I-7080, I-7080B
Contents
1. 38 2 15 AA1H data Description Set the high trigger level of non isolated input Refer to Sec 1 8 4 for more information O Syntax SAA1H data chk cr is a delimiter character AA 2 character HEX module address from 00 to FF data 2 character decimal value for high trigger level The unit is 0 1 volt and the range can be from 0 0 to 5 0 volt chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 011H24 cr High trigger level 2 4 volt response 01 cr command 021H30 cr ee E response lt 102 en High trigger level 3 0 volt Note default is 2 4V I 7080 I 7080D I 7080B 17080BD User Manual V 2 2 39 2 16 AAIL Description Read the Low trigger level of non isolated input Refer to Sec 1 8 4 for more information Syntax SAAIL chk cr is a delimiter character AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D Response valid command gt AA data chk cr invalid command gt AA chk cr no response gt syntax err
2. 80
3. 0x0D O Example command O1DAO cr Disable counter O alarm response 01 cr command 02DA1 cr Disable counter 1 alarm response 02 cr 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 67 2 44 AAGN O Description Read the preset value of counter The AA6 command can reset counter to the preset value Refer to Sec 1 8 7 for more information O Syntax AAGN chk cr is a delimiter character AA 2 character HEX module address from 00 to FF N 0 gt read counter 0 1 gt read counter 1 chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA data chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address data 8 character HEX value chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command O1G0 cr The preset value of counter 0 response 010000 FFFF cr lis OOOOFFFF command O02G1 cr The preset value of counter 1 response 0200000000 cr lis 00000000 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 68 2 45 AAPN data Description Set the preset value of counter The AA6 command can reset counter to preset value Refer to Sec 1 8 7 for more information O Syntax
4. AA 2 character HEX module address S 0 host watchdog is disable S 1 host watchdog is enable TT 2 character HEX value from 00 to FF unit 0 1 second chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example Host watchdog timer of command 012 cr module 01 is disable response 01000 cr command 022 cr host watchdog timer of response 0210A cr module 02 is enable and 0 1 10 1 second 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 30 2 7 AA3ETT Description Enable disable the timer value of host watchdog The host watchdog timer is designed for software host watchdog When the software host watchdog is enable the host must send command to all modules before the timer is up When the command is received the host watchdog timer is reset and restart Use AA2 to read the host watchdog status amp value O Syntax AA3ETT chk cr is a delimiter character AA 2 character HEX module address from 00 to FF E 0 is disable and 1 is enable TT 2 character HEX value from 00 to FF unit 0 1 second chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address ch
5. VS Ext 24V Inl Data RS 485 Data 1 External Load Inl Data Gate0 Init A Gate0 Gatel E Inl RS 485 Data 1N4001 i RI 18 Ind D Gnd VS rm 19 Do0O Lo Gate0 SSR AC AA es R2 Note O If the external load is resistive load the 1N4001 can be omitted transistor lamp resistor O If the external load is inductive load the 1N4001 can tbe omitted relay coil 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 10 1 5 2 Frequency Input Use AABS command to select isolated non isolated input Gatel Gatel Ext GND Ext 24V RS 485 Data RS 485 Data Frequency 1 Frequency 0 non iolated isolated A Do0 Lo Frequency 0 bol Do1 Hi non iolated I 7018 amp I 7018D 1 5 3 Counter Input Counter 1 Ext GND amp Gate 1 Ext 24V isolated Inl RS 485 Data Inl Data RS 485 Data Counter 0 Gate0 i Counter 1 amp amp Gate 0 16 Gate 1 isolated non iolated A Do0 Lo Counter 0 amp bo Do1 Hi Gate 0 1 7018 amp 1 7018D non iolated 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 11 1 6 Quick Start Refer to I 7000 Bus Converter User Manual chapter 5 for the following functions module status unknown Sec 5 1 change address Sec 5 2 change baud rate Sec 5 3 checksum enable disable Sec 5 4 Wire connection Sec 2 4 Test program TEST EXE
6. Isolated or non isolated programmable O Isolation input levels Logic level 0 1V max Logic level 1 3 5V to 30V Isolation voltage 3750 Vrms non isolation input threshold level programmable Logic level 0 0 to 5V default 0 8V Logic level 1 0 to 5V default 2 4V Maximum count 32 bit 4 294 967 295 Programmable digital noise filter 2 us to 65 ms Alarming alarm on counter 0 or counter 0 amp 1 programmable Counter preset value programmable Display e LED Indicator 5 digit readout channel 0 or channel 1 Frequency Measurement O Input frequency 1Hz to 100K Hz max O Programmable built in gate time 1 0 0 1sec Digital Output 2 channels open collector to 30V 30mA max load O Power dissipation 300mW Power Power requirements I 7080 7080D 10V to 30V non regulated I 7080B 7080BD 24V to 30V non regulated Power consumption 2W for I 7080 2 2W for I 7080D 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 8 1 4 Block Diagram 5 digit LED 1 7080D Alarm Output Programmable Digital Filter Isolated Non isolated input selection Isolated Non isolated gate selection Programmable threshold voltage Save to i Ee ee Ee n Non isolated input EE EE EL EEPROM For 7080B 7080BD only 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 1 5 Application Wiring 1 5 1 Output Drive SSR or Other Load 1 7018 1 7018D Gatel Ext GND Gatel
7. Sec 1 8 2 for more information O Syntax AADA chk cr is a delimiter character AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 01DA cr Disable alarm response 01 cr command 02DA cr Dicsabloalarm response 02 cr 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 66 2 43 AADAN Description Disable alarm for alarm mode 0 Refer to Sec 1 8 2 for more information O Syntax AADAN chk cr is a delimiter character AA 2 character HEX module address from 00 to FF N 0 gt disable counter 0 1 gt disable counter 1 chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr
8. Sec 1 8 5 for more information Syntax SAAOL chk cr is a delimiter character AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D Response valid command gt AA data chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address data 5 character decimal value for min width at low level The unit is uS and the range can be from 2 uS to 65535 uS chk 2 character checksum if checksum disable gt no chk cr 0x0D Example command 010H cr Min width 20 uS response 0100020 cr command 020H cr ROET OPE response 0202000 cr EE a 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 36 2 13 AAOL data Description Set the min input signal width at low level Refer to Sec 1 8 5 for more information Syntax SAAOH data chk cr is a delimiter character AA 2 character HEX module address from 00 to FF data 5 character decimal value for min width at low level The unit is uS and the range can be from 2 uS to 65535 uS chk 2 character checksum if checksum disable gt no chk cr 0x0D Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or ad
9. They provide A D D A DI O Timer Counter and other functions These modules can be remote controlled by a set of commands The common features of I 7080 and I 7080D are given as following 2 independent 32 bit counter counter 0 amp counter 1 input signal can be isolated or non isolated programmable digital filter for isolated and non isolated input external gate control for isolated and non isolated input programmable threshold value for non isolated input programmable alarm output input frequency measurement up to 100K Hz The I 7080D is the I 7080 with a 5 digit LED display The counter value and input signal frequency can be shown in LED directly without PC control The I 7080B will save the counter value to EEPROM when the power goes off Refer to Sec 3 3 for details More Information Refer to I 7000 Bus Converter User Manual chapter 1 for more information as following 1 1 I 7000 Overview 1 2 I 7000 RELATED DOCUMENTATION 1 3 I 7000 COMMON FEATURES 1 4 I 7000 SYSTEM NETWORK CONFIGURATION 1 5 I 7000 Dimension 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 4 1 1 7080 7080D amp 4080 4080D Comparison between I 7080 amp I 7080D o 080080 S digitLED No Yes command Alarm on counter 0 only Yes programmable Yes programmable Alarm on counter 0 amp 1 Yes programmable Yes programmable Channel 0 amp channel 1 are Yes Yes both non isolated input mode 0 AABO Channel
10. cr is a delimiter character AA 2 character HEX module address from 00 to FF data 8 character HEX value chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command O1SAFFFFOOOO cD JThe alarm limit of counter 1 response 01 cr is FFFF0000 command 02SA0000FFFF cr Frhe alarm limit of counter 1 response 02 cr is OOOOFFFF 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 72 2 49 AASA data Description Set Hi Hi alarm limit of counter O for alarm mode 1 Refer to Sec 1 8 2 for more information O Syntax AASA data chk cr is a delimiter character AA 2 character HEX module address from 00 to FF data 8 character HEX value chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 cha
11. or counter to the preset value amp clear the overflow flag Refer to Sec 1 8 7 for more information O Syntax AA6N chk cr is a delimiter character AA 2 character HEX module address from 00 to FF N 0 2 counter 0 1 gt counter 1 chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 01GO cr Preset value 0 response 0100000000 cr Reset counter 0 to preset value command 0160 cr 0 response 01 cr command O1G1 cr Preset value 0xABCD response 010000ABCD cr Reset counter 1 to preset value command 0161 cr OxXABCD response 01 cr 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 49 2 26 AA7N Description Read the overflow flag of counter The user can use AA6S comand to reset counter amp clear overflow flag O Syntax AA7N chk cr is a delimiter character AA 2 character HEX module address from 00 to FF N 0 2 counter 0 1 gt counter 1 chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AAS chk cr invalid c
12. trigger level Sec 2 16 SAA1L data Set low trigger level Sec 2 17 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 22 General Counter Command Set SAAOL data IAA Setmin width of High Sec 2 13 SAAIH AA data Read high trigger level__ Sec 2 14 SAATH data IAA Sethightriggerlevel Sec 2 15 SAAIL AA data Read low trigger level__ Sec 2 16 SAA IL data IAA Setlowtriggerlevel_ Sec 2 17 SAA3N____ AA data Read max counter value Sec 2 19 AA3N data IAA Set max counter value Sec 2 20 SAAA AAS Read filter status Sec 221 SAAAS IAA Set filter status Sec 2 22 SAASN AAS Read the counter status Sec 2 23 SAASNS AA Set the counter status See 2 24 SAA N AA Reset counter Sec 225 SAA7N VAAS Read overflow status _ Sec 2 26 SAAA JAAG Read gatemode__ Sec 2 30 SAAAG AA Set gate mode Sec 231 SAAB AAS Read input mode Sec 2 32 SAABS AA Set inputmode See 2 33 AADI___ AASODO0_ Read D O amp alarm state Sec 2 37 AADOOD AA Set D O value See 2 38 AAGN __ AAdata _ Read preset value __ Sec 2 44 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 23 Alarm mode 0 Command Set value value Alarm mode 1 Command Set LED Command Set SAAS HAAS Read LED configuration Sec 2 27 SAA8V MAA SetLED configuration Sec 2 28 A A9 data MAA Send data to LED Sec 2 29 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 24 2 1 AANNTT
13. 0 amp channel 1 are Yes both isolated input mode 1 AAB1 Channel 0 is non isolated Yes amp channel 1 is isolated input mode 2 AAB2 Channel 0 is isolated amp Yes channel 1 is non isolated input mode 3 AAB3 Input frequency 100K max 100K max Default setting 4080 compatible 4080D compatible default setting of I 7080 High alarm on counter 0 amp Counter preset value 0 Module name 7080 default setting of I 7080D O High High High alarm on counter 0 Counter preset value 0 Module name 7080D 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 5 Comparison between 4080 amp 4080D po OB BOD Channel O amp channel 1 are Yes Yes both non isolated input mode 0 AABO Channel 0 amp channel 1 are Channel 0 is non isolated amp No No channel 0 is isolated input mode 2 AAB2 Channel 0 is isolated amp No No channel 1 is non isolated input mode 3 AAB3 Input frequency 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 6 1 2 Pin Assignment Isolated Input Non isolated Input 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 1 3 Specifications i 7080 Counter Frequency Module i 7080D i 7080 with LED Display i 7080B Refer to Sec 3 3 for details i 7080BD Refer to Sec 3 3 for details Counter Input O Channels Two independents 32 bit counters counter 0 amp 1 Input signal
14. 1L data gt low level threshold value read back 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 1 8 9 Counter Input Applications Tyepe 50 Counter 0 Counter AABO gt input mode 0 Non isolated channel Non isolated channel AA1H data amp O amp threshold value 1 amp threshold value AA1L data active active AAB1 gt input mode 1 SAA1H data amp AA 1L data Isolated channel 0 Isolated channel 1 AAB2 gt input mode 2 AA1H data amp AA 1L data Non isolated channel O amp threshold value active Isolated channel 1 AAB3 gt input mode 3 AA1H data amp AA 1L data Isolated channel 0 Non isolated channel 1 amp threshold value active Note the threshold value command AA1H data amp AA1L data are effective to Non isolated input only 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 1 9 Tables Configuration Code Table CC 06 9600BPS 08 38400BPS 09 57600 BPS_ Configuration Code FF 2 char for all frequency gate time O disable 0 0 1 second 1 enable 1 1 0 second Configuration Code Table TT TT Input Range 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 21 2 Command Set General Command Set AANNTTCCFF JAA Setmodule configuration S Enable Host Watchdog Timer Frequency Command Set SAA 1H data Set high trigger level Sec 2 15 SAAIL AA data Read low
15. 7080B I7080BD User Manual V 2 2 58 2 85 AAI Description Read the value of INIT pin O Syntax SAAI chk cr is a delimiter character AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AAS chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address S 0 2 INIT pin is connected to GND pin 1 gt INIT pin is open chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 01I cr INIT pin is connected to GND pin response 010 cr command 02I cr ET response 021 cr INIT pin is open 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 59 2 36 SAAM Description Read the module name O Syntax AAM chk cr is a delimiter character AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA data chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 charact
16. AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 01B0 cr Counter freguency channel 0 is non response 01 cr isolated channel 1 is non isolated ond il Counter frequency channel 0 is A a AGE isolated channel 1 is isolated o o Counter frequency channel 0 is non p m isolated channel 1 is isolated 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 57 2 34 AAF Description Read the version number of firmware O Syntax SAAF chk cr is a delimiter character AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA data chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address data 5 character for version number chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 01F cr Ver A2 0 response 01A2 0 cr command 02F cr Ver A3 0 1 7080 I 7080D I
17. AAPN data chk cr is a delimiter character AA 2 character HEX module address from 00 to FF data 8 character HEX value chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA data chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command O1POFFFFOOOO cr The preset value of counter response 01 cr 0 is FFFFOOOO command 02P10000FFFF cr pre preset value of counter response 02 cr 1 is OOOOFFFF 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 69 2 46 AAPA data Description Set alarm limit of counter O for alarm mode 0 Refer to Sec 1 8 2 for more information O Syntax AAPA data chk cr is a delimiter character AA 2 character HEX module address from 00 to FF data 8 character HEX value chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module add
18. APPLICATION WIRING WEE Re SE Ge Ee n Ee ee ee SR sege Oe bdts 10 1 6 VQUICK START EE AE A OR Re EE Re DEEG 12 1 7 DEFAULT SETTINGS 20332 EES EE SR ER as el adh sd 14 1 8 APPLICATION NOTES iis sessie iii Gee RR Geb ee Ge SEG ee Reg Rees Ee 14 19 TABLES EE OE ER EE EE EE OR 21 2 COMMAND SET ee Se es ds Ge n es de gees els re ee deed sees ee ee ee dee bees ee deso ees ee ee Ge Dee 22 21 POAANNTTC GRE EE N RE EE EE EE N EE 25 22 NE EE EE EE EE EE HEN 26 DI a 27 PvR EE EE EE ON 28 YE SERE EE ER eter EE EE EE 29 O NA et 30 2 1 SAA ETI a ds 31 a SN EER EO OER EE EE ORN 32 29 EAAD NAME escorial ASE EER Seg ER E ek ak eeue Ee Gee ee ceive it dee ee ek 33 2 10 DAA Os ve ES GE TE We aed tence oh tds ie Hes Gon ES Ee Ne Re 34 AE SEEN ST sie alate Sle ei i A eles alee pean alee alae bl eye 35 2 12 SAA OD EER tects heaved tee eet aa a ee thee ete hehe 36 III RIC a oe EE O cacnnetaaae 37 2 14 BAA oho RA N N A EA 38 VS KAB YA e edo e 39 2 16 NN 40 A e E o a Mad A Re 41 DA AA tea e it OE RE Ao e RE Di 42 2 19 BAAS ER EE EE EE OE nea oats eee eae 43 2200 BANDA a a des a etek 44 2 21 A O 45 2 22 SAAAS Ed EE EE EE bee Re hh etal al nt ena ae 46 2 23 ASTE ER EE ER EE EE EE EE EE ER OE 47 2 24 BAASING A eid eee Shieh een Bi ee a E hee EEEE A es 48 2 25 BAAGON EE EE OE N EE ET EIE 49 2 26 SAA TN SS EG ota 50 2 27 SAAB SE doce Hei An en ee ee E i ees 51 2 28 DAA e o e die ed en SU AE es EE BES is 52 2 29 DAA DATA ridad tdi tada tds e
19. CCFF Description Set the configuration of module O Syntax JAANNTTCCFF chk cr is a delimiter character AA 2 character HEX module address from 00 to FF NN new AA TT input type code refer to Sec 1 9 CC baud rate code refer to Sec 1 9 FF status code refer to Sec 1 9 chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 0102500600 cr address 01 is configured to a response 02 cr new address 02 counter command 0202510600 cr Change to frequency mode response 02 cr Refer to I 7000 Bus Converter User Manual chapter 5 for the following functions O module status unknown Sec 5 1 change address Sec 5 2 O change baud rate Sec 5 3 checksum enable disable Sec 5 4 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 25 2 2 AAN Description Read counter or freguency value Syntax AAN chk cr 1s a delimiter character AA 2 character HEX module address from 00 to FF N 0 gt channel 0 of counter or frequency 1 gt channel 1 of counter or frequency chk 2 chara
20. Description Enable counter alarm for alarm mode 0 Refer to Sec 1 8 2 for more information O Syntax AAEAN chk cr is a delimiter character AA 2 character HEX module address from 00 to FF N 0 2 enable counter 0 1 gt enable counter 1 chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command OIEAO cr Enable counter 0 response 01 cr corn N EE response 02 cr 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 63 2 40 AAEAT Description Enable counter alarm for alarm mode 1 Refer to Sec 1 8 2 for more information O Syntax AAEATIchk cr is a delimiter character AA 2 character HEX module address from 00 to FF T M gt momentary alarm T L gt latch alarm chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2
21. Digital filter is disable response 010 cr command 024 cr Digital filter 1s enable response 021 cr 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 45 2 22 AA4S Description Set the filter status Refer to Sec 1 8 5 for more information O Syntax AA4S chk cr is a delimiter character AA 2 character HEX module address from 00 to FF S 0 gt digital filter is disable 1 gt digital filter is enable chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 0140 cr Digital filter is disable response 01 cr command 0241 cr Digital filter 1s enable response 02 cr 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 46 2 23 AA5N Description Read the counter status O Syntax SAASN chk cr is a delimiter character AA 2 character HEX module address from 00 to FF N 0 2 counter 0 1 gt counter 1 chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AAS chk cr invalid command gt AA chk cr no
22. I 7080 I 7080B User Manual I 7000 New Features gt Your Powerful Tools 1 Self Tuner Inside 2 Multiple Baud Rate 3 Multiple Data Format Create New Ideas Create New Applications Warranty All products manufactured by ICP DAS are warranted against defective materials for a period of one year from the date of delivery to the original purchaser Warning ICP DAS assume no liability for damages consequent to the use of this product ICP DAS reserves the right to change this manual at any time without notice The information furnished by ICP DAS is believed to be accurate and reliable However no responsibility is assumed by ICP DAS for its use nor for any infringements of patents or other rights of third parties resulting from its use Copyright Copyright 1998 by ICP DAS All rights are reserved Trademark The names used for identification only maybe registered trademarks of their respective companies i 4 Dual WatchDog Inside 5 True Distributed Control 6 High Speed amp High Density I O 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 1 Table of Contents 1 INTRODUCTION asse sede ese ie gids dee Ge Ee Se vo ed eko Ge Bede dd bede De dd be ge ee ee ie ged es ie ek colo degie ae d 1 1 7080 7080D amp A08S0O AO8OD ee ee RA AR ee RA AR RA ee ee ee Re ee ee ee ee 5 1 2 PIN ASSIGNMENT lt 3 sos RE OE E E alee TE 7 1 3 SPECIFICATION Sia 8 1 4 dele doe TARKA io e 9 125
23. O set high alarm limit of channel 0 AAPA data if counter 0 gt alarm limit 0 gt D O 0 turn ON if counter O lt alarm limit 0 gt D O O turn OFF enable channel 1 AAEAI1 disable channel 1 AADAI set high alarm limit of channel 1 AASA data if counter 1 gt alarm limit 1 gt D O 1 tum ON if counter 1 lt alarm limit 1 gt D O 1 turn OFF The alarm mode 1 is designed for single channel application as following select alarm mode 1 AAA 1 for channel 0 only enable channel 0 AAEAT disable channel 0 AADA clear latch alarm AACA set high alarm limit AAPA data set high high alarm limit AASA data D O 0 Counter 0 lt high alarm OFF high alarm lt counter 0 amp ON counter 0 lt high high alarm High high alarm lt counter 0 ON ON Note high high alarm must greater than high alarm 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 15 1 8 3 Digital Output Application Notes The D OO0 amp D O1 can be used as D O or alarm output as following e can be used as D O in the frequency mode e can be used as D O in the counter mode amp alarm disable by AADA or AADAN command e can be used as alarm output in the counter mode amp alarm enable by AAEAT or AAEAN command D O 0 D O 1 Frequency mode D O 0 D O 1 Counter mode amp alarm disable D O 0 D O 1 Counter mode amp alarm enable alarm High alarm Hi
24. O will not change and the module status is set to 04 If the host computer send out AADO to those modules now those modules will ignore this command and return as warning information The host can use AA1 command to clear the module status to O then the I 7080 amp I 7080D module will accept the AADO again If the D O output is configured as alarm output the module will control the ON OFF state automatically Therefore the AADO command will be ignored in this condition 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 79 3 3 New Features of 7080B Difference between 7080 amp 7080B 7080 7080B type 50 or 51 50 51 or 52 default type 50 counter 52 backup counter Firmware Version A1 9 B1 0 Other commands Same Windows driver amp utility Same Pins assignment Same 0 AAPN data in Type 50 Same AAPN data in Type 51 Same 0 AAPN data in Type 52 N A Set current counter value amp preset value in EEPROM Note 1 The 7080B will 100 as same as 7080 if the type is set to 50 or 51 2 Assume 7080 7080B is set to type 50 AAPN data command will set the preset value in EEPROM but the current counter is no changed 3 Assume 7080B is set to type 52 AAPN data command will set the current counter value amp preset value in EEPROM at the same time 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2
25. Refer to NAP7000S User Manual for details 1 6 1 Frequency Input Measurememt 1 Refer to Sec 1 5 2 for wire connection Power on and run test exe 2 press 2 3 press 012 Enter gt Receive 01500600 4 press 2 5 press 0101510600 Enter gt Receive gt 01 6 press 2 7 press 01B0 Enter gt Receive 01 8 press 2 9 press 010 Enter gt Receive gt 10 press 2 11 press 011 Enter gt Receive gt O step 3 the status of I 7080 is COUNTER mode O step 5 change to frequency mode O step 7 select non isolated input O step 9 frequency measurement of channel 0 O step 11 frequency measurement of channel 1 Note the command 01B1 step 7 can be used to select the iso lated input the command 01B2 and 01B3 are used for the other selections 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 12 1 6 2 Counter input Measurement 1 Refer to Sec 1 5 2 for wire connection Power on and run test exe 2 press 2 3 press 012 Enter gt Receive 01500600 4 press 2 5 press 01B0 Enter gt Receive 01 6 press 2 7 press 010 Enter gt Receive gt 8 press 2 9 press 011 Enter gt Receive gt step 3 the status of I 7080 is COUNTER mode step 5 select non isolated input O step 7 counter measurement of channel 0 step 9 counter measurement of channel 1 Note the command 01B1 step 7 can be used to select the iso lated input t
26. able gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 01M cr Change module name from response 017080 cr 7080 to 8080 command 0108080 cr response 01 cr command 01M cr Change module name from response 017080D cr 7080D to 8080D command 0108080D cr response 01 cr Note This command is designed for OEM ODM user The user can use it to change the module name for other purpose 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 33 2 10 AAOH Description Read the min input signal width at high level Refer to Sec 1 8 5 for more information Syntax SAAOH chk cr is a delimiter character AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D Response valid command gt AA data chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address data 5 character decimal value
27. acter AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command 2 AA data chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address data 8 character HEX value chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 01RP cr The Hi alarm limit of response 01FFFFOOOO cr counter 0 is FFFF0000 command 02RP cr The Hi alarm limit of response O20000FFFF cr counter 0 is OOOOFFFE 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 75 2 52 AARA Description Read alarm limit of counter 1 for alarm mode 0 Refer to Sec 1 8 2 for more information O Syntax AARA chk cr is a delimiter character AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address data 8 character HEX value chk 2 character checksum if checksum disable
28. ble gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 01999999 cr Show max 99999 response 01 cr command 0290 0000 cr Show min 0 0000 response 02 cr command 03912 345 cr Show display 12 345 response 03 cr 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 53 2 30 AAA Description Read gate control mode Refer to Sec 1 8 6 for more information O Syntax AAA chk cr is a delimiter character AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AAG chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address G 0 gt gate is low active 1 gt gate is high active 2 gt gate is disable chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example er ee response 010 cr command 02A cr
29. character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command O1EAL cr Latch alarm response 01 cr command 02EAM cr Momentary alarm response 02 cr NOTE if the alarm is enable the D O 0 amp D O 1 will be always controlled by module Therefore the following D O commands will be ignored O power on value is changed to hi lo condition immediately O the AADOOD command is ignored 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 64 2 41 AACA Description Clear latch alarm for alarm mode 1 Refer to Sec 1 8 2 for more information O Syntax AACA chk cr is a delimiter character AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 01CA cr Clear latch alarm response 01 cr command 02CA cr Clear latch alarm response 02 cr 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 65 2 42 AADA Description Disable alarm for alarm mode 1 Refer to
30. cter checksum if checksum disable gt no chk cr 0x0D O Response valid command gt gt chk data cr invalid command gt No Response no response gt syntax error or communication error or address error gt is a delimiter character indicating a valid command data 8 character data in HEX format chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 012 cr Counter 0 0x 1E 30 in response 01500600 cr decimal command 010 cr response gt 0000001E cr command ae Frequency 1 0x1E Hz 30 response 02510600 cr Hz in decimal command 021 cr response gt 0000001E cr 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 26 93 Ek 7080 7080D Description Host send this command to tell all modules Host is OK Syntax chk cr is a delimiter character chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response no response O Example command cr response No Response 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 27 2 4 ARO O Description Read the module status The module status will be latched until AA1 command is sent If the host watchdog is enable and the host is down the module status will be set to 4 If the module status 4 all output command will be ignored O Syntax AAO chk cr is a delimiter character AA 2 character HEX module addre
31. dita 53 2 30 TAAA ER OR llo OO rd lt EE 54 2 31 O EE ee eee Ae Bie GE R EG Ge gee SE ee 55 2 32 SAAB ES EE EE a etait a 56 2 33 SAAB Sois EE ER EE ER EE OE OE he ee 57 2 34 SNARE A eee eee N ea ae ge epee ere eee 58 2 35 BAA Tits EE EE EE ED oh EE EE De ae eee Es ee ee ee ees 59 2 36 STER ER eo goth EE OE ER 60 2 37 AAD I oss EL ee ese ed duce dacs Re A ee De ER ee ee ee ee Re Ee ese 61 2 38 AADOOD ie EE GE Ee GE EE GR ene ee ae eae aa aes 62 2 39 CAABAN EE N EE EO eave E ean ede eas 63 2 40 AABA MEE EE ER EE OE EE EG 64 2 41 AACA EO AE EE EL ER wenes 65 2 42 OAADA EER GR WE EE att 66 2 43 AADAN SE Sins ee Os 67 2 44 OAAGN A ER AE N OR EE ewan oes AEA KEN 68 JA A AA 69 A E CO 70 DAT AO PRP RINT e oe e al o e e A A e et e 71 DAS AAAS SADATA o e ie Se 72 J49 DRA IRI RE ta 73 2 50 OAAR Pi RE KOLE OR N EE EE N 74 2 51 OAARP EE EE EN aii 75 2 52 OVER EO EE RE N OE RE OE ER EE 76 2 53 OPEN AE EE EN EE EE EE EE Ie TI OPERATIONS PRINCIPLE amp APPLICATION NOTES esse esse esse esse esse esse see sees sees see see se 78 3 1 INIT PIN OPERATION PRINCIPLE sass sees ees ee ee seg se seep se age pil 78 3 2 DIO OPERATION PRINGIPEE s5 Gass kepe eE GEE Gee Se Ee SE BE Reg ee De EER BES EKG EED Red sos Ve De ke Fee 79 3 3 New Features of 7080B tds GR ESE AS RE EG damian senses 80 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 3 1 Introduction I 7000 is a family of network data acquisition and control modules
32. dress error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D Example command 010H00020 cr Min width 20 uS response 01 cr command 020H02000 cr Min width 2000 uS 2 mS response 02 cr 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 37 2 14 SAATR Description Read the high trigger level of non isolated input Refer to Sec 1 8 4 for more information O Syntax SAA1H chk cr is a delimiter character AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA data chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address data 2 character decimal value for high trigger level The unit is 0 1 volt and the range can be from 0 0 to 5 0 volt chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 011H cr High trigger level 2 4 volt response 0124 cr command 021H cr a responses 10230 en High trigger level 3 0 volt 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2
33. e 01 cr command 021L10 cr 7 E response lt 102 en Low trigger level 1 0 volt Note default is 0 8 V I 7080 I 7080D I 7080B 17080BD User Manual V 2 2 41 2 18 AA2 Description Read the configuration of module O Syntax SAA2 chk cr is a delimiter character AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AATTCCFF chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address TT CC FF refer to Sec 1 9 chk 2 character checksum if checksum disable gt no chk cr 0x0D apa Address 01 counter 9600 BPS command 012 cr checksum disable response 01500600 cr command 022 cr Address 02 frequency 19200 BPS response 102510700 cr checksum disable NOTE If the user use lA ANNTTCCFF command to change module configuration the new configuration code will be stored into EEPROM immediately The configuration code includes module address module type baud rate code checksum enable disable code calibration code power on value and safe value The EEPROM data of 1 7000 can be read infinite times and can be written about 100 000 times max Therefore the user should not change configura
34. er HEX module address data 4 character for module name chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 01M cr Module name of 01 is 7080 response 017080 cr command 02M cr Module name of 02 is 7080D response 1027080D cr 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 60 2 37 AADI Description Read the status of D O amp alarm Refer to Sec 2 8 for more information O Syntax AADI chk cr is a delimiter character AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AASODOO chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address D 0 gt D O0 D 01 OFF 1 gt D O0 ON D O1 OFF 2 gt D OO OFF D O1 ON 3 gt D O0 D O1 ON Alarm S 0 gt counter 0 alarm disable counter 1 alarm disable mode 0 1 gt counter 0 alarm enable counter 1 alarm disable 2 gt counter 0 alarm disable counter alarm enable 3 gt counter 0 alarm enable counter 1 alarm enable S 0 gt counter 0 alarm disable ce 1 gt counter 0 alarm enable amp MOMENTARY mode 2 gt counter 0 alarm enable amp LATCH mode chk 2 character checksum if checksum disable gt
35. for min width at high level The unit is uS and the range can be from 2 uS to 65535 uS chk 2 character checksum if checksum disable gt no chk cr 0x0D Example command 010H cr Min width 10 uS response 0100010 cr command 020H cr ea response 0201000 cr Min width 1000 us 1 ms 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 34 2 11 AAOH data Description Set the min input signal width at high level Refer to Sec 1 8 5 for more information Syntax SAAOH data chk cr is a delimiter character AA 2 character HEX module address from 00 to FF data 5 character decimal value for min width at high level The unit is uS and the range can be from 2 uS to 65535 uS chk 2 character checksum if checksum disable gt no chk cr 0x0D Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D Example command 010H00010 cr Min width 10 uS response 01 cr command 020H01000 cr Min width 1000 uS 1 mS 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 35 2 12 AAOL Description Read the min input signal width at low level Refer to
36. gh high alarm mode 1 AAA1 on counter O on counter 0 Counter mode amp alarm enable alarm Alarm on D O 1 or alarm mode 0 AAAO amp AAEAO counter 0 on counter 1 Counter mode amp alarm enable alrm D O 0 or alarm on counter mode 0 AAAO amp AAEAI1 alarm on 1 counter 0 1 8 4 Programmable Threshold Voltage Setting The programmable threshold voltage is valid for non isolated input of counter mode 50 amp frequency mode 51 The default setting are given as following TTL compatible low trigger level 0 8 volt high trigger level 2 4 volt The high trigger level can be changed by AA1H data command the low trigger can be changed by AA1L data comand The high trigger level must be greater than the low trigger level 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 16 1 8 5 Digital Filter Setting The digital filter is disable in frequency mode 51 The digital filter is designed as a pulse width filter in both high low pulse The digital filter is valid for both nono isolated amp isolated input The digital filter can be enable or disable The key points of using digital filter are given as following 1 Use AABS to select input signal Use AAOH data to set min width of high level Use AAOL data to set min width of low level Use AA4S to enable disbale digital filter both channels naa ile Sa If the high width of input signal is small than the min high width
37. gt no chk cr 0x0D O Example command 01RA cr The alarm limit of counter 1 response 01FFFFOOO0O cr is FEFFOOOO command 02RA cr The alarm limit of counter 1 response O20Q000FFFF cr is OOOOFFFF 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 76 2 53 AARP Description Read Hi Hi alarm limit of counter O for alarm mode 1 Refer to Sec 1 8 2 for more information O Syntax AARP chk cr is a delimiter character AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command 2 AA data chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address data 8 character HEX value chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 01RP cr The Hi Hi alarm limit of response O1FFFFOOOO cr counter 0 is FFFFO000 command 02RP cr The Hi Hi alarm limit of response 1020000FFFFE cr counter 0 is OOOOFFFF 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 77 3 Operations Principle amp Application Notes 3 1 INIT _pin Operation Principle All I 7000 modules contain an EEPROM to store configuration information Therefore the user is difficu
38. he command 01B2 and 01B3 are used for the other selections 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 13 1 7 Default Setting The default setting is given as following address 01 baud rate 9600 checksum disable data 1 start 8 data 1 stop no parity type 50 gt counter input alarm hi alarm on counter 0 amp counter 1 I 7080 hi hi hi alarm on counter 0 1 7080D 1 8 Application Notes 1 8 1 Counter Frequency Input Mode Selection The counter frequency input can be selected from isolated or non isolated signal The channel 0 amp channel 1 can be selected separately There are 4 different input mode given as following These four input modes can be used in both of I 7080 amp 1 7080D Input Mode Command Channel 0 Channel 1 Input mode 0 AABO Non isolated Non isolated Input mode 1 AABI1 Isolated Isolated Input mode 2 AAB2 Non isolated Isolated Input mode 3 AAB3 Isolated Non isolated 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 14 1 8 2 Counter Alarm Mode Selection There are no alarm function in frequency mode 51 There are two counter alarm mode alarm mode O amp alarm mode 1 These two alarm modes can be used in both of I 7080 amp I 7080D The alarm mode 0 is designed for two channel application as following select alarm mode 0 AAAO for both channels enable channel 0 AAEAO disable channel 0 AADA
39. k 2 character checksum if checksum disable gt no chk cr 0x0D O Example O oe command 013000 cr a ro E chdog timer response 01 cr command 02310A cr host watchdog timer of response 02 cr module 02 is enable and 0 1 10 1 second 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 31 2 8 AAAS Description Set counter alarm mode Refer to Sec 1 8 2 for more information O Syntax AAAS chk cr is a delimiter character AA 2 character HEX module address from 00 to FF S 0 gt alarm mode 0 1 gt alarm mode 1 chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command O1A0 cr Set alarm mode 0 response 01 cr command ee Set alarm mode 1 response 02 cr 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 32 2 9 AAO name Description Set module name O Syntax AAO name lchkl cr is a delimiter character AA 2 character HEX module address from 00 to FF name 4 character 5 character module name chk 2 character checksum if checksum dis
40. k cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address S 0 gt channel 0 is non isolated channel 1 is non isolated 1 gt channel 0 is isolated channel 1 is isolated 2 gt channel 0 is non isolated channel 1 is isolated 3 gt channel 0 is isolated channel 1 is non isolated chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 01B cr Counter frequency channel 0 is non response 010 cr lisolated channel 1 is non isolated command o Counter frequency channel 0 is A EE isolated channel 1 is isolated o 7 EN Counter frequency channel 0 is non p m isolated channel 1 is isolated 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 56 2 33 AABS Description Set input mode Refer to Sec 1 8 1 for more information O Syntax AABS chk cr is a delimiter character AA 2 character HEX module address from 00 to FF S 0 gt channel 0 is non isolated channel 1 is non isolated 1 gt channel 0 is isolated channel 1 is isolated 2 gt channel 0 is non isolated channel 1 is isolated 3 gt channel 0 is isolated channel 1 is non isolated chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt
41. lt to find out the status of the I 7000 modules The user can connect the INIT _pin to GND_pin and power on the module The I 7000 modules will go to the factory default setting without changing the EEPROM data The factory default setting is given as following address 00 baud rate 9600 checksum DISABLE data format 1 start 8 data bits 1 stop bit If the user disconnect the INIT _pin and GND pin the I_7000 module will be auto configured according to the EEPROM data The user is easy to find the EEPROM configuration data in the default setting The steps are shown as following Step 1 power off and connect INIT _pin to GND_pin Step 2 power on Step 3 send command string 002 0x0D to the module the module will return back the EEPROM data Step 4 record the EEPROM data of this I 7000 module Step 5 power off and disconnect INIT _pin and GND_pin Step 6 power on Refer to I 7000 Bus Converter User Manual Sec 5 1 for more information 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 78 3 2 D O Operation Principle 1 2 3 4 5 Refer to Sec 1 8 3 for more information The D O output of I 7080 amp I 7080D modules will be turn OFF after first power on The D O output will be changed to the desired state if the AADO command is received Then all these D O will keep in the same states until next AADO command If the host watchdog is active all the D
42. lue of channel 1 response 021 cr command 038 cr response 1032 cr HOST control the LED display 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 51 2 28 AA8V FosoD Description Select LED Configuration O Syntax AA8V chk cr is a delimiter character AA 2 character HEX module address from 00 to FF V 0 gt LED shows counter frequency channel 0 1 gt LED show counter frequency channel 1 2 gt HOST control LED chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 0181 cr LED shows channel 1 response 01 cr command 0282 cr HOST will control LED response 02 cr command 029040 00 cr response 02 cr 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 52 2 29 AA9 data osoo Description Send data to LED display O Syntax AA9 data chk cr is a delimiter character AA 2 character HEX module address from 00 to FF data gt 5 decimal digit 1 decimal point max 99999 min 0 0000 chk 2 character checksum if checksum disa
43. no chk cr 0x0D O Example command 01DI cr Alarm disable response 0100000 cr D OO D O1 0OFF command 02DI cr Alarm enable D OO ON response 0230100 cr b O1 0FF 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 61 2 38 AADOOD Description Set digital output O Syntax AADOOD chk cr is a delimiter character AA 2 character HEX module address from 00 to FF D 0 gt D O0 D O1 0FF 1 gt D O0 ON D O1 OFF 2 gt D OO OFF D O1 ON 3 gt D O0 D 01 ON chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr alarm is enable gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command O1DOOO cr Turn all D O OFF response 01 cr command 02DOO01 cr Turn D O 0 ON response 02 cr Turn D O 1 OFF NOTE if the alarm is enable the D O 0 D O 1 will be always controlled by module Therefore the following D O commands will be ignored O power on value is changed to hi lo condition immediately O the AADOOD command is ignored 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 62 2 39 AAEAN O
44. ntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 010 cr module status 0x04 gt host is down response 0104 cr command 01DO000 cr Output command is ignored response cr ee ae response 01 cr command 010 cr dule status 0x00 response 0100 cr eee ee command 01DO00 cr Output command is OK response gt cr 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 29 2 6 AA2 Description Read the status and timer value of host watchdog The host watchdog timer is designed for host watchdog When the host watchdog is enable the host must send command to all modules before the timer is up When the command is received the host watchdog timer is reset and restart Use AA3ETT to enable disable setting the host watchdog timer O Syntax AA2 chk cr is a delimiter character AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AASTT chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command
45. of digital filter this input signal will be filtered out Also the low width of input signal must be greater than the min low width of digital filter For example the width of input signal is greater than 1000 us the user can set the digital filter at 900 us Therefore all noise below 900 us will be filtered out by the digital filter These steps are given as following 1 SAABO 2 SAAOHOO9OO 3 AA0L00900 4 AA41 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 17 1 8 6 Gate Control Setting The gate control will be ignored in frequency mode 51 The gate control is defaultly disable in counter mode 50 The user can use command to enable disable the gate control as following AAAO gt gate input must be low to enable counter SAAAI gt gate input must be high to enable counter AAA2 gt gate input is ignored The counter will be always enable 1 8 7 Preset Value Setting The preset value will be ignored in frequency mode 51 The counters will go to their preset value in the first power on state The reset counter command AA6N also force the counters go to their preset value The factory default setting of preset value is 0 The user can use the AAPN data command to change the preset value The key points are given as following I 7080 amp I 7080D Factory default setting Counter preset value is 0 Power on state Counter 0 1 go to preset value AA6N Counter N go to p
46. ommand gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address S 0 gt no overflow 1 gt is overflow chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 0170 cr Counter 0 is overflow response 011 cr command 0160 cr Clear the overflow flag response 01 cr command 0171 cr Counter 1 is OK response 010 cr 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 50 2 27 AA8 osoo Description Read the LED configuration O Syntax AA8 chk cr is a delimiter character AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AAS chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address S 0 2 show counter frequency channel 0 1 gt show counter frequency channel 1 2 gt HOST control chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 018 cr LED show the value of channel 0 response 010 cr Command 302 LED show the va
47. or or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address data 2 character decimal value for low trigger level The unit is 0 1 volt and the range can be from 0 0 to 5 0 volt chk 2 character checksum if checksum disable gt no chk cr 0x0D Example command 01 1L cr Low trigger level 0 8 volt response 0108 cr command 021L cr response 0210 cr Low trigger level 1 0 volt 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 40 2 17 AA1L data Description Set the low trigger level of non isolated input Refer to Sec 1 8 4 for more information Syntax SAA 1L data chk cr is a delimiter character AA 2 character HEX module address from 00 to FF data 2 character decimal value for low trigger level The unit is 0 1 volt and the range can be from 0 0 to 5 0 volt chk 2 character checksum if checksum disable gt no chk cr 0x0D Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D Example command 011L08 cr Low trigger level 0 8 volt respons
48. racter checksum if checksum disable gt no chk cr 0x0D O Example command O1SAFFFFOOOO cDIThe Hi Hi alarm limit of response 01 cr counter 0 is FFFF0000 command 02SA0000FFFF cr mennari imitar response 02 cr counter 0 is 0000FFFF 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 73 2 50 AARP Description Read alarm limit of counter O for alarm mode 0 Refer to Sec 1 8 2 for more information O Syntax AARP chk cr is a delimiter character AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address data 8 character HEX value chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 01RP cr The alarm limit of counter 0 response 01FFFF0000 cr is FEFFOOOO command 02RP cr The alarm limit of counter 0 response O20Q000FFFF cr is OOOOFFFF 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 74 2 51 AARP Description Read Hi alarm limit of counter O for alarm mode 1 Refer to Sec 1 8 2 for more information O Syntax AARP chk cr is a delimiter char
49. reset value AAPN data Set preset value of counter N 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 18 1 8 8 Frequency Input Applications Type 51 Frequency 0 Frequency AABO gt input mode 0 Non isolated channel Non isolated channel AA1H data amp O amp threshold value 1 amp threshold value AA1L data active active AAB1 gt input mode 1 SAA 1H data amp SAA IL data Isolated channel 0 Isolated channel 1 AAB2 gt input mode 2 Non isolated channel Isolated channel 1 AA1H data amp O amp threshold value AA 1L data active AAB3 gt input mode 3 Isolated channel 0 Non isolated channel SAA1H data amp 1 amp threshold value AA1L data active The steps to measure frequency are given as following 1 Use SAA1H data amp AA1L data to set the threshld value if the frequency is non isolated input 2 Use SAAB to select the mode this command will clear the current frequency first 3 Use AA to perform frequency measurement Note Only four commands are important in frequency measurement mode These commands are given as following e AAB gt select mode AA1H data gt set high level threshold value AA1L data gt set low level threshold value FAA gt perform frequency measurement The status read back commands are given as following e SAAB gt mode read back e AA1H gt high level threshold value read back e AA
50. response 021 cr Gate is high active command 03A cr response 1032 cr Gate is disable always active 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 54 2 31 AAAG Description Set gate control mode Refer to Sec 1 8 6 for more information O Syntax SAAAGT chk cr is a delimiter character AA 2 character HEX module address from 00 to FF G 0 gt gate is low active 1 gt gate is high active 2 gt gate is disable chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example ee ori ee response 01 cr command 02A1 cr ee response 02 cr od ER N command 03A2 cr response 03 cr Gate is disable always active 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 55 2 32 AAB Description Read input mode Refer to Sec 1 8 1 for more information O Syntax AAB chk cr is a delimiter character AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AAS ch
51. response gt syntax error or communication error or address error is a delimiter character indicating a valid command 1s a delimiter character indicating a invalid command AA 2 character HEX module address S 0 gt counter is stop disable 1 gt counter is start enable chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example O response 010 cr command 0151 cr Counter 1 is start now response 011 cr 1 7080 1 7080D I 7080B I7080BD User Manual V 2 2 47 2 24 AASNS Description Set the counter status O Syntax AA5NS chk cr is a delimiter character AA 2 character HEX module address from 00 to FF N 0 gt counter 0 1 gt counter 1 S 0 gt stop counter 1 gt start counter chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 01500 cr Stop the counter 0 response 01 cr command 01511 cr Start the counter 1 response 01 cr 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 48 2 25 AAG6N Description Reset counter 0
52. ress chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 01PAFFFFOOOO cr The alarm limit of counter response 01 cr 0 is FFFFOOOO command O2PAOOOOFFFF cr The alan imito countro response 02 cr is OOOOFFFF 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 70 2 47 AAPA data Description Set Hi alarm limit of counter O for alarm mode 1 Refer to Sec 1 8 2 for more information O Syntax AAPA data chk cr is a delimiter character AA 2 character HEX module address from 00 to FF data 8 character HEX value chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command 2 AA data chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 01PAFFFF0000 cr The Hi alarm limit of response 01 cr counter 0 is FFFF0000 command O2PAOOOOFFFF cr Tie ed ESE response 02 cr counter 0 is OOOOFFFF 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 71 2 48 AASA data O Description Set alarm limit of counter 1 for alarm mode 0 Refer to Sec 1 8 2 for more information O Syntax AASA data chk
53. ss from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AASS chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address SS 2 character HEX status value as following Bit 0 Bit_1 reserved Bit_2 0 gt OK 1 gt host watchdog failure chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 010 cr Status of module 01 is OK response 0100 cr command 020 cr Module status 04 gt host watchdog response 0204 cr failure gt HOST is down now 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 28 2 5 AA1 Description Reset the module status The module status will be latched until AA1 command is sent If the module status 4 all output command will be ignored Therefore the user should read the module status first to make sure that the module status is O If the module status is not 0 only AAI command can clear the module status O Syntax AA1 chk cr is a delimiter character AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA chk cr invalid command gt AA chk cr no response gt sy
54. tion code often for testing The AA2 command is used to read EEPROM data only therefore the user can send this command to I 7000 module infinitely 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 42 2 19 AA3N Description Read the max counter value O Syntax SAA3N chk cr is a delimiter character AA 2 character HEX module address from 00 to FF N 0 gt channel 0 of counter or frequency 1 gt channel 1 of counter or frequency chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA data chk cr invalid command gt gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address data 8 character HEX value chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 0130 cr Counter 0 from preset value response 010000 FFFF cr lto FFFF command 0131 cr response 01FFFFFFFF cr Dee 8 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 43 2 20 AA3N data Description Set the max counter value O Syntax SAA3N data chk cr is a delimiter character AA 2 character HEX module address from 00 to FF N 0 gt channel 0 of counter or frequency 1 gt channel 1 of counter or frequency data 8 character HEX
55. value chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AA data chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 01300000FFFF cr Counter 0 from preset value response 01 cr to FFFF command 0131FFFEFFEF cr Counter 1 from preset value response 01 cr to FFFFFFFF 1 7080 I 7080D I 7080B I7080BD User Manual V 2 2 44 2 21 AA4 Description Read the status of digital filter Refer to Sec 1 8 5 for more information Syntax AA4 chk cr is a delimiter character AA 2 character HEX module address from 00 to FF chk 2 character checksum if checksum disable gt no chk cr 0x0D O Response valid command gt AAS chk cr invalid command gt AA chk cr no response gt syntax error or communication error or address error is a delimiter character indicating a valid command is a delimiter character indicating a invalid command AA 2 character HEX module address S 0 gt digital filter is disable 1 gt digital filter is enable chk 2 character checksum if checksum disable gt no chk cr 0x0D O Example command 014 cr
Download Pdf Manuals
Related Search
Related Contents
Running the PIT Report WARREN F. MOTTE JR. Department of French - VIVO CU 2LT dual load and dual time-series USER`S MANUAL Defort DBC-12 Targus TSS58015CA summa d60 & d120 EZ17 - Minipelle Zéro Déport 1,7 T (Wacker Neuson) Wireless doorbell ECO - produktinfo.conrad.com Copyright © All rights reserved.