1. EUR OPROT sF IEC 101 104 103 interoperability list IEC 101 104 103 interoperability list 1 CONTENTS IEC 60870 5 101 Edition 2 and IEC 60870 5 104 2000 interoperability list 3 II System Or GSIN 3 1 2 Network configuration IEC 60870 5 101 GOO rrura 3 1 3 Physical layer IEC 60870 5 101 only ss 3 1 4 Link layer IEC 60870 5 101 only rrura 4 Lo Application layo eitea dod luen Seteae ds cbiiiesbeedase E eian ztei 5 1 6 Selection of standard AGOITZ rss 6 Lf Basic application fUNCtONS aiurria Ea aar 8 IEC 60870 5 103 interoperability Sira 12 2 1 Physical ASAN 12 22 LAK LAV e 12 2 3 Aplication layer ccs ccna a eee eee 12 2 4 Selection of standard information numbers in monitor direction rra 13 2 5 Selection of standard information numbers in control direction rra 18 2011 05 27 2 19 IEC 101 104 103 interoperability list 1 IEC 60870 5 101 Edition 2 and IEC 60870 5 104 2000 interoperability list 1 1 System or device CI System definition C Controlling station definition master W Controlled station definition slave 1 2 Network configuration IEC 60870 5 101 only Mi Point to point C Multipoint partyline C Multiple point to point WM Multipoint star 1 3 Physical layer IEC 60870 5 101 only Transmission speed C 100 bit s C 200 bit s L 300 bit s L 600 bit s WM 1200 bit s JZ 2400 bit s WM 4800 bit s WM 9600 bit s JZ 19200 bit s WM 38400 bit s L 56000 bit s C 64000 bit s
2. Note The transmission speed is equal in the control and the monitor direction Supported media is RS 485 HFBR type 1 mm plastic fiber optic and unmodulated multimode glass fiber with ST type connector Please note all kind of serial connectors are ordering option 2011 05 27 3 19 IEC 101 104 103 interoperability list 1 4 Link layer IEC 60870 5 101 only Link transmission procedure C Balanced transmission W Unbalanced transmission Address field of the link LI Not present W One octet W Two octets CI Structured C Unstructured Frame length Maximum length of the frame in control direction Not limited Maximum length of the frame in monitor direction General parameter in EuroCAP tool ASDU class 2 assignment Type identification Cause of transmission lt 1 gt M_SP_NA_1 lt 2 gt Background scan lt 3 gt M_DP_NA_1 lt 13 gt NM ME NC_1 lt 15 gt MIT NA Note ASDU class 2 data sent only if background scan enabled generally and at least one object has background scan property set 2011 05 27 4 19 IEC 101 104 103 interoperability list 1 5 Application layer Common address of ASDU W One octet W Two octets Note The common address of ASDU is always the same as the link address In IEC 60870 5 101 the length of the common address can be set by EuroCAP tool In IEC 60870 5 104 the length of the common address is always two octets Information object address W One octet C
3. 28 gt Auxiliary input 2 WM lt 29 gt Auxiliary input 3 V lt 30 gt Auxiliary input 4 Note Not all of these information objects presented in the device Any internal boolean or enumerated event channel can be mapped to these information objects by the user See the EuroCAP tool user manual for the details 2011 05 27 13 19 IEC 101 104 103 interoperability list Supervision indication in monitor direction MW lt 32 gt Measured supervision I MW lt 33 gt Measured supervision U WM lt 35 gt Phase sequence supervision WM lt 36 gt Trip circuit supervision V lt 37 gt I gt gt back up operation WV lt 38 gt VT fuse failure WM lt 39 gt Teleprotection disturbed WM lt 46 gt Group warning WM lt 47 gt Group alarm Note Not all of these information objects presented in the device Any internal boolean or enumerated event channel can be mapped to these information objects by the user See the EuroCAP tool user manual for the details Earth fault indication in monitor direction W lt 48 gt Earth fault L1 W lt 49 gt Earth fault L2 WM lt 50 gt Earth fault L3 W lt 51 gt Earth fault forvard i e line W lt 52 gt Earth fault reverse i e busbar Note Not all of these information objects presented in the device Any internal boolean or enumerated event channel can be mapped to these information objects by the user See the EuroCAP tool user manual for the details Fault indication in monitor direct
4. M_ME_TF_1 lt 37 gt M_IT_TB_1 lt 45 gt C_SC_NA 1 lt 7 gt activation confirmation lt 6 gt activation edit D DZ NA lt 9 gt deactivation confirmation lt 8 gt deactivation lt 47 gt ZZ EO NA 1 lt 10 gt activation termination lt 59 gt C SC TA 1 lt 60 gt C DC TA 1 lt 61 gt C_RC_TA_1 lt 70 gt M_EI_NA_1 lt 4 gt initialized lt 100 gt C_IC_NA_1 lt 7 gt activation confirmation lt 9 gt deactivation confirmation lt 10 gt activation termination lt 6 gt activation lt 8 gt deactivation lt 103 gt C_CS_NA_1 lt 7 gt activation confirmation lt 6 gt activation These commands are not part of the IEC 60970 5 101 standard but introduced in 60870 5 104 The EuroProt platform devices accept these commands too 1 7 Basic application functions Station initialization O Remote initialization Cyclic data transmission Cl Cyclic data transmission Note Cyclic data transmission not supported but background scan messages used Read procedure CI Read procedure Spontaneous transmission V Spontaneous transmission 2011 05 27 8 19 IEC 101 104 103 interoperability list Note All changes of single and double point information floating point measurands and counters causes spontaneous transmission The generated ASDUs always contain 7 octet binary time tag Cp56Time2a The time stamp is always local time Double transmission of information objects with c
5. of one groups WM lt 243 gt Read directory of a single entry V lt 244 gt Read value or attribute of a single entry MW lt 245 gt General interrogation of generic data L lt 248 gt Write entry C lt 249 gt Write entry with confirmation L lt 250 gt Write entry with execution C lt 251 gt Write entry abort 2011 05 27 18 19 IEC 101 104 103 interoperability list Basic application functions CI Test mode Cl Blocking of monitor direction CI Disturbance data W Generic services V Private data 2011 05 27 19 19
6. Structured W Two octets O Unstructured W Three octets Note In IEC 60870 5 101 the length of the information object address can be set by EuroCAP tool In IEC 60870 5 104 the length of the information object address is always three octets Cause of transmission Mi One octet WM Two octets with originator Note In IEC 60870 5 101 the length of the COT can be set by EuroCAP tool In IEC 60870 5 104 the length of the COT is always two octets 2011 05 27 5 19 IEC 101 104 103 interoperability list 1 6 Selection of standard ASDU s Process information in monitor direction WM lt 1 gt Single point information C lt 2 gt Single point information with time tag WM lt 3 gt Double point information C lt 4 gt Double point information with time tag C lt 5 gt Step position information C lt 6 gt Step position information with time tag L lt 7 gt Bitstring of 32 bit C lt 8 gt Bitstring of 32 bit with time tag L lt 9 gt Measured value normalized value CI lt 10 gt Measured value normalized value with time tag C lt 11 gt Measured value scaled value CI lt 12 gt Measured value scaled value with time tag WM lt 13 gt Measured value short floating point value C lt 14 gt Measured value short floating point value with time tag WM lt 15 gt Integrated total C lt 16 gt Integrated total with time tag Cl lt 17 gt Event of protection equipment with time tag C lt 18 gt Packed start events of pro
7. ause of transmission spontaneous Cl Single point information C Double point information CI Step position information C Bitstring of 32 bit C Measured value normalized value C Measured value scaled value C Measured value short floating point number Station interrogation M global C group 1 C group 2 C group 3 C group 5 Cl group 6 Cl group 7 C group 9 C group 10 C group 11 C group 13 C group 14 C group 15 Clock synchronization Mi Clock synchronization Cl Day of week used C SU bit summertime used CI RES1 GEN time tag substituted not substituted used Cl group 4 Cl group 8 C group 12 C group 16 Note Legacy protocol time synchronization should be enabled to set the system time See the system settings using HMI or WEB interface The sent and received time is always local time 2011 05 27 9 19 IEC 101 104 103 interoperability list Command transmission MV Direct command C Direct set point command Mi Select and execute command CI Select and execute set point command WM C_SE_ACTTERM used CI No additional information CI Short pulse duration Cl Long pulse duration C Persistent output Transmission of integrated totals C Mode A local freeze with spontaneous transmission C Mode B local freeze with counter interrogation C Mode C freeze and transmit by counter interrogation commands C Mode D freeze by counter interrogation command frozen va
8. e of the 2nd counter lt 10 gt Description lt 1 gt OS8ASCIl 1 64 1 Internal name of the 2nd counter O208h urz jj Jase anes seve irran Internal structure of the entries in the EuroProt platform 2011 05 27 17 19 IEC 101 104 103 interoperability list 2 5 Selection of standard information numbers in control direction System functios in control direction JZ lt 0 gt Initiation of general interrogation MW lt 0 gt Time synchronization Note Legacy protocol time synchronization should be enabled to set the system time See the system settings using HMI or WEB interface The sent and received time is always local time General commands in control direction Vi lt 16 gt Auto recloser on off MW lt 17 gt Teleprotection on off W lt 18 gt Protection on off W lt 19 gt LED reset W lt 23 gt Activate characteristic 1 W lt 24 gt Activate characteristic 2 V lt 25 gt Activate characteristic 3 W lt 26 gt Activate characteristic 4 Note Not all of these commands available in all devices Any internal control channel can be mapped to these commands by the user See EuroCAP tool user manual for the details Private commands in control direction V lt 32 239 gt Private command can be mapped any internal control channel using EuroCAP tool Generic functions in control direction WM lt 240 gt Read headings of all defined groups V lt 241 gt Read values or attributes of all entries
9. ion WV lt 64 gt Start pick up L1 WM lt 65 gt Start pick up L2 WM lt 66 gt Start pick up L3 Hd lt 67 gt Start pick up N JZ lt 68 gt General trip WV lt 69 gt Trip L1 WM lt 70 gt Trip L2 WV lt 71 gt Trip L3 Hd lt 72 gt Trip I gt gt back up operation MW lt 73 gt Fault location X in ohms WM lt 74 gt Fault forward line WM lt 75 gt Fault reverse busbar WM lt 76 gt Teleprotection signal transmitted 2011 05 27 14 19 IEC 101 104 103 interoperability list WM lt 77 gt Teleprotection signal received Hd lt 78 gt Zone 1 WM lt 79 gt Zone 2 Mi lt 80 gt Zone 3 WM lt 81 gt Zone 4 WM lt 82 gt Zone 5 WM lt 83 gt Zone 6 V lt 84 gt General start pick up WM lt 85 gt Breaker failure MW lt 86 gt Trip measuring system L1 V lt 87 gt Trip measuring system L2 V lt 88 gt Trip measuring system L3 WM lt 89 gt Trip measuring system E WV lt 90 gt Trip I gt WV lt 91 gt Trip I gt gt WM lt 92 gt Trip IN gt WM lt 93 gt Trip IN gt gt Note Not all of these information objects presented in the device Any internal boolean or enumerated event channel can be mapped to these information objects by the user See the EuroCAP tool user manual for the details Auto reclosure indication in monitor direction MW lt 128 gt CB on by AR MW lt 129 gt CB on by long time AR Hd lt 130 gt AR blocked Note Not all of these information objects presented in the device Any i
10. lues reported spontaneously C Counter read C Counter freeze without reset C Counter freeze with reset C Counter reset CI General request counter CI Request counter group 1 CI Request counter group 2 C Request counter group 3 Cl Request counter group 4 Parameter loading Cl Threshold value C Smoothing factor C Low limit for transmission of measured value Cl High limit for transmission of measured value Parameter activation C Act deact persistent cyclic or periodic transmission of the addressed object 2011 05 27 10 19 IEC 101 104 103 interoperability list Test procedure Cl Test procedure File transfer File transfer in monitor direction Cl Transparent file Cl Transmission of disturbance data of protection equipment C Transmission of sequences of events Cl Transmission of sequences of recorded analogue values File transfer in control direction Cl Transparent file Background scan M Background scan Note The background scan should be enabled generally and the BG scan property of the monitored object should be set The periodicity of the messages is a general setting See EuroCAP tool user manual for the details Acquisition of transmission delay C Acquisition of transmission delay 2011 05 27 11 19 IEC 101 104 103 interoperability list 2 IEC 60870 5 103 interoperability list 2 1 Physical layer Electrical interface V RS 485 ordering option Optical interface Mi Glas
11. nternal boolean or enumerated event channel can be mapped to these information objects by the user See the EuroCAP tool user manual for the details Measurands in monitor direction L lt 144 gt Measurand I C lt 145 gt Measurand V C lt 146 gt Measurand I V P Q L lt 147 gt Measurand In Ven L lt 148 gt Measurand Ili 23 V123 P Q f Note In EuroProt platform floating point type data is used to represent measurands There is no general way to convert them to MEA value without loss of information Generic functions are used to transfer measurands and counters 2011 05 27 15 19 IEC 101 104 103 interoperability list Private information in monitor direction WM lt 160 239 gt Private data can be mapped any internal data using EuroCAP tool Note Any internal boolean or enumerated event channel can be mapped to this information objects by the user See the EuroCAP tool user manual for the details Generic functions in monitor direction WM lt 240 gt Read headings of all defined groups V lt 241 gt Read values or attributes of all entries of one groups WM lt 243 gt Read directory of a single entry V lt 244 gt Read value or attribute of a single entry WM lt 245 gt End of general interrogation of generic data C lt 249 gt Write entry with confirmation L lt 250 gt Write entry with execution L lt 251 gt Write entry aborted Note Generic service is used to access the current value of the meas
12. s fibre ordering option Mi Plastic fibre ordering option V Idle state light on V Idle state light off Note idle state is defined in the standard as light on IEC 60870 5 103 first edition chapter 5 1 For compatibility reason the idle state can be changed using the EuroCAP tool Transmission speed WM 9600 bit s JZ 19200 bit s Note transmission speed supported from 1200 to 38400 bit s The speed can be set by local HMI or WEB interface 2 2 Link layer There are no choices for the link layer 2 3 Aplication layer Common address of ASDU WM One common address of ARDU identical with station address C More than one common addrss of ASDU 2011 05 27 12 19 IEC 101 104 103 interoperability list 2 4 Selection of standard information numbers in monitor direction System functions in monitor direction MW lt 0 gt End of General Interrogation JZ lt 0 gt Time synchronization WM lt 2 gt Reset FCB WM lt 3 gt Reset CU C lt 4 gt Start Restart WM lt 5 gt Power on Status indication in monitor direction V lt 16 gt Auto recloser active WM lt 17 gt Teleprotection active V lt 18 gt Protection active V lt 19 gt LED reset V lt 20 gt Monitor direction blocked V lt 21 gt Test mode WM lt 22 gt Local parameter setting W lt 23 gt Characteristic 1 W lt 24 gt Characteristic 2 W lt 25 gt Characteristic 3 W lt 26 gt Characteristic 4 WM lt 27 gt Auxiliary input 1 WM lt
13. tection with time tag CI lt 19 gt Packed output circuit information of protection with time tag C lt 20 gt Packed single point information with status change detection C lt 21 gt Measured value normalized value without quality descriptor WM lt 30 gt Single point information with time tag Cp56Time2a WM lt 31 gt Double point information with time tag Cp56Time2a C lt 32 gt Step position information with time tag Cp56Time2a C lt 33 gt Bitstring of 32 bit with time tag Cp56Time2a CI lt 34 gt Measured value normalized value with time tag Cp56Time2a CI lt 35 gt Measured value scaled value with time tag Cp56Time2a WM lt 36 gt Measured value short floating point value with time tag Cp56Time2a V lt 37 gt Integrated total with time tag Cp56Time2a L lt 38 gt Event of protection equipment with time tag Cp56Time2a C lt 39 gt Packed start events of protection with time tag Cp56Time2a L lt 40 gt Packed output circuit information of protection with time tag Cp56Time2a 2011 05 27 6 19 IEC 101 104 103 interoperability list Process information in control direction WM lt 45 gt Single command WM lt 46 gt Double command WM lt 47 gt Regulating step command L lt 48 gt Set point command normalized value C lt 49 gt Set point command scaled value LI lt 50 gt Set point command short float value C lt 51 gt Bitstring of 32 bit WM lt 58 gt Single command with time tag Cp56Time2a WM lt 59 gt Do
14. uble command with time tag Cp56Time2a WM lt 60 gt Regulating step command with time tag Cp56Time2a System information in monitor direction W lt 70 gt End of initialization System information in control direction M lt 100 gt Interrogation command C lt 101 gt Counter interrogation command C lt 102 gt Read command M lt 103 gt Clock synchronization command C lt 104 gt Test command CI lt 105 gt Reset process command C lt 106 gt Delay acquisition command Parameter in control direction C lt 110 gt Parameter of measured value normalized value C lt 111 gt Parameter of measured value scaled value CI lt 112 gt Parameter of measured value short floating point value C lt 113 gt Parameter activation File transfer L lt 120 gt File ready CI lt 121 gt Section ready C lt 122 gt Call directory select file call section L lt 123 gt Last section last segment C lt 124 gt Ack file section C lt 125 gt Segment L lt 126 gt Directory 2011 05 27 7 19 IEC 101 104 103 interoperability list Type identification and cause of transmission assignments Type identification COT in monitor direction COT in control direction lt 1 gt M_SP_NA_1 lt 2 gt M_DP_NA_1 lt 2 gt background scan lt 20 gt interrogated by general lt 13 gt M_ME_NC_1 interrogation lt 15 gt MIT NA lt 30 gt M_SP_TB_1 lt 3 gt spontaneous lt 31 gt M_DP_TB _1 lt 36 gt
15. urands and the counter data The following group headings are supported GIN 0100h Measurands GIN 0200h Counters All other headings are not existed These headings have description field only Inside the group there are some entries The number of entries are configuration dependent All measurand type entry has an OS8ASCII type description an OS8ASCI type unit definition and a R32 23 float type actual value data All counter type entry has an OS8ASCII type description and an UI type actual value data 2011 05 27 16 19 IEC 101 104 103 interoperability list GIN KOD Datatype Datasize Nr Value 0100h lt 10 gt Description lt 1 gt OS8ASCII 9 1 Measurands 0101h lt 1 gt Actual value lt 7 gt R32 23 4 1 Value of the first measurand lt 9 gt Dimension lt 1 gt OS8ASCII 0 32 1 The name of the unit lt 10 gt Description lt 1 gt OS8ASCII 1 64 1 Internal name of the first meas 0102h lt 1 gt Actual value lt 7 gt R32 23 4 1 Value of the 2nd measurand lt 9 gt Dimension lt 1 gt OS8ASCII 0 32 1 The name of the unit lt 10 gt Description lt 1 gt OS8ASCII 1 64 1 Internal name of the 2nd meas ANN A A E 0200h lt 10 gt Description lt 1 gt OS8ASCIl 8 1 Counters 0201h lt 1 gt Actual value lt 3 gt Ul 4 1 Value of the first counter lt 10 gt Description lt 1 gt OS8ASCIl 1 64 1 Internal name of the first counter 0202h lt 1 gt Actual value lt 3 gt Ul 4 1 Valu

Download Pdf Manuals

image

Related Search

Related Contents

Commercial Electric EFG8195L-2 Instructions / Assembly  生活を豊かにする  413876 - Bedienungsanleitung  Series 90-70 Programmable Controller Data Sheet Manual, GFK  2006 Infiniti G35x Owner`s Manual - Z  取扱説明書(Ver. 1.17)  Université Libre de Bruxelles Biophysique Travaux pratiques de  Whirlpool RH123A1 User's Manual  GNSS Solutions Referenzhandbuch, rev F  