Home
4110DL Installation Manual
Contents
1. na Age 10 Keyswitch LED Indications 10 Keyswitch Operation 10 Section 5 TESTING THE SYSTEM canenseaeees 11 REGULATORY AGENCY 12 DOC STATEMENT 13 THE LIMITATIONS THIS ALARM SYSTEM 14 SUMMARY OF CONNECTIONS DIAGRAM INSIDE BACK COVER ADEMCO LIMITED WARRANTY BACK COVER RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations For The Location Of Fire And Burglary Detection Devices Help Provide Proper Coverage For The Protected Premises Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke heat detectors we subscribe to the recommendations contained in the National Fire Protection Association s NF PA Standard 72 noted below Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows For minimum protection a smoke detector should be installed outside of each separate sleeping area and on each additional floor of a multi floor family living unit including basements The installation of smoke detectors in kitchens attics finished or unfini
2. 3 Install Remote Keypads 4 Install Hardwired Zones 5 Install Sounding Devices UL Use only UL Listed sounding devices for UL installations 6 Install the Remote Keyswitch 7 Connect Telephone Line alarm control panel disconnect from the incoming phoneline at the Make sure telephones on the premises are connected only through the telephone jack This is necessary to have true line seizure IMPORTANT 8 Connect the AC Transformer DO NOT PLUG THE TRANSFORMER INTO THE AC OUTLET UNTIL ALL OTHER WIRING TO THE CONTROL IS COMPLETE WARNING 9 Connect the Battery Do not attach the connector cable to the battery s terminals until after you have plugged the AC transformer into an uninterrupted iMPORTANT 120VAC outlet U L L In UL installations maximum current draw from the Auxiliary Output and the Alarm Output combined must not exceed 500mA 2 Usea battery or larger for UL installations 11 Connect Earth Ground Section 3 PROGRAMMING THE SYSTEM Se THE MECHANICS OF PROGRAMMING For actual program fields refer to the programming form included at the center of this manual Entering Program Mode Use one of the following methods e Press both the and keys at the same time within 50 seconds after power is appled to the Control or e After power up enter the Master Code 8 0 default Master Code is 4110 This
3. Wiring Run Chart For Devices Drawing Aux Power From The Control 12V amp GND TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED A SINGLE WIRE RUN SOmAorles soma soma sorasam orem eotea forum 750 266m women 308 GEM borean Includes Keypads and alarm devices requiring separate power Example If you have two motion detectors that draw a total of 44 mA and you are using 20 AWG wire the distance from the control panel Aux and terminals to the last device can be up to 750 ft The length of all wire runs for keypads must not exceed 1500 feet 457m when unshielded quad conductor cable is used 750 feet if shielded cable is used This restriction is due to the capacitive effect on the data lines when IMPORTANT quad cable is used Transformer Wiring Table Distance of Transformer Wire Gauge From the Control Panel To Use Up to 50 feet 50 100 feet Section 2 SYSTEM INSTALLATION AND WIRING ss nes INSTALLING THE SYSTEM Refer to the Summary of Connections diagram on the inside back cover of this manual for terminal connections when following these procedures 1 Mount the Control Cabinet 2 Mount the PC board BE SURE TO USE THE PLASTIC MOUNTING CLIPS SUPPLIED TO ISOLATE THE CIRCUIT BOARDS FROM THE CABINET FAILURE TO DO SO MAY RESULT IN DAMAGE TO THE TRANSFORMER WARNING AND OR THE CIRCUIT BOARDS
4. No plus Downloading 96 resets the Subscriber Account number and CSID in preparation for an initial download If 97 was entered previously 96 must be entered last Clearing All Data Fields 97 clears zeros all data fields The Master Code will now be 0 000 DO NOT PRESS 97 IF ANY PROGRAMMING HAS BEEN DONE PREVIOUSLY DATA ALREADY PROGRAMMED INTO THE SYSTEM WiLL BE DELETED WARNING Exiting Program Mode 98 inhibits re entry into the programming mode with the use of the Master Code 99 allows re entry into the program mode using Master Code 8 0 8 Section 4 SYSTEM OPERATION USER ACCESS CODES Adding a Secondary User Code MASTER CODE CODE KEY USER 2 3 OR 4 DESIRED 4 DIGIT ACCESS CODE The system will emit a single beep when a secondary code has been successfully entered Deleting a Secondary User Code MASTER CODE CODE KEY USER 2 3 OR 4 Notes Master and Secondary security codes permit access to the system for arming disarming etc e If a secondary code is inadvertently repeated for different users the lower user number will take priority e Opening and closing reports are sent for the Master as No 1 User codes are sent as Numbers 2 3 and 4 respectively System Commands Before arming the system must be in the READY condition all zones must be intact If the NOT READY message appears press the READY
5. will be displayed Silence the alarm by entering the Security Code and pressing OFF e If the system has been programmed for silent emergency there will be no audible alarms or displays but a report will be sent to the central station 4 Notify the central station when all tests are finshed and verify results with them TO THE INSTALLER Regular maintenance and inspection at least annually by the master and frequent testing by the user are vital to continuous satisfactory operation of any alarm system The master should assume the responsibility of developing and offering a regular maintenance program to the user as well as acquainting the user with the proper operation and limitations of the alarm system and its component parts Recommendations must be included for a specific program of frequent testing at least weekly to insure the system s proper operation at all times 11 REGULATORY AGENCY STATEMENTS UL NOTICE This is a Grade A residential system FEDERAL COMMUNICATIONS COMMISSION FCC Part 15 STATEMENT This equipment has been tested to FCC requirements and has been found acceptable for use The FCC requires the following statement for your information This equipment generates and uses radio frequency energy and if not installed and used properly that is in strict accordance with the manufacturer s instructions may cause interference to radio and television reception It has been type tested and found to comply w
6. AC is restored before the report goes out no report will be sent Telephone number entries can now contain and a 2 second pause Enter 11 for x Enter 12 for Enter 13 for 2 sec pause Audible Exit Warning option has been added field 27 0 no 1 yes default 1 If enabled beeping will occur during exit time and will change from slow to rapid beeping during last 5 seconds of exit delay Master code is now able to change itself in normal operating mode To change enter Master code 8 1 new Master code new Master code again New Telco Hand off feature allows the technician at the site to call the downloading facility from the control panel phone line initiate a site download Master Code 1 and the control will immediately be on line with the modem at the downloading facility If all power is lost at the control upon power up the armed status will be the same as it was before the power loss Bypasses however are not retained The control checks for the physical battery connection every two minutes If connection is lost a visual and audible trouble is indicated and a communicator report will be sent if programmed The actual condition of the battery is still checked once every four hours To clear the low battery message after the low battery condition is restored enter Test mode User code 5 otherwise it will clear itself the next time the system checks the battery s condi
7. ADEMCO SECURITY SYSTEM 4110DL ASIN FOR ON VER cov Installation Instructions Please Read INFORMATION CONCERNING NEW FEATURES Controls with microprocessor part number N7185V3 or higher contain the following new features These controls can be identified via the downloader as Rev 06 1 D 10 11 This control complies with National Fire Protection Association NFPA requirements for temporal pulse sounding of fire notification appliances Fire alarms now sound as interrupted pulses consisting of three pulses and a brief pause i e ring ring ring pause ring ring ring pause etc Capability has been added for the control to call a pager on the secondary telephone number This can only be used if the primary reporting format is Ademco Contact ID The following entries have been added to program field 49 Split Dual Reporting for the purpose of paging messages Primary Secondary Paging number 6 All reports except Open Close Alarms Open Close Troubles 7 All reports Alarms Troubles 8 All reports Alarms Open Close Troubles Touch tone codes sent to the pager are 1911 Alarm 1001 Open 1002 Close 1811 Trouble No restore reports are sent to the pager Three additional user codes have been added identified as Users 5 6 and 7 Duress is now User 8 no longer User code 1 AC Loss report is now sent at a random time delay up to 1 hour If
8. I LO ZONE 6 ZONE 2 ZONE 3 ZONE 4 1 ONMS OHMS OHMS OHMS OHMS EOLR EOLR EOLR EOLR EOLR MAXIMUM LOOP RESISTANCE EACH ZONE 300 OHMS PLUS EOLR RESPONSE ZONES 1 6 300 500MSEC ZONE CAN BE PROGRAMMED FOR N C SENSOR FAST RESPONSE TO m 1000 1 1000 1000 71 1000 a A 2 2 o Q alr L 2 gt LS lt gt m9 wy clo gt 1000 5 EOLR BLACK CONSOLE GROUND RETURN RED CONSOLE PWR G REMOTE CONSOLE No 4127 20mA OPEN 10MSEC MAX No 4137AD 60mA ZONE 5 CAN BE PROGRAMMED FOR USE AS A FIRE ZONE SEE DIAGRAM No 6127 20mA No 6128 30mA THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES OPERATION No 6137 85mA IS SUBJECT TO THE FOLLOWING TWO CONDITIONS 1 IT MAY NOT OR CAUSE HARMFUL INTERFERENCE 2 IT MUST ACCEPT ANY INTER No 5330 105mA FERENCE THAT MAY CAUSE UNDESIRED OPERATION COMPLIES WITH FCC RULES PART 68 FCC REGISTRATION NO AC398U 68192 AL E RINGER EQUIVALENCE 0 7B WARNING WEEKLY TESTING IS REQUIRED TO ENSURE PROPER OPERATION OF THIS SYSTEM No 4110DL SUMMARY OF CONNECTIONS HI ONE 5 IF PROGRAMMED FOR FIRE LOCATED AT LOWER RIGHT CORNER TIP RING TIP RING OF CIRCUIT BOARD BROWN GRAY GREEN INCOMING PHONE LINE TELEPHONE WIRING 5 VIA RU31X JACK DIRECT ARTH GROUND CONNECT CORD SEE INSTRUCTIONS IN CANADA CA38A JACK FOR
9. Low Speed Standard or Expanded 1400 2 ACK KISSOFF Sescoa Radionics Standard or Expanded 2300 2 ACK KISSOFF Ademco Express DTMF 1400 2300Hz ACK 1400Hz KISSOFF Ademco Contact ID DTMF 1400 2300Hz ACK 1400Hz KISSOFF SPECIFICATIONS 411001 CONTROL 1 Physical 12 1 2 W x 14 1 2 H x 3 D 76mm 2 Electrical VOLTAGE INPUT 16 5VAC from plug in 25VA transformer Ademco No 1321 TF2 in U S A 1321CN in Canada RECHARGEABLE BACK UP BATTERY 12VDC 4AH Gel type CHARGING VOLTAGE 13 8VDC ALARM SOUNDER 12V 2 0 Amp output AUXILIARY POWER OUTPUT 12VDC 500mA max Interrupts for 4 wire smoke detector reset 318mm x 368mm x MAXIMUM ZONE RESISTANCE Zones 1 8 300 ohms exduding EOLR Remote Keypads up to 4 Model Type 4127 6127 Fixed English 4137AD 6137 6128 Fixed English Addressable 5330 Select for Vista Alpha Smoke Detectors 4 wire only Model Type 1412 lonization Products of Combustion Detector 2412 Photoelectric Smoke Detector 2412TH Photoelectric Smoke Detector w 1352 F 572C Heat Detector IMPORTANT U L draw from the Auxiliary Output and the Alarm Output combined must not exceed 500mA total FUSE Battery 3A No 90 12 LINE SEIZE Double Pole REGULATORY INFORMATION Ringer Equivalence 0 7B FCC Registration No 3980 68192 AL E UL File No 1632 Guide UXOU eyp the no
10. PROPER GROUNDING DOC LOAD NO 3 WARNING TO PREVENT RISK OF SHOCK DISCONNECT TELEPHONE LINE AT TELCO JACK BEFORE SERVICING THIS UNIT THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH THE NATIONAL FIRE PRO TECTION ASSOCIATION S STANDARD 74 NATION AL FIRE PROTECTION ASSOC BATTERYMARCH PARK QUINCY MA 02269 PRINTED INFORMATION DESCRIBING PROPER INSTALLATION OPERATION TESTING MAINTENANCE EVACUATION PLANNING AND REPAIR SERVICE IS TO BE PROVIDED WITH THIS EQUIPMENT ADEMCO LIMITED WARRANTY Alarm Device Manufacturing Company Division of Pittway Corporation and its divisions subsidiaries and affili ates Seller 165 Eileen Way Syosset New York 11791 warrants its products to be in conformance with its own plans and specifications and to be free from defects in materials and workmanship under normal use and service for 24 months from the date stamp control on the product or for products not having an Ademco date stamp for 12 months from date of original purchase unless the installation instructions or catalog sets forth a shorter period in which case the shorter period shall apply Seller s obligation shall be limited to repairing or replacing at its option free of charge for materials or labor any product which is proved not in compliance with Seller s specifications or proves defective in materials or workmanship under normal use and service Seller shall have no obligation under this Limited Warranty or oth
11. THER DIRECTLY OR INDIRECTLY FOR ANY LOSS OR DAMAGE ARISING UN DER THIS LIMITED WARRANTY OR OTHERWISE REGARDLESS OF CAUSE OR ORIGIN SELLER S MAXIMUM LIABILITY SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE OF THE PRODUCT WHICH SHALL BE THE COMPLETE AND EXCLUSIVE REMEDY AGAINST SELLER This warranty replaces any previous warranties and is the only warranty made by Seller on this product No increase or alteration written or verbal of the obligations of this Limited Warranty is authorized ADEMCO
12. X POWER OUTPUT AND REMOTE CONSOLE CURRENTS USE UL LISTED LIMITED ENERGY CABLE FOR ALL CONNECTIONS AUX POWER OUTPUT 10 5 13 8VDC 500mA MAX INTERRUPTS FOR FIRE ALARM RESET FOR COMPLETE INFORMATION SEE INSTRUCTIONS N5672VS TO 110 UNSWITCHED OUTLET 24HR PLUG IN TRANS FORMER 16 5VAC 25VA e g ADEMCO No 1321 TF2 USE No 1321CN IN CANADA NOTE CONSOLE AUX CURRENT DRAIN CALCULATIONS ALARM OUTPUT 10 5 13 8VDC 2A MAX 600mA MAX FOR UL USAGE INCLUDING AUX POWER STEADY FOR BURGLARY PANIC PULSING FOR FIRE e g USE ADEMCO No 702 OR 719 SIREN OR 12V BELL CONNECTION OF THE FIRE ALARM SIGNAL TO A FIRE ALARM HEADQUARTERS OR A CENTRAL STATION SHALL BE PERMITTED ONLY WITH THE PERMISSION OF THE LOCAL AUTHORITY HAV ING JURISDICTION THE BURGLAR ALARM SIGNAL SHALL NOT BE CONNECTED TO A POLICE EMERGENCY NUMBER CURRENT MUST BE INCLUDED IN NOTE MULTIPLE CONSOLES MAY BE USED BUT EACH 5330 CONSOLE MUST BE ON AN INDI VIDUAL HOME RUN USE MAX OF 220FT OF 22 WIRE OR 550 FT OF 18 WIRE FUSE FOR REPLACEMENT USE SAME VALUE AUXPWR 4 OUTPUT BLK RED TERMS BATTERY EOL g No 90 12 Fe VISION 4 WIRE SMOKE RELAY OR COMBUSTION MODULE DETECTOR A77 716B OPTIONAL No 4116 ARMING DISARMING DETECTOR KEYSWITCH pe SINGLE LED LOCK SWITCH TAMPER HI LO HI HI LO LO HI H
13. arning devices such as sirens bells or horns may not alert people or wake up sleepers if they are located on the other side of closed or partly open doors If warning devices are located a different level of the residence from the bedrooms then they are less likely to waken or alert people inside the bedrooms Even persons who are awake may not hear the warning if the alarm is muffled by noise from a stereo radio air conditioner or other appliance or by passing traffic Finally alarm warning devices however loud may not warn hearing impaired people Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or temporarily out of service Telephone lines are also subject to compromise by sophisticated intruders Even if the system responds to the emergency as intended however occupants may have insuffi cient time to protect themselves from the emergency situation In the case of a monitored alarm system authorities may not respond appropri ately This equipment like other electrical devices is subject to component failure Even though this equipment is designed to last as long as 20 years the electronic components could fail at any time The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance This alarm system should be tested weekly to make sure all sensors and transmitters are working properly The security keypad an
14. d remote keypad should be tested as well Wireless transmitters used in some systems are designed to provide long battery life under normal operating conditions Longevity of batteries may be as much as 4 to 7 years depending on the environment usage and the specific wireless device being used External factors such as humidity high or low temperatures as well as large swings in temperature may all reduce the actual battery life a given installation This wireless system however can identify a true low battery situation thus allowing time to arrange a change of battery to maintain protection for that given point within the system Installing an alarm system may make the owner eligible for a lower insurance rate but an alarm system is not a substitute for insurance Homeowners property owners and renters should continue to act prudently in protecting themselves and continue to insure their lives and property We continue to develop new and improved protection devices Users of alarm systems owe it to themselves and their loved ones to learn about these developments 14 GEL LEAD ACID DO NOT USE GATES BATTERY BATTERY NORMALLY NEED NOT BE REPLACED FOR AT LEAST 3 YRS BATTERY CAPACITY FOR EMERGENCY STANDBY USE AT LEAST 4 HOURS BLACK CHARGING VOLTAGE 13 8VDC BATTERY RED 12V 4AH OR 12V 1 2AH CONNECTOR TABS TO DETERMINE TOTAL STANDBY LOAD ON BATTERY ADD 100mA TO TOTAL OF AU
15. erwise if the product is altered or improperly repaired or serviced by anyone other than Ademco factory service For warranty service return product transportation prepaid to Ademco F actory Service 165 Eileen Way Syosset New York 11791 THERE ARE NO WARRANTIES EXPRESS OR IMPLIED OF MERCHANTABILITY OR FITNESS FOR PARTICULAR PURPOSE OR OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER EVEN IF THE LOSS OR DAMAGE 15 CAUSED BY THE SELLER S OWN NEGLIGENCE OR FAULT Seller does not represent that the products it sells may not be compromised or circumvented that the products will prevent any personal injury or property loss by burglary robbery fire or otherwise or that the products will in all cases provide adequate warning or protection Customer understands that a properly installed and maintained alarm may only reduce the risk of a burglary robbery fire or other events occurring without providing an alarm but it is not insurance a guarantee that such will not occur or that there will be no personal injury or property loss as a result CONSEQUENTLY SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJ URY PROPERTY DAMAGE OR OTHER LOSS BASED ON A CLAIM THE PRODUCT FAILED TO GIVE WARNING HOWEVER IF SELLER IS HELD LIABLE WHE
16. fications could void the user s authority to operate the equipment FEDERAL COMMUNICATIONS COMMISSION FCC Part 68 STATE MENT This equipment complies with Part 68 of the FCC rules On the front cover of this equipment is a label that contains among other information the FCC registration number and ringer equivalence number REN for this equipment If requested this information must be provided to the telephone company This equipment uses the following jacks RJ 31X is used to connect this equipment to the telephone network The REN is used to determine the quantity of devices which may be connected to the telephone line Excessive RENS on the telephone line may result in the devices not ringing in response to an incoming call In most but not all areas the sum of the RENs should not exceed five 5 0 To be certain of the number of devices that may be connected to the line as determined by the total RENs contact the telephone company to determine the maximum REN for the calling area If this equipment causes harm to the telephone network the telephone company will notify you in advance that temporary discontinuance of service may be required If advance notice is not practical the telephone company will notify the customer as soon as possible Also you will be advised of your right to file a complaint with the FCC if you believe necessary The telephone company may make changes in its facilities equipment operations or procedures that co
17. fournisseur La compagnie de t l communications peut demander l utilisateur de d brancher un appareil la suite de r parations ou de modifications effectu es par l utilisateur cause de mauvais fonctionnement Pour sa propre protection l utilisateur doit s assurer que tous les fils de mise en terre de la source d nergie lectrique des lignes t l phoniques de r seau de conduites d eau s il en soient raccord s ensemble Cette pr caution est particuli rement importante dans les r gions rurales Avertissement L utilisateur ne doit pas tenter de faire ces raccordements lui m me il doit avoir recours un service d inspection des installations lectriques ou un lectricien selon le cas L indice de charge 1 assign chaque dispositif terminal pour viter toute surcharge indique le pourcentage de la charge totale qui peut tre raccord un circuit t l phonique boucl utilis par ce dispositif La terminaison du circuit boucl peut tre constitu e de n importe quelle combinaison de dispositifs pourvu que la somme des indices de charge de l ensemble des dispositifs ne d passe pas 100 13 WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system it does not offer guaranteed protection against burglary fire other emergency Any alarm system whether commercial or residential is subject to compromise or failure to warn for a vari ety of rea
18. ith the limits for a Class computing device in accordance with the specifications in Part 15 of FCC Rules which are designed to provide reasonable protection against such interference in a residential installation However there is no guarantee that interference will not occur in a particular installation If this equipment does cause interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures If using an indoor antenna have a quality outdoor antenna installed Reorient the receiving antenna until interference is reduced or eliminated Move the radio or television receiver away from the receiver control Move the antenna leads away from any wire runs to the receiver control Plug the receiver control into a different outlet so that it and the radio or television receiver are on different branch circuits If necessary the user should consult the dealer or an experienced radio television technician for additional ae re The user or master may find the following booklet prepared by the F ederal Communications Commission elpful Interference Handbook This booklet is available from the U S Government Printing Office Washington DC 20402 The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User s Manual Unauthorized changes or modi
19. method is disabled if you exit the program mode using 98 instead of 99 See Exiting Program Mode later in this section Once you have entered program mode data field 20 will be displayed this is the first field in the system The system will now accept entries for field 20 Programming a Data Field Field Number Press plus Field No e g 20 and then make the required entry Note the following keypad beeps three times when the data field has been completely programmed e Field No is displayed If you do not want to program this field press the Field No you want to program e If thenumber of digits that you need to enter in data field is less than the maximum digits available e g the phone number field enter the desired data then press the next Field No to be programmed e Ifyou try to enter a non existent field the keypad will display or Entry Error Simply reenter plus a valid Field No Reviewing a Data Field Press plus Field No Note the following e Data will be displayed for that field number entry by entry a beep will be heard between entries and three beeps after the last e changes will be accepted in this mode e Ifyou try to enter a non existent field the keypad will display EE or Entry Error Simply reenter plus a valid field number Erasing an Entry in a Data Field Applies only to fields 40 43 and 94 Press plus Field
20. n addressable ode Device Address 31 which is pre set at the factory Do not set these keypads to any other addresses Fire Supervisory Module 77 71601 EOL Relay Module supervises power for 4 wire fire zone Optional Keyswitch 4116 Keyswitch 1 Entry xit Burglary Provides entry delay when panel is armed Away and Stay modes only 3 Perimeter Burglary Provides an instant alarm when panel is armed in any arming mode 4 Interior Follower Provides exit delay time when panel is armed in any mode Will only provide entry delay if an Entry Exit zone is faulted first upon entry Otherwise alarm will be instant Bypassed automatically when panel is armed in the Stay or Instant mode 5 Trouble by Day Alarm by Provides a trouble response if panel is not armed when zone is faulted Night Provides an instant alarmif panel is armed in any mode 6 24 Hr Silent Alarm Provides a silent alarm to Central Station whether panel is armed or disarmed 7 24Hr Audible Alarm Provides an audible alarm at the bell output and keypad whether panel is armed or disarmed 8 24 Auxiliary Alarm Provides an audible alarm at the keypad only No bell output is provided 9 Fire Provides a fire alarm when zone is shorted Causes bell output to pulse Provides a trouble response when zone is open 10 Interior w Delay Provides entry and exit delay times Bypassed automatically when panel is armed in the Stay or Instant mode
21. or proper intrusion coverage sensors should be located at every possible point of entry to a home or commercial premises This would include any skylights that may be present and the upper windows in a multi level building In addition we recommend that radio backup be used in security system so that alarm signals still be sent to the alarm monitoring station in the event that the telephone lines are out of order alarm signals are normally sent over the phone lines if connected to an alarm monitoring station Section 1 GENERAL DESCRIPTION The 411001 is a microprocessor based state of the art security controls intended for wired applications Control Panel supports up to 6 hardwired zones and can be programmed either through the keypad or remotely using ADEMCO s V LINK downloading software eae ee ae ee ares ae FEATURES Zones Supported 6 hardwire zones characteristics having the following EOLR supervision supporting N O or N C sensors 300 500 msec normal response Zone 3 programmable for Fast Response to open 1015 Security Codes 1 master code for entire system user 1 secondary user codes users 2 4 Keypad Panic Keys e Provides panic key functions Alarm Output Provides a 12VDC 2 AMP output assumes a fully charged battery is connected Steady output for Burglary Panic or pulsing output for Fire Output is current limited Communication Formats Ademco
22. r basement fire Finally smoke detectors have sensing limitations No smoke detector can sense every kind of fire every time In general detectors may not always warn about fires caused by carelessness and safety hazards like smoking in bed violent explosions escaping gas improper storage of flammable materials overloaded electrical circuits children playing with matches or arson Depending on the nature of the fire and or location of the smoke detectors the detector even if it operates as antic pated may not provide sufficient warning to allow all occupants to escape in time to prevent injury or death Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their installation manual Passive Infrared Detectors do not provide volumetric area protection They do create multiple beams of protection and intrusion can only be detected in unobstructed areas covered by those beams They cannot detect motion or intrusion that takes place behind walls ceilings floors dosed doors glass partitions glass doors or windows Mechanical tampering masking painting or spraying of any material on the mirrors windows or any part of the optical system can reduce their detection ability Passive Infrared Detectors sense changes in temperature however as the ambient temperature of the protected area approaches the temperature range of 90 to 105 F 32 to 40 C the detection performance can decrease Alarm w
23. s should ensure that it is permissible to be connected to the facilities of the local telecommunications company The equipment must also be installed using an acceptable method of connection In some cases the company s inside wiring associated with a single line individual service may be extended by means of certified connector assembly telephone extension cord The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier Any repairs or alterations made by the user to this equipment or equipment malfunctions may give the telecommunications company cause to request the user to disconnect the equipment Users should ensure for their own protection that the electrical ground connections of the power utility telephone lines and internal metallic water pipe system if present are connected together This precaution may be particularly important in rural areas Caution User should not attempt to make such connections themselves but should contact the appropriate electric inspection authority or electrician as appropriate The Load Number LN assigned to each terminal device denotes the percentage of the total load to be connected to a telephone loop which is used by the device to prevent overloading The termination on a loop may consist of any combination of device
24. s subject only to the requirement that the total of the Load Numbers of all the devices does not exceed 100 AVIS L tiquette du minist re des Communications du Canada identifie le mat riel homologue Cette tiquette certifie que le mat riel est conforme certaines normes de protection d exploitation et de s curit des r seaux de t l communications Le minist re toutefois pas que le mat riel fonctionnera la satisfaction de l utilisateur Avant d installer ce mat riel l utilisateur doit s assurer qu il est permis de le raccorder aux installations de l entreprise locale de t l communications Le mat riel doit galement tre install en suivant une m thode accept e de raccordement Dans certains cas les fils int rieurs de l entreprise utilis s pour un service individuel la ligne unique peuvent tre prolong s au moyen d un dispositif homologu de raccordement cordon prolongateur t l phonique interne L abonne ne doit pas oublier qu il est possible que la conformit aux conditions nonc es ci dessus n emp che pas la d gradation du service dans certaines situations Actuellement les entreprises de t l communications ne permettent pas que l on raccorde leur mat riel aux prises d abonn s sauf dans les cas precis pr vus par les tarifs particuliers de ces entreprises Les r parations du mat riel homologu doivent tre effectu es pas un centre d entretien canadien autoris d sign par le
25. shed or in garages is not normally recommended For additional protection the NFPA recommends that you install heat or smoke detectors in the living room dining room bedroom s kitchen hallway s attic furnace room utility and storage rooms basements and attached garages In addition we recommend the following e Install a smoke detector inside every bedroom where a smoker sleeps e Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely closed Smoke could be blocked by the closed door Also an alarm the hallway outside may not wake up the sleeper if the door is closed Install a smoke detector inside bedrooms where electrical appliances such as portable heaters air conditioners or humidifiers are used Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet 12 meters long e Install smoke detectors any room where an alarm control is located or in any room where alarm control connections to an AC source or phone lines are made If detectors are not so located a fire within the room could prevent the control from reporting a fire or an intrusion A KITCHEN DINING _ BDRM LIVING ROOM BDRM Smoke Detectors for Minimum Protection Smoke Detectors for Additional Protection A Heat Activated Detectors KITCHEN A TV ROOM 9 DINING Recommendations For Proper Intrusion Protection F
26. sons F or example e Intrusion detectors eg passive infrared detectors smoke detectors and many other sensing devices will not work without power Battery operated devices will not work without batteries with dead batteries or if the batteries are not put in properly Devices powered solely by AC will not work if their AC power supply is cut off for any reason however briefly Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver Even if the signal path has been recently checked during a weekly test blockage can occur if a metal object is moved into the path A user may not be able to reach a panic or emergency button quickly enough While smoke detectors have played a key role reducing residential fire deaths in the United States they may not activate or provide early warning for a variety of reasons in as many as 35 of all fires according to data published by the Federal Emergency Management Agency Some of the reasons smoke detectors used in conjunction with this System may not work are as follows Smoke detectors may have been improperly installed and positioned Smoke detectors may not sense fires that start where smoke cannot reach the detectors such as in chimneys in walls or roofs or on the other side of closed doors Smoke detectors also may not sense a fire on another level of a residence or building A second floor detector for example may not sense a first floor o
27. the Security System should be carefully tested as follows Test Mode 1 With the system in the disarmed state check that all zones areintact NOT READY message 15 displayed press the key to display the faulted zone s Restore faulted zone s if necessary 2 Enter the Security Code 5 TEST The following will occur e The outside sounder will sound for 1 second e A test report will be transmitted if programmed to the Central Station immediately If the backup battery is discharged or missing the sounder may not turn on and a LOW BATTERY report will be transmitted with a TEST report 3 Fault and restore each zone e Thekeypad will emit beeps each time a contact is faulted e The keypad will beep once per minute as a reminder that the system is in the Test Mode 4 Exit this mode by entering the Security Code 1 Armed System Test Alarm messages will be sent to the central station during the following tests Notify them in advance that tests will bein progress 1 Armthesystem and fault one or more zones 2 After 15 seconds if optional dialer delay is selected silence alarm sounder s by entering the Security Code OFF Check Entry Exit delay zones 3 Check the keypad panic alarms that in the system by pressing the Panic key key pairs on some keypads e If the system has been programmed for audible emergency the keypad will emit a steady alarm sound and ALARM and Zone Number
28. tion TABLE OF CONTENTS RECOMMENDATIONS FOR PROPER PROTECTION 5 Section 1 GENERAL 6 FEATURES atteste te ta he eens teaser ts An 6 SPECIFIGATIONSE Se a 6 COMPATIBLE DEVICES 6 ZONE RESPONSE CHARACTERISTICS 7 WIRING GUIDELINES usine 7 Section 2 SYSTEM INSTALLATION AND WIRING ss ss 8 Section 3 PROGRAMMING THE 5 5 1 9 THE MECHANICS OF PROGRAMMING 2 4 4000 9 Entering Program Mode 9 Programming a Data Field 9 Reviewing a Data Field 9 Erasing an Entry a Data Field 9 Downloa INN tannins 9 Clearing All Data 9 Exiting Program 9 Section 4 SYSTEM 10 USER ACCESS 5 cates 10 Adding a Secondary User Code 10 Deleting a Secondary User Code 10 KEYPAD FUNCTIONS ie enr 10 SYSTEM COMMANAS 10 Panic
29. uld affect the operation of the equipment If this happens the telephone company will provide advance notice in order for you to make the necessary modifications in order to maintain uninterrupted service If trouble is experienced with this equipment please contact the manufacturer for repair and warranty information If the trouble is causing harm to the telephone network the telephone company may request you remove the equipment from the network until the problem is resolved There are no user serviceable components in this product and all necessary repairs must be made by the manufacturer Other repair methods may invalidate the FCC registration on this product This equipment cannot be used on telephone company provided coin service Connection to Party Line Service is subject to state tariffs This equipment is hearing aid compatible When programming or making test calls to an emergency number briefly explain to the dispatcher the reason for the call Perform such activities in the off peak hours such as early morning or late evening 11 CANADIAN DEPARTMENT OF COMMUNICATIONS DOC STATEMENT NOTICE The Canadian Department of Communications label identifies certified equipment This certification means that the equipment meets certain telecommunications network protective operational and safety requirements The Department does not guarantee the equipment will operate to the user s satisfaction Before installing this equipment user
30. x key to display faulted zones SUMMARY OF SYSTEM COMMANDS HOW TO PERFORM EXIT DELAY ENTRYDELAY PERIMETER INTERIOR ARMED ARMED f oree e S e e Od INSTANT f oree e S e SS O mmm soro es es DISARM A A BYPASS Security Code 6 gt QUICK BYPASS Security Code 6 Nene CHIME MODE Security Code 9 OOMS S ewes f Wess e E e DOWNLOAD Initiates phone call to the downloading facility Panic Keys A panic function is activated when Both keys of the appropriate key pair are pressed at the same time or e The appropriate lettered key is pressed for at least 2 seconds The panic functions are identified by the system as follows as Zone Zone Notes 1 amp amp or Keys are not on all keypads x amp or Programmable 24 Hr D if present is not active here Silent Audible Auxiliary or Fire BI amp orlc 24Hr Audible Keyswitch LED Indications Keyswitch Operation RED meane ToarmAWAY turn key and release within 1 2 second Torr DISARMED amp NOT READY Toarm STAY turn and hold key for longer than 2 seconds OFF DISARMED NOT READY e Todisarm turn key and immediately release SLOW FLASH ARMED READY RAPID FLASH ARMED 10 Section 5 TESTING THE SYSTEM After installation is completed
Download Pdf Manuals
Related Search
Related Contents
CLASSIC-DSP - Nobreak & Cia Model 9120 Gigabit Ethernet Media Converter User Manual MAX 15 MAX 20 CERTIFICAT D`EXAMEN DE TYPE 取 扱 説 明 書 Boiler Manual CK152 Mode d`emploi NuTone 235 User's Manual Hotpoint DD77 DT77 Oven User Manual Copyright © All rights reserved.
Failed to retrieve file