CP 210 - Interautomatika

image

Contents

1. PLC BMS passive type 4 20 mA output 0 10 V output Ground PLC BMS passive type Neutral Power supply 115 230 Vac Phase AUTOZERO Auto calibration CP210 transmitters have a temperature compensation of the gain from 0 to 50 C and an auto calibration process that guarantees over the time an excellent stability and a perfect reliability of the measurement on low and high ranges Auto calibration principle the microprocessor of the transmitter drives a solenoid valve that compensates the possible drifts on the sensitive element over the time The compensation is performed by the permanent adjustment of the zero So the measurement of the differential pressure is then independent from the environmental conditions of the transmitter Advantage no drift Frequency of auto calibration resetable or from 1 to 60 minutes Autozero To perform an autozero unplug the 2 pressure connections tubes and press the Autozero key On CP211 and CP 212 transmitters it is not necessary to unplug the 2 pressure connection tubes When an autozero has been performed On green light turns off then turns on and on transmitters equipped with a display autoZ is displayed CONFIGURATION OF THE TRANSMITTERS It is possible on the class 210 to configure all the parameters managed by the transmitter units measuring ranges outputs channels calculation functions etc via different methods e Keypad for models with
2. KIMO INSTRUMENTS Technical Data Sheet Pressure Temperature Humidity Air Velocity Airflow Sound level Temperature and differential pressure CE transmitter F Imo D CP 210 KEY POINTS Range from 100 100 Pa to 2000 2000 mbar according to see Part number Input Pt100 on terminal block for temperature measurement range from 100 to 400 C probes as option Configurable intermediate ranges 4 wires analogue output 0 5 10 V or 0 4 20 mA Power supply 24 Vdc Vac or 115 230 Vac Trend indicator ABS V0 housing IP65 with or without display 4 turn system mounting with wall mount plate Solenoid valve for auto calibration only on CP211 and CP212 models FEATURES OF THE HOUSING 59 2 mm 115mm PART NUMBER Material ABS V0 as per UL94 Protection IP65 Display 75 x 40 mm LCD 19 digits 2 lines Height of digits Values 10 mm Units 5 mm Connection Ribbed 6 2 mm CP211 212 Compression for tubes 4x6 mm CP213 214 215 Pass through for cables 6 mm maximum Cable gland for cables 8 mm maximum Weight 320g To order just add the codes to complete the part number Example CP 211 HO cP Measuring range 1 100 100 Pa 2 1000 1000 Pa 3 10 000 10 000 Pa 4 500 500 mbar 5 2000 2000 mbar TECHNICAL FEATURES Units of measurement Accuracy Response time Resolution Tolerated overpres
3. ating temperature Storage temperature 24 Vac Vdc 10 115 Vac or 230 Vac 10 50 60 Hz 2 x 4 20 mA or 2 x 0 20 mA or 2 x 0 5 V or 2 x 0 10 V 4 wires Maximum load 500 Ohms 0 4 20 mA Minimum load 1 K Ohms 0 5 10 V Inputs and outputs 115 Vac 230 Vac models Outputs 24 Vac Vdc models 5 VA EN61326 Screw terminal block for cables 2 5 mm Kimo USB Mini Din cable Air and neutral gases Manual by push button Automatic by solenoid valve only CP211 CP212 Air and neutral gases From 0 to 50 C From 10 to 70 C CONFIGURABLE INTERMEDIATE OR CENTER ZERO RANGES Transmitter Breese tand Aivclocine vance These air velocity ranges are given for information based on a 3 y Fang Debimo differential probe Cm 0 81 and do not take into account CP211 100 100 Pa From 3 to 10 m s temperature compensation CP212 1000 1000 Pa From 3 to 30 m s CP213 10 000 10 000 Pa From 3 to 100 m s CP214 500 500 mbar Not available CP215 2000 2000 mbar Not available AIR FLOW AND AIR VELOCITY FUNCTION available option on CP211 CP212 and CP2T3 instruments Class 210 transmitters have 2 analogue outputs that correspond to both displayed parameters It is possible to activate one or two outputs and select for each output between pressure air velocity and air flow functions as option Linked to a differential pressure device Debimo blade Pitot tube orifice plate they can be equipp
4. display a code locking system allows to secure the installation See class 210 user manual e Software optional on all models Simple user friendly configuration See LCC SD user manual Configurable analogue output Range with central zero 50 0 50 Pa with offset zero 300 0 70 Pa or standard range 0 100 Pa it is possible to configure your own intermediate ranges Caution the minimum difference between the high range and the low range is 20 Configure the range according to your needs outputs are automatically adjusted to the new measuring range 100 0 100 100 0 50 100 New range So 0V 10 V 4 mA 20 mA OV 10V 4mA 20 mA 75 mm MOUNTING To mount the transmitter mount the ABS plate on the wall drilling 6 mm screws and pins are supplied Insert the transmitter on the fixing plate see A on the drawing beside Rotate the housing in clockwise direction until you hear a click which confirms that the transmitter is correctly installed 23 75 mm Once the transmitter is installed and powered up please make an autozero to guarantee the correct working of the transmitter in any position B14 mm 68 mm CALIBRATION Adjusting and calibration on site The professional configuration interface with a dynamic pressure calibration bench enables you to adjust and calibrate your transmitters directly on site or in laboratories Outputs diagnostic With th
5. ed as option with the SQR 3 function square root function allowing to calculate the air velocity and or air flow in a duct from a differential pressure e Air velocity calculation V C par p p Features Measuring ranges Units and resolutions Functions Air velocity From 3 to 100 m s according to model 0 1 m s 0 1 fom From 0 to 100 000 m h according to 1m h 0 1 m s Air flow air velocity and section 0 1I s 1 cfm Differential pressure device Pitot tube Debimo as option Po 287 1X 273 15 With C differential pressure device coefficient Pitot tube type L C 1 0015 Pitot tube type S C 0 84 Debimo blade C 0 8165 given temperature C P given atmospheric pressure Pa e Air flow calculation Air flow m h air velocity m s x surface m x 3600 Surface setting of duct type rectangular or circular and duct size mm or inch INTEGRATION OF PRESSURE MEASUREMENT The pressure measurement element is very sensitive and reacts to pressure changes When making measurements in unstable air movement conditions the pressure measurement may fluctuate The integration coefficient from 0 to 9 makes an average of the measurements and then helps avoid any excessive variations it guarantees a stable measurement CONNECTIONS Analogue outputs a DIP switch d Power supply type of the transmitter b Solenoid valve onl
6. is function you can check with a multimeter or on a regulator display or a PLC BMS if the transmitter outputs work properly The transmitter generates a voltage of 0 V 5 V and 10 V or a current of 4 mA 12 mA and 20 mA Certificate Class 210 transmitters are supplied with adjusting certificates Calibration certificates are available as an option MAINTENANCE Please avoid any aggressive solvent Please protect the transmitter and its probes from any cleaning product containing formalin that may be used for cleaning rooms or ducts OPTIONS AND ACCESSORIES e LCC S configuration software with USB cable Connection tube Straight connections e SQR 3 function square root for the measurement of air e Connection fittings e Spherical coupling nut velocity and air flow e Through connections e Calibration certificate Distributed by rale EXPORT DEPARTMENT iso 9001 Tel 33 1 60 06 69 25 Fax 33 1 60 06 69 29 Qualit e mail export kimo fr FTang transmitter_CP210 04 04 13 RCS 24 P rigueux 349 282 095 Non contractual document We reserve the right to modify the characteristics of our products without prior notice
7. sure Pressure transmitter 100 100 Pa measuring range with E power supply 115 or 230 Vac with display Display O with display N without display Power supply Output B 24 Vac Vdc H 115 or 230 Vac CP211 212 213 Pa mmH O mbar inWG mmHG daPa kPa hPa CP214 mbar mmH O kPa inWG mmHG hPa daPa PSI CP215 mbar mmH O kPa inWG mmHG hPa daPa PSI bar CP211 212 213 214 215 temp rature Pt100 C F CP211 212 0 5 of reading 2 Pa CP213 0 5 of reading 10 Pa CP214 40 5 of reading 0 5 mbar CP215 0 5 of reading 2 mbar CP211 212 213 214 215 Pt100 temperature 0 5 of reading 0 5 C 1 e 63 0 3 s CP211 212 213 1 Pa 0 1 mmH O 0 01 mbar 0 01 inWG 0 01 mmHG 0 1 daPa 0 001 kPa 0 01hPa CP214 1 mbar 1 mmH O 0 1 kPa 0 1 inWG 0 01 mmHG 1 hPa 10 daPa 0 01 hPa CP215 1 mbar 1 mmH O 0 1 kPa 0 1 inWG 0 01 mmHG 1 hPa 10 daPa 0 01 hPa 0 001 bar CP211 212 21 000 Pa CP213 69 000 Pa CP214 1400 mbar CP215 4100 mbar All the accuracies indicated in this technical datasheet were stated in laboratory conditions and can be guaranteed for measurements carried out in the same conditions or carried out with calibration compensation TECHNICAL SPECIFICATIONS Power supply Output Galvanic isolation Consumption Electromagnetical compatibility Electrical connection PC communication Environment Autozero Type of fluid Oper
8. y on Power supply CP211 212 terminal block c LCC S software connection Autevars V a Pressure connections paua a Cable glands Analogue output 1 Analogue output 2 Ba For power supply 24 For power supply 24 For power supply 230 Vac 115 Vdc models Vac models Vac models lt Ground Neutral N Oo Neutral N Phase L Oo Phase L 0 5 10 V Voltage GND Ground 0 4 20 mA Current 0 5 10 V Voltage GND Ground 0 4 20 mA Current ELECTRICAL CONNECTIONS as per NA15 100 standard This connection must be made by a qualified technician To make the connection the transmitter must not be energized Before making the connection you must first check the power supply indicated on the transmitter board see b on Connections part The selection of the output signal in voltage 0 10 V or 0 5 V or in current 4 20 mA or gt I POr tan emimere with AR VAG power SUPPI 0 20 mA is made via the DIP switch d of the electronic board of the transmitter put the on of switches as shown in the table below Configurations 4 20 mA 0 10 V 0 5 V 0 20 mA mme AAN NNN M D 1234 123 Power supply 24 Vac class II O Vac N L gt Connection of the output gt Connection of output in 230 Vac VacL in current 4 20 mA voltage 0 10 V 0 5 10V 0 4 20 mA 0 510 V 0 4 20 mA 230 Vac Power supply gt For transmitters with 115 or 230 Vac power supply