WI 53201    96 UNT Controller   Unitary Controller  UNT     Notes    www johnsoncontrols com   FAN 636 3   Application Specific Controllers Technical Manual  Printed in U S A     
62. or more information on HV AC PRO for Windows  refer to the  HVAC PRO for Windows User s Manual  FAN 637 5      70 UNT Controller   Unitary Controller  UNT     Johnson  Controls Code  Numbers    Controllers    Ordering Information       Tables 28   31 list code numbers and descriptions for the UNTs and  accessory equipment     Table 28  UNT Controllers and Accessory Equipment    AS UNT110 1 UNT with eight binary outputs  N2 Isolation   and triac  high or low side selectable  AS UNT111 1 UNT with six binary outputs  two analog    outputs  N2 Isolation  and triac  high or low  side selectable    AS UNT120 1 UNT110 controller with heater  for low  temperature use    AS UNT121 1 UNT111 controller with heater  for low  temperature use    AS UNT140  UNT110 controller with screw terminals for  field terminations and spare 6 pin Zone Bus  phone jack    AS UNT141 1 UNT111 controller with screw terminals for  field terminations and spare 6 pin Zone Bus  phone jack    AS UNT110 101 UNT110 mounted in EN EWC10 0  enclosure with 50 VA transformer  AS UNT111 101 UNT111 mounted in EN EWC10 0  enclosure with 50 VA transformer  AS UNT140 101 UNT140 mounted in EN EWC10 0  enclosure with 50 VA transformer  AS UNT141 101 UNT141 mounted in EN EWC10 0  enclosure with 50 VA transformer       UNT Controller   Unitary Controller  UNT  71    Sensors   Transmitters    Dampers and  Valve Actuators       Table 29  UNT Sensors and Transmitters    Code Number   EP 8000 Series Electro Pneumatic 0 to 10 VDC  H
63. ou may be able to determine the cause of the problem  by asking yourself the following questions     e Are the    2 Bus wires securely terminated to each UNT   e Is the    2 polarity correct   e  5 the UNT powered and ready to respond     e Have you cycled power         UNT after changing its address    Refer to Installing the N2 Bus in this technical bulletin      e Are the UNTs configured properly with the correct number of points     A WARNING  Electrical shock hazard  When troubleshooting     always measure the REF to earth ground voltage  with the DMM  If line voltage is measured  have a  qualified electrician locate the fault        Table 27  Troubleshooting the N2 Bus    Symptom       PossibleCause  Action _______         Bus is Offline EOL jumpers and or W3 Install EOL jumpers and W3  jumper on MM CVT101 or jumper properly   Companion Panel LTD are not  installed     MM CVT101 is not plugged Plug MM CVT101 into PC or   into PC or 9 VDC source  into    9 VDC source    N2 Bus polarity is incorrect  Rewire N2 Bus wires for  proper polarity     UNT Does Not Come Two or more UNTs have the Change each duplicate UNT  Online same address  address to a unique number     The address of the UNT was Cycle power on the UNT   changed without its power  being cycled afterward     The 10 second delay after Wait until the delay expires   downloading the UNT has not   yet expired  HVAC PRO      Revision 1 0 or earlier      Someone is commissioning Wait until the Zone Bus is  over the Z
64. ower  connector     c  Tighten the 24 VAC and COM screws of the input power  connector     If a separate transformer is used to supply the binary output  voltage  install a Metal Oxide Varistor  MOV  according to the  following procedure  see Figure 38      a  Order an AS MOVKIT O as needed  Each kit contains  12 Metal Oxide Varistor  MOV  assemblies     b  Remove the field wire that currently connects to the triacs terminal     c  Attach the field wire to the male terminal of the MOV assembly     82 UNT Controller   Unitary Controller  UNT     d  Attach the female terminal with two wires to the TRIACS terminal     e  Attach the female terminal with one wire to the common terminal  immediately adjacent to the TRIACS terminal     Note  The MOV assembly will be factory installed on UNT220 1  controllers mounted in York rooftop units beginning  March 16  1998     The MOV assembly will not be factory installed on  UNT120 1 controllers     e   For units meeting both conditions  install transient voltage  protectors in both locations as described above     Attach  field wire  here         Common  Triacs    workaround    Figure 38  Installation of MOV    UNT Controller   Unitary Controller  UNT  83    Considerations    for Gas Ignition    Rooftop Units containing Gas Ignition Control  see Figure 39 or  Figure 40      IMPORTANT  If the gas valve or ignition controller has a full wave  bridge rectifier  you must install a relay between the  BO and the gas valve and ignition controller
65. r fan dropout or cycling that  appears as abnormal operation to the customer  Lennox has authorized  bypassing K25 blower control when you use Johnson Controls UNTs     2  York   Rooftop Units  UNT120 1 and UNT220 1 controllers  when installed in rooftop units   may experience nuisance resets  This is evidenced by numerous  unexplained offline conditions with durations of less than one minute   To alleviate this situation in York rooftop units  bypass or disable the  supply fan relay according to the following procedure     Note  These modifications apply only to those units described below   Units built after the dates indicated have already been modified  by York and do not require this change     The date of manufacture of York rooftop units can be  determined from the second and third digits of the serial  number  as shown in Table 41     e On 3to 6 ton units built before February 17  1997  the       relay must be disabled by disconnecting the wire that connects the  time delay relay contacts to the relay board  This is typically the  234 BLUE wire     e On 3 to 6 ton units built between February 17  1997 and  May 30  1997  York implemented a different relay interface  board  On this new relay board the K5 relay must be bypassed by  moving the wire currently connected to the G terminal on the  York relay board to the A2 terminal     e On7 to 25 ton units built before February 28  1997  the K5  relay must be bypassed by moving the wire currently connected  to the G termina
66. r relay coils that might be  energized by some means other than directly by the UNT   s  binary outputs  A common example of this is a time delay relay  contact closure in a BO circuit     e      individual BO load exceeds 800 mA     e All loads together will cause the UNT to require more than  40 VA of 24 VAC power when mounted in an enclosure  or more  than 75 VA when mounted in a well vented open area     e Voltages other than 24 VAC need to be switched     Note  Install pilot relays for isolation between the UNT and the  rooftop unit contactors relays     4  You may drive rooftop unit contactor relay loads directly  see  Figure 39  if all of the following conditions exist     e Under normal operation  the UNT binary outputs directly drive  all contactor relay coils within the rooftop unit     e Individual BO loads exceed 50 mA   Required to keep the  triac on      e Individual BO loads      not exceed 800 mA     e The UNT and all its loads together draw less than 40 VA of  24 VAC power when mounted in an enclosure  or less than  75 VA when mounted in a well vented open area     e  Triac load voltage is 24 VAC  5      Note  Connect the UNT binary outputs  triacs  to the rooftop unit  terminal strip     80 UNT Controller   Unitary Controller  UNT     Electrical Noise    in Rooftop Units    IMPORTANT  When using pilot relays to ensure electrical  isolation between the binary outputs and their  loads  pilot relays must be used on all BOs  This  ensures that electrical noise c
67. reated by contact closure  or opening of a pilot relay cannot travel back through  the BO wiring  or any other BO  and adversely affect  the UNT   s other binary outputs that are not relay  isolated  A pilot relay to the economizer is an  exception to this because it drives a circuit  not a  relay contactor load     Ensure that relays have adequate isolation  between coil and contacts     Many relays on the market do not provide suitable  isolation  Capacitance between the coil and contacts  must be less than 3 pico farads  As manufacturers do  not specify this parameter  remember that smaller  relays generally have more capacitance   RLY 100 and  RLY050 relays provide suitable isolation      Ensure that relays provide a minimum of 50 mA  load to the UNT binary output    If the selected relays draw less than 50 mA  you must  add appropriately rated resistors in parallel with the  relay coil to avoid possible relay chattering  We  recommend using 1k ohm  2 watt resistors        Rooftop air handling units may be very    noisy    from an electrical  standpoint  This is due to contacts switching inductive loads and electrical  spark ignition devices  You must take precautions to prevent electrical  noise from causing false BO triggering  resetting of UNTs  or interference  with N2 communication     There is wide variation in relays  contactors  and gas ignition control  devices  Some are much noisier than others  Electromagnetic fields can  radiate from wires carrying spark or co
68. res or less  However  if  you use one low voltage power trunk to power multiple controllers   follow these precautions     e Ensure that polarity is maintained at each 24 VAC connection     e Enclose 24 VAC power trunks with greater than 4 amperes  100 VA   in conduit as required by the National Electric Code  NEC      e Do not share a UNT   s power transformer with a Companion Panel       any other device with a full wave rectifier in its power supply   UNTs  use    half wave    rectification  Half wave circuitry and full wave  circuitry must not share the same transformer          Consider all the actual loads as well as the basic load of the controller  when determining the system load     Notes  Some local electrical codes require that the secondary common of  the stepdown transformer be connected to earth ground  typically  on units which are powered by greater than 150 VAC      The M100 draws 20 VA if using common power for the controller  and the M100 actuator  It is recommended that each M100 use its  own 24 VAC isolation transformer     UNT Controller   Unitary Controller  UNT  19    IMPORTANT  Any individual binary output  triac  can drive up to  800 mA when you limit the total 24 VAC power  draw  You must limit the power draw of a controller  and its load to avoid heat dissipation problems     The total 24 VAC power draw of a UNT installed in  an ENC100 or similar size box must be limited to a  maximum of 40 VA     The total 24 VAC power draw of a UNT mounted in  a
69. rials           Valve Actuator VA 8052 Valve Actuator Assembly  R1 Lighting Relay GE RR7       52 UNT Controller   Unitary Controller  UNT     Unit Vent Table 20 lists the selections made through HVAC PRO for Windows for  Applications the example in Figure 28     Table 20  Unit Vent Parameters and Configuration Selections    Unoccupied Override of Heating Valve  Cooling Type  Lighting Integration                                                                                     Return Air     ae    WY Discharge Air               NS  Outdoor Air              L 4   ER                          LA        gt  1                                             Figure 28  Unit Vent Mechanical Flow Diagram    UNT Controller   Unitary Controller  UNT  53    A    240 24 VAC      TE1  240 VAC Power 24 VAC RM T          Transformer RM SP   m       7     7                       BINARY OUTPUTS    Prd tl  LII    ANALOG INPUTS    BINARY IN    aN                                                                                 Triac to  24 VAC  BOs High  Side  Switched                                    PNEUM     uvwire       Figure 29  Unit Vent Wiring Example           Table 21  Unit Vent Bill of Materials    TES Discharge Air Sensor TE 6300 Series  EP1 Electric to Pneumatic Interface EP 8000 Series  DA1 Zone Damper Actuator M100CGA 2       54 UNT Controller   Unitary Controller  UNT     Packaged  Rooftop  Applications    Table 22 lists the selections made through HVAC PRO for Windows for  the ex
70. ries actuator     Figure 31  Packaged Rooftop Wiring Example with Separate Transformers  for Controller and Loads    56 UNT Controller   Unitary Controller  UNT     Bill of Materials    Heat Pump    Applications    Table 23  Packaged Rooftop Bill of Materials    TE3 Outdoor Air Sensor TE 6300 Series  S1 Air Flow Switch P32 Series  DA1 Damper Actuator M110CGA 2    For more information on rooftop installations  refer to Appendix A   Precautions for Rooftop Installations in this technical bulletin        Table 24 lists the selections made through HVAC PRO for Windows for  the example in Figure 32     Table 24  Heat Pump Parameters and Configuration Selections    Supplemental Heat Two Stages  Lighting Integration          A       Discharge Air      gt             1    Return Air      d                     TO 0 4 I                                lt  TE                hpmech          Figure 32  Heat Pump Mechanical Flow Diagram    UNT Controller   Unitary Controller  UNT  57       BINARY OUTPUTS    4 1111      L  EEEE mmo Wri  d    ______                  PUTS BINARY IN                                                                         Triac  to  R  Equipment 24 VAC 24 VAC  B  Equipment Ground   G  Indoor Blower  W  Reversing Valve  Y  Compressor                               R    GW Y      W2  W1  Heat Stage 1  R1  Auxi Aux2  W2  Heat Stage 2 Elect  Heat    Unit Terminal Strip                   120 24 VAC       120 VAC 24           hpwire       X    Figure 33  Heat Pump and E
71. rom the UNT   but leave the transformer wires attached     With the DVM still connected  reconnect each set of field wires  one at a time until you read 5 VDC VAC or greater  At this  point  you have discovered one cause of the ground loop   Correct the problem  If you check all the field wires and you  still read greater than 5 VDC VAC  the transformer secondary  is earth grounded  In this case  wire a 24 VAC to 24 VAC  isolation transformer to the UNT and measure again  If the  value is still 5 VDC VAC or greater  replace the UNT     Continue to reconnect each set of field wires until all ground  loops are found and corrected  You   ll know that all grounds are  corrected when you read less than 5 VDC VAC on the DVM     If you read less than 5 VDC VAC  the circuit is properly isolated   A value of less than 0 10 VDC VAC indicates a completely isolated  circuit     UNT Controller   Unitary Controller  UNT  65    UNT       24 VAC  AWC  Line     Voltage  lt     24        gt     24        COM  Field Wiring      P  100k ohm D DVM    5 VDC VAC   OK  Isolated   1 4 watt  gt  DVM  gt  5 VDC VAC   Earth Grounded  1   AICOM  BICOM  ZBUS COM  AOCOM  BOCOM grdloop    Figure 37  Testing for Ground Loops    e Connect the DVM across the 24 VAC and the 24 VAC common  terminal of the UNT  Read the voltage with all typical loads  energized     A reading of 24 VAC is required when the line voltage is nominal     If you read a value less than 20 VAC  make sure the primary voltage  matches the 
72. ry Controller  UNT  is an electronic device for digital control of  packaged air handling units  unit ventilators  fan coils  heat pumps  and  other terminal units serving a single zone or room  It also can be  configured as a generic Input Output  I O  device for basic point  monitoring applications when used within a Metasys   Network     You can easily configure point inputs and outputs  and software features to  control a wide variety of Heating  Ventilation  and Air Conditioning   HVAC  equipment applications  The UNT may be used as a standalone  controller or connected to the Metasys Network through a Network  Control Module  NCM  or Companion M     When connected to the Metasys Network  the UNT provides all point  control information to the rest of the network  The devices communicate  through an N2 Bus  For a smaller facility  the UNT can function as a  standalone controller  Figure 1 illustrates the UNT     JgHNSON               5     METASYS                                                                             Figure 1  Unitary Controller  UNT     You may use the UNT for unit ventilator  rooftop  heat pump  or fan coil  applications  or as a generic I O multiplexer and I O sideloop control   Each has a different sequence of operation  all of which are covered in the  HVAC PRO for Windows User   s Manual  FAN 637 5      The Unitary Controller is available in different hardware sets to suit  different environmental and application needs  Table 1 lists the common
73. ser   s Manual  FAN 634  describes the general procedures for  entering and modifying data     Table 3  Blank UNT Object Attributes    Attribute __________ Description   Entry Values         Object Name Identifies the object 1 to 8 alphanumeric   i e   UNT1   The object characters  name cannot be duplicated    in the system     Expanded ID Further identifies the object 0 to 24 alphanumeric   i e   Garage Level Heater  characters   optional        9  On the Item menu  select Save to save the new UNT object and add  the object to the NCM database     10  Upload the NCM to make an archive copy of the new object  Refer to  the Operator Workstation User   s Manual  FAN 634   Uploading from  the NCM     To define a UNT control device in Companion  refer to the Metasys  Companion Technical Manual  FAN 628 1      UNT Controller   Unitary Controller  UNT  9    10 UNT Controller   Unitary Controller  UNT     Design  Considerations    Tools Needed    Installation Procedures       Instructions for installing the UNT and its accessories are detailed in this  section  The number and types of components  sensors and actuators  used  with the UNT will vary according to application  Analyze the proposed  installation for logical locations to place these devices and draw an  inventory based on that study  Information on available accessory devices  is in the Ordering Information section of this technical bulletin     Decide how close the UNT can be to the air handling equipment while still  al
74. tage electrical compartment of the mechanical unit being  controlled  The BZ 1000 7 enclosure is the common package for a  UNT120 121 mounted in the air stream or in the mixed air chamber of a  mechanical unit     The BZ 1000 7 enclosure is the recommended size for optimum  performance of the UNT120 121  Venting the BZ 1000 enclosure   possibly removing unused knockouts   using the AS ENC100 0 or  EN EWC 10 0  or using a larger enclosure is recommended for  environments that regularly exceed 32  C  95  F      The UNT120 121 series controller has the following dimensions   e 165 x 163 x 56 mm  6 5 x 6 4 x 2 2 in   H x W x D without enclosure       259 x 249 x 76 mm  10 2 x 9 8 x 3 in   Hx W x D with the  BZ 1000 7 enclosure    e 229 x 406 x 191 mm  9 0 x 16 0 x 7 5 in   Hx W x D with the  EWC10 or UNTxxx 101 version    Before installation  position the controller and enclosure on the proposed  mounting surface to ensure that the calculated mounting area is correct   Precise distance measurements can be made between controller terminals  and sensor actuator mounting points on the air handling equipment if the  equipment is in place  Confirm electrical power source and conduit  requirements at this time     Note  You can install    UNT100 101  UNT110 111  or UNT140 141  series controller in a control panel  or in an AS ENC100 0 or  EN EWC10 0 enclosure  You must enclose      UNT120 121  series controller in a BZ 1000 7 enclosure or another enclosure of  comparable dimensions    
75. tion  which must be at the transformer  secondary common  whether one or multiple  controllers are powered by the same transformer        Table 26 indicates symptoms and corrections for possible controller  malfunctions  We recommend the use of HVAC PRO for Windows  Commissioning mode during all troubleshooting procedures     Note  While in the commissioning program  you are actively viewing the  controller   s inputs and outputs  The screens will automatically  refresh the data values when the controller senses a change in  value     UNT Controller   Unitary Controller  UNT  67    Table 26  Troubleshooting the UNT with HVAC PRO for Windows    Indoor Fan Does Not  Run    M100C Zone Bus  Economizer Actuator  Does Not Open to  Minimum Position    Heating or Cooling Will  Not Turn On  Automatically    ZT Display Contains  Dots    Binary Output Will Not  Turn On or Chatters    68 UNT Controller   Unitary Controller  UNT     Unit not in Occupied  mode     Unit does not need  heating or cooling     Fan off due to air flow  loss     Indoor fan not proven     Actuator or linkage    Wiring problem    Zone Sensor not  connected     Zone temperature not  above below setpoint     Heating or cooling  lockout from outdoor  temperature     Delay timers present     Configuration mismatch  between the controller  and the ZT  a ZTU100 0  is used with a UNTxxx 1  controller      TRIAC Jumper is not set  correctly     Load is not drawing  50 mA  minimum load  for triac      Use the Commissioning
76. transformer   s voltage rating  For details  refer to the  Power Source and Loads section of this technical bulletin and  recalculate the VA requirements for the UNT     You have completed the UNT isolation tests  If you plan to connect this  UNT to the N2 Bus for communication to other devices  refer to the  Application Specific Controllers Technical Manual  FAN 636 3   the  Introduction tab  the ASC and N2 Bus Networking and Troubleshooting  Guide Technical Bulletin  LIT 6363003      66 UNT Controller   Unitary Controller  UNT     Grounding  UNT110 111   UNT120 121  and  UNT140 141 with  an Earth Ground  Connection    Troubleshooting    the UNT  Controller with  HVAC PRO for  Windows    An earth ground connection to the common terminal of the UNT110 111   UNT120 121  and UNT140 141 series controllers is allowed for the   24 VAC power supply and the binary output triacs  when set up for high  side switching   If this earth ground connection exists  it must be at the  transformer secondary common terminal only  There should be 0 VAC  measured from a common terminal to earth ground and over 20 VAC from  a 24 VAC terminal to earth ground  when power is applied  If no earth  ground connections were planned for the power supply and or triacs  and  you suspect that an earth ground may exist  use the procedure described  above for the UNT100 101 controller to test for the presence of a ground  loop condition     A CAUTION  You may have a maximum of one single earth ground    connec
77. ture                                                                                                                                                                                  Metastat  8 pin Connection  on Back             Sensor    Sensor                        Note  Route sensor wiring and N2 wiring together   Since the UNT Controller is a self terminating device     end of line termination for the N2 Bus is not required  cd    Figure 22  Example of Sharing a Sensor Among UNT Controllers    A CAUTION  Multiple controllers sharing a sensor may only have  one single earth ground connection among them     Even if separate transformers are used  only one may  be physically tied to earth ground and that connection  must be at the transformer secondary common        UNT Controller   Unitary Controller  UNT  43    Note  If the master Zone Sensor uses the Zone Bus connection  only the  master controller can be loaded and commissioned from the sensor  connection  The AI offset feature in HVAC PRO for Windows will  have to adjust 1  F at the slave AIs to compensate for each  additional controller sharing a sensor     44 UNT Controller   Unitary Controller  UNT     N2 Bus  Overview  Wiring the  Controller to an  NCU    N2 Bus  Characteristics    Networking the Controller       If you are already familiar with the N2 Bus  go to Installing the N2 Bus     A hardware connection between the N2 Communications Bus and the  Network Control Module  NCM  of the Network Control Unit  NCU 
78. urn    Spring Return    Non spring Return  Voltage  0 to 10 VDC     Voltage  0 to 10 VDC     Follow these precautions when wiring     Make all wiring connections in accordance with the NEC as well as in  accordance with local regulations     Locate equipment and route the wiring so that signal wiring is a  twisted pair  and separated from power wiring as much as possible     Make all wiring connections to the UNT using only copper  conductors     Daisy chain the N2  The use of  Y  or          bus topologies without a  repeater installed in the  T  may cause a loss of communications   Do not use wire smaller than 22 AWG     Do not run N2 Bus  Zone Bus  Analog Input  AD  Binary Input  BI    Analog Output  AO   or Binary Output  BO  wiring in the same  conduit or bundle as line voltage wiring  30 VAC or above   or wiring  that switches power to highly inductive loads such as contactors   coils  motors  or generators     Notes  Shielded N2 Bus wiring can be run in the same conduit or bundle    as 24 VAC power wiring     Zone Bus  AI  AO  and BI wiring can be run in the same bundle or  conduit  where convenient  If the binary output wiring is not wired  through other switches or contacts  you may also bundle it with the  other I O wiring  where convenient     UNT Controller   Unitary Controller  UNT  21    You may have either no earth ground connection  or one earth  ground connection which must be at the transformer secondary  common  whether one or multiple controllers are power
79. xternal Transformer Wiring Example    Sor Materials Table 25  Heat Pump Bill of Materials    Part Number  C1 Digital Controller AS UNT 110 1       TE1 Zone Temperature Sensor TE 6400 Series    58 UNT Controller   Unitary Controller  UNT     Commissioning    Procedures    Via Zone Bus    Via N2 Bus    Downloading Commissioning       Commissioning a UNT begins after the unit is mounted and wired  and the  control and hardware software features have been defined through   HVAC PRO for Windows  Refer to the HVAC PRO for Windows User s  Manual  FAN 637 5  for complete controller configuration and  commissioning information  A Zone Terminal or laptop PC with   HVAC PRO for Windows is recommended to perform a complete system  startup procedure  However  these accessories are not required for the  basic procedure detailed in this section     Downloading and commissioning via the Zone Bus requires using the  CBLPRO interface and a laptop or PC running the HVAC PRO for  Windows software  You can connect to the Metastat 6 pin connector or  directly at the controller  UNT140 141 models have a spare 6 pin  connector so that the connection from a Metastat or Zone Sensor would  not need to be disconnected during download commissioning   Communication rate is 1200 baud over the Zone Bus  See Figure 20     HVAC PRO for Windows  release 5 00 or higher  allows you to perform  downloading and commissioning over the N2 Bus using MM CVT101 0   Metasys OWS Release 6 0 or higher  or Companion Releas
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Welcome to DiskTracker! Introduction  golden scan 4  HVAC MOBILESALES USER MANUAL  BXN-11556-132  Illlllll?l?l?llllllllllllll  PSM3000, PSM4000, and PSM5000 Series RF and Microwave  ポイントチェッカー 取扱説明書  Kicker 2015 CompRT Subwoofer Owner's Manual  Trevi DLX 670  OPERATOR`S MANUAL MANUEL de L`UTILISATEUR MANUAL del    Copyright © All rights reserved. 
   Failed to retrieve file