Home

PD76-E4E-MFF

image

Contents

1. 3 7 Switching output 0 The switching output channel is off DOSIx Switching output items 1 26 For 26 measuring energy 128 The switching output channel is on DOSxL Warning lower limit value 0 9999 Output warning when measured value is less than this value DOSxH Warning upper limit value 0 9999 Output warning when measured value is higher than this value Note 1 refer to table 15 for energy address 2 when warning lower limit is 0 lower limit warning will be invalid when warning upper limit is 9999 upper limit warning will be invalid Figure 2 Switching output settings All setting data of switching output is standardized to 2 bytes SX according to a formula The value is range from 1 to 1999 absolute value details of the formula as shown in figure 4 The meter has 10 units Schmitt sections when calculating alarm output For example if the measurement value is less than warning lower limit at first then it must be higher than warning upper limit with10 units in order to end warning Likewise the measurement value must be less than warning upper limit 10 units in order to stop warning So warning upper limit should be higher than warning lower limit with 20 units The maximal warning lower _ limit is 9979 and the least warning upper limit is 0020 For example for 10kV 100V meter set the first switching output corresponding with UA warning when UA lt 8kV or UA gt 12kV We know DOSI1 DOSI1 1 and PT PT 100 accordin
2. HRUA24 HRUA27 HRUA28 Phase A voltage 24 times harmonic content 2019H HRUA25 Phase A voltage 25 times harmonic content A 5 times harmonic content O 0 6 times harmonic content 0 0 a 0 Phase A voltage 28 times harmonic content HRUA29 Phase A voltage 29 times harmonic content HRUA30 Phase A voltage 30 times harmonic content HRUB6 Phase B voltage 6 times harmonic content HRUB7 HRUB8 HRUB9 HRUB10 HRUB11 HRUB12 HRUB13 HRUB14 HRUB15 HRUB16 HRUB17 HRUB18 Phase B voltage 7 times harmonic content Phase B voltage 8 times harmonic content Phase B voltage 9 times harmonic content Phase B voltage Phase B voltage Phase B voltage 12 Phase B voltage Phase B voltage Phase B voltage Phase B voltage Phase B voltage Phase B voltage A A A A A A A A O O Er o C S 0 times harmonic content 0 1 times harmonic content 3s times harmonic content O O O O O O 0 3 times harmonic content 4 times harmonic content 5 times harmonic content O 6 times harmonic content El 7 times harmonic content 8 times harmonic content 0 R R R R R R R R R R R 201AH P HRUA26 Phase A voltage 26 times harmonic content R
3. Phase B current 25 times harmonic content D D D D way D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D Dd Phase B current 26 times harmonic content Phase B current 27 times harmonic content Phase B current 28 times harmonic content Phase B current 29 times harmonic content Phase B current 30 times harmonic content 1 PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 43 241FH HRIB31 Phase B current 31 times harmonic content 2507H A HRIC7 Phase C current 7 times harmonic content 2508H HRIC8 Phase C current 8 times harmonic content 250AH Phase C current 10 times harmonic content 250BH HRIC11 Phase C current 11 times harmonic content 250CH Po Re Phase C current 12 times harmonic content 250DH Porta Phase C current 13 times harmonic content 250EH TS Phase C current 14 times harmonic content 250FH Po Ricas Phase C current 15 times harmonic content 2510H Po Ricas Phase C current 16 times harmonic content 2511H EA Phase C current 17 times harmonic content 2512H Po nrc Phase C current 18 times harmonic content 2513H Po Ro Phase C current 19 times harmonic content 2514H Rico Phase C current 20 times harmonic content 2516H o mez Phase C current 22 times harmonic content 2518H P R Phase C current 24 times harmonic cont
4. PD76 E4E MFF Multifunction Digital Panel Meter User Manual Table of contents A e RC o UU aiara a aa 1 A A N 1 1 2 Technical parameter nia aa Washed a iia 1 2 Outline and Installation lt lt lt wi casersntad aaea daana araar EEEE Naaa 3 AN OS A O PRE CO PES o N 3 2 2 OW 1 Sta llana ona 3 Za EM UU aran 3 CS a 6 3 1 Electri al parameters Mea SUING isos an spadn 6 A nn e 6 dl UL dd CCOO OP EG OOO E E OE A 6 2 Maximal dema sotano ll a 6 Eo lie MIn UMD Anea es ates cosets EE E 6 lA PA 6 ee Roa AAA PP o o 6 a EE ig 0 Ea ACACIA oo 8 os Oo COMMUN GUO aio 8 OO A ado 10 AIM A AAA AA AA AA el ab dates 10 42 Keyboard crite een lt ace Fatwa odo aed dss Suc poco eset ek cenit eae Dade mse deal tSeadostn 10 43 A tomati display MOde cai AA eae Dade Ad 10 4 4 Manual switch display TNS A AN AA A AA cd 13 4 5 Ment Opera ON ani A A A dd io 13 5 COMMUNICATION coincida diana 20 SN FOOT postiar a 20 e o nn 20 9 22 RTU a LOA RR O queen enced E ER 20 93 ene fo Mates O A Ri o geen eae teers 21 E AP non rere ee ee ae eo ee Pe ene eee ey ere een E 23 5 5 Communication TSS AC ssp 24 A A O 27 Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 1 O Introduction 1 1 General PD76 E4E MFF Digital indicating Panel Mounted Electrical Measuring Instrument is designed for the electrical monitoring for utilities industrial mining corporations intelligence towers and communities It adopts large
5. 034BH O L E Last month reverse active demand R W 034CH A DPPT H Occur time of last month reverse active demand RIW 034DH Sasi DPPT L Month day hour minute R W 034EH a DPP1 Last month T1 reverse active demand RIW 034FH ENS DPPT1 H Occur time of last month T1 reverse active demand R W 0350H G DPPT1 L Month day hour minute R W 0351H EEN DPP2 Last month T2 reverse active demand RIW 0352H a DPPT2 H Occur time of last month T2 reverse active demand RIW 0353H a DPPT2 L Month day hour minute RIW 0354H P DPP3 Last month T3 reverse active demand R W 0355H DPPT3 H Occur time of last month T3 reverse active demand RIW 0356H DPPT3 L Month day hour minute R W 0357H PS DPP4 Last month T4 reverse active demand RIW 0358H PAE DPPT4 H Occur time of last month T4 reverse active demand RIW 0359H EA DPPTA4 L Month day hour minute RIW 035AH P ee Last month forward reactive demand RIW 035BH aa DPPT H Occur time of last month forward reactive demand RIW 035CH a DPPT L Month day hour minute RIW 035DH Fs DPP1 Last month T1 forward reactive demand R W 035EH DPPT1 H Occur time of last month T1 forward reactive demand R W Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 36 035FH 0360H 0361H 0362H 0363H 0364H 0365H 0366H 0367H 0368H 0369H 036AH 036BH 036CH 036DH 036EH 036FH 0370H 0371H 0372H 0373H
6. Time period 6 starting time setting Time period 7 rate setting Time period 7 starting time setting reactive reactive reactive reactive reactive reactive reactive energy energy energy energy energy energy energy Time period 4 rate setting R W R W R W R W R W R W R W R W R W R W R W R W R W R W Property R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 33 0212H 0213H 0214H 0215H 0216H 0217H 0218H 0219H 021AH 021BH Address 0301H 0302H 0303H 0304H 0305H 0306H 0307H 0308H 0309H 030AH 030BH 030CH 030DH 030EH 030FH 0310H 0311H 0312H 0313H 0314H 0315H 0316H RATES PS8 RATE9 Time period 8 rate setting Time period 8 starting time setting Time period 9 rate setting 0000 Ps Time period 9 starting time setting Ooa RATE10 Time period 10 rate setting 00 00 PS10 Time period 10 starting time setting ROLL Demand sliding period Second signal reactive pulse output select 0 reactive 1 second signal NOS Rate of current time period high bit is time period BATT Voltage of back up battery Demand information R W R W R W R W R W R W DPPT H DPPT L DPPT1 H 0300H IO Current month forward active demand Occur time of current month forward active demand Month
7. 2H 3H 4H 5H 6H 7H 8H 9H AH BH CH DH EH HRIB8 HRIB30 Phase A current 27 times harmonic content Phase A current 28 times harmonic content Phase A current 29 times harmonic content Phase A current 30 times harmonic content Phase A current 31 times harmonic content Phase B current AC content Phase B fundamental wave content Phase B current 2 times harmonic content Phase B current 3 times harmonic content Phase B current 4 times harmonic content Phase B current 5 times harmonic content Phase B current 6 times harmonic content Phase B current 7 times harmonic content Phase B current 8 times harmonic content Phase B current 9 times harmonic content Phase B current 10 times harmonic content Phase B current 11 times harmonic content Phase B current 12 times harmonic content Phase B current 13 times harmonic content Phase B current 14 times harmonic content Phase B current 15 times harmonic content Phase B current 16 times harmonic content Phase B current 17 times harmonic content Phase B current 18 times harmonic content Phase B current 19 times harmonic content Phase B current 20 times harmonic content Phase B current 21 times harmonic content Phase B current 22 times harmonic content Phase B current 23 times harmonic content Phase B current 24 times harmonic content
8. 201BH m Phase A voltage 27 times harmonic content h R R R R R R R R R R R R R R R R R R R R R R R R Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 40 2113H rta Phase B voltage 19 times harmonic content 2114H Pro Phase B voltage 20 times harmonic content 0 2115H Po ras Phase B voltage 21 times harmonic content 2116H Po ra Phase B voltage 22 times harmonic content 2117H Po ras Phase B voltage 23 times harmonic content 2118H ras Phase B voltage 24 times harmonic content 0 2119H Po ras Phase B voltage 25 times harmonic content 211AH Po ras Phase B voltage 26 times harmonic content 211BH Po Rar Phase B voltage 27 times harmonic content 211CH MENS Phase B voltage 28 times harmonic content 211DH ras Phase B voltage 29 times harmonic content 211EH Pro Phase B voltage 30 times harmonic content 211FH Po ras Phase B voltage 31 times harmonic content 2200H HRUCO Phase C voltage AC content 0 2201H O Phase C voltage fundamental content C 2202H Po RUR Phase C voltage 2 times harmonic content 2203H Po rca Phase C voltage 3 times harmonic content 2204H Pros Phase C voltage 4 times harmonic content 2205H Pros Phase C voltage 5 times harmonic content 2206H Pros Phase C voltage 6 times harmonic content 2208H Po Ro
9. bean 00 kWh current month total forward active energy Current Tariff x 000000 00 kWh current month tarrif x forward active energy dal last month total f d acti 00 kWh ast month total forward active energy Act Energy Last Month a a 000000 00 kWh last month tarrif x forward active energy Total 000000 00 kWh before last month total forward active energy Before Last Mon Tariff x 000000 00 kWh before last month tarrif x forward active energy Total Act Current 000000 00 kWh current month total reverse active energy Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 15 4 5 3 deamnd and the time stamp inquire mode When in the main menu push lt or gt to select Max Demand then push to enter into deamnd and the time stamp inquire mode Below is the sub munu structure E Tariff Energy aoodi 00 kWh current month tarrif x reverse active energy Total l 000000 00 kWh last month total reverse active energy Last Month n Tariff x 000000 00 kWh last month tarrif x reverse active energy Total l 000000 00 kWh before last month total reverse active energy Before Last Mon Tariff x 000000 00 kWh before last month tarrif x reverse active energy Total current month total forward reactive energy Bett 000000 00 kvarh es current month tarrif x forward reactive energy 0
10. 0374H 0375H 0376H 0377H 0378H 0379H 037AH 037BH 037CH 037DH 037EH 037FH 0380H 0381H 0382H ee oe EEC as f es onto al a ee e EEC ae i ee e ECETIA a ee o EEE Ed Ea ee oe EEC a en OO oe EEC si DPP4 Last month T4 reverse reactive demand DPPT4 H DPPT1 L DPPT2 H DPPT2 L DPPT3 H DPPT3 L DPPT4 H DPPTA L DPPT H DPPT L DPPT1 H DPPT1 L DPPT2 H DPPT2 L DPPT3 H DPPT3 L DPPTA L DPPT H Month day hour minute Occur time of last month T2 forward reactive demand Month day hour minute Occur time of last month T3 forward reactive demand Month day hour minute Occur time of last month T4 forward reactive demand Month day hour minute Occur time of last month reverse reactive demand Month day hour minute Occur time of last month T1 reverse reactive demand Month day hour minute Occur time of last month T2 reverse reactive demand Month day hour minute Occur time of last month T3 reverse reactive demand Month day hour minute Occur time of last month T4 reverse reactive demand Month day hour minute two months before Occur time of forward active demand O P E two months before forward active demand DPPT L Month day hour minute ME DPP1 two months before T1 forward active demand DPPT1 H DPPT1 L DPPT2 H two months before Occur time of T1 forward active demand Month
11. Digital Indicating Panel Mounted Electrical Measuring Instruments 19 Program MENU Max Demand Act Demand Re Demand Max Demand Act Demand Re Demand Max Demand Act Demand Act Demand Re Demand Max Demand Active Demand Re Demand Re Demand Act Demand Last Month Before Last Mon Act Demand Current Before Last Mon Act Demand Current Last Month Before Last Mon Act Demand Current Last Month Before Last Mon Re Demand Last Month Before Last Mon Re Demand Current Last Month Before Last Mon 00 00 kW 00 00 00 00 00 00 kW 00 00 00 00 00 00 kW 00 00 00 00 00 00 kW 00 00 00 00 00 00 kvar 00 00 00 00 00 00 kvar 00 00 00 00 Picture 12 demand and time stamp inquiry 00 00 kW 00 00 00 00 00 00 kW 00 00 00 00 00 00 kW 00 00 00 00 00 00 kW 00 00 00 00 00 00 kvar 00 00 00 00 00 00 kvar 00 00 00 00 Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 20 5 Communication 5 1 Forward PD76 24C M7F provides RS485 communication port adopts Modbus both Modbus RTU and Modbus ASCII communication protocol Up to 32 meters can be connected together with single communication wire you can set its own communication address for each of them Different series meter varies in the number of communication wiring terminals it should use twisted pair wire for communication connecting an
12. R W R W R W R W R W T3 PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 38 03A7H Me DPPT L Month day hour minute R W 03A8H PE DPP1 two months before T1 reverse reactive demand RIW 03A9H el DPPT1 H two months before occur time of T1 reverse reactive RIW 03AAH DPPT1 L demand Month day hour minute R W 03ABH A DPP2 two months before T2 reverse reactive demand R W 03ACH Sa DPPT2 H two months before occur time of T2 reverse reactive RIW 03ADH EFE DPPT2 L demand Month day hour minute R W 03AEH iea DPP3 two months before T3 reverse reactive demand R W 03AFH a DPPT3 H two months before occur time of T3 reverse reactive RIW 03B0H MERA DPPT3 L demand Month day hour minute RIW 03B1H EEEE DPP4 two months before T4 reverse reactive demand R W 03B2H DPPT4 H two months before occur time of T4 reverse reactive RIW 03B3H A DPPT4 L demand Month day hour minute RIW a E Additional energy data A EE Eee Harmonic information 200AH Po HRUD Phase A voltage 10 times harmonic content 200EH HRUA14 Phase A voltage 14 times harmonic content D D wD D D D way wa D D D D D D T3 PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 39 201CH 201DH 201EH 2106H 2107H 2108H 2109H 210AH 210BH 210CH 210DH 210EH 210FH 2110H 2111H 2112H
13. R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 32 0185H 0186H 0187H 0188H 0189H 018AH 018BH 018EH 018FH 0190H 0191H 0192H Address 0200H 0201H 0202H 0203H 0204H 0205H 0206H 0207H 0208H 0209H 020AH 020BH 020CH 020DH 020EH 020FH 0210H 0211H Qh H Initial setting 01 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 Itme RTC ADT RATE1 PS1 RATE2 PS2 RATE3 PS3 RATE4 PS4 RATE5 PS5 RATE6 PS6 RATE7 PS7 two months ago T3 consumption two months consumption two months consumption two months consumption two months consumption two months consumption two months consumption Multi rate information forward forward reverse reverse reverse reverse reverse Description Minute second MMSS Day hour DDHH Year month YYMM AMR date and time DDHH Time period 1 rate setting Time period 1 starting time setting Time period 2 rate setting Time period 2 starting time setting Time period 3 rate setting Time period 3 starting time setting Time period 4 starting time setting Time period 5 rate setting Time period 5 starting time setting Time period 6 rate setting
14. compatibility Fast transient burst 4KV Electromagnetic RF fields 80MHz 1000MHz 10V m Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 2 Ambient temperature Operation 10 60 Ternperatire Storage 25 700 Humidity 95 RH without dew corrosive gas Altitude lt 3000m Ta PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 3 2 Outline and installation 2 1 Dimension Face i e 00000000000000 6 68466588586666 Display 4 o e LA LT a E Key pad Menu fo 00000000000000 o Clamps Current test and communication terminals Input and Output terminals Picture 1 Installation Diagram 2 2 How to Install Drill a hole size 90 mmx90 mm in the switching cabinet Take out the meter clamps and screws Insert the meter into the hole Fix the clamps and fasten the screws 2 3 Terminals Layout Upper row Current test and communication terminals Current terminal Test terminal 4850 4850 1 2 3 4 5 6 7 8 9 10 11 12 13 14 IA IB IC P Q P Q A1 B1 A2 B2 Picture 2 Current test and communication terminals Note P active impulse output positive P active impulse output earthed Q reactive impulse output positive Q reactive impulse output ea
15. day hour minute two months before Occur time of T2 forward active demand Po DPP2 two months before T2 forward active demand DPPT2 L DPPT3 H Month day hour minute Po DPP3 two months before T3 forward active demand two months before Occur time of T3 forward active demand RIW RIW RIW RIW RIW RIW RIW RIW RIW RIW RIW RIW RIW RIW R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 37 0383H 0384H 0385H 0386H 0387H 0388H 0389H 038AH 038BH 038CH 038DH 038EH 038FH 0390H 0391H 0392H 0393H 0394H 0395H 0396H 0397H 0398H 0399H 039AH 039BH 039CH 039DH 039EH 039FH 03A0H 03A1H 03A2H 03A3H 03A4H 03A5H 03A6H DPPT3 L Month day hour minute a DPP4 two months before T4 forward active demand DPPT4 H two months before Occur time of T4 forward active demand DPPT4 L Month day hour minute e two months before reverse active demand DPPT H two months before Occur time of reverse active demand DPPT L Month day hour minute SS DPP1 two months before T1 reverse active demand DPPT1 H two months before Occur time of T1 reverse active demand DPPT1 L Month day hour minute EJEM DPP2 two months before T2 reverse active demand DPPT2 H two months before Occur time of T2 reverse
16. day hour minute Occur time of current month T1 forward active demand Poe DPP1 Current month T1 forward active demand DPPT1 L Month day hour minute Occur time of current month T2 forward active demand MO DPP2 Current month T2 forward active demand DPPT2 H DPPT2 L Month day hour minute DPP3 Current month T3 forward active demand DPPT3 H DPPT3 L DPPT4 H Occur time of current month T3 forward active demand Month day hour minute Occur time of current month T4 forward active demand DPP4 Current month T4 forward active demand DPPTA L Month day hour minute Occur time of current month reverse active demand HA A Current month reverse active demand DPPT H DPPT L Month day hour minute r DPP1 Current month T1 reverse active demand DPPT1 H DPPT1 L DPPT2 H Occur time of current month T1 reverse active demand Month day hour minute esa DPP2 Current month T2 reverse active demand Occur time of current month T2 reverse active demand RIW RIW RIW RIW RIW RIW RIW RIW RIW RIW RIW RIW RIW R W R W R W R W R W R W R W R W Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 34 0317H 0318H 0319H 031AH 031BH 031CH 031DH 031EH 031FH 0320H 0321H 0322H 0323H 0324H 0325H 0326H 0327H 0328H 0329H 032AH 032BH 032CH 032DH 032EH 032FH 0330H 0331H 0332H 0333
17. scale IC digital sampling technology and SMT technology The instrument is equipped with 128 24 dot matrix LCD display can measure all the common electrical parameters with high accuracy such as three phase voltage three phase current active power reactive power frequency power factor active energy reactive energy four quadrant energy 1 31 times harmonic measuring energy pulse output and 1Hz clock output With high speed RS485 communication port and conformance to the Modbus protocol There are four programming pushbuttons in the faceplate it is very convenient for users to achieve switching display and meter s parameters program setup at site with high flexibility There are many extended function modules to choose for instance 4 switching input and 4 analog output O 20mA 4 20mA module 4 switching input and 4 switching output module 6 switching input and 2 analog output module Analog output is for energy and electricity transportation output and the function of 4 switching input and output is for local or remote switching signal monitoring and control output remote communication and remote control function PD76 E4E M7F with excellent performance and reasonable price it can replace the normal electricity transportation instrument measurement indicating meter energy measuring meter and other related accessorial units PD76 E4E M7F can be used widely for energy management system transformer substation automati
18. 00000 00 kvarh Er last month total forward reactive energy Re Last Month 000000 00 kvarh Energy T last month tarrif x forward reactive energy 000000 00 kvarh Tol before last month total forward reactive energy Before Last Mon eee kvar Taniy before last month tarrif x forward reactive energy 000000 00 kvarh Tial current month total reverse reactive energy Current 000000 00 kvarh ue current month tarrif x reverse reactive energy 000000 00 kvarh Total last month total reverse reactive energy Re Energy Last Month a ASE 000000 00 kvarh last month tarrif x reverse reactive energy Pal before lastt month total reverse reactive energy Before Last Mon oem kvark Taniy before last month tarrif x reverse reactive energy 000000 00 kvarh Figure8 Multi rate menu structure First layer Second layer Data format Description Total E Act current month forward active demand and time stamp 00 00 kW e Demand j month day hour minute 00 00 00 00 Current Tariff x current month taffif x forward active demand and time stamp ees month day hour minute 00 00 00 00 y Total i last month forward active demand and time stamp 00 00 kW month day hour minute 00 00 00 00 Last Month Tariff x last month taffif x forward active demand and time stamp Seely month day hour minute 00 00 00 00 y Beare LaskMon Total before last month forward active demand and time stamp 00 00 kW
19. 013CH Qh L R W Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 30 013DH Qh H R W current T2 reverse reactive energy consumption 013FH R W current T3 reverse reactive energy consumption 0140H R W 0141H R W current T4 reverse reactive energy consumption 0142H R W 0143H R W last month total forward active energy consumption 0144H R W 0145H R W last month T1 forward active energy consumption 0146H R W 0147H R W last month T2 forward active energy consumption 0148H R W 0149H R W last month T3 forward active energy consumption 014AH R W 014BH R W last month T4 forward active energy consumption 014CH R W 014DH R W last month total reverse active energy consumption 014EH R W 014FH R W last month T1 reverse active energy consumption 0150H R W 0151H R W last month T2 reverse active energy consumption 0152H R W 0153H R W last month T3 reverse active energy consumption 0154H R W 0155H R W last month T4 reverse active energy consumption 0156H R W 0157H R W last month total forward reactive energy consumption 0158H R W 0159H R W last month T1 forward reactive energy consumption 015AH R W 015BH R W last month T2 forward reactive energy consumption 015CH R W 015DH R W last month T3 forward reactive energy consumption 015EH R W 015FH aa Qh H RIW last month T4 forward reactive energy consumptio
20. 0H 31H Function code 03 30H 33H Original register address 0107 30H 31H 30H 37H Number of register 0003 30H 30H 30H 33H Verification code F1 46H 31H Stop lt CR gt lt LF gt ODH OAH Figure 14 read register master demand data frame ASCII code Start 4 bytes time interval Address code 01H Function code 03H Original register High byte Original register address address Low byte High byte Number of register Number of register Low byte Low byte Verification code Verification code High byte Stop 4 bytes time interval Figure 15 Read register master inquire data frame RTU mode The data return from the master indicating IAQ O3EDH 1 005 IBLE 03FOH 1 008 ICL 03E0H 0 992 the actually value of current can be gained according to the appendix ASCII code HEX code Start 3AH Address code 01 30H 31H Function code 03 30H 33H Byte 06 30H 36H Register 1 data 03ED 30H 33H 45H 44H Register 2 data 03F0 30H 33H 46H 30H Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 25 Register 3 data 03E0 30H 33H 45H 30H Verification code 30 33H 30H Stop lt CR gt lt LF gt ODH OAH Figure 16 Write register slave response data frame Start 4 bytes time interval Address code 01H Function code 03H Byte 06H High byte 03H Register 1 data Low byte EDH High byte 03H Register 2 dat
21. A hex The allowable characters transmitted for all other fields are hexadecimal 0 9 A F The frame format as shown in figure 10 Start addressing Address code Function code Data field LRC check End SAH 2 bytes 2 bytes N bytes 2 bytes 0DH 0AH Figure 10 ASCII frame format In RTU mode messages start with as well as end at a silent interval of at least 3 5 character times The entire message frame must be transmitted as a continuous stream If a silent interval of more than 1 5 character times occurs before completion of the frame the receiving device flushes the incomplete message and assumes that the next byte will be the address field of a new message RTU message format as shown in figure 11 Start Address code Function code Data field LRC check end 4 bytes interval time 1 byte 1 byte N byte 2 bytes 4 bytes interval time Figure 11 RTU frame format 5 3 1 Address code Address Address code is to specify which slave communicates with the master each slave has its unique address code Both address code sending to or response from the slave indicates its address Available addresses are 1 247 the rest are reserved 5 3 2 Function code Function Function code is to specify what function the slave to perform The supported function codes and their definition as well as their operation are listed below Tz PD76 E4E WFF Digital Indicating Pane
22. CPS Y C DTT w C NET Network type 0 3P4W 1 3P3W DOS3H Switching output 3 alarm upper limit value R R R R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W T PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 01 01 01 01 01 01 01 01 0020H 0021H 0022H 0023H 0024H Address 00H Address 0101H 02H 03H 04H 05H 06H DOSI4 Switching output 4 item setting 0000 DOS4L Switching output 4 alarm lower limit value 9999 DOS4H Switching output 4 alarm upper limit value MEN DIDLY Switching input stable time MS DODLY Switching output stable time Initial setting Energy address 1 129 2 130 3 131 4 132 6 E Item UA UAB Working information Switching state Electrical data Description A phase voltage 3P4W AB phase voltage 3P3W UB UBC B phase voltage 3P4W BC phase voltage 3P3W UC UCA C phase voltage 3P4W CA phase voltage 3P3W AB line voltage 3P4W BC line voltage 3P4W CA line voltage 3P4W 07H 7 135 Aphase current OAH OBH OCH ODH OEH OFH 0110H 0111H 0114H 0115H 16H 0117H 0118H 0119H 1AH 1137 10 13 11 139 12 140 13 141 14 142 15 143 16 144 17 145 18 146 19 147 20 1 21 1 22 1 23 1 24 152 25 15 26 154 o Jaj amp 090 oo E
23. H 0334H 0335H 0336H 0337H 0338H 0339H 033AH DPPT2 L Month day hour minute AO DPP3 Current month T3 reverse active demand DPPT3 H Occur time of current month T3 reverse active demand DPPT3 L Month day hour minute Loa DPP4 Current month T4 reverse active demand DPPT4 H Occur time of current month T4 reverse active demand DPPT4 L Month day hour minute P re Current month forward reactive demand DPPT H Occur time of current month forward reactive demand DPPT L Month day hour minute aa DPP1 Current month T1 forward reactive demand DPPT1 H Occur time of current month T1 forward reactive demand DPPT1 L Month day hour minute MA DPP2 Current month T2 forward reactive demand DPPT2 H Occur time of current month T2 forward reactive demand DPPT2 L Month day hour minute y DPP3 Current month T3 forward reactive demand DPPT3 H Occur time of current month T3 forward reactive demand DPPT3 L Month day hour minute a DPP4 Current month T4 forward reactive demand DPPT4 H Occur time of current month T4 forward reactive demand DPPT4 L Month day hour minute MAA Current month reverse reactive demand DPPT H Occur time of current month reverse reactive demand DPPT L Month day hour minute DPP1 Current month T1 reverse reactive demand DPPT1 H Occur time of current month T1 reverse reactive demand DPPT1 L Month day hour minute ER DPP2 Curre
24. Ts e i A B uy C DJ L N N Power supply Direct connection Picture 7 Wiring method 1 Type 2 three phase three wire two CTs Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 5 anni el al TA B L N c Power supply Note A Voltage input input voltage should not be higher than the rated voltage 100V or 400V otherwise it should adopt PT and 1A fuse is required B Current input the rated input current is 5A outside CT is required in the case of the input current gt 5A if there are other instruments also connected to the same CT the instruments should be connected in series Before disconnecting current input DI Direct connection Picture 8 Wiring method 2 E A B C P T operated first make sure the CT is off In order to remove conveniently we suggest use socket instead connected to the CT directly C Make sure the voltage and current line connected correctly phase and direction in sequence otherwise the value and symbol can t be shown normally power and energy D Power supply the voltage range of power supply is AC DC 80 270V In order to protect the instrument we suggest install 1A fuse for the phase line when adopting alternating current power supply In the region where the quality of electricity is poo
25. a Low byte FOH High byte 03H Register 3 data Low byte EOH Low byte 8CH Verification code High byte 5EH Stop 4 bytes time interval Figure 17 Read register slave response data frame 5 5 2 Write multiple register 10H This function is for the master to write multiple data into register the register should be writable and the number should be within the range of address The maximal number of registers which Modbus communication protocol allows to save into is 60 Following is the example of setting LED display to the lightest grade 16t ASCII code HEX code Start 3AH Address code 01 30H 31H Function code 10 31H 30H Original register address 000A 30H 30H 30H 41H Number of register 0001 30H 30H 30H 31H Write bytes 02 30H 32H Write data 0010 30H 30H 31H 30H Verification code D2 44H 32H Stop lt CR gt lt LF gt ODH OAH Figure 18 write register server enquire data frame ASCII mode Start 4 bytes time interval Address code 01H Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 26 Function code 10H Original register High byte 00H address Low byte OAH High byte 00H Number of register Low byte 01H Write byte 02H High byte 00H Write data Low byte 10H Low byte ATH Verif
26. a Ta a lt a e lt Frequency RW R W RW R W R W Property Property R Al D D D D D D D D D D D D D D D D D D D D D D D Dd T3 PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 29 Energy data current total forward active energy consumption 011DH R W current T1 forward active energy consumption 011EH RIW 011FH R W current T2 forward active energy consumption 0120H R W 0121H R W current T3 forward active energy consumption 0122H R W 0123H R W current T4 forward active energy consumption 0124H R W 0125H R W current total reverse active energy consumption 0126H RIW 0127H RIW current T1 reverse active energy consumption 0128H RIW 0129H R W current T2 reverse active energy consumption 012AH R W 012BH R W current T3 reverse active energy consumption 012CH R W 012DH RIW current T4 reverse active energy consumption 012EH RIW 012FH RIW current total forward reactive energy consumption 0130H RIW 0131H RIW current T1 forward reactive energy consumption 0132H RIW 0133H R W current T2 forward reactive energy consumption 0134H R W 0135H R W current T3 forward reactive energy consumption 0136H R W 0137H R W current T4 forward reactive energy consumption 0138H R W 0139H R W current total reverse reactive energy consumption 013AH R W current T1 reverse reactive energy consumption
27. active demand DPPT2 L Month day hour minute es DPP3 two months before T3 reverse active demand DPPT3 H two months before Occur time of T3 reverse active demand DPPT3 L Month day hour minute es DPP4 two months before T4 reverse active demand DPPT4 H two months before Occur time of T4 reverse active demand DPPT4 L Month day hour minute pee two months before forward reactive demand DPPT H two months before Occur time of forward reactive demand DPPT L Month day hour minute a DPP1 two months before T1 forward reactive demand DPPT1 H two months before Occur time of T1 forward reactive DPPT1 L demand Month day hour minute Pe DPP2 two months before T2 forward reactive demand DPPT2 H two months before Occur time of T2 forward reactive DPPT2 L demand Month day hour minute ME DPP3 two months before T3 forward reactive demand DPPT3 H two months before Occur time of T3 forward reactive DPPT3 L demand Month day hour minute Pe DPP4 two months before T4 forward reactive demand DPPT4 H two months before Occur time of T4 forward reactive DPPT4 L demand Month day hour minute ICI two months before reverse reactive demand BA DPPT H two months before occur time of reverse reactive demand RIW RIW RIW RIW R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W R W
28. armonic of phase A current shown as the percent of fundamental wave HRI B Es Display harmonic of phase B current shown as 15 the percent of fundamental wave HRI C E Display harmonic of phase C current shown as 16 the percent of fundamental wave Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 13 Display mode Example Description State of switching input 7 without the switching input 0 the switching input is disconnected C the switching input is connected State of switching output 18 gt without the switching output 0 the switching output is disconnected C the switching output is connected Ti me 1996 01 01 19 12 00 00 Display the time and date Figure 6 display mode 4 4 Manually display mode Under automatic display mode push lt q or to enter into manually display mode then again push lt 4 or to display the contents It will return to automatic display mode if there is no operation for 30 seconds 4 5 Menu operation mode when instrument under free working mode push MENU to enter into menu operation mode then firstly gets the main menu the contents of it are as follows Max Demand Programme Push lt gt or lt to enter into different sub menus Push MENU to return to free working mode Note the LCD can only di
29. d R Vcc 5mA kO e _ testing earth meter inside photo copper output 3 9 Backlight By setting the BCW to turn on off the backlight Backlight control word BCW AUTO automatic off after 10 minuters if no 0 operation BCW 1 ON always on 2 OFF always off Figure 4 Backlight control word TY PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 9 3 10 RS485 The instrument is equipped with a RS485 communication port the available baud 9600bps 19200bps 38400bps Communication control word as follows rate 1200bps 2400bps 4800bps 00H 1200bps 01H 2400bps CBS 02H 4800bps Baud rate 03H 9600bps 04H 19200bps 05H 38400bps 00H NONE Without verify CDS 01H ODD Odd Data format 02H EVEN Even CPs 00H RTU Modbus RTU Protocol 01H ASCII Modbus ASCII Figure 5 communication control word T3 PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 10 4 Operation 4 1 Nameplate Display Key pad Menu Picture 9 nameplate 4 2 Pushbutton lt lt It is for the switch from automatic display mode to manually display mode Forth display modes under manually display Under menu operation mode to forth the menu item and contrast display When type into numbers push lt to increase the number quickly gt lt lt is for the switch from automatic display mo
30. d diameter of the twisted pair wire should not be less than 0 5mm The communication wire should be away from strong electric cable or strong electric field maximal communication distance is 1200 meters the typical wiring method is as picture 9 shown User can also select other proper wiring method according to site situation cd cd prs 220I v son P000 bdo dl rco ocee oo 90 l l TR j 1 a A E A 2320 485 77 Picture 13 Communication connecting Modbus protocol uses a master slave technique in which firstly one device the master initiates transactions queries The other devices the slaves respond by supplying the requested data to the master or by taking the action requested in the query The work mode is semi duplex Modbus protocol only allows the communication between master PC PLC etc and slaves and does not allow the data exchange between independent terminal devices As a result the terminal devices will not use communication line when initialization only response the query signal 5 2 Byte format 5 2 1 ASCII mode When controllers are setup to communicate on a Modbus network using ASCII mode each eight bit byte in a message is sent as two ASCII characters The main advantage of this mode is that it allows time intervals of up to one second to occur between character
31. de to manually display mode Forth display modes and contrast display item under manually display When type into numbers push lt to move cursor MENUS under automatic display mode push it to enter menu mode Under menu mode it is for returning to upper menu lt lt under menu mode push lt to enter into sub menu or to comfirm the input and return to upper menu If the instrument shows Errors then means the data input is incorrect user may push any key to re input When return from menu mode to automatic display mode if any parameter has been amended the instrument will show saves then push MENUS to exit without saving push lt to save and exit If no parameter changed then exit directly 4 3 Automatic display mode The instrument will work in automatic display mode when one of the following happened 1 Firstly instrument shows the startup interface after powr on then enter into automatic display mode as soon as the system becomes stable 2 No operation for 30 seconds under manually display mode 3 After exiting from the main menu After entering into this mode the instrument displays according to the pre stting modes User can program by stting the DCW display control word details of the display modes are as follows Display mode Example Description 00 Cycle display mode 01 19 T3 PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measur
32. ent 2519H o Re Phase C current 25 times harmonic content 251AH R Phase C current 26 times harmonic content 251BH A Phase C current 27 times harmonic content 251DH RE Phase C current 29 times harmonic content 251EH R Phase C current 30 times harmonic content 251FH HRIC31 Phase C current 31 times harmonic content D D D D D D D D D A DO 2509H HRIC9 Phase C current 9 times harmonic content pe D D D D D D D D D D D D D D D D D D D D Dd Figure 22 Address Information Note 1 the product of voltage and current rate should not be exceed 100000 otherwise some displayed data may be overflow 2 when the value read is zero write OAA55H to reset accumulated energy data other values are invalid 3 write OAA55H into WRST 7 000EH for energy data resetting Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 44 2 Energy data exchange All the energy data response from the meter is regulated as 2 bytes 4 bytes for energy the negative is shown by offset according to a formula The details of formula is as 16 shown PT voltage variation rate CT current variation rate Item Formula Value range symbol Note Voltage U RXxPTx0 01 0 65535 No symbol UA UB UC UAB UBC UCA Current RXxCTx0 001 0 65535 No symbol 1A IB IC Frequency F RXx0 01 0 65535 No symbol FR Power factor PF RX
33. er confirmation reset the demand data to zero Reset Setting YES After confirmation reset the system parameters as factory s setting Network Type 3P4W 3P3W Electrical network type 3P3W 3P4W Input Voltage Rate 1 9999 Voltage variation Current Rate 1 9999 Current variation Address 1 247 Meter Modbus communication address Communicati Baud 1200 38400 Baud rate 1200 2400 4800 9600 19200 38400 on Parity Bit 3 modes None Odd Even Protocol RTU ASCII 2 communication modes Modbus RTU Modbus ASCII Billing Date DD HH Set automatic month switching time DD day HH hour Multi Tariff Time Period xx HH MM RR Set the starting time of time period RR stands for the tariff number About PD76 E4E Figure 7 Menu structure Note 1 The product of voltage and current variation rate should be lt 100000 otherwise some displayed data will be overflow 2 when x is 1 7 2 7 3 or 4 it 3 XX range from 1 7 10 stand for 10 periods of time is for no 1 no 2 no 3 or no 4 analog or switching output setting 4 demand period is fixed to be 15 minutes User cant reset again within 5 minutes after resetting the demand it wont be effect 4 5 2 Multi rate energy inquire mode When in the main menu push lt 4 or gt o select Energy then push to enter into multi rate energy sub menu Below is the sub munu structure First layer Second layer Data format Description
34. g to Figure 20 Likewise we know DOS1L and DOS1H DOS1L UL PTx10 8kV 100x10 800 DOS1H UH PTx10 12kV 100x10 1200 According to Figure 3 So when the first side voltage is less than 8kV or more than 12kV the first switching output closed Item Formula Value range Symbol Note voltage Sx U PTx10 1 9999 No symbol UA UB UC UAB UBC UCA current Sx 1 CTx1000 1 9999 No symbol IA IB IC Frequency S x Fx100 1 9999 No symbol FR Power factor Sx PFx1000 1 9999 No symbol PFA PFB PFC PFS Active power Sx P PT CT 1 9999 No symbol PA PB PC PS Reactive power Sx Q PT CT 1 9999 No symbol QA QB QC QS Apparent power Sx S PT CT 1 9999 No symbol SA SB SC SS Note PT voltage variation rate CT current variation rate Figure 3 switching output analog outut setting data exchange formula 3 8 Energy pulse output function With active reactive two energy pulse output testing ports the pulse constant active 10000imp kwh reactive 10000imp kVARh T3 PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 8 Vec 5V 12V 24V gt R Vcc 5mA kOQ Pulse width 80420ms e _ testing earth meter inside photo copper output when period lt 200ms 1 1 By setting the SOUT to change reactive energy pulse output to 1Hz clock output The sketch map of testing port is as follows Vcc Pulse width 500ms E Vec 5V 12V 24V i
35. ic content R 2305H P R Phase A current 5 times harmonic content R 2307H P nar Phase A current 7 times harmonic content R 2308H P ORB Phase A current 8 times harmonic content R 2309H O Phase A current 9 times harmonic content R 230AH P RAD Phase A current 10 times harmonic content R 230BH P nr Phase A current 11 times harmonic content R 230CH Mee Phase A current 12 times harmonic content R 230EH P m Phase A current 14 times harmonic content R 2310H P HRAB Phase A current 16 times harmonic content R 2311H P Ria Phase A current 17 times harmonic content R 2312H P Ria Phase A current 18 times harmonic content R 2313H PT RM Phase A current 19 times harmonic content R 2315H P Rint Phase A current 21 times harmonic content R 2317H P ma Phase A current 23 times harmonic content R 2318H P RIAA Phase A current 24 times harmonic content R 2319H P HRAS Phase A current 25 times harmonic content R 231AH EOS Phase A current 26 times harmonic content R Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 42 231 231 231 231 BH CH DH EH 231FH 2400H 2401H 2402H 2403H 2404H 2405H 2406H 2407H 2408H 2409H 240AH 240BH 240CH 240DH 240EH 240FH 241 0H 2411H 241 241 241 241 241 241 241 241 241 241 241 241 241
36. ication code High byte 36H Stop 4 bytes time interval Figure 19 Write register master enquire data frame RTU mode ASCII code HEX code Start 3AH Address code 01 30H 31H Function code 10 31H 30H Original register address 000A 30H 30H 30H 41H Number of write register 0001 30H 30H 30H 31H Verification code E4 45H 34H Stop lt CR gt lt LF gt ODH OAH Figure 20 Write register slave response data frame ASCII mode Start 4 bytes time interval Address code 01H Function code 10H Original register High byte 00H address Low byte OAH High byte 00H Number of register Low byte 01H Low byte 21H Verification code High byte CBH Stop 4 bytes time interval Figure 20 Write register slave response data frame RTU mode T3 PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 21 1 Address information Appendix 0000H 0001H 0002H 0003H 0004H 0005H 0006H 0007H 0008H 0009H 000AH 000BH 000CH 000DH 000EH 000FH 0010H 0011H 0012H 0013H 0014H 0015H 0016H 0017H 0018H 0019H 001AH 001BH 001CH 001DH 001EH 001FH System Parameters oo SERH Series Number high bit po SERL Series Number low bit 4 STATE System working state reserved 8888 TU SW Password for programming ADDR Meter address 9600 RTU 4 9999 9999 9999 9999 0000 9999 0000 9999 0000 9999 CBS CDS
37. ing Instruments 11 Display mode Example Description ji Display A B C three phase voltage and neutral voltage Unit V or kV 02 Display AB BC CA voltage Unit V or kV A Display A B C three phase current and neutral current Unit A or kA 0000kW 0 0000kW Display A B C three phase active power and total 0000kW active power 0000kW p 0000kvar a 0000kvar Display A B C three phase reactive power and 0000kvar total reactive power 0000kvar j 0000KkVA 0000KkVA 06 0000KkVA Display A B C three phase apparent power 0000KkVA e Display A B C three phase power factor and total power factor 0000kW 0000kvar Display total active power reactive power is D000KVA apparent power and frequency 00 00Hz T PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments Display mode Example Description Act Energy 000000 00 kWh Display forward active power reverse active 09 Act Energy power 000000 00 kWh Re Energy 000000 00 kvarh Display forward reactive power reserve reactive 10 Re Energy i ower 000000 00 kvarh i HRUA a Display harmonic of phase A voltage shown as 11 the percent of fundamental wave HRUB 7 a Display harmonic of phase B voltage shown as the percent of fundamental wave HRUC a Display harmonic of phase C voltage shown as 13 the percent of fundamental wave HRI A Display h
38. ion period Integration period It is fixed to be 15 minutes Sliding period lt is for the maximal demand measurement range from 1 15 minutes 3 5 Switching input The instrument has t 4 or 6 switching input monitor function need the support of hardware and software Real time monitoring the state of each switching input it s indicated by the low byte of DIO DIO low byte BIT7 BIT6 BITS BIT4 BIT3 BIT2 BIT1 BITO DI3 DI2 Dit DIO DIO DI5 stand for the 1 6 switching input state 0 input signal disconnected 1 input signal connected 3 6 Analog output 0 Close the channel of analog output AOSIx output item 1 26 26 energy consumption measured output 0 20mA 129 154 26 energy consumption measured output 4 20mA AOSx Output parameter value 1 9999 corresponding with the parameter value of 20mA output Analog output setting All setting data of analog output is standardized to 2 bytes SX according to a formula The value is range from 1 to 1999 absolute value Example for 10kV 100V meter set the first analog output 4 20mA corresponding with UA we get AOSI1 and PT T3 PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 7 should be setto 129 and 100 according to Figure 19 We also get AOS1 AOS1 U PTx10 10kV 100x10 1000 according to Figure 21 When the first side voltage is 10kV the first analog output 20 mA current
39. l Mounted Electrical Measuring Instruments 22 Function code Definition Operation 03 04H Read register Read data from the register s 10H Write one or more continuous registers Write n 16 bit binary number into n regesters Figure 12 Function code 5 3 3 Date field Data Data field are different because of different function code These data can be numerical value reference address etc for instance function code 03H specifies the value which meter read register then the data field much contain the start address and read length of the register 5 3 4 Verify code Verify code is to estimate the data received correct or not for the master and slave it guarantees the communication system more reliable Modbus ASCIl adopts the LRC to verify The LRC is calculated by adding together successive eight bit bytes in the message discarding any carries and then two s complementing the result The LRC is an eight bit field therefore each new addition of a character that would result in a value higher than 255 decimal simply rolls over the field s value through zero Because there is no ninth bit the carry is discarded automatically Modbus RTU adopts the CRC 16 to verify it contains a 16 bit binary value The CRC value is calculated by the transmitting device which appends the CRC to the message The receiving device recalculates a CRC during receipt of the message and compares the calculated value to the actual
40. month day hour minute Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 16 00 00 00 00 AN before last month taffif x forward active demand and time i j stamp month day hour minute 00 00 00 00 Total 00 00 kW current month reverse active demand and time stamp i month day hour minute Curent on 00 00 kW current month taffif x reverse active demand and time stamp i th day hour minute 00 00 00 00 mon Total l 00 00 kW last month reverse active demand and time stamp i month day hour minute Act Last Month 00 00 00 00 Demand Tariff x 00 00 kW last month taffif x reverse active demand and time stamp i th day hour minute 00 00 00 00 a Total f 00 00 kW before last month reverse active demand and time stamp 00 00 00 00 month day hour minute Before Last Mon Tariff x 00 00 kW before last month taffif x reverse active demand and time y stamp month day hour minute 00 00 00 00 Total f 00 00 kvar current month forward reactive demand and time 00 00 00 00 stamp month day hour minute Current Tariff x 00 00 kvar current month tarrif x forward reactive demand and time i stamp month day hour minute 00 00 00 00 ka kvar last month forward reactive demand and time Re 00 00 00 00 stamp month day hour minute Demand Last Month Tariff x l 00 00 kvar last month tarrif x fo
41. n Multi Tariff Programme Communication Multi Tariff Password Hess Basic Setting Display Item Backlight Scroll Time Network Type Voltage Rate Current Rate Communication Baud Parity Bit Multi Tariff Billing Date Time Period 1 Time Period 2 Password 8888 Display Item Display Item oogo ooofl lt _ save the input data Network Type Network Type 3P4W 3P4W 3P3W EEN lt save the input data Billing Date Billing Date 1 00 28 09 save the input data Picture 10 program mode operation sample Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 18 Max Demand Program Act Energy Re Energy Act Energy Act Energy Re Energy Act Energy Act Energy Re Energy Act Energy Re Energy Re Energy Act Energy Current Last Month 000000 00 kWh Before Last Mon Active Energy Current Before Last Mon 000000 00 kWh Active Energy Current Last Month 000000 00 kWh Before Last Mon Act Energy Current Last Month 000000 00 kWh Before Last Mon Re Energy Current Last Month Before Last Mon Re Energy Current Last Month Before Last Mon Picture 11 multi rate energy inquiry 000000 00 kWh 000000 00 kWh 000000 00 kWh 000000 00 kWh 000000 00 kvar h 000000 00 kvar h Tz PD76 E4E WFF
42. n 0160H Qh L R W Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 31 0161H 0162H 0163H 0164H 0165H 0166H 0167H 0168H 0169H 016AH 016BH 016CH 016DH 016EH 016FH 0170H 0171H 0172H 0173H 0174H 0175H 0176H 0177H 0178H 0179H 017AH 017BH 017CH 017DH 017EH 017FH 0180H 0181H 0182H 0183H 0184H last month total reverse reactive energy consumption last month T1 reverse reactive energy consumption last month T2 reverse reactive energy consumption last month T3 reverse reactive energy consumption last month T4 reverse reactive energy consumption two months ago total forward active energy consumption two months ago T1 forward active energy consumption two months ago T2 forward active energy consumption two months ago T3 forward active energy consumption two months ago T4 forward active energy consumption two months ago total reverse active energy consumption two months ago T1 reverse active energy consumption two months ago T2 reverse active energy consumption two months ago T3 reverse active energy consumption two months ago T4 reverse active energy consumption two months ago total forward reactive energy consumption two months ago T4 forward reactive energy consumption two months ago T2 forward reactive energy consumption RIW RIW RIW RIW R W
43. nt month T2 reverse reactive demand DPPT2 H Occur time of current month T2 reverse reactive demand DPPT2 L Month day hour minute MA DPP3 Current month T3 reverse reactive demand DPPT3 H Occur time of current month T3 reverse reactive demand DPPT3 L Month day hour minute a Saeed DPP4 Current month T4 reverse reactive demand SSS DPPT4 H Occur time of current month T4 reverse reactive demand R W R W R W TY PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 35 033BH Pe DPPT4 L Month day hour minute R W 033CH pe Last month forward active demand R W 033DH aa DPPT H Occur time of last month forward active demand R W 033EH MEA DPPT L Month day hour minute RIW 033FH e DPP1 Last month T1 forward active demand RIW 0340H a DPPT1 H Occur time of last month T1 forward active demand RIW 0341H bw DPPT1 L Month day hour minute RIW 0342H ME DPP2 Last month T2 forward active demand RIW 0343H A DPPT2 H Occur time of last month T2 forward active demand RIW 0344H ME DPPT2 L Month day hour minute RW 0345H DPP3 Last month T3 forward active demand R W 0346H a DPPT3 H Occur time of last month T3 forward active demand RIW 0347H ME DPPT3 L Month day hour minute R W 0348H oo DPP4 Last month T4 forward active demand R W 0349H MIS DPPT4 H Occur time of last month T4 forward active demand RIW 034AH Poe DPPTA4 L Month day hour minute RIW
44. r we suggest use surge suppresser and fast impulse suppresser Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 6 3 Functions 3 1 Electrical parameters measuring Three phase voltage three phase current active powr reactive power frequency power factor active energy reactive energy four quadrant energy 3 2 Harmonic measuring The instrument can measure 1 31 times harmonic current voltage it s convenient for users to analyse the network harmonic Both current harmonic and voltage harmonic are shown as the percent of fundamental wave 3 3 Multi rate The instrument has the multi rate function for energy measurement Maximal supports 10 time periods and 4 tariff It can storage the forward active energy reserve active energy forward reactive energy reserve reactive energy of current month last month and the month before last month Time period when programming it shows which time period the instrument is working in the duration of time period starts at its beginning time and ends at the beginning time of the coming time period Tariff when programming they are shown as 1 2 3 and 4 which mean peak tarrif off peak tarrif shouder tarrif and vale tarrif 3 4 Maximal demand record Record the each tarrifs maximal demand includes A A R R as well as the time stamp of current month last month and the month before last month Maximal demand The maximal everage power within intergrat
45. rthed A1 B1 RS4850 optional needs hardware support A2 B2 RS4850 optional needs hardware support Middle row Input and output terminals Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 4 Output terminals Switching input terminals 29 30 31 32 33 34 35 36 37 38 39 40 41 42 AOUT1 AOUT2 AOUT3 AOUT4 DIN1 DIN2 DIN3 DIN4 COM Picture 3 4 switching inout and 4 analog output terminals Output terminals Switching input terminals 29 30 31 32 33 34 35 36 37 38 39 40 41 42 DOUT1 DOUT2 DOUT3 DOUT4 DIN DIN2 DIN3 DIN4 COM Picture 4 4 switching inout and 4 switching output terminals Output terminals Switching input terminals 29 30 31 32 33 34 35 36 37 38 39 40 41 42 DOUT1 DOUT2 DIN1 DIN2 DIN3 DIN4 DINS DIN6 COM Picture 5 6 switching inout and 2 switching output terminals Note According to the type of meter there are two kinds of output terminals switching output terminals and analog output terminals the function needs hardware support Com switching input earthed Bottom row Voltage and power supply terminals Voltage terminals Power supply Picture 6 Singal terminals The instrument has different wiring methods for different types of load Type 1 three phase four wire three C
46. rward reactive demand and time i i stamp month day hour minute 00 00 00 00 Total 00 00 kvar before last month forward reactive demand and time Before Last Mon 00 00 00 00 stamp month day hour minute Tariff x before last month tarrif x forward reactive demand and time 000000 00 kvarh stamp month day hour minute ai kvar current month reverse reactive demand and time 00 00 00 00 stamp month day hour minute Current A Tariff x 00 00 kvar current month tarrif x reverse reactive demand and time i stamp month day hour minute 00 00 00 00 o kvar last month reverse reactive demand and time 00 00 00 00 stamp month day hour minute Re Demand Last Month Tariff x A 00 00 kvar last month tarrif x reverse reactive demand and time i stamp month day hour minute 00 00 00 00 Total l 00 00 kvar before last month reverse reactive demand and time 00 00 00 00 stamp month day hour minute Before Last Mon reata Tariff x 00 00 kvar before last month tarrif x reverse reactive demand and time i stamp month day hour minute 00 00 00 00 Figure 9 demand and the time stamp menu structure Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 17 Max Demand Programme Programme Basic Setting Input Communication Programme Basic Setting Communication Programme Basic Setting Input Communication Programme Input Communicatio
47. s Phase C voltage 8 times harmonic content 2209H Po Ro Phase C voltage 9 times harmonic content 220AH Po PRUG Phase C voltage 10 times harmonic content 220BH Po mr Phase C voltage 11 times harmonic content 220CH Po ruca Phase C voltage 12 times harmonic content 220DH Po ucts Phase C voltage 13 times harmonic content 220EH ENS Phase C voltage 14 times harmonic content 220FH Po PRUCIS Phase C voltage 15 times harmonic content 2210H Po PRUCIS Phase C voltage 16 times harmonic content 2211H Po uci Phase C voltage 17 times harmonic content 2212H Po PRUCIS Phase C voltage 18 times harmonic content 2213H ENS Phase C voltage 19 times harmonic content 2214H MENS Phase C voltage 20 times harmonic content 2215H MENOS Phase C voltage 21 times harmonic content 2216H HRUC22 Phase C voltage 22 times harmonic content D D D D way way D D D D D D D D D D D D D D D D D D D D D D D D D D D D D Dd T3 PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 41 2217H HRUC23 Phase C voltage 23 times harmonic content R 221FH Po PRUSIO Phase C voltage 31 times harmonic content R 2300H HRIAO Phase A current AC content R 2301H HRIA1 Phase A fundamental wave content R 2302H P m Phase A current 2 times harmonic content R 2303H HRIA3 Phase A current 3 times harmon
48. s without causing an error Each transmission contains 10 bit serial data During transmission lower bit first then higher bit User can select odd even or without parity The transmission sequence of both types are as follows start data Picture 14 transmission sequence with parity bit ASCII mode start data 000 erar end end 00g Picture 15 transmission sequence without parity bit ASCII mode Ty PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 21 5 2 2 RTU When controllers are setup to communicate on a Modbus network using RTU mode each byte in the frame can be used for transaction directly So its greater character density allows better data throughput than ASCII for the same baud rate Each transmission contains 11 bit serial data During transmission lower bit first then higher bit User can select odd even or without parity The transmission sequence of both types are as follows DODODODOA start data parity end Picture 16 transmission sequence with parity bit RTU mode start data end Picture 17 transmission sequence without parity bit RTU mode 5 3 Frame format Frame is the basic unit for transaction message In Modbus protocol master and slave use the same frame format In ASCII mode messages start with a colon character ASCII 3A hex and end with a carriage return line feed CRLF pair ASCII OD and 0
49. splay 4 lines information user can push lt q or gt to show the next screen page 4 5 1 Programme mode When in the main menu push lt a or to select Programme then push to program Firstly the system will ask the user to type into password only with correct password can enter into the sub menu Under menu operation mode the instrument provides some parameters setting menu items such as Basic Setting Input Communication Analog Output Digital Output Multi Tariff etc The menu s structure is as follows users can set the proper parameters as per their own requirements First layer Second layer Data format Description Password 0000 Input password only valid password can enter program Basic Setting Display Item 0 19 Set display control word Backlight 3 modes Backlight control modes AUTO ON OFF Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 14 Scroll Time 1 99 Turning time it effects when DISP set as 0 YYYY MM DD Time Set the date and time of instrument HH MM SS Rolling Time 1 15 Sliding period unit minute Second signal reactive energy pulse output select 0 output reactive Pulse Output 0 1 energy pulse 1 second signal Clear Energy YES After confirmation reset the energy data to zero ClearDemand YES Aft
50. value it received in the CRC field If the two values are not equal an error results The CRC is started by first preloading a 16 bit register to all 1 s Then a process begins of applying successive eight bit bytes of the message to the current contents of the register Only the eight bits of data in each character are used for generating the CRC Start and stop bits and the parity bit do not apply to the CRC During generation of the CRC each eight bit character is exclusive ORed with the register contents The result is shifted in the direction of the least significant bit LSB with a zero filled into the most significant bit MSB position The LSB is extracted and examined If the LSB was a 1 the register is then exclusive ORed with a preset fixed value If the LSB was a 0 no exclusive OR takes place This process is repeated until eight shifts have been performed After the last eighth shift the next eight bit character is exclusive ORed with the register s current value and the process repeats for eight more shifts as described above The final contents of the register after all the characters of the message have been applied is the CRC value The calculating process of CRC 16 is as follow T3 PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 23 Picture 18 calculating progress of CRC 16 verif
51. x0 0001 10000 10000 No symbol PFA PFB PFC PFS Active power P RXxPTxCT 32768 32767 No symbol PA PB PC PS Reactive power Q RXxPTxCT 32768 32767 No symbol QA QB QC QS Apparent power S RXxPTxCT 0 65535 No symbol SA SB SC SS Energy W RXxPTxCTx10 0 232 1 No symbol Wh Wh varh varh Figure 23 Data exchange formula
52. y code 5 4 Error management The meter will response message when it has examined error which out of the error codes the highest bit of function code is 1 That is the function code slave response is what it received plus 128 The format of error message frame which rebound from the slave is as follows Function code Verification code Address code Error code highest bit 1 Low byte High byte 1 byte 1 byte 1 byte 1 byte 1 byte Figure 13 Invalid message frame format return from the slave Error code as follows 01H Invalid function code Meter doesn t support the function code received 02H Invalid data address 03H Invalid data value The data address received is out of range The date value received is out of range Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 24 5 5 Samples of Communication message 5 5 1 Read Register function code 03 04H This function allows user to obtain the data and system parameters which the meter sampling and recording The maximal register number which master requests is 125 The following sample is reading three basic data IAL IB IC from the client which address code is 01H the length of each register is 2 bytes the start address of IA is 0100H number of register is 3 ASCII code HEX code Start 3AH Address code 01 3
53. zation switching network automatization industrial automatization intelligence buildings intelligence switchboards and switch cabinets it is characteristic of convenient installation simple wiring easy maintenance and less works It also can be connected with PLC and industry control computers Tz PD76 E4E WFF Digital Indicating Panel Mounted Electrical Measuring Instruments 1 1 2Technical parameters Technical parameter Value Network 3P3W 3P4W Reference AC 100V 220V 400V Overload Lasting 1 2 Un Momently 2 Un 30 s Voltage Consumption lt 0 5VA each phase Input Resistance gt 500KQ Reference AC 1A 5A Current Overload Lasting 1 2 In Momently 20 In 2s Resistance lt 20mQ each phase Frequency 450 65Hz Energy pulse Two pulse output crs aa Mode RS 485 Output Communication Protocol MODBUS RTU ASCII Baud rate 1200 2400 4800 9600 Display LCD U 0 2 kW kVAR kVA 0 5 Accurancy Frequency 0 2 kWh 0 5 kVARh 12 Range AC DC 800 270V Power supply Consumption lt 5VA Input and auxiliary power gt 2KV50Hz 1min supply Over voltage Input and output gt 2KV50Hz 1min Output and auxiliary power gt 2KV50Hz 1min Security supply Insulated resistance Input output and auxiliary power supply against the watchcase gt 100MQ Case anti fire VO class Electromagnetic Electrostatic discharge 15KV

Download Pdf Manuals

image

Related Search

PD76 E4E MFF

Related Contents

CLUB3D SenseVision MST HUB 1-3 HDMI  Q-See QSDT16PCRP Technical Manual  SVAirFlow Tutorial Manual  OP500 User Manual - AV-iQ  90, rue de la Pointe Langlois Tel. bureau : 450-937  Betriebsanleitung (Original) SK 41 Sicherheitsschaltgerät  Plaquette - gutermann  さようなら 馬場目小学校・馬場目保育園  KPNO MOSAIC-1.1 IMAGER USER MANUAL Version: 4.2  Citizen CLP-8301 User Manual  

Copyright © All rights reserved.
Failed to retrieve file