Home
MODEL GT15-J61BT13 CC-Link communication unit User`s Manual
Contents
1. SD RuN The error mode has been entered ON OFF No errors A starting error has OFF not occurred A starting error has ON occurred A hardware failure has not occurred A hardware failure has occurred Extension interface relay board 24 0 94 64 2 52 27 5 1 08 Unit mm inch 5 INSTALLATION PROCEDURE The installation procedure for the CC Link communication unit is explained using the GT1575 5 1 CC Link communication unit installation 1 Power off the GOT 2 Remove two extension unit covers of the GOT 3 Attach the extend interface relay board to the extend I F 2 side on the GOT After the installation detach the connector cover from the extend interface relay board For the following GOT types the extension interface relay board is not needed GT1655 155 1 of the GOT1000 series GT27 GT25 of the GOT2000 series 4 Fit the CC Link communication unit in the GOT case Remove the connector cover 11 5 Fasten the CC Link communication unit by tightening its mounting screws 4 places with tightening torgue 0 36 to 0 48 Nem 6 Fasten the bus connection unit by tightening the board fixing screws 2 places with the tightening torque of 0 36 to 0 48 Nem 7 When installing an extension unit on the unit that has been installed remove
2. For relevant manuals refer to the PDF manuals stored in the DVD ROM for the drawing software used Compliance with the EMC and Low Voltage Directives To configure a system meeting the requirements of the EMC and Low Voltage Directives when incorporating the Mitsubishi GOT EMC and Low Voltage Directives compliant into other machinery or equipment refer to EMC AND LOW VOLTAGE DIRECTIVES of the General Description included with the GOT used The CE mark indicating compliance with the EMC and Low Voltage Directives is printed on the rating plate of the GOT Compliance with the Radio Waves Act South Korea This product complies with the Radio Waves Act South Korea Note the following when using the product in South Korea OIE SSS AS SXHIAE2I2IgA BHA LE ASME Ol SS FOSH 10599 ASA ASSE AS SAO SUC The product is for business use Class A and meets the electromagnetic compatibility requirements The seller and the user must note the above point and use the product in a place except for home A 9 Packing List The following items are included Product Quantity CC Link communication unit Mounting screw set 2 screws 2 stickers Extension interface relay board Terminating resistor 1102 1 2W brown brown brown Plate type solderless terminal set Terminating resistor 1309 1 2W brown orange brown Plate type solderless terminal set GT15 J61BT13 Solderless terrninal
3. For the details of CC Link connection refer to GOT1000 Series Connection Manual 2 SPECIFICATIONS 2 1 Performance Specifications The following is the performance specification of CC Link communication unit The general specification of the CC Link communication unit are the same as those of the GOT For the general specifications of the GOT refer to the User s Manual for the GOT used 1 Item Specifications CC Link station type Intelligent device station Number of occupied stations May be selected between 1 and 4 Ver 2 mode Maximum number of link Remote RY 8192 points Remote register RWw 2048 points Remote register RWr 2048 points points per system Ver 1 mode Remote RY 2048 points Remote register RWw 256 points Remote register RWr 256 points Number of link points per station Refer to 3 Number of link points per number of occupied stations Refer to 4 Transmission speed 156kbps 625kbps 2 5Mbps 5Mbps 10Mbps Max transmission distance Depends on the transmission speed Max number of modules connected 26 The max number of modules connected depends on the configuration of the CC Link system to be used For more details on the max number of modules connected refer to the CC Link System Master Local Module User s Manual Connection cable CC Link dedicated cable Internal current co
4. cable Master module module etc DA Blue n Apa ha eem pg veto i ji Terminal DG White id d G Terminal resistor E ee x resistor 510 CC Link CC Link FG dedicated cable dedicated 4 FG cable T When connecting the CC Link dedicated cables of the previous station and next station strip the wire sheaths off for 10mm 0 39 inch and insert the cables into the terminal block socket with every two wires in the same color together When connecting the braid shields of the CC Link dedicated cables of the previous station and the next station caulk each braid shield to the supplied solderless terminal Plate type then insert the shields into the terminal block socket Solderless terminal Plate type Braid shield 2 When connecting the terminating resistor and FG cable When connecting the terminating resistors to the GOT be sure to connect the terminating resistors with the supplied plate type solderless terminal at the position as shown below When connecting the FG cable strip the wire sheath of the FG cable 2mm off for 10mm 0 39 inch and insert it into the terminal block socket Terminating resistor with plate type solderless terminal Power supply cable com Conductor plate Tighten the terminal block wiring screws with the tightening torque of 0 5
5. to 0 6 Nem Tighten terminal block mounting screws with the tightening torque of 0 7 to 0 8 Nem The terminating resistors supplied with the master module or the CC Link com munication unit must be connected to the PLC module or GOT at both ends of the data link Connect them across DA DB Connect the shield wire of the CC Link dedicated cable to SLD of each module Since SLD is connected to FG internally always ground the FG terminal and FG1 terminal to the protective ground conductor The FG terminal of the GOT power supply and the FG terminal of the CC Link Communication unit must be connected separately When using the plate type solderless terminal be sure to insert the terminal in the horizontal direction toward the terminal block The solderless terminal may come off when it is inserted in the vertical direc tion 15 MEMO Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi machine damage or lost profits caused by faults in the Mitsubishi products damage secondary damage accident compensation caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi products and to other duties NFor safe use This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorpo
6. 7 11 928 2000 Tel 61 2 9684 7777 AM MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN NAGOYA WORKS 1 14 YADA MINAMI 5 CHOME HIGASHI KU NAGOYA JAPAN When exported from Japan this manual does not require application to the of Economy Trade and Industry for service transaction permissio Specifications subject to change without notice Printed in Japan October 2014
7. For connecting the braid shield wire Plate type Terminal block socket 1 Useit when using the Ver 1 10 compatible CC Link dedicated cable Ver 1 00 compatible CC Link dedicated cable 2 Use it when using the Ver 1 00 compatible CC Link dedicated high performance cable A 10 1 OVERVIEW This user s manual introduces the model GT15 J61BT13 CC Link communication unit hereinafter referred to as CC Link communication unit used in the Control amp Communication Link system hereinafter referred to as CC Link For attachable GOTs refer to the User s Manual for the GOT used The CC Link communication unit can be connected to the GOT which can perform monitoring as an intelligent device station number of occupied stations selectable from 1 station 4 stations in the CC Link system The PLC CPU on the Master local station of Monitoring by he CC Link system can be monitored Transient Transmission Intelligent device station Remote device Local station Master station station a 00000 CC Link dedicated cable All remote inputs outputs and remote registers assigned to the Master station by CC Link parameter setting can be monitored Monitoring by Cyclic Transmission When using the CC Link connection make the communication setting to perform communication with PLCs
8. MITSUBISHI MODEL GT15 J61BT13 CC Link communication unit User s Manual Thank you for purchasing the GOT1000 Series Prior to use please read both this manual and detailed manual thoroughly to fully understand the product MODEL GT15 J61BT13 U MODEL CODE 1D7M57 IB NA 0800351 G 1410 MEE GOTicoo eSAFETY PRECAUTIONSe Always read these instructions before using this equipment Before using this product please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly The instructions given in this manual are concerned with this product In this manual the safety instructions are ranked as WARNING and CAUTION 5 1 ______________ Indicates that incorrect handling may cause hazardous I AN WARNING conditions resulting in death or severe injury 1 1 1 Indicates that incorrect handling may cause hazardous A CAUTION conditions resulting in medium or slight personal injury or physical damage 1 Note that the A CAUTION level may lead to a serious accident according to the circumstances Always follow the precautions of both levels because they are important to personal safety Please save this manual to make it accessible when required and always forward it to the end user A 1 DESIGN PRECAUTIONS Some faults of this unit may keep the outputs on or off An external mo
9. No Quadruple 1 station occupied RYnO to RY n 2 F Extension cyclic setting 4 station occupied RYnO to RY n 1A F 1 station occupied RYn0 to RY n 6 F 4 station occupied RYnO to RY n 36 F Signal name User area RY n 3 O to RY n 3 F 1 2 RY n 1B O to RY n 1B F RY n 7 0 to RY n 7 F RY n 37 0 to RY n 37 F Reserved When the mode setting of CC Link is Ver 1 the extension cyclic setting is not available Fixed to Single The remote READY flag is on during startup of the GOT It switches on when GOT power is switched on hardware reset is made or the GOT is ready to operate If GOT power is on the remote READY flag is off when offline operation is performed during OS installation or screen data downloading or while initial processing is executed Use it for the interlock ladder when writing or reading data to or from the CC Link Master station 3 2 Remote Register Assignment The following is the assignment of the remote registers of the GOT The remote registers differ according to the set number of occupied stations 1 or 4 stations All areas are use areas m and n in the table indicate the addresses assigned to the Master module by station number setting Address Extension cyclic setting Transfer a Description Default Direction Single Double Value 1 station 4 station 1 station 4 station occupied occupied occupied occupied Master station RWwm to RWwm t
10. ch Seoul 157 200 Korea Travellers Lane Hatfield Hertfordshire Tel 82 2 3660 9552 AL10 8XB U K Singapore Mitsubishi Electric Asia Pte Ltd 1707 307 Alexandra Road 05 01 02 Mitsubishi Tel 44 1707 276100 lexandra Road Italy Mitsubishi Electric Europe B V Italian Electric Building Singapore 159943 Branch Tel 65 6470 2460 Thailand Mitsubishi Electric Automation Thailand Centro Dir Colleoni Pal Perseo Ingr 2 Via Paracelso 12 1 20041 Agrate Brianza Milano Italy Moo 4 Serithai Rd T Kannayao Tel 39 039 60531 Mitsubishi Electric Europe B V Spanish A Kannayao ergs 30230 Thalland Branch Carretera de Rubi 76 80 E 08190 Sant Cugat del Valles Co Ltd Bang Chan Industrial Estate No 111 Indonesia P T Autoteknindo Sumber Makmur Muara Karang Selatan Block A Utara No 1 Kav No 11 Kawasan Industri Barcelona Spain Per gudangan Jakarta Utara 14440 Tel 34 93 565 3131 P O Box 5045 Jakarta 11050 Indonesia France Mitsubishi Electric Europe B V French Tel 62 21 6630833 Branch India Messung Systems Pvt Ltd 25 Boulevard des Bouvets F 92741 Electronic Sadan NO III Unit No15 Nanterre Cedex France M L D C Bhosari Pune 411026 India Tel 33 1 5568 5568 Tel 91 20 2712 3130 South Africa Circuit Breaker Industries Ltd Australia Mitsubishi Electric Australia Pty Ltd Private Bag 2016 2 1600 Isando 348 Victoria Road Rydalmere South Africa N S W 2116 Australia Tel 2
11. e used for disinfecting and protecting wooden packaging from insects they cause malfunction when entering our products Please take necessary precautions to ensure that remaining materials from fumigant do not enter our products or treat packaging with methods other than fumigation heat method Additionally disinfect and protect wood from insects before packing products A 6 REVISIONS The manual number is noted at the lower right of the top cover Print Date Manual Number Revision Mar 2006 IB NA 0800351 A First edition Sep 2006 IB NA 0800351 B Partial additon Chapter 1 Addition Compliance with the EMC and Low Voltage Directives Jul 2007 IB NA 080351 C Partial corrections Compliance with the EMC and Low Voltage Directive Chapter 2 4 5 Jan 2009 IB NA 0800351 D Partial addition Chapter 1 2 4 5 Jun 2009 IB NA 0800351 E Partial corrections Compliance with the EMC and Low Voltage Directives Jun 2011 IB NA 0800351 F Partial corrections Chapter 4 Partial addition Compliance with the Radio Waves Act South Korea Oct 2014 IB NA 080351 G Partial corrections SAFETY PRECAUTIONS Chapter 4 5 This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible fo
12. er off externally in all phases Not doing so can cause a unit failure or misoperation Undertightening can cause a drop short circuit or misoperation Overtightening can cause a drop short circuit or misoperation due to damaged screws or unit Do not disassemble or modify the unit Doing so can cause a failure misoperation injury or fire Do not touch the conductive areas and electronic parts of the unit Doing so can cause the unit to misoperate or fail Do not drop the unit or subject it to strong impact Doing so can damage the unit Always make sure to touch the grounded metal to discharge the electricity charged in the body etc before touching the unit Failure to do so may cause a failure or malfunctions of the unit DISPOSAL PRECAUTIONS N CAUTION Dispose of this product as industrial waste A 5 TRANSPORTATION PRECAUTIONS N CAUTION Make sure to transport the GOT main unit and or relevant unit s in the manner they will not be exposed to the impact exceeding the impact resistance described in the general specifications of Use this unit in the environment that satisfies the general specifications described in the User s Manual for the GOT used as they are precision devices Failure to do so may cause the unit to fail Check if the unit operates correctly after transportation When fumigants that contain halogen materials such as fluorine chlorine bromine and iodine ar
13. ied ied ied 32 128 32 224 64 448 128 896 points points points points points points points points 4 16 8 32 16 64 32 128 points points points points points points points points 4 16 8 32 16 64 32 128 points points points points points points points points Link device Remote RY Remote register RWw Remote register RWr For CC Link Ver 1 Number of link points per station Link device 1 station occupied 4 station occupied Remote RY 32 points 128 points Remote register RWw 4 points 16 points Remote register RWr 4 points 16 points 2 2 Specifications of terminal block socket Screw tightening torgue Wiring screw 10 5 to 0 6 Nem Terminal block fixing screw 0 7 to 0 8 Nem Flat blade screwdriver Recommended driver Blade thickness 0 6mm Width 3 5mm 3 1 0 SIGNALS AND REMOTE REGISTER ASSIGNMENT 3 1 I O Signals Transferred to from the Master Module The following table lists the I O signals assigned to the GOT The I O signals differ according to the set number of occupied stations 1 or 4 stations nin the table indicates the address assigned to the Master module by station number setting Signal Direction GOT Master module Device No Extension cyclic setting 1 station occupied RXnO to RXnF 4 station occupied RXnO to RX n 6 F 1 station occupied RX
14. nO to RXnF 4 station occupied RXn0 to RX n C F Signal name User area RX n 1 0 to RX n 1 A RX n 7 0 to RX n 7 A 1 0 to 1 RX n D O to RX n D A Reserved RX n 1 B RX n 7 B RX n 1 B RX n D B Remote READY flag 2 RX n 1 C to 1 RX n 7 C to RX n 7 F RX n 1 C to RX n 1 F RX n D C to RX n D F Reserved Signal Direction GOT Master module Device No Quadrup 1 station occupied RXnO to RX n 2 F Extension cyclic setting 4 station occupied RXnO to RX n 1A F 1 station occupied RXnO to RX n 6 F 4 station occupied RXn0 to RX n 36 F Signal name User area RX n 3 0 to RX n 3 A RX n 1B O to 1 RX n 7 O to RX n 7 A RX n 37 0 to RX n 37 A Reserved RX n 3 B RX n 1B B RX n 7 B RX n 37 B Remote READY flag 2 RX n 3 C to RX n 3 F RX n 1B C to RX n 1B F RX n 7 C to RX n 7 F RX n 37 C to RX n 37 F Reserved 1 station occupied RYn0 to RYnF Signal Direction GOT Master module Device No Extension cyclic setting 4 station occupied RYnO to RY n 6 F 1 station occupied RYnO to RYnF 4 station occupied RYnO to RY n C F Signal name User area RY n 1 O to RY n 1 F RY n 7 O to RY n 7 F RY n 1 0 to RY n 1 F RY n D O to RY n D F Reserved Signal Direction GOT Master module Device
15. nitoring circuit should therefore be provided to check for output signals which may lead to a serious accident Not doing so can cause an accident due to mis output or misoperation If a communication error including cable disconnection occurs during monitoring with the GOT communication between the GOT and master station is interrupted disabling operation When using the GOT to configure a system assume that a GOT communication error will occur and configure a system in which switches used to perform significant operation for the system are provided on any device other than the GOT Not doing so can cause an accident due to mis output or misoperation N CAUTION Do not bunch the control wires or communication cables with the main circuit or power wires or lay them close to each other As a guide separate the lines by a distance of at least 100mm 3 94 inches otherwise malfunctions may occur due to noise INSTALLATION PRECAUTIONS Be sure to shut off all phases of the external power supply used by the system before mounting or removing this unit to from the GOT Not doing so can cause a unit failure or misoperation A 2 INSTALLATION PRECAUTIONS N CAUTION Use this unit in the environment that satisfies the general specifications described in the User s Manual for the GOT used Not doing so can cause an electric shock fire malfunction or product damage or deterioration When installing thi
16. nsumption 5VDC 0 56A Weight i 0 18kg 0 4016 When installing an extension unit on the CC Link communication unit limit the maximum operating ambient temperature by subtracting 5 degrees from operating ambient temperature of the general specifications 2 Each of the I O signals RX RY occupies 16 points of a system area within device points For more details on the I O signals refer to Section 3 1 3 The number of link points per station depends on the mode setting of CC Link as shown below For CC Link Ver 2 Number of link points per station Link device Extension cyclic setting Double Quadruple Octuple Remote I O RX RY 32 points 32 points 64 points 128 points Remote register RWw 4 points 8 points 16 points 32 points Remote register RWr 4 points 8 points 16 points 32 points For CC Link Ver 1 Link device Number of link points per station Remote I O RX RY 32 points Remote register RWw 4 points Remote register RWr 4 points 4 The number of link points per number of occupied stations depends on the mode setting of CC Link as shown below For CC Link Ver 2 Number of link points per station Extension cyclic setting Single Double Quadruple Octuple 1 4 1 4 1 4 1 4 station station station station station station station station occup occup occup occup occup occup occup occup ied ied ied ied ied
17. o RWwm to RWwm to User wirte 1 RWwm 3 RWwm F RWwm 7 RWwm 1F area GOT GOT l RWrn to RWrn to RWrn to RWrn to User read Master RWrn 3 RWrn F RWrn 7 RWrn 1F area station Address Extension cyclic setting Transfer _ Default Quadruple Octuple Description Value 1 station 4 station 1 station 4 station occupied occupied occupied occupied Direction Master station RWwm to RWwm to RWwm to RWwm to User wirte l RWwm F RWwm 3F RWwm 1F RWwm 7F area GOT GOT l RWrn to RWrn to RWrn to RWrn to User read Master RWrn F RWrn 3F RWrn 1F RWrn 7F area station 3 When the mode setting of CC Link is Ver 1 the extension cyclic setting is not available Fixed to Single 4 PART NAMES AND EXTERNAL DIMENSIONS GT15 J61BT13 133 5 24 108 4 25 30 5 1 20 19 5 0 77 21 0 83 23 0 91 18 0 71 18 0 71 23 0 91 23 0 91 21 0 83 21 0 83 23 0 91 23 0 91 23 0 91 23 0 91 23 0 91 23 0 91 23 0 91 23 0 91 Unit mm inch Description CC Link communication Connector for connecting the CC Link dedicated cable connector Interface Extension connector installed to a front extension unit or the GOT connector Extension connector Mounting screw Extension connector to which a back extension unit is installed Mounting screws fixed with a front extension unit
18. or the GOT Board fixing screw Rating plate Terminal block Socket for connecting the CC Link dedicated cable to the CC Link socket communication connector Screw for fixing the extension interface relay board This indicates the status of the CC Link communication unit and the communication status The LED lighting status includes the normal mode and error mode 1 Normal mode If any communication Status error occurs in the The GOT is being normal mode specify the reset error cause by the The unit is in a NETWK unit status normal status display screen The unit is ina Refer to the User s normal status Manual for the GOT used TTE E The communication for details on the statues of all stations NETWK unit status are abnormal display screen A communication 2 Error mode error has occurred at When the RUN LED is Flicker station or a station flickering the LED number is indication will change to duplicated Operation the error mode Data have not been indicator LED If an error occurs in the transmitted or the error mode restart the GOT is being reset GOT Data are being If the error mode is not transmitted released after restarting FN 4 Data have not been RDC ERR the GOT the system received or the GOT alarm 460 is being reset Communication unit Data are being error may have received occurred For system alarms refer to the User s Manual for the GOT used Bud Flicker
19. r any problems involving industrial property rights which may occur as a result of using the contents noted in this manual 2006 MITSUBISHI ELECTRIC CORPORATION A 7 CONTENTS OVERVIEW c E M 1 EET OR dces 2 2 1 Performance Specifications sssssssssseeeeeeeenneees 2 2 2 Specifications of terminal block socket 4 O SIGNALS AND REMOTE REGISTER ASSIGNMENT 5 3 1 I O Signals Transferred to from the Master Module 3 2 Remote Register Assignment 4 PART NAMES AND EXTERNAL DIMENSIONS 8 5 INSTALLATION PROCEDURE netten tot hte veto eec cde 11 5 1 CC Link communication unit installation 11 5 2 Terminal block socket installation eee 13 MEHO D usce eec ona a AMARUM 14 A 8 Manuals The following shows manuals relevant to this product Detailed Manual Manual number Model code GT16 User s Manual Hardware SH 080928ENG Sold separately 1D7MD3 GT15 User s Manual SH 080528ENG Sold separately 1D7M23 GOT1000 Series Connection Manual Mitsubishi Products for GT Works3 Sold separately Manual name SH 080868ENG 1D7MC2 Relevant Manuals
20. r misoperation due to damaged screws or unit Ensure that foreign matters such as chips and wire off cuts do not enter the unit They can cause a fire failure or misoperation Be sure to fix the wires or cables by ducts or clamps when connecting them to the unit Not doing so can damage the unit or cables due to dangling moved or accidentally pulled cables or can cause misoperation due to cable contact fault Do not install the control lines together with the communication cables or bring them close to each other Failure to do so may cause malfunctions due to noise When disconnecting a communication or power supply cable from the unit do not pull on the cable itself Disconnect cables fitted with connectors by holding and pulling the cable connector Disconnect cables not fitted with a connector by removing the screws from the part connected to the unit Pulling on a cable that is connected to the unit can cause damage to the unit or cable or malfunction due to cable connection faults TEST OPERATION PRECAUTIONS NWARNING Do not output switch on any reserved signal among the output signals provided from the master unit to the GOT Doing so can cause the PLC system to misoperate A 4 STARTUP AND MAINTENANCE PRECAUTIONS Do not touch the terminals while power is on Doing so can cause an electric shock or misoperation Before starting cleaning or terminal screw retightening always switch pow
21. rated in a device or system used in purposes related to human life Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi This product has been manufactured under strict quality control However when installing the product where major accidents or losses could occur if the product fails install appropriate backup or failsafe functions in the system Country Region Sales office Tel Country Region Sales office Tel U S A Mitsubishi Electric Automation Inc Hong Kong Mitsubishi Electric Automation 500 Corporate Woods Parkway Vernon Hong Kong Ltd Hills IL 60061 U S A 10th Floor Manulife Tower 169 Electric Tel 1 847 478 2100 Road North Point Hong Kong Brazil MELCO TEC Rep Com e Assessoria Tel 852 2887 8870 Tecnica Ltda China Mitsubishi Electric Automation Rua Correia Dias 184 China Ltd Edificio Paraiso Trade Center 8 andar 4 F Zhi Fu Plazz No 80 Xin Chang Road Paraiso Sao Paulo SP Brazil Shanghai 200003 China Tel 55 11 5908 8331 Tel 86 21 6120 0808 Germany Mitsubishi Electric Europe B V German Taiwan Setsuyo Enterprise Co Ltd Branch 6F No 105 Wu Kung 3rd Rd Wu Ku Gothaer Strasse 8 D 40880 Ratingen Hsiang Taipei Hsine Taiwan GERMANY Tel 886 2 2299 2499 Tel 49 2102 486 0 Korea Mitsubishi Electric Automation Korea Co Ltd UK Mitsubishi Electric Europe B V UK 1480 6 Gayang dong Gangseo ku Bran
22. s unit to the GOT fit it to the connection interface of the GOT and tighten the mounting screws in the specified torque range 0 36 N m to 0 48 Nem with a Phillips head screwdriver No 2 Undertightening can cause a drop failure or malfunction Overtightening can cause a drop failure or malfunction due to screw or unit damage WIRING PRECAUTIONS NWARNING Be sure to shut off all phases of the external power supply used by the system before wiring Not doing so can cause an electric shock product damage or misoperation N CAUTION Connect the connectors to the unit securely Always ground the FG terminal of the GOT power supply and the FG termial of this unit to the protective ground conducter Be sure to ground the GOT and this unit separately Not doing so may cause an electric shock or misoperation Before wiring the unit confirm the rated voltage and terminal arrangement of the product A fire or failure can occur if the power supply connected is different from the rating or wiring is incorrect Use applicable solderless terminals and tighten them with the specified torque If any solderless spade terminal is used it may be disconnected when the terminal screw comes loose resulting in failure A 3 WIRING PRECAUTIONS Z CAUTION Tighten the terminal screws within the specified torque range Undertightening can cause a short circuit or misoperation Overtightening can cause a short circuit o
23. the connector cover and the sticker When not installing an extension unit on the unit that has been installed in order to avoid receiving electrostatic stick accessory stickers to cover the top of mounting screws 4 places Keep the connector cover fixed Keep the sticker stuck as it is Connector cover Accessory sticker H gt Sticker Accessory sticker Remove the screws that fixes the extension interface relay board before removing the unit Above 6 5 2 Terminal block socket installation Be sure to fix the wires or cables by ducts or clamps when connecting them to the unit Not doing so can damage the unit or cables due to dangling moved or accidentally pulled cables or can cause misoperation due to cable contact fault 1 Insert the terminal block socket in the CC Link communication unit 2 Fasten the terminal block by tightening the terminal block fixing screws 2 places with the tightening torque of 0 7 to 0 8 Nem Expanded figure of part A A terminal block fixing screw When attaching or removing a communication cable to from the terminal block socket detach the terminal block socket from the connector When extension units are installed in multiple layers the units do not have to be removed from the GOT main unit 13 6 WIRING METHOD The following diagram shows how to wire the GOT and CC Link system modules 1 Wiring the GOT and CC Link system modules by CC Link dedicated
Download Pdf Manuals