        PT2060-53-User Manual
         Contents
1.             Save    Save As          System Setup          Rack Setup          Exit    Figure 4    Menu item Communication  gt Upload is used to upload all messages of the PT2060 rack currently connected  to the computer and Communication  gt Download is used to download all messages configured in the  computer to the currently connected PT2060 rack     From Communication Setup  connection with PT2060 monitor can be established  Setup communication  parameters and click button Download to re set the parameters for the PT2060 rack     da PI2060 CORFICURATION        tee Hack Calibration    Upload  Download          Communication Setup          Figure 5    ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  10    PT2060 53 O SPEED Over speed System    Communication Setup    Protocol     e MODBUS RTU    C MODBUS TCP    Figure 6       Menu item Rack relates to rack operations  Its sub items are listed below     Rack Clock Setup  Setup system clock for the PT2060 rack    Rack Reset  Reset all alarms of the PT2060 rack    Factory Information  Operations related to factory information    Configurable Modbus Registers  Operations related to Modbus Registers of the rack   Signal Module Control  Operations related to alarm bypass and Alarms Trip multiply alarms   Self Test  To make the rack go into self test mode  This is useful for troubleshooting     IGURATION  on Bee  Calibration Status Event Securit     Rack Clock Setup     Rack Reset   
2.       Mrovib lech    Innovative Machine Monitoring       PT2060 Monitor    PT2060 53 O SPEED Over speed System  User Manual    Installation  Operation  Maintenance    PT2060    D  S      Se KC  m PT2060    MEA e       ProvibTech  Inc  11011 Brooklet Drive  Suite 300  Houston  Texas 77099  USA    Phone   1 713 830 7601  Fax   1 281 754 4972  Email  pvt provibtech com   Web  www provibtech com  PT2060 53 USR A 11 COPY RIGHT PROVIBTECH 2007       N  PT2060 53 O SPEED Over speed System    Contents    Receiving Inspection and Handling CGude 3  Jee e E 3  Handling and Storing Consideratons  3   PRT2000  593 VIC OUST OCCU OA WEE 4  Sie Wall MT ORM le e EE 4  Noaue ESS ai e TEE 6   m  ll EE 6  EE 6  IS CIN CANONS ee 6  Set  er EE 6  SEENEN ee 8  Seu le 8   Module Configuration and Channel Setup               ccccseeccceceeeeeeeeeeeeseeeeeeeeeeeeeseeeeeeseeueeesseeeeeeseeseesseeeeesseeseeesaees 9  Hardware Configuration EE 9  Module Type  Channel Configuration Setting            cccccccsceeceesseeeeseeeeeeseeeeeeeseeseeesseeeeeeseeeeeeseeeeesaeeeesanaeeees 9   Configuration Software General Operation              cccccccseeceeeeeeeeeeeeeeeeeeseeeeeeeeeeeesaaeeeeeaaeeeesseneeesaeeeeeeaaees 9  PT2060 53 O SPEED Module Function Descrpton     12  Parameter Configuration             cccccccccseeeceeceeeeeeceeeeeeseeeeeeeeeeeeesaeeeesaeeeeeeseaseeessaeeesseeeeeeseaeeeesaeeeeesaaeeees 13  Transducer Mm  ete eee SE E E E aE a a E a 19  Module Control and Real time Montong    20   Hardware Mod
3.     Signal Module Control     self Test      Factory Information       Customized Modbus Registers          Figure 7    Menu item Calibration contains two subs  User Calibration and Factory Calibration  Users could perform User  calibration only         ck DRARQS Staton  StatusfEvent Sect    User Calibration     Factory Calibration    d                Figure 8    Menu item Status Event contains operations related to current status and alarm history  recent 500 records    such as reading or deleting  Its sub item Real time Value and Status is used to display the messages of all  channels  Sub item Modbus Range Setup is used to set a coefficient to PT2060 in order to make it compatible  with other devices based on the standard Modbus        ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  11    PT2060 53 O SPEED Over speed System       ion     LTE Security Help      Modbus Range Setup         Real Time Value And Status  gt     Overall Record     Channel Status Record     Module Status Record     Rack Status Record       Alarm Event       System Event     Rack Event Reset          Figure 9    Item Security is used for security consideration  Here you can enter different passwords for different  permissions  The Factory Password allows factory permission and is for the factory staff only  However  you  can modify the passwords here and set effective time for them  If the period is expired  password should be  reentered to go on wor
4.     The maintenance of PT2060 53 O SPEED Over speed System includes two parts  PT2060 53 O SPEED  module and PT2060 43 R RELAY module  The former is described in this section and the latter is referred to  PT2060 43 R RELAY Redundant Relay Module User Manual     Components inside a PT2060 53 O SPEED module can not be repaired in the field  The maintenance  mentioned here means to check channel working status and determine whether it is in good condition  If the  linearity of some channels is not perfect  user could perform current calibration  If other faults are discovered   please substitute for it with another spare part     It is described how to check channel working status and how to calibrate output current in several sections   v   Periodic maintenance   Tool preparation   Build of maintenance environment   Software operation   Module check   Current calibration    Ss SS SN  e ON    Exceptional module treatment  Periodic Maintenance    The time interval is very important for PT2060 maintenance  Generally  a yearly maintenance is sufficient  If  the equipment is used in an extraordinary circumstance  user should shorten the maintenance interval  according to the situation in the field     Extraordinary circumstance means that   v _ PT2060 is used to monitor some critical equipment   v __PT2060 works in high temperature  high humidity  and high corrosive environment  Besides  the maintenance interval should be adjusted according to the present result     Preparations   
5.    Transducer input Module output    TM0180 5m  TM0180 9m  TM0105 5m  TM0105 9m  TMO0110 5m  TMO0110 9m  3300 8mm 5m  5mm 5m  3300 8mm 9m  5mm 9m  Proximity Transducer   7200 8mm 5m  5mm 5m  7200 8mm  9m  5mm 9m Over speed  3300 11mm 5m  3300 11mm 9m  7200 11mm 5m  7200 11mm 9m  Other 8mm Proximity probe transducer  Other 5mm Proximity probe transducer  Other 11mm Proximity probe transducer          Magnetic pickup TMO0605    ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972  19    sales provibtech com   www provibtech com    PT2060 53 O SPEED Over speed System       Module Control and Real time Monitoring    PT2060 53 O SPEED Over speed System can measure rotation speed and give out high speed alarm via the  PT2060 System Configuration software  The description in this section is based on PT2060 System  Configuration software  For more detailed information  please refer to PT2060 System Configuration software  user manual     ea PT2060 CONFIGURATION   File Communication Rack Calibration ARATO SONA Security Help   Modbus Range Setup    e  Peak Value Setup    et  Real Time Value And Status P List      BarGr aph  Single channel             Overall Record     Channel Status Record     Module Status Record     Rack Status Record             Save         Alarm Event       a   System Event    PT2060    d Rack Event Reset       D   re  Download 8 e w  E    Report       vr    A  PT2060    A   A   A   a A   A  A N N N SV N  N  1  Exit    S K   K   K   L   A e e e   ge E      Help
6.  H        Figure 17    Calibration  control  and maintenance of PT2060 53 O SPEED module are performed with PT2060 System  Configuration software which is shown in above figure     When PT2060 is in RUN state  from menu item Status Event  gt Real Time Value and Status  gt List open the  real time monitoring window  as shown in the following figure     Real time Value And Status       19 0 RPM  10 0 v False False False     40 um  10 3 v False False False  314 um  7 5    True True False    ch b b b  anna  awn    Figure 18    In this window Real time value  GAP value  alarm message are shown  Rack number  slot number  channel  number are seen at a glance  Besides  PT2060 53 O SPEED modules can save various history events and  working status including alarm events  system events  channel status records  module status records  and  rack status records  Refer to section Troubleshooting     PT2060 53 O SPEED modules support alarm bypass  self test functions  Alarm bypass is segregated into  software bypass and hardware bypass  Self test is implemented through software control  In the PT2060 53  O SPEED Over speed System  PT2060 53 O SPEED module channels  which is set to measuring speed     ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  20    PT2060 53 O SPEED Over speed System       does not support Alarms Trip multiply alarm  Working in other type of systems  it behaves the same as  PT2060 10 PROX module  See section PT2060 10 PRO
7.  Tool Preparation    The following tools are needed for PT2060 53 maintenance    v One Personal Computer   Two digital multi meters for voltage measuring and current measuring  Signal generator   Oscilloscope   Some terminals    Ss SS ON    ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  Zi    PT2060 53 O SPEED Over speed System       Build of Maintenance Environment    Follow these steps to build maintenance environment    1  Make test terminals   Refer to Appendix for the procedure    2  Make bypass terminals   Refer to appendix for the procedure    3  Install PT2060 System Configuration software in a PC    4  Connect the PT2060 to a PC using a communication cable    5  Save the configuration setting of PT2060 to maintain to a file  Power it off  demount it from the equipment   and move it to a workbench     Application Advisory    ProvioTech recommends strongly that the original configuration    setting must be uploaded and saved before performing any  modification to it and restore it after maintenance has been done        6  Geta signal generator set  and the oscilloscope ready   7  Get two multimeters ready     Software Preparation    You should be familiar with these functions    v Upload  download  save configuration parameters  v __Enable disable channels and alarms latching   v   Bypass channels    latching   v Observe real time value and status    On powering on and open the configuration software  the system upload
8.  enabled channels are ok  No digital communication  This means the PT2060 53  O SPEED module has a problem with communication    Off  One or more channels are not ok     lf OK   IO green LED is off  the reason may be  some of enabled channels have GAP alarms  the connection  to transducers has broken  the proximity transducers are damaged  module is damaged  If the first reason  caused the problem  there is a 15s delay before the module changes from NOT OK status to OK status     Try these to solve the problems  adjust transducers    position to make the GAP value normalized  remount the  module  reset  check probes and connection cable     Alarm LED    On  One or more channels have alarms  When alarm type is Alert  the alarms can be either alert or  danger or both  When alarm type is GAP  the alarms can be either GAP or danger    Off  All channels on the module are in normal status  No alarms engaged    If Alarm red LED does not work  it may be caused by that  the module is failed  transducers are broken  Try  these to solve the problem  remount the module  reset  check probes and connection cable     Bypass LED    On  PT2060 system is in hardware Bypass mode  All alarms on this module are inhibited from alarming    no alarms will be engaged   PT2060 53 O SPEED module   s real time values and current outputs are not  affected    Off  Abnormal operation mode   e    ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  34    PT2060 5
9.  maximum input frequency of 10 kHz   Start at 1RPM  0 0167Hz  for proximity probes  Start at 200RPM  3 3Hz  for magnetic pickup    ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  6    PT2060 53 O SPEED Over speed System       Sensors   Proximity probes  Magnetic pickups  Overall in 4 20mA Output   Maximum distance   300m  1000ft   Proportional to monitor full scale  each channel has its own overall speed output  The short of the  4 20mA will not affect system performance   Maximum Load   3000  Accuracy      0 1RPM   lt  100RPM      1 0RPM   gt  100 and  lt  10 000RPM   0 01    gt  10 000 and  lt  60 000RPM   Threshold   Auto    gt  1 0 V pk pk  Manual    gt  0 5 V pk pk  Trigger level can be programmed from  17VDC to  3VDC  Hysteresis   0 5   2 5 V user selectable  Alarm Time Delay    lt  30ms for frequency  pulses  over 300Hz  Rack Space   Require four slots for an over speed protection system   Buffered Output   On the front panel  each channel has one BNC connector  The output is the unfiltered raw signal   Output impedance   5500  Maximum distance   300m  1000ft   Proximity Transducer Power    24V DC  current limited  Less than 50mA on each channel  Alarm   Alarm set point   Each channel has single alarm set point which can be field adjusted from 0 to 100  FS   Set point accuracy      1 RPM  LED Indicators   OK   IO  green  Alarms  red  Bypass  red  Approvals   CE     ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 
10.  nominal voltage that the Hysteresis is centered about  The system gives a default  value  When Manual Threshold is selected  user could modify it manually or by clicking the button Adjust to let  the system get it automatically  Default is  10V    Full Scale High  Full Scale Low   These determine the low limit and high limit of full scale  Full scale low is set to 0 by default  Full scale high  can be set by user as per actual situation  After these are set  the alarm hysteresis is determined  Alarm  hysteresis default is 1ORPM constantly    Notes  All set points have an Alarm Hysteresis value  The Alarm Hysteresis band for an over set point is  below the set point and the Alarm Hysteresis band for an under set point is above the set point  For example   if an over speed set point is set at 3 000 rpm  the hysteresis is 10RPM  The module would enter over speed  alarm at 3 000 rpm but would not go out of alarm until the speed has fallen to 2 990 rpm    Measurement Type   User could choose desired type from the drop list  Default is NA    Measurement Unit   From the menu item File System Setup a window  like the following figure  can be opened where user could  alternate the measurement unit  For over speed measuring  it is RPM constantly     C English Unit    Figure 13       Alert Type   Alert type means that PT2060 53 O SPEED modules give out alarm message  when the measured value  exceeds or equals to alert and or danger set point assigned by PT2060 System Configuration  Eve
11.  with a signal correspond to 50  of full scale  the output current should be 12 0 16mA   Demount the lower power module and observe the output current whether it is stable  Remount the lower  power module and demount the upper power module and observe the output current     Current Calibration    Users should not repair the components inside PT2060 53 O SPEED modules  However  if some channels     linearity is not satisfied after the testing  user can perform current calibration     1  Connect the red pen of an ampere meter to OUT pin of the current output port  connect the black pen to  COM pin of that port    2  Click menu item Calibration  gt User Calibration and enter password to open calibration window  See the  following figure  Select the slot number and channel number to be calibrated     User Calibration    Slot 5   Channel H      4 20mA  Calibration    Full scale low Zero  Calibration       Full Scale high Calibration          Figure 28  3  The whole procedure is implemented in the 4 20mA Calibration   Click the button Full scale low Zero  Calibration to open the zero calibration window figure 29   Follow the  steps showed in the window to perform calibration  First  click the button Start Calibration in step1  then read  the output current value from multimeter  after it settled down  Enter this value  three significant decimal digits   in the text area in step2   After that  click the button Full scale low Calibration in step3 to download  Wait till  the multimete
12. 060 rack  Click one of these  items to get its detail event list in the right field  By browsing this event list  you will be able to know what  happened recently  It may help you to solve your problem     If you could not solve the problem by yourself  please save these messages for ProvibTech service staff   Exceptional Module Treatment    If you find PT2060 53 O SPEED modules in problem from the above analyses  please contact ProvibTech  office     ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  37    PT2060 53 O SPEED Over speed System       Additional Information    Ordering Information    A PT2060 53 O SPEED module consists of a front panel and a back panel  Please make your order as per  the code   PT2060 53 AX   AX  Back panel IO module  AO  Basic IO module    Optional Accessories    There are several accessories for selecting   PT2060 005300  PT2060 53 Front panel  PT2060 005301  PT2060 53 Back panel    Examination    The encapsulation of PT2060 can protect modules from all kind of damage  As soon as the reception  user  should examine the conducts whether it is damaged and whether it is caused by transportation  Please  contact the carrier  if it happened     If no damage is found and the system does not work properly  please check the user manual first  If the  problem can not solve  please contact the closer ProvibTech office     Factory Default Configuration    When customers purchase PT2060 53 O SPEED Over speed 
13. 14 59 98C  The module entered the run model 2009 4 30 13 14 59 98C  The module entered the run model 2009 4 30 13 14 59 98C  The module entered the run model 2009 4 30 13 14 59 98C  The module entered the run model 2009 4 30 13 15 00  OY    Figure 34    OOWNIA OO Bw 4    pare ES     oo       Click the button Upload at left bottom corner of the window to obtain the new system events  In the left area   there is a list of upload time which is the time you perform an upload from PT2060 rack  Click one of these  items to get its detail event list in the right field  Event without channel number means it does not concern any  channel  Take the highlighted line in figure above for example  the PT2060 53 O SPEED module in slot 6  entered run model sometime  By browsing this event list  you will be able to know what happened recently  It  may help the user to solve some problems     If you could not solve the problem by yourself  please save all information for ProvibTech service staff   Alarm Event List    Like system event  the software deals with alarm event list in the same way  It also keeps 500 recent alarm  events     Click menu item Status Event  gt Alarm Event of the software to open a new window like the figure below     ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  36    PT2060 53 O SPEED Over speed System    Alarm Event Record    Upload Time Check Value    2009 04 30 11 10 24 Alarm Time  2009 04 30 11 15 02 Entered Dange
14. 3 O SPEED Over speed System       lf Bypass red LED does not work  it may be caused by that  the PT2060 53 O SPEED module fails  In this  case  please contact ProvibTech office     Real time Value and Status    From Real time Value and Status interface  you may acquire something useful     Real time Value And Status              19 0 RPM  10 0 v False False False     40 um  10 3   False False False  4 314 um  7 5    True True False    ech b   ech b  annn  LA P      Figure 33  Alert    False    When alarm type is Alert  it means there is no Alert alarm  When alarm type is GAP  it means there is  no GAP alarm    True  When alarm type is Alert  it means there is an Alert alarm  When alarm type is GAP  it means there is  a GAP alarm     Danger    False    There is no Danger alarm  in despite of the alarm type   True  There is a Danger alarm  in despite of the alarm type     GAP not OK    False    The channel is in okay status    True  The channel is in GAP not OK status  The reason may be that  the transducers    GAP voltage is out  of range  some transducers are broken  the connection cable is not reliable  If the first reason caused the  problem  there is a 15s delay before the module changes from GAP not OK status to OK status     System Event List    PT2060 53 O SPEED modules    system event list will be displayed in the software PT2060 System  Configuration  It lists 500 recent events   Select Status Event  gt System Event from the main menu  go into this interface as shown 
15. AP voltage  and 4 20mA current to users  It also provides alarm status  and OK status to PT2060 43 R RELAY Redundant Relay module of the system  The PT2060 43 R RELAY  module receives the messages from PT2060 53 modules and conducts Boolean calculation of these  messages and output calculated result trough the LEDs  and the relays  Working in the over speed system   PT2060 43 R RELAY Redundant Relay module can run in Default 53 Mode or Individual Mode  For more  details  please refer to PT2060 43 R RELAY Redundant Relay Module User Manual     Warning    When the 3  and the AT channel of a PT2060 53 O SPEED module  are used as PT2060 10 module  its operation and configuration are  the same as the normal PT2060 10 PROX module  Please refer to  PT2060 10 PROX manual for more information     This manual describes the application of PT2060 53 O SPEED  module in O SPEED system mainly        The system should be installed in the rack and configured by software PT2060 System Configuration  PT2060  System Configuration configures parameters for PT2060 53 O SPEED System  It will also display various  messages including real time value  GAP voltage and alarm status  alarm event and system event     ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  5       2 PT2060 53 O SPEED Over speed System    Module Description    Hardware    The hardware of PT2060 53 O SPEED Over speed System consists of up to three PT2060 53 O SPEED  modules and one P
16. IE ours       A ol E CONI    74 ours  E    ovt E  oe    Si  1         RS485 SHIELD SHIELD  ay  I On  O  0  O CH Oh O  C4 dr  i  Ke A d  Ke      V  ome  f        f d    Oo   d      o A  o ER  o     oO   _   Mees  o      E IT  AJ A 3  ei UN    Figure 2    Module Type  Channel Configuration Setting    Configuration Software General Operation    PT2060 System Configuration software is an important part of configuring  controlling and maintaining the  PT2060 system  The software is used to configure PT2060 internal parameters and display PT2060 running  status  Refer to PT2060 System Configure User Manual for its details     ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  9    PT2060 53 O SPEED Over speed System       The figure below is the main frame window of PT2060 System Configuration  where are seven main menu  items     ea PT2060 CONFIGURATION    File Communication Rack Calibration Status Event Security Help    Wy Proviblech    Save  Upload 3 3 4   PT2060    G      Download    Report           e   ERT 2060  Ay Ay A  A SAS A SAS   A  A  A  A d d d   Exit     lt   lt   lt  L   Ss Ss Ss L    lt   lt  E F e 7       Help  H     K         Figure 3    Menu item File relates to file operations such as open  save and save as of a configuration file  Also  the item  System Setup in it is used to alternate the system measurement unit  See the figure below        ra PT2060 CONFIGURATION        SOR  Communication Rack Ca          Open   
17. It  needs configuration password when first download or  The default password is 1234     ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  13    PT2060 53 O SPEED Over speed System    Configuration Password    Password       Figure 12       Warning    PT2060 is unable to alarm and protect in configuration status       Warning    ProvioTech recommends strongly that the original configuration  setting must be uploaded and saved before performing any  modifications to PT2060 53 inner parameters        In PT2060 53 O SPEED Over speed System  the configuration procedure of PI2060 43 R RELAY  Redundant Relay module is referred to PT2060 43 R RELAY Redundant Relay Module User Manual     PT2060 53 O SPEED modules support over speed measure  Proximity probes or magnetic pickups should  be mounted in radial direction     PT2060 53 O SPEED modules measure the shaft rotation speed  provide measured message to the user   and give alarm messages to the PT2060 43 R RELAY Redundant Relay module to implement the function of  over speed protection     While working in the PT2060 53 O SPEED Over speed System  only the first channel of PT2060 53  O SPEED module is in use  Its configuration procedure is the same as of PT2060 10 Speed     Configuration Considerations    Consider the following items before configuring a PT2060 53 O SPEED Over speed System    1  All modules in the Over speed system must have identical configurations    2  Athree modul
18. It is also directly output to the redundant alarm module for process     ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  4       N  PT2060 53 O SPEED Over speed System    A PT2060 53 O SPEED System consists of three PT2060 53 O SPEED modules and one PT2060 43  R RELAY Redundant Relay module  A standard 19  PT2060 rack can contain three such systems at most   slot 1 4  slot 5 8 and slot 9 12 are the defined slots to hold the sub systems  PT2060 43 R RELAY modules  can be mounted in slot 4  slot 8 or slot 12 only  A standard 12    PT2060 rack can contain one such system  slot  1 4  In the case  PT2060 43 R RELAY module is mounted in slot 4  Three PT2060 53 O SPEED modules  must be installed in three adjacent slots  For example  three PT2060 53 O SPEED modules installed in slot  1 3 and a PT2060 43 R RELAY module installed in slot 4 constitute an over speed system     A PT2060 53 O SPEED module contains three channels  the first channel is an over speed protection  channel  channel 3 and 4 can be used as two PT2060 10 channels  Any PT2060 10 mode can be configured  into these two channels    For PT2060 53 O SPEED Over speed System  the PT2060 43 R RELAY Redundant Relay module works  only with the first channel of the PT2060 53 module  The rest of the channels will have no effect to the relay  module     In PT2060 53 O SPEED Over speed System  PT2060 53 O SPEED modules measure machine rotation  speed and provide real time value  G
19. System  if no detailed request  it will be  configured with the following setting and shipped to the customers     PT2060 53 O SPEED Module Configuration Setting    Channel 1   Channel Type  Overspeed   Transducer Type  TM0180 5mm Channel Enabled  checked  Transducer Sensitivity  8 Omv um Alarm Latching  checked  Teeth per Cycle  60 Danger High  4500RPM  Hysteresis Voltage  1V Alert High  3000RPM  Full Scale High  6000RPM GAP High   24V   Full Scale Low  ORPM GAP Low   1V  Measurement Unit  RPM Threshold Type  Auto  Alert Type  Alert Signal Polarity    Notch    ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  38       2 PT2060 53 O SPEED Over speed System    Appendix    Terminal for Proximity Probe    Take an 8 pin plug pin distance 3 8mm  like what is shown in the figure below  a potentianmeter of 10KOhm  and an electrolytic capacitor of 220UF 50V  1000UF 35V if used for low frequency testing   Solder the  movable pin of the potentialmeter and the negative pin of the electrolytic capacitor together and then connect  it to SIG pin on the port  Connect the other two pins of the potentialmeter to PWR and COM respectively  Left  the positive pin of the electrolytic capacitor float  through which the signal will come in     Potentialmeter    Signal Generator    G be L  PWR XX XXXXXX HZ  COM O    SHD   moomoo  PWR  a       Figure 36    Terminal for Magnetic Pickup    Take an 8 pin plug  pin distance 3 8mm  like what is shown in the 
20. T2060 43 R RELAY Redundant Relay module     PT2060 53 O SPEED module has status indication on board  There are three LEDs that display different  status of the monitored channels on front panel  There are four BUFs of the four channels and 4 20mA  current output port on the back panel  This manual mainly describes the application of PT2060 53 O SPEED  module in PT2060 53 O SPEED Over speed System  The functions of PI2060 43 R RELAY  Redundant Relay module are described in PT2060 43 R RELAY Redundant Relay Module User Manual     Software    PT2060 53 O SPEED Over speed System needs PT2060 System Configuration to cooperate with it   Relevant introduction of the software is described in PT2060 10 PROX Proximity Module User Manual and  PT2060 system Configuration User Manual  PT2060 43 R RELAY Redundant Relay module relevant  introduction of the software is described in PT2060 43 R RELAY Redundant Relay Module User Manual and  PT2060 system Configuration User Manual     Specifications  Electrical    PT2060 53 O SPEED Over speed System includes three PT2060 53 O SPEED modules and a PT2060 43  R RELAY Redundant Relay module     PT2060 53 O SPEED Over speed Module    Power supply   Internally converted by the rack power supply module  8 0W total typically for each module  Signal Input   Input impedance    gt  20KQ  Input voltage range    10 to  24VDC  Input frequency   The PT2060 53 module will support 1   255 events per revolution with a maximum full scale range of  60000 rpm and a
21. X module maintenance     In PT2060 53 O SPEED Over speed System  PT2060 43 R RELAY Redundant Relay module should be  configured to    53 Default type    or    53 Individual type     The procedure of configuration is referred to PT2060 43  R RELAY Redundant Relay Module User Manual     ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  21    PT2060 53 O SPEED Over speed System       Hardware Module Operation    Besides the software monitoring  PT2060 53 O SPEED module hardware can directly provide some  messages of monitored equipment     There are four BUF on the front panel and four current output ports on the back panel corresponding to the  four channels  This enhanced the versatility of the module  User could acquire desired signals from these  ports in the field  In PT2060 53 O SPEED over speed system  only the first BUF is used on PT2060 53  module     Front  Back Panels and Functions    Front Panel    Via  i    N       Y   A    WK     Fr  gensz  LL O SPEED H                N   f              J d un   aa e SE E F  E  ECH  et VU       W N pag i hon J        gt l 1 BYPASS   N P Al                                S   L  ATIN  W       lii       jj  SNL  LY  VW ji V     D          Figure 19       ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  22    PT2060 53 O SPEED Over speed System       1  OK IOLED   2  Alarm LED   3  Bypass LED   4  Buffered output    The output is raw unfilt
22. aims for damages must be claimed without delay against  the shipper and before the installation     Handling and Storing Considerations    PT2060 should be handled with care during unpacking and installation  Damage to PT2060 is typically  caused by rough handling  shock  or electrostatic discharge  ESD      Be aware of the following precautions when unpacking and handling PT2060 Rack or any module     v Please have attention about the sharp corners sides of the rack to avoid any of injuries during the  installation  transporting and un installation     v All circuit boards and electronic modules associated with this rack contain components which are  susceptible to damage caused by electrostatic discharge  It should be necessary to discharge any static  electricity from yourself and your clothing before handling the rack     v Whenever the module is not installed in a system  always keep it in the protective antistatic bag     ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  3    PT2060 53 O SPEED Over speed System       PT2060 53 Module Introduction    General Information    ProvibTech   s PT2060 53 O SPEED over speed System provides a highly reliable  triple  redundant over speed protection system  PT2060 53 O SPEED over speed module can accept  speed from both proximity probe and magnetic pickup signal input  It can output the following  measurements    v  Over speed protection    The following function only for channel 3 a
23. below     ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  35    PT2060 53 O SPEED Over speed System    System Event Record  Upload Time Check Value    2009 430 13 17 22 EL los   Een Type ___  Event Time  Relay was TITT 2009 4 30 13 14 59 94C  Relay was configured 2009 4 30 13 14 59 94C  The module entered the run model 2009 4 30 13 14 59 94C  Relay was configured 2009 4 30 13 14 59 94C  Relay was configured 2009 4 30 13 14 59 94C    Relay was configured 2009 4 30 13 14 59 94C  Relay was configured 2009 4 30 13 14 59 94C  Relay was configured 2009 4 30 13 14 59 94C  Relay was configured 2009 4 30 13 14 59 94C  Relay was configured 2009 4 30 13 14 59 94C  Relay was configured 2009 4 30 13 14 59 94C  Relay was configured 2009 4 30 13 14 59 96C    The module entered the run model 2009 4 30 13 14 59 96C  Relay was configured 2009 4 30 13 14 59 96C  The module entered the run model 2009 4 30 13 14 59 96C  The module entered the run model 2009 4 30 13 14 59 96C  The module entered the run model 2009 4 30 13 14 59 96C  68 RER REESEN 2009 4 30 13 14 59 960  The module mmer the run model 2009 4 30 13 14 59 96C  The module entered the run model 2009 4 30 13 14 59 96C  The module entered the run model 2009 4 30 13 14 59 98C  The module entered the run model 2009 4 30 13 14 59 98C  The module entered the run model 2009 4 30 13 14 59 98C  The module entered the run model 2009 4 30 13 14 59 98C  The module entered the run model 2009 4 30 13 
24. current output port and  connect the black pen to GND pin on that port  Set the ampere meter to measure direct current  Feed a signal  to the terminal  Connect an oscilloscope to the BUF of the first channel    Turn on the PC and invoke the configuration software    2  Test of powering on   On powering  OK   IO LED and Alarm LED should be on for 3s or so that indicates that the channel is  operating correctly    3  Test of communication   Click the button Upload to obtain the parameters and save them in a safe place  If the upload failed  check  whether PC and PT2060 are set correctly and connected reliably    4  Test of parameter setting   Click the picture of the tested module in the PT2060 System Configuration software main frame window to  open its configuration window where you could make some modifications  After that  you could download it  and re upload it again to compare whether they are changed correctly    5  Test of OK status   Disable PT2060 53 O SPEED modules channel 3 and 4    lf transducer type is one of proximity probes  tune the variable resistor  10kKOhm  of the terminal plugged in  the first channel  Observe OK   IO LED status  it flashes only when all enabled channel are OK   When the  variable resistor is out of the assigned OK range  the OK   IO LED will go off  At this time  the output current is  3 0  0  16mA    If transducer type is magnetic pickup  the OK   IO LED is always on    6  Test of linearity   According to the configured full scale and fre
25. e Over speed protection System is the most reliable    3  When a full scale range is modified  the set points associated with this proportional value should be  re adjusted    4  PT2060 53 Over speed protection System provides fast response relays for shutdown purposes  Do not  use any other PT2060 system relays for Over speed shutdown    5  PT2060 53 Over speed protection System is only one of several components in an Over speed  Shutdown System  All components must be verified for proper operation     ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  14       2 PT2060 53 O SPEED Over speed System    Over speed Parameter Setting    Typical full scale cam be set to 3000  3600  6000  10000  GOOOORPM     Channel Type  Over speed  Transducer Type  PT2060 53 O SPEED modules can interface with many kinds of transducers    TMO0180 5m   TMO0180 9m   TMO0105 5m   TMO0105 9m   TM0110 5m   TM0110 9m   3300 8mm 5m  5mm 5m   3300 8mm 9m  5mm 9m   7200 8mm 5m  5mm 5m   7200 8mm  9m  5mm 9m   3300 11mm 5m   3300 11mm 9m   7200 11mm 5m   7200 11mm 9m   Other 8mm Proximity probe transducer   Other 5mm Proximity probe transducer   Other 11mm Proximity probe transducer   Magnetic pickup  Transducer Sensitivity  This is the most important parameter in monitoring process  The value is related to the transducer type  When  the transducer type is anyone of proximity probes  this value is set by the system and also can be modified  manually  This valu
26. e is typically expressed as millivolt per unit  for example mV mil for displacement   Default  value is 8mv um  When the transducer type is magnetic pickup  this item invalidates   Alert Time Delay  Danger Time Delay  PT2060 53 O SPEED Over speed System doesn t support alarm time delay   Teeth Per Cycle  Teeth number on the gear  The number of input pulses per shaft revolution when observing an integral  multi event signal source  such as a gear  The Events per Revolution may be specified as a number between  1 and 255 with four decimals   Default is 60   User could set it according to the actual value in the field  For  example  if there are 24 teeth on the gear  teeth per cycle can be set to 23 9998 to slightly adjust the  rotation speed according to the need in the field   Hysteresis Voltage  The voltage level above and below the threshold value which is required to  trigger  the input signal from the  transducer  The larger the hysteresis  the greater the immunity to noise on the input signal  When the input  Signal passes the threshold voltage plus 1 2 of the Hysteresis voltage  the signal goes high  When the input  signal returns to the threshold voltage minus 1 2 of the Hysteresis voltage  the signal goes low  The default    ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  15       N  PT2060 53 O SPEED Over speed System    value is 1V and user could modify it between 0 5 2 5V    Trigger Voltage   The Trigger Value is the
27. ent output Full Scale  High   and enter into below field        Figure 32    5  Click the button Exit to go back to the RUN state  You could optionally do linearity test again to check the  calibrating result  If you does not satisfy  you could redo it     Exceptional Module Treatment    Some exceptions may be discovered through the testing mentioned above  Except the linearity problem which  could be solved by recalibrating  users sould treat it in no case  Please substitute it by a spare part and    contact ProvibTech office     ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  33       2 PT2060 53 O SPEED Over speed System    Troubleshooting    PT2060 53 O SPEED Over speed System Troubleshooting consists of two parts  PT2060 53 O SPEED  module Troubleshooting and PT2060 43 R RELAY Redundant Relay module Troubleshooting     Troubleshooting relative to PT2060 43 R RELAY modules is described in PT2060 43 R RELAY  Redundant Relay Module User Manual     This section describes how to solve the problems in operation and analyze the status from the LED  Real time  Value and Status  system event list  and alarm event list     LED    There are OK   IO LED  Alarm LED  and Bypass LED on the front panel  They directly reflect the status of  PT2060 53 O SPEED modules  If something abnormal happened  users could make a simple judgment     OK   IO LED   Flash  All enabled channel are okay  Digital communication is ok    On without flash  All
28. ered sensor signal to portable data collector    5  Channel label   Customer is able to mark channels on the label in the field  Label can be marked by removing the front plastic  cover with a flat screw driver     Back Panel    SIGNAL PROCESS  53 0 SPRED                            z    THERE    PWR    SC    SIG   SHD  PWR    LOCH    SIG   SHD                          o  E   2       b S    SS                                  Figure 20    ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  KK    PT2060 53 O SPEED Over speed System       1  Signal port   The arrow is pointing the port which the channel 1 receives the signal  PT2060 53 module in the over speed  system has only a channel     2  4 20mA output   Be proportional to the full scale  standard 4 20mA output  Connect with PLC or DCS     Field wiring Diagram  Field wiring Diagram for all 5mm  8mm and 11mm Probe Systems    NEP   SIGNAL PROCESS    10 PROX          PROBE                                                                                           PWR  D    Sic    enn  E  mp    ON E   siej seg  enn  JI                       Z                            COM    4 20mA to PLCIDCS                                                                                        oN             Figure 21    ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  24    PT2060 53 O SPEED Over speed System       Field wiring Diagram for Magnetic P
29. figure above and two short wires  Connect  one wire to SIG  and other wire to COM     Bypass Terminal    Take a six pin plug  centre distance 3 8mm   and short RST_BY and GND pins according to the label on the  back panel of the PT2060 91 SIM module     Alarms Trip multiply Terminal    Take a six pin plug  centre distance 3 8mm   and short ALM_MU and GND pins according to the label on the  back panel of the PT2060 91 SIM module     ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  39    
30. ges in the input signal  Auto threshold  requires minimum signal amplitude of 1Vpp and minimum frequency of 0 0167 Hz   Manual  The trigger threshold is set by the user to any value in the range of  8V to  14V  Manual threshold  requires that the minimum signal amplitude would be 500 millivolt with peak to peak   Signal Polarity   Notch   An output pulse  produced for use by the modules that is triggered by the leading edge of a  negative going pulse in the input signal  If a magnetic pickup is used  set Notch Projection setting to Notch    Projection   An output pulse  produced for use by the modules that is triggered by the leading edge of a positive going  pulse in the input signal   Peak Value   The maximum speed recorded by the PT2060 53 since the last peak value reset occurred  Click the drop  down list Peak Value Setup of menu status Event to open Peak value window where peak value is present   see figure 14 and 15          Calibration Ra Security Help            Modbus Range Setup       Peak Value Setup    d        Real Time Value And Status  gt        Overall Record      Channel Status Record     1 Module Status Record     Rack Status Record       Alarm Event     System Event     Rack Event Reset          Figure 14    ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  17    PT2060 53 O SPEED Over speed System       PT2060 53 retains the peak value even after loss of module power  Click the the Reset button in configurati
31. iable resistor to make it outputs a voltage of about   10V and check the BUF output noise which should be less than 50mV    If transducer type is magnetic pickup  check the BUF directly  the output noise should be less than 50mV   This figure shows how to connect an oscilloscope to the BUF                       Figure 26    9  Test of software bypass   Checking the Channel Bypass switch will cause the module to indicate a  bypass  status but can not  illuminate the module bypass LED  Set Alert bypass and or danger bypass for the tested channel and adjust  the input signal  When the signal reaches the magnitude corresponding to alarm threshold  the machine does  not give alarm signal  i e  it is prohibited    10  Test of hardware bypass   Provide a signal to make the system alarm  Plug in a bypass terminal into the socket on the back panel of  PT2060 91 SIM module  Bypass LED of the PT2060 53 O SPEED module should be on and Alarm LED  should be off  The alarm status in Real time Value and Status window disapear  Unplug the terminal and the  system goes on to alarm    11  Test of voltage   Power supply is critical for PT2060 53 O SPEED module to work properly  Measure the voltages of the  channels as per the figure below  They should be about  24V          EZ    NI ml ml     ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  31    PT2060 53 O SPEED Over speed System       Figure 27    12  Test of redundant power   Provide channel 1
32. ickup Systems       e D   UY   SIGNAL PROCESS  10 PROX             m PROBE    C     White CABLE  _ Rel L    ae  1    Shield e                                                                                              NIO             EROR WH                                     z                                                          ATO LACH       oO  CS     diy  El al                                          Z                                           4 20mA to PLC DCS                                                                                                                            Figure 22    ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  25    PT2060 53 O SPEED Over speed System       Field wiring Diagram for Hazardous Area Application    With TM0412 as the barrier  For other barriers  please consult Provib Tech for tech support        24V DC               Se    J  4                                                                          et   NEO FEO  s                                                                                    O    S  SAFE AREA N HAZARDOUS AREA      x    Se  N    A PROVIBTECH O                        BEQ wna                                                                                                 oe       Figure 23    ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  26    PT2060 53 O SPEED Over speed System       Module Maintenance
33. king         Help    Control Password       Configuration Password       I  n    Factory Password       Modify Control Password     Modify Configuration Password       Password Effective Time Period          Figure 10    The item Help introduces detailed operation steps to the user  It is a quick way to become acquainted with the    software   pecurity           Help i  OVI   itive Mach    About                Figure 11    PT2060 53 O SPEED Module Function Description  GAP not OK    When the GAP voltage is above the Upper OK limit and below the Lower OK limit  the OK   IO LED on the  front panel is off  The GAP not OK status in the window Real Time Value and Status is true  If alarms are true  and those alarms have been configured as latching  after GAP becomes not OK  they retain true     Once a channel has gone not OK status  the output current of this channel is 3 0  0 16mA     Notes  Usually  Alert type can be configured as either alert or gap alarm  When PT2060 53 module is used for  PT2060 53 O SPEED Over speed System  it does not support GAP alarm      _    ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  12    PT2060 53 O SPEED Over speed System       Bypass    This indicates when the module has bypassed alarming  Both digital port and hardware port can trigger  bypass mode  When it is hardware bypassed  the Bypass LED on the front panel comes on  When it is  software bypassed  the LED does not come on  No matter what i
34. ld  There are two levels of alert alarm  It can be  set to some certain percentage of full scale  Danger High is set to 75  and Alert High is set to 50  by default   PT2060 53 O SPEED modules in PT2060 53 O SPEED Over speed System do not support GAP alarm   The GAP OK voltage range is related to the transducer type  When the transducer type is anyone of proximity  probes  this value is set by the system and also can be modified manually  The default settings are  24V and   1V for GAP High and GAP Low respectively  When the transducer type is magnetic pickup  this item  invalidates   Notes  Timed OK Channel Defeat  an option that prevents a channel from returning to an OK status until that  channel s transducer has remained in an OK state for the specified period of time  The time is set to 15  seconds  The time protects against false trips caused by intermittent transducers   Threshold Type  The threshold options are Auto and Manual   The threshold type is related to the transducer type  When the transducer type is anyone of proximity probes   there are two choices  Auto and Manual  If the expected average running speed of the machine is less than  200 RPM  Manual threshold is suggested  When the transducer type is magnetic pickup  the default value is  Auto  The value can t be modified manually   Auto  The trigger threshold is automatically set to a value that is midway between the most positive peak and  the most negative peak of the input signal  This value tracks any chan
35. nd channel 4    v Radial vibration  monitoring shaft vibration  single or dual XY  2 channels    v Axial  Thrust position  monitoring shaft thrust position  with 5mm  8mm  and 11 mm  proximity probes  2 channels    Eccentricity  1 channel    Differential expansion  2 channels    Low frequency vibration  2 channels    Speed output  1 channel    Zero speed and speed  1 channel    Reverse rotational protection output  1 channel     ZS SN  Se NN    Voting    PT2060 53 O SPEED Over speed System supports two out of three voting     Redundancy Requirement    To reach the maximum system reliability  PT2060 53 requires redundant power supplies  Alarms       Trip multiply PT2060 53 modules are required  With three over speed modules  system will  perform two out of three redundant logic     Figure 1    To maximum system reliability  Proviob Tech highly recommend customer utilize three over speed modules and  one redundant alarm module as an over speed protection system     Alarm Option    PT2060 53 of O SPEED System will output alarms to drive the redundant PT2060 43 module  The redundant  alarm module will perform redundant logic or simply deliver the individual alarms from each channel to  up level control system for logic output     The main task for PT2060 53 O SPEED module is to process the incoming signal  compare it with the alarm  set point and output the appropriate status information  The status information will be routed to PT2060  internal bus for other modules to sharing  
36. on  software as the figure 15 shows  the Peak value will be reset to the present speed  Clicking the Reset button  can reset the peak values of the current corresponding slots and channels  while Reset All can reset the peak  values of all the speed type channels     Peak Value       Slot No   H   Channel No   f1    Peak Value    Upload      Figure 15          The following figure is an example of configuration     53 Overspeed Module Configuration    Slot No  11 Channel No  fi    copy          Parameter    Channel Type   Overspeed D jw Channel Enabled  Transducer Type   TM0180 5m D Iw Alarm Latching    Transducer Sensitivity  i ora  l Danger High   a500 RPM    Alert Time Delay   Alert High   3000 RPM  Danger Time Delay   Alert Low   0 RPM    RPM    Danger Low     Zero Position Gap     10 Adiust SS  GAP High  EI v  Hysteresis Voltage  GAP Low  AN S    Trigger Yoltage Gap      Teeth Per Cycle           Transducer Direction  Full Scale High     rd Probe       Full Scale Low   C Threshold Type    Measurement Type  C Manual   Auto       Measurement  Unit   Rotate Speed Alarm Type    Alert Type            Signal Polarity     e Notch C Projection    Frequency Type     Primary PR  wa  e Ka BE    Backup PR   na   Alarm Hysteresis       Figure 16             ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  18    PT2060 53 O SPEED Over speed System       Transducer List    The transducers PT2060 53 O SPEED modules can be connected with  
37. quency in the field  provide a signal to the first channel using a  generator set  Check the output current to see whether it suffices the linearity requirement  If it is not perfect     you can perform recalibration        4 20mA  mA  4 00 0 16 8 00 0 16 12 00 0 16 16 00 0 16 20 00 0 16       Notes  The magnitude of the input signal is 8V  Change the frequency as per the full scale  If the current full  scale is 0 6000RPM  number of teeth is 1  then the frequency should be in the range 0 100Hz    7  Test of alarm   Disable the PT2060 53 O SPEED module   s channel 3 and 4  Provide a signal to the first channel  Observe  the change of the Alarm LED  when the signal exceed or equal to any set point and check the status in the  Real time Value and Status window    If the channel is not alarm latched  the alarm status will be reset after the input signal is removed  Otherwise  it  can be reset only by pressing the button RESET  or clicking menu item RACK  gt Rack Reset Setup   Check  the status in the Real time Value and Status window  This part has also relation to alarm hysteresis    8  Test of BUF   If necessary  users can perform BUF testing    Tune the signal generator and monitor the BUF output with an oscilloscope which should be conformable with  e    ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  30    PT2060 53 O SPEED Over speed System       the input one    If transducer type is one of proximity probes  adjust the var
38. r High 2009 04 30 8 48 34 4  Entered Danger High 2009 04 30 8 48 34   Entered Alert High 2009 04 30 8 46 36   Entered Alert High 2009 04 30 8 48 36    Left Danger High 2009 04 30 10 15 34   Left Alert High 2009 04 30 10 15 34   Left Danger High 2009 04 30 10 15 35  Left Alert High 2009 04 30 10 15 35  Entered Danger High 2009 04 30 10 54 54   Left Danger High 2009 04 30 10 54 55   Entered Alert High 2009 04 30 10 55 14   Left Alert High 2009 04 30 11  2 e  A TEE TET  Entered Alert High 2009  03  18 14  48  a  Left Danger High 2009 03 18 14 58 25  Left Alert High 2009 03 18 14 56 25  Entered Danger High 2009 03 18 14 58 26   Entered Alert High 2009 03 18 14 58 28   Left Danger High 2009 03 18 14 58 31   Left Alert High 2009 03 18 14 58 31   Entered Danger High 2009 03 18 14 56 32   Entered Alert High 2009 03 18 14 58 34   Left Danger High 2009 03 18 14 59 13   Left Alert High 2009 03 18 14 59 13   Entered Danger High 2009 03 18 14 59 15   Entered Alert High 2009 03 18 14 59 17   Left Danger High 2009 03 18 15 01 45   Left Alert High 2009 03 18 15 01 45   Entered Danger High   2009 03 18 15 02 41       FAA AT AG Ar en am    E    OO JO Om P D        3  4  d  3  3  4  4  3  3  3  3    ho     Oo oO Oo OO Oo Oo OO Oo OO O  AGO GO GO GO Gi GO GD GO GO Gi GO Di GO GO GD L         Figure 35       Click the button Upload at left bottom corner of the window to obtain the new Alarm events  In the left field   there is a list of upload time which is the time you perform an upload from PT2
39. r outputs a right value  Click Exit to exit the zero calibration     Full Scale Low Calibration    Start Calibration    Step2  Read current output Full Scale  Low   and enter into below field        Figure 29  4  Click the button Full scale high Calibration  Click OK button in the WARNING window figure 30   Enter  YES in the Warning dialogue  figure 31  and click OK to open the calibration window figure 32   Follow the  steps showed in the window to implement calibration  First  click the button Start Calibration in step1  then  TTT    ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  32    PT2060 53 O SPEED Over speed System       read the output current value from multimeter  after it settled down  Enter this value  three significant decimal  digits  in the text area in step2  After that  click the button Full scale high Calibration in step3 to download   Wait till the multimeter outputs a right value  Click Exit to exit the high calibration     WARNING     1  Fullscale calibration may cause system malunction if operation improperty  o Make sure   1  Understand he calibration peocodune    OI Hiring peteesiey calitvalion instruments ready     For example  slali cabrian ch  k table and signal generator ole        Figure 30       Barong     Please input  YES  in the edit below if you confirm  to continue your calibration operation               Figure 31       Full Scale High Calibration    Start Calibration      Step2  Read curr
40. ry channel  of a monitor is capable of producing an Alert indication  These indications can be used in relay alarm drive  logic which is configured in the Relay    When a PT2060 53 O SPEED module works in PT2060 53 O SPEED Over speed System  it does not  support GAP alarm    Channel Enabled   Channel Enabled lets you control whether or not the monitor channel is used   If the box is checked  V   the  channel is used   Its default status is checked  User could modify it as need    Alarm Latching   Causes the PT2060 53 O SPEED module to retain an alarm status after the alarm condition has gone away   The latching alarm mode allows you to determine if an alarm set point has been exceeded or equaled since  the last rack reset  The rack reset contact or reset button on the PT2060 91 SIM module will reset all latched  alarms in the PT2060 rack if the current proportional value is less than the set point value  You can also reset  the rack by using the PT2060 System Configuration software  Non latching alarm causes the PT2060 monitor  to remove an alarm status after the alarm condition has gone away  The Event list for the monitor will provide    ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  16    PT2060 53 O SPEED Over speed System       information about faulted transducers even if non latching is selected  The default status is latched  User  could modify it   Set Point  This is set for PT2060 53 O SPEED modules    alarm thresho
41. s  A standard 19    rack can contain three  such sub systems at most  A 12    rack can contain one such sub systems only     To configure PT2060 53  communication between PT2060 CFG software and PT2060 53 module has to be  established  This communication is normally setup via PT2060 91  the system interface module  As Figure 2  shows  Computer will connects PT2060 91  the System Interface Module via the RS232 on the front panel or  RS485 or RS232 on the back panel  Please consult PT 1060 91 SIM User Manual for more details                                                                                                                                                                                                                                                                                                                                         TT   D Q D 0  Q Q  O O O O CH CO  0  Q  Q  SYSTEM KH sabes  en Gi  O INTERFACE    Osod Ae  SEN 91 SIM iad  Ss       _  ETHERNET E    L   1 Be    ay  2 L Si B  r   D E  Ge D A D Gd CO   CA Loaf ad gn I  Kl   er zd bee  Ges      RS485 a   d  E    Ez   z g       3 SS    x  pz  Z T d d D  pa E z     Pi Pover  Pa me 2  Es a  we    vA ee ol a     e P By   pwr  GV    com  EY   com  E    SIG  E93   sic    u  fy SHD  EX Sun EP    pwr  Edd   pwr  Ou    com  Eag   com  Eg  sig  E sic  E    fy am 31   sn Gi    f bg bg       J         5    bg  NI   com  E COM  Nee Ki outi  E OUTI    S   ZS ol E COMI    os K outa  El Io    i i vu E conl IE    ovT3  
42. s configuration parameters  automatically  You could also click the button Upload in the main frame window of the software to get all of the  configuration parameters and click the button Download to save them to the machine  after you have done  your modifications     Click on the picture of PT2060 53 O SPEED module to open PT2060 53 O SPEED Module Configuration  window  At the right up corner  there are items Channel enable and alarm latching  They are checked by                default   ae  Slot No  6 Channel No fi           Parameter   Channel Type  lQverspeed    W Channel Enabled   Transducer Typis Tratten    ht Alam Latching  peas ek Set Point  Transducer enges   E reesei E  Dargar Hgh   4500 RP  Figure 24    ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  28    PT2060 53 O SPEED Over speed System       From menu item    Rack  gt Signal Module Controf open the status control window  where slot number and  alarm set point multiplication and bypass status are specified  Click the button Download to save it to  PT2060 53 O SPEED module  The PT2060 53 O SPEED module has no relation to alarm set point  multiplication function  when it works in PT2060 53 O SPEED Over speed System     Signal Module State Control      PT2060 Rack  Mode    Slot No   11   Channel No   1      Trip Multiply Bypass        e None   Alert Bypass  C Double Multiply C Danger Bypass  C Trip Multiply  Figure 25  Module Testing    When PT2060 53 O SPEED mod
43. s the case  the measured value will not be  affected except the alarms on the module  Bypass is valid for Alert type and GAP type alarms  Bypass has  higher priority than alarm latching does     The system is not bypassed by default     A channel bypass status may result from the following conditions   PT2060 53 O SPEED module has never been configured   PT2060 53 O SPEED module is in configuration mode   Channel of PT2060 53 O SPEED module has an invalid configuration  PT2060 53 O SPEED module is in power up self test   Fatal error found during self test   Alarming is bypassed via PT2060 System Configuration software  Channel of PT2060 53 O SPEED module is disable    Ze ZS  e  e  e SS    Alarms Trip multiply    In PT2060 53 O SPEED Over speed System  PT2060 53 O SPEED module channels working in speed  measuring mode does not support Alarms Trip multiply alarm     Channel Disable    If PT2060 53 O SPEED module is configured into channel disable status  The GAP not OK is False  Alarms  are False  GAP value is 10 0V and real time value is full scale low     Parameter Configuration    After the host computer and the PT2060 are connected  Start PT2060 CFG configuration software  In the  main window of the software  click the button Up oad to upload all PT2060 messages     Click the picture of the module you want to configure to open a configuration window for that module  where  all parameters can be edited  Download or upload the configuration information according to the need  
44. sales provibtech com   www provibtech com  T    PT2060 53 O SPEED Over speed System       CSA   Non incendive  class    div 2  Gros ABCD  T4 Ta   40  C to  75   C  Certificate Number  2011996    PT2060 43 R RELAY Redundant Relay Module    Please refer to PT2060 43 R RELAY Redundant Relay Module User Manual     Environmental  Temperature   Operation   20  C to  65  C  Storage   40  C to  85  C    Humidity   95  non condensing    Physical  PT2060 53 O SPEED Over speed Module  Each module comes with two components  the front panel assembly and the back panel assembly     Dimensions   241mm  9 5in  X 24 5mm  0 96in   For 19    rack  mounts in any one of the following slots   1 3  5 7  9 11   For 12    rack  mounts in slot 1 3     Weight   1 0 kg  2 0 Ibs     PT2060 43 R RELAY Redundant Relay Module    Please refer to PT2060 43 R RELAY Redundant Relay Module User Manual     ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  8    PT2060 53 O SPEED Over speed System       Module Configuration and Channel Setup    In a PT2060 53 O SPEED Over speed System  PT2060 53 O SPEED module can accept either proximity  probe or magnetic pickup signal input  Monitor function has to be configured by the software PT2060 System  Configuration before using  The following description of software configuration setting is based on PT2060  System Configuration software     Hardware Configuration    Each PT2060 53 O SPEED Over speed System occupies four slot
45. ule Operation             ccccccceccceeececeeececeeeeeceeeeeeeeeesseeeeaeeceeseecesseeeeeeeeeeseeeeseecessaeeesseeeesageeeseneeeseeeenas 22   Front  Back Panels and Functions escenesctcnetencccensecnatesmiciadenctanadeceeaiedsnetinntasaeinstaaesanaddeemniadanetneeasabadaeseseenues 22  Reicg Su ER  Elei E 23   FEAN MIEN INC  EI el 24   Mo  du  le EE NET e EE 27  Perngdi   MaintenanCE EE 27  Bee EN 27    Reie D ON EEN 27  Build of Maintenance Environment    28  Sonware Preparation eege 28   VOG TOSIN rae EEN 29   C  rrent Calibration EE 32   Exceptional Module Treatmment A 33   Ural flet SOO GAG EE 34  Dee ee 34  Real time Value and KEE 35  VEVO EE 35  Alarm ug E 36  Exceptional Module Treatmment 37   Additional ATT un Ne E 38  Ordering Information EE 38  Optional ACCesSsorieS  ee eee eee ee 38  ug e E 38  Factory Default Confguraton    E 38   APOORO X ee r a E E A RE 39  Terminal for Proximity Free oesgteeseeeggieebseeg  ie eege sa unsmodteecsd aE AEE AAAA REAREN ERAO aadA 39  Terminal for Magnetic PICKUD EE 39  Bypass Terminal sn etd b mn fj alien nll fe hn fact ed dai ca hacen so i dt dla R 39  Alarms HPI GUNN WC EE 39    ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  2    PT2060 53 O SPEED Over speed System       Receiving Inspection and Handling Guide    Inspection    Check the devices for possible damage that may have occurred from improper transport  Damages in transit  must be recorded on the transport documents  All cl
46. ule works in the PT2060 53 O SPEED Over speed System  it is only the first  channel that needs to be tested  When it works as other modules  the channel 3 and 4 are also need to be  test  For the latter testing  refer to the relevant section of PT2060 10 PROX Proximity Module User Manual     Warning    High voltage  Contact could cause shock  burns  or death  Do not  touch exposed wires or terminals     Application Alert    Tests will exceed alarm set point levels causing alarms to activate   This could result in a relay contact state change     Application Alert    Disconnecting field wiring will cause a not OK condition        1  System construction  If transducer type is anyone of proximity probes  take one proximity terminal  Plug the terminal into the first  channel of PT2060 53 back panel  Connect the red pen of an ampere meter to OUT pin of the current output    ProvibTech Phone   1 713 830 7601 Fax   1 281 754 4972 sales provibtech com   www provibtech com  29       N  PT2060 53 O SPEED Over speed System    port and connect the black pen to GND pin on that port  Set the ampere meter to measure direct current  Feed  a signal to the channel through the positive pin of the electrolytic capacitor  220uF 50V  of the terminal   Connect an oscilloscope to the BUF of the first channel    If transducer type is magnetic pickup  take one magnetic terminal  Plug the terminal into the first channel of  PT2060 53 back panel  Connect the red pen of an ampere meter to OUT pin of the 
    