FX3U-3A-ADP USER`S MANUAL
Contents
1. Item Specification Digital input and 12 bits binary output e FX3U FX3UC Series PLC 80 us for each selected input channel 40 us for each selected output channel Conversion The data will be updated at every scan time of the PLC time e FX3S FX3G FX3GC Series PLC 90 us for each selected input channel 50 us for each selected output channel The data will be updated at every scan time of the PLC e A photocoupler is employed to insulate the analog input and N output area from the PLC Insulation e A DC DC converter is employed to insulate the power supply method A f line from the analog input and output area e Channels are not insulated from each other Occupied 0 point This number is not related to the maximum number of points input output points of the PLC kom Voltage input Current input This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be Analog input 0 to 10V DC 4to 20 mA DC held responsible for any problems involving industrial property rights which may range Input resistance 198 7 kQ Input resistance 250 O occur as a result of using the contents noted in this manual Maximum 0 5 V 15 V 2 mA 30 mA absolute input Resolution 2 5 mV 10 V 4000 5 uA 16 mA 3200 Total accuracy e e 0 5 50 mV for full scale of 10 V when ambient temperature is 25 C 5 C 1
2. Input For the terminal configuration refer to Section 1 2 Using current Terminal 3A ADP block 110kQ cho 2500 gt r 88 7KQ 110k9 cho 2500 DOr 88 7kQ eel 15V e I H iasi Grounding Vor IO chO Orepresents the channel number 1 Use 2 core shielded twisted pair cable for the analog input lines and separate the analog input lines from other power lines or inductive lines 2 Make sure to short circuit the VD1 and IO terminals when current is input O input channel number 3 24 V DC service power supply of the FX3S FX3G FX3U Series PLC can also be used 3 4 Wiring of Analog Output For the terminal configuration refer to Section 1 2 Using voltage Terminal 3A ADP block VV VV VO tp emailemail IO T con 2 Grounding rh Using current ee Terminal 3A ADP block e te genie POON COM ET Z 2 Grounding 1 Use 2 core shielded twisted pair cable for the analog output lines and separate the analog output lines from other power lines or inductive lines 2 Ground the shielded wire at one point on the signal receiving side 3 5 Grounding Grounding should be performed as stated below e The grounding resistance should be 100 Q or less e Independent grounding should be performed for best results When independent grounding is not perf
3. make sure that there are no loose wires Do not solder plate the electric wire ends Do not connect more than the specified number of wires or electric wires of unspecified size Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed Make sure to properly wire the terminal block in accordance with the following precautions Failure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual of the PLC main unit Tightening torque should follow the specifications in the manual of the PLC main unit 3 1 Applicable Cable and Terminal Tightening Torque 3 1 1 Terminal block European type 1 Wire size Wiring to analog device should use 22 20 AWG wire 2 Applicable cable Type Wire size Single wire 0 3 mm to 0 5 mm AWG22 to 20 2 wire 2 pieces of 0 3 mm AWG22 3 Termination of cable end Strip the coating of strand wire and twist the cable core before connecting it or strip the coating of single wire before connecting it An alternative connection is to use a ferrule with insulating sleeve lt Reference gt 3 2 Power Supply Wiring For the power supply wiring refer to the following manual FX3S FX3G FX3GC FX3U FX3UC Series User s Manual Analog Control Edition 3 3 Wiring of Analog
4. off all phases of the power supply externally before attempting installation or wiring work Failure to do so may cause electric shock or damage to the product WIRING PRECAUTIONS CAUTION e When drilling screw holes or wiring make sure cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions Make sure to observe the following precautions in order to prevent any damage to the machinery or accidents due to abnormal data written to the PLC under the influence of noise 1 Do not bundle the power line or shield of the analog input output cable together with or lay it close to the main circuit high voltage line or load line Otherwise noise disturbance and or surge induction are likely to take place As a guideline lay the control line at least 100mm 3 94 or more away from the main circuit high voltage line or load line 2 Ground the shield of the analog input output cable at one point on the signal receiving side However do not use common grounding with heavy electrical systems Make sure to properly wire to the terminal block European type in accordance with the following precautions Failure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual Tightening torque should follow the s
5. output e FX3U FX3UC Series PLC 80 us for each selected input channel 40 us for each selected output channel Conversion The data will be updated at every scan time of the PLC time e FX3S FX3G FX3GC Series PLC 90 us for each selected input channel 50 us for each selected output channel The data will be updated at every scan time of the PLC e A photocoupler is employed to insulate the analog input and N output area from the PLC Insulation e A DC DC converter is employed to insulate the power supply method i f line from the analog input and output area e Channels are not insulated from each other Occupied 0 point This number is not related to the maximum number of points input output points of the PLC Item Voltage input Current input This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be Analog input 0 to 10V DC 4to 20 mA DC held responsible for any problems involving industrial property rights which may range Input resistance 198 7 kQ Input resistance 250 9 occur as a result of using the contents noted in this manual Maximum 0 5 V 15 V 2 mA 30 mA absolute input Resolution 2 5 mV 10 V 4000 5 pA 16 mA 3200 Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi opportunity loss or lost profits caused by faults in the Mi
6. the product or exert strong impact to it Doing so may cause damage CAUTION DISPOSAL PRECAUTIONS CAUTION e Please contact a certified electronic waste disposal environmentally safe recycling and disposal of your device company for the TRANSPORTATION AND STORAGE PRECAUTIONS CAUTION e The product is a precision instrument During transportation avoid any impacts Failure to do so may cause failures in the product After transportation verify the operations of the product 4 141 Applicable PLC Model name FX3S Series PLC FX3G Series PLC FX3GC Series PLC FX3U Series PLC FX3UC Series PLC Applicability Ver 1 00 or later from first production Ver 1 20 or later Ver 1 40 or later from first production Ver 2 61 or later Ver 2 61 or later The version number can be checked by monitoring D8001 D8101 as the last three digits indicate it 4 2 General Specifications Items other than the following are equivalent to the those of the PLC main unit For general specifications refer to the respective PLC User s manual Hardware Edition Item Specification Dielectric withstand 500 V AC for one minute voltage Between all terminals and ground terminal of PLC 5 MQ or more by 500 V DC main unit megger Insulation resistance 4 3 Power Supply Specifications Item Specification 24 V DC 20 15 90 mA Connect a 24 V DC power s
7. 0 100 mV for full scale of 10 V when ambient temperature is 0 C to 55 C e 0 5 80 uA for full scale of 16 mA when ambient temperature is 25 C 5 C e 1 0 160 pA for full scale of 16 mA when ambient temperature is 0 C to 55 C Input characteristics 4080 or 3280 fo aN cot 3200 s o 2 rot g D 1 1 f 2 tid e g so S 0 gt 10V 10 2V 2 0 4mA gt 20mA 20 4mA Analog input Analog input Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi opportunity loss or lost profits caused by faults in the Mitsubishi products damage secondary damage accident compensation caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi products and to other duties A For safe use e This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life e Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi Electric e This product has been manufactured under strict quality control However when installing the product where major accidents or losses could occur if the product fails install appropriate backup or
8. J 997D35601D JAPANESE Pd Side B ENGLISH MITSUBISHI ELECTRIC PROGRAMMABLE CONTROLLERS MELSEG F FX3uU 3A ADP USER S MANUAL FX 3u JY997D35601 This manual describes the part names dimensions mounting and specifications of the product Before use read this manual and the manuals of all relevant products fully to acquire proficiency in handling and operating the product Make sure to learn all the product information safety information and precautions Store this manual in a safe place so that it can be taken out and read whenever necessary Always forward it to the end user Registration The company and product names described in this manual are registered trademarks or the trademarks of their respective companies Effective April 2013 Specifications are subject to change without notice 2009 Mitsubishi Electric Corporation Manual Number Revision D Date April 2013 Safety Precaution Read these precautions before use This manual classifies the safety precautions into two categories ZAWARNING Z CAUTION and Indicates that incorrect handling may cause hazardous Z WARNING conditions resulting in death or severe injury Indicates that incorrect handling may cause hazardous Z CAUTION conditions resulting in medium or slight personal injury or physical damage Depending on the circumstances pro
9. KU TOKYO 100 8310 JAPAN HIMEJI WORKS 840 CHIYODA CHO HIMEJI JAPAN J 997D35601D JAPANESE Pd Side B ENGLISH MITSUBISHI ELECTRIC PROGRAMMABLE CONTROLLERS MELSEG F FX3uU 3A ADP USER S MANUAL FX 3u JY997D35601 This manual describes the part names dimensions mounting and specifications of the product Before use read this manual and the manuals of all relevant products fully to acquire proficiency in handling and operating the product Make sure to learn all the product information safety information and precautions Store this manual in a safe place so that it can be taken out and read whenever necessary Always forward it to the end user Registration The company and product names described in this manual are registered trademarks or the trademarks of their respective companies Effective April 2013 Specifications are subject to change without notice 2009 Mitsubishi Electric Corporation Manual Number Revision D Date April 2013 Safety Precaution Read these precautions before use This manual classifies the safety precautions into two categories ZAWARNING Z CAUTION and Indicates that incorrect handling may cause hazardous Z WARNING conditions resulting in death or severe injury Indicates that incorrect handling may cause hazardous Z CAUTION conditions resulting in medium or slig
10. User s Manual Analog Control Edition 3 3 Wiring of Analog Input For the terminal configuration refer to Section 1 2 ang cuten Terminal 3A ADP 110kQ cho 2500 T DOr 88 7KQ 110kQ cho 2500 Dr 88 7KQ Land 15V 3 y ane ch Grounding VO I chO Crepresents the channel number 1 Use 2 core shielded twisted pair cable for the analog input lines and separate the analog input lines from other power lines or inductive lines 2 Make sure to short circuit the VD1 and IO terminals when current is input O input channel number 3 24 V DC service power supply of the FX3S FX3G FX3U Series PLC can also be used 3 4 Wiring of Analog Output For the terminal configuration refer to Section 1 2 Using voltage Terminal ___ 9D block VN V V VO T 10 mI COM 2 Grounding rh Using current ce de oe ee Terminal 3A ADP block lt aa COM aT Th 2 Grounding 1 Use 2 core shielded twisted pair cable for the analog output lines and separate the analog output lines from other power lines or inductive lines 2 Ground the shielded wire at one point on the signal receiving side 3 5 Grounding Grounding should be performed as stated below e The grounding resistance should be 100 Q or less e Independent grounding should be perfo
11. cedures indicated by A CAUTION may also cause severe injury It is important to follow all precautions for personal safety Associated Manuals Manual name Manual No Description Describes specifications for enone JY997D16701 analog control and User s Manual MODEL CODE programming method for Analog Control Edition 09R619 FX3S FX3G FX3GC FX3U 9 FX3UC Series PLC FX3S FX3G FX3GC FX3U FX3UC Series JY997D16601 Describes PLC programming for Programming Manual MODEL CODE basic applied instructions and Basic amp Applied Instruction 09R517 devices Edition FX3S Series JY997D48601 Explains FX3S Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition 09R535 installation and maintenance FX3G Series JY997D31301 Explains FX3G Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition 09R521 installation and maintenance FX3GC Series JY997D45401 Explains FX3GC Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition 09R533 installation and maintenance FX3U Series JY997D16501 Explains FX3U Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition O9R516 installation and maintenance FX3UC Series JY997D28701 Explains FX3UC Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition 09R519 installation and maintenance How to obtain manuals For product man
12. e sure to cut off all phases of the power supply externally before attempting INSTALLATION PRECAUTIONS installation or wiring work Failure to do so may cause electric shock or damage to the product Z CAUTION e Use the product within the generic environment specifications described in PLC main unit manual Hardware Edition Never use the product in areas with excessive dust oily smoke conductive dusts corrosive gas salt air Cl2 H2S SO2 or NO2 flammable gas vibration or impacts or expose it to high temperature condensation or rain and wind If the product is used in such conditions electric shock fire malfunctions deterioration or damage may occur When drilling screw holes or wiring make sure cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions Do not touch the conductive parts of the product directly Doing so may cause device failures or malfunctions Connect special adapter securely to their designated connectors Loose connections may cause malfunctions 2 1 Connection to the PLC This section describes the connection method to the PLC FX3U Series PLC is used for the following example For installation method to other PLCs refer to the respective PLC User s manual Hardware Edition Procedure 1 Turn off the power Disconnect all the cables connected to the PLC main unit and special adapter and demount the main un
13. failsafe functions in the system MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN HIMEJI WORKS 840 CHIYODA CHO HIMEJI JAPAN
14. he PLC main unit and special adapter and demount the main unit and special adapter mounted on DIN rail or mounted directly using screws Install an expansion board to the main unit For the expansion board installation procedure refer to the following manual FX3u Series User s Manual Hardware Edition Remove the special adapter connector cover on the expansion board fig A When connecting this product to another special adapter please replace the expansion board in the above description with a special adapter and perform the procedure as indicated 4 Slide the special adapter slide lock fig B of the main unit When connecting this product to another special adapter please replace the main unit in the above description with a special adapter and perform the procedure as indicated Please replace the following procedures similarly 5 Connect the special adapter fig C to the main unit as shown on the right 6 Slide back the special adapter slide lock fig B of the main unit to fix the special adapter fig C v 3 Connection precautions Connect all the high speed I O special adapters before connecting other special adapters when they are used in combination Do not connect a high speed I O special adapter on the left side of any Special adapters other than other high speed I O special adapters 3 Wiring WIRING PRECAUTIONS Z WARNING e Make sure to cut
15. ht personal injury or physical damage Depending on the circumstances procedures indicated by A CAUTION may also cause severe injury It is important to follow all precautions for personal safety Associated Manuals Manual name Manual No Description Describes specifications for enone JY997D16701 analog control and User s Manual MODEL CODE programming method for Analog Control Edition 09R619 FX3S FX3G FX3GC FX3U 9 FX3UC Series PLC FX3S FX3G FX3GC FX3U FX3UC Series JY997D16601 Describes PLC programming for Programming Manual MODEL CODE basic applied instructions and Basic amp Applied Instruction 09R517 devices Edition FX3S Series JY997D48601 Explains FX3S Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition 09R535 installation and maintenance FX3G Series JY997D31301 Explains FX3G Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition 09R521 installation and maintenance FX3GC Series JY997D45401 Explains FX3GC Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition 09R533 installation and maintenance FX3U Series JY997D16501 Explains FX3U Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition O9R516 installation and maintenance FX3UC Series JY997D28701 Explains FX3UC Series PLC User s Manual MODEL CODE specifications for I O wiring Hardware Edition 09R519 insta
16. ir contact your local Mitsubishi Electric representative Do not drop the product or exert strong impact to it Doing so may cause damage CAUTION DISPOSAL PRECAUTIONS Z CAUTION e Please contact a certified electronic waste disposal environmentally safe recycling and disposal of your device company for the TRANSPORTATION AND STORAGE PRECAUTIONS Z CAUTION e The product is a precision instrument During transportation avoid any impacts Failure to do so may cause failures in the product After transportation verify the operations of the product 4 1 Applicable PLC Model name Applicability FX3S Series PLC Ver 1 00 or later from first production Ver 1 20 or later FX3G Series PLC FX3GC Series PLC Ver 1 40 or later from first production FX3U Series PLC Ver 2 61 or later FX3UC Series PLC Ver 2 61 or later The version number can be checked by monitoring D8001 D8101 as the last three digits indicate it 4 2 General Specifications Items other than the following are equivalent to the those of the PLC main unit For general specifications refer to the respective PLC User s manual Hardware Edition Item Specification Dielectric withstand 500 V AC for one minute voltage Between all terminals and ground terminal of PLC main unit 5 MQ or more by 500 V DC megger Insulation resistance 4 3 Power Supply Specifications Item Specificatio
17. it and special adapter mounted on DIN rail or mounted directly using screws 2 Install an expansion board to the main unit For the expansion board installation procedure refer to the following manual FX3u Series User s Manual Hardware Edition Remove the special adapter connector cover on the expansion board fig A When connecting this product to another special adapter please replace the expansion board in the above description with a special adapter and perform the procedure as indicated 4 Slide the special adapter slide lock fig B of the main unit When connecting this product to another special adapter please replace the main unit in the above description with a special adapter and perform the procedure as indicated Please replace the following procedures similarly 5 Connect the special adapter fig C to the main unit as shown on the right 6 Slide back the special adapter slide lock fig B of the main unit to fix the special adapter fig C 3 Connection precautions Connect all the high speed I O special adapters before connecting other special adapters when they are used in combination Do not connect a high speed I O special adapter on the left side of any Special adapters other than other high speed I O special adapters 3 Wiring WIRING PRECAUTIONS Z WARNING e Make sure to cut off all phases of the power supply externally before attempti
18. l Hardware Edition INSTALLATION PRECAUTIONS Z WARNING e Make sure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do so may cause electric shock or damage to the product INSTALLATION PRECAUTIONS Z CAUTION e Use the product within the generic environment specifications described in PLC main unit manual Hardware Edition Never use the product in areas with excessive dust oily smoke conductive dusts corrosive gas salt air Cl2 H2S SO2 or NO2 flammable gas vibration or impacts or expose it to high temperature condensation or rain and wind If the product is used in such conditions electric shock fire malfunctions deterioration or damage may occur When drilling screw holes or wiring make sure cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions Do not touch the conductive parts of the product directly Doing so may cause device failures or malfunctions Connect special adapter securely to their designated connectors Loose connections may cause malfunctions 2 1 Connection to the PLC This section describes the connection method to the PLC FX3U Series PLC is used for the following example For installation method to other PLCs refer to the respective PLC User s manual Hardware Edition Procedure 1 Turn off the power Disconnect all the cables connected to t
19. llation and maintenance How to obtain manuals For product manuals or documents consult with the Mitsubishi Electric dealer from who you purchased your product Applicable standards FX3U 3A ADP units made in June 2009 or later comply with the EC Directive EMC Directive and UL standards UL cUL Further information can be found in the following manual ies Hardware Manual Manual No JY997D48301 s Hardware Manual Manual No JY997D46001 s Hardware Manual Manual No JY997D45201 s Hardware Manual Manual No JY997D18801 FX3uc D DS DSS Series Hardware Manual Manual No JY997D28601 FX3UC 32MT LT 2 Hardware Manual Manual No JY997D31601 Regarding the standards that relate to the main unit please refer to either the FX series product catalog or consult with your nearest Mitsubishi product provider Attention e This product is designed for use in industrial applications Note e Manufactured by Mitsubishi Electric Corporation 2 7 3 Marunouchi Chiyoda ku Tokyo 100 8310 Japan e Manufactured at Mitsubishi Electric Corporation Himeji Works 840 Chiyoda machi Himeji Hyogo 670 8677 Japan e Authorized Representative in the European Community Mitsubishi Electric Europe B V Gothaer Str 8 40880 Ratingen Germany Caution for compliance with EC Directive The analog special adapters have been found to be compliant to the European standards in the aforesaid manual and directive However fo
20. n 24 V DC 20 15 90 mA Connect a 24 V DC power supply to the terminal block Conversion circuit driving power ne 5V DC 20 mA REE griving 5 V DC power is supplied from the internal power supply of P main unit 4 4 Performance Specifications Performance Specifications of Analog Input Specification Performance Specifications of Analog Output Specification Item Voltage output Current output Aag Oto 10V DC 4 to 20 mA DC PRA External load 5 kQ to 1 MQ External load 500 Q or less Resolution 2 5 mV 10 V 4000 4 pA 16 mA 4000 e 0 5 50 mV for full scale of 10 V when ambient temperature is 25 C 5 C e 1 0 100 mV for full scale of 10 V when ambient 0 5 80 pA for full temperature is 0 C to z scale of 16 mA when 55 C F A ambient temperature is Total If the external load resistance 25 C 5 C accuracy Rs is less than 5 kQ the e 1 0 160 pA for full accuracy will be increases as scale of 16 mA when shown in the following formula ambient temperature is 0 C Addition will be 100 mV per to 55 C 47x100 eadi 9 Rs 47 03 i for full scale of 10 V r A Ji 1 10V A fal 20mA 1 gt 1 1 1 Output a I f gt i characteristics 9 i pl l i 2 1 S 4mA i g S Z o gt 40004080 0 gt 4000 4080 Digital input ze Digital input Common Specifications of Analog Input and Output
21. n the package Product FX3U 3A ADP analog input and output special adapter Accessories User s Manual This manual A 1 2 External Dimensions Part Names and Terminal Layout 8 9 2 10 106 4 18 90 3 55 98 3 86 mounting hole pitch Special adapter 4 connector cover is removed Weight Approx 0 1 kg 0 22 Ibs DIN rail mounting groove DIN rail DIN46277 Name plate Special adapter slide lock Used to connect additional special adapters onto the left side of this special adapter Special adapter connector cover Remove this cover to connect additional special adapters to the left side Direct mounting hole 2 holes of 4 5 0 18 mounting screw M4 screw Not used when connecting to FX3GC FX3UC Series PLC POWER LED green Lit while 24 V DC power is supplied properly to terminals 24 and 24 Terminal block European type Connect the analog voltage current signal and 24 V DC power supply Special adapter connector Used to connect this special adapter to PLC main unit or special adapter DIN rail mounting hook 10 Special adapter fixing hook 11 Special adapter connector Used to connect communication or analog special adapters to the left side of the 3AD ADP Installation For installation uninstallation details refer to the respective PLC User s manual Hardware Edition INSTALLATION PRECAUTIONS Z WARNING e Mak
22. ncorporated Items Verify that the following product and items are included in the package Product FX3U 3A ADP analog input and output special adapter Accessories User s Manual This manual A 1 2 External Dimensions Part Names and Terminal Layout 10 90 3 55 98 3 86 mounting hole pitch 106 4 18 Special adapter 4 connector cover is removed Weight Approx 0 1 kg 0 22 Ibs DIN rail mounting groove DIN rail DIN46277 2 Name plate 3 Special adapter slide lock Used to connect additional special adapters onto the left side of this special adapter 4 Special adapter connector cover Remove this cover to connect additional special adapters to the left side 5 Direct mounting hole 2 holes of 4 5 0 18 mounting screw M4 screw Not used when connecting to FX3GC FX3UC Series PLC 6 POWER LED green Lit while 24 V DC power is supplied properly to terminals 24 and 24 7 Terminal block European type Connect the analog voltage current signal and 24 V DC power supply 8 Special adapter connector Used to connect this special adapter to PLC main unit or special adapter 9 DIN rail mounting hook 10 Special adapter fixing hook 11 Special adapter connector Used to connect communication or analog special adapters to the left side of the 3AD ADP 2 Installation For installation uninstallation details refer to the respective PLC User s manua
23. ng installation or wiring work Failure to do so may cause electric shock or damage to the product WIRING PRECAUTIONS Z CAUTION e When drilling screw holes or wiring make sure cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions Make sure to observe the following precautions in order to prevent any damage to the machinery or accidents due to abnormal data written to the PLC under the influence of noise 1 Do not bundle the power line or shield of the analog input output cable together with or lay it close to the main circuit high voltage line or load line Otherwise noise disturbance and or surge induction are likely to take place As a guideline lay the control line at least 100mm 3 94 or more away from the main circuit high voltage line or load line 2 Ground the shield of the analog input output cable at one point on the signal receiving side However do not use common grounding with heavy electrical systems Make sure to properly wire to the terminal block European type in accordance with the following precautions Failure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual Tightening torque should follow the specifications in the manual Twist the end of strand wire and
24. ormed perform shared grounding of the following figure Manufacturer Model Caulking tool For details refer to the respective PLC User s manual Hardware Edition ay Other Other Other Phoenix Contact Co Ltd Al 0 5 8WH or Crivecox ELF PLC equipment PLC equipment PLC equipment 1 Old model name CRIMPFOX ZA 3 2 Old model name CRIMPFOX UD 6 Strand wire single wire d KS 0 3 Stick terminal with insulating sleeve Contact area Crimp area Insulation sleeve 8mm 0 31 2 6mm 0 1 14mm 0 55 When using a stick terminal with insulating sleeve choose a wire with proper cable sheath referring to the above outside dimensions or otherwise the wire cannot be inserted easily The tightening torque must be 0 22 to 0 25 Nem Do not tighten terminal screws exceeding the specified torque Failure to do so may cause equipment failures or malfunctions a Independent grounding Best condition Shared grounding Common grounding Good condition Not allowed The grounding wire size should be AWG 22 20 0 3 0 5 mm e The grounding point should be close to the PLC and all grounding wire should be as short as possible 4 Specifications STARTUP AND MAINTENANCE PRECAUTIONS e Do not disassemble or modify the PLC Doing so may cause fire equipment failures or malfunctions For repair contact your local Mitsubishi Electric representative Do not drop
25. pecifications in the manual Twist the end of strand wire and make sure that there are no loose wires Do not solder plate the electric wire ends Do not connect more than the specified number of wires or electric wires of unspecified size Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed Make sure to properly wire the terminal block in accordance with the following precautions Failure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual of the PLC main unit Tightening torque should follow the specifications in the manual of the PLC main unit 3 1 Applicable Cable and Terminal Tightening Torque 3 1 1 Terminal block European type 1 Wire size Wiring to analog device should use 22 20 AWG wire 2 Applicable cable Type Wire size Single wire 0 3 mm2 to 0 5 mm2 AWG22 to 20 2 wire 2 pieces of 0 3 mm2 AWG22 3 Termination of cable end Strip the coating of strand wire and twist the cable core before connecting it or strip the coating of single wire before connecting it An alternative connection is to use a ferrule with insulating sleeve lt Reference gt 3 2 Power Supply Wiring For the power supply wiring refer to the following manual FX3S FX3G FX3GC FX3U FX3UC Series
26. r the very best performance from what are in fact delicate measuring and controlled output device Mitsubishi Electric would like to make the following points As analog devices are sensitive by nature their use should be considered carefully For users of proprietary cables integral with sensors or actuators these users should follow those manufacturers installation requirements Mitsubishi Electric recommend that shielded cables should be used If NO other EMC protection is provided then users may experience temporary loss or accuracy between 10 in very heavy industrial areas However Mitsubishi Electric suggest that if adequate EMC precautions are followed for the users complete control system users should expect accuracy as specified in this manual e Sensitive analog cable should not be laid in the same trunking or cable conduit as high voltage cabling Where possible users should run analog cables separately e Good cable shielding should be used When terminating the shield at Earth ensure that no earth loops are accidentally created e When reading analog values EMC accuracy can be improved out by averaging the readings This can be achieved either through functions on the analog special adapters or through a users program 1 Outline The FX3U 3A ADP special adapter for analog input and output hereinafter called 3A ADP is a special adapter that adds to add two analog input points and one analog output point 1 1 I
27. rmed for best results When independent grounding is not performed perform shared grounding of the following figure Manufacturer Model Caulking tool For details refer to the respective PLC User s manual Hardware Edition M Other Other Other Phoenix Contact Co Ltd Al 0 5 8WH or GRivecox re PLC equipment PLC equipment PLC equipment 1 Old model name CRIMPFOX ZA 3 2 Old model name CRIMPFOX UD 6 Strand wire single wire d KS 0 3 Stick terminal with insulating sleeve Contact area Crimp area Insulation sleeve 8mm 0 31 2 6mm 0 1 14mm 0 55 a When using a stick terminal with insulating sleeve choose a wire with proper cable sheath referring to the above outside dimensions or otherwise the wire cannot be inserted easily The tightening torque must be 0 22 to 0 25 Nem Do not tighten terminal screws exceeding the specified torque Failure to do so may cause equipment failures or malfunctions aa Independent grounding Best condition Shared grounding Common grounding Good condition Not allowed The grounding wire size should be AWG 22 20 0 3 0 5 mm e The grounding point should be close to the PLC and all grounding wire should be as short as possible 4 Specifications STARTUP AND MAINTENANCE PRECAUTIONS e Do not disassemble or modify the PLC Doing so may cause fire equipment failures or malfunctions For repa
28. trolled output device Mitsubishi Electric would like to make the following points As analog devices are sensitive by nature their use should be considered carefully For users of proprietary cables integral with sensors or actuators these users should follow those manufacturers installation requirements Mitsubishi Electric recommend that shielded cables should be used If NO other EMC protection is provided then users may experience temporary loss or accuracy between 10 in very heavy industrial areas However Mitsubishi Electric suggest that if adequate EMC precautions are followed for the users complete control system users should expect accuracy as specified in this manual e Sensitive analog cable should not be laid in the same trunking or cable conduit as high voltage cabling Where possible users should run analog cables separately e Good cable shielding should be used When terminating the shield at Earth ensure that no earth loops are accidentally created e When reading analog values EMC accuracy can be improved out by averaging the readings This can be achieved either through functions on the analog special adapters or through a users program 1 Outline The FX3U 3A ADP special adapter for analog input and output hereinafter called 3A ADP is a special adapter that adds to add two analog input points and one analog output point 1 1 Incorporated Items Verify that the following product and items are included i
29. tsubishi products damage secondary damage accident compensation Total accuracy e 0 5 50 mV for full scale of 10 V when ambient temperature is 25 C 5 C e 1 0 100 mV for full scale of 10 V when ambient temperature is 0 C to 55 C e 0 5 80 uA for full scale of 16 mA when ambient temperature is 25 C 5 C e 1 0 160 uA for full scale of 16 mA when ambient temperature is 0 C to 55 C Input characteristics 4000 yndjno eya 0 10V 10 2V Analog input 3200 yndyno ebia 0 4mA gt 20mA 20 4mA Analog input caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi products and to other duties A For safe use e This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life e Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi Electric e This product has been manufactured under strict quality control However when installing the product where major accidents or losses could occur if the product fails install appropriate backup or failsafe functions in the system MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA
30. uals or documents consult with the Mitsubishi Electric dealer from who you purchased your product Applicable standards FX3U 3A ADP units made in June 2009 or later comply with the EC Directive EMC Directive and UL standards UL cUL Further information can be found in the following manual FX3S Series Hardware Manual Manual No JY997D48301 s Hardware Manual Manual No JY997D46001 s Hardware Manual Manual No JY997D45201 s Hardware Manual Manual No JY997D18801 FX3uc D DS DSS Series Hardware Manual Manual No JY997D28601 FX3UC 32MT LT 2 Hardware Manual Manual No JY997D31601 Regarding the standards that relate to the main unit please refer to either the FX series product catalog or consult with your nearest Mitsubishi product provider Attention e This product is designed for use in industrial applications Note e Manufactured by Mitsubishi Electric Corporation 2 7 3 Marunouchi Chiyoda ku Tokyo 100 8310 Japan e Manufactured at Mitsubishi Electric Corporation Himeji Works 840 Chiyoda machi Himeji Hyogo 670 8677 Japan e Authorized Representative in the European Community Mitsubishi Electric Europe B V Gothaer Str 8 40880 Ratingen Germany Caution for compliance with EC Directive The analog special adapters have been found to be compliant to the European standards in the aforesaid manual and directive However for the very best performance from what are in fact delicate measuring and con
31. upply to the terminal block Conversion circuit driving power Interface drivin eV DG 20m g 5 V DC power is supplied from the internal power supply of Rower main unit 4 4 Performance Specifications Performance Specifications of Analog Input Specification Performance Specifications of Analog Output Specification Item Voltage output Current output prog Oto 10 V DC 4 to 20 mA DC Ane External load 5 kQ to 1 MQ External load 500 Q or less Resolution 2 5 mV 10 V 4000 4 pA 16 mA 4000 e 0 5 50 mV for full scale of 10 V when ambient temperature is 25 C 5 C e 1 0 100 mV for full scale of 10 V when ambient 0 5 480 pA for full temperature is 0 C to scale of 16 mA when 55 C A ambient temperature is Total If the external load resistance 25 C 5 C accuracy Rs is less than 5 kQ the e 1 0 160 pA for full accuracy will be increases as scale of 16 mA when shown in the following formula ambient temperature is 0 C Addition will be 100 mV per to 55 C 47x100 Aei E 9 Rs 47 os h for full scale of 10 V Pyl i d Z a T EEE fi 20mA an gt I 1 1 Output a i z i characteristics 9 io gt l A 1 1 a 1 5 psp eam i o gt 40004080 0 gt 4000 4080 Digital input ai Digital input Common Specifications of Analog Input and Output Item Specification Digital input and 12 bits binary
Download Pdf Manuals
Related Search
Related Contents
SC.600.I - MAKSIWA Tripp Lite Multimode Fiber Optics 11-m (35-ft.) Duplex MMF 62.5/125 Patch Cable, MTRJ/SC User Guide Mode d`eMploi operating instructions Sikabond vinil - Sika Ecuatoriana 11 fasciolo di manutenzione preliminare MR.ジョーカー粉剤DL KAPROMETER K4 LASER DISTANCE MEASURER Model No. 370 fichier PDF - Les Amis de George Sand Copyright © All rights reserved.