1. 1 Introduction The FX1N 2EYT BD output expansion board hereafter referred to as FX1N 2EYT BD or Function expansion board is a function expansion board to be installed in the FXis or FX1N series programmable controller hereafter referred to as PLC to increase the output of two points 1 1 Features of the FX1N 2EYT BD Additional increase of two output points Internal mounting in the top of the PLC meaning no need for change to the installation area of the PLC Additional outputs have special auxiliary relays associated to each point which are turned ON or OFF depending on the required output state of the FX1N 2EYT BD As special auxiliary relays are used in the PLC program for the output points the additional outputs are not included in the regular system I O count 1 2 External Dimensions and Each Part Name Dimensions mm inches 43 1 69 Accessories Top cover for board 1 M3 screw to mount board 2 M3 screw to fix top cover 1 1 Output terminal e Unused Do not wire BY0 side terminal of output BYO BYO side terminal of output BYO BY1 side terminal of output BY1 BY1 side terminal of output BY1 The top face of this connector is higher than the top face of the PLC panel cover by approximately 7 mm 2 Mounting hole 2 03 5 0 14 3 Output LED BYO LED The LED lights when BYO is turn on BY1 LED The LED lights when BY1 is turn on 4 External po
2. R Bris External Fuse load 1A A BY1 PRR i E 4 Device allocation and program example Caution Do not turn the special auxiliary relays either side of M8116 and M8117 ON and OFF carelessly This may cause malfunction 4 1 Device allocation Each output of FXin 2EYT BD is allocated a special auxiliary relay The ON OFF state of each output is reflected in its corresponding special auxiliary relay BYO output of FXiN 2EYT BD M8116 BY1 output of FX1N 2EYT BD M8117 4 2 Program example e Turn the special auxiliary relay allocated to each output ON and OFF by X000 program of PLC M8116 Mo M8117 When the END instruction of the program is executed the output process is completed The interruption output processing of HSCS high speed counter comparison set and HSCR high speed counter comparison reset etc are not carried out Output refreshing by REF instruction can not be done Do not use the special auxiliary relay for an instruction by which the bit device is of three points or more such as comparison result of the CMP instruction and comparison result of the ZCP instruction is occupied Do not use the special auxiliary relays for the operand of each application instruction as data K1M8116 and K2M81 16 etc 5 Specifications Caution i Electric shock is possible e Cleaning and additional tightening of the
3. Art NOT 4 Tt 77 MITSUBISHI ELECTRIC a MITSUBISHI oo PROGRAMMABLE CONTROLLERS era MELSEGF FXin 2EYT BD Output Expansion Board USER S MANUAL JY992D95201A This manual contains text diagrams and explanations which will guide the reader in the correct installation safe use and operation of the FXin 2EYT BD Output Expansion Board and should be read and understood before attempting to install or use the unit Further information can be found in the associated manuals list below Specifications are subject to change without notice Guidelines for the Safety of the User and Protection of the FXin 2EYT BD This manual has been written to be used by trained and competent personnel The definition of such a person or persons is as follows a Any engineer using the product associated with this manual should be of a competent nature trained and qualified to the local and national standards These engineers should be fully aware of all aspects of safety with regards to automated equipment b Any commissioning or service engineer must be of a competent nature trained and qualified to the local and national standards c All operators of the completed equipment should be trained to use that product in a safe and coordinated manner in compliance to established safety practices Note The term completed equipment refers to a third party constructed device which contains or uses the product associated with this manual Note s
4. an cause malfunction 2 1 Mounting Turn off all power to the PLC before installing the FX1N 2EYT BD a Top cover for FX1N 2EYT BD supplied as an accessory a b M3 screw to fix top cover supplied as an accessory c M3 screw to fix FX1N 2EYT BD 2 pieces supplied as accessories d External port for optional equipment e FX1N 2EYT BD function expansion board A Note Do not remove this screw on the PLC FX1s d 1 Remove the top cover of the main unit and keep 2 Plug FX1N 2EYT BD e in to the external port d 3 Fix the function expansion board to the main unit with two M3 screws c Tightening torque 0 3 to 0 6 N m 4 Attach the top cover for FX1N 2EYT BD a in place of the original cover During attachment remove a with a suitable tool so that the output terminals are exposed 5 Fix the top cover with an M3 screw b Tightening torque 0 3 to 0 6 N m 3 Output Wiring Wiring cautions Observe the following cautions to avoid electrical shock short circuit disconnection or damage in the unit Do not lay signal cable near to high voltage power cable or house them in the same trunking duct Effects of noise or surge induction may occur Keep signal cables a safe distance of more than 100 mm 4 from these power cables Where output signal lines are used over an extended distance consideration for voltage drop and noise interference should be made Twist the end of each stranded cable so t
5. hat barbed wires are not present Never solder the end of any cables Never connect cables of a non permitted size Make sure that the number of connected cables is not more than the unit has been designed for Fix cables so that any stress is not directly applied on the terminal block or the cable connection area The terminal tightening torque is 0 5 to 0 6 N m Tighten securely to avoid malfunction Use an interlock circuit for external circuit protection Do not wire terminal 3 1 Applicable cables e Use AWG26 16 for the connection with output equipment The maximum tightening torque is 0 5 to 0 6N m e When using a different type of cable defective contact of the terminal part is possible Use a crimp terminal achieve a good contact Linear and sectional area gt O Linear Sectional area mm Terminal AWG26 0 1289 Stranded cable Remove sheath twist core wires then 3 connect cable AWG16 1 309 Single cable Remove sheath then connect cable Terminal processing of wire 6mm 0 2inches 3 2 Wiring of output Sink Type FX1N 2EYT BD s E I F yternal Fuse Bio 30V DC 7 BYO eE BYO External Fuse T load 1A BY1 LY Byr Source type FX1N 2EYT BD e 5 to 30V DC BYO ot External Fuse lgad 1A a BYO
6. on the Symbols Used in this Manual At various times through out this manual certain symbols will be used to highlight points of information which are intended to ensure the users personal safety and protect the integrity of equipment 1 Indicates that the identified danger WILL cause physical and property damage damage A 2 Indicates that the identified danger could POSSIBLY cause physical and property Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage that may arise as a result of the installation or use of this equipment All examples and diagrams shown in this manual are intended only as an aid to understanding the text not to guarantee operation Mitsubishi Electric will accept no responsibility for actual use of the product based on these illustrative examples Owing to the very great variety in possible application of this equipment you must satisfy yourself as to its suitability for your specific application Associated manuals Manual name Manual No Description FX1S Series Describes contents related to hardware of FXis Series PLC such JY992D83901 aie ay Hardware Manual as specifications wiring and installation FX1N Series Describes contents related to hardware of FX1N Series PLC such JY992D89301 Paes Re A Hardware Manual as specifications wiring and installation Fabie e JY992D88101 Describes instructions in FX1s FX1N FX2n FXeNc Series
7. rt for display module FX1N 5DM or memory cassette FX1N EEPROM 8L iaa sas OAS toag O 38 5 1 52 5 External connector for PLC 1 3 System configuration Only one function expansion board can be used on one FX1S and FX1N series PLC main unit Do not try to install two or more expansion boards FX1N 2EYT BD can be used together with FX1N 5DM Refer to the FX1s or FXin HARDWARE MANUAL when using the FX1N 2EYT BD together with an FX1N 5DM When using with the memory cassette FXi1N EEPROM 8L only program transfer is possible The memory cassette cannot be connected permanently 1 4 Applicable PLC Series name Applicable version FX1S V2 0 or later FX1N V2 0 or later 2 Installation Caution A 1 Do not use the function expansion board in environments that contain excessive or conductive dust corrosive or flammable gas moisture or rain excessive heat regular impact shocks or excessive vibration Use in these environment may cause electric shock fire malfunction damage or deterioration of the product 2 Cut off all phases of power source before installing removing or performing wiring work on the unit in order to avoid electric shock or damage of product 3 After the installation wiring etc replace the PLCs top cover before power ON 4 Securely install the function expansion board and fix it to the PLC Defective contact c
8. terminal should only be done after turning OFF the power supply Do not touch the terminal while power is ON Electric shock is possible while the power is ON e For repair please contact a service representative Incorrect repair can cause malfunction or electric shock e Install or uninstall FXin 2EYT BD after turning OFF the power supply Installing and uninstalling while the power supply ON may cause malfunction e Treat as industrial waste when disposing of the product 5 1 Environmental specifications The environmental specifications are equivalent to those of the PLC main unit Refer to the manual of the PLC main unit 5 2 Power supply specifications Item Specification Consumption current 5V DC Supply by PLC 5 3 Output specifications Item Specification External power supply 5 to 30V DC Circuit insulation Photo coupler Operation display LED lighting when photo coupler is driven The maximum resistance load 0 5A 1 point The maximum inductive load 12W 24V DC The maximum lamp load 1 5W 24V DC Open road leakage current 0 1mA DC30V Response time OFF to ON 0 2ms or less Response time ON to OFF 0 2ms or less sfa MITSUBISHI ELECTRIC CORPORATION MITSUBISHI DENKI BLDG MARUNOUTI TOKYO 100 8310 HEAD OFFICE Manual number JY992D95201 Manual revision A May 2001 Date HIMEJI WORKS 840 CHIYODA CHO HIME
9. uJI JAPAN TELEX J24532 CABLE MELCO TOKYO

Download Pdf Manuals

image

Related Search

Related Contents

  PowerNET P-300  Assembly instructions - Micro  NEC Express5800/R120d-2E SR User's Guide  Bedienungsanleitung - buehler  Brodit ProClip 805039  OM, 150 BT, 2013-01, EN, FR, ES  Manual - Swimming Pool & Spa Warehouse  Brixton KA-5010 space heater  Le Targum De Job De La Grotte 11 De Qumran (11QtgJob  