        Ethernet Open Connectivity via Modbus/TCP
         Contents
1.             starts at 12369 decimal                                               Parameter Data Access Modbus    Modbus Same Comments  Type Function   Starting As  Offsets are for  Code Address UMC800    decimal addressing     Dec  see Table 1 in User  Manual 51 52 25 111  Set Point Float  amp    Read Write   3  16 12801  3200 h    Yes  for Allows read write of segment  Scheduler Integer Sched 1 data  SP Scheduler 2 starts at  Segment Data Only  27649 decimal    28 per  segment   Sequencer Float  amp  Read and 3 6  16 23201  5AA0  No Provides status and control of  Parameters Integer   Read Write loaded sequence for all outputs  and events  Add 608 for each  successive sequencer   Sequencer Float amp    Read Write   3 6  16 23233  5ACO  No Allows read write next step data   Step Table Integer step time  Aux  Out   up to 64    Add 608 for each successive  sequencer   Sequencer Integer Read Write   3 6  16 23745  5CCO  No Allows read write of state    State Table assignment to steps  Add 608  for each successive sequencer   Note  state table is configured  by HC Designer config  Tool  only   Stage Float amp    Read  amp  3 6  16 25089  6200h  No Add 48 for each Stage  Integer Read Write  Ramp Float amp    Read  amp  3 6  16 25601  6400h  No Add 48 for each Ramp  Integer   Read Write  Hand Off Auto   Integer Read and 3  6  16 26113 6600h  Yes Add 16 as offset for each HOA  Write  Alternator Integer   Read  amp  3  6  16 26369  6700h  No Add 48 as offset for each   amp  Float   
2.    Honeywell  HCS900 Hybrid Controller    When you need more than just discrete control       Open Ethernet Connectivity via Modbus TCP     Product Note    Background    Ethernet  or more exactly  Ethernet TCP IP networks  operating at 10MBits sec or higher  are  becoming increasingly popular in an industrial production environment  This is due to their speed   versatility  and commonality with other business level networks based on the same networking  standards within a plant location  Many industrial level products now offer an Ethernet interface   either direct to the equipment or through a hardware bridge  The protocols used within this Ethernet  environment are an important factor in connectivity between a software package running in a PC  and the field hardware     A Modbus RTU protocol interface has been used as a defacto standard for many years in lower  speed  RS 485 serial network applications and is available for most of Honeywell   s data recording  and control products  A relatively new protocol standard gaining popularity  Modbus TCP  also  called Modbus TCP IP   is now available as a communications driver in many popular software  application packages used for operator interface and data acquisition  Modbus TCP combines the  Modbus RTU protocol with Ethernet TCP IP  allowing data access over an Ethernet LAN  Local  Area Network  connection  Since standard Modbus addressing is used  interfacing is well known     HC900 controllers support the Modbus TCP protocol
3.   Function Code 1  Read Digital Output Status   Function Code 2  Read Digital Input Status   Function Code 3  Read Holding Registers   Function Code 4  Read Input Registers  Analog Inputs   Function Code 5  Force Single Digital Output   Function Code 6  Preset Single Register  Write    Function Code 16  10 hex   Preset Multiple Registers  Writes   Function Code 17  11 hex   Report HC900 ID    Floating point values take  2  consecutive 16 bit registers  32 bits  and it is normal to just address  the first register  For example  Analog Input 1 on an Al card  8 inputs  in Rack 1  Slot 1 would be  addressed  using function code 4  by entering 0000  Analog Input 2 would have address 0001  and  so on  Integers use only  1  16 bit register  Sometimes the driver will add a leading 4 or 40 to the  address  e g  400065 for Loop1 PV  to represent    Holding    registers accessed using Modbus  Function Code 3  or a 3 or 30 to the address  to represent    Input    registers accessed using Function  Code 4   The application via the communications driver knows by data type how many registers to  obtain in sequence     The table lists only the starting address for the first parameter of many for a certain type or for a set  of parameters such as for control loops  The addresses are the same as for the UMC800 to the  extent of the UMC800 capacity  There is extending addressing in the HC900 due to its greater  capacity  This necessitated creation of duplicate addressing to provide full contigu
4.  as standard via a direct Ethernet connection   This is also the case for Trendview paperless recorders  Honeywell   s other serial RS 485 Modbus  products such as UDC3300 controllers or UMC800 support the protocol via an external  Ethernet Modbus bridge hardware device or an internal bridge card     For reference  a section provided later in this document provides a review of Ethernet TCP IP  networks and protocols and a Glossary of Terms     Client or   2nd Application Application Software  Software Package F with M odbus T CP  With Modbus TCP   Driver   Driver    _   _    fF          To other network    Ethernet  Modbus segments    Bridge    oa    UDC3300    CLOOOIIIT   Switch    HC900 Controllers Trendview    UMC800 DPR180   l Recorder  E E E  Direct Ethernet Connection     Ethernet Modbus Bridge     Fig  1 Ethernet TCP IP Network with 10Base T Star Topology    Why is Ethernet communications using Modbus TCP protocol important     e Customer demand   Ethernet LAN connection to application software is becoming a  requirement for many customers  most of which have business or production networks  using Ethernet with IT  Information Technology  support    e Growing popularity of Modbus TCP over Ethernet     most HMI and data acquisition  software packages offer a Modbus TCP driver  it is becoming an open standard   e Modbus familiarity   Data access for read and write is via normal serial Modbus RTU  methods using the same function code and parameter definitions  known to ma
5.  subnets                         Ethernet LAN protocol defined by IEEE 802 3 10 or 100 Mbps  Baseband network  networking standard  physical and that uses various media  twisted pair   data link layers   Uses CSMA CD thick coax  thin coax  or fiber optic  access method at a variety of speeds cable    and using several different media Example  10Base T is 10 Mbps   Twisted Pair    Ethernet Modbus A hardware device that serves as an Most bridges support sub addressing   Bridge interface between serial Modbus RTU for multiple devices connected to its  devices and host applications using serial RS 485 port  Modbus TCP protocol   FTP File Transfer Protocol Use to send and receive files between   a PC acting as an FTP client and a PC  acting as an FTP Server    Hub A hardware device with multiple ports A hub forwards all messages on one of  enabling one device to be connected its ports to all of its other ports with no  to several others isolation between devices    IEEE 802 3 The basis for the Ethernet standard    It defines the physical and data link  communication layers  uses the  CSMA CD access method at a  variety of speeds with a variety of  media such as unshielded twisted  pair    Internet A system of networks  local  regional        national  and international  linked by  the TCP IP protocol suite that  function as single  cooperative   virtual network                 Name Acronym    Name Definition    Comments       IP Address    Internet Protocol Address    A 32 bit num
6. 2 Modbus addressing is transparent  data is  selected by name from groups called Yes  Instrument Views  Windows 98  Me  NT   2000  XP supported   Honeywell PlantScape    Specify Modicon PLC  Modbus Interface  Vista SCADA    uses Modbus register addressing  which Yes    includes Modbus TCP driver  Available  for R320  NT based  and later  Latest  R400 requires Windows 2000  Standard  in Vista  Model   MZ NTIFO5 in SCADA   Improved interface including acronym   addressing and SP Programmer Recipe  displays is planned for mid 2002              Wonderware In Touch Specify mbenet exe v7 5 0 9 I O Server   Ci Technologies   CiTect Specify MODNET driver Ethernet   Modbus TCPIP   Win95  NT support   Intellution iFIX Specify Modicon Modbus Ethernet Driver                 MBE   Win NT  2000 support             This is as of March  2002  Consult IPC Marketing for updates relative to driver improvements   Other Ethernet Interface Protocols    Modbus TCP is not to be confused with Ethernet IP  This is also an emerging open standard that  bundles TCP IP with DeviceNet and ControlNet protocols     Review of Ethernet TCP IP Networks and Protocols    Networking of data in an Ethernet environment actually involves a suite of communication protocols  to assure that the proper data is delivered and understood between devices at separate nodes on  the network  TCP IP is a networking protocol as is Modbus TCP  However  each is part of a  different    layer    in a networking communications structu
7. Read Write Alternator  Alternator Integer Read Write   3  6  16 27137 6A00h  No  Output Order  Scratch Pad  Device Control   Float amp    Read  amp  3  6  16 27393 6B00  Yes Add 16 as offset for each  Integer   Read Write Device Control                           This is the decimal equivalent address for zero based Hex addressing  add 1 after conversion of  Hex to decimal   You may need to subtract 1 from that listed if entry is not zero based  In other  cases  such as with Honeywell   s PlantScape Modbus driver  you are required to add 1 to this  listing  See HC900 Ethernet Modbus TCP Communications User Manual 51 52 25 111 for more  information     What Software Packages Provide Modbus TCP Drivers     The following software packages are known to have Modbus TCP  also called Modbus Ethernet or  Modbus TCP IP  drivers  or servers   Most of these packages only provide this interface for certain  operating environments such as Windows NT or 2000  HC900 Signal Tags and Variables are  floating point format regardless of whether it is digital or analog  digital values are communicated as  0 0 for logic 0 or OFF and 1 0 for logic 1 or ON   Some software packages support use of analog  floating point values for digital objects  Please consult with the software vendor for further  information  This list does not imply that Honeywell certifies interface compatibility for third party  software           Vendor Package Comments on Interface Honeywell          Support  Specview Specview3
8. e to the high Ethernet communications bandwidth if the network segment assigned to  the data acquisition task is isolated in some way from other plant Ethernet LAN operations  If the  LAN is to be linked to another LAN at the plant location  it is typical to use switches to protect  against non pertinent data traffic from other LAN segments  The plant IT department would need to  be consulted in this matter     Glossary of Terms             Name Acronym Name Definition Comments  10Base T Ethernet network using twisted pair Most popular Ethernet standard  In the  wiring and RJ 45 connectors  used in name 10Base T  the    10    refers to 10  star topologies Mbps transmission speed  the    Base     refers to Baseband  which means that  no frequency multiplexing is applied   and the     T    refers Twisted Pair  conductors in the cable   CSMA CD Carrier Sense Multiple Access with All nodes on the same network are    Collision Detection    free to initiate message transmission   If two nodes transmit simultaneously   the Collision is detected  both nodes   abort transmission and attempt to re   transmit after a pause        Data Link Layer    Layer 2 of the OSI Model that is  media independent  and functions  above Layer 1  Physical Layer      Defines protocols for data packets and  how they are transmitted between  networking devices  Includes two  sublayers  Medium Access Control   MAC   and Logical Link Control  LLC         Default Gateway    A PC that controls traffic between 
9. ed as The content of a packet varies with the  an entity on a network  protocols that are applied  It includes  the data message itself and various  routing and control information such as  source and destination addresses   In many cases  a packet includes a set  of frames for one protocol embedded   or encapsulated  in a set of frames for  another protocol   Several levels of  encapsulation could be incorporated in  a packet    Protocol A system of rules for communicating  over a network   Segment A section of a network connecting 2 Recorders  controllers  and PC   s may  or more computers separated by be in a segment  switches  hubs or routers  Subnet A portion of the network that shares a       common address component             10       Name Acronym    Name Definition    Comments       Subnet Mask    Acts as a filter when identifying IP  addresses on a subnet  It is simply a  screen that indicates which numbers  to access  255 255 255 0 is an  example default     A single IP network can be divided into  many subnets by using some of the  most significant bits of the host  address portion of an IP address as a  subnet              Switch A multi port Ethernet device that An Ethernet switch looks like a hub   switches traffic between two or more but unlike a hub automatically  network segments on an address  determines and remembers where an  selective basis  Also called Ethernet device is located and routes  switching hubs  messages only through the appropriate  port  T
10. eric address written as 4     octets     eight bits  translating to  integers from 0 to 255  separated by  periods  e g   164 142 145 065  Itisa  software address  Within an isolated  network you can assign the addresses  at random as long as each is unique   but connecting a private network to the  Internet requires registered IP  addresses to avoid duplication        LAN    Local Area Network    Networked devices  logically  isolated from other networks and  devices        MAC Address    MAC coded ID    A Data Link layer address also known  as hardware address  physical  address  Unique code is    burned in     into the product by its manufacturer  A  set  6  2 digit hexadecimal numbers        Modbus TCP or  Modbus TCP IP    Variant of Modbus protocol    Modbus TCP is a derivative of related  Modbus RTU protocol used with  RS232 RS 485 data acquisition and  supervisory structures  Basically   Modbus TCP encapsulates Modbus  RTU frames in TCP frames for  transport over an Ethernet network        Node    An intelligent device on a network  that has a hardware address such as  a PC  printer  a controller or recorder       OSI 7 Layer Model    Open Systems Interconnection  Reference Model    The OSI model is established by  International Standards Organization   ISO  to enable computer  communications using disparate media  and protocols  Includes seven     Layers    refer to OSI Reference Model     for more information                    Packet A bit sequence that is transmitt
11. hat Data Can Be Communicated     HC900 controllers provide access to an array of parameters that are categorized by function in the  HC900 Ethernet Modbus TCP Communications User   s Manual  51 52 25 111  The HC900 retains  all of the Modbus addresses available for the UMC800 and expands the listing due to its greater  capacity and functionality  Table 1 summarizes this parameter access  including the read write  capability  when using an Ethernet Modbus TCP or Modbus Ethernet protocol driver  server  for the  host software application  The HC Designer tool also provides the Modbus addresses for all Signal  Tags and Variables plus the starting Modbus addresses for the major functions supporting a  Modbus address set such as control loops  SP programmers  etc  The Tag Information and the  Block Modbus Addresses reports may be viewed on line and printed out for reference when  configuring the database for the host software application     Entering Modbus Addresses in Third Party Software    After selecting the driver for the TCP IP channel in a third party software package  the tag database  would then be created in some cases via a Wizard  The tag definition dialog box would have entries  typically for Data Type  Float  Integer  etc   and decimal  or Hex  parameter addressing  typically  decimal with a range of 1 to 65535  The Modbus function code  1  2  3  4  16  etc   may also be a  separate entry or part of the decimal address  These function codes are defined as follows   
12. his minimizes network loading  and enables true deterministic  communications over Ethernet by  eliminating    collisions      TCP IP Transport Control Protocol Internet Transmission Control Protocol  TCP         Protocol         Operates at the Transport Layer of  the OSI Model    manages  connections between computers   Internet Protocol  IP       operates at the Network Layer  one  step below TCP      defines how data is addressed   source destination        11       
13. ive loops  Loop 25  starts at 30785 decimal  7840  h   add 256 up through Loop 32  PV  Loop 1   Float Read 3 65  40 h  Yes  WSP  Working   Float Read 3 69  44 h  Yes  SP   Loop 1  Output  Loop1   Float Read Write   3 71  46h  Yes  LSP  Local SP     Float Read Write   3  16 107  6A h  Yes  Loop1  Auto Manual    Integer   Read write   3  16 251  FA h  Yes Bit 0   0 for Manual and 1 for  Loop 1 Auto   Remote Local    Integer   Read write   3  16 253  FA h  Yes Bit 0   0 for LSP and 1 for RSP   Loop 1  Set Point Float  amp    Read and 3  16 7681  1E00 h  Yes Provides status and control of  Programmer Integer Read Write loaded program  add 16 to  Parameters decimal address for successive   10  programmers 1 4   Programmers 5 8 start at  address 32769   Set Point Float amp    Readand   3 16 7681  1E00 h  Yes Provides loading of new profile  Programmer Integer   Read Write and other setup parameters   Add  add 64 to decimal address for  successive programmers 1 4   a e Programmers 5 8 start at  address 32881   Set Point Float amp    Read Write   3 16 10241 2800 h  Yes Allows read write of segment  Programmer Integer data  add 512 to decimal  Segment Data address for successive   5 per programmers 1 4  Programmers  segment  5 8 start at address 33281  Set Point Float amp    Read and 3  16 12289  3000 h    Yes  for Provides status and control of  Scheduler Integer   Read Write Sched 1 loaded program for all outputs  Parameters Only  and events  SP Scheduler 2     Approx  37           
14. ntation and Custom Applications FTP  code formatting  Defines how Modbus TCP   system provides files and services  in a uniform way to applications     v       5 Session Establishes  maintains  and  manages network connections       Transport Responsible for constructing 4  Protocols  streams of data packets  sending TCP       and checking for correct delivery S    Network Responsible for routing packets of IP  data across network       Data Link Provides data framing  low level  error detection and correction  Ethernet  retransmitting as necessary          1 Physical Hardware layer  transmits bits 1   s 802 3  and 0   s   cable connection                      Fig  4 OSI 7 Layer model and Ethernet TCP IP Representation    It is important to note that Ethernet alone is only the lower level part of a communications structure      the physical  bit transmission  data framing  and data flow control portion  Physical and Data Link  Layers   The Ethernet hardware interfaces in our products support the physical connection   typically RJ 45 connector for 10 Base T networks  and the CSMA CD  Carrier Sense Multiple  Detection Collision Detection  feature of Ethernet communications     Ethernet is non deterministic meaning that any node can broadcast a request for information at any  time  The CSMD CD feature allows a collision  more than one node communicating at once  to be  detected and will cause a variable timeout at each node before trying again  This is normally not a  problem du
15. ny users   Real time data available in the HC900 such as control loop parameters  signal tags   variables  analog inputs  etc  can be accessed real time via the appropriate Modbus  address    e Speed     Ethernet networks  now normally 10Base T star topology  offer higher speed data  access versus serial RS 485 networks  This is especially true for direct Ethernet connected  products such as the HC900  Depending on Networks will not be slowed significantly as  more units are placed on the network due to Ethernet   s higher    bandwidth     A 10Base T  network offers 10MBits sec  data rates although there is possible contention for network  access due to Ethernet CSMA CD principles    e Ethernet Multi Channel Support     Many applications can operate concurrently over an  Ethernet LAN between Ethernet    nodes    using separate    channels     The HC900 can  support up to 5 concurrent connections to software applications  As an example  2 separate  HMI packages  HC900   s Hybrid Control Designer software  a Visual BASIC and an EXCEL  application at different network locations can all address the same controller concurrently   On the other hand  RS 485 supports only a single channel connection     Multiple applications  F  can run concurrently         E Application A  Application C   between nodes   gt  Application B       Switch    HC900 Controllers    Fig  2  Multiple Channel Application Support    Modbus TCP Protocol    The Modbus TCP protocol was released publicly in 1999 b
16. ous address  space for some parameter types as noted  For further detail on Modbus addressing  consult the  HC900 Ethernet Modbus TCP Communications User Manual                                                                 Parameter Data Access Modbus  Modbus Same Comments  Type Function Starting As  Offsets are for  Code Address UMC800  decimal addressing     Dec  see Table 1 in User  Manual 51 52 25 111  Analog Inputs   Float Read 3 6145  1800 h  Yes First 8 slots  64 Al s  of Rack 1   Al   s only  Float  Read 4 0  0 h  No All Al   s  up to 128   addressed  on a consecutive rack basis  Digital Inputs Integer   Read 01 0  0h  Yes  upto   See 51 52 25 111 User Manual  capacity  for address map   Digital Outputs   Integer   Read  Write   02 05 0  0h  Yes  up to See 51 52 25 111 User Manual  capacity  for address map   Signal Tags Float Read 3 8193  2000 h  Yes Access to Signal Tags 1 to  1000  Digital tags read as 0 0  and 1 0 for logic 0 and 1  Float Read 3 15201  3B60 h    No Access to Signal Tags 1 to  2000  Digital tags read as 0 0  and 1 0 for logic 0 and 1  Variables Float Read Write   3  16 6337  18C0 h  Yes  upto   Access to Variables 1 to 600   Variable Digital Variables read write as  150  0 0 and 1 0 for logic 0 and 1  Loop Float   amp    Read and 3  16 65  40 h  Yes  upto   For all loops beyond Loop 1 up  Parameters some Read Write  for Loop 1  loop 16  Loop 24  add 256 to decimal   approx  50  Integer  starting with PV  address for parameters applied  to success
17. ovided     Modbus TCP double register format   FB B   Big Endian  0 1 2 3  bi  FB B   Bia Endian  0 1 2 3  _  T Requires return to RUN mode td FE BE   Big Endian Byte Swap  1 0 3 2     FB L   Little Endian  3 2 1 0   FB LB   Little Endian Byte Swap                                     Selection Register  Word  Order   Floating Pt Format Comment  FBB First word High Big Endian  0 1 2 3  Default  FB BB Big Endian Byte   Swapped  1 0 3 2   FBL Little Endian  3 2 1 0   FB LB First word low Little Endian Byte  Most  Swapped  2 3 0 1  common       The Modbus TCP double register transmission format selection  FB LB    Little Endian Byte   Swapped     would be selected for interface to most third party software packages which use this  format as standard  Our default  FB B    Big Endian    is used with SpecView32 or PlantScape  software and follows the    Honeywell    default format of other control and recording products     Fortunately  most PC software packages offer a word swap selection in their driver package  anyway  so there should never be an incompatibility     The application software Modbus TCP driver  server  must be configured per the software vendor s  documentation for dialog box entries  This usually involves setting up a communications channel  based on using an installed Ethernet NIC  Network Interface Card or adapter   a TCP IP port   default is 502   entry of the unit   s IP address  use  or non use  of zero based register addressing   and connection timeout     W
18. re     Ethernet TCP IP networks  widely popular today  use TCP IP  Transportation Control  Protocol Internet Protocol  to transport messages between PC   s  TCP IP is the basis for Internet  connectivity  It is actually two protocols that provide a set of services that devices use to  communicate over Ethernet LAN   s  Using TCP IP does not guarantee that a recorder or controller  will communicate with a PC  it only guarantees that messages will be transferred successfully  To  establish understanding and interoperability between devices  a common application protocol is  needed  This is where Modbus  TCP protocol is utilized as part of a software application     As indicated  a suite of networking protocols is necessary to allow various types of equipment to  reliably communicate  A networking protocol structure developed by the International Standards  Organization  popularly known as the OSI  Open Standards Interface  7 layer Model  provides a  framework for defining network communications  Fig  4 shows the generalized model with the layer  definitions at the left and how Ethernet TCP IP networks apply to the model at the right  Each higher  layer depends on services provided by a lower level layer  The acronyms for some of the various  protocols that apply at various layers are shown  See the Glossary for a full definition     Ethernet TCP IP       Application Defined by applications software   PP Protocols Services for Applications       6 Presentation Handles data prese
19. y Groupe Schneider   s Modicon division to  provide open  vendor independent access to PLC   s  I O modules  Ethernet Modbus bridges  or  other process instrumentation over Ethernet TCP IP networks  This is simply an encapsulation of  Modicon   s Modbus RTU protocol within a TCP IP frame as shown in Fig  3  Function codes and  data registers are accessed the same as with Modbus RTU  The address in the Modbus frame is  set to 00 since addressing to direct Ethernet connected devices utilizes the IP address  In addition   there is no checksum for error checking since this is implemented at the TCP IP network levels  The  specification is available for royalty free licensing from Modicon  To review the specification  access  the Modicon website at     http   www modicon com openmbus standards openmbus htm        TRARAL To PRT  IDEN TIMIDA CEHTFER    Fig  3 Modbus TCP frame    HC900 Modbus TCP Setup    The HC900 Ethernet network connection for Modbus TCP is inherent once the Ethernet IP address  for the controller host port is established  The HC900 predominantly uses an IEEE floating point  format for communicating data to software applications supported by Modbus TCP protocol  A  floating point value is sent as  2  consecutive 16 bit registers  each register of which consists of two  8 bit bytes  Some software packages require the registers to be sent in a certain order  The HC  Designer software tool allows this order to be selected  The following table lists the selections  pr
    