        KOBOLD SV FLOWMETER/SWITCH User Instructions
         Contents
1.  Loosen the hold down screws on the reed contact housing     2  Slide the contact downwards  toward inlet  along the rail until it reaches its  stops  The reed contact will be actuated at this point     3  Open the feed line and introduce flow until the reed contact deactuates   then lower the flow value to the desired minimum     4  Slide the contact upwards  toward outlet  until the reed contact actuates  again     5  Tighten the hold down screws     FM Rev  4 16 13    56 ArivalofC   Equi  Your instrument was inspected prior to shipment and found to be defect free  If damage  is visible on the unit  we advise that you carefully inspect the packing in which it was  delivered  If damage is visible  notify your local carrier at once  since the carrier is liable  for a replacement under these circumstances  If your claim is refused  please contact  KOBOLD Instruments for further instructions     70 Maintenance   The KOBOLD SV contains no active mechanisms  such as springs or diaphragms  to  wear out  Operation is achieved using gravitv and magnetism  This means that reliable  operation and a long life may be expected from the SV  We do strongly recommend that   since dirt is the primary enemy of this instrument  only clean or filtered media be passed  through it     Ba  Nes hel wii SV Flow Switch   Call one of our friendly engineers at 412 788 2830     FM Rev  4 16 13    Caution    PLEASE READ THE FOLLOWING GENERAL FLOW METER  MONITOR  WARNINGS BEFORE ATTEMPTING INSTALLATION OF
2.  YOUR NEW  DEVICE  FAILURE TO HEED THE INFORMATION HEREIN MAY  RESULT IN EQUIPMENT FAILURE AND POSSIBLE SUBSEQUENT  PERSONAL INJURY     FM Rev  4 16 13    SV    User s Responsibility for Safety  KOBOLD manufactures a wide range of  process sensors and technologies  While each of these technologies are  designed to operate in a wide variety of applications  it is the user s  responsibility to select a technology that is appropriate for the application   to install it properly  to perform tests of the installed system  and to  maintain all components  The failure to do so could result in property  damage or serious injury     Inspect instrument for damage upon arrival  Cracked  fractured  bent or  otherwise damaged instruments must not be put into use  since the device  is weakened to an unknown extent  Refer to Section 6 0  Arrival of  Damaged Equipment  for additional information     Media and Chemical Compatibility  The maximum tolerances of the  device have been determined using water and air  If using other media   especially corrosive media  it is critically important that the user determine  chemical compatibility with our instruments  KOBOLD Instruments Inc   cannot accept responsibility for failure and consequences resulting from  use of media other than water  air  and nitrogen     Material Compatibility  Make sure that the model which you have  selected is chemically compatible with the application liquids  While the  meter is liquid and spray resistant when installe
3. KOBOLD SV FLOWMETER SWITCH    User Instructions          OBOLD KOBOLD Instruments Inc  1801 Parkway View Drive Pittsburgh PA 15205    l Phone  412  788 2830   Fax  412  788 4890   www koboldusa com  R2_4 13    1 0   2 0   3 0   4 0   5 0  5 1  5 2  5 3   6 0   7 0   8 0    Diagram 4 1    Table 2 1    Table Of Contents    KOBOLD SV FLOWMETER SWITCH    SV      eneral  yaa EX te e Cp Fas See M edd 1  DDECHICALON Sis a eadein m ee RN GDA soit M ag 1  Installation   40325 Bate d pex rock VoU RECO a ardt d et A OR x RAS qs 2  Electrical Installation       22 4  so eee dd ICE hos a ORA 3  Operation  n s Gul Sea hoy ob Mans b basta E rad S AU s 4  Reading FOW sew daa tler a I pe MES E e d 4  Adjusting the Setpoint for Increasing Flow                    4  Adjusting the Setpoint for Decreasing Flow                    4  Arrival of Damaged Equipment    5  Maintenance na E Ve SOME be Le gai 5  Need help with your SV Flow Switch             ooo o    o o   5  List Of Diagrams  Electrical Connections 0 45 22 84 nam Rr Rd fh 3  List of Tables  Material Composition              liliis  2    FM Rev  4 16 13    SV    KOBOLD SV FLOWMETER SWITCH  User Instructions    CAUTION  For safety reasons  please read the cautionary information located at  the end of the manual  before attempting installation     10 General    The KOBOLD SV flowmeter switch is intended for applications where only  measurement  or measurement and flow monitoring of liquids and gases with vertical   upward flow is required  
4. The instrument has a direct reading scale and may be factory  fitted with single or dual magnetic reed contacts that actuate when the desired flow is  achieved     The principle of operation of the SV is that of the well known float in a conical tube  The  KOBOLD SV  however  uses our patented cylindrical control tube with V groove to  replace the conical tube  This method has advantages in that the float is stabilized over  its entire measuring range and offers a large flow range in a small instrument  The float  has a built in permanent magnet that actuates a reed switch  when equipped  mounted  on the exterior housing of the device  The optional switch is therefore hermetically  separated from the medium  The optional switches are user adjustable so that setpoints  may be adjusted to any flow value within the range of the instrument     20 Specificati    Measurement Accuracy      5  of Full Scale  Maximum Medium Temperature  240 Degrees F   with PP or PVDF Float 160 Degrees F  Maximum Operating Pressure  145 PSIG  Switch Specifications   Maximum Voltage  240 VAC  Maximum Current  SPST  N O   1 5 A  SPDT  0 8 A  Maximum Power Dissipation  SPST  N O   50 VA 50 W    SPDT  30 VA 30 W    Environmental Protection  IP 65  IEC 259    Equal to NEMA 4     cCSAus Approval    FM Rev  4 16 13    SV 2    Table 2 1 Material Composition    Brass Version  Housing  Anodized Aluminum  Flow Tube  Borosilicate Glass  Slotted Nozzle  Ni Plated Brass  Float  Ni Plated Brass or PP  Fittings  Ni P
5. d properly  it is not  designed to be immersed     Proper Installation in Flow System  Install the device in a fully supported  position within your flow system  This avoids excessive stresses which may  damage the instrument  In particular     a   Ensure that the plumbing leading to and from the instrument is fully  supported and that the instrument does not perform the physical function of  a joint    b   When calculating stress on the device caused by plumbing  the weight  of the medium in the pipes must be considered as well     C   Misaligned runs of rigid piping can cause large stresses when  connected to the instrument  Do not connect in such a fashion     d   When connecting fittings  hold the instrument fittings rigid with a  correctly sized wrench  Do not install by twisting the instrument into the  pipe fittings    e   Do NOT install by holding the device housing to provide counter torque  to the pipe fitting     f   Use an appropriate amount of PTFE tape on male threads of fitting  This  reduces the twisting stresses produced by tightening the fittings into each  other     9   Do not use pliers or wrenches on the housing  as this may damage it   h   Do not overtighten  as this may fracture the fittings     FM Rev  4 16 13    While Operating the Flow System  During operation  there are a number  of situations to avoid     a   The sudden cessation of fluid flow causes what is typically referred to  as  water hammer   Most people are familiar with this phenomenon fro
6. lated Brass  Seals  NBR    3 0 Installation    CAUTION  For safety reasons  please read the cautionary information located at    SS Version    Anodized Aluminum  Borosilicate Glass  304 SS   304 SS or PVDF    304 SS  FKM    the end of the manual  before attempting installation     To install  proceed as follows     1  The SV flowmeter switch must be installed in a vertical position with the flow    inlet at the bottom     2  The medium must not contain any solids or contaminants that could precipitate  out of solution and deposit on the instrument s inner walls  This would prevent  proper operation of the device  Unclean media should be filtered upstream of  the SV  KOBOLD offers a magnetic screened filter suitable for such purposes     type MFR      3  Do not install meter on large masses of ferritic materials  or in areas where  strong electric fields are present  as this will hamper proper operation of the    reed contact     FM Rev  4 16 13    40 Electrical Installation    Maximum values of current and voltage must not be exceeded on the reed relay  If  driving inductive or capacitive loads  we recommend the use of a suitable isolation relay   KOBOLD provides a line of relays for such instances  If an isolation relay is not used  a  clamping diode is highly recommended for DC inductive loads to minimize contact  arcing  which will destroy the reed switch     Di L1 Electrical C    N O Contact  SPST  Changeover Contact  SPDT        Reed switch Reed switch         ka  lt   g
7. m  their home experience   it is the cause behind the loud clank of water pipes  which occurs when faucets are turned off too suddenly  The cause behind  this  water hammer  is quite easy to visualize  Water is fairly massive  The  amount of water in long runs of pipe is quite substantial  When the faucets  are turned off suddenly  especially from a full on condition  the water has  considerable momentum and does not want to stop flowing  The situation  is similar to stopping a car by running into a wall  rather than by applying  brakes  Both are sudden rather than gradual  The damage to the wall can  be substantial  not to mention the car      b   The  water hammer  causes surges in fluid pressure which could cause  the measurement instrument s pressure limit to be exceeded  resulting in  failure and possible personal injury     c   Fluid surges  as well as the water hammer  can be particularly  damaging to empty flowmeters since there is no back pressure in the  device  The damage is caused  once again  by momentary excess  pressure  To avoid these surges  fluid lines should remain full  if possible   and water flow should be introduced to the device slowly     d   If the instrument is isolated with inlet and outlet valves  the flowmeter  must be completely drained when said valves are both closed  Failure to  do so could result in damage to the device caused by thermal expansion of  fluid     e   Freezing of water in the instrument must be avoided since the resultant  expa
8. nsion will damage the flowmeter and make it unsafe for use     Wiring and Electrical  Section 2 0  Specifications and Section 4 0   Electrical Connections  provide the voltage and current limitations and the  wiring for the various sensor types  The sensor electrical ratings should  never be exceeded  Electrical wiring of the sensor should be performed in  accordance with all applicable national  state and local codes     Temperature and Pressure  Section 2 0  Specifications  provides the  temperature and pressure limits for each model  Operation outside these  limitations will cause damage to the unit and can potentially cause personal  injury  Fluid should never be allowed to freeze inside the sensor     Make a Fail safe System  Design a fail safe system that accommodates  the possibility of switch or power failure  In critical applications  KOBOLD  recommends the use of redundant backup systems and alarms in addition  to the primary system     FM Rev  4 16 13    
9. t      R4   T_T   i switch i   gt  R 09 C R      Load           Lara MER Min parana fa BES   Protection with an RC circuit for a c   resistance to the switch  current and inductive load          ik  H       Reed switch    Wire Capacitance         7 Protection against high discharge from  condensers and loadcapacitances     Protection with an idle diode for d c   current and inductive load     FM Rev  4 16 13    sv 4    2 0 Operation   We recommend that if possible  a flow control valve be installed downstream of the  instrument and be closed as pressure is introduced to the system  Thereafter  the control  valve can be opened gradually to achieve the needed flow  This procedure prevents  oscillation of the float as the medium is introduced  More importantly  it prevents possible  damage due to pressure surges  as described in the cautionary section  to the SV     5 1 Reading Flow    Read the flow rate off the top edge of the float     52 ndiustina the S EM ina El  Adjust the setpoint for increasing flow as follows   1  Loosen the hold down screws on the reed contact housing     2  Slide the contact upwards  toward outlet  along its rail until it reaches its  stops  The reed contact will be deactuated at this point     3  Open the medium feed line and set flow to desired volume   4  Slide the reed contact downwards  toward inlet  until the contact actuates     5  Tighten the hold down screws       2  adus sonori inq El    Adjust the setpoint for decreasing flow as follows   1 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
User Manual  Bohner 2-3SL 8807:COMBISAUGER 8706  Samsung 34" Curved Monitor SE790 Bruksanvisning  YARDGARD 328568B Instructions / Assembly  零 ~濡鴉ノ巫女~  Sun Fire X4140, X4240, and X4440 Servers Diagnostics Guide  INSTRUCTIONS FOR USE MODE D`EMPLOI  AL2- 2TC- ADP Installation Manual    Copyright © All rights reserved. 